designing for fire safety parts 3 and 4 active systems …
TRANSCRIPT
Active Fire Safety Systems 9/29/2011
chong lee siong 1
DESIGNING FOR FIRE SAFETY
PARTS 3 and 4
ACTIVE SYSTEMS
And
ACCESS for FIRE FIGHTING and RESCUE
Ar Chong Lee Siong APAM MIFireE MMIArbs
with
Ir Wong See Foong
FIEM MIFireE PEng CEng PJB
“A re-visit to the interpretations and applications
of the Uniform Building By-Laws 1984”
Uniform Building By-Laws 1984
is a
“PRESCRIPTIVE” BUILDING CODE
•Compliance with this code is a requirement by law
•Sets rules and regulations on the application of the code
•Provides pre-determined prescriptions
The prescriptions are absolute :
no smaller than……..
no bigger than……..
no shorter than……
no longer than……
or
no less than and no more than.
Active Fire Safety Systems 9/29/2011
chong lee siong 2
CONCEPTS OF FIRE SAFETY
1 EVACUATION
2 PASSIVE CONTAINMENT
3 ACTIVE INTERVENTION
4 ACCESS FOR FIRE FIGHTING AND RESCUE
Time
Tem
per
atu
re /
siz
e
Stage 1
Ignition & growth
Stage 2
development
Stage 3
Full fire
Stage 4
Decay
Flashover
Untenable condition
NATURE OF FIRE
Active Fire Safety Systems 9/29/2011
chong lee siong 3
Active systems for…..
EVACUATION
Detection and Alarm
Communication
Smoke control
Portable fire extinguishers
Tem
per
atu
re /
siz
e
Time
Un
ten
ab
le c
on
dit
ion
Available Safe Egress Time ASET
detection
alarm
movement Total
evacuation
ignition
Required Safe Egress Time RSET
Factor of safety:
RSET < 0.75 ASET
Active Fire Safety Systems 9/29/2011
chong lee siong 4
detection
Very early detection
Early detection
Manual detection
alarm
Automatic
Pre alarm
Local / manual
Active Fire Safety Systems 9/29/2011
chong lee siong 5
FIRE DETECTION AND ALARM
System objective are:
To detect outbreak of fire and warn occupants
To activate fire safety systems
To inform Fire Brigade
To monitor fire safety equipment
RELEVANT BY-LAWS
Under UBBL 237, fire alarm systems are required for buildings defined under the 10th Schedule
Under UBBL 238, a fire command center is required for all buildings above 30.5 meters or exceeding 9,290 sq. meters in gross area.
Active Fire Safety Systems 9/29/2011
chong lee siong 6
MAIN FIRE ALARM PANEL
Main fire alarm panel comprises:
Alarm, fault and isolation indication for each zone.
Indicator lights to monitor status of power supply and fire safety systems such as fire pumps, smoke control equipment, carbon dioxide systems, fire tank water levels, etc.
Mimic panel to identify location of each zone.
Battery with charger to provide power supply for the whole system.
FIRE DETECTION DEVICES
Manual break glass for occupants to activate manually.
Heat detectors to detect heat intensive fires automatically for spaces up to 9 meters high.
Smoke detectors to detect smoke intensive fires automatically for spaces up to 10 meters high.
Beam (smoke) detectors for high spaces such as atriums up to 25 meters high.
Flame (IR or UV) detectors
Active Fire Safety Systems 9/29/2011
chong lee siong 7
Heat …..or Smoke?
Smoke detectors for electrical rooms and store rooms.
Heat detectors for general areas.
Smoke detectors for areas where rapid heat development is normal for the function of the space, or where combustibles may burn with high release of smoke
Heat detectors for areas where smoke may be a common presence in the space, or where combustibles may burn rapidly and efficiently
VOICE COMMUNICATION SYSTEMS
To guide the occupants in an orderly manner during evacuation upon detection of fire.
For the firemen to communicate with one another during fire fighting operations.
Active Fire Safety Systems 9/29/2011
chong lee siong 8
RELEVANT BY-LAW
Under UBBL 239, two voice communication system is required for all large buildings and high rise buildings and they are:
Public address system, and
Fire brigade intercommunication system
PORTABLE FIRE EXTINGUISHERS
Intended for use by the occupants during the early stages of the fire
Under UBBL 227, portable fire extinguishers are required for first aid use.
Active Fire Safety Systems 9/29/2011
chong lee siong 9
CLASSES OF FIRES
Class A: Combustible solids like paper, wood
Class B: Inflammable Liquids like kerosene, diesel
Class C: Flammable gases
Class D: Reactive metals like sodium, potassium,
Class E: Ignition of an electrical nature
Class F: Cooking oil fires
TYPES OF EXTINGUISHERS
Water type for Class A fires
Dry powder type for Class A, B, C and F fires
Carbon Dioxide type for Class E fires
Foam type for Class B fires
Dry powder type of 6 kg for general use.
Carbon Dioxide type for electrical rooms
Active Fire Safety Systems 9/29/2011
chong lee siong 10
LOCATION AND SPACING
Beside exit and staircase doors
Generally located within 20 meters of any potential hazard
Active systems for…..
COMPARTMENTATION
Smoke Control
Extinquishment
Manual
Automatic
Active Fire Safety Systems 9/29/2011
chong lee siong 11
SMOKE CONTROL TYPES
Pressurization system to prevent entry of smoke by pressurizing the compartment with air.
Space depressurization system to prevent the spread of smoke by extraction.
Smoke dilution system to remove the smoke by extraction and make-up of air.
DEPRESSURIZATION SYSTEMS
Typical application are multi-storey office buildings.
Floor on fire is maintained under negative
pressure by extracting the smoke laden air.
Immediate floors above and below are maintained at positive pressure by supplying air to these floors.
Active Fire Safety Systems 9/29/2011
chong lee siong 12
DILUTION SYSTEMS
Typical application are basement car parks and shopping complexes.
Smoke is extracted from zone on fire.
Make-up air is provided to zones adjacent to area on fire.
HOSE REELS
Intended for the occupants to use during early stages of the fire
Active Fire Safety Systems 9/29/2011
chong lee siong 13
LOCATION AND SPACING
Near exit and staircase doors
All spaces to be within 36 meters of a hose reel.
No restriction on location of hose reel pumps and tanks.
Active Fire Safety Systems 9/29/2011
chong lee siong 14
SPRINKLER SYSTEM
Intended to detect and extinguish a fire and warn the occupants to evacuate.
Under UBBL 226, automatic sprinkler systems are required for storage and other types of occupancies where automatic extinguishing system is necessary.
Active Fire Safety Systems 9/29/2011
chong lee siong 15
TYPES OF SYSTEMS
Wet pipe system where pipe work is charged with water at all times.
Dry pipe system where pipe is charged with water only after the sprinkler head is activated.
Pre-action system where system is charged with water after fire is detected but before the sprinkler head is activated.
Deluge system where water is discharged simultaneously from all sprinkler heads upon activation.
TYPES OF HAZARDS
Light Hazard e.g. apartments, schools
Ordinary Hazards:
OH Group I : Offices, restaurants
OH Group II : Laundries, bakeries
OH Group III : Departmental Stores, Car parks
OH Group IV : Film and television studios
High Hazards:
Process risks
High piled storage risks
Active Fire Safety Systems 9/29/2011
chong lee siong 16
SPRINKLER TANKS
Typical location at ground or first basement although no restriction on the location except for distance from pump.
AREAS EXEMPTED
Transformer Rooms;
Switch gear Rooms;
Lift Motor Rooms; and
Toilets;
Active Fire Safety Systems 9/29/2011
chong lee siong 17
INSTALLATION CONTROL VALVE
Water supply to sprinklers feed from Installation control valve with alarm gong and shut-off valves.
For life safety systems, Sprinklers are grouped such that each zone does not have more than 200 sprinkler heads with its own flow switch.
Active Fire Safety Systems 9/29/2011
chong lee siong 18
SPRINKLER PIPE WORK
The height between the lowest and highest sprinkler within one stage not to exceed 45 m.
For buildings exceeding 45 m., multiple stages are required.
Express risers are permitted to bypass lower stgages and serve the upper stage.
8. CARBON DIOXIDE EXTINGUISHING SYSTEM
System using carbon dioxide to extinguish a fire by excluding oxygen from the fire and commonly used for electrical rooms where water may not be suitable.
The by-law relevant to this system is UBBL 235.
Active Fire Safety Systems 9/29/2011
chong lee siong 19
TYPES OF SYSTEMS
Total Flooding System uses CO2 to displace oxygen within entire room.
Local Application creates envelope around fire and exclude oxygen around the fire only.
Active Fire Safety Systems 9/29/2011
chong lee siong 20
AUTOMATIC ACTIVATION
Heat and smoke detectors installed to detect fire.
Activation of one detector initiates alarm but not gas discharge.
Activation of any two detectors initiates gas discharge.
Time delay of 30 sec. before gas discharge.
MANUAL ACTIVATION
Manual activation by pull station in event of failure of automatic activation.
Pull station to be outside of room protected.
Audio and visual warning activated upon gas discharge to warn occupants from entering.
Active Fire Safety Systems 9/29/2011
chong lee siong 21
Active systems for…..
FIRE FIGHTING and RESCUE
Lifts
Risers
Hydrants
FIRE LIFT
Intended to assist the firemen to reach the floors on fire rapidly.
Under UBBL 243, any building exceeding 18.5 meters high shall be provided with firemen’s lift.
Active Fire Safety Systems 9/29/2011
chong lee siong 22
LOCATION AND SPACING
Not more than 61 meters from the furthermost point of the floor.
Not more than 61 meters from the main entrance of the building or the fire control room whichever is nearer.
DESIGN REQUIREMENTS
Lift capacity to be able to carry 550kg. min.
Lift car platform size to be not less than 1.45 sq. meters.
Lift car door to be min. 800 mm clear in width.
Lift to serve all occupied floors.
Active Fire Safety Systems 9/29/2011
chong lee siong 23
FIRE MODE OF OPERATION
Lift to be provided with emergency power for operation during power failure.
Lift to return to main landing upon detection of power failure and remain inoperable until firemen arrive.
Fire switch to be provided at main landing for firemen to activate the lift for their use.
DRY RISER SYSTEMS
Intended for the firemen to pump water up to the floors on fire.
Under UBBL 230, dry risers required for all buildings with topmost floor above 18.3 meters from fire appliance access level
Active Fire Safety Systems 9/29/2011
chong lee siong 24
LOCATION AND SPACING
Landing valves located within fire access lobbies.
Provided on every upper floor such that all spaces are within 45 m from a landing valve.
Breeching inlet to be no more than 18 m. from fire appliance access road and not more than 30 meters from nearest outdoor hydrant.
Active Fire Safety Systems 9/29/2011
chong lee siong 25
DRY RISER PIPE WORK
Dry riser to be 100 mm dia. If highest outlet is no more than 23 m. above breeching inlet.
Dry riser to be 150 mm dia. If highest outlet is more than 23 m. above breeching inlet.
5. WET RISER SYSTEMS
Intended to supply water up to the floors on fire for the firemen to use.
Under UBBL 231, wet risers required for all buildings with topmost floor above 30.5m. From the fire appliance access level.
Active Fire Safety Systems 9/29/2011
chong lee siong 26
LOCATION AND SPACING
Landing valves located within fire access lobbies.
Provided on every upper floor such that all spaces are within 45 m from a landing valve.
Distance between landing valves on the same floor not to exceed 60 m.
Breeching inlet to be no more than 18 m. from fire appliance access road and not more than 30 meters from nearest outdoor hydrant.
Active Fire Safety Systems 9/29/2011
chong lee siong 27
PUMPS AND PIPE WORK
Each stack not to exceed 60 m or 71 m if approved by the Director General of Fire and Rescue Dept.
Stack height is defined as the height from the wet riser pump to the topmost floor protected.
WET RISER PUMPS AND TANKS
Location of wet riser pumps and tanks restricted to ground, first or second basement.
Lowest basement may not be premitted due to possibility of flooding.
Active Fire Safety Systems 9/29/2011
chong lee siong 28
6. DOWNCOMER SYSTEMS
Intended to provide water from roof fire tank to the floors on fire using static head available.
Only permitted for private residential buildings where the topmost floor is no higher than 60 m. above fire appliance access level.
Active Fire Safety Systems 9/29/2011
chong lee siong 29
LOCATION AND SPACING
Landing valves located within fire access lobbies
Provided on every upper floor such that all spaces are within 45 m from a landing valve.
Breeching inlet to be no more than 18 m. from fire appliance access road and not more than 30 meters from nearest outdoor hydrant.
DOWNCOMER TANKS
Tanks located on roof of building for maximum pressure.
Active Fire Safety Systems 9/29/2011
chong lee siong 30
196, 197 - smoke lobbies, protected lobbies
198, 199, 200, 201 – ventilation of stairs
229 – fire fighting lobbies
UBBL
Protection of stairs and lobbies
Protection of stairs and lobbies
Protected Lobby : protected lobby separated or isolated from fire and smoke infiltration
Smoke Lobby : a protected lobby primarily to isolate staircases from smoke infiltration
ventilated lobby : protected/smoke lobby by means of natural ventilation from outside
Fire Fighting Access Lobby : a protected lobby designed for fire fighting access
Active Fire Safety Systems 9/29/2011
chong lee siong 31
SMOKE CONTROL SYSTEMS
To control the spread of smoke from the source of fire to other occupied spaces and maintain visibility as much as possible during evacuation.
RELEVANT BY-LAWS
Under UBBL clauses 196 and 197 requires fire fighting access lobbies and smoke lobbies to be pressurized if natural ventilation cannot be provided.
Under UBBL clauses 200, 201 and 202 requires escape staircases to be pressurized if natural ventilation cannot be provided.
Active Fire Safety Systems 9/29/2011
chong lee siong 32
STAIRCASE PRESSURIZATION
Entire staircase pressurized with air.
Air pressure within staircase is controlled to permit opening of exit doors without the need of excessive force.
LIFT LOBBY PRESSURIZATION
Lift lobbies are individually pressurized with air.
Air pressure within lift lobbies is controlled to permit opening of exit doors without the need of excessive force.
Active Fire Safety Systems 9/29/2011
chong lee siong 33
Protected
lobby
requirement
for building >
18m
(By-Law 197)
External wall
Protected
lobby
requirement Building more than
18m above ground
level
No protected
lobby required
Ventilation opening
No protected
lobby required
Omission of
protected lobby
for pressurised
staircase for
buildings
below 45m For building
above
18m but below
45m
No protected
lobby
required
Ventilated
opening
Staircase
pressurised
Active Fire Safety Systems 9/29/2011
chong lee siong 34
Above 18m, need PROTECTION
Above 45m, need protection with
PRESSURISATION
Ventilation opening
No protected
lobby required
Protected
lobby to be
pressurised
Protected lobby
requirement for
building > 45m
[By-Law 197(2)]
PROTECTED / PRESSURISED
Active Fire Safety Systems 9/29/2011
chong lee siong 35
UBBL 229
EXTERNAL FIRE HYDRANTS
System of Pipe work connected to public water mains to provide water for the pumps in the fire engine.
For industrial plants, fire pumps have to be provided where flow is unreliable or pressure is inadequate
Active Fire Safety Systems 9/29/2011
chong lee siong 36
RELEVANT BY-LAWS
Under UBBL 225, every building shall be provided with at least one fire hydrant.
Active Fire Safety Systems 9/29/2011
chong lee siong 37
Hydrants should be located:
i) away from obstructions such as street furniture (benches), phone
booths, etc.
ii) not less than 2,000mm from adjacent buildings and overhangs.
iii) between 610mm to 2,400mm from Fire Appliance Access.
iv) away from risks of vehicular damage.
v) not more than 90m apart from each other (in new buildings adjacent
to existing developments, a new hydrant within 45m radius of the new
building).
Active Fire Safety Systems 9/29/2011
chong lee siong 38
No overhangs
over hydrants
Verandah
Pavement
Access
Hydrant
Building
EMERGENCY POWER SUPPLY
Intended to provide emergency power to operate all fire safety systems.
Under UBBL 253, emergency power is to be provided for fire pumps, fire lifts, fire alarm, smoke control, emergency lighting, voice communication, firemen intercom, etc.
Active Fire Safety Systems 9/29/2011
chong lee siong 39
SOURCES OF EMERGENCY POWER
Standby electrical generator with changeover switch activated upon power failure;
Battery banks with charger to maintain them in charged condition.
LOCATION
Generator to be located at ground or first basement for easy access by firemen.
Outdoor air required to cool diesel engine’s radiator.
Active Fire Safety Systems 9/29/2011
chong lee siong 40
INTEGRATION WITH PASSIVE SYSTEMS
Under UBBL clauses 136, limits of dimensions for compartmentation can be doubled with the provision of automatic sprinkler system.
INTEGRATION WITH PASSIVE SYSTEMS
Under UBBL clause 202, escape staircases have to be pressurized if inadequate natural ventilation is provided.
Likewise under UBBL clause 196(5), smoke lobbies have to be pressurized or ventilated if natural ventilation is inadequate.
Active Fire Safety Systems 9/29/2011
chong lee siong 41
INTEGRATION WITH PASSIVE SYSTEMS
Under UBBL clauses 250 for smoke venting, mechanically operated smoke vents have to be provided if there are inadequate openings for smoke venting.
INTERFACE WITH PASSIVE SYSTEMS
Under UBBL clauses 164(3), fire doors can be held open provided the device incorporates a heat activated mechanism to release the door.
However, this cannot be used for doors to protected corridors or staircases.
Active Fire Safety Systems 9/29/2011
chong lee siong 42
INTERFACE WITH PASSIVE SYSTEMS
Fire shutters to meet compartmentation requirements can be left open until activated by fire alarm.
Glass curtain walls can be utilized to contain smoke and fire if water spray or water curtain is provided to cool the glass.
FIRE APPLIANCE ACCESS
Refers to an area “Access Way” specifically allocated for the
parking of Bomba appliances during fire fighting and rescue operations. UBBL 140 “Access Way” (street, road or open space) is to be provided as a proportion of the perimeter of the building, with reference to the volume of the building.
Active Fire Safety Systems 9/29/2011
chong lee siong 43
EXTERNAL ACCESS
Access for emergency and rescue vehicles, equipment and personnel
•Roads •Pavements •Parking
Availability of water : •Hydrants •Storage tanks •Lakes, rivers, ponds
And access to fire fighting systems in the premises
Clarity of : •Type of building and function •Configuration of building •Location of fire control panel •Location of breaching inlets and pump rooms
AT THE PREMISES
Access into the building •Protected passage •Protected stairs •Firemen’s lift •Fire fighting lobby
Active Fire Safety Systems 9/29/2011
chong lee siong 44
Pressurised Hydrant System
Sprinkler System
Active Fire Safety Systems 9/29/2011
chong lee siong 45
Dry Riser system
Wet Riser System
Active Fire Safety Systems 9/29/2011
chong lee siong 46
External source of water
•Hydrants
•Lakes, Ponds, Pools, rivers
•Fire Tenders
Fire Fighting Appliance
on ‘Access Way’
Internal Systems
•Sprinklers
•Hose reels
•Dry/Wet Risers
Breaching Inlet
Vehicles in use by JBPM :
•Motorcycle
•Terrain buggy
•Rapid Fire Rescue Tender
•Fire Rescue Tender
•Turntable ladder
•Hydraulic platform
•Hazmat
Active Fire Safety Systems 9/29/2011
chong lee siong 47
Rapid response motorcycles
Terrain buggy
Active Fire Safety Systems 9/29/2011
chong lee siong 48
Rapid Fire Rescue Tender
Fire Rescue Tender (medium)
Active Fire Safety Systems 9/29/2011
chong lee siong 49
Fire Rescue Tender (light)
HAZMAT tender
Active Fire Safety Systems 9/29/2011
chong lee siong 50
Turntable ladders
Pump tanker
Active Fire Safety Systems 9/29/2011
chong lee siong 51
Hydraulic platforms
Fire appliance
access level and
Access Way
Access Way at upper ground level
Active Fire Safety Systems 9/29/2011
chong lee siong 52
13,000 m3 (1/6)
8,600m3 (1/6)
36,000m3 (1/4)
Access way at appliance access level
Access way at upper ground level
Access road / ramp Access road
/ ramp
Note: Turning provision required for fire appliances if dead end access
exceeds 18 m.
Turning provision can be in the form of hammer-head or turning
circle
Building volume
7,001 cu m
to 28,000 cu m
D
A
B
Isolated site/location
with no adjacent
property/building.
X => 1/6 (A+B+C+D)
Fire appliance
access X
C
Active Fire Safety Systems 9/29/2011
chong lee siong 53
C => 1/6 (A+B+C+D)
Appliance access from main road is sufficient if the building volume does not exceed
28,000 m3.
In the event the 6 m back lane is accessible by fire fighting appliances and the
building volume exceeds 28,000 m3 but is less than 56,000 m3, then,
A + C => 1/4 (A+B+C+D)
Building volume
7,001 cu m
to 28,000 cu m
City/Built up location
with adjacent buildings D
A
B
C
Accessible perimeter
of building
Main road used for
appliance access
if not less than 12m wide
Pavement
6m back lane
D
A
B
D
A
C
Access
road
> 18m
Building volume
56,001 cu m to
84,000 cu m
min. 6m
B + C => 1/2 (A+B+C+D)
C
Fire appliance access Access road
12m
B
6m back lane
accessible to fire appliance
Pavement
Access road
12m A + C => 1/2 (A+B+C+D)
Active Fire Safety Systems 9/29/2011
chong lee siong 54
D
Fire appliance
access minimum
6m width
Building volume
84,001 cu m to
112,000 cu m
A + B + C 3/4 (A+B+C+D)
A
B
C
Access road 12m
D
A
B
Building volume
84,001 cu m to
112,000 cu m
B + C + D => 3/4 (A+B+C+D)
C
Access road 12m
Active Fire Safety Systems 9/29/2011
chong lee siong 55
A
Building
volume
above
112,000 cu m
Minimum 6m width
Fire appliance access
D B
C
Access road 12m
W2
(min 6m)
L(13m)
L(13m) min. 6m W1
d1
d2
W = unobstructed width of Appliance Access
L = length of largest Fire Appliance (currently 13m)
d - cut-back distance is obtained by intersecting the imaginary corner of a
building with line A - C
The minimum permissible width of a Fire Appliance Access is 6.0m.
The minimum turning radius around corners of buildings shall be provided as follows:
Active Fire Safety Systems 9/29/2011
chong lee siong 56
Thank you !