differential pressure and flow meters accessories for ...samson-automation.info/pdf/t95550en.pdf ·...

12
Differential Pressure and Flow Meters Accessories for Media Series Associated Information Sheet T 9500 EN Edition June 2007 Data Sheet T 9555 EN Selection and application Use these accessories to supplement the devices of the Media Series and customize them to the plant depending on the specific application. The following pages contain exact descriptions of all accessories with order numbers. Contents Page 7 Range springs 8 8 Electric pressure sensor CTMd(r) for direct attachment 8 9 Power supply and indicator unit with limit switches 9 10 Media Tank Management 10 11 TROVIS-VIEW configuration software Connecting cable · Memory pen · Modular adapter 12 Media 5 Media 05 Media 4 Media 6 9 6 3 4 5 7 8 1 10 2 11 Contents Page 1 Valve block with shut-off valves and test connection 3 2 Pressure gauge for valve block 4 3 Pipe fittings · Screw joint/cap kits 5 4 Equalizing tanks · Shut-off valves 6 5 Mounting material for wall and pipe mounting 6 6 Limit switches · Analyzing instruments for limit switches 7

Upload: dothuan

Post on 28-Jan-2019

241 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

Differential Pressure and Flow Meters

Accessories for Media Series

Associated Information Sheet T 9500 EN Edition June 2007

Data Sheet T 9555 EN

Selection and applicationUse these accessories to supplement the devices of the Media Series and customize them to the plant depending on the specificapplication. The following pages contain exact descriptions of all accessories with order numbers.

Contents Page

7 Range springs 88 Electric pressure sensor CTMd(r) for direct attachment 89 Power supply and indicator unit with limit switches 9

10 Media Tank Management 1011 TROVIS-VIEW configuration software

Connecting cable · Memory pen · Modular adapter 12

Media 5Media 05

Media 4

Media 6

9

6

34

5

78

1

10

2

11

Contents Page

1 Valve block with shut-off valves and test connection 32 Pressure gauge for valve block 43 Pipe fittings · Screw joint/cap kits 54 Equalizing tanks · Shut-off valves 65 Mounting material for wall and pipe mounting 66 Limit switches · Analyzing instruments for limit switches 7

Page 2: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

Media Series · Mechanical and electric accessories

2 T 9555 EN

Fig. 1.1 · Overview, mechanical and electric accessories

Valve block withshut-off valves andtest connection

Equalizing tank;shut-off valve

Isolating switchamplifier, e.g.KFA6-SR2-Ex2.W

Power supply and indicatorunit, e.g. Type 5024-1

Electric pressure sensorCTMd(r) for direct attachmentwith screw joint for mounting

Screw joints forattachment ofMedia 4/05/5to Media 6

Media 5

Media 05

Media 4

Media 6/Media 6 Z

Mounting material

Screw glands for attachmentto valve block

Switch modules for2 or 3 SJ-3.5N-LED orSB-3.5-E2-LEDinductive limit switches

Switch module for 1 or 2SJ2-SN inductive limitswitches

Pipe fittings

Pressure gauge

Screw joint/cap kit

Range springs

Page 3: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

117 30

Ø9

847

59

31 26

60

97 35

max. 160

25G½

Fig. 1.3 · Dimensions, valve block with G ½ and G ¼ pressure gauge connection

Coupling nut

Bore holes for wallmounting of valve block

Screw gland G 3/8 AOnly required for attachment toMedia 4 devices

Adjustment;lead-sealable

Coupling sleeve G ½ DIN 16283(part of valve block) for connectionof a pressure gauge NG 100

1 Valve block with shut-off valves and test connection

3 T 9555 EN

For direct attachment to devices of the Media 05/5 and Media 6 Series · Screw glands to attach devices of the Media 4 SeriesShut-off valves for (+/–) process lines and pressure balancing · Lead-sealing bore holes for pressure balancing and shut-off valvesPressure gauge connection G ½ and G ¼ for pressure gauge of operating pressure NG 100 and NG 63 · Process connection G 3/8 ·Screw cap for test connection according to DIN 16287, version C made of CrNi steel · PN 50

Table1.1 · Technical data and materials

Valve block Free of oil and grease for oxygen

Max. temperature range 1) –40 to +80 °C

Max. permissible pressure 50 bar

Materials

Body Brass CrNi steel

Spindle, complete Brass · CrNi steel · Silicone CrNi steel · Silicone

Screw gland 2) Brass CrNi steel

Coupling nut 2) CrNi steel

Seal O-ring NBR

Weight, approx. 2 kg 2.5 kg

1) When mounted on Media device · For oxygen service: –40 to +60 °C2) Not required for Media 05/5 and Media 6

Fig. 1.2 · Valve block for Media 05/5/6

Table 1.2 · Order numbers

For device ... Media 05/5 andMedia 6

Media 04/4/4K andType 5014

Application Material Order no.

Standard/oxygen industry

BrassCrNi steel

1400-70771400-7078

1400-70791400-7080

Tobacco industry/ 1)

compatible with paint Brass 1400-7726 –

Food processingversion 2)

BrassCrNi steel

1400-73961400-7397

––

1) In combination with a Media device: –20 to +80 °C2) In combination with a Media device: –25 to +80 °C

Combined connectionG ½-LH with coupling sleeveG ½ for pressure gaugeNG 100 and O-ring 12x2 aswell as for G ¼ for pressuregauge NG 63 with G ¼ seal

Page 4: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

2 Pressure gauge for valve block

4 T 9555 EN

Table 2.2 · Order numbersPressure gauge NG 63 · With Ex vent plug · Free of oil and grease for oxygen

Nominal pressure PN 2.5 PN 4 PN 6 PN 10 PN 16 PN 25 PN 40 PN 60

Orderno.

SS/Brass · EN 837-2 S1 8520-1099 8520-1093 8520-1094 8520-1095 8520-1096 8520-1097 8520-1098 –

SS/SS · EN 837-2 S1 – 8520-1110 8520-1111 8520-1112 8520-1113 8520-1114 8520-1115 –

Pressure gauge NG 100 · Free of oil and grease for oxygen

Nominal pressure PN 2.5 PN 4 PN 6 PN 10 PN 16 PN 25 PN 40 PN 60

Orderno.

SS/Brass · EN 837-2 S1 – 8520-1266 8520-1261 8520-1262 8520-1263 8520-1264 8520-1265 8520-1267

SS/SS · EN 837-2 S3 – 8520-1320 – – 8520-1323 8520-1324 8520-1325 –

SS/SS · EN 837-S1 8520-1271 8520-1269 – 8250-1270 – – – 8520-1272

Additional versions on request

Pressure gauge NG 100 with limit switch(es)

Pressure gauge withlimit switch(es)

Function MaterialsBody/Internal parts

Order no.

Safety class S1 (plug) 25 bar1 solenoid snap-action contact 812.2

Contact opens whenactual value > set point

Stainless steel/Stainless steelDIN EN 837 8520-1291

Safety class S1 (plug) 40 bar1 solenoid snap-action contact M2

Contact opens whenactual value > set point

Stainless steel/BrassDIN EN 837 8520-1284

Safety class S1 (plug) 25 bar2 solenoid snap-action contacts M22

Contact opens whenactual value > set point

Stainless steel/BrassDIN EN 837 8520-1279

Pressure gauge NG 63/NG 100

Table 2.1 · Technical data and materialsPressure gauge NG 63 · NG 100

Safety class S1 (EN 837-2) S3 (EN 837-2)

Safety With Ex vent plug With solid baffle walland blowout rear panel

Pressure range Between 0 to 4 bar and 0 to 40 bar

Version for oxygen Free of oil and grease

Limit switches Max. 2

Connection

NG 100 G ½ B rear side

NG 63 G ¼ B rear side –

Materials

Body CrNi steel

Wetted components Brass or CrNi steel

Fig. 2.2 · Dimensions, pressure gauges NG 63 and NG 100

97

55

SW17

30

520

G1/

2 A

Ø6 Ø

101

Pressure gauge NG 100,safety class S1

92

60

SW22

34

3 20

G1/

2 A

Ø6 Ø

101

Pressure gauge NG 100,safety class S3

58

36

SW14

18

2 13

G1/

4 B

Ø5

Ø64

Pressure gauge NG 63,safety class S1

Fig. 2.1 · Pressure gauge NG 100

Page 5: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

3 Pipe fittings · Screw joint/cap kits

Pipe fittings with restriction · Used to dampen vibrations of the process medium in the measuring line with integrated restriction(especially for gas flow measurement) · Compression-type fittings G 3/8 · Used to connect the differential pressure lines with outerpipe diameters 6, 8, 10 and 12 mm · Screw joints G 3/8 · Used to close the dp-cell · Vent screws G 3/8 · Used to vent the dp-cell ·Additional screw joints · Screw joints for attachment of Media 4/05/5 to Media 6 · Special screw joints

5 T 9555 EN

Table 3.1 · Materials · Order numbers

Tube fittings, vent plugs, screw plugs, etc.Order no.

Standard Free of oil and grease for 02

Compression-type fitting G 3/8 for outer pipe Ø 12 mm, steel 1400-5842 –

Compression-type fitting G 3/8 for outer pipe Ø 12 mm, CrNi steel 1400-5844 1400-5845

Compression-type fitting G 3/8 for outer pipe Ø 10 mm, steel 1400-5846 –

Compression-type fitting G 3/8 for outer pipe Ø 8 mm, steel 1400-5860 –

Vent plug brass, including flat gasket, copper 1400-5654 1400-5658

Screw plug ,brass including flat gasket, copper 1400-5655 1400-5659

4 flat gaskets, copper 1400-5660 1400-5661

2 O-rings 18 x 2.5, NBR (dp-cell connection) – 1400-9477

2 screw plugs G 3/8 brass, including 2 NBR O-rings 1400-7643 –

Screw joint for attachment of Media 4/05/5 to Media 6, brass – 1400-7748

Screw joint for attachment of Media 4/05/5 to Media 6, stainless steel – 1400-7762

Screw joint for attachment of valve block to Media 4, brass – 1400-7478

Screw joint for attachment of valve block to Media 4, stainless steel – 1400-7479

Cap G ½ LH for valve block’s pressure gauge connection, brass – 1400-7873

Cap G ½ LH for valve block’s pressure gauge connection, stainless steel – 1400-7874

2 screw joints G ½ to G 3/8 stainl. steel, incl. O-rings (WIKA conversion kit) – 1400-7749

Special screw joints in st. steel, free of oil and grease for oxygen, with restriction of brass (CW617N), restriction bore Ø 0.5 mm

Straight screw joints G 3/8 For pipe Ø in mm Order no.

Ermeto 6 1400-9108

Ermeto 8 1400-9109

Swagelok 8 1400-9110

Ermeto 10 1400-9111

DIN 2553 12 1400-9112

Screw joint/cap kits, for attachment to dp-cell and valve block · Free of oil and grease for oxygen · Additional kits on request

Table 3.2 · Materials · Order numbers

Attachment to dp-cell Attachment to valve block Order no.

2 hexagonal caps, brass · 2 O-rings NBR 2 screw joints 8 mm, stainless steel 1400-8823

1 hexagonal cap, brass · 1 O-ring NBR1 screw joint 8 mm, stainl. steel (high-pressure connection) 2 screw joints 10 mm, stainless steel 1400-8824

2 hexagonal caps G 3/8, brass · 2 O-rings NBR – 1400-7644

2 hexagonal caps G 3/8, stainless steel – 1400-7872

Fig. 3.1 · Screw joints

Tube fittingswith/without restriction

Screw plugs;screw joint/cap kits

Screw joints for attachment ofMedia 4/05/5 to Media 6

Screw joints for attachment ofvalve block to Media 4

Page 6: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

4 Equalizing tanks · Shut-off valves

Equalizing tanks · Used to build a liquid column above the measuring unit (compulsory for steam measurement) · If arrangement ofscrew joints is changed, the device can also be used as separation chamber for gas measurement

Shut-off valves · High-pressure valves used to shut off the differential pressure line downstream of the point of measurement · Attach-ment via 12 mm compression-type fitting

5 Mounting material for wall and pipe mounting

Mounting material for all devices of the Media SeriesPipe clips for 2-inch pipe mounting or holding brackets for wallmounting

6 T 9555 EN

Table 4.1 · Technical data and materials · Material numbers according to DIN EN

Shut-off valves ·Equalizing tanks

Shut-off valves Equalizing tanks 1)

Type A Type B Type A Type 3994-9002

Max. perm. operating overpressure 400 bar 40 bar 35 bar 20 bar 113 bar 105 bar 93 bar

Max. perm. temperature 2) 120 °C 120 °C 250 °C 400 °C 120 °C 250 °C 400 °C

Weight 0.4 kg 0.5 kg 0.9 kg 1.25 kg

Materials

Body C22 1.4571 1.0037 (St 37-2) 1.4571

Spindle 1.4571 – –1) For gas measurement: if arrangement of screw joints is changed, device can also be used as equalizing tank2) Max. permissible temperature according to DIN EN 837-1; shut-off valves and pressure measuring devices must be protected against a temperature increase due to

hot process media through measuring lines or siphons of appropriate length

Ø60

88

1186

Fig. 4.2 · Dimensions, equalizing tanks and high-pressure valve

35˚

35˚

155

105

Ø13

0

Type A Equalizing tank Type 3994-9002 Equalizing tank Type A/B High-pressure shut-off valve

35˚

35˚

Ø89

110

Pipe Ø 12 mm

Table 4.2 · Order numbers

Type Connection Order no.

Equalizing tank, Type ACompression-type fitting

G 3/8for pipe Ø 12 mm

1080-0261

Equalizing tank, Type 3994-9002 3994-9002

High-pressure shut-off valve, A 1000017

High-pressure shut-off valve, B 1000016

Fig. 5.1 · Mounting material

Fig. 4.1 · High-pressure shut-off valveand equalizing tank

Table 5.1 · Order numbers

Mounting material Order no.

Mounting material for 2-inch pipe mounting 1400-5656

Mounting material for wall mounting 1400-5657

Page 7: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

6 Limit switches · Analyzing instruments for limit switches

7 T 9555 EN

Table 6.1 · Retrofit switch module for Media 5/05 · Order numbers

Retrofit switch module Function Order no. · Image

Media 5

2 inductive limit switches, Type SJ3.5N-LED, acc. to ATEX 2 universal adjustable contacts 1400-8839

3 inductive limit switches, Type SJ3.5N-LED, acc. to ATEX 2 min. and 1 max. contacts 1400-8840

2 inductive limit switches, Type SB3.5-E2-LED, not expl. prot. 1) 2 universal adjustable contacts 1400-7808

Media 05

1 inductive limit switch, Type SJ2-SN, acc. to ATEX 1 min. contact 1400-9241

2 inductive limit switches, Type SJ2-SN, acc. to ATEX 2 min. contacts 1400-9242

2 inductive limit switches, Type SJ2-SN, acc. to ATEX 1 min. and 1 max. contacts 1400-92431) Three-wire version, 10 to 30 V DC, controllable without isolating switch amplifier

FunctionMin. contact: metal tag moves in when reading decreases · Max. contact: metal tag moves in when reading increasesMetal tag inside pick-up field: switching signal “OFF” (0 signal of the proximity switch) - contact opened or output effectively non-conducting -proximity switch highly resistive (dampened), power consumption ≤ 1 mAMetal tag outside pick-up field: switching signal “ON” (L signal of the proximity switch) - contact closed or output effectively conducting - proximityswitch lowly resistive, power consumption ≥ 3 mA

Analyzing instruments for limit switches

Isolating switch amplifier, system KThese isolating switch amplifiers transmit the digital signals of the limit switches (alarm contacts).

Table 6.2 · Technical data

Type KFD2-SR2-Ex... KFA5-SR2-Ex... KFA6-SR2-Ex...

Mains voltage 20 to 30 V DC 103.5 to 126 V AC 207 to 253 V AC

Nominal data according to DIN 19234 or NAMUR

Open circuit voltage/short circuit flux Approx. 8 V DC / approx. 8 mA

Switch point/differential gap 1.2 to 2.1 mA / approx. 0.2 mA

Input pulse length/input pulse interval ≥ 20 ms / ≥ 20 ms

Line monitor Rupture J ≤ 0.1 mA

Maximum value according to certificate of conformity PTB 00 ATEX 2081

Voltage Uo 10.5 V 10.6 V

Current Io 13 mA 19 mA

Power Po 34 mW 51 mW

Fig. 6.1 · Isolating switch amplifier, system K

20 115

111 11

8

Table 6.3 · Order numbers

Type Version Order no.

KFA6-SR2-Ex1.W 1 channel 8812-0100

KFA6-SR2-Ex2.W 2 channels 8812-0103

KFA5-SR2-Ex1.W 1 channel 8812-0099

KFA5-SR2-Ex2.W 2 channels 8812-0102

KFD2-SR2-Ex1.W 1 channel 8812-0098

KFD2-SR2-Ex2.W 2 channels 8812-0101

In terminal box On request

In alarm system On request

Page 8: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

7 Range springs

When replacing range springs, observe themounting and operating instructions!

8 Electric pressure sensor CTMd(r) for direct attachment

8 T 9555 EN

Table 7.1 · Range springs for Media 4 Series · Free of oil andgrease · Span · Order numbers

Span dp-cell Order no.

40 to 60 mbar 1400-5871

60 to 100 mbar 1400-5872

100 to 160 mbar 1400-5873

160 to 250 mbar 1400-5874

250 to 400 mbar 1400-5875

400 to 600 mbar 1400-5876

250 to 400 mbar 1400-5879

400 to 600 mbar 1400-5880

600 to 1000 mbar 1400-5881

1000 to 1600 mbar 1400-5882

1600 to 2500 mbar 1600 to 2500 mbar 1400-5885

Discs for mounting of range springs 1400-5653

Table 8.1 · Technical data and materials · Free of oil and grease for oxygen

Pressure sensor CTMd(r) 1)

Supply voltage 24 V DC ±10%

Electrical connection according to DIN EN 175301-803 4-pin DIN connector

Output, optional2-wire version3-wire version 2)

4 to 20 mA0 to 20 mA or 0 to 10 V DC

Permissible temperature range –20 to +80 °C

Deviation from linearity < 1 % of the pressure measuring range

Hysteresis < 0.5 % of the pressure measuring range

Degree of protection (IEC 60529) IP 65

Connection sleeve G ½ B according to EN 837-1

Materials · Material numbers according to DIN EN

Housing 1.4305

Measuring element 1.4404

Seal NBR1) Other pressure sensors, see T 994-0050-3 EN or T 994-0050-6 EN · 2) On request

Table 8.2 · Order numbersPressure measuring range Order no.

0 to 4 bar 8523-0295

0 to 6 bar 8523-0296

0 to 10 bar 8523-0297

0 to 16 bar 8523-0298

0 to 25 bar 8523-0299

0 to 40 bar 8523-0300 Fig. 8.1 · Pressure sensor

CTMd(r) withoutscrew joint for mounting CTMd(r) screwed into the

dp-cell of a Media 6

Table 7.2 · Range springs for Media 05/5 · Free of oil andgrease · Span · Order numbers

Span Order no.

40 to 60 mbar 1400-7822

50 to 100 mbar 1400-7823

80 to 160 mbar 1400-7824

125 to 250 mbar 1400-7825

200 to 400 mbar 1400-7826

300 to 600 mbar 1400-7827

500 to 1000 mbar 1400-7828

800 to 1600 mbar 1400-7829

1250 to 2500 mbar 1400-7830

2000 to 3600 mbar 1400-7831

Clamp for mounting range springs 1180-9907

Fig. 7.1 · Range springs for Media 05/5

A spring set comprises sixrange springs

Note! The range springs of Media 6can only be changed at the factory.

40 to600 mbar

400 to1600 mbar

Page 9: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

Screw joint to attach pressure gauge with radial connectionand pressure sensor · Free of oil and grease for oxygen– Coupling sleeve G ½ (stainless steel)– O-ring 8 x 3 (NBR)– Screw joint G 3/8 x G ½ LH (stainless steel)

9 Power supply and indicator unit with limit switches

Type 5024-1 Power Supply and Indicator Unit · Used to supplyvoltage for Type 5014 Media 4 A 2-wire and Media 6

Apart from indicating the current measured values, two floatinglimit switches generate analog limit alarms if the measured val-ues are below/above the set values.

Table 9.1 · Technical data

9 T 9555 EN

Fig. 8.2 · Dimensions, pressure sensor

Fig. 9.1 · Type 5024-1 Power Supply and Indicator Unit

Fig. 8.3 · Screw joint for mounting with coupling sleeve

Table 8.3 · Screw joint for mounting, complete · Order numbersScrew joint for mounting Order no.

Coupling sleeve, O-ring, screw joint 1400-7642

Pressure sensor CTMD(r),mounted on low-pressureconnection of dp-cell

Ove

rall

heig

htaf

ter

mou

ntin

g~1

35m

m

Scre

wjo

intf

orm

ount

ing

7520

SW 24

G ½ B

Ø 6

Ø 27

Pressure sensor CTMd(r)

Type 5024-1 withdigital display andconnection for floatinglimit switches

Power Supply and Indicator Unit Type…for 2-wire circuit 4 to 20 mA 5024-1001 5024-1002 1) 5024-1003 1)

Power supply 230 V, 45 to 60 Hz 115 V, 45 to 60 Hz 24 V, 45 to 60 Hz

Power consumption Approx. 1.8 VA

Measuring circuit 4 to 20 mA

Transmitter supply 20 V at 20 mA

Output 2 floating limit switches, max. 250 V~/3 A

Switching cycles ≥ 10 6 at AC voltage and max. 300 Ω ohmic load

Perm. ambient temperature range 0 to 50 °C

Degree of protection IP 541) On request

Page 10: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

The device may be mounted on a panel or the wall eitherdirectly or using the included mounting bracket, nuts and bolts.

10 Media Tank Management

MTM 32 Media Tank Management System fromSAMSOMATIC Automationssysteme GmbH (a subsidiary ofSAMSON AG) has been especially designed for use with Me-dia 6 devices as liquid level sensors.

– MTM 32 hardwareand

– MTM 98 softwareThe signals, which are proportional to the content, of the Me-dia 6 transmitter are transferred via phone lines from the tankfarm to the control center and analyzed there.

10 T 9555 EN

Table 9.2 · Version · Order numbers

Type · Operating voltage Order no.

5024-1001 · 230 V AC 238 741

5024-1002 · 115 V AC 238 742

5024-1003 · 24 V AC 238 743Fig. 9.2 · Dimensions, Type 5024-1 Power Supply and Indicator

Unit

70 Pg 13.5 2256

120.

5

122.5110

12890

Fig. 10.1 · Media Tank Management System

Hardware for the tank management system is available as singlemodule or as readily configured module in a steel cabinet.

Table 10.1 · Technical data

MTM 32 Tank Management System

Supply voltageOperating voltage, internal

230 V AC, 50 to 60 Hz10 to 30 V DC

1 device interface RS-232

Degree of protectionin steel cabinet IP 54

Remote data transmission Analog, ISDN or GSM

Indicators and display LCDLED status indication

8 analog inputs 0 (4) to 20 mA

11 (max. 16) digital inputs 24 V DC

2 digital outputsmax. 16

24 V DC, max. 0.5 A24 V DC, max. 20 mA

Permissible ambienttemperature range –20 to +70 °C

Refer to the Data Sheet T-MTM 32 from SAMSOMATIC Automa-tionssysteme GmbH for more details

Operator interface for monitoring several storage tanks (alarmfunctions); visualized by the MTM 98 software

MTM 32 hardware in a steel cabinet with power supply unit,heating, and ready-to-connect wiring for four Media 6 devices

Page 11: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

Remote tank monitoring and data transmission · Overview

11 T 9555 EN

Fig. 10.2 · Overview, remote tank monitoring system and data transmission

Memory pen with modular adapter

or

PC

Notebook

Media 6

MTM 32 Media TankManagement System

Memory pen

Type 5024-1 PowerSupply and Indicator Unit

Phone line

Cable

PC withMTM 98 software

Remote tank monitoring system

Data transmission

RJ-12 jack

TROVIS-VIEWconfiguration software

OptionallyCOM 1...255interface

Page 12: Differential Pressure and Flow Meters Accessories for ...samson-automation.info/pdf/t95550en.pdf · Differential Pressure and Flow Meters Accessories for Media Series Associated Information

11 TROVIS-VIEW configuration software · Connecting cable · Memory pen · Modular adapter

TROVIS-VIEW 6661 configuration softwareThe Media 6 Digital Transmitter can be operated over aPC/notebook computer using the TROVIS-VIEW Configurationand Operator Interface.

The operator interface contains all functions of Media 6, to-gether with the required information. The system can be config-ured and operated entirely over a PC/notebook.

Media 6 needs to be connected to the serial interface at COM 1to 225 of the PC/notebook with an appropriate connecting ca-ble.

The software for installation of the TROVIS-VIEW 6661 Config-uration and Operator Interface is available from SAMSON onCD-ROM (see ordering information in Table 11.1).

Connecting cable (PC/notebook computer <> Media 6)To enable communication between PC/notebook and Media 6,the serial interface (COM 1 to 225) of the PC/notebook needsto be connected to the serial interface of Media 6. The appro-priate connecting cable (see ordering information inTable 11.1) is available from SAMSON.

Memory penThe memory pen is a small, handy storage medium. Independ-ently of the PC/notebook, data (e.g. tank type and associatedgas data) can be saved on site and transmitted to Media 6 overthe RS-232 interface (see ordering information in Table 11.1).A connection between PC/notebook and Media 6 is not re-quired.

Modular adapterConfiguration data are transmitted between PC/notebook andmemory pen over the SAMSON modular adapter (see orderinginformation in Table 11.1).

USB/RS-232 adapterIf the PC does not have a COM port, a USB/RS-232 adapter(order no. 8812-0016), as shown in Fig. 11.1, can be usedwith Windows operating systems 98, ME, 2000, XP.

Specifications subject to change without notice.

SAMSON AG · MESS- UND REGELTECHNIKWeismüllerstraße 3 · 60314 Frankfurt am Main · GermanyPhone: +49 69 4009-0 · Fax: +49 69 4009-1507Internet: http://www.samson.de T 9555 EN

Table 11.1 · Order numbers

Ordering text · Product Order no.

1 CD-ROM TROVIS-VIEW 6661Configuration and Operator Inter-face with Media 6 database moduleand SSP-DDE communication server

1043723

1 hardware package (1x memorypen, 1x modular adapter,1x connecting cable)

1400-7704

1 memory pen 1400-7697

USB/RS-232 adapter 8812-0016

Fig. 11.1 · Connecting cable, memory pen, modular adapterand USB/RS-232 adapter

Connecting cable

Memory pen

Modular adapter

USB/RS-232 adapter

USB RS-232