detail booklet stotherm ci · 2020. 9. 14. · stotherm® ci termination at grade - sheathing flush...

49
Detail Booklet StoTherm ® ci Series 52s.xx Steel Frame Construction December 2018 ® ATTENTION Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com. www.stocorp.com Property of Sto Corp. All Rights Reserved. 3800 Camp Creek Pkwy. SW Bldg. 1400 • Suite 120 Atlanta, GA 30331 Tel: (800) 221-2397 Fax: (404) 346-3119 helpdesk.stocorp.com Sto Corp.

Upload: others

Post on 19-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

Detail Booklet StoTherm® ciSeries 52s.xxSteel Frame Construction December 2018

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.comProperty of Sto Corp.All Rights Reserved.

3800 Camp Creek Pkwy. SWBldg. 1400 • Suite 120Atlanta, GA 30331Tel: (800) 221-2397Fax: (404) 346-3119helpdesk.stocorp.com

Sto Corp.

Page 2: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSystem Components

Detail No.: 52s.00 Date: December 2018

Notes:

1. StoTherm ci SystemComponents:

- StoGuard Air andMoisture Barrier

- Sto Adhesive- Sto EPS Insulation Board- Sto Mesh- Sto Primer (optional)- Sto Base Coat- Sto Finish

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Sheathing

Sto EPS Insulation Board

Sto MeshSto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Page 3: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSystem Components: Ultra-High Impact Resistance

Detail No.: 52s.01 Date: December 2018

®

Notes:

1.StoTherm ci SystemComponents:- StoGuard air and Moisture

Barrier- Sto Adhesive- Sto EPS Insulation Board- Sto Armor Mat XX- Sto Mesh- Sto Primer (optional)- Sto Base Coat- Sto Finish

2. Ultra-high impactresistance recommended atall ground floors to aminimum height of 6'-0"(1.8 m) above finished gradeand other areas accessible topedestrian traffic, abnormalstress or impact.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

Sto Materials:

1.Sample Text

1.Sample Notes

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

(with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Sheathing

Sto EPS Insulation Board

Sto MeshSto Base Coat

Sto Base Coat (with Sto Armor Mat Embedded)

Page 4: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

®

Notes:

1.StoTherm ci Components:- StoGuard Air and Moisture

Barrier- Sto Adhesive- Sto EPS ProD or Sto GPS

ProD Insulation Board- Sto Base Coat embedded

with Sto Mesh- Sto Armat Classic Plus

Fortification Layer embeddedwith Sto Mesh- Sto Finish

2. Sto Armat Classic PlusFortification Layer improves theimpact resistance of the entirecladding assembly from bluntimpact and from repetitive andconcentrated impacts (e.g. birdstrikes)

- Refer to StoTherm ci SystemBulletins and Specifications, StoProduct Bulletins, Tech Hotlines,and Sto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified as Stoare furnished by othermanufacturers and are notnecessarily installed by trades whoinstall the Sto products. Refer toproject specific contract documents.

Sto Materials:

1.Sample Text

1.Sample Notes

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoTherm® ci with Sto IMPACTSystem Components

Detail No.: 52s.02 Date: December 2018

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Sto Armat Classic Plus Fortification Layer with Sto Mesh(See Note #2)

Sto Finish

Sto Adhesive

Sheathing

Sto EPS ProD or Sto GPS ProD Insulation Board

Sto Base Coat with Sto Mesh (embedded)

Page 5: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciTermination at Grade - Sheathing Flush with Foundation or Slab Edge

Detail No.: 52s.03A Date: December 2018

®

Notes:

1. Terminate systemminimum 6" (15.2 cm)above finished grade, higherfor areas with heavy snowaccumulations, or whererequired by code.

2. Ultra-high impactresistance recommended atall ground floors to aminimum height of 6'-0"(1.8 m) above finished gradeand other areas accessible topedestrian traffic, abnormalstress or impact.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Sto AdhesiveSheathing

Sto EPSInsulation Board, Pre- Wrapped

Sto Mesh

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (Protect with StoCoat Acryl Plus or Flashing)

StoGuard® Air and Moisture Barrier Detail ComponentFlashing, Sloped

Backer Rod & Sealant w/ Weep Holes

Terminate Assembly 6" (152 mm) Above Grade, min.

Page 6: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciTermination at Grade - Sheathing Overlapping Slab or Foundation

Detail No.: 52s.03B Date: December 2018

®

Notes:

1. Terminate systemminimum 6" (15.2 cm)above finished grade, higherfor areas with heavy snowaccumulations, or whererequired by code.

2. Ultra-high impactresistance recommended atall ground floors to aminimum height of 6'-0"(1.8 m) above finished gradeand other areas accessible topedestrian traffic, abnormalstress or impact.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Sto AdhesiveSheathing

Sto EPSInsulation Board, Pre-Wrapped

Terminate Assembly 6" (152 mm) Above Grade, min.

Sto Mesh

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (Protect with StoCoat Acryl Plus or Flashing)

StoGuard® Air and Moisture Barrier Detail Component

Flashing, Sloped

Backer Rod & Sealant w/ Weep Holes

Page 7: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciAesthetic Feature Band

Detail No.: 52s.04Date: December 2018

®

Notes:

1. Feature band attachedwith Sto TurboStickAdhesive, also used as fillerand rasped smooth at anygaps between feature bandand base layer of insulationboard.

2. Slope top surface offeature band minimum 27degrees. Increase slope fornorthern climates to preventsnow and ice accuulations.

3. Limit thickness of build-out to reduce maintenanceassociated with projectingarchitectural features.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sheathing

Sto EPSInsulation Board

Sto Base Coat (with Sto Mesh Embedded)

StoGuard® Air and Moisture Barrier

Sheathing

Sto EPSInsulation Board

(with Sto Mesh Embedded) Sto Base Coat

Sto Flexyl (with Sto Mesh or Sto Detail Mesh Embedded); Return Vertically 4" (102 mm) min. Above and Below Feature Band

Sto Mesh

Sto Mesh

Sto Finish

Sto Finish

Sto Primer (Required over Sto Flexyl and Sto Base Coat Above and Below)

Sto Adhesive

Sto Adhesive

Thin Build-Out

Thick Build-Out

Thick Build-Out, 2-4 in. (51-102 mm)

Thin Build-Out,

≤ 2 in. (51 mm)

Page 8: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciAesthetic Reveal

Detail No.: 52s.05 Date: December 2018

®

Notes:

1. Slope bottom surface ofreveal minimum 27 degrees.Increase slope for northernclimates to prevent snowand ice accumulations.

2. Maintain minimum 3/4inch (19 mm) thickness ofinsulation board at base ofreveal.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Sto EPSInsulation Board

Sto Base Coat (with Sto Detail Mesh Embedded)

3/4" (19 mm) min.

2 1/2" (64 mm) min. Ovelap of Sto Detail Mesh w/ Sto Mesh @ Top and Bottom of Reveal

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Detail Mesh

Sto Primer (Optional)

Sto Finish

Sto Adhesive

Sto EPSInsulation Board

3/4" (19 mm) min.

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sheathing

Sheathing

Option 1 with Sto Detail Mesh

Option 2 with Continuous Sto Mesh

Page 9: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciReceptor-Type Window Sill

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23A-1 Date: December 2018

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection Over Blocking

Blocking

StoGuard® Air and Moisture Barrier Rough Opening Protection

Step 1 - Rough Opening Protection

Page 10: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciReceptor-Type Window Sill

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23A-2 Date: December 2018

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

End Dam Set in Sealant

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped

Sto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth)

Sto EPS Insulation Board, Pre-Wrapped around Rough Opening

Sill Receptor w/ Weep Holes (Sill Flashing Extender Not Shown for Clarity)

Sto Adhesive

Weep Holes

Angle (As Needed for Attachment of Sill Receptor and Support)

StoGuard® Air and Moisture Barrier Rough Opening Protection

Blocking

Step 2 - Receptor with End Dam

Page 11: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciReceptor-Type Window Sill

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23A-3 Date: December 2018

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

Backer Rod & Sealant (Entire Perimeter)

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped at Jamb

Sto EPS Insulation Board, Pre-Wrapped around Rough Opening

Sill Receptor w/ Weep Holes

Sto Adhesive

Spray Polyurethane Foam Insulation

Jamb Receptor

Sill Extender w/ Continuous Bead of Sealant @ Bottom

Window Assembly

Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)

Angle (As Needed for Attachment of Sill Receptor and Support)

StoGuard® Air and Moisture Barrier Rough Opening Protection

Blocking

Step 3 - Window and Sill Flashing, Cladding, and Perimeter Weather and Air Seals

Page 12: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciReceptor-Type Window Head

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23B-1 Date: December 2018

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Cement Board Filler or Other TrimFlashing

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier Detail Component

Step 1 - Rough Opening Protection, Head Flashing

Page 13: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciReceptor-Type Window Head

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23B-2 Date: December 2018

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped

Sto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth, Reinforce Top Corner with Sto Mesh or Sto Detail Mesh Embedded in Base Coat)

Sto EPS Corner Board, Pre-Wrapped around Rough Opening

Window Assembly

Spray Polyurethane Foam Insulation

Head Receptor

Jamb Receptor

Cement Board Filler or Other TrimFlashing

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Air and Moisture Barrier

Sto Adhesive

Step 2 - Receptor and Window

Page 14: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciReceptor-Type Window Head

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.23B-3 Date: December 2018

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-WrappedSto TurboStick Adhesive (Fill Gap Between EPS Boards at Corner with this Adhesive, Cut Flush with Surface and Rasp Smooth)

Sto EPS Corner Board, Pre-Wrapped around Rough Opening

Window Assembly

Sto Adhesive

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

Air Seal, Backer Rod and Sealant (Air Seal Entire Perimeter)

Head Receptor

Jamb Receptor Backer Rod & Sealant (Entire Perimeter, with Weeps at Head)

Cement Board Filler or Other Trim (Finish Cement Bd. w/ StoCoat Acryl Plus)

Flashing

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Air and Moisture Barrier

Spray Polyurethane Foam Insulation

Step 3 - Cladding and Perimeter Weather and Air Seals

Page 15: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFlanged Window-Sill

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.24A-1 Date: December 2018

Property of Sto Corp. All Rights Reserved.

Step 1 - Rough Opening Protection, Sill Flashing

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

1/8" (3 mm) Thick Washers Behind Mounting Flange

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Detail Component

Flashing

Slope

Page 16: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFlanged Window-Sill

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.24A-2 Date: December 2018

Property of Sto Corp. All Rights Reserved.

Step 2 - Window and Trim

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening (Cut Kerf in Back of Insulation and Slide over End Dam. Position insulation over Flashing with 1/4" [6 mm] Gap for Drainage)

Spray Polyurethane Foam Insulation

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sealant Behind Mounting Flange (Jambs and Head Only)

Sto Adhesive

StoGuard® Detail Component

Flashing

Slope

Window Assembly

1/8" (3 mm) Thick Washers Behind Mounting Flange

Spray Polyurethane Foam Insulation

Page 17: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFlanged Window-Sill

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.24A-3 Date: December 2018

Step 3 - Cladding and Perimeter Weather and Air Seals

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

Backer Rod & Sealant (Entire Perimeter)

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening

Sto EPS Insulation Board

Spray Polyurethane Foam Insulation

Window Assembly

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto Adhesive

StoGuard® Detail ComponentFillet Bead of Sealant (not

shown) Between Underside of Flashing and Base Coat

1/8" (3 mm) Thick Washers Behind Mounting Flange

Sealant Behind Mounting Flange (Jambs and Head Only)

Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)

Spray Polyurethane Foam Insulation

Backer Rod & Sealant with Weeps Between Trim and Flashing Leg

Flashing

Air Seal, Backer Rod & Sealant (Air Seal Entire Perimeter)

Page 18: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFlanged Window-Head

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.24B-1 Date: December 2018

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Window Assembly

StoGuard® Air and Moisture Barrier Rough Opening Protection

StoGuard® Detail Component

Sealant Behind Mounting Flange (Jambs and Head Only)

Flashing

Sealant Behind Mounting Flange (Jambs and Head Only)

Sealant

Property of Sto Corp. All Rights Reserved.

Step 1 - Rough Opening Protection, Head Flashing

Page 19: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFlanged Window-Head

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.24B-2 Date: December 2018

Property of Sto Corp. All Rights Reserved.

Step 2 - Window and Trim

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening

Sto EPS Insulation Board

Window Assembly

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto Adhesive

StoGuard® Detail Component

Sealant Behind Mounting Flange (Jambs and Head Only)

Sealant

Spray Polyurethane Foam Insulation

Flashing

Backer Rod & Sealant Weather and Air Seals (Entire Perimeter with Weeps Between Underside of Trim & Flashing Leg)

Spray Polyurethane Foam Insulation

Page 20: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFlanged Window-Head

®

Notes:

1. Consult with window andsealant manufacturers toverify window installation anddetailing and to assure nowater leakage into the wallassembly. Consult withwindow manufacturerregarding window and/orflashing assembly thermalbreaks to avoid condensation.Test the final assembly usingmaterials and tradesassociated with the project toverify performance. Correctany deficiencies associatedwith excess air leakage,water infiltration into the wallassembly, or structuralinadequacies.

2. Construct a site built mock-up using materials and sub-trades associated with theproject to verify installationsequencing, detailing, andaesthetics.

- Refer to StoTherm ci SystemBulletins and Specifications,Sto Product Bulletins, TechHotlines, and Sto Installationand Maintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.24B-3 Date: December 2018

Step 3 - Cladding and Perimeter Weather and Air Seals

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded)

Sto Base Coat

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto EPS Insulation Board, Pre-Wrapped Around Opening

Sto EPS Insulation Board

StoGuard® Air and Moisture Barrier Rough Opening Protection

Sto Adhesive

StoGuard® Detail Component

Sealant Behind Mounting Flange (Jambs and Head Only)

Sealant

Spray Polyurethane Foam Insulation

Flashing

Spray Polyurethane Foam Insulation

Window Assembly

Backer Rod & Sealant Weather and Air Seals (Entire Perimeter with Weeps Between Underside of Trim & Flashing Leg)

Page 21: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSoffit: Insulated and Unvented

Detail No.: 52s.30 Date: December 2018

®

Notes:

1. Continue StoGuard air andmoisture barrier onto dissimilarmaterial or construction whererequired after verifying substratematerial compatibility. Refer toSto Detail 52s.53 for typicaldetailing of inside corner ifsubstrate material orconstruction is dissimilar. Referto Sto Detail 52s.54A ifsubstrate material is similar atinside corner.

2. 4" (10 cm) thick insulationboard typically required forproper lap of accessory withmesh "tail." For thinnersections of insulation board pre-wrap insulation board with Stobase coat and mesh.

3. Multi-story buildings whereconstruction is required to beNoncombustible may requirespecial examination of soffitconditions with foam plasticinsulation. Verify withprofessional fire protectionengineer and building codeofficial.

- Refer to StoTherm ci SystemBulletins and Specifications, StoProduct Bulletins, Tech Hotlines,and Sto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Nominal 1/4 inch (6 mm) Gap for Drainage

Sheathing

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive

StoGuard® Joint Treatment

Backer Rod and Sealant

Structure

Sto Drip Edge Profile

Sto Drip Edge Profile (See Drawing Below) Dissimilar Material or

Wall Construction

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Page 22: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSoffit: Uninsulated and Vented

Detail No.: 52s.31 Date: December 2018

®

Notes:

1. Prevent "communication"of vented air space withconditioned interior air toreduce the likelihood ofcondensation on materials inthe vented space.

3. Typical soffit board isgypsum sheathing incompliance with ASTM C1177. Refer to StoSpecification No. F601S andSto Detail Series 14.xx.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Nominal 1/4 inch (6 mm) Gap for Drainage

Sheathing

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive

Backer Rod and Sealant

Structure

Sto Drip Edge Profile

Sto Drip Edge Profile (See Drawing Below) Dissimilar Material or

Wall Construction

Light Gauge Steel Stud FramingStoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

StoGuard® Joint Treatment

Soffit Vent

Casing Bead

Page 23: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFloor Line Without Deflection

Detail No.: 52s.40 Date: December 2018

®

Notes:

1. This detail is typicallylimited to low-riseconstruction where no floorline deflection is anticipated.Refer to Sto Detail 52s.41A,B, or C for a floor linecondition with deflection.

2. Sheathing attachment istypically at 8" (20.3 cm) oncenter or less vertically. AddC-channels or otherattachment means alongslab edge if necessary toconform with requiredfastener spacing.

3. Provide fire stopping atfloor line as needed.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sheathing

Sto EPS Insulation Board

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive

Sto Mesh

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Structure

Page 24: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFloor Line With Deflection -Concealed Flashing and Drainage at Floor Line

Detail No.: 52s.41A Date: December 2018

Notes:

1. Sheathing attachment istypically at 8" (20.3 cm) oncenter or less vertically. AddC-channels or otherattachment means alongslab edge if necessary toconform with requiredfastener spacing.

2. Provide fire stopping atfloor line as needed.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICCReports for building codecompliance information.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

Cant Bead of Sto RapidGuard

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

®

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sheathing

Sto EPS Insulation Board, Pre-Wrapped @ Top and Bottom to Allow for Drainage

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

StoGuard® Transition Membrane

Horizontal Deflection Joint: Backer Rod & Sealant w/ Weeps. Sealant Applied to Base Coat as per Sealant Manufacturer Instructions

Slotted Deflection Track

Backer Rod

Structure

Page 25: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFloor Line With Deflection - No Drainage at Floor Line

Detail No.: 52s.41B Date: December 2018

®

Notes:

1. Sheathing attachment istypically at 8" (20.3 cm) oncenter or less vertically. AddC-channels or otherattachment means alongslab edge if necessary toconform with requiredfastener spacing.

2. Provide fire stopping atfloor line as needed.

3. Provide drainage at floorlines as deemed by DesignProfessional, typically nomore than every third floorline. Refer to Sto Detail52s.41A.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sheathing

Sto EPS Insulation Board, Pre-Wrapped @ Top and Bottom to Allow for Drainage

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

StoGuard® Transition Membrane

Horizontal Deflection Joint: Backer Rod & Sealant. Sealant Applied to Base Coat as per Sealant Manuf'r Instructions

Slotted Deflection Track

Backer Rod

Structure

Page 26: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFloor Line With Deflection -Flashing and Drainage at Floor Line

Detail No.: 52s.41C Date: December 2018

Notes:

1. Sheathing attachment istypically at 8" (20.3 cm) oncenter or less vertically. AddC-channels or otherattachment means alongslab edge if necessary toconform with requiredfastener spacing.

2. Provide fire stopping atfloor line as needed.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICCreports for building codecompliance information.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

®

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sheathing

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

StoGuard® Transition Membrane

Sto EPS Insulation Board, Pre-Wrapped @ Top and Bottom to Allow for Drainage

Slotted Deflection Track

Backer Rod

Structure

Flashing

Sealant

Horizontal Deflection Joint: Backer Rod & Sealant w/ Weeps. Sealant Applied to Base Coat as per Sealant Manufacturer Instructions

StoGuard® Air and Moisture Transition Component

Page 27: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

®

Notes:

1. Detail apples to BalconyProtected Overhead byBalcony Ceiling Above.

2. Slope balcony to directwater away from wall.

3. Consider the use of highor ultra-high reinforcingmeshes on balcony walls tosupplement standardreinforcing mesh for addedabuse and impact resistance.

4. Verify compatibility ofStoGuard Air and MoistureBarrier with balconywaterproof membranematerial where they interfaceor lap one another.

5. Counter flash balconymembrane on wall if notfluid applied.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.42A Date: December 2018

StoTherm® ciBalcony Floor/Wall

Sto Primer (Optional)

Sto Finish

Sto Mesh

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

Sto EPS Insulation Board, Pre-Wrapped

Sto Adhesive

Balcony Slab Recess

Backer Rod & Sealant w/ Weeps

Balcony Waterproof Membrane and Finished Flooring

Balcony

Cant and Air Seal Transition Material

Page 28: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

®

Notes:

1. Detail applies to BalconyProtected by Balcony CeilingAbove.

2. Underside of balcony mayalso be finished with StoFinish or other Sto smooth ortextured coatings.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.42B Date: December 2018

StoTherm® ciBalcony Ceiling/Wall

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Sto Adhesive

(with Sto Mesh Embedded) Sto Base Coat

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Sheathing

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Mesh

Backer Rod

Backer Rod and Sealant

Balcony

Slotted Deflection Track

Skim Coat of Sto Base Coat

Sto Primer Smooth

StoCoat Acryl Plus

Page 29: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciHorizontal Termination at Dissimilar Cladding

Detail No.: 52s.50 Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Backer Rod and Sealant with Weep Holes

Sheathing

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

Sealant

StoGuard® Air and Moisture Barrier Detail Component

Wood Blocking

Brick Cavity Wall

Masonry Sill

Flashing

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier

Page 30: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciVertical Termination at Dissimilar Cladding

Detail No.: 52s.51A Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sheathing

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto AdhesiveLight Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sto Finish

Masonry Veneer or Other Dissimilar Material

Sealant and Backer Rod

Page 31: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciVertical Termination at Dissimilar Backup Wall Construction

Detail No.: 52s.51B Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier Sheathing

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier (Minimum Two Coats on CMU Wall Surface)

CMU Backup

Masonry Veneer or Other Dissimilar Material

Sto Finish

Sealant and Backer Rod

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Primer (Optional)

Sto Adhesive

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Page 32: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciVertical Expansion Joint in Back-Up Wall

Detail No.: 52s.52A Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sheathing

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto AdhesiveLight Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

Sto Primer (Optional)

Sealant and Backer Rod

Sto Finish

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

Page 33: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciVertical Expansion Joint in Back-Up Wall,StoTherm ci and Dissimilar Cladding

Detail No.: 52s.52B Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Masonry Veneer or Other Dissimilar Material

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier

SheathingSto Primer (Optional)

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Finish

Sealant and Backer Rod

Light Gauge Steel Stud Framing

Page 34: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciInside Corner with Dissimilar Backup Wall

Detail No.: 52s.53 Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Mesh

Sto Adhesive

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture BarrierLight Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

Sealant and Backer Rod

StoGuard® Air and Moisture Barrier (Minimum Two Coats on CMU Wall Surface)

CMU Backup

Sheathing

Page 35: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciInside and Outside Corner with Common Substrateand StoMesh Corner Bead Reinforcement

Detail No.: 52s.54A Date: December 2018

®

Notes:

1. Provide joint at interiorcorner if movement isanticipated. Refer to StoDetail 52s.53.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive StoGuard® Joint Treatment

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier

Sheathing

Sto-Mesh Corner Bead Standard (Embedded in Sto Base Coat)

Sto Mesh, (Overlap StoMesh Corner Bead 4 in. ea. Side, min.)

Return Sto Mesh 6 in. min. @ Inside Corner

Page 36: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciInside and Outside Corner with Common Substrateand Sto Mesh Reinforcement

Detail No.: 52s.54B Date: December 2018

®

Notes:

1. Provide joint at interiorcorner if movement isanticipated. Refer to StoDetail 52s.53.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive StoGuard® Joint Treatment

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier

Sheathing

Return Sto Mesh 6 in. min. Around Corner

Return Sto Mesh 6 in. min. @ Inside Corner

Sto Mesh

Page 37: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciTermination at Parapet - Front

Detail No.: 52s.60A Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive

Metal Coping

Light Gauge Steel Stud Framing

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier

Sheathing

Roof Structure

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

Wood Blocking

StoGuard® Detail Component

Sto Mesh

Backer Rod & Sealant

Page 38: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciTermination at Parapet - Back

Detail No.: 52s.60B Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Adhesive

Metal Coping

Roof Membrane

Sto Primer (Optional)

Sto Finish

StoGuard® Air and Moisture Barrier Detail Component

Sheathing

Roof Structure

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

Wood Blocking

Backer Rod and Sealant

Sto Mesh

StoGuard® Detail Component

Termination Bar for Roof Membrane

Light Ga. Steel Stud Framing

Cover BoardRoof Insulation

StoGuard® Air and Moisture Barrier

Termination Bar for Roof Membrane

Sto EPS Insulation Board, Pre-Wrapped

Wood Blocking

StoGuard® Detail Component

Insulation

Z-Flashing

Roof Membrane

StoGuard® Air and Moisture Barrier

Sheathing

Backer Rod and Sealant with Weep Holes

Page 39: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciParapet with Cornice Feature

Detail No.: 52s.61 Date: December 2018

®

Notes:

1. Cornice feature limited to 12"(30.5 cm) maximum thicknessfor noncombustible typeconstruction. Special analysiswith regard to fire propagationmay enable thicker sections.Thicker sections permittedwithin practical limits forcombustible construction.

2. Cornice feature attached withSto TurboStick Adhesive; alsoused as filler and rasped smoothat any gaps between featureband and base layer ofinsulation board.

3. Cornice feature may also beattached directly to StoGuardwhere applicable.

4. Supplemental mechanicalattachment of feature bandmaybe necessary in some cases.Verify installation method foradequate attachment beforecommencing work.

- Refer to StoTherm ci SystemBulletins and Specifications, StoProduct Bulletins, Tech Hotlines,and Sto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

View of Pre-Wrapped CorniceView of Mesh Overlap

Sto Mesh Embedded in Base Coat Laps Sto Mesh on Cornice 2 1/2 in. (64 mm) min.

Sto EPS Insulation Cornice Feature

Cornice Feature Pre-Wrapped with Sto Base Coat (with Sto Mesh Embedded)

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

Wood Construction as Required StoGuard® Air and Moisture Barrier Sheathing Joint Treatment Extends 2 in. (51 mm) min. at Vertical and Horizontal Surfaces

Sto EPS Insulation Board, Back-Wrapped or Pre-Wrapped at Termination

Sto Base Coat (with Sto Mesh Embedded)

Metal Coping

Sto Primer (Optional)

Sto Finish

Sheathing

Backer Rod and Sealant

Sto Mesh

Light Gauge Steel Stud Framing

StoGuard® Air and Moisture Barrier

1/2 in. (13 mm) min. Gap Between Top Surface of Cornice Feature and Underside of Wood ConstructionPre-Wrapped

Cornice

Page 40: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciDiverter Flashing at Roof/Wall Abutment

Detail No.: 52s.62 Date: December 2018

®

Notes:

1. Maintain minimum 2" (51mm) gap between roofshingles and StoTherm citermination. Increase gapfor low slope roofs toprevent snow and iceaccumulations.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Backer Rod and Sealant Around Vertical Leg of Diverter Flashing

Diverter Flashing

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier Detail Component

Sto EPS Insulation Board, Pre-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sheathing

Sto Mesh

Light Gauge Steel Stud Framing

Drip Edge Flashing

Gutter

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Sto AdhesiveDiverter Flashing

Terminate StoTherm ci 2 in. (51 mm) Above Finished Roof

Fascia

Drip Edge Flashing

Roof Structure

Step Flashing

Step Flashing

Sto Finish

Roof ShinglesRoof Underlayment

Page 41: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciGravel Stop

Detail No.: 52s.63 Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Roof Air Barrier

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Gravel Roof Ballast

Continuous Cleat

Gravel Stop

Sheathing

1/4" (6 mm) Min. Gap Between Top of EPS Insulation Board and Wood Blocking

Wood Blocking

Roof Membrane

Roof Insulation

Roof Sheathing

Roof Structure

StoGuard® Air and Moisture Barrier Sheathing Joint Treatment

Backer Rod & Sealant

Page 42: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment

®

Notes:

1. Provide minimum 2" (51mm) gap between parapetcap flashing and StoThermci termination.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Sheathing

Detail No.: 52s.64-1 Date: December 2018

StoGuard® Detail Component

StoGuard® Air and Moisture Barrier

Light Gauge Steel Stud Framing

Step 1 - Air and Moisture Barrier

Page 43: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment

®

Notes:

1. Provide minimum 2" (51mm) gap between parapetcap flashing and StoThermci termination.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved. Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.64-2 Date: December 2018

A

BC

StoGuard® Air and Moisture Barrier

StoGuard® Air and Moisture Barrier

Assembled Saddle Flashing

Saddle Flashing Components

Step 2 - Saddle Flashing

Page 44: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSaddle Flashing at Lower/Higher Wall Abutment

®

Notes:

1. Provide minimum 2" (51mm) gap between parapetcap flashing and StoThermci termination.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved. Property of Sto Corp. All Rights Reserved.

Detail No.: 52s.64-3 Date: December 2018

Parapet Cap Flashing Assembly Extends to Perpendicular Wall

Light Gauge Steel Stud Framing

StoGuard® Transition Membrane Embedded in StoGuard® Air and Moisture Barrier (or Compatible Roofing Membrane)

StoGuard® Detail Component

Wood Blocking

Saddle Flashing Assembly

Backer Rod & Sealant Between StoTherm ci and Saddle Flashing Assembly

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Pre-Wrapped at Termination

StoTherm ci Assembly

Step 3 - Cladding, Coping, and Sealant

Page 45: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciScupper Penetration

Detail No.: 52s.65 Date: December 2018

®

Notes:

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped Around Scupper Penetration

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Sheathing

Wood Blocking

Roof Membrane

Roof Insulation

Roof Structure

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component

Scupper Assembly

Page 46: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

®

Notes:

1. Refer to Sto Detail52s.70B where sheathing is"rough cut" around pipe orwhere gap around pipeexceeds allowable gapdimension for StoGuard Airand Moisture Barrier DetailComponent.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped Around Pipe Penetration

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Sheathing

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component

Pipe

Detail No.: 52s.70A Date: December 2018

StoTherm® ciPipe Penetration - Precision Cut Sheathing

Page 47: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

®

Notes:

1. Appropriate spray foam isused to fill gaps insheathing. Where sheathingfits snug around pipe refer toSto Detail 52s.70A.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Retrofit or Oversized Pipe Penetration Opening

Detail No.: 52s.70B Date: December 2018

StoTherm® ciPipe Penetration - Rough Cut Sheathing

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board, Back-Wrapped Around Pipe Penetration Sto Base Coat (with

Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto Adhesive

Sheathing

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component

Pipe

Spray Foam (to Fill Gaps, Shaved or Rasped Flush with Sheathing Surface)

Page 48: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciSign Attachment

Detail No.: 52s.71 Date: Date: December 2018

®

Notes:

1. Blocking not requiredwhere solid substrate orwood-based sheathing iscapable of supporting thesign (or other attachedobject). Use appropriatefasteners for attachment.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sheathing

Wood Blocking

Hole Drilled in EIFS and Lined with Sealant

PVC or Stainless Steel Sleeve (Sleeve Extends From Finish Through Blocking, Shown Partial Length for Clarity)

Neutral Cure Sealant

Sign

Washer Behind Sign Set in Sealant

Sto EPS Insulation Board

Sto Adhesive

Bolt w/ Washers at Each End

Page 49: Detail Booklet StoTherm ci · 2020. 9. 14. · StoTherm® ci Termination at Grade - Sheathing Flush with Foundation or Slab Edge Detail No.: 52s.03A Date: December 2018 ® Notes:

StoTherm® ciFixture Attachment

Detail No.: 52s.73 Date: December 2018

®

Notes:

1. Attach fixture to blockingor solid substrate. Whereattached to blocking seal theblocking with Sto DetailComponent.

- Refer to StoTherm ciSystem Bulletins andSpecifications, Sto ProductBulletins, Tech Hotlines, andSto Installation andMaintenance Guides forcomplete information.

- Refer to applicable ICC orCCMC Evaluation Reports forbuilding code complianceinformation.

- Components not identified asSto are furnished by othermanufacturers and are notnecessarily installed by tradeswho install the Sto products.Refer to project specific contractdocuments.

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, or for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

StoGuard® Air and Moisture Barrier

Sto Base Coat (with Sto Mesh Embedded)

Sto Primer (Optional)

Sto Finish

Sto Mesh

Light Gauge Steel Stud Framing

Sto AdhesiveSheathing

Backer Rod & Sealant

StoGuard® Air and Moisture Barrier Detail Component on Blocking; Extend onto Sheathing 2" min.

Electric Box for Fixture AttachmentBlocking

Sto EPS Insulation Board, Back-Wrapped Around Electric Box Penetration