designing a doas/radiant system for american univ. law school€¦ · [ashrae 62.1-2010 user’s...
TRANSCRIPT
Designing a DOAS/Radiant System for American Univ. Law School Cindy Cogil, PE LEED BD+C SmithGroupJJR
Building The Case for DOAS
2 11/12/2013 | Illinois ASHRAE
Law School Program
3 11/12/2013 | Illinois ASHRAE
Students
Library
Clinic
Faculty
Administration
Other
Instructional
Student Activities Library Career Center Faculty
Clinical Center Socratic Classroom Computer Lab Centers
Mock Trial Law Review Moot Court Food Service Events
Reading Room
Group Study
Law School Program
4 11/12/2013 | Illinois ASHRAE
Students
Library
Clinic
Faculty
Administration
Other
Instructional
Student Activities Library Career Center Faculty
Clinical Center Socratic Classroom Computer Lab Centers
Mock Trial Law Review Moot Court Food Service Events
Reading Room
Group Study
VAV Systems
5 11/12/2013 | Illinois ASHRAE
Multiple Spaces Equation - Excess OA Explained
AHU
Instructional
Library
Ext. Office - enclosed
Int. Office - enclosed
Building:System Tag/Name:Operating Condition Description:Units (select from pull-down list)
w /o diversity w / diversityInputs for System Name Units System Diversity System
Floor area served by system As sf 8250 Default entry has been overridden.Population of area served by system Ps P 110 D 85% 94 Default entry has been overridden.Design primary supply fan airflow rate Vpsd cfm 8,665 93% 8,058 Default entry has been overridden.OA req'd per unit area for system (Weighted average) Ras cfm/sf 0.08 Default entry has been overridden.OA req'd per person for system area (Weighted average) Rps cfm/p 6.5 Default entry has been overridden.Percent increase in Vbz over minimum required 0%
Inputs for Potentially Critical zones
Zone NameZone title turns purple italic for critical zone(s)
Lecture classroom
Library ext. office - enclosed
int. office - enclosed
Zone Tag Z-1 Z-2 Z-3 Z-4
Occupancy CategorySelect from pull-down list:
Lecture classroom
Libraries Office space Office space
Floor Area of zone Az sf 1,650 2475 2,063 2,063Design population of zone Pz P (default value listed; may be overridden) 65 24.75 10.3125 10.3125Design total supply to zone (primary plus local recirculated) Vdzd cfm 1,570 2970 2,269 1,856Induction Terminal Unit, Dual Fan Dual Duct or Transfer Fan? Select from pull-down list or leave blank if N/A: Induction Termi Induction Termi Induction Termi Frac. of local recirc. air that is representative of system RA Er 0.50 0.50 0.50 0.50
Inputs for Operating Condition AnalyzedPercent of total design airflow rate at conditioned analyzed Ds % May need to manually edit Ds: 100% 100% 100% 80% 80%Air distribution type at conditioned analyzed Select from pull-down list: CS CS CS CSZone air distribution effectiveness at conditioned analyzed Ez 1.00 1.00 1.00 1.00Primary air fraction of supply air at conditioned analyzed Ep 1.00 1.00 1.00 1.00
ResultsSystem Ventilation Efficiency Ev 0.78Outdoor air intake required for system Vot cfm 1600Outdoor air per unit floor area Vot /As cfm/sf 0.19Outdoor air per person served by system (including diversity) Vot /Ps cfm/p 17.1Outdoor air as a % of design primary supply air Ypd % 18%
Potentially Critical Zones
Law School Sample ProgramAHU-1Design cooling w/critical zone at min. airflowIP
Add Zone
Show Values per Zone
Show codes for Ez
Delete Zone
VAV – Design Cooling Minimum Ventilation Requirements
6 11/12/2013 | Illinois ASHRAE
Building:System Tag/Name:Operating Condition Description:Units (select from pull-down list)
w /o diversity w / diversityInputs for System Name Units System Diversity System
Floor area served by system As sf 8250.5 Default entry has been overridden.Population of area served by system Ps P 110 D 85% 94 Default entry has been overridden.Design primary supply fan airflow rate Vpsd cfm 8,665 93% 8,058 Default entry has been overridden.OA req'd per unit area for system (Weighted average) Ras cfm/sf 0.08 Default entry has been overridden.OA req'd per person for system area (Weighted average) Rps cfm/p 6.5 Default entry has been overridden.Percent increase in Vbz over minimum required 0%
Inputs for Potentially Critical zones
Zone NameZone title turns purple italic for critical zone(s)
Lecture classroom
Library ext. office - enclosed
int. office - enclosed
Zone Tag Z-1 Z-2 Z-3 Z-4
Occupancy CategorySelect from pull-down list:
Lecture classroom
Libraries Office space Office space
Floor Area of zone Az sf 1,650 2475 2,063 2,063Design population of zone Pz P (default value listed; may be overridden) 65 24.75 10.315 10.3125Design total supply to zone (primary plus local recirculated) Vdzd cfm 1,570 2970 2,269 1,856Induction Terminal Unit, Dual Fan Dual Duct or Transfer Fan? Select from pull-down list or leave blank if N/A: Induction Termi Induction Termi Induction Termi Frac. of local recirc. air that is representative of system RA Er 0.50 0.50 0.50 0.50
Inputs for Operating Condition AnalyzedPercent of total design airflow rate at conditioned analyzed Ds % May need to manually edit Ds: 23% 100% 100% 100% 80%Air distribution type at conditioned analyzed Select from pull-down list: CSCRW CSCRW CSCRW CSZone air distribution effectiveness at conditioned analyzed Ez 1.00 1.00 1.00 1.00Primary air fraction of supply air at conditioned analyzed Ep 0.25 0.00 0.00 1.00
ResultsSystem Ventilation Efficiency Ev 0.67Outdoor air intake required for system Vot cfm 1870Outdoor air per unit floor area Vot /As cfm/sf 0.23Outdoor air per person served by system (including diversity) Vot /Ps cfm/p 19.9Outdoor air as a % of design primary supply air Ypd % 22%
Potentially Critical Zones
Law School Sample ProgramAHU-1Design heatingIP
Add Zone
Show Values per Zone
Show codes for Ez
Delete Zone
VAV – Design Heating Minimum Ventilation Requirements
7 11/12/2013 | Illinois ASHRAE
DESIGN OUTSIDE AIRFLOW
VAV Systems
8 11/12/2013 | Illinois ASHRAE
Multiple Spaces Equation – Excess OA Explained
AHU
Instructional
Library
Ext. Office - enclosed
Int. Office - enclosed
541 388 161 161
1570
1877 1870
7
1870 (619 CFM unvitiated)
412
1158 2970
0
2970 2269
0
2269
1856
Series fan-powered box (typ of 3) to comply with ASHRAE Std. 62.1 & 90.1
VAV Systems
9 11/12/2013 | Illinois ASHRAE
Uncertainly in Multiple Space Analysis
AHU
Instructional
Library
Ext. Office - enclosed
Int. Office - enclosed
541 388 161 161
1570
1877 1870
7
1870 (619 CFM unvitiated)
412
1158 2970
0
2970 2269
0
2269
1856
Fraction of local recirculation air that is representative of system? RA = 0.5?
ASHRAE RP-1276
10 11/12/2013 | Illinois ASHRAE
Fraction of local recirculated air that is representative of system RA, Er
Ventilation Rate Procedure Flow Chart
11 11/12/2013 | Illinois ASHRAE
Multi-Zone Recirculating vs. DOAS
DOAS
Multi-Zone Recirculating
Determine max zone OA ratio, Zp
Determine ventilation efficiency, Ev
Determine occupant diversity, D
Calculate uncorrected OA, Vou
Vot = Vou/Ev
“Calculating ventilation rates for multiple zone systems can be complex and requires considerable judgment on the part of the designer.” [ASHRAE 62.1-2010 User’s Manual]
Building:System Tag/Name:Operating Condition Description:Units (select from pull-down list)
w /o diversity w / diversityInputs for System Name Units System Diversity System
Floor area served by system As sf 8250 Default entry has been overridden.Population of area served by system Ps P 110 D 100% 110 Default entry has been overridden.Design primary supply fan airflow rate Vpsd cfm 1,362 100% 1,362 Default entry has been overridden.OA req'd per unit area for system (Weighted average) Ras cfm/sf 0.08 Default entry has been overridden.OA req'd per person for system area (Weighted average) Rps cfm/p 6.5 Default entry has been overridden.Percent increase in Vbz over minimum required 0%
Inputs for Potentially Critical zones
Zone NameZone title turns purple italic for critical zone(s)
Lecture classroom
Library ext. office - enclosed
int. office - enclosed
Zone Tag Z-1 Z-2 Z-3 Z-4
Occupancy CategorySelect from pull-down list:
Lecture classroom
Libraries Office space Office space
Floor Area of zone Az sf 1,650 2475 2,063 2,063Design population of zone Pz P (default value listed; may be overridden) 65 24.75 10.3125 10.3125Design total supply to zone (primary plus local recirculated) Vdzd cfm 588 422 176 176Induction Terminal Unit, Dual Fan Dual Duct or Transfer Fan? Select from pull-down list or leave blank if N/A: Frac. of local recirc. air that is representative of system RA Er 0.50 0.50 0.50 0.50
Inputs for Operating Condition AnalyzedPercent of total design airflow rate at conditioned analyzed Ds % May need to manually edit Ds: 100% 100% 100% 100% 100%Air distribution type at conditioned analyzed Select from pull-down list: CS CS CS CSZone air distribution effectiveness at conditioned analyzed Ez 1.00 1.00 1.00 1.00Primary air fraction of supply air at conditioned analyzed Ep 1.00 1.00 1.00 1.00
ResultsSystem Ventilation Efficiency Ev 1.00Outdoor air intake required for system Vot cfm 1359Outdoor air per unit floor area Vot /As cfm/sf 0.16Outdoor air per person served by system (including diversity) Vot /Ps cfm/p 12.3Outdoor air as a % of design primary supply air Ypd % 100%
Potentially Critical Zones
Law School Sample ProgramDOAS-1Design cooling w/critical zone at min. airflowIP
Add Zone
Show Values per Zone
Show codes for Ez
Delete Zone
DOAS Minimum Ventilation Requirements
12 11/12/2013 | Illinois ASHRAE
27% SAVINGS COMPARED TO VAV
Dedicated Outside Air Systems
13 11/12/2013 | Illinois ASHRAE
Key Features
• 100% OA distributed by ductwork to each zone
• Flow rate to each zone as required to ventilate and handle latent load
• Requires TER, per ASHRAE 90.1 • Decouples S/L loads in the space • OA supplied below space neutral
temperature
DOAS Unit w/ER
Building w/Decoupled
Sensible and Latent Cooling
Cool/Dry Vent/Latent
Parallel Sensible Cooling System
Minimum Ventilation Requirements
14 11/12/2013 | Illinois ASHRAE
DOAS Supply Air Conditions
55F DPT / 64.5 grains
47F DPT / 47.9 grains
Maximum CFM required to: • Handle space latent load at desired space humidity ratio • Comply with ASHRAE 62.1
SF/# OA/# OA/SF # (1000 SF)ASHRAE 62.1 OA (1000 SF)
Cumulative OA/#
Latent Load, Btuh Wroom Wprimary DPTPrimary
Cumulative OA/# OA Wprimary DPTPrimary
% OA increase
Auditorium/Lecture Hall 25 7.5 0.06 40 360 9 6,200 64.5 39 41.7 14 560 48 47.1 56%Library 100 5 0.12 10 170 17 1,550 64.5 51 48.7 17 170 51 48.7 0%
Private Office 200 5 0.06 5 85 17 775 64.5 51 48.7 17 85 51 48.7 0%SA DPT 45-53F; need desiccant for SA DPT <=40F
Supply Air DPT DOAS
15 11/12/2013 | Illinois ASHRAE
QL=CFM*0.68*(Wroom – Wprimary)
DOAS vs. VAV Minimum Ventilation Requirements
16 11/12/2013 | Illinois ASHRAE
Lecture Classroom Library Ext. Office – enclosed
Int. Office – enclosed
Total OA Intake Required for System
VAV System (ASHRAE Std. 62.1)
1870
DOAS (ASHRAE Std. 62.1)
587 421 175 175 1358 (-27%)
DOAS (Latent Load)
893 340 142 142 1516 (-19%)
DOAS (Design) 893 421 175 175 1664 (-11%)
Parallel Sensible Conditioning
17 11/12/2013 | Illinois ASHRAE
Options
Fan Coil Unit
Radiant Ceiling Panel
Parallel VAV AHU
Variable Refrigerant Volume Heat Pumps
Parallel Sensible Conditioning
18 11/12/2013 | Illinois ASHRAE
Options
Fan Coil Unit
Radiant Ceiling Panel
Parallel VAV AHU
Variable Refrigerant Volume Heat Pumps
Noise / Space Space/Control
Aesthetics
Radiant Ceiling Panels
19 11/12/2013 | Illinois ASHRAE
Key Features
• Low mass / fast response • Active panel area limited to < 70%
ceiling area • Quiet operation • Increased zoning potential • Accommodates low floor-to-floor heights • Requires dew point monitoring
Air Handling Unit Selection
20 11/12/2013 | Illinois ASHRAE
DOAS
DOAS AHU
21 11/12/2013 | Illinois ASHRAE
Low Temp Supply
48 47
• Requires cold chilled water temp (potential chiller efficiency penalty) •High aspirating diffusers •May reduce active panel area for cooling load dominated
spaces, especially where ventilation rates can be reset • Can use standard AHU manufacturers
DOAS AHU
22 11/12/2013 | Illinois ASHRAE
Slightly Lower than Space Neutral Supply
•Dual Wheel (passive dehumidification) • PDW dehumidifies and reheats (saves cooling capacity) •Uses conventional CHWS/R, more efficient chiller • Custom, proprietary equipment • TER in custom unit typically has higher efficiency than
in non-custom unit
DOAS AHU
23 11/12/2013 | Illinois ASHRAE
Slightly Lower than Space Neutral Supply
Total energy wheel
Sensible energy wheel
•Dual Wheel (sensible) • Requires cold chilled water temp (potential chiller
efficiency penalty) • Custom AHU equipment • TER in custom unit typically has higher efficiency
than in non-custom unit
DOAS AHU
24 11/12/2013 | Illinois ASHRAE
Slightly Lower than Space Neutral Supply
•Heat Pipe • Requires cold chilled water temp (potential chiller
efficiency penalty) • TER in custom unit typically has higher efficiency
than in non-custom unit • Lower maintenance than dual wheel • Slightly larger unit
Water Side Selection
25 11/12/2013 | Illinois ASHRAE
Secondary Chilled Water Circuit
26 11/12/2013 | Illinois ASHRAE
Separate, Dedicated Secondary Chiller Plant
Secondary Chilled Water Circuit
27 11/12/2013 | Illinois ASHRAE
Plate Heat Exchanger
Secondary Chilled Water Circuit
28 11/12/2013 | Illinois ASHRAE
Mixing/Injection Valve
Mixing / Injection Valve
Secondary Chilled Water Pump
Radiant Ceiling Panel
29 11/12/2013 | Illinois ASHRAE
Design Considerations
• Capacity is a function of installation • Be cautious of minimum mass flow
rates to maintain turbulence • Limit maximum circuit pressure
drop to 6-7 ft. wg (2-4 panels in series)
Capacity Correction Factors
Schematic Design – HVAC Analysis
30 11/12/2013 | Illinois ASHRAE
High Efficiency DOAS/Radiant vs. High Efficiency VAV
DOAS/Radiant
31 11/12/2013 | Illinois ASHRAE
Floor 1
Floor 3
Floor 4
Floor LL
Floor 2
DOAS/Radiant
32 11/12/2013 | Illinois ASHRAE
VAV
33 11/12/2013 | Illinois ASHRAE
Floor 1
Floor 3
Floor 4
Floor LL
Floor 2
VAV SYSTEM Yuma Flrs LL, 1 Law Library Nebraska Yuma Flrs 2, 3 Yuma Flr 4 AHU-1-1 ERAHU-2 ERAHU-3 AHU-1-2 AHU-1-3
Peak Population 1506 1394 1394 409 325
Area, sf 59889 58997 26853 63831 14064
Design Supply Air 38110 45870 20620 47200 14840
VAV
34 11/12/2013 | Illinois ASHRAE
Initial Costs
35 11/12/2013 | Illinois ASHRAE
Energy Consumption
36 11/12/2013 | Illinois ASHRAE
Energy Costs
37 11/12/2013 | Illinois ASHRAE
Life-Cycle Costs
38 11/12/2013 | Illinois ASHRAE
End of Study 8/1/40
DOAS Supply Air Temperature
39 11/12/2013 | Illinois ASHRAE
Optimization
• Low temperature supply can result in overcooling and higher reheat loads for certain space types where internal and envelope sensible cooling loads are low
• By adjusting the supply air upwards to ~66F, we decreased total active surface area by 13.7%.
BIM Documentation
40 11/12/2013 | Illinois ASHRAE
Lessons Learned
BIM Documentation
41 11/12/2013 | Illinois ASHRAE
Workflow Graphics
BIM Documentation
42 11/12/2013 | Illinois ASHRAE
RCP Family Building
BIM Documentation
43 11/12/2013 | Illinois ASHRAE
Ductwork Plan Piping Plan RCP Plan
BIM Documentation
44 11/12/2013 | Illinois ASHRAE
Ceiling Coordination Exit Signs
Projector Screens
Wall Wash Lighting
Sprinklers
Radiant Ceiling Panels
Ceiling Cameras
Metal Infill
Recessed Lighting
Projectors
Wireless Access Points
Ceiling Speakers
Questions?
45 11/12/2013 | Illinois ASHRAE
Condensation Prevention
46 11/12/2013 | Illinois ASHRAE
Step 1: Condensation Prevention • Fix windows closed • Construct a tightly sealed building • Use airlocks/vestibules at main entrances • Maintain CRCP surface temperature above space dewpoint temperature (DPT) Step 2: Condensation Control • Multi-zone system strategy (Variable flow/constant temp)
1. Proximity switches detect open windows (more cost-effective than individual zone DPT sensors and faster reacting)
2. Then, if OA DPT exceeds space design DPT, the CRCP control valve serving that specific zone or collection of zones would be closed
3. Once windows return to closed position, the valve is permitted to modulate again following suitable time delay or confirmation that DOAS has returned space to design DPT
Condensation Prevention
47 11/12/2013 | Illinois ASHRAE
Cooling Only & Heating/Cooling RCPs
48 11/12/2013 | Illinois ASHRAE
Occupant-Based Controls
49 11/12/2013 | Illinois ASHRAE