distribution transformer connections · 2 exchangingexpertisesince1893 nwems 26 mva substation...

21
1 EXCHANGING EXPERTISE SINCE 1893 NWEMS DISTRIBUTION TRANSFORMER CONNECTIONS Rebekah Wotton Tacoma Public Utilities [email protected] EXCHANGING EXPERTISE SINCE 1893 NWEMS

Upload: others

Post on 03-Aug-2020

18 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

1

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

DISTRIBUTIONTRANSFORMERCONNECTIONS

Rebekah Wotton

Tacoma Public Utilities

[email protected]

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 2: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

2

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

26 MVA SUBSTATION TRANSFORMER

» High Voltage connected 115KV Delta

» Distribution Voltage 7200/12,470 (12.5) Wye

» 26MVA

Amperage

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

VOLTAGE REGULATING TRANSFORMER

» 3 Single Phase Regulators

» Distribution Voltage 7200

» Each Regulator can raise or lower the voltage by 16, 5/8% steps

Page 3: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

3

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 4: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

4

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

BASICS» A conductor carrying current has a magnetic field around it.

» With alternating current (ac), the magnetic field expands and contracts, reversing polarity each half cycle.

Page 5: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

5

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

BASICS» When more conductors are placed near the first conductor 

carrying current, a current is induced in them and in the opposite direction.

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

The main purpose of a distribution transformer is to transform the primary voltage level (usually high) to a specific secondary 

voltage level which is required for specific connected equipment.

Page 6: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

6

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

» The core, which is usually made of iron with low magnetic permeability.

» Primary windings, a coil which receives the energy from the source.

» Secondary windings, a coil that receives the energy from the primary and delivers it to the load.

TRANSFORMER MAIN PARTS

Page 7: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

7

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

COOLANT

» For distribution transformers the coolant is almost always oil.

» The electrical insulating qualities of oil is excellent, as well as the ability of oil to transmit heat away from the core and coils to the exterior radiating surfaces.

Page 8: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

8

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

TURNS RATIO

» The ratio is the number of turns on the primary winding to the number of turns on the coil of the secondary winding.

» A primary coil with 600 turns at 7200 volts coupled with a secondary coil with 10 turns will deliver a secondary voltage of…

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

TRANSFORMER LOSSES

» The transformer is not 100% efficient due to two types of energy losses.

» No load losses are associated with magnetizing the iron core.

» Load losses are associated with current flow.

Page 9: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

9

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

DISTRIBUTIONTRANSFORMERCONNECTIONS

Page 10: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

10

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

DELTA / DELTA

» 120/240/208 or 240/480/415 Volt 3‐Phase 4‐Wire, grounded neutral bushing.

Page 11: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

11

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

NeutralNeutral

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

NeutralNeutral

Page 12: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

12

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

NeutralNeutral

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 13: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

13

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

NeutralNeutral

Page 14: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

14

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

If your transformer is:

A) 8660v or higher

or

B) 200kVa or more

Then it is Subtractive Polarity

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 15: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

15

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 16: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

16

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

OPEN WYE / OPEN DELTA

» High Voltage Connected 2‐Phase Wye with Neutral

» Secondary connected 3‐Phase 4‐Wire Open Delta

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 17: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

17

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

WYE – WYE

» High Voltage Connected 3‐Phase 4‐Wire Wye.

» Secondary Connected 3‐Phase 4‐Wire Wye.

» The secondary voltage is 120/208 or 277/480 volts.

Page 18: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

18

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 19: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

19

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

NeutralNeutral

NeutralNeutral

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 20: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

20

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

Page 21: DISTRIBUTION TRANSFORMER CONNECTIONS · 2 EXCHANGINGEXPERTISESINCE1893 NWEMS 26 MVA SUBSTATION TRANSFORMER » High Voltage connected 115KV Delta » Distribution Voltage 7200/12,470

21

EXCHANGING EXPERTISE SINCE 1893 

NWEMS

N

EXCHANGING EXPERTISE SINCE 1893 

NWEMS