differential-protection.ppt
DESCRIPTION
DIFFERENTIAL-PROTECTIONTRANSCRIPT
DIFFERENTIAL RELAY
- SHOULD TRIP INSTANTANEOUSLYFOR AN INTERNAL FAULT
- SHOULD NOT TRIP FOR AN EXTERNAL FAULT
- NORMAL SETTINGS FORDIFFERENTIAL PICK UP = 15%
INTERNAL / EXTERNAL FAULTS
I1 I2 Id
100 100 0 NORMAL LOAD
500 500 0 THROUGH FAULT (500%)
500 300 200 INTERNAL FAULT (200%)
100 80 20 INTERNAL FAULT (20%)
NOTE :1. THROUGH FAULT CONDITION HAS TO BE DETECTED BY
NORMAL O/C RELAY (SINCE FAULT CURRENT IS HIGHER THAN 100%)
2. INTERNAL FAULT HAS TO BE CLEARED BY DIFFERENTIALRELAY - SINCE FAULT CURRENT IS LESS THAN FULL LOAD,NORMAL O/C RELAY WILL NOT PICK UP
MOTTO OF A DIFFERENTIAL RELAY
SHOULD OPARATE FORINTERNAL FAULT
SHOULD NOT OPERATEFOR EXTERNAL FAULT
SATABILITY OF DIFFERENTIAL RELAY
CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY
I1 - I2 RELAY OPERATINGCURRENT
TRIP IN TERMS OF SETTING CT PRIMARY
(20% OF In)
RELAY WILL TRIP IF I1-I2 IS GREATER THAN 20% 0F In(In = RATING OF CT PRIMARY)
CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY
Id
Is =20%
Average current Ir /In =((I1 +I2)/2)/In
0.5 1.51.0 2.52.0
RELAY TRIP AREA
CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY
DISADVANTAGES :
DUE TO CT CHARACTERISTICS MISMATCH,RELAY CAN DETECT A CONDITION WHEREI1-I2 EXCEEDS SET VALUE
A) UNDER NORMAL OPERATRING CONDITIONS B) UNDER THROUGH FAULT CONDITIONSC) WHENEVER THE TAPS ARE CHANGED IN
TRANSFORMERS
THIS IS MAINLY DUE TO :DC OFFSET EFFECT AND ASSYMMETRIC CT RESPONSE UNDER LARGE THROUGH FAULT CURRENTS.
CIRCULATING CURRENT(HIGH IMPEDENCE) DIFFERANTIAL RELAY
ADD A STABILISING RESISTORTO IMPROVEPERFORMANCE
CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY
STABILISING RESISTOR
WILL IMPROVE PERFORMANCE OF RELAYFOR CT CHARACTERISTICS MISMATCH - TO CERTAIN LIMITS
BUT RELAY HAS BECOME INSENSITIVE DUE TO ADDITION OF RESISTOR.RELAY MAY NOT TRIP FOR A REAL INTERNAL FAULT.
FOR TOTAL IMPROVEMENT USE PERCENTAGE BIASED RELAY
BIASED DIFFERENTIAL
I1 - I2 RELAY OPERATINGCURRENT
(I1+I2)/2 RELAY RESTRAINING CURRENT
TRIP SETTING = (I1- I2)
(I1 +I2)/2(BIAS %)
NORMALLY BIAS % = 20%
RELAY WILL TRIP WHEN (2*(I1 - I2)/(I1+I2))*100VALUE EXCEEDS TRIP SETTING
PERCENTAGE BASED DIFFERENTIAL RELAY BIASE CHARECTERSTICS
I1+I2 2
%Id
( I1-I2)
RELAY NOT TO OPERATE
RELAY OPERATES
SUM CURRENT
DIFFERENCE CURRENT
MIN I1-I2SLOPE
DUAL SLOPE ?
DIFFERENTIAL RELAYS
INTERPOSING CTs
IN TRANSFORMER DIFFERENTIAL RELAYSFOLOWING COMPENSATIONS WILL BE REQUIRED FOR:
A) PROVIDING MAGNITUDE COMPENSATION
B) PHASE ANGLE COMPENSATION DUETO VECTOR GROUP SHIFT BETWEEN Py & Sy
DIFFERENTIAL RELAYS
INTERPOSING CTs
INELECTROMECHANICAL / SOLIDSTATE RELAYSINTERPOSING CTs ARE USED FOR PROVIDING THE MAGNITUDE AND VECTOR COMPENSATION
IN NUMERICAL RELAYS THE SOFTWARE INSIDE INSIDE THE RELAY TAKES CARE OF THESECOMPENSATION
RESTRAINTS IN DIFFERENTIAL RELAYS
2ND HARMONIC RESTRAINT
WHEN A TRANSFORMER IS SWITCHED ON,THE DIFFERENTIAL RELAY MAY SENSE A DIFFERENTIAL CURRENT AND INITIATE TRIP.
THIS IS DUE TO THE MAGNETISING CURRENTINRUSH ON ONE SIDE OF THE TRANSFORMER.THIS WILL RESULT IN A LARGE VALUE OFI1-I2 FOR ABOUT 4 OR 5 CYCLES.
RELAY IS RESTRAINED FROM OPERATION AT THE TIME OF SWTICH ON BY THE 2ND HARMONIC RESTRAINT FEATURE.
RESTRAINTS IN DIFFERENTIAL RELAYS
5TH HARMONIC RESTRAINT
WHEN OVER FLUXING OCCURS IN A TRANSFORMERTHE DIFFERENTIAL RELAY MAY SENSE A DIFFERENTIAL CURRENT AND INITIATE TRIP.
THIS IS DUE TO THE HIGH LEVEL OF FLUXPRESENT IN THE CORE CAUSING AN ARTIFICIALI1-I2 FOR A SHORT TIME.
RELAY IS RESTRAINED FROM OPERATION AT THE TIME OF OVER FLUXING BY THE 5TH HARMONIC RESTRAINT FEATURE.