direct current hybrid breakers
DESCRIPTION
bookTRANSCRIPT
-
5/25/2018 Direct Current Hybrid Breakers
1/195
DIRECT CURRENT HYBRID BREAKERS:
A DESIGN AND ITS REALIZATION
-
5/25/2018 Direct Current Hybrid Breakers
2/195
Cover: The Hindu temple in Lake Bratan, Bali, Indonesia.
-
5/25/2018 Direct Current Hybrid Breakers
3/195
DIRECT CURRENT HYBRID BREAKERS:
A DESIGN AND ITS REALIZATION
PROEFSCHRIFT
ter verkrijging van de graad van doctor aan de
Technische Universiteit Eindhoven, op gezag van de
Rector Magnificus, prof.dr. M. Rem, voor een
commisie aangewezen door het College voor
Promoties in het openbaar te verdedigen
op donderdag 4 Mei 2000 om 16.00 uur
door
Ali Mahfudz Surya Atmadji
geboren te Semarang, Indonesi
-
5/25/2018 Direct Current Hybrid Breakers
4/195
iv
Dit proefschrift is goedgekeurd door de promotoren:
prof. ir G.C. Damstra
en
prof. dr.-ing. H. Rijanto
CIP-DATA LIBRARY TECHNISCHE UNIVERSITEIT EINDHOVEN
Atmadji, Ali M.S.
Direct current hybrid breakers : A design and its realization / by Ali
M.S. Atmadji. - Eindhoven : Technische Universiteit Eindhoven, 2000.Proefschrift. - ISBN 90-386-1740-2
NUGI 832
Trefw.: kortsluitingsbeveiliging / kortsluitstromen /
vacuumschakelaars / elektrische schakelaars.
Subject headings: current limiters / short-circuit currents /
vacuum circuit breakers / switchgear testing.
Copyright 2000 by A.M.S. Atmadji, Departement of Electrical Engineering, EindhovenUniversity of Technology, Eindhoven, The Netherlands.
-
5/25/2018 Direct Current Hybrid Breakers
5/195
v
Do not believe in anything simply because you have heard it. Do not
believe in anything simply because it is spoken and rumored by many. Do
not believe in anything simply because it is found written in your religious
books. Do not believe in anything merely on the authority of your teachers
and elders. Do not believe in traditions because they have been handed
down for many generations. But after observation and analysis, when you
ind that anything agrees with reason and is conducive to the good and
benefit of one and all, then accept it and live up to it.
Buddha
To my parents
Samoeri and Koestiwati
-
5/25/2018 Direct Current Hybrid Breakers
6/195
vi
Summary
The use of semiconductors for electric power circuit breakers instead of conventional breakers
remains a utopia when designing fault current interrupters for high power networks. The major
problems concerning power semiconductor circuit breakers are the excessive heat losses and their
sensitivity to transients. However, conventional breakers are capable of dealing with such matters. Acombination of the two methods, or so-called hybrid breakers, would appear to be a solution;
however, hybrid breakers use separate parallel branches for conducting the main current and
interrupting the short-circuit current. Such breakers are intended for protecting direct current (DC)
traction systems. In this thesis hybrid switching techniques for current limitation and purely solid-
state current interruption are investigated for DC breakers.
This work analyzes the transient behavior of hybrid breakers and compares their operations with
conventional breakers and similar solid-state devices in DC systems. Therefore a hybrid breaker was
constructed and tested in a specially designed high power test circuit. A vacuum breaker was chosen
as the main breaker in the main conducting path; then a commutation path was connected across the
vacuum breaker where it provided current limitation and interruption. The commutation path
operated only during any current interruption and the process required additional circuits. These
included a certain energy storage, overvoltage suppressor and commutation switch. So that when
discharging this energy, a controlled counter-current injection could be produced. That counter-
current opposed the main current in the breaker by superposition in order to create a forced current-
zero. One-stage and two-stage commutation circuits have been treated extensively.
This study project contains both theoretical and experimental investigations. A direct current short-
circuit source was constructed capable of delivering power equivalent to a fault. It supplied a direct
voltage of 1kVDCwhich was rectified having been obtained from a 3-phase 10kV/380V supply. The
source was successfully tested to deliver a fault current of 7kA with a time constant of 5ms. The
hybrid breaker that was developed could provide protection for 750VDC traction systems. The
breaker was equipped with a fault-recognizing circuit based on a current level triggering. An
electronic circuit was built for this need and was included in the system. It monitored the system
continuously and took action by generating trip signals when a fault was recognized. Interruption
was followed by a suitable timing of the fast contact separation in the main breaker and the current-zero creation. An electrodynamically driven mechanism was successfully tested having a dead-time
of 300s to separate the main breaker contacts. Furthermore, a maximum peak current injection of
3kA at a frequency of 500Hz could be obtained in order to produce an artificial current-zero in the
vacuum breaker. A successful current interruption with a prospective value of 5kA was achieved by
the hybrid switching technique. In addition, measures were taken to prevent overvoltages.
Experimentally, the concept of a hybrid breaker was compared with the functioning of all
mechanical (air breaker) and all electronical (IGCT breaker) versions. Although a single stage
interrupting method was verified experimentally, two two-stage interrupting methods were analyzed
theoretically.
-
5/25/2018 Direct Current Hybrid Breakers
7/195
vii
Samenvatting
Het gebruik van halfgeleider schakelaars om conventionele schakelaars te vervangen blijft een
utopia voor de foutstroom onderbreking in elektrische netten. Voor de halfgeleider
stroomonderbrekers zijn er beperkingen zoals het grote warmte verlies en de gevoeligheid voor
transienten waar conventionele schakelaars juist heel goed tegen bestand zijn. Samenstellingen van
beide soorten schakelaars noemt men hybride schakelaars. Hybride schakelaars maken gebruik van
twee afzonderlijke paden; voor de doorgaande nominale stroom en voor de foutstroom
onderbreking. Zulke schakelaars zijn grotendeels bedoeld voor de beveiliging van tractiesystemen.
In dit proefschrift zijn hybride technieken voor de stroombegrenzing en volledige halfgeleider
stroomonderbreking behandeld voornamelijk in gelijkstroom circuits.
In dit werk wordt een analyse gepresenteerd van het transient gedrag van hybride schakelaars en
worden hun functies vergeleken met conventionele en halfgeleider schakelaars. Een ontwerp voor
een hybride schakelaar is gerealiseerd en beproefd in een hiertoe opgebouwd gelijkstroom test
circuit. Een vacuum schakelaar is gekozen als de hoofdschakelaar in het hoofdpad. Hieraan parallel
is een commutatie pad aangebracht dat voorziet in stroombegrenzing en stroomonderbreking. Het
commutatie pad wordt alleen gedurende een stroomonderbreking bedreven om de commutatie van
de hoofdstroom mogelijk te maken. Het commutatie proces vereist componenten voor het opslaan
van energie en het onderdrukken van overspanningen. Door het vrijgeven van opgeslagen energie
kan een gecontroleerde tegenstroom injectie worden bewerkstelligd. Deze tegenstroom forceert een
stroom nuldoorgang in het hoofdpad. Een en twee-trap commutatie circuits zijn vergeleken.
Het onderzoek bevat zowel theoretisch als experimenteel werk. Een gelijkstroom circuit is gebouwd
om de kortsluitstroom te leveren van 7kA met een tijdkonstant 5ms. De bron heeft een nominale
spanning van 1kVDC door gelijkrichting van twee distributie transformatoren (10kV/380V). Het
ontwerp van de hybride schakelaar is gericht op toepassing voor het beveiligen van 750VDCtractie
systemen. De schakelaar is uitgerust met een foutdetectiesysteem gebaseerd op een stroomlevel trip.
De stroom in het circuit wordt bewaakt waarbij uitschakel commando gegenereerd wordt zodra de
stroom in het circuit de ingestelde waarde overschrijdt. Het feitelijke onderbrekingsproces wordt
bepaald door de snelheid van contactscheiding in de vacuum schakelaar en het creren van de
benodigde nuldoorgang. Een snelle contactscheiding na ongeveer 300s is gerealiseerd met een
elektrodynamische aandrijving. Een injectie stroom met een frequentie van 500Hz en amplitude
3kA is gebruikt voor het creren van de nuldoorgang in de vacuum schakelaar. Een successvolle
stroomonderbreking van een prospective gelijkstroom van 5kA is met de hybride techniek
gerealiseerd. Bovendien is een geschikte overspanning onderdrukking bereikt. Het hybride concept
is experimenteel vergeleken met volledig mechanische en volledig electronische (IGCT)
schakelaars. Terwijl alleen de een-trap commutatie circuit ook experimenteel is uitgevoerd, zijn 2
twee-trap commutatie circuits alleen theoretisch geanalyseerd.
-
5/25/2018 Direct Current Hybrid Breakers
8/195
viii
CONTENTS
Summary vi
Samenvatting vii
1 Concepts of direct current limitation and interruption ........................ 11.1 Introduction ............................................................................................................. 1
1.2 Current limiting and interrupting techniques ........................................................... 3
1.2.1 Conventional direct current air breakers ....................................................... 3
1.2.2 Current Limiting Fuses ................................................................................. 6
1.2.3 Pyrotechnique ................................................................................................ 6
1.2.4 Positive Temperature Coefficient Resistors (PTCR) ..................................... 7
1.2.5 Superconducting Current Limiter (SCCL) ..................................................... 8
1.2.6 Solid-state breakers (SSBs) ......................................................................... 9
1.3 Hybrid switching techniques ................................................................................... 10
1.4 Outline of thesis ....................................................................................................... 14
1.5 References and reading lists .................................................................................... 14
2 Analysis of commutating circuits for hybrid breakers .......................... 192.1 Introduction ............................................................................................................... 19
2.2 Analysis of the active commutation circuit ............................................................... 22
2.3 Dimensions for the components of the parallel circuit ............................................. 32
2.4 Simulating one-stage interruptions using MATLAB ................................................ 35
2.4.1 Successful interruption using a bi-directional switch .................................. 38
2.4.2 Successful interruption at the first current-zero using a uni-directional
switch ........................................................................................................... 392.4.3 Successful interruption at the second current-zero using a uni-directional
switch ........................................................................................................... 40
2.4.4 Unsuccessful interruption ............................................................................. 40
2.5 Protection against excessive overvoltages ................................................................ 41
2.5.1 Linear energy absorbing devices as the primary protection ......................... 44
2.5.2 Non-linear energy absorbing elements as the secondary protection ............ 45
2.5.3 Snubber circuits as the tertiary protection .................................................... 46
2.5.4 Applications of the freewheeling diode ....................................................... 48
2.5.5 Combining all the components ..................................................................... 48
2.6 Circuit simulation using PSPICE .............................................................................. 492.6.1 Device modelling ......................................................................................... 49
2.6.2 Simulation diagram ...................................................................................... 51
2.6.3 Simulation results using PSPICE ................................................................. 52
2.7 Conclusions ............................................................................................................... 57
2.8 References and reading lists ...................................................................................... 57
3 Two-stage commutation circuits for direct current interrupters ......... 593.1 Introduction .............................................................................................................. 59
3.2 Basic principles of the first variant .......................................................................... 61
3.3 Basic principles of the second variant ...................................................................... 67
3.4 Computer simulation using PSPICE ......................................................................... 72
3.4.1 The short-circuit simulation of a DC source with a prospective current of
10kA .............................................................................................................
73
-
5/25/2018 Direct Current Hybrid Breakers
9/195
ix
3.4.2 The one-stage DC interruption of 10kA with Itrip=5kA ................................ 74
3.4.3 The first variant of two-stage DC interruption with Itrip=5kA ...................... 75
3.4.4 The second variant of two-stage DC interruption with Itrip=5kA ................. 76
3.5 Conclusions .............................................................................................................. 77
3.6 References and reading lists .................................................................................... 77
4 Fault identification and direct current measurement ........................... 794.1 Introduction .............................................................................................................. 79
4.2 Realization of a detection circuit .............................................................................. 80
4.3 Direct current transducers ......................................................................................... 81
4.4 Rogowski-coils as current transducers ..................................................................... 84
4.5 Conclusions .............................................................................................................. 88
4.6 References and reading lists ..................................................................................... 88
5 Fast electrodynamic drives for the hybrid breaker ............................... 91
5.1 Introduction .............................................................................................................. 915.2 Description of the electrodynamic drive system ....................................................... 92
5.3 Mathematical analysis of the electrodynamic drive system ...................................... 94
5.3.1 Analysis of the electrodynamic drive using the coupled coils theory .......... 95
5.3.2 Analysis of the electrodynamic drive using equivalent lumped parameters 103
5.4 Comparison between simulation and measurement results ...................................... 107
5.5 Conclusions .............................................................................................................. 116
5.6 References and reading lists ..................................................................................... 116
6 Test circuit for DC breakers ..................................................................... 1196.1 Introduction ............................................................................................................... 119
6.2 Analysis of rectifier circuits for a direct current short-circuit source ....................... 120
6.2.1 One 3-phase rectifier .................................................................................... 121
6.2.2 Two 3-phase rectifiers in series .................................................................... 123
6.3 Realization of the direct current short-circuit source (DCSCS) ................................ 129
6.3.1 Sequential timing operation ......................................................................... 130
6.3.2 Overvoltage suppression .............................................................................. 131
6.3.3 Surge phase-currents in the transformer secondary when switching-on ...... 134
6.3.4 Overcurrent protection by I2t fusing ............................................................. 138
6.3.5 Protection from overheating.......................................................................... 139
6.4 Simulation results ...................................................................................................... 140
6.4.1 Simulation of a 10kA prospective short-circuit current ............................... 1416.4.2 A short-circuit current directly after the bridge ............................................ 142
6.5 Measured and simulated results ................................................................................ 143
6.5.1 An open circuit test ...................................................................................... 144
6.5.2 Short-circuit test ........................................................................................... 144
6.6 Conclusions ............................................................................................................... 145
6.7 References and reading lists ...................................................................................... 146
7 Experimental and modelling results ........................................................ 1497.1 The air breaker experiment ....................................................................................... 149
7.2 The hybrid breaker experiment ................................................................................. 151
7.2.1 Hybrid breaker test without anti-parallel diode across the vacuum breaker 151
7.2.2 Hybrid breaker test with anti-parallel diode across the vacuum breaker ..... 156
7.3 The solid-state breaker experiment ........................................................................... 159
-
5/25/2018 Direct Current Hybrid Breakers
10/195
x
7.2.1 A brief description of the Integrated Gate Commutated Thyristor (IGCT) .. 160
7.2.2 Experimental and simulated results using IGCT .......................................... 161
7.4 Conclusions ............................................................................................................... 164
7.5 References and reading lists ...................................................................................... 165
8 General conclusions and future developments ....................................... 1678.1 General conclusions .................................................................................................. 1678.2 Future developments ................................................................................................. 169
Appendix A ....................................................................................................... 171
List of symbols ................................................................................................. 173
Acknowledgements .......................................................................................... 177
Biography ......................................................................................................... 179
-
5/25/2018 Direct Current Hybrid Breakers
11/195
xi
-
5/25/2018 Direct Current Hybrid Breakers
12/195
xii
-
5/25/2018 Direct Current Hybrid Breakers
13/195
Chapter 1
Concepts of direct current limitation and interruption
Abstract
This chapter presents an overview of available electric current limitation and interruption
techniques for protecting direct current systems. Some of them were installed in networks for long
periods while others are still in the development stage. Attention was focused on hybrid switching
techniques which were the subject of this study. Finally, the form of this thesis is discussed.
1.1 Introduction
Faults in electric currents impose severe thermal and mechanical stresses on electrical systems and
their related apparatus and the severity depends on the peak current value and the time of the
interruption. Thermal overloading can result in the burning of lines or cables, while electrodynamic
forces can deform bus bars or the coils of reactors and transformers. Moreover, arcing resulting
from a fault can initiate explosions. Protection against such events is usually provided by installing
circuit breakers or current limiters in the line to be protected. A conventional AC circuit breaker is
capable of conducting high continuous currents and has a substantial short-circuit interrupting
capacity; but it is not able to perform current limitation at nominal high current ratings. On the otherhand, fuses which are the best known current limiting devices, have a relatively low continuous
current rating. Due to this contradictory situation, an ideal circuit breaker should have the following
features which are difficult to combine into one concept:
fast breaking action (at earliest current-zero);
minimal arcing after contact separation (to reduce contact erosion);
minimal conduction losses (a small voltage drop across the contacts);
reliable and efficient protection against all types of faults;
repetition of switching operation (allowing contacts to reclose after a fault clearance);
prevention of excessive overvoltage (during operation).While these features are applicable for all circuit breakers, the task of direct current breakers is even
heavier because current limitation is required in the absence of current-zeros.
Direct current (DC) can be used for a large voltage range. According to the provisions of standards,
DC voltages are classified as low voltages (LV) up to 1200V (for instance, urban vehicles use
750V), systems for 1500V and 3000V are generally referred to as medium voltages (MV) and high
voltage (HV) is up to 1500kV. High voltage direct current (HVDC) technology applies especially to
high power transmission lines and for the back-to-back stations of AC systems. In the medium
voltage range, direct current is used principally in electric traction, electric heating devices andsome drives. In the low voltage range, direct current is used for most kinds of urban and mine
electric traction, in various drives and converter systems. Short-circuit parameters for specific
-
5/25/2018 Direct Current Hybrid Breakers
14/195
2 Chapter 1
circuits are very different. Time constant values in HV circuits generally are rather high. In LV and
MV circuits, time constants are in the range of 5 to 30ms, prospective short-circuit currents are in
the range of 10 to 150kA, initial rates of current rise in the range of 0.5 to 15A/s and magnetic
energy of the short-circuits in the range of 5 to 30kJ [1.1].
Current interruption in DC systems is more problematic than in AC systems since there is no natural
current-zero available and the magnetic energy stored in the circuit inductance has to be dissipated.
Breakers must not only be able to interrupt but also to reduce the current to zero within a certain
time [1.2,3,4,5]. During the interruption process, an excessive high voltage should not be created in
the system.
A current-zero can be created in two ways. The first one is the traditional method used in DC
circuits: a switching device develops arc voltages significantly in excess of the system voltage. The
second method creates a virtual current-zero by producing a counter-current from auxiliary
commutation circuits. This counter-current is usually provided by a capacitor bank. The diagram in
Figure 1.1shows the classification of fault clearances in DC systems [1.4].
Inverse voltage method
DC Interruption
Current Limiting
Current commutation method
Current Oscillation
Self oscillation
Arc Switches & LC orRLC (active)
LC+Arc(passive)
Forced oscillation
Impulse circuitLC & Switches
R+Arc+Switches
FusesExplosive chargefuses
Non-linear materialor devices
ConventionalDC and HVDCbreakers
PTC-resistorSuperconductor
Hybrid breakersPure solid-statebreakers
Unknown
Figure 1. 1 Classification of DC interrupting methods; where PTC: Positive Temperature Coefficient,
R: resistor, RLC and LC: oscillating loops with and without damping.
-
5/25/2018 Direct Current Hybrid Breakers
15/195
Concepts of direct current limitation and interruption 3
1.2 Current limiting and interrupting techniques
A current limiting device can be seen as a series of elements in the line; they offer low impedance to
the load current and high impedance to the fault current. In principle, it is not necessary for the
current limiting device itself to create the final current-zero. An auxiliary interrupter can be
connected in series in order to interrupt the limited current. In the following sub-sections, a number
of current limiting techniques are summarized.
1.2.1 Conventional direct current air breakers
Classical direct current interruption utilizes arc plasma in order to build up the inverse voltage
opposing the supply voltage for the current-zero creation. In the closed position, conventional
mechanical breakers are able to conduct high continuous currents with low power dissipation. In the
open position, these breakers provide excellent isolation. During the switching process, the arc
plasma causes contacts to erode and it generates noises and hot gasses. Moreover, these switches
generally react slowly. Hence, they hardly limit the maximal fault current, due to their slow opening
and long arcing times which together take longer than 20ms, which is usually above the time
constant of a circuit.
Interrupting DC is accompanied by different phenomena depending on the systems parameters and
the exact location of the breaker. For example, see Figure 1.2, for a given simple 1kV DC system
containing the total lumped resistance RS=100m and inductance LS=400H with a breaker and
load. In the closed position, the breaker has a low resistance. During a fault, the current has to be
interrupted. The prospective short-circuit current is 10kA. The fault is distinguished from a normal
current load by the setting of a trip current value. As soon as the current exceeds that trip value, the
electromagnetic device in the circuit breaker (CB) separates the contacts creating an arc between the
electrodes.
LoadV
CBi(t)
LS R
S
ES
Figure 1. 2 A typical DC system with a conventional breaker.
The current can be reduced to zero only if the breaker can generate and maintain a switching arc
voltage of VCB that ishigher than the systems voltage ESfor long enough. While this occurs, the
-
5/25/2018 Direct Current Hybrid Breakers
16/195
4 Chapter 1
breaker dissipates the inductive energy and any excess energy delivered by the source during the
interruption process. Obviously, this method is suitable for conventional air breakers. Figure 1.2
shows the application of a conventional breaker in a simple circuit.
Much depends on the way that the switching arc voltage VCB is generated, this may be represented
by a function of several different quantities, such as: current, time derivative, stored magnetic
energy, time, etc. The equation for voltages in the circuit (Figure 1.2) is given by the expression:
E V V VS R L CB= + + (1.1)
where: V R i t R S= , V Ldi
dtL S= and V f i
di
dti dt t CB=
, , , .
During the switching process, the energy stored in the system must be dissipated by the circuit
resistance and the breaker. The energy dissipated in the resistance is calculated by:W R i dt R S= 2 (1.2)
And the arcing energy is given by the relationship:
W V i dt CB CB= (1.3)The let-through energy integral for the breaker can be computed using the expression:
i dt i t 2 2 .
To demonstrate the interruption process, a switching arc voltage VCB across the breaker was
represented empirically by some idealized algebraic functions, in order to simulate the relationship
between the voltage across the breaker and the current through it. The trip current for opening the
breaker was set to 2kA. After a successful interruption, a transient recovery voltage appears across
the breaker. Now two cases: A and B, for empirical switching arc voltage traces will be presented
(Table 1.1).
Table 1. 1Switching arc voltage patterns.
Case A Case B
V t
S t t
t t
t t tCB
=
0 0
1
1
1 2
V t
S t t
t t
t t tCB
=
0
3
0
1
1
1 2
where: t1 is tripping time, t2 is current-zero time and Sis the slope of the switching arc voltage. The
interruption time is defined as the time difference between t2 and t1 . In case A, the rate of change of
the switching arc voltage Swas about 250V/ms which is a typical value for conventional breakers.
The switching arc voltage increased and suppressed the current within 6.8ms, see the left hand
column of Figure 1.3. In case B, the switching arc voltage grew three times faster (750V/ms). The
interrupting time then became 2.95ms, see the right hand column of Figure 1.3. The energy balance
for both cases can be calculated too as shown below the current and voltage graphs.
-
5/25/2018 Direct Current Hybrid Breakers
17/195
Concepts of direct current limitation and interruption 5
Case A Case B
ICBVCB
0 2 4 6 8 100
500
1000
1500
2000
2500
3000
3500
4000
time [ms]
Current[A],Voltage[V]
Current and voltage
ICBVCB
0 2 4 6 8 10-500
0
500
1000
1500
2000
2500
3000
time [ms]
Current[A],Voltage[V]
Current and voltage
WTotWRWCB
0 2 4 6 8 100
5
10
15
20
25
time [ms]
Energy[kJ]
Energy balance
WTotWRWCB
0 2 4 6 8 100
1
2
3
4
5
6
7
8
time [ms]
Energy[kJ]
Energy balance
Figure 1. 3 DC interruption for different patterns of the arc voltage with a trip current I trip=2kA;
where: ICBand VCBare the current in and voltage across the breaker and W Tot, WRand WCBrepresent the
energy dissipated during the interruption; due to the total, line resistance and in the breaker, respectively.
From these results, it can be seen why the interruption must not be too fast because it caused high
surge voltages and not too slow because it caused long energy dissipation times that might damage
the contacts. The simulated results are summarized in Table 1.2.
Table 1. 2 The energy balance of the interruption;
WRand WCBfor the dissipated energy in the line resistance and the breaker respectively.
WR
[Joule]
WCB
[Joule]
tint
[ms]
Imax
[A]
Case Awith S=250V/ms 6322 13909 6.8 3929
Case Bwith S=750V/ms 1586 5576 2.95 2807
Adequate current limiting capacity could be achieved by minimizing the arcing time and generating
switching voltages 1.1 to 1.5 times higher than the supply voltage. This was possible by using a
special cooling mechanism to destabilize the arc plasma. Clearly, the appearance of switchingvoltages across the breaker could cause energy dissipation through the arcing process. It was
-
5/25/2018 Direct Current Hybrid Breakers
18/195
6 Chapter 1
released mainly as heat to the surroundings. At the same time, this energy could damage and
corrode the contacts, thus shortening the breaker life and reducing its interrupting capacity.
In this thesis, a conventional air breaker was investigated and it is described in Chapter 7.
1.2.2 Current limiting fuses
The simplest current limiting device is the fuse [1.6], which is able to conduct a continuous current,
sense a fault automatically, limit the current, dissipate the energy and interrupt the fault. Current
limiting fuses unlike circuit breakers become operational before the short-circuit current reaches a
prospective peak value and thereby they effectively limit the let-through current to lower values.
Due to this current limiting action and the subsequent rapid interruption and isolation of the circuit,
thermal and electrodynamic effects on components of the circuit are reduced to a minimum. The
most important characteristics of fuses are low continuous current ratings, small size, cheapness and
suitability for both low and medium voltage AC and DC systems.
Self-recovery fuses based on sodium (Na) have been developed in the past [1.7], but so far further
development is uncertain; however, it should be noted that the fuse arc voltage will be
superimposed on the system and must, therefore, be limited to avoid excessive overvoltages. On the
other hand, energy considerations and fuse size limitations require that the fuse arc voltage is
typically up to twice the line to neutral voltage. Disadvantages of a fuse are its limited continuous
current rating and the need for replacement after each fault. These shortcomings can be partly
overcome by using triggerable current limiting devices with a parallel path for the continuous
current.
1.2.3 Pyrotechnique
By separating the continuous current conduction and interruption duties of triggerable current
limiting devices, the fusible element is shunted by a link which can be removed as required. Theinterrupting duty is provided by a fuse once the current has been commutated from the shunting
device. In principle, such breakers consist of two main components, firstly a special copper
conductor which can carry large continuous currents during normal operation, but it can be sheared
at high speed by a pyrobreaking technique when overloaded, and, secondly, current limiting fuses
which are mounted in parallel with the large continuous current conductor [1.8]. A diagram of this
device is depicted in Figure 1.4.
-
5/25/2018 Direct Current Hybrid Breakers
19/195
Concepts of direct current limitation and interruption 7
Main conductor
Control Circuit
I
I dI/dt
Fuse
Figure 1. 4 Schematic of the Pyrotechnique
The main current conductor is broken by the pyrotechnique mechanism which is triggered by a
control circuit fed by a sensor system. The pyrotechnique mechanism contains an explosivechemical charge. After that charge explodes, the current commutates to the fuse for controlling
current limitation and interruption. System parameters, such as the current and current slope , are
monitored using appropriate sensors. The signal generated by the sensors is compared with a preset
reference value in the control circuit and this can trigger the chemical charge. The pyrotechnique
circuit interrupter is very useful for protecting electrical systems with high continuous currents
(>5kA) when rapid interrupting is required. Clearly, this device can not be reset. The recovery time
is long and the cost of the replacement is high.
Several manufacturers deliver pyrotechnique products [1.8,9,10]. Their main uses are in medium
voltage AC networks although they can be used in DC systems too (but not for traction, due to fast
reclosing requirements).
1.2.4 Positive Temperature Coefficient Resistors (PTCR)
A composite of polymer and metal forms the main part of this device which like fuses, is inserted in
the line where it carries a rated current continuously. In such situations, the ohmic losses are
sufficiently low in order to prevent any real resistance increase. When the current suddenly
increases, the internal heating will exceed the natural cooling capability. If the temperature of the
polymer resistor increases above a critical limit, its resistance changes stepwise up to ten orders of
the normal magnitude (Figure 1.5). Consequently, the current is limited. A load breaker then
interrupts the final current. When the internal temperature returns to the ambient temperature, the
PTCR resumes normal service after the short-circuit has been removed; therefore, this device can be
used repetitively.
-
5/25/2018 Direct Current Hybrid Breakers
20/195
8 Chapter 1
20 40 60 80 100 120 140
10-2
100
102
104
106
108
Temperature [C]
Spec.
Resistivity[cm]
Figure 1. 5 Specific resistivity as a function of temperature TiB2.
These devices have been tested in 220V AC networks [1.11] when a prospective current of 16kA
can be reduced to just 3kA. Recently, a device for 12kV networks was announced [1,12] for
repetitive current limitation of prospective currents of 4 to 14kA within 1ms. Their reliability and
economy are not yet generally accepted and suitability for DC networks is also unknown as yet.
1.2.5 Superconducting Current Limiters (SCCL)
Because superconducting materials operate below the ambient temperature they require cooling in
order to maintain their superconducting properties. A fault current brings the superconducting
material to its normal resistive state which limits the fault current to an acceptable level. Basically,
two methods are employed; firstly, the so-called resistive method which uses a superconducting
element for transferring the fault current to a shunt resistor thereby limiting it, see Figure 1.6(a).
Secondly, a system of coupled coils in which the secondary winding is connected to the
superconducting material, see Figure 1.6 (b). This is also known as the inductive method
[1.13,14,15].
Rshunt
iline
Cryogenic shield
Load breaker
(a)iline
Cryogenic shield
Load breaker
Lprim
Lsec
(b)
Figure 1. 6Schematic of the superconducting current limitation types; (a) resistive (b) inductive.
Resistive type
Commutating the current is accomplished by switching the superconducting element from a state of
zero resistance (this occurs below the critical temperature TC) to its resistive state, by increasing thetemperature above TC. The critical temperature TCdepends on the superconducting material. Under
normal conditions, the load current flows through the superconductor but after a fault, the resistance
-
5/25/2018 Direct Current Hybrid Breakers
21/195
Concepts of direct current limitation and interruption 9
of the superconductor becomes much greater than the shunt resistance. So, after commutation only a
small current flows in the superconducting element. A load breaker for fully rated continuous
current can finally interrupt the limited current.
Inductive type:Under normal conditions, coupled coils consisting of a normal conducting primary coil and a
superconducting secondary coil act as a short-circuited transformer, so that a low impedance is
introduced into the primary circuit. But when the current exceeds a certain value, the current
induced in the secondary coil becomes too high, resulting in a change in the state of the
superconducting material. A high impedance value will then appear on the primary side and it limits
the fault current. Finally, a load breaker can disconnect this current. The secondary side can also
include a stack of short-circuit rings composed of superconducting material [1.16].
These interrupting devices have the following advantages : there are no moving parts; and there are
low losses, but the main drawback is their need for permanent cooling. Apparently, the
superconducting current limiter may become economically attractive for medium voltage AC
networks; however, the inductive type is unsuitable for DC systems.
1.2.6 Solid-State Breakers (SSB)
Since the invention of power semiconductors (power diode, thyristor, GTO-thyristor, power
transistor, IGBT, power MOSFET, and recently the IGCT), these components have been considered
for load switching in power networks [1.17,18,27,30,32,37]. Power semiconductor switches provide
a fast acting arcless mechanism with great reliability and reduced maintenance. There are some
disadvantages, however, such as their sensitivity to transient overvoltage and overcurrent. Such
transients can break down the junctions of power semiconductors. Also the power losses in them
can be relatively high which will limit their current ratings. Effective cooling is required too. Figure
1.7 shows an overview of the voltage-current-range capacities of solid-state devices [1.28]. The
IGCT has a rating comparable with the GTO.
101
102
103
104
101
102
103
104
SCR
GTO-thyristor
HPBT
IGBTSIT
MOSFET
Current maximum [A]
Figure 1. 7Application ranges of power semiconductor devices
where SCR: Silicon Controlled Rectifier or Thyristor; GTO-thyristor: Gate Turn-Off thyristor;
HPBT: High Power Bipolar Junction Transistor; IGBT: Insulated Gate Bipolar Transistor;
SIT: Static Induction Transistor; MOSFET: Metal Oxide Semiconductor Field Effect Transistor;
-
5/25/2018 Direct Current Hybrid Breakers
22/195
10 Chapter 1
As a controllable solid-state switch with its highest rating for forward currents and blocking
voltages, the thyristor is still invincible, followed by the GTO-thyristor and the IGCT. Since such
devices are controlled by currents, they can be unsuitable for some applications. Transistor-based
devices which are controlled by voltage are faster, but generally, they have much lower current
ratings and blocking voltages. Figure 1.8shows a general application of solid-state breakers with
auxiliary protective devices.
Commutation Circuit
Voltage Limiting Element
Control Circuit
I
SSB dI/dt
Snubber Circuit
I
Figure 1. 8 Schematic of the Solid-state breaker (SSB).
Research and testing of breakers based on pure solid-state switches have been reported in many
papers both for AC and DC systems. Basically, two methods are known; one and two-stage
interruptions. One-stage interruption is the commonest type where the interruption process can be
difficult, because the device must reduce the overcurrent to zero [1.19,20,21,22,33,43,49,56].
During this process, the solid-state switches may undergo stresses and not be able to interrupt the
current, particularly in high voltage or high current systems. A combination of both series and
parallel arrangements of the solid-state switches may help solve the problem. However, a new
problem arises, that is, the sharing of voltages and currents among those switches. On the other
hand, two-stage interruption facilitates the interruption process by firstly reducing the fault current
to a much lower value after which the current is interrupted in the second stage [1.23].
In this thesis, a new solid-state device (IGCT) was investigated and the results are presented in
Chapter 7.
1.3 Hybrid switching techniques
Purely mechanical and solid-state breakers have both positive and negative points. Table 1.3
summarizes and compares a number of breaker features.
-
5/25/2018 Direct Current Hybrid Breakers
23/195
Concepts of direct current limitation and interruption 11
Table 1. 3 Comparison of mechanical and semiconductor breakers.
Feature mechanical breaker semiconductor breaker
Switching mechanism metallic contact and arc PN-junction
Contact resistance - m few m
Power loss very small relative high
Voltage drop at rated current less than 10mV 1-2V
Galvanic isolation Yes No
Isolation capability very high limited (sensitive for overvoltage)
Overload capability very high limited by I2t value
Delay/response time few ms-20ms few s
Life expectancy limited by contact erosion theoretically unlimited
Contact reliability high very high
Frequent switching ability high very high
Surge capabilities high limited (device dependence)
Overvoltage protection not necessary snubber circuit/varistor
Size & volume compact and small relatively big due to cooling being
necessary
Maintenance necessary not necessary
Cost relatively low relatively high
Integrating solid-state devices with a mechanical breaker in a combined configuration is called the
Hybrid Switching Technique(HST) [1.24,25,26,31,35,36,40,42,44,48,49]. Intentionally, the positive
points from each method are retained and the negative points are eliminated. As a result of the fast
actions of semiconductors, the moving mechanism of the main contact is critical. The hybrid
switching technique is very suitable for limiting currents especially for repetitive use.
Generally, within a hybrid switching system, two different mechanical switches are incorporated; a
main breaker and an isolation switch; the main breaker is accompanied by a solid-state switch inparallel. The main breaker provides a path for the continuous current, while the isolation switch
allows dielectric separation of the load after a current interruption. The solid-state switch will
operate only when the main current has to be interrupted. Figure 1.9shows the basic components of
hybrid switching. A commutation path is connected in parallel with the main breaker, it includes a
snubber circuit as a transient suppressor and a voltage limiting element as an energy absorber.
During normal operation, the snubber circuit and voltage limiting element provide high impedance
paths. The commutation path is introduced by solid-state switches and only operates during the
interruption process. All the switches are controlled by electronic circuits.
-
5/25/2018 Direct Current Hybrid Breakers
24/195
12 Chapter 1
Snubber Circuit
Isolation Switch
Voltage Limiting Element
I
CommutationCircuit
Main Breaker
Solid-stateSwitch
Figure 1. 9 Basic components of hybrid switching techniques.
The fact that the reaction times of solid-state switches are much quicker than those of the
mechanical ones, means that the mechanical drive of hybrid breakers must be as fast as possible
[1.53]. The higher the rated current, the greater the mass of the mechanism that is needed. Also, the
main breaker MB must be able to maintain insulation at the time of the first current-zero event;
consequently, a vacuum breaker is most suitable because of its excellent insulating properties after
the current-zero. For the development of a high-speed current limiting circuit breaker based on
hybrid switching techniques, the features needed are listed in Table 1.4[1.29,50,52].
Table 1. 4 Design requirements for hybrid breakers.Subject Purpose Methods
High-speed operation fast fault detecting time suitable criteria for faults in a certain
network based on parameters i , di/dtfast main breaker MB opening
time adoption of a fast electrodynamic drive
system
decrease the entire mass of the movingpart of the MB
High-current interruption fast current commutation from
main breaker MB to
commutating path
reduction of circuit inductance on thecommutation path
increase the arc voltage in the MB
adaptation of main breakerMB and commutating devices
application of fast switches forinitiating the counter-current, (high
di/dt and dv/dt capabilities)
limitation of the overvoltage
during the interruption using proper overvoltage protection
devices (snubber and non-linear
resistance)
free-wheeling diodes to absorb the load-stored inductive energy
increase the capacitance value anddecrease its initial voltages
-
5/25/2018 Direct Current Hybrid Breakers
25/195
Concepts of direct current limitation and interruption 13
Economic considerations will follow these engineering design aspects of hybrid breakers in the
field. Investigations of contact erosion with HST are reported in [1.34,38], whilst the role of ZnO as
a voltage clipper during operation is discussed in [1.45,46].
An interest in developing HST breakers has been shown by a few electric power companies andtheir breakers are detailed in Table 1.5.
Table 1. 5 Commercial types of HCB for fault current limitation.
ACEC (1992) Meiden (1995) Fuji
(1994)
Zwar (1996)
rated voltage 750V,1.5kV,3kV
(DC)
1.5kV(DC) 400V(AC) 3kV(DC)
rated current 6kA 4kA 2kA 250, 400A
interruption
time
-
5/25/2018 Direct Current Hybrid Breakers
26/195
14 Chapter 1
capacitance of 1.44F with initial voltage of 400V [1.58]. Nevertheless, this solution could not
penetrate into existing DC applications because of their triggering criteria and economics.
1.4 Outline of thesis
The outline of this thesis is given below.
Chapter 2 characterizes one-stage hybrid interruption techniques using analytic and numeric
solutions.
Chapter 3 presents two-stage interruption methods that alleviate the component problems, with the
aid of analysis and simulations.
Chapter 4 describes DC measurement and fault detection methods.
Chapter 5 describes and models the fast opening mode of the prototype breaker developed using a
specially designed electrodynamic drive.
Chapter 6 gives an explanation of the direct current short-circuit source with the models required for
the experiments.
Chapter 7 covers the experimental and simulation results including those for an air breaker, a hybrid
breaker and a solid-state breaker.
Chapter 8 presents and discusses the conclusions that can be drawn from the work described in this
thesis giving recommendations for future work.
1.5 References and reading lists
[1.1] Bartosik, M., Progress in D.C. breaking, Proc. 8th Int. Conf. Switching Arc Phenomena,
Summary of discussed items on fuses, Lodz, Poland 3-6 Sept. 1997, Vol. 2, p. 24-41.
(Published in 1998)
[1.2] Kenn Lian, DC Breaker Applications, HVDC Circuit Breaker Symposium 1972, IEEE
Summer Power Conference, p. 9-10.
[1.3] Schaufelberger, F.G., HVDC Circuit Breakers- Application, HVDC Circuit Breaker
Symposium 1972 IEEE Summer Power Conference, p. 13-4.
[1.4] Pucher, W., Fundamentals of HVDC Interruption,Electra, No. 5, 1968, p. 24-38.
[1.5] Lee, A., et. al., The development of a HVDC SF6 breaker, IEEE Trans. on Power
Apparatus and Systems, Vol. PAS-104, No. 10, October 1985, p. 2721-9.
[1.6] Newbery, P. and Wright, A., Electric fuses, Proc. IEE, Vol. 124, No. 11R, November
1977, p. 909-24.
[1.7] Nakayama, H. et.al., Development oh high voltage, self-healing current limiting element
and verification of its operating parameters as a CLD for distribution substations, IEEE
Trans. on Power Delivery, Vol. 4, No. 1, January 1989, p. 342-8.
[1.8] Benouar, M., Pyrotechnique circuit interrupter for the protection of electrical systems,
IEEE Trans. on Power Apparatus and Systems, Vol. PAS-103, No. 8, August 1984, p.
2006-10.[1.9] -, Is-limiter, ABB Calor Emag Schaltanlagen AG, 1996.
-
5/25/2018 Direct Current Hybrid Breakers
27/195
Concepts of direct current limitation and interruption 15
[1.10] Das, J.C., Limitations of fault current limiters for expansion of electrical distribution
systems, IEEE Trans. on Industry Applications, Vol. 33, No. 4, July/August 1997, p.
1073-82.
[1.11] Skindhj, J., et.al., Repetitive current limiter based on polymer PTC resistor, IEEE
Trans. on Power Delivery, Vol. 13, No. 2, April 1998, p. 489-94.
[1.12] Strumpler, R., et.al., Novel medium voltage fault current limiter based on polymer PTCresistors,IEEE Trans. on Power Delivery, Vol. 14, No. 2, April 1999, p. 425-30.
[1.13] Tixador, P., et.al., Hybrid superconducting a.c. fault current limiter principle and previous
studies,IEEE Trans. on Magnetics, Vol. 28, No. 1, January 1992, p. 446-9.
[1.14] Gray, K.E., and Fowler, D.E., A superconducting fault-current limiter, Journal of
Applied Physics, 49(4) April 1978, p. 2546-50.
[1.15] Noe, M., Supraleitende Strombegrenzer als neuartige Betriebmittel in
Elektroenergiesystemen, PhD Dissertation 1998, Hannover University. (In German)
[1.16] Tanaka, T, et.al, Electrical insulation in HTS power cables, fault-current limiters and
transformers,Electra, No. 186, October 1999, p. 11-29.
[1.17] Smith, R.K., et. al., Solid state distribution current limiter and circuit breaker: application
requirements and control strategies, IEEE Trans. on Power Delivery, Vol. 8, No. 3, July
1993, p. 1155-64.
[1.18] Ueda, T., et. al., Solid-state current limiter for power distribution system,IEEE Trans.
On Power Delivery, Vol. 8, No. 4, October 1993, p. 1796-1801.
[1.19] Jinzenji, T., and Kudor, T., GTO DC circuit breaker based on a single-chip
microcomputer,IEEE Trans. on Industrial Electronics, Vol. IE-33, No. 2, May 1986, p.
138-43.
[1.20] Salama, M.M.A., et. al., Fault-current limiter with thyristor-controlled impedance (FCL-
TCI),IEEE Trans. on Power Delivery, Vol. 8, No. 3, July 1993, p. 1518-27.
[1.21] Chokhawala, R., and G. Castino, IGBT Fault current limiting circuit, IEEE Industry
Applications Magazine, September/October 1995, p. 30-5.[1.22] Zyborski, J., J. Czucha and M. Sajnacki, Thyristor circuit breaker for overcurrent
protection of industrial d.c. power installations, Proc. IEE, Vol. 123, No. 7, July 1976, p.
685-8.
[1.23] McEwan, P.M., and Tennakoon, S.B., A two stage DC thyristor circuit breaker, IEEE
Trans. on Power Electronics, Vol. 12, No. 4, July 1997, p. 597-607.
[1.24] Atmadji, A.M.S., Hybrid switching: a review of current literature,Int. Conf. on Energy
Management and Power Delivery 1998, Mar. 1998 Singapore, p. 631-8.
[1.25] Amft, D., and Drummer, G., Hohere Schaltstuecklebensdauer durch
Hybridschutztechnik,Elektrie24, 1970, H.5, p. 165-7. (In German)
[1.26] Humann, K., and Koppelmann, F., Lichtbogenfreies von Wechselstrom mit mechanischen
Schaltern in Verbindung mit Paralleldioden im Niederspannungsbereich,
Elektrotechnische Zeitschrift ETZ-A, Bd. 86, 1965, H. 15, p. 496-500. (In German)
[1.27] Baliga, J.,Modern power devices, Wiley-Interscience, 1987.
[1.28] Chen, D.Y., Power Semiconductors: fast, though and compact, IEEE Spectrum
Magazine, September 1987, p. 30-5.
[1.29] Genji, T., et. al., 400V class high-speed current limiting circuit breaker for electric power
system,IEEE Trans. on Power Delivery, Vol. 9, No. 3, July 1994, p. 1428-35.
[1.30] Bonhomme, H., and Legros, W., Use of Power semiconductors in circuit breakers,
Proceedings of the fifth International PCI Conf., September 28-30 1982, Geneva
Switzerland, p. 319-25.
[1.31] Hartig, G., and Wedell, H., Betrachtungen uber Ausgleichvorgange bei derParallelschaltung von mechanischen Schaltstrecken und Halbleiterleistungsventilen,
Elektrie27, 1973, H. 6, p. 309-10. (In German)
-
5/25/2018 Direct Current Hybrid Breakers
28/195
16 Chapter 1
[1.32] Humann, K., and Koppelmann, F., Kontaktloses Schalten mit steuerbaren
Halbleiterelementen im Niederspannungsbereich, Elektrotechnische Zeitschrift ETZ-A,
Bd. 86, 1965, H. 17, p. 552-7. (In German)
[1.33] Bonhomme, H., et.al., A 6kV/500A Switching device with thyristors : dream or reality,
Proceedings of the sixth International PCI Conf., April 1983, Orlando, USA, p. 1-5.
[1.34] Greitzke, S., Untersuchungen an Hybridschaltern, Dissertation TU Braunschweig, 1988.
(In German)
[1.35] Bonhomme, H., et. al., A semistatic switching device,Int. Conf. on Power Electronics
and Variable-Speed Drives, PEVSD '84, London, May 1984, p. 27-9.
[1.36] Krstic, S., and P.J. Theisen, Push-Button Hybrid Switch,IEEE Trans. on Components,
Hybrids and Manufacturing Technology, Vol. CHMT-9, No. 1, March 1986, p. 101-105.
[1.37] Holroyd, F.W., and Temple, V.A.K., Power Semiconductor devices for hybrid breakers,
IEEE Trans. on Power Apparatus and Systems, Vol. PAS-101, No.7, July 1982, p. 2103-8.
[1.38] Greitzke, S., and Lindmayer, M., Commutation and erosion in hybrid contactor systems,
IEEE Trans. on Components, Hybrids and Manufacturing Technology, Vol. CHMT-8, No.
1, March 1985, p. 34-9.[1.39] Collart, P., and Pellichero, S., A new high speed DC circuit breaker: the DHR, IEE
Colloquium on Electronic-aided current limiting circuit breaker developments and
applications, No. 1989/137, p. 7/1-3.
[1.40] Chaly, M., et. al., Switching arc in combined switching systems, 3th Int. Symp. on
Switching Arc Phenomena(SAP), Lodz, Poland, September 1977, Part 1, p. 153-6.
[1.41] Collart, P., and Pellichero, S., A super high speed intelligent circuit breaker, GEC
Alsthom Technical Review, No. 9, 1992, p. 35-42.
[1.42] Theisen, J., et. al., 270-V DC Hybrid Switch,IEEE Trans. on Components, Hybrids and
Manufacturing Technology, Vol. CHMT-9, No. 1, March 1986, p. 97-100.
[1.43] Lasota, R., Reduction of switching arc energy in direct current hybrid switches with GTO
thyristors, 7th International Conference Switching Arc Phenomena(SAP), 27 September -
1 October 1993, Lodz, Poland, p. 264-7.
[1.44] Shammas, N.Y.A., Combined conventional and solid-state device breakers, IEE
Colloquium on Power semiconductor devices, No. 1994/247, p. 5/1-5.
[1.45] Hasan, S., et.al., The critical switching parameters of a new hybrid AC low voltage circuit
breaker without and with ZnO varistor, 6th Int. Symp. On Short-Circuit Currents in
Power System, September 1994, Liege Belgium, p. 3.11.1-8.
[1.46] Czucha, J., et.al., AC low-voltage arcing fault protection by hybrid current limiting
interrupting device, 7th Int. Symp.on Short-Circuit Currents in Power Systems, September
1996, Warsaw Poland, p. 3.8.1-5.
[1.47] Brice, C.W., et.al., Review of Technologies for Current-Limiting Low-Voltage CircuitBreakers,IEEE Trans. on Industry Applications, Vol. 32, No. 5, Sept./Oct. 1996, p. 1005-
10.
[1.48] Lasota, R., The work of hybrid switches in low voltage direct current circuits, Fifth
International Symposium on Switching Arc Phenomena (SAP), September 1985, Lodz,
Poland, p. 152-5.
[1.49] Lasota, R., Some problems of arc energy limitation in the DC hybrid switches with power
MOSFET, Sixth International Conference on Switching Arc Phenomena (SAP),
September 1989, Lodz, Poland, p. 40-3.
[1.50] Bartosik, W., Theoretical and practical aspects of fault direct current switching-off by
counter-current, Proc. of the Int. Conf. on Electrical Contacts, Arcs, Apparatus and Their
Applications, May 3-7 1989, Xi'an China, p. 5-12.
-
5/25/2018 Direct Current Hybrid Breakers
29/195
Concepts of direct current limitation and interruption 17
[1.51] Takehara, K. and Yamada, Y., High-speed circuit-breaker incorporating a digital current
detector to support safe operation of electric trains, Meiden review [International
Edition],1995, No. 3, p. 29-32.
[1.52] Shammas, N.Y.A., and Naumovski, N., Combined conventional and solid-state device
breakers 'Hybrid circuit breakers' , Proc. 29th Univ. Power Eng. Conf, UPEC 1994,
Galway (Ireland), p. 716-9.[1.53] Czucha, J., and J. Zyborski, Ultra fast hybrid circuit breaker for AC network theoretical
analysis, 29th University Power Engineering Conf, UPEC 1994, Galway Ireland, Vol. 1,
p. 173-6.
[1.54] -, Ultra high-speed direct current-limiting vacuum circuit breakers, Manufacture Catalogue
Sheet, 1996, Zwar, Poland.
[1.55] Bartosik, W., et. al., Arcless DC Hybrid circuit breaker,Eight International Conference
on Switching Arc Phenomena(SAP), September 1997, Lodz Poland, p. 115-9.
[1.56] Dawson, F.P., et.al., A fast DC current breaker,IEEE Trans. on Industry Applications,
Vol. IA-21, No. 5, Sept./Oct. 1985, p. 1176-81.
[1.57] Dokopoulos, P. and Kriechbaum, K., Gleichstromschalter fuer 73kA und 24kV in der
Plasmaphysik, Elektrotechnische Zeitschrift ETZ-A, Bd. 97, 1976, H.8, S. 499-503. (In
German)
[1.58] Dijk, E. van., Experimental results obtained with the 1 MA resonant series counterpulse
opening switch system, developed at TNO, 11th IEEE International Pulsed Power Conf.,
June 29 - July 2 1997, Baltimore, Maryland, USA, p. 287-92.
-
5/25/2018 Direct Current Hybrid Breakers
30/195
18 Chapter 1
-
5/25/2018 Direct Current Hybrid Breakers
31/195
Chapter 2
Analysis of commutating circuits for hybrid breakers
Abstract
For DC networks, current limiting devices are necessary for disconnecting faulty circuits rapidly.
This work presents an analysis of the hybrid techniques which apply to current commutation.
Firstly the basic commutation circuit known as one-stage interruption is described. Results from
simulations of the complete system are presented giving an estimation of the possible transient
behavior during the interruption processes. Analytical and numerical solutions have been obtained
for the relevant differential equations.
2.1. Introduction
The fact that DC systems have no natural current-zero, becomes a problem when currents have to be
interrupted. Principally, breakers may use two ways of producing current-zeros. According to one
method, an arc voltage is created between the electrodes of the breaker which opposes the supply
voltage. The breaker has to be able to produce arc voltages greater than the systems voltage in order
to produce the current-zero. The success of arc plasma quenching depends on the ability of the
surrounding medium to absorb all the inductive energy stored in the system. Unfortunately, thismethod eventually results in long arcing times causing considerable erosion of the contacts of the
breaker. The greater the inductive energy content of the system, the longer the arcing times
necessary. An effective current limitation may be hampered by the chance of the contacts opening
and a fast voltage building up in the early stages of the interruption process.
Another way of interrupting a current is known as current commutation. The commutation process
requires additional circuits to be connected in parallel across the main breaker. Generally, such
circuits are able to store a certain amount of energy and by discharging this energy, a controlled
counter-current injection can be made. This counter-current injection opposes the main current in
the breaker (by superposition) in order to produce a forced current-zero. Indeed, current-zero can
only be produced if the counter-current injected is greater than the instantaneous fault current;
consequently, it is very important to identify the fault current level in which the counter-current
injection will be able to force the current to zero. This method reduces the arcing time effectively
thereby reducing contacts erosion [2.1]. The basic DC commutation system is shown in Figure 2.1
[2.2,3].
-
5/25/2018 Direct Current Hybrid Breakers
32/195
20 Chapter 2
MOV
RLoad
ES
iS iB S1
DFWCC LC
iMOV
S3
S2
-
+
iCRT
LT LLoadvC
Figure 2. 1Basic DC systems with a commutation circuit; S1: main breaker, S2: auxiliary switch,
S3: load breaker, CCand LC: commutation capacitor and coil, and MOV: metal oxide varistor.
A DC source ESwith circuit resistance RT and inductance LT is connected in series with a main
breaker S1 and a load breaker S3 followed by a load. The circuit resistance and inductance may
comprise the value of the DC source and linking lines or tracks. The current normally passes
through the main breaker S1. A commutation circuit is connected in parallel across the main breaker
S1; it consists of capacitor CC, coil LCand auxiliary switch S2. The metal oxide varistor (MOV)
connected across S1 have a clamp voltage protecting devices in the system. The capacitor CCcan be
initially pre-charged, as is required of the active commutation mode, otherwise it is called the
passive commutation mode. Because the load is inductive, the system may require a freewheelingdiode DFWin parallel with the load side. The freewheeling diode DFWwill bypass the circuit current
when the current slope changes to negative. Intentionally, this is very useful for avoiding any energy
being transferred from the downstream lines (transmission lines and inductive loads) to the
commutation capacitor CC during the interruption. In contrary, the source side inductive energy
cannot be bypassed using the freewheeling diode.
In the active mode, a current oscillation provided by the precharged commutation capacitor CCwill
arise instantly and it will grow to oppose the current in the main breaker S1 when the auxiliary
switch S2 is closed. A trip command provided by a fault sensor controls closing of the auxiliary
switch S2 and opening the main breaker S1. A proper combination of LC and CC will create an
oscillation that generates at least one current-zero crossing in the main breaker S1. After an
interruption at current-zero in the main breaker S1, the main current i S will commutate to the
parallel path thereby changing the polarity of the capacitor CC. Oscillation of the commutated
current will create another current-zero crossing in the switch S2 that will be determined by the
upstream line and the commutation parameters. Therefore, the capacitor will be charged up to a
value depending on the initial voltage, the system voltage and a voltage related to the stored
inductive energy in the upstream line. In short, the residual capacitor voltage will depend on the
network parameters to a great extent. When the main breaker S1 is not separated at the first current-
zero, the current interruption can be produced at the second current-zero crossing. If the switch S2 is
-
5/25/2018 Direct Current Hybrid Breakers
33/195
Analysis of commutating circuits for hybrid breakers 21
bi-directional, the damped current will oscillate in the circuit until it becomes zero and the capacitor
voltage becomes equal to the supply voltage. As a matter of fact, this oscillation enables the stored
inductive fault energy to be dissipated in the circuit resistance. However, the switch S2 and the
rectifier station are generally uni-directional. As a consequence, after the first current-zero occurs in
the switch S2, it opens and the capacitor CCwill have to withstand high voltages. At this instant,current interruption is achieved. Finally, the load breaker S3 can be opened without any arcing. For
a successful commutation, the main breaker S1 must be able to maintain the isolation between its
electrodes at and after the current -zero creation. This active commutation circuit is known as the
one-stage interruption method. Disadvantages of this method include:
the need of a continuous external voltage for charging the capacitor CC;
high overvoltages across the breaker when a current interruption occurs and this requires
voltage limiting devices, such as arresters, MOVs, etc.;
CCmust have a large capacitance value, consequently, it must have a large size and a high
price;
the commutation circuit may be unable to fulfill its function after an interruption failure.
Apart from the active mode described above, a passive mode is needed sometimes. In the passive
commutation mode, it can be assumed that a short circuit has been caused on the load-side, resulting
in fault current iS=iBflowing in the circuit. When the fault current iSexceeds the critical limit, the
main breaker S1 will open drawing an arc between its electrodes. The switch S2 subsequently must
be closed in order to initiate a counter-current iCin the branch S1. A proper combination of LCand
CCwill create an oscillation that generates at least one current-zero crossing in the main breaker S1.
For the passive mode, the current commutation needs a longer time due to the interaction between
the arc and the LCCC-loop. An oscillatory current will be created by an uncharged capacitor that is
repeatedly charged and discharged by the arc voltage in the course of current interruption. The
condition for current interruption in the main breaker S1 is created solely by passive elements in
parallel with the breaker and by the properties of the arc itself. When the contacts are separated, arc
plasma is formed. The arc voltage will increase further as a result of arc lengthening and the heat
loss increases. During a short period, the current in the LCCC branch will show a growing
oscillation. At a time when its magnitude is equal to the main current, current-zero in the main
breaker S1 can be produced. The main current iS commutates entirely to the parallel path.Consequently, the source will charge up the capacitor increasing its voltage. At a moment that the
current is zero in the auxiliary switch S2, the capacitor will be fully charged so that its voltage will
reach its highest value. As a result, the interruption succeeds. If the auxiliary switch S2 is bi-
directional, the oscillation can continue until the capacitor voltage is equal to the supply voltage,
otherwise the interruption will occur as soon as the current becomes zero.
Every DC system has a maximum fault current. Obviously, the rate of change of the fault current
depends on the line inductance. Since the energy stored in the commutation capacitor is limited too,
there will be another significant quantity of energy available for creating a successful current-zero.
Therefore, the maximum trip current for recognizing a fault has to be determined carefully for each
DC system. As an illustration of the current interruption procedure, a DC system with a prospective
-
5/25/2018 Direct Current Hybrid Breakers
34/195
22 Chapter 2
fault current of 10kA will now be analyzed. For the fault current, a rate of change between 1 and
10A/s has been assumed. Figure 2.2shows typical DC faults and their current slopes.
=1ms
=3ms
=6ms
=9ms
0 2 4 6 8 100
1
2
3
4
5
6
7
8
9
10
time [ms]
Current[kA]
(a)
=1ms
=3ms=6ms
=9ms
0 2 4 6 8 100
1
2
3
4
5
6
7
8
9
10
time [ms]
di
dt__[
A/s]
(b)
Figure 2. 2Typical DC faults with Ipros=10kA and 4 different time constants;
(a) the currents and (b) the current slopes.
This study will now concentrate on the active counter-current injection method which is controlled
by a uni-directional solid-state switch. That will lead to the realization of a hybrid breaker with a
current limiting ability using the current commutation principle which can limit a 5kA prospective
DC fault to just 3kA in 1kV/1kA DC systems.
2.2. Analysis of the active commutation circuit
A typical sequence for one-stage DC interruption is illustrated in Figure 2.3. For convenience, the
current is represented by a straight line rising from zero.
t
i
i
1st CZ
t3
tiB
Isp
t
t1
iiS
I t1iC
(a) t0tt1
(c) t2tt3
(b) t1tt2
vC
VCO
t
t
VCE
iS
t2
iS=iC
t2 t3
t1
t2VCt2
t1
t0
t0
It1
It2
vC
vC
t
2nd CZ
Figure 2. 3The sequence of one-stage DC fault interruption; CZ current-zero crossing in the main breaker.
-
5/25/2018 Direct Current Hybrid Breakers
35/195
Analysis of commutating circuits for hybrid breakers 23
At time t1, the source current iSreached a level It1, see (a), the threshold for starting the interruption
process. A counter-current injection iCwas applied to oppose the source current iS, see (b). As a
result, the current in the breaker iBwould decrease. At instant t2, the current iBbecame zero and the
voltage across the commutation capacitor reached VCt2. After that, current-zero was produced and
the current iSwas completely commutated from the main breaker to the parallel path. During theinterval t1-t2, the source current iSkept increasing. When charging in the interval t2-t3, the source
current was firstly increased due to the stored magnetic energy transfer and that remaining in the
capacitor CC. Subsequently, charging changed to the opposite polarity. At time t3, the source current
iS reached zero when the capacitor CC was fully charged, see (c). The capacitor current was
eventually interrupted and its final voltage (VCE) increased to a higher value but having an opposite
polarity. Hereafter, the load breaker S3 could be opened in order to isolate the fault from the source.
The final voltage across the capacitor CChad to be limited which depended on the magnetic energy
stored in the system, the initial voltage of the capacitor, and the supply voltage. When that voltage
reached the clipping value of the arrester, it limited the overvoltage. This process prevented any
further voltage rise as the arrester partly absorbed the inductive DC-line energy (W Lim= 1 22).
Obviously, a proper choice of arrester voltage for the clip was vital. Energy absorption by the
arrester would lead to a decay of the fault current at a certain time depending on the line inductance
and the last current value before the commutation. However, in a very high inductive system, the
arrester might not be capable of absorbing such amounts of energy repetitively. If this energy was
excessive, it might cause permanent damage or even destruction of associated devices (S2, MOV,
capacitor, etc.). Accordingly, the whole breaker would not interrupt the current and it would lose its
ability to function repetitively.
For the sake of clarity, the following analysis does not include circuit resistance. Furthermore, the
line inductance on the source side LTwas considerably larger than in the commutation coil LC. The
energy required for a counter-current injection depended on the capacitance value and the initial
voltage (W C VCO C CO= 1 22). Such energy had to be prepared and maintained permanently. The larger
currents had to be interrupted so that more energy was needed. Charging energy for the capacitor
could be supplied by the main voltage system itself or by means of an external supply.
In an oscillatory circuit without damping, the maximum counter-current injection could be
determined roughly by the equation (2.1) :
i VC
LC CO
C
C
= . (2.1)
Obviously, a high initial voltage would result in a high initial rate of change of the counter-current.
A rough expression for this slope of the current is di dt V LC CO C max = . The following initial
conditions apply; S1 is closed, S2 is open, v t VC t CO = =0 and the circuit current could be consideredto increase linearly. Assuming, that the current in the source iS reached the trip value, then S2
-
5/25/2018 Direct Current Hybrid Breakers
36/195
24 Chapter 2
closed and initiated a counter-current iC. This counter-current can be represented linearly, see
Figure 2.3(b), so that i t tV LC CO C = and the capacitor voltage can be written as :
v tC
i d Vt
L CV VC
C
C
t
CO
C C
CO CO = + +1 20
2
At time t2 , current in the breaker becomes zero; which can be defined as current-zero time tz
i t i t i t B z S z C z = . This current will be i t i t V LC z z z CO C = = and the capacitor voltagechanges to v t t V L C V C z z CO C C CO = +2 2 . Subsequently, current from the source will follow thecommutation path, see Figure 2.1. This current obeys the following differential equation:
E v t L Ldi
dtv tS C z T C
CC+ = + + (2.2)
with the initial current i t iC z z = .The solution of this differential equation is :
i tE v t
L Lt t i t t C
S C z
o T C
o z z o z =
+
+
+
sin cos (2.3)
where : oT C CL L C
=+
1
.
Introducing a new parameter :
tan
=
+
+=
+
i L L
E v t
i
C E v t
z o T C
S C z
z
o C S C z
(2.4)
and using the trigonometric equivalent, the capacitor current from equation (2.3) can be rewritten
as:
i tE v t
L Lt t
C E v t t t
C
S C z
o T C
o z
o C S C z
o z
= +
+
+
=+
+
cossin
cossin
(2.5)
By integrating this current, the capacitor voltage becomes : v t
C
i d KCC
C
t
t
z
= +
1
and substituting : t tz= , the integration constant can be found : K ES= .
The capacitor voltage is governed by :
v tE v t
t t ECS C z
o z S =
+
+ cos
cos
(2.6)
The maximum current of the capacitor obtained from equation (2.5) at tx occurs when :
sin o x z o
t t + =
1, so that i
C E v t
C
o C S C z
omax
max
cos=
+
.
From equation (2.4), the maximum current iz max can be defined as :
-
5/25/2018 Direct Current Hybrid Breakers
37/195
Analysis of commutating circuits for hybrid breakers 25
tan max
max
oz
o C S C z
i
C E v t =
+ (2.7)
so that :
t t
i
C E v t x z o
z
o C S C z= + +
1
2
arctanmax
max (2.8)
Further, from the trigonometry, we can define oz
C
i
i=
arcsin max
max
or sin max
max
oz
C
i
i= .
The time when the capacitor voltage is zero at the instant when v tC y = 0, can be derived from
equation (2.6), namely coscos
o y zS
S C z
t tE
E v t + =
+
so that :
tE
E v tty
o
S
S C z
z=+
+1
arccos cos
(2.9)
The current becomes zero when i tC int = 0. The time tint is called the total interrupting time and it iswritten as :
t
i
C E v t t
z
o C S C z
o
zint
arctan
=
+
+
(2.10)
From equation (2.7) :
oz
o C S C z
i
C E v t =
+max
maxtan .
Substituting this into equation (2.9) and extracting CC, gives :
Ci
E v tE
E v t
t tCz
o S C zS o
S C z
o
y z=
++
max
maxtan arccoscos
(2.11)
By definition : L L L CL T C
o C= + =
12
, therefore : L
C E v t
iL
o C S C z
z=
+tan max
max
2
After substituting (2.11) and performing algebraic manipulation, this becomes :
LE v t t t
iE
E v t
L
o S C z y z
zS o
S C z
o
=+
+
tan
arccoscos
max
max
(2.12)
To make the expressions (2.11) and (2.12) appropriate, it is necessary to define three new terms:
Ci t
v tt tCo
C z
C z
y z= max
max
, Lv t
i tt tLo
C z
C z
y z= max
max
and parameter kv t
E
C z
S
= max
.
A per unit basic expression can be obtained by simplifying the above ratio as :
-
5/25/2018 Direct Current Hybrid Breakers
38/195
26 Chapter 2
C
C
k
E
E v t
C
Co
oS o
S C z
o
=
+
+
1
11
tan arccoscos
(2.13)
and
L
L
k
E
E v t
L
Lo
o
S o
S C z
o
=
+
+
tan
arccoscos
1 1
(2.14)
The graphs in Figure 2.4 represent equations (2.13) and (2.14) for two different k values. The
horizontal axis represents the term sin o from equation (2.7).
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.91
2
3
4
5
6
7
8
9
10
izmax
icmax
____
CC
CCo
____
k=1
k=4
(a)
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.90
2
4
6
8
10
12
14
16
18
20
izmax
icmax
____
LL
LLo
____
k=1k=4
(b)
Figure 2. 4 (a) The unit base of the capacitor and (b) The unit base of the circuit inductance.
Next, in order to make the circuit analysis more realistic, circuit resistance had to be included in the
analytical solution. Figure 2.5 presents the extended circuit to show the interrupting sequences.
Additionally, discharged energy stored in the commutation capacitor can be taken into account by
extending an energy absorbing circuit across the capacitor. The energy absorbing circuit (LA, and
RA) played a part only after the capacitors polarity changed, so that in the idling (waiting) state, thepre-charged capacitor had to retained its stored energy continuously. Therefore a reverse biased
diode D1was required. The following new symbols are introduced now : the MS-make switch and
the Thy-thyristor as an auxiliary switch. When considering ideal DC systems, the following
assumptions can be made :
-
5/25/2018 Direct Current Hybrid Breakers
39/195
Analysis of commutating circuits for hybrid breakers 27
the DC voltage source ESis constant in time and the internal resistance is negligible;
switches are ideal (no voltage drop or heat loss) and they introduce no transients duringswitching;
the lines and devices have linear characteristics without limitation for the rate of change ofcurrent and voltage.
Therefore, the interruption process could be separated into intervals in which each interval
represents a linear differential equation. In this way, each differential equation could be solved
successively to give analytical solutions.
+
MS
S1-
Thy
LA
RA
D1
+
-
MS
AB
+
MS
-
Thy
C
+
MS
-
Thy
D
+
MS
-
Thy
E
+
MS
-
RA
LA
D1
ES
ES
ESES
ESES
RS LS
RS LSRS LS
RS LS
RS LS RS LS
CC
LC,RC
CC
CC CC
LC,RC
LC,RC
vCS1 S1
Figure 2. 5The sequence of the one-stage interruption; MS: make switch, S1: main breaker.
By solving the differential equations that corresponded to each interval, the analytical solution was
obtained, where the end state of the previous interval was introduced as the initial state of the
following interval.
A The first interval0 1 t t
In this interval, when make switch MS was closed, the current can be expressed by the differential
equation :
Ldi t
dt
R i t v tSS
S S S
+ = , (2.15)
Generally, before a fault occurred, the rated current IR flowed, so that the initial condition becomes:
i t IS t R = =0 otherwise i tS t = =0 0.
The source is defined as a constant voltage source: v t ES S = for all values of t . The source currentiScan be solved from the expression:
i t I I e I S R
t
R( )=
+
1 (2.16)
where: is the time constant ( =L
RS
S), LSand RSare the inductance and the resistance at the fault
location relative to the source; I is the steady-state fault current (prospective) determined only
-
5/25/2018 Direct Current Hybrid Breakers
40/195
28 Chapter 2
from the resistance and DC voltage system, (IE
R
S
S
= ). For convenience, it is assumed that IR is
zero. In the commutation path, the capacitor voltage and its current are constants
v t v t V C C CO( ) ( )= =1 and i tC( )= 0 . Initially, the current in the breaker was equal to the current in the
source until the commutation process occurred during the next interval i t i t B S( ) ( )= . At the end ofthe first interval, the source current becomes i t IS t( )1 1
= (where a counter-current injection would
be performed).
B The second intervalt t t1 2
The counter-current iCwas injected during the second interval in which the current in the main
b