design manual...design manual rweq-tatju, 208 / 230 v rweq-taydu, 460 v rweq-taycu, 575 v...

116
Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz

Upload: others

Post on 11-Nov-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

Design ManualRWEQ-TATJU, 208 / 230 VRWEQ-TAYDU, 460 VRWEQ-TAYCU, 575 V

EDUS301864-D201812

Engineering Data

Heat Pump 60 HzHeat Recovery 60 Hz

Page 2: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …
Page 3: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

1

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ-TATJU (208 / 230 V, 60 Hz)RWEQ-TAYDU (460 V, 60 Hz)RWEQ-TAYCU (575 V, 60 Hz)

1. FeaturesandBenefits ................................................................................32. Nomenclature .............................................................................................43. Model Names of Indoor Unit and Outside Unit ...........................................8

3.1 Outside Units ....................................................................................83.2 Indoor Units .....................................................................................103.3 Branch Selector Unit .......................................................................103.4 Air Treatment Equipment ................................................................11

4. External Appearance ................................................................................124.1 Outside Units ..................................................................................124.2 Indoor Units .....................................................................................134.3 Branch Selector Unit .......................................................................144.4 Air Treatment Equipment ................................................................14

5. Outside Unit Combination ........................................................................156. Interchangeability .....................................................................................167. Capacity Range ........................................................................................17

7.1 Connection Ratio ............................................................................177.2 Indoor Unit Connection Capacity ....................................................187.3 Limitation of Capacity Index for Heat Recovery ..............................19

8. Specifications ...........................................................................................208.1 RWEQ-TATJU ................................................................................208.2 RWEQ-TAYDU ...............................................................................348.3 RWEQ-TAYCU ...............................................................................48

9. Dimensions ...............................................................................................6210. Service Space ..........................................................................................6511. Center of Gravity ......................................................................................6612. Piping Diagrams .......................................................................................6713. Wiring Diagrams .......................................................................................6814. Field Wiring ..............................................................................................74

14.1 Heat Pump ......................................................................................7414.2 Heat Recovery ................................................................................77

15. Electrical Characteristics ..........................................................................8016. Operation Limits .......................................................................................83

16.1 Heat Pump ......................................................................................8316.2 Heat Recovery ................................................................................84

Page 4: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

2

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

17. Operation Limits (Antifreeze Usage) ........................................................8517.1 Heat Pump ......................................................................................8517.2 Heat Recovery ................................................................................86

18. Sound Levels (Reference Data) ...............................................................8719. Accessories ..............................................................................................90

19.1 Optional Accessories ......................................................................9020. Selection Procedure .................................................................................91

20.1 Selection Procedure ........................................................................9121. Instructions for Antifreeze Usage .............................................................97

21.1 Instruction of Setting Water (Brine) Lower Flow Limit % for Variable Flow System .....................................................................97

22. Caution for Refrigerant Leaks ..................................................................9922.1 Introduction .....................................................................................9922.2 Procedure for Checking Maximum Concentration ........................100

23. Safety Devices Setting ...........................................................................10223.1 FXFQ-T .........................................................................................10223.2 FXZQ-TA .......................................................................................10223.3 FXUQ-P ........................................................................................10223.4 FXEQ-P .........................................................................................10223.5 FXDQ-M ........................................................................................10323.6 FXSQ-TA ......................................................................................10323.7 FXMQ-PB ......................................................................................10323.8 FXMQ-M .......................................................................................10323.9 FXHQ-M ........................................................................................10423.10 FXAQ-P .......................................................................................10423.11 FXLQ-M, FXNQ-M .......................................................................10423.12 FXTQ-TA .....................................................................................104

Appendix......................................................................................................1051. Introduction .............................................................................................106

1.1 ED Book List .................................................................................1061.2 Publication List of Engineering Data for VRV Products ................107

2. GuideSpecifications ...............................................................................1092.1 GuideSpecifications .....................................................................109

Page 5: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

3

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

1. Features and Benefits

• Wide offering with 8, 10 and 12 ton single module and up to 36¹ tons with multi-module • Flexible System design with increased diversity up to 150%² • Up to 50%² and 38%² reduction in space and weight respectively to install systems of similar

capacity when compared to RWEYQ-PC series • Triple-stack capable to deliver up to 36¹ tons in 3.2 m (10.5 ft.) ceiling height•Flexibleandeasyinstallationwithfieldselectabletoporfrontrefrigerantconnections•Designflexibilitywithlongpipinglengthsupto300m(980ft.)total(165m(540ft.)max.linear

liquid piping length) and up to 30 m (100 ft.) vertical separation between indoor units• Engineered with heat rejection cancelation technology³ to minimize mechanical room conditioning

requirements•YearroundcomfortandenergyefficiencybycombiningVRV and Variable Refrigerant

Temperature (VRT) technologies•2-9Vvariablewaterflowcontrollogicasstandardtoincreasewatersidesystemoperationalefficiencies

• Refrigerant cooled inverter technology to deliver consistent and reliable printed circuit board operations

• Factory ships ready for Geothermal applications •Easycommissioningwithabilitytoprogramsettingsoffsiteusingnewconfiguratortool•3-digit7-segmentdigitaldisplayontheunitforimprovedandfasterconfiguration,commissioning,

and troubleshooting• Engineered for easy service with drop-down electrical box to access key components• Seamless integration to full suite of Daikin Control Solutions for complete system control• Backed by 10 year parts limited warranty and 10 years replacement compressor limited

warranty *

¹ - 35.5 ton for 575 V units²-Modelspecific,checkproductspecificationfordetails³-Refertoinstallationmanualforfieldsettingsrequiredtoactivatethisfeature* Complete warranty details available from local distributor or manufacturer's representative

Page 6: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

4

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

2. Nomenclature

Outside Unit

Standard symbolU: United States of America

Power supply symbolTJ: 3 phase, 208/230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 Hz

Indicates minor change category

Indicates major design category

Capacity indication in cooling96: 96,000 Btu/h 288: 288,000 Btu/h120: 120,000 Btu/h 312: 312,000 Btu/h144: 144,000 Btu/h 336: 336,000 Btu/h192: 192,000 Btu/h 360: 360,000 Btu/h216: 216,000 Btu/h 384: 384,000 Btu/h240: 240,000 Btu/h 408: 408,000 Btu/h264: 264,000 Btu/h 432: 432,000 Btu/h, 426,000 Btu/h for 575 V units

RefrigerantQ: R410A

Indicates that this is aRWE: Heat pump / Heat recovery water cooled

Q YC UT A432RWE

Page 7: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

5

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Indoor Unit

M 54 VJPB UX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Capacity indication in cooling05: 5,800 Btu/h 18: 18,000 Btu/h 48: 48,000 Btu/h07: 7,500 Btu/h 24: 24,000 Btu/h 54: 54,000 Btu/h09: 9,500 Btu/h 30: 30,000 Btu/h 60: 60,000 Btu/h12: 12,000 Btu/h 36: 36,000 Btu/h 72: 72,000 Btu/h15: 15,000 Btu/h 42: 42,000 Btu/h 96: 96,000 Btu/h

RefrigerantQ: R410A

ShapeF: Ceiling mounted cassette (Round flow with sensing)Z: VISTA™ 2 × 2 cassette unitU: 4-way blow ceiling-suspendedE: One way blow cassetteD: Slim ceiling mounted ductS: MSP concealed ducted unitM: Ceiling mounted ductH: Ceiling suspendedA: Wall mountedL: Floor standingN: Concealed floor standingT: Air handling unit

Series categoryX: Inverter

Unit categoryF: Indoor unit for air cooled type

Page 8: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

6

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Branch Selector Unit

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Capacity indication36: 36,000 Btu/h60: 60,000 Btu/h96: 96,000 Btu/h

Refrigerant: R410A

Unit categoryBS: Branch selector unit

BS T VJQ 36

Single Branch Selector Unit (only necessary for Heat Recovery System)

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Capacity indication of connectable indoor units per branch

Refrigerant: R410A

Number of branches4: 4 branches 10: 10 branches6: 6 branches 12: 12 branches8: 8 branches

Unit categoryBS: Branch selector unit

BS T VJQ12 54

Multi Branch Selector Unit (only necessary for Heat Recovery System)

Page 9: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

7

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Air Treatment Equipment

M 48 VJ UM FX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Outdoor air processing unit

Indicates major design category

Capacity indication in cooling48: 48,000 Btu/h72: 72,000 Btu/h96: 96,000 Btu/h

RefrigerantQ: R410A

ShapeM: Ceiling mounted duct

Series categoryX: Inverter

Unit categoryF: Indoor unit for air cooled type

Outdoor Air Processing Unit

UG300V A M VJ

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 Hz

Indicates major design category

Airflow rate (H)300: 300 cfm 600: 600 cfm470: 470 cfm 1200: 1,200 cfm

Mounted type

Air

Ventilation

Energy Recovery Ventilator (VAM series)

Page 10: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

8

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

3. Model Names of Indoor Unit and Outside Unit3.1 Outside Units

Capacity range 8 ton 10 ton 12 ton 16 ton 18 ton 20 ton 22 ton Power supply, StandardCapacity index 96 120 144 192 216 240 264

Heat pump / Heat recovery 208/230 V RWEQ 96TA 120TA 144TA 192TA 216TA 240TA 264TA TJUHeat pump / Heat recovery 460 V RWEQ 96TA 120TA 144TA 192TA 216TA 240TA 264TA YDUHeat pump / Heat recovery 575 V RWEQ 96TA 120TA 144TA 192TA 216TA 240TA 264TA YCU

Capacity range 24 ton 26 ton 28 ton 30 ton 32 ton 34 ton 36 ton * Power supply, StandardCapacity index 288 312 336 360 384 408 432

Heat pump / Heat recovery 208/230 V RWEQ 288TA 312TA 336TA 360TA 384TA 408TA 432TA TJUHeat pump / Heat recovery 460 V RWEQ 288TA 312TA 336TA 360TA 384TA 408TA 432TA YDUHeat pump / Heat recovery 575 V RWEQ 288TA 312TA 336TA 360TA 384TA 408TA 432TA YCU

* 35.5 ton for 575 V units

TJ : 3 phase, 208/230 V, 60 HzYD : 3 phase, 460 V, 60 HzYC : 3 phase, 575 V, 60 HzU(TJU) : Standard symbol

Heat Pump / Heat Recovery 208/230 V

Model name RWEQ96TATJU RWEQ120TATJU RWEQ144TATJUOutside unit 1 RWEQ96TATJU RWEQ120TATJU RWEQ144TATJU

Model name RWEQ192TATJU RWEQ216TATJU RWEQ240TATJU RWEQ264TATJU RWEQ288TATJUOutside unit 1 RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU RWEQ144TATJUOutside unit 2 RWEQ96TATJU RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU

Model name RWEQ312TATJU RWEQ336TATJU RWEQ360TATJU RWEQ384TATJU RWEQ408TATJU RWEQ432TATJUOutside unit 1 RWEQ120TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU RWEQ144TATJU RWEQ144TATJUOutside unit 2 RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU RWEQ144TATJUOutside unit 3 RWEQ96TATJU RWEQ96TATJU RWEQ120TATJU RWEQ120TATJU RWEQ120TATJU RWEQ144TATJU

Heat Pump / Heat Recovery 460 V

Model name RWEQ96TAYDU RWEQ120TAYDU RWEQ144TAYDUOutside unit 1 RWEQ96TAYDU RWEQ120TAYDU RWEQ144TAYDU

Model name RWEQ192TAYDU RWEQ216TAYDU RWEQ240TAYDU RWEQ264TAYDU RWEQ288TAYDUOutside unit 1 RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ144TAYDUOutside unit 2 RWEQ96TAYDU RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU

Model name RWEQ312TAYDU RWEQ336TAYDU RWEQ360TAYDU RWEQ384TAYDU RWEQ408TAYDU RWEQ432TAYDUOutside unit 1 RWEQ120TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ144TAYDU RWEQ144TAYDUOutside unit 2 RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ144TAYDUOutside unit 3 RWEQ96TAYDU RWEQ96TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ120TAYDU RWEQ144TAYDU

Page 11: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

9

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Heat Pump / Heat Recovery 575 V

Model name RWEQ96TAYCU RWEQ120TAYCU RWEQ144TAYCUOutside unit 1 RWEQ96TAYCU RWEQ120TAYCU RWEQ144TAYCU

Model name RWEQ192TAYCU RWEQ216TAYCU RWEQ240TAYCU RWEQ264TAYCU RWEQ288TAYCUOutside unit 1 RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU RWEQ144TAYCUOutside unit 2 RWEQ96TAYCU RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU

Model name RWEQ312TAYCU RWEQ336TAYCU RWEQ360TAYCU RWEQ384TAYCU RWEQ408TAYCU RWEQ432TAYCUOutside unit 1 RWEQ120TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU RWEQ144TAYCU RWEQ144TAYCUOutside unit 2 RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU RWEQ144TAYCUOutside unit 3 RWEQ96TAYCU RWEQ96TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ120TAYCU RWEQ144TAYCU

Page 12: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

10

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

3.2 Indoor Units

Capacity range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power supply, StandardCapacity index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96

Ceiling mounted cassette (Roundflowwithsensing)type

FXFQ — 07T 09T 12T 15T 18T — 24T 30T 36T — 48T — — — —

VJU

VISTA™ 2 × 2 cassette unit FXZQ 05TA 07TA 09TA 12TA 15TA 18TA — — — — — — — — — —4-way blow ceiling-suspended type FXUQ — — — — — — 18P 24P 30P 36P — — — — — —

One way blow cassette type FXEQ — 07P 09P 12P 15P 18P — 24P — — — — — — — —Slim ceiling mounted duct type FXDQ — 07M 09M 12M — 18M — 24M — — — — — — — —

MSP concealed ducted unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA — 24TA 30TA 36TA — 48TA 54TA — — —Ceiling mounted duct type (Middle and high static pressure)

FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — —

Ceiling mounted duct type FXMQ — — — — — — — — — — — — — — 72M 96MCeiling suspended type FXHQ — — — 12M — — — 24M — 36M — — — — — —Wall mounted type FXAQ — 07P 09P 12P — 18P — 24P — — — — — — — —Floor standing type FXLQ — 07M 09M 12M — 18M — 24M — — — — — — — —Concealedfloorstandingtype FXNQ — 07M 09M 12M — 18M — 24M — — — — — — — —

Air handling unit FXTQ— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUA— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUD

VJ : 1 phase, 208/230 V, 60 HzU(VJU) : Standard symbol

3.3 Branch Selector UnitSingle Branch Selector Unit for Heat Recovery

Series Model name Power supply, StandardHeat recovery BSQ 36T 60T 96T VJ

Note: No interchangeability between BSVQ-PVJU and BSQ-TVJ.

VJ: 1 phase, 208/230 V, 60 Hz

Multi Branch Selector Unit for Heat Recovery

Series Model name Power supply, StandardHeat recovery BS 4Q54T 6Q54T 8Q54T 10Q54T 12Q54T VJ

Note: No interchangeability between BSV-Q36PVJU and BS-Q54TVJ.

VJ: 1 phase, 208/230 V, 60 Hz

Page 13: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

11

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

3.4 Air Treatment EquipmentOutdoor Air Processing Unit

Series Model name Power supply, StandardFXMQ 48MF 72MF 96MF VJU

VJ : 1 phase, 208/230 V, 60 HzU(VJU) : Standard symbol

Energy Recovery Ventilator (VAM series)

Series Model name Power supply, StandardVAM 300G 470G 600G 1200G VJU

VJ : 1 phase, 208/230 V, 60 HzU(VJU) : Standard symbol

Page 14: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

12

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

4. External Appearance4.1 Outside UnitsSingle Outside Units

RWEQ96TAYDURWEQ120TAYDURWEQ144TAYDU

8, 10, 12 ton

RWEQ96TATJURWEQ120TATJURWEQ144TATJU

RWEQ96TAYCURWEQ120TAYCURWEQ144TAYCU

Double Outside Units

RWEQ192TAYDU RWEQ264TAYDURWEQ216TAYDU RWEQ288TAYDURWEQ240TAYDU

RWEQ192TAYCU RWEQ264TAYCURWEQ216TAYCU RWEQ288TAYCURWEQ240TAYCU

RWEQ192TATJU RWEQ264TATJURWEQ216TATJU RWEQ288TATJURWEQ240TATJU

16, 18, 20, 22, 24 ton

Triple Outside Units

26, 28, 30, 32, 34, 36 * ton

RWEQ312TAYDU RWEQ384TAYDURWEQ336TAYDU RWEQ408TAYDURWEQ360TAYDU RWEQ432TAYDU

RWEQ312TAYCU RWEQ384TAYCURWEQ336TAYCU RWEQ408TAYCURWEQ360TAYCU RWEQ432TAYCU

RWEQ312TATJU RWEQ384TATJURWEQ336TATJU RWEQ408TATJURWEQ360TATJU RWEQ432TATJU

* 35.5 ton for 575 V units

Page 15: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

13

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

4.2 Indoor Units

Ceilingmountedcassette(Roundflowwithsensing)type

FXFQ-T

Shown with BYCQ125B-W1

Ceiling mounted duct type

FXMQ-M

VISTA™ 2 × 2 cassette unit

FXZQ-TA

Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S

Ceiling suspended type

FXHQ-M

4-way blow ceiling-suspended type

FXUQ-P

Wall mounted type

FXAQ-P

One way blow cassette type

FXEQ-P

Floor standing type

FXLQ-M

Slim ceiling mounted duct type

FXDQ-M

Concealedfloorstandingtype

FXNQ-M

MSP concealed ducted unit

FXSQ-TA

Air handling unit

FXTQ-TA

Ceiling mounted duct type (Middle and high static pressure)

FXMQ-PB

Page 16: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

14

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

4.3 Branch Selector Unit

Single branch selector unit

BSQ-T

Multi branch selector unit

BS-Q54TVJ

4.4 Air Treatment Equipment

Outdoor air processing unit

FXMQ-MF

Energy recovery ventilator (VAM series)

VAM-G

Page 17: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

15

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

5. Outside Unit Combination

Model nameSystem capacity Number of

unitsModule Outside unit multi connection piping

kit *1Ton HP kW 96 120 144RWEQ96TATJURWEQ96TAYDURWEQ96TAYCU

8 10.0 28.1 1 l

—RWEQ120TATJURWEQ120TAYDURWEQ120TAYCU

10 12.5 35.2 1 l

RWEQ144TATJU RWEQ144TAYDURWEQ144TAYCU

12 15.0 42.2 1 l

RWEQ192TATJURWEQ192TAYDURWEQ192TAYCU

16 20.0 56.3 2 ll

Heat pump: BHFP22T84UHeat recovery: BHFP26T84U

RWEQ216TATJURWEQ216TAYDURWEQ216TAYCU

18 22.5 63.3 2 l l

RWEQ240TATJURWEQ240TAYDURWEQ240TAYCU

20 25.0 70.3 2 ll

RWEQ264TATJURWEQ264TAYDURWEQ264TAYCU

22 27.5 77.4 2 l l

RWEQ288TATJURWEQ288TAYDURWEQ288TAYCU

24 30.0 84.4 2 ll

RWEQ312TATJURWEQ312TAYDURWEQ312TAYCU

26 32.5 91.4 3 ll l

Heat pump: BHFP22T126UHeat recovery: BHFP26T126U

RWEQ336TATJURWEQ336TAYDURWEQ336TAYCU

28 35.0 98.5 3 l ll

RWEQ360TATJURWEQ360TAYDURWEQ360TAYCU

30 37.5 105.5 3 lll

RWEQ384TATJURWEQ384TAYDURWEQ384TAYCU

32 40.0 112.5 3 ll l

RWEQ408TATJURWEQ408TAYDURWEQ408TAYCU

34 42.5 119.6 3 l ll

RWEQ432TATJURWEQ432TAYDURWEQ432TAYCU

36 *2 45.0 126.6 3 lll

Notes:*1. For multiple connection, the outside unit multi connection piping kit (separately sold) is required.*2. 35.5 ton for 575 V units

Page 18: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

16

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

6. Interchangeability

Branch selector unit

Outside unit

T-series branch selector unit (Reference)P-series branch selector unit

Single branch selector unit

Multi branch selector unit

Single branch selector unit

Multi branch selector unit

BSQ36TVJBSQ60TVJBSQ96TVJ

BS4Q54TVJBS6Q54TVJBS8Q54TVJBS10Q54TVJBS12Q54TVJ

BSVQ36PVJUBSVQ60PVJUBSVQ96PVJU

BSV4Q36PVJUBSV6Q36PVJU

Heat recovery Heat pump RWEQ-TA

RWEQ-TATJU Standardly connectable (*1)

Standardly connectable (*1) Connectable (*1) Connectable (*1)

RWEQ-TAYDU Standardly connectable (*1)

Standardly connectable (*1) Connectable (*1) Connectable (*1)

RWEQ-TAYCU Standardly connectable (*1)

Standardly connectable (*1) Connectable (*1) Connectable (*1)

Note:*1. Combination of P-series and T-series of Branch selector units in a single system is not permitted.

Combining the two series may cause malfunction.

Page 19: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

17

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

7. Capacity Range7.1 Connection Ratio

Connection ratio =Total capacity index of the indoor units

Capacity index of the outside units

TypeMin.

connection ratio

Max. connection ratio

Types of connected indoor units Type of connected air treatment equipments

When using only FXDQ, FXMQ-PB,

FXAQ, FXSQ07-54T

When using at least one FXFQ07/09,

FXZQ05T,FXSQ05T

Other indoor unit models

FXMQ-MF

When FXMQ-MF is only connected

When FXMQ-MF and indoor units are

connectedSingle outside units

50%150% *1

150% *1 150% *1100% 100% *3*4Double outside units 130% 130%

Triple outside units 150% *1 130% *2 130% *2

Notes:*1. Iftheoperationalcapacityofindoorunitsismorethan130%,lowairflowoperationisenforcedinalltheindoorunits.Thiscanbeabolished

throughfieldsettings.*2. 120% for RWEQ432TATJU/TAYDU/TAYCU*3. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air

processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outside units. And the connection ratio must not exceed 100%.*4. It is permitted to use a maximum connection ratio of 130% in some circumstances – please contact your local Daikin representative for further

details.*5. For indoor units used for cooling only (do not connect to Branch selector unit when using for heat recovery), total capacity index of cooling only

indoor units must be 50% or less than the total capacity index of the indoor units.

Page 20: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

18

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

7.2 Indoor Unit Connection Capacity

Type Ton Capacity index Model name Combination

Outside unit multi connection piping kit

*1

Total capacity index of connectable indoor

units *2

Maximum number of connectable indoor

units

Single outside units

8 96 RWEQ96TA RWEQ96TA—

48 to 124 (144) 1610 120 RWEQ120TA RWEQ120TA 60 to 156 (180) 2012 144 RWEQ144TA RWEQ144TA 72 to 187 (216) 24

Double outside units

16 192 RWEQ192TA RWEQ96TA+RWEQ96TA

Heat pump: BHFP22T84UHeat recovery: BHFP26T84U

96 to 249 (288) 33

18 216 RWEQ216TA RWEQ96TA+RWEQ120TA 108 to 280 (324) 37

20 240 RWEQ240TA RWEQ120TA+RWEQ120TA 120 to 312 (360) 41

22 264 RWEQ264TA RWEQ120TA+RWEQ144TA 132 to 343 (396) 45

24 288 RWEQ288TA RWEQ144TA+RWEQ144TA 144 to 374 (432) 49

Triple outside units

26 312 RWEQ312TARWEQ96TA+RWEQ96TA+RWEQ120TA

Heat pump: BHFP22T126UHeat recovery: BHFP26T126U

156 to 405 (468) 54

28 336 RWEQ336TARWEQ96TA+RWEQ120TA+RWEQ120TA

168 to 436 (504) 58

30 360 RWEQ360TARWEQ120TA+RWEQ120TA+RWEQ120TA

180 to 468 (540) 62

32 384 RWEQ384TARWEQ120TA+RWEQ120TA+RWEQ144TA

192 to 499 (576) 64

34 408 RWEQ408TARWEQ120TA+RWEQ144TA+RWEQ144TA

204 to 530 (612) 64

36 *4 432 RWEQ432TARWEQ144TA+RWEQ144TA+RWEQ144TA

216 to 561 (648) 64

Notes:*1. For multiple connection, the outside unit multi connection piping kit (separately sold) is required.*2. Values inside brackets are based on connection of indoor units rated at maximum capacity, 150% for single outside units, 150% for double

outside units, and 150% for triple outside units.*3. For indoor units used for cooling only (do not connect to Branch selector unit when using for heat recovery), total capacity index of cooling only

indoor units must be 50% or less than the total capacity index of the indoor units.*4. 35.5 ton for 575 V units

Page 21: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

19

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

7.3 Limitation of Capacity Index for Heat RecoverySingle Branch Selector Unit

Model BSQ36TVJ BSQ60TVJ BSQ96TVJMaximum number of connectable indoor units 4 8 8Total capacity index of connectable indoor units unit ≤ 36 36 < unit ≤ 60 60 < unit ≤ 96

Multi Branch Selector Unit

Model BS4Q54TVJ BS6Q54TVJ BS8Q54TVJ BS10Q54TVJ BS14Q54TVJMaximum number of connectable indoor units 20 30 40 41 41Maximum number of connectable indoor units per branch 5 5 5 5 5

Number of branches 4 6 8 10 12Maximum capacity index of connectable indoor units 144 or less 216 or less 290 or less 290 or less 290 or less

Maximum capacity index of connectable indoor units per branch (*1) 54 or less 54 or less 54 or less 54 or less 54 or less

Note: *1. When the total capacity of indoor units to be connected downstream is larger than 54 (Max. 96), use a junction pipe kit (KHRP26A250T,

optional parts) to join two connections downstream from the Branch selector unit.

High and low pressuregas pipingSuction gas pipingLiquid piping

Indoor unit(Heating)

Indoor unit(Cooling)

Indoor unit*(Cooling only)

Heat Recovery operation!

* For indoor units used for cooling only (do not connect to Branch selector unit when using for heat recovery), total capacity index of cooling only indoor units must be 50% or less than the total capacity index of the indoor units.

Branch Selector unit

Branch Selector unit

Heat Recovery

Outside unit

Page 22: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

20

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

8. Specifications8.1 RWEQ-TATJURWEQ96TATJU

Model RWEQ96TATJUPower supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)96,000 (28.1)

Rated 92,000 (27.0)

H2 Heating capacityNominal Btu/h

(kW)108,000 (31.7)

Rated 103,000 (30.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 544 (15.4)

Number of revolutions r/min 4,542

Motor output × Number of units kW 4.7 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/8 (9.5) C1220T (Brazing connection)Suction gas pipe in. (mm) f7/8 (22.2) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f7/8 (22.2) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 432.1 (196)H6 Sound pressure level (Reference data) dB(A) 54

H6 Sound power level (Reference data) dB 71

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 15-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 (7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109377GSound level C: 4D109785A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.:86°F (30°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 23: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

21

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ120TATJU

Model RWEQ120TATJUPower supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)120,000 (35.2)

Rated 114,000 (33.4)

H2 Heating capacityNominal Btu/h

(kW)135,000 (39.6)

Rated 129,000 (37.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 (19.0)

Number of revolutions r/min 5,592

Motor output × Number of units kW 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 (198)H6 Sound pressure level (Reference data) dB(A) 55

H6 Sound power level (Reference data) dB 72

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 12-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109378GSound level C: 4D109786A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 75 ft. (23 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 75 ft. (23 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 24: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

22

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ144TATJU

Model RWEQ144TATJUPower supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)144,000 (42.2)

Rated 138,000 (40.4)

H2 Heating capacityNominal Btu/h

(kW)162,000 (47.5)

Rated 154,000 (45.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 848 (24.0)

Number of revolutions r/min 7,080

Motor output × Number of units kW 7.4 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f7/8 (22.2) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 (198)H6 Sound pressure level (Reference data) dB(A) 60.5

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 11-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109379FSound level C: 4D109787A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW)4. There are some cases where capacity decreases depending on operating states.

Page 25: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

23

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ192TATJU

Model (Combination Unit) RWEQ192TATJU

Model (Independent Unit) RWEQ96TATJURWEQ96TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)192,000 (56.3)

Rated 184,000 (53.9)

H2 Heating capacityNominal Btu/h

(kW)216,000 (63.3)

Rated 206,000 (60.4)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 551 + 551 (15.6 + 15.6)

Number of revolutions r/min 4,602 + 4,602

Motor output × Number of units kW 4.8 × 1 + 4.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 432.1 + 432.1 (196 + 196)H6 Sound pressure level (Reference data) dB(A) 57

H6 Sound power level (Reference data) dB 74

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 8-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 + 17.4 (7.9 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109380GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 26: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

24

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ216TATJU

Model (Combination Unit) RWEQ216TATJU

Model (Independent Unit) RWEQ120TATJURWEQ96TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)216,000 (63.3)

Rated 206,000 (60.4)

H2 Heating capacityNominal Btu/h

(kW)243,000 (71.2)

Rated 232,000 (68.0)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 + 669 (19.0 + 19.0)

Number of revolutions r/min 5,592 + 5,592

Motor output × Number of units kW 5.8 × 1 + 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 432.1 (198 + 196)H6 Sound pressure level (Reference data) dB(A) 57.5

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 7-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 (9.6 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109381HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 27: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

25

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ240TATJU

Model (Combination Unit) RWEQ240TATJU

Model (Independent Unit) RWEQ120TATJURWEQ120TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)240,000 (70.3)

Rated 228,000 (66.8)

H2 Heating capacityNominal Btu/h

(kW)270,000 (79.1)

Rated 258,000 (75.6)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 708 + 708 (20.0 + 20.0)

Number of revolutions r/min 5,910 + 5,910

Motor output × Number of units kW 6.2 × 1 + 6.2 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 (198 + 198)H6 Sound pressure level (Reference data) dB(A) 58

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 6-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109382HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 28: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

26

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ264TATJU

Model (Combination Unit) RWEQ264TATJU

Model (Independent Unit) RWEQ144TATJURWEQ120TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)264,000 (77.4)

Rated 252,000 (73.9)

H2 Heating capacityNominal Btu/h

(kW)297,000 (87.0)

Rated 284,000 (83.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 860 + 860 (24.3 + 24.3)

Number of revolutions r/min 7,182 + 7,182

Motor output × Number of units kW 7.5 × 1 + 7.5 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 (198 + 198)H6 Sound pressure level (Reference data) dB(A) 61.5

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 6-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109383GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 29: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

27

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ288TATJU

Model (Combination Unit) RWEQ288TATJU

Model (Independent Unit) RWEQ144TATJURWEQ144TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)288,000 (84.4)

Rated 274,000 (80.3)

H2 Heating capacityNominal Btu/h

(kW)324,000 (95.0)

Rated 308,000 (90.3)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 961 + 961 (27.2 + 27.2)

Number of revolutions r/min 8,028 + 8,028

Motor output × Number of units kW 8.4 × 1 + 8.4 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 (198 + 198)H6 Sound pressure level (Reference data) dB(A) 63.5

H6 Sound power level (Reference data) dB 78

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 5-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109384GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 30: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

28

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ312TATJU

Model (Combination Unit) RWEQ312TATJU

Model (Independent Unit)RWEQ120TATJURWEQ96TATJURWEQ96TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)312,000 (91.4)

Rated 298,000 (87.3)

H2 Heating capacityNominal Btu/h

(kW)351,000 (102.9)

Rated 334,000 (97.9)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 + 669 + 669 (19.0 + 19.0 + 19.0)

Number of revolutions r/min 5,592 + 5,592 + 5,592

Motor output × Number of units kW 5.8 × 1 + 5.8 × 1 + 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 432.1 + 432.1 (198 + 196 + 196)H6 Sound pressure level (Reference data) dB(A) 59

H6 Sound power level (Reference data) dB 76

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 5-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 + 17.4 (9.6 + 7.9 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109385GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 31: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

29

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ336TATJU

Model (Combination Unit) RWEQ336TATJU

Model (Independent Unit)RWEQ120TATJURWEQ120TATJURWEQ96TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)336,000 (98.5)

Rated 320,000 (93.8)

H2 Heating capacityNominal Btu/h

(kW)378,000 (110.8)

Rated 360,000 (105.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 688 + 688 + 688 (19.5 + 19.5 + 19.5)

Number of revolutions r/min 5,748 + 5,748 + 5,748

Motor output × Number of units kW 6.0 × 1 + 6.0 × 1 + 6.0 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 + 432.1 (198 + 198 + 196)H6 Sound pressure level (Reference data) dB(A) 59.5

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 17.4 (9.6 + 9.6 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109386HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 2 + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 32: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

30

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ360TATJU

Model (Combination Unit) RWEQ360TATJU

Model (Independent Unit)RWEQ120TATJURWEQ120TATJURWEQ120TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)360,000 (105.5)

Rated 342,000 (100.2)

H2 Heating capacityNominal Btu/h

(kW)405,000 (118.7)

Rated 386,000 (113.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 825 + 825 + 825 (23.4 + 23.4 + 23.4)

Number of revolutions r/min 6,888 + 6,888 + 6,888

Motor output × Number of units kW 7.2 × 1 + 7.2 × 1 + 7.2 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198)H6 Sound pressure level (Reference data) dB(A) 60

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109387HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 34. There are some cases where capacity decreases depending on operating states.

Page 33: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

31

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ384TATJU

Model (Combination Unit) RWEQ384TATJU

Model (Independent Unit)RWEQ144TATJURWEQ120TATJURWEQ120TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)384,000 (112.5)

Rated 366,000 (107.3)

H2 Heating capacityNominal Btu/h

(kW)432,000 (126.6)

Rated 410,000 (120.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 860 + 860 + 860 (24.3 + 24.3 + 24.3)

Number of revolutions r/min 7,182 + 7,182 + 7,182

Motor output × Number of units kW 7.5 × 1 + 7.5 × 1 + 7.5 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198)H6 Sound pressure level (Reference data) dB(A) 62

H6 Sound power level (Reference data) dB 78

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D111941FSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 34: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

32

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ408TATJU

Model (Combination Unit) RWEQ408TATJU

Model (Independent Unit)RWEQ144TATJURWEQ144TATJURWEQ120TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)408,000 (119.6)

Rated 388,000 (113.7)

H2 Heating capacityNominal Btu/h

(kW)459,000 (134.5)

Rated 435,000 (127.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 1,006 + 1,006 + 884 (28.5 + 28.5 + 25.0)

Number of revolutions r/min 8,400 + 8,400 + 7,386

Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 7.7 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198)H6 Sound pressure level (Reference data) dB(A) 64

H6 Sound power level (Reference data) dB 79

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D111942FSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 2 + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 35: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

33

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ432TATJU

Model (Combination Unit) RWEQ432TATJU

Model (Independent Unit)RWEQ144TATJURWEQ144TATJURWEQ144TATJU

Power supply 3 phase, 208/230 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)432,000 (126.6)

Rated 410,000 (120.2)

H2 Heating capacityNominal Btu/h

(kW)486,000 (142.4)

Rated 460,000 (134.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 1,006 + 1,006 + 1,006 (28.5 + 28.5 + 28.5)

Number of revolutions r/min 8,400 + 8,400 + 8,400

Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 8.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 435.9 + 435.9 + 435.9 (198 + 198 + 198)H6 Sound pressure level (Reference data) dB(A) 65

H6 Sound power level (Reference data) dB 80

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D111943ESound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 34. There are some cases where capacity decreases depending on operating states.

Page 36: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

34

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

8.2 RWEQ-TAYDURWEQ96TAYDU

Model RWEQ96TAYDUPower supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)96,000 (28.1)

Rated 92,000 (27.0)

H2 Heating capacityNominal Btu/h

(kW)108,000 (31.7)

Rated 103,000 (30.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 544 (15.4)

Number of revolutions r/min 4,542

Motor output × Number of units kW 4.7 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/8 (9.5) C1220T (Brazing connection)Suction gas pipe in. (mm) f7/8 (22.2) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f7/8 (22.2) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 438.7 (199)H6 Sound pressure level (Reference data) dB(A) 54

H6 Sound power level (Reference data) dB 71

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 15-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 (7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109388GSound level C: 4D109785A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 37: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

35

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ120TAYDU

Model RWEQ120TAYDUPower supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)120,000 (35.2)

Rated 114,000 (33.4)

H2 Heating capacityNominal Btu/h

(kW)135,000 (39.6)

Rated 129,000 (37.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 (19.0)

Number of revolutions r/min 5,592

Motor output × Number of units kW 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 (201)H6 Sound pressure level (Reference data) dB(A) 55

H6 Sound power level (Reference data) dB 72

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 12-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109389GSound level C: 4D109786A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 75 ft. (23 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 75 ft. (23 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 38: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

36

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ144TAYDU

Model RWEQ144TAYDUPower supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)144,000 (42.2)

Rated 138,000 (40.4)

H2 Heating capacityNominal Btu/h

(kW)162,000 (47.5)

Rated 154,000 (45.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 848 (24.0)

Number of revolutions r/min 7,080

Motor output × Number of units kW 7.4 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f7/8 (22.2) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 (201)H6 Sound pressure level (Reference data) dB(A) 60.5

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 11-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109390FSound level C: 4D109787A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW)4. There are some cases where capacity decreases depending on operating states.

Page 39: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

37

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ192TAYDU

Model (Combination Unit) RWEQ192TAYDU

Model (Independent Unit) RWEQ96TAYDURWEQ96TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)192,000 (56.3)

Rated 184,000 (53.9)

H2 Heating capacityNominal Btu/h

(kW)216,000 (63.3)

Rated 206,000 (60.4)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 551 + 551 (15.6 + 15.6)

Number of revolutions r/min 4,602 + 4,602

Motor output × Number of units kW 4.8 × 1 + 4.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 438.7 + 438.7 (199 + 199)H6 Sound pressure level (Reference data) dB(A) 57

H6 Sound power level (Reference data) dB 74

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 8-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 + 17.4 (7.9 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109391GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 40: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

38

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ216TAYDU

Model (Combination Unit) RWEQ216TAYDU

Model (Independent Unit) RWEQ120TAYDURWEQ96TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)216,000 (63.3)

Rated 206,000 (60.4)

H2 Heating capacityNominal Btu/h

(kW)243,000 (71.2)

Rated 232,000 (68.0)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 + 669 (19.0 + 19.0)

Number of revolutions r/min 5,592 + 5,592

Motor output × Number of units kW 5.8 × 1 + 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 438.7 (201 + 199)H6 Sound pressure level (Reference data) dB(A) 57.5

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 7-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 (9.6 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109392HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 41: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

39

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ240TAYDU

Model (Combination Unit) RWEQ240TAYDU

Model (Independent Unit) RWEQ120TAYDURWEQ120TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)240,000 (70.3)

Rated 228,000 (66.8)

H2 Heating capacityNominal Btu/h

(kW)270,000 (79.1)

Rated 258,000 (75.6)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 708 + 708 (20.0 + 20.0)

Number of revolutions r/min 5,910 + 5,910

Motor output × Number of units kW 6.2 × 1 + 6.2 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 (201 + 201)H6 Sound pressure level (Reference data) dB(A) 58

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 6-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109393HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 42: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

40

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ264TAYDU

Model (Combination Unit) RWEQ264TAYDU

Model (Independent Unit) RWEQ144TAYDURWEQ120TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)264,000 (77.4)

Rated 252,000 (73.9)

H2 Heating capacityNominal Btu/h

(kW)297,000 (87.0)

Rated 284,000 (83.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 860 + 860 (24.3 + 24.3)

Number of revolutions r/min 7,182 + 7,182

Motor output × Number of units kW 7.5 × 1 + 7.5 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 (201 + 201)H6 Sound pressure level (Reference data) dB(A) 61.5

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 6-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109394GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 43: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

41

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ288TAYDU

Model (Combination Unit) RWEQ288TAYDU

Model (Independent Unit) RWEQ144TAYDURWEQ144TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)288,000 (84.4)

Rated 274,000 (80.3)

H2 Heating capacityNominal Btu/h

(kW)324,000 (95.0)

Rated 308,000 (90.3)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 961 + 961 (27.2 + 27.2)

Number of revolutions r/min 8,028 + 8,028

Motor output × Number of units kW 8.4 × 1 + 8.4 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 (201 + 201)H6 Sound pressure level (Reference data) dB(A) 63.5

H6 Sound power level (Reference data) dB 78

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 5-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109395GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 44: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

42

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ312TAYDU

Model (Combination Unit) RWEQ312TAYDU

Model (Independent Unit)RWEQ120TAYDURWEQ96TAYDURWEQ96TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)312,000 (91.4)

Rated 298,000 (87.3)

H2 Heating capacityNominal Btu/h

(kW)351,000 (102.9)

Rated 334,000 (97.9)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 + 669 + 669 (19.0 + 19.0 + 19.0)

Number of revolutions r/min 5,592 + 5,592 + 5,592

Motor output × Number of units kW 5.8 × 1 + 5.8 × 1 + 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 438.7 + 438.7 (201 + 199 + 199)H6 Sound pressure level (Reference data) dB(A) 59

H6 Sound power level (Reference data) dB 76

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 5-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 + 17.4 (9.6 + 7.9 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109396GSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 45: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

43

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ336TAYDU

Model (Combination Unit) RWEQ336TAYDU

Model (Independent Unit)RWEQ120TAYDURWEQ120TAYDURWEQ96TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)336,000 (98.5)

Rated 320,000 (93.8)

H2 Heating capacityNominal Btu/h

(kW)378,000 (110.8)

Rated 360,000 (105.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 688 + 688 + 688 (19.5 + 19.5 + 19.5)

Number of revolutions r/min 5,748 + 5,748 + 5,748

Motor output × Number of units kW 6.0 × 1 + 6.0 × 1 + 6.0 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 + 438.7 (201 + 201 + 199)H6 Sound pressure level (Reference data) dB(A) 59.5

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 17.4 (9.6 + 9.6 + 7.9)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109397HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 2 + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 46: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

44

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ360TAYDU

Model (Combination Unit) RWEQ360TAYDU

Model (Independent Unit)RWEQ120TAYDURWEQ120TAYDURWEQ120TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)360,000 (105.5)

Rated 342,000 (100.2)

H2 Heating capacityNominal Btu/h

(kW)405,000 (118.7)

Rated 386,000 (113.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 825 + 825 + 825 (23.4 + 23.4 + 23.4)

Number of revolutions r/min 6,888 + 6,888 + 6,888

Motor output × Number of units kW 7.2 × 1 + 7.2 × 1 + 7.2 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201)H6 Sound pressure level (Reference data) dB(A) 60

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D109398HSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 34. There are some cases where capacity decreases depending on operating states.

Page 47: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

45

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ384TAYDU

Model (Combination Unit) RWEQ384TAYDU

Model (Independent Unit)RWEQ144TAYDURWEQ120TAYDURWEQ120TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)384,000 (112.5)

Rated 366,000 (107.3)

H2 Heating capacityNominal Btu/h

(kW)432,000 (126.6)

Rated 410,000 (120.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 860 + 860 + 860 (24.3 + 24.3 + 24.3)

Number of revolutions r/min 7,182 + 7,182 + 7,182

Motor output × Number of units kW 7.5 × 1 + 7.5 × 1 + 7.5 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201)H6 Sound pressure level (Reference data) dB(A) 62

H6 Sound power level (Reference data) dB 78

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D111944FSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 48: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

46

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ408TAYDU

Model (Combination Unit) RWEQ408TAYDU

Model (Independent Unit)RWEQ144TAYDURWEQ144TAYDURWEQ120TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)408,000 (119.6)

Rated 388,000 (113.7)

H2 Heating capacityNominal Btu/h

(kW)459,000 (134.5)

Rated 435,000 (127.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 1,006 + 1,006 + 884 (28.5 + 28.5 + 25.0)

Number of revolutions r/min 8,400 + 8,400 + 7,386

Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 7.7 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201)H6 Sound pressure level (Reference data) dB(A) 64

H6 Sound power level (Reference data) dB 79

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D111945FSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 2 + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 49: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

47

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ432TAYDU

Model (Combination Unit) RWEQ432TAYDU

Model (Independent Unit)RWEQ144TAYDURWEQ144TAYDURWEQ144TAYDU

Power supply 3 phase, 460 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)432,000 (126.6)

Rated 410,000 (120.2)

H2 Heating capacityNominal Btu/h

(kW)486,000 (142.4)

Rated 460,000 (134.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 1,006 + 1,006 + 1,006 (28.5 + 28.5 + 28.5)

Number of revolutions r/min 8,400 + 8,400 + 8,400

Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 8.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 442.5 + 442.5 + 442.5 (201 + 201 + 201)H6 Sound pressure level (Reference data) dB(A) 65

H6 Sound power level (Reference data) dB 80

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessories Installation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose

Drawing No.Specification C: 4D111946ESound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 34. There are some cases where capacity decreases depending on operating states.

Page 50: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

48

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

8.3 RWEQ-TAYCURWEQ96TAYCU

Model RWEQ96TAYCUPower supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)96,000 (28.1)

Rated 92,000 (27.0)

H2 Heating capacityNominal Btu/h

(kW)108,000 (31.7)

Rated 103,000 (30.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 544 (15.4)

Number of revolutions r/min 4,542

Motor output × Number of units kW 4.7 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/8 (9.5) C1220T (Brazing connection)Suction gas pipe in. (mm) f7/8 (22.2) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f7/8 (22.2) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 436.5 (198)H6 Sound pressure level (Reference data) dB(A) 54

H6 Sound power level (Reference data) dB 71

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 15-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 (7.9)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117549BSound level C: 4D109785A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 50 ft. (15.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 51: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

49

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ120TAYCU

Model RWEQ120TAYCUPower supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)120,000 (35.2)

Rated 114,000 (33.4)

H2 Heating capacityNominal Btu/h

(kW)135,000 (39.6)

Rated 129,000 (37.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 (19.0)

Number of revolutions r/min 5,592

Motor output × Number of units kW 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f3/4 (19.1) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 (200)H6 Sound pressure level (Reference data) dB(A) 55

H6 Sound power level (Reference data) dB 72

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 12-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117550BSound level C: 4D109786A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 75 ft. (23 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 25 ft. (7.6 m) for ducted indoor units, 75 ft. (23 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 52: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

50

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ144TAYCU

Model RWEQ144TAYCUPower supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)144,000 (42.2)

Rated 138,000 (40.4)

H2 Heating capacityNominal Btu/h

(kW)162,000 (47.5)

Rated 154,000 (45.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) 38-9/16 × 30-1/8 × 22-1/16 (980 × 765 × 560)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 848 (24.0)

Number of revolutions r/min 7,080

Motor output × Number of units kW 7.4 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f1/2 (12.7) C1220T (Brazing connection)Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3High/low pressure gas pipe in. (mm) H4 f7/8 (22.2) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection)

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 (200)H6 Sound pressure level (Reference data) dB(A) 60.5

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 11-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 (9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117551BSound level C: 4D109787A

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW)4. There are some cases where capacity decreases depending on operating states.

Page 53: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

51

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ192TAYCU

Model (Combination Unit) RWEQ192TAYCU

Model (Independent Unit) RWEQ96TAYCURWEQ96TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)192,000 (56.3)

Rated 184,000 (53.9)

H2 Heating capacityNominal Btu/h

(kW)216,000 (63.3)

Rated 206,000 (60.4)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 551 + 551 (15.6 + 15.6)

Number of revolutions r/min 4,602 + 4,602

Motor output × Number of units kW 4.8 × 1 + 4.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 436.5 + 436.5 (198 + 198)H6 Sound pressure level (Reference data) dB(A) 57

H6 Sound power level (Reference data) dB 74

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 8-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 17.4 + 17.4 (7.9 + 7.9)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117552BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 54: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

52

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ216TAYCU

Model (Combination Unit) RWEQ216TAYCU

Model (Independent Unit) RWEQ120TAYCURWEQ96TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)216,000 (63.3)

Rated 206,000 (60.4)

H2 Heating capacityNominal Btu/h

(kW)243,000 (71.2)

Rated 232,000 (68.0)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 + 669 (19.0 + 19.0)

Number of revolutions r/min 5,592 + 5,592

Motor output × Number of units kW 5.8 × 1 + 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-1/8 (28.6) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-1/8 (28.6) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 436.5 (200 + 198)H6 Sound pressure level (Reference data) dB(A) 57.5

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 7-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 (9.6 + 7.9)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117553BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 55: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

53

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ240TAYCU

Model (Combination Unit) RWEQ240TAYCU

Model (Independent Unit) RWEQ120TAYCURWEQ120TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)240,000 (70.3)

Rated 228,000 (66.8)

H2 Heating capacityNominal Btu/h

(kW)270,000 (79.1)

Rated 258,000 (75.6)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 708 + 708 (20.0 + 20.0)

Number of revolutions r/min 5,910 + 5,910

Motor output × Number of units kW 6.2 × 1 + 6.2 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f5/8 (15.9) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 (200 + 200)H6 Sound pressure level (Reference data) dB(A) 58

H6 Sound power level (Reference data) dB 75

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 6-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117554BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 56: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

54

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ264TAYCU

Model (Combination Unit) RWEQ264TAYCU

Model (Independent Unit) RWEQ144TAYCURWEQ120TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)264,000 (77.4)

Rated 252,000 (73.9)

H2 Heating capacityNominal Btu/h

(kW)297,000 (87.0)

Rated 284,000 (83.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 860 + 860 (24.3 + 24.3)

Number of revolutions r/min 7,182 + 7,182

Motor output × Number of units kW 7.5 × 1 + 7.5 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 (200 + 200)H6 Sound pressure level (Reference data) dB(A) 61.5

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 6-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117555BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 57: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

55

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ288TAYCU

Model (Combination Unit) RWEQ288TAYCU

Model (Independent Unit) RWEQ144TAYCURWEQ144TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)288,000 (84.4)

Rated 274,000 (80.3)

H2 Heating capacityNominal Btu/h

(kW)324,000 (95.0)

Rated 308,000 (90.3)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 2 ((980 × 765 × 560) × 2)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 961 + 961 (27.2 + 27.2)

Number of revolutions r/min 8,028 + 8,028

Motor output × Number of units kW 8.4 × 1 + 8.4 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 (200 + 200)H6 Sound pressure level (Reference data) dB(A) 63.5

H6 Sound power level (Reference data) dB 78

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 5-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 (9.6 + 9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117556BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 58: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

56

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ312TAYCU

Model (Combination Unit) RWEQ312TAYCU

Model (Independent Unit)RWEQ120TAYCURWEQ96TAYCURWEQ96TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)312,000 (91.4)

Rated 298,000 (87.3)

H2 Heating capacityNominal Btu/h

(kW)351,000 (102.9)

Rated 334,000 (97.9)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 669 + 669 + 669 (19.0 + 19.0 + 19.0)

Number of revolutions r/min 5,592 + 5,592 + 5,592

Motor output × Number of units kW 5.8 × 1 + 5.8 × 1 + 5.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 436.5 + 436.5 (200 + 198 + 198)H6 Sound pressure level (Reference data) dB(A) 59

H6 Sound power level (Reference data) dB 76

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 5-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 17.4 + 17.4 (9.6 + 7.9 + 7.9)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117557BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) + 2,730 Btu/h (0.8 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 59: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

57

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ336TAYCU

Model (Combination Unit) RWEQ336TAYCU

Model (Independent Unit)RWEQ120TAYCURWEQ120TAYCURWEQ96TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)336,000 (98.5)

Rated 320,000 (93.8)

H2 Heating capacityNominal Btu/h

(kW)378,000 (110.8)

Rated 360,000 (105.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 688 + 688 + 688 (19.5 + 19.5 + 19.5)

Number of revolutions r/min 5,748 + 5,748 + 5,748

Motor output × Number of units kW 6.0 × 1 + 6.0 × 1 + 6.0 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-3/8 (34.9) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-1/8 (28.6) C1220T, H5 f1-3/8 (34.9) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 + 436.5 (200 + 200 + 198)H6 Sound pressure level (Reference data) dB(A) 59.5

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 17.4 (9.6 + 9.6 + 7.9)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117558BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 2 + 2,730 Btu/h (0.8 kW)4. There are some cases where capacity decreases depending on operating states.

Page 60: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

58

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ360TAYCU

Model (Combination Unit) RWEQ360TAYCU

Model (Independent Unit)RWEQ120TAYCURWEQ120TAYCURWEQ120TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)360,000 (105.5)

Rated 342,000 (100.2)

H2 Heating capacityNominal Btu/h

(kW)405,000 (118.7)

Rated 386,000 (113.1)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3 )Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 825 + 825 + 825 (23.4 + 23.4 + 23.4)

Number of revolutions r/min 6,888 + 6,888 + 6,888

Motor output × Number of units kW 7.2 × 1 + 7.2 × 1 + 7.2 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 60

H6 Sound power level (Reference data) dB 77

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117559BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 50 ft. (15.5 m) for ducted indoor units, 100 ft. (30.5 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 3,412 Btu/h (1.0 kW) × 34. There are some cases where capacity decreases depending on operating states.

Page 61: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

59

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ384TAYCU

Model (Combination Unit) RWEQ384TAYCU

Model (Independent Unit)RWEQ144TAYCURWEQ120TAYCURWEQ120TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)384,000 (112.5)

Rated 366,000 (107.3)

H2 Heating capacityNominal Btu/h

(kW)432,000 (126.6)

Rated 410,000 (120.2)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 860 + 860 + 860 (24.3 + 24.3 + 24.3)

Number of revolutions r/min 7,182 + 7,182 + 7,182

Motor output × Number of units kW 7.5 × 1 + 7.5 × 1 + 7.5 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 62

H6 Sound power level (Reference data) dB 78

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117560BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) + 3,412 Btu/h (1.0 kW) × 24. There are some cases where capacity decreases depending on operating states.

Page 62: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

60

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ408TAYCU

Model (Combination Unit) RWEQ408TAYCU

Model (Independent Unit)RWEQ144TAYCURWEQ144TAYCURWEQ120TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)408,000 (119.6)

Rated 388,000 (113.7)

H2 Heating capacityNominal Btu/h

(kW)459,000 (134.5)

Rated 435,000 (127.5)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 1,006 + 1,006 + 884 (28.5 + 28.5 + 25.0)

Number of revolutions r/min 8,400 + 8,400 + 7,386

Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 7.7 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 64

H6 Sound power level (Reference data) dB 79

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117561BSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH.

Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 2 + 3,412 Btu/h (1.0 kW)4. There are some cases where capacity decreases depending on operating states.

Page 63: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

61

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ432TAYCU

Model (Combination Unit) RWEQ432TAYCU

Model (Independent Unit)RWEQ144TAYCURWEQ144TAYCURWEQ144TAYCU

Power supply 3 phase, 575 V, 60 Hz

H1 Cooling capacityNominal Btu/h

(kW)426,000 (124.8)

Rated 410,000 (120.2)

H2 Heating capacityNominal Btu/h

(kW)486,000 (142.4)

Rated 460,000 (134.8)Casing color Ivory white (5Y7.5/1)Dimensions: (H × W × D) in. (mm) (38-9/16 × 30-1/8 × 22-1/16) × 3 ((980 × 765 × 560) × 3)Heat exchanger Stainless steel plate type

Compressor

Type Hermetically sealed scroll type

Displacement ft.³/h (m³/h) 1,006 + 1,006 + 1,006 (28.5 + 28.5 + 28.5)

Number of revolutions r/min 8,400 + 8,400 + 8,400

Motor output × Number of units kW 8.8 × 1 + 8.8 × 1 + 8.8 × 1

Starting method Soft start

Connecting pipes

Liquid pipe in. (mm) f3/4 (19.1) C1220T (Brazing connection) -Main line-Suction gas pipe in. (mm) f1-5/8 (41.3) C1220T (Brazing connection) H3 -Main line-High/low pressure gas pipe in. (mm) H4 f1-3/8 (34.9) C1220T, H5 f1-5/8 (41.3) C1220T (Brazing connection) -Main line-

Water inlet in. ISO 228-1-G1 1/4B (External thread)Water outlet in. ISO 228-1-G1 1/4B (External thread)Drain outlet in. (mm) For ID 3/8 (10)

Weight lbs (kg) 440.9 + 440.9 + 440.9 (200 + 200 + 200)H6 Sound pressure level (Reference data) dB(A) 65

H6 Sound power level (Reference data) dB 80

Safety devices High pressure switch, Inverter overload protector, Fusible plug, Leak detecting device, Overcurrent fuse

Capacity control % 4-100

RefrigerantRefrigerant name R410ACharge lbs (kg) 21.2 + 21.2 + 21.2 (9.6 + 9.6 + 9.6)Control Electronic expansion valve

Standard accessoriesInstallation manual, Operation manual, Connection pipes, Clamps, Conduit mounting plates, Drain hose, Strainer (water line) (50mesh, ANSI-ASME B1.20.1·1 1/4-11.5 NPT female), Pipe adaptor

(waterline)(ISO228-1-G11/4B→ANSI-ASMEB1.20.1·11/4-11.5NPTfemale)

Drawing No.Specification C: 4D117562CSound level —

Notes:1. H1 Indoor temp.: 80.6°FDB (27°CDB), 66.2°FWB (19°CWB) / Entering water temp.: 86°F (30°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H2 Indoor temp.: 68°FDB (20°CDB), 59°FWB (15°CWB) / Entering water temp.: 68°F (20°C)

Equivalent piping length: 75 ft. (23 m) for ducted indoor units, 150 ft. (45.7 m) for non-ducted indoor units, level difference: 0 ft. (0 m).H3 In the case of heat pump system, the suction gas pipe is not used.H4 In the case of heat recovery system.H5 In the case of heat pump system.H6 Anechoic chamber conversion value.

During actual operation, these value may be higher as a result of ambient conditions.2. This unit cannot be installed outdoors. Install indoors (Machine room, etc.).3. Hold ambient condition at 35~104°FDB (2~40°CDB), ~80%RH. Heat release from the unit (approx.): 4,436 Btu/h (1.3 kW) × 34. There are some cases where capacity decreases depending on operating states.

Page 64: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

62

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

9. Dimensions

RWEQ96 - 144TATJU / TAYDU / TAYCU

3D10

9305

B

Page 65: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

63

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ192 - 288TATJU / TAYDU / TAYCU

3D11

2152

B

Page 66: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

64

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ312 - 432TATJU / TAYDU / TAYCU

3D11

2153

B

Page 67: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

65

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

10. Service Space

RWEQ96 - 432TATJU / TAYDU / TAYCU

3D

1093

04B

Page 68: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

66

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

11. Center of Gravity

RWEQ96 - 144TATJU

RWEQ96 - 144TAYDU / TAYCU4D109344A

Unit. in. (mm)

4D109345A

Unit. in. (mm)

Page 69: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

67

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

12. Piping Diagrams

RWEQ96 - 144TATJU / TAYDU / TAYCU

4D109343B

Page 70: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

68

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

13. Wiring Diagrams

RWEQ96 - 144TATJU

4D10

8929

D

Page 71: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

69

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ96 - 144TATJU, continued

4D10

8929

D

Page 72: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

70

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ96 - 144TAYDU

4D10

8930

D

Page 73: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

71

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ96 - 144TAYDU, continued

4D10

8930

D

Page 74: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

72

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ96 - 144TAYCU

4D11

7733

A

Page 75: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

73

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ96 - 144TAYCU, continued

4D11

7733

A

Page 76: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

74

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

14. Field Wiring14.1 Heat PumpRWEQ96 - 144TATJU / TAYDU / TAYCU

C: 3

D12

0276

[Ope

ratio

n sy

stem

: Hea

t pum

p]

Not

es:

1) A

ll w

iring

, com

pone

nts

and

mat

eria

ls to

be

proc

ured

on

the

site

mus

t com

ply

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.2)

Use

cop

per c

ondu

ctor

s on

ly.

3) A

s fo

r det

ails

, see

wiri

ng d

iagr

am.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

W

iring

sho

uld

com

ply

with

app

licab

le lo

cal a

nd n

atio

nal c

odes

.5)

Uni

t sha

ll be

gro

unde

d in

com

plia

nce

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.6)

Wiri

ng s

how

n is

gen

eral

poi

nts-

of-c

onne

ctio

n gu

ides

onl

y an

d is

not

inte

nded

for o

r to

incl

ude

all d

etai

ls fo

r a s

peci

fic in

stal

latio

n.7)

Be

sure

to in

stal

l a s

witc

h an

d a

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8) In

stal

l a m

ain

switc

h th

at c

an in

terr

upt a

ll th

e po

wer

sou

rces

in a

n in

tegr

ated

man

ner b

ecau

se th

is s

yste

m c

onsi

sts

of th

e eq

uipm

ent u

tiliz

ing

the

mul

tiple

pow

er s

ourc

es.

9) If

ther

e ex

ists

the

poss

ibili

ty o

f rev

erse

d ph

ase,

lost

pha

se, m

omen

tary

bla

ckou

t or t

he p

ower

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed p

hase

pro

tect

ion

circ

uit l

ocal

ly.

R

unni

ng th

e pr

oduc

t in

reve

rsed

pha

se m

ay b

reak

the

com

pres

sor a

nd o

ther

par

ts.

Page 77: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

75

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ192 - 288TATJU / TAYDU / TAYCU

C: 3

D12

0277

[Ope

ratio

n sy

stem

: Hea

t pum

p]

Not

es:

1) A

ll w

iring

, com

pone

nts

and

mat

eria

ls to

be

proc

ured

on

the

site

mus

t com

ply

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.2)

Use

cop

per c

ondu

ctor

s on

ly.

3) A

s fo

r det

ails

, see

wiri

ng d

iagr

am.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

W

iring

sho

uld

com

ply

with

app

licab

le lo

cal a

nd n

atio

nal c

odes

.5)

Uni

t sha

ll be

gro

unde

d in

com

plia

nce

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.6)

Wiri

ng s

how

n is

gen

eral

poi

nts-

of-c

onne

ctio

n gu

ides

onl

y an

d is

not

inte

nded

for o

r to

incl

ude

all d

etai

ls fo

r a s

peci

fic in

stal

latio

n.7)

Be

sure

to in

stal

l a s

witc

h an

d a

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8) In

stal

l a m

ain

switc

h th

at c

an in

terr

upt a

ll th

e po

wer

sou

rces

in a

n in

tegr

ated

man

ner b

ecau

se th

is s

yste

m c

onsi

sts

of th

e e q

uipm

ent u

tiliz

ing

the

mul

tiple

pow

er s

ourc

es.

9) If

ther

e ex

ists

the

poss

ibili

ty o

f rev

erse

d ph

ase,

lost

pha

se, m

omen

tary

bla

ckou

t or t

he p

ower

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed p

hase

pro

tect

ion

circ

uit l

ocal

ly.

R

unni

ng th

e pr

oduc

t in

reve

rsed

pha

se m

ay b

reak

the

com

pres

sor a

nd o

ther

par

ts.

Page 78: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

76

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ312 - 432TATJU / TAYDU / TAYCU

C: 3

D10

9399

[Ope

ratio

n sy

stem

: Hea

t pum

p]

Not

es:

1) A

ll w

iring

, com

pone

nts

and

mat

eria

ls to

be

proc

ured

on

the

site

mus

t com

ply

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.2)

Use

cop

per c

ondu

ctor

s on

ly.

3) A

s fo

r det

ails

, see

wiri

ng d

iagr

am.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

W

iring

sho

uld

com

ply

with

app

licab

le lo

cal a

nd n

atio

nal c

odes

.5)

Uni

t sha

ll be

gro

unde

d in

com

plia

nce

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.6)

Wiri

ng s

how

n is

gen

eral

poi

nts-

of-c

onne

ctio

n gu

ides

onl

y an

d is

not

inte

nded

for o

r to

incl

ude

all d

etai

ls fo

r a s

peci

fic in

stal

latio

n.7)

Be

sure

to in

stal

l a s

witc

h an

d a

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8) In

stal

l a m

ain

switc

h th

at c

an in

terr

upt a

ll th

e po

wer

sou

rces

in a

n in

tegr

ated

man

ner b

ecau

se th

is s

yste

m c

onsi

sts

of th

e e q

uipm

ent u

tiliz

ing

the

mul

tiple

pow

er s

ourc

es.

9) If

ther

e ex

ists

the

poss

ibili

ty o

f rev

erse

d ph

ase,

lost

pha

se, m

omen

tary

bla

ckou

t or t

he p

ower

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed p

hase

pro

tect

ion

circ

uit l

ocal

ly.

R

unni

ng th

e pr

oduc

t in

reve

rsed

pha

se m

ay b

reak

the

com

pres

sor a

nd o

ther

par

ts.

Page 79: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

77

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

14.2 Heat RecoveryRWEQ96 - 144TATJU / TAYDU / TAYCU

C: 3

D12

0278

[Ope

ratio

n sy

stem

: Hea

t rec

over

y]

Not

es 1

) All

wiri

ng, c

ompo

nent

s an

d m

ater

ials

to b

e pr

ocur

ed o

n th

e si

te m

ust c

ompl

y w

ith th

e ap

plic

able

loca

l and

nat

iona

l cod

es.

2)

Use

cop

per c

ondu

ctor

s on

ly.

3)

As

for d

etai

ls, s

ee w

iring

dia

gram

.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

Wiri

ng s

houl

d co

mpl

y w

ith a

pplic

able

loca

l and

nat

iona

l cod

es.

5)

Uni

t sha

ll be

gro

unde

d in

com

plia

nce

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.

6) W

iring

sho

wn

is g

ener

al p

oint

s-of

-con

nect

ion

guid

es o

nly

and

is n

ot in

tend

ed fo

r or t

o in

clud

e al

l det

ails

for a

spe

cific

inst

alla

tion.

7)

Be

sure

to in

stal

l a s

witc

h an

d a

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8)

Inst

all a

mai

n sw

itch

that

can

inte

rrup

t all

the

pow

er s

ourc

es in

an

inte

grat

ed m

anne

r bec

ause

this

sys

tem

con

sist

s of

the

equi

pmen

t util

izin

g th

e m

ultip

le p

ower

sou

rces

.

9) If

ther

e ex

ists

the

poss

ibili

ty o

f rev

erse

d ph

ase,

lost

pha

se, m

omen

tary

bla

ckou

t or t

he p

ower

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed p

hase

pro

tect

ion

circ

uit l

ocal

ly.

Run

ning

the

prod

uct i

n re

vers

ed p

hase

may

bre

ak th

e co

mpr

esso

r and

oth

er p

arts

.

Page 80: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

78

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ192 - 288TATJU / TAYDU / TAYCU

C: 3

D12

0279

[Ope

ratio

n sy

stem

: Hea

t rec

over

y]

Not

es 1

) All

wiri

ng, c

ompo

nent

s an

d m

ater

ials

to b

e pr

ocur

ed o

n th

e si

te m

ust c

ompl

y w

ith th

e ap

plic

able

loca

l and

nat

iona

l cod

es.

2)

Use

cop

per c

ondu

ctor

s on

ly.

3)

As

for d

etai

ls, s

ee w

iring

dia

gram

.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

Wiri

ng s

houl

d co

mpl

y w

ith a

pplic

able

loca

l and

nat

iona

l cod

es.

5)

Uni

t sha

ll be

gro

unde

d in

com

plia

nce

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.

6) W

iring

sho

wn

is g

ener

al p

oint

s-of

-con

nect

ion

guid

es o

nly

and

is n

ot in

tend

ed fo

r or t

o in

clud

e al

l det

ails

for a

spe

cific

inst

alla

tion.

7)

Be

sure

to in

stal

l a s

witc

h an

d a

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8)

Inst

all a

mai

n sw

itch

that

can

inte

rrup

t all

the

pow

er s

ourc

es in

an

inte

grat

ed m

anne

r bec

ause

this

sys

tem

con

sist

s of

the

equi

pmen

t util

izin

g th

e m

ultip

le p

ower

sou

rces

.

9) If

ther

e ex

ists

the

poss

ibili

ty o

f rev

erse

d ph

ase,

lost

pha

se, m

omen

tary

bla

ckou

t or t

he p

ower

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed p

hase

pro

tect

ion

circ

uit l

ocal

ly.

Run

ning

the

prod

uct i

n re

vers

ed p

hase

may

bre

ak th

e co

mpr

esso

r and

oth

er p

arts

.

Page 81: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

79

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ312 - 432TATJU / TAYDU / TAYCU

C: 3

D10

9406

[Ope

ratio

n sy

stem

: Hea

t rec

over

y]

Not

es 1

) All

wiri

ng, c

ompo

nent

s an

d m

ater

ials

to b

e pr

ocur

ed o

n th

e si

te m

ust c

ompl

y w

ith th

e ap

plic

able

loca

l and

nat

iona

l cod

es.

2)

Use

cop

per c

ondu

ctor

s on

ly.

3)

As

for d

etai

ls, s

ee w

iring

dia

gram

.

4) F

ield

wiri

ng d

iagr

am is

to b

e us

ed a

s a

guid

elin

e on

ly.

Wiri

ng s

houl

d co

mpl

y w

ith a

pplic

able

loca

l and

nat

iona

l cod

es.

5)

Uni

t sha

ll be

gro

unde

d in

com

plia

nce

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.

6) W

iring

sho

wn

is g

ener

al p

oint

s-of

-con

nect

ion

guid

es o

nly

and

is n

ot in

tend

ed fo

r or t

o in

clud

e al

l det

ails

for a

spe

cific

inst

alla

tion.

7)

Be

sure

to in

stal

l a s

witc

h an

d a

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8)

Inst

all a

mai

n sw

itch

that

can

inte

rrup

t all

the

pow

er s

ourc

es in

an

inte

grat

ed m

anne

r bec

ause

this

sys

tem

con

sist

s of

the

equi

pmen

t util

izin

g th

e m

ultip

le p

ower

sou

rces

.

9) If

ther

e ex

ists

the

poss

ibili

ty o

f rev

erse

d ph

ase,

lost

pha

se, m

omen

tary

bla

ckou

t or t

he p

ower

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed p

hase

pro

tect

ion

circ

uit l

ocal

ly.

Run

ning

the

prod

uct i

n re

vers

ed p

hase

may

bre

ak th

e co

mpr

esso

r and

oth

er p

arts

.

Page 82: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

80

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

15. Electrical Characteristics

RWEQ96 - 432TATJU

Model name Units Power supply CompressorSCCR

Combination unit Independent unit Hz Volts Voltage range MCA MOP RLA

RWEQ96TATJU 60 208 / 230Max. 253 V

28.8 35 19.0

SCCR kA rms, Symmetrical

@600 V MAX: 5

Min. 187 V

RWEQ120TATJU 60 208 / 230Max. 253 V

36.5 45 20.9Min. 187 V

RWEQ144TATJU 60 208 / 230Max. 253 V

44.6 50 29.4Min. 187 V

RWEQ192TATJURWEQ96TATJU

60 208 / 230Max. 253 V

28.8 + 28.8 35 + 35 19.0 + 19.0RWEQ96TATJU Min. 187 V

RWEQ216TATJURWEQ96TATJU

60 208 / 230Max. 253 V

28.8 + 36.5 35 + 45 19.0 + 20.9RWEQ120TATJU Min. 187 V

RWEQ240TATJURWEQ120TATJU

60 208 / 230Max. 253 V

36.5 + 36.5 45 + 45 20.9 + 20.9RWEQ120TATJU Min. 187 V

RWEQ264TATJURWEQ120TATJU

60 208 / 230Max. 253 V

36.5 + 44.6 45 + 50 20.9 + 29.4RWEQ144TATJU Min. 187 V

RWEQ288TATJURWEQ144TATJU

60 208 / 230Max. 253 V

44.6 + 44.6 50 + 50 29.4 + 29.4RWEQ144TATJU Min. 187 V

RWEQ312TATJURWEQ96TATJU

60 208 / 230Max. 253 V

28.8 + 28.8 + 36.5 35 + 35 + 45 19.0 + 19.0 + 20.9RWEQ96TATJUMin. 187 VRWEQ120TATJU

RWEQ336TATJURWEQ96TATJU

60 208 / 230Max. 253 V

28.8 + 36.5 + 36.5 35 + 45 + 45 19.0 + 20.9 + 20.9RWEQ120TATJUMin. 187 VRWEQ120TATJU

RWEQ360TATJURWEQ120TATJU

60 208 / 230Max. 253 V

36.5 + 36.5 + 36.5 45 + 45 + 45 20.9 + 20.9 + 20.9RWEQ120TATJUMin. 187 VRWEQ120TATJU

RWEQ384TATJURWEQ120TATJU

60 208 / 230Max. 253 V

36.5 + 36.5 + 44.6 45 + 45 + 50 20.9 + 20.9 + 29.4RWEQ120TATJUMin. 187 VRWEQ144TATJU

RWEQ408TATJURWEQ120TATJU

60 208 / 230Max. 253 V

36.5 + 44.6 + 44.6 45 + 50 + 50 20.9 + 29.4 + 29.4RWEQ144TATJUMin. 187 VRWEQ144TATJU

RWEQ432TATJURWEQ144TATJU

60 208 / 230Max. 253 V

44.6 + 44.6 + 44.6 50 + 50 + 50 29.4 + 29.4 + 29.4RWEQ144TATJUMin. 187 VRWEQ144TATJU

Notes:1. RLA is based on the following conditions.

Indoor temp. 80.6°FDB (27°CDB) / 66.2°FWB (19°CWB) Entering water temp. 86°F (30°C)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. Maximum allowable voltage variation between phases is 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protective Device (A)RLA: Rated Load Amps. (A)SCCR: Short-Circuit Current Rating

3D109376C

Page 83: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

81

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ96 - 432TAYDU

Model name Units Power supply CompressorSCCR

Combination unit Independent unit Hz Volts Voltage range MCA MOP RLA

RWEQ96TAYDU 60 460Max. 506 V

13.0 15 8.6

SCCR kA rms, Symmetrical

@600 V MAX: 5

Min. 414 V

RWEQ120TAYDU 60 460Max. 506 V

16.5 20 9.4Min. 414 V

RWEQ144TAYDU 60 460Max. 506 V

20.2 25 13.3Min. 414 V

RWEQ192TAYDURWEQ96TAYDU

60 460Max. 506 V

13.0 + 13.0 15 + 15 8.6 + 8.6RWEQ96TAYDU Min. 414 V

RWEQ216TAYDURWEQ96TAYDU

60 460Max. 506 V

13.0 + 16.5 15 + 20 8.6 + 9.4RWEQ120TAYDU Min. 414 V

RWEQ240TAYDURWEQ120TAYDU

60 460Max. 506 V

16.5 + 16.5 20 + 20 9.4 + 9.4RWEQ120TAYDU Min. 414 V

RWEQ264TAYDURWEQ120TAYDU

60 460Max. 506 V

16.5 + 20.2 20 + 25 9.4 + 13.3RWEQ144TAYDU Min. 414 V

RWEQ288TAYDURWEQ144TAYDU

60 460Max. 506 V

20.2 + 20.2 25 + 25 13.3 + 13.3RWEQ144TAYDU Min. 414 V

RWEQ312TAYDURWEQ96TAYDU

60 460Max. 506 V

13.0 + 13.0 + 16.5 15 + 15 + 20 8.6 + 8.6 + 9.4RWEQ96TAYDUMin. 414 VRWEQ120TAYDU

RWEQ336TAYDURWEQ96TAYDU

60 460Max. 506 V

13.0 + 16.5 + 16.5 15 + 20 + 20 8.6 + 9.4 + 9.4RWEQ120TAYDUMin. 414 VRWEQ120TAYDU

RWEQ360TAYDURWEQ120TAYDU

60 460Max. 506 V

16.5 + 16.5 + 16.5 20 + 20 + 20 9.4 + 9.4 + 9.4RWEQ120TAYDUMin. 414 VRWEQ120TAYDU

RWEQ384TAYDURWEQ120TAYDU

60 460Max. 506 V

16.5 + 16.5 + 20.2 20 + 20 + 25 9.4 + 9.4 + 13.3RWEQ120TAYDUMin. 414 VRWEQ144TAYDU

RWEQ408TAYDURWEQ120TAYDU

60 460Max. 506 V

16.5 + 20.2 + 20.2 20 + 25 + 25 9.4 + 13.3 + 13.3RWEQ144TAYDUMin. 414 VRWEQ144TAYDU

RWEQ432TAYDURWEQ144TAYDU

60 460Max. 506 V

20.2 + 20.2 + 20.2 25 + 25 + 25 13.3 + 13.3 + 13.3RWEQ144TAYDUMin. 414 VRWEQ144TAYDU

Notes:1. RLA is based on the following conditions.

Indoor temp. 80.6°FDB (27°CDB) / 66.2°FWB (19°CWB) Entering water temp. 86°F (30°C)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. Maximum allowable voltage variation between phases is 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protective Device (A)RLA: Rated Load Amps. (A)SCCR: Short-Circuit Current Rating

3D109357C

Page 84: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

82

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ96 - 432TAYCU

Model name Units Power supply CompressorSCCR

Combination unit Independent unit Hz Volts Voltage range MCA MOP RLA

RWEQ96TAYCU 60 575Max. 632 V

13.0 15 6.9

SCCR kA rms, Symmetrical

@600 V MAX: 5

Min. 518 V

RWEQ120TAYCU 60 575Max. 632 V

16.3 20 7.5Min. 518 V

RWEQ144TAYCU 60 575Max. 632 V

19.9 25 10.6Min. 518 V

RWEQ192TAYCURWEQ96TAYCU

60 575Max. 632 V

13.0 + 13.0 15 + 15 6.9 + 6.9RWEQ96TAYCU Min. 518 V

RWEQ216TAYCURWEQ96TAYCU

60 575Max. 632 V

13.0 + 16.3 15 + 20 6.9 + 7.5RWEQ120TAYCU Min. 518 V

RWEQ240TAYCURWEQ120TAYCU

60 575Max. 632 V

16.3 + 16.3 20 + 20 7.5 + 7.5RWEQ120TAYCU Min. 518 V

RWEQ264TAYCURWEQ120TAYCU

60 575Max. 632 V

16.3 + 19.9 20 + 25 7.5 + 10.6RWEQ144TAYCU Min. 518 V

RWEQ288TAYCURWEQ144TAYCU

60 575Max. 632 V

19.9 + 19.9 25 + 25 10.6 + 10.6RWEQ144TAYCU Min. 518 V

RWEQ312TAYCURWEQ96TAYCU

60 575Max. 632 V

13.0 + 13.0 + 16.3 15 + 15 + 20 6.9 + 6.9 + 7.5RWEQ96TAYCUMin. 518 VRWEQ120TAYCU

RWEQ336TAYCURWEQ96TAYCU

60 575Max. 632 V

13.0 + 16.3 + 16.3 15 + 20 + 20 6.9 + 7.5 + 7.5RWEQ120TAYCUMin. 518 VRWEQ120TAYCU

RWEQ360TAYCURWEQ120TAYCU

60 575Max. 632 V

16.3 + 16.3 + 16.3 20 + 20 + 20 7.5 + 7.5 + 7.5RWEQ120TAYCUMin. 518 VRWEQ120TAYCU

RWEQ384TAYCURWEQ120TAYCU

60 575Max. 632 V

16.3 + 16.3 + 19.9 20 + 20 + 25 7.5 + 7.5 + 10.6RWEQ120TAYCUMin. 518 VRWEQ144TAYCU

RWEQ408TAYCURWEQ120TAYCU

60 575Max. 632 V

16.3 + 19.9 + 19.9 20 + 25 + 25 7.5 + 10.6 + 10.6RWEQ144TAYCUMin. 518 VRWEQ144TAYCU

RWEQ432TAYCURWEQ144TAYCU

60 575Max. 632 V

19.9 + 19.9 + 19.9 25 + 25 + 25 10.6 + 10.6 + 10.6RWEQ144TAYCUMin. 518 VRWEQ144TAYCU

Notes:1. RLA is based on the following conditions.

Indoor temp. 80.6°FDB (27°CDB) / 66.2°FWB (19°CWB) Entering water temp. 86°F (30°C)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. Maximum allowable voltage variation between phases is 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protective Device (A)RLA: Rated Load Amps. (A)SCCR: Short-Circuit Current Rating

4D117563

Page 85: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

83

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

16. Operation Limits16.1 Heat PumpRWEQ96 - 432TATJU / TAYDU / TAYCU

3D109400

Page 86: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

84

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

16.2 Heat RecoveryRWEQ96 - 432TATJU / TAYDU / TAYCU

C: 3D109407

Page 87: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

85

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

17. Operation Limits (Antifreeze Usage)17.1 Heat PumpRWEQ96 - 432TATJU / TAYDU / TAYCU

3D109408A

Page 88: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

86

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

17.2 Heat RecoveryRWEQ96 - 432TATJU / TAYDU / TAYCU

C: 3D109409B

Page 89: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

87

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

18. Sound Levels (Reference Data)

RWEQ96TATJU / TAYDU / TAYCU

4D109785A

Page 90: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

88

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ120TATJU / TAYDU / TAYCU

4D109786A

Page 91: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

89

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

RWEQ144TATJU / TAYDU / TAYCU

4D109787A

Page 92: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

90

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

19. Accessories19.1 Optional AccessoriesRWEQ96 - 432TATJU / TAYDU / TAYCU

Optional accessoriesRWEQ96TATJU RWEQ120TATJU RWEQ144TATJU RWEQ192 - 288TATJU RWEQ312 - 432TATJURWEQ96TAYDU RWEQ120TAYDU RWEQ144TAYDU RWEQ192 - 288TAYDU RWEQ312 - 432TAYDURWEQ96TAYCU RWEQ120TAYCU RWEQ144TAYCU RWEQ192 - 288TAYCU RWEQ312 - 432TAYCU

Cool / Heat selector (Note 2) KRC19-26A6ABC I/P printed circuit board BRP2A81Fixing box KJB111A

Distributive piping

REFNET header

for 3 pipes

KHRP25M33H9 (Max.8 branch)

KHRP25M33H9 (Max.8 branch)KHRP25M72H9 (Max.8 branch)

KHRP25M33H9 (Max.8 branch)KHRP25M72H9 (Max.8 branch)

KHRP25M73HU9 (Max.8 branch)

for 2 pipes

KHRP26M22H9 (Max.4 branch)KHRP26M33H9 (Max.8 branch)

KHRP26M22H9 (Max.4 branch)KHRP26M33H9 (Max.8 branch)KHRP26M72H9 (Max.8 branch)

KHRP26M22H9 (Max.4 branch)KHRP26M33H9 (Max.8 branch)KHRP26M72H9 (Max.8 branch)

KHRP26M73HU9 (Max.8 branch)

REFNET joint

for 3 pipes

KHRP25A22T9KHRP25A33T9

KHRP25A22T9KHRP25A33T9

KHRP25M72TU9

KHRP25A22T9KHRP25A33T9

KHRP25M72TU9KHRP25M73TU9

for 2 pipes

KHRP26A22T9KHRP26A33T9

KHRP26A22T9KHRP26A33T9

KHRP26M72TU9

KHRP26A22T9KHRP26A33T9

KHRP26M72TU9KHRP26M73TU9

Outside unit multi connection piping kit

for 3 pipes — — BHFP26T84U BHFP26T126U

for 2 pipes — — BHFP22T84U BHFP22T126U

External control adaptor for outside unit DTA104A62

Notes:1. Refer to the latest drawing.2. In the case of heat recovery system.

Cool / Heat selector cannot be connected.C: 3D109401B

Page 93: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

91

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

20. Selection Procedure20.1 Selection Procedure20.1.1 Flowchart

Confirm that the number of indoor units connected to the outside unit is within limitation.

Provisionally select outside unit type and size based on limitation of connection ratio

Correct cooling & heating capacity of the outside unit for the following items

VRV system selection is complete.

Corrected capacity of the outside unit ≥ Required total heat load to the outside unit

2) Use the system peak load1) Use the sum of the peak load of each room

Define required total heat load to outside unit

Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units

Yes

No

-Piping length, level difference-Piping heat loss-Safety factor for the outside unit

-Entering water temperature-Indoor air temperature-Connection ratio

Given Conditions:· Indoor unit design temperature and humidity· Outside unit entering water temperature and water flow rates· Required heat load of each room· System peak load (if necessary)· Piping length, level difference· Specifications of indoor units (type and number)

Define safety factor for the indoor units and outside unit

[1] Given conditions

[2] Selection of indoor units

[3] Selection of outside unit

-Antifreeze ratio

-Water flow rate

Page 94: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

92

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

20.1.2 Selection Example

The following is a selection example based on total heat load for cooling.

Room ARoom H Room G

Room F

E mooRB mooRRoom C Room D

Floor plan

[1] Given conditions-Design conditionsIndoorairtemperature:67°FWB/80°FDB,Outdoorenteringwatertemperature:85°Fandwaterflowrateof25gpm.

-Determine peak load of each room (and system peak load if necessary)

-Required heat load of each room

From the above heat load calculation, the maximum heat load for the system (system peak load) is 173.2 MBH.

-Safety factorIn this example, safety factor is not used. (i. e., safety factor = 1.0)

[2] Selection of indoor unitsCalculate total heat capacity of indoor units corrected for indoor air temperature.In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.

Time Room A Room B Room C Room D Room E Room F Room G Room H Total9:00 16.4 16.5 10.4 10.4 30.9 30.8 10.0 10.0 135.4

12:00 22.4 24.4 17.3 17.3 25.1 23.2 13.7 13.7 157.114:00 30.7 32.2 16.8 16.8 24.9 23.4 14.2 14.2 173.216:00 36.1 36.4 13.3 13.3 21.5 21.2 13.0 13.0 167.8

Total heat load (MBH)

Level difference10 ft.

Select VRV indoor units FXMQ-PB series for each room.

Equivalent pipe length 100 ft.

Page 95: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

93

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Capacity table of indoor unitCooling Capacity

TC: Total capacity: MBHSHC: Sensible heat capacity: MBH

Selection results of indoor units

[3] Selection of outside unit[3] –1 Define the required total heat load from the indoor units to the outside unitDefinetherequiredtotalheatload(A)basedon(1)thesumofthepeakloadofeachroomor(2)thesystempeakload.In this example, select an outside unit by (2).Therefore, (A) = 173.2 MBH

Model Capacity indication

Indoor air temp.°FWB (Te: 43°F (6°C))61 64 67 70 72 75

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH

FXMQ07PBVJU 07 5.9 5.7 6.7 6.1 7.5 6.4 7.6 6.7 7.8 6.1 7.9 6.0FXMQ09PBVJU 09 7.5 6.9 8.5 7.3 9.5 7.8 9.7 8.1 9.8 7.1 10.0 7.2FXMQ12PBVJU 12 9.5 8.5 10.7 9.1 12.0 9.7 12.2 10.0 12.4 9.2 12.6 9.2FXMQ15PBVJU 15 11.8 10.8 13.4 11.3 15.0 12.0 15.3 12.2 15.5 12.2 15.8 10.1FXMQ18PBVJU 18 14.2 13.9 16.1 14.7 18.0 15.6 18.4 16.1 18.6 14.6 18.9 12.1FXMQ24PBVJU 24 19.0 16.5 21.5 17.7 24.0 18.8 24.5 19.2 24.8 17.9 25.3 20.1FXMQ30PBVJU 30 23.7 20.8 26.8 22.3 30.0 23.8 30.6 24.4 31.0 22.5 31.6 22.5FXMQ36PBVJU 36 28.4 25.0 32.2 26.9 36.0 28.8 36.7 30.0 37.2 27.7 37.9 27.7FXMQ48PBVJU 48 37.9 31.3 43.0 33.6 48.0 35.8 49.0 36.9 49.6 34.7 50.5 33.2FXMQ54PBVJU 54 42.6 35.2 48.3 37.8 54.0 40.3 55.1 41.5 55.8 39.0 56.8 37.4

Room A Room B Room C Room D Room E Room F Room G Room HMax. heat load (MBH) 36.1 36.4 17.3 17.3 30.9 30.8 14.2 14.2

Selected IDU FXMQ48PBVJU FXMQ48PBVJU FXMQ18PBVJU FXMQ18PBVJU FXMQ36PBVJU FXMQ36PBVJU FXMQ15PBVJU FXMQ15PBVJUCorrected TC (MBH) 48.0 48.0 18.0 18.0 36.0 36.0 15.0 15.0

* In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.

Page 96: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

94

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

[3] –2 Provisionally select outside unit(1) Calculate CI (Capacity Index) of the selected indoor units.

CI of VRV indoor units CI of FXMQ15PBVJU = 15 CI of FXMQ18PBVJU = 18 CI of FXMQ36PBVJU = 36 CI of FXMQ48PBVJU = 48

Capacity Range 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 7.5 9.5 12 15 18 20 24 30 36 42 48 54 72 96

Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB —

5 ton60

— — VJU

0.5 ton5.8

Calculate the total CI of the indoor units.Total CI = 15 × 2 + 18 × 2 + 36 × 2 + 48 × 2 = 234

(2) Provisionally select an outside unit based on the total CI of the indoor units

The connection ratio of RWEQ-TA shall be between 50% and 150%.As the total CI of the indoor units is 234, outside units from 16 ton to 36 ton are connectable.Start from 16 ton which is the smallest outside unit.

(3) Confirm that the number of the connected indoor units is within the limitation.

The number of the connected indoor units = 8The max. number of connectable indoor units of 16 ton outside unit = 33

Page 97: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

95

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

[3] –3 Calculate the corrected capacity of the outside unit.-Calculate the connection ratio of the system.Total CI = 234, CI of RWEQ192TATJU = 192Connection ratio = 234 / 192 = 122%

-Usingthecapacitytableoftheoutsideunit,calculatethecapacity(B)correctedforoutsideenteringwatertemperature,waterflowrate,indoorairtemperature, and connection ratio.

*Incasetheoutsideenteringwatertemperature,waterflowrate,theindoorairtemperature,ortheconnectionratiofallsbetweentemperatureslisted in the table, calculate the capacity by interpolation.

120% 122% 130%

228 (B) 232

Connection ratio

Cooling capacity

(B) = 228 + (232 – 228) × (122 – 120) / (130 – 120) = 228.8

Page 98: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

96

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

-Confirmcapacitycorrectionfactorbypipinglengthandleveldifference(K1)

(K1) = 0.984

0.984

10

100

-Calculate capacity correction factor by piping heat loss (K2)(K2) = 1 + (heat loss factor per feet of piping × (equivalent piping length – 25 ft.)) / 100

In cooling mode, heat loss factor per feet at 93°F is calculated as below.(R) Heat loss factor per feet = 0.072*2 + (0.098*1 – 0.072*2) × (93*3 – 86*4) / (95*5 – 86*4) = 0.0922

Using “Equivalent piping length = 100 ft” and “Heat loss factor per feet = 0.0922”, (K2) = 1 + (0.0922 × (100 – 25)) / 100 = 1.07

Cooling Ambient temperature

Heat loss factor per feet of piping (%)

41°F 50°F 59°F 68°F 77°F 86°F*4 93°F*3 95°F*5 104°F0.000 0.000 0.013 0.030 0.046 0.072*2 (R) 0.098*1 0.125

erutarepmet tneibmAgnitaeH

Heat loss factor per feet of piping (%)

5°F 14°F 23°F 32°F 41°F 50°F 59°F 68°F0.328 0.305 0.282 0.256 0.233 0.210 0.187 0.161

-Calculate capacity correction factor by antifreeze loss (K3)It is 1.0 when using water.Antifreeze Correction Factor

Ethylene Glycol Propylene Glycol

Cooling Capacity

10% 0.998

Cooling Capacity

10% 0.99220% 0.994 20% 0.98830% 0.990 30% 0.98340% 0.985 40% 0.97450% 0.980 50% 0.968

Heating Capacity

10% 0.993

Heating Capacity

10% 0.98520% 0.989 20% 0.98230% 0.986 30% 0.97840% 0.982 40% 0.97050% 0.979 50% 0.966

CA12A095B-Calculate the corrected capacity of RWEQ216TATJU by using (K1), (K2) and (K3).Corrected capacity of RWEQ216TATJU = (B) × (K1) × (K3) / (K2)Therefore (C) = 228.8 × 0.984 × 1.0 / 1.07 = 210 MBH

If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.If (C) < (A), return to Procedure [3]–2 and provisionally select a larger outside unit.In this example, 210 MBH (C) > 173.2 MBH (A), so there is no need to select a larger outside unit.

Page 99: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

97

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

21. Instructions for Antifreeze Usage21.1 Instruction of Setting Water (Brine) Lower Flow Limit % for Variable Flow SystemPleasesetthefieldsetting[2-24]accordingtolocalpump/valveinstallationsituationandoperatevariableflowcontrol.

[2-24-0]:VariableflowcontrolfunctionisOFF.(default)[2-24-1]: One pump/valve per module

Pump/valve on secondary units remain ON when secondary units are OFF.[2-24-3]: One pump/valve per module

Pump/valve on secondary units are OFF when secondary units are OFF.Please connect the valve/pump for each unit.

Sub2 Sub1 Main

H/E H/E

Pump

Pump Operation

Indoor unit

Outside unitOutside unitOutside unit

H/E

H/E : Heat exchanger

[2-24-2]: One pump/valve per system

Sub2 Sub1 Main

H/E H/E H/E

Pump

Pump Operation

Indoor unit

Outside unitOutside unitOutside unit

Page 100: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

98

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Pleasesetthefieldsetting[2-25]sothattheminimumwatervolumedoesnotgodownbelow13.2gpm(50L/min).Whenusingbrineatenteringwatertemperatureof50˚F(10˚C)orless,pleasesettheminimumwaterflowlimitto21.2gpm(80L/min)ormore.lowerlimitwater(brine)flowratesettingforvariablewaterflow

[2-25] Flow%ofmaxflowrate DC output (V)

— 0%(thermo-off) 2.0

0 10% 2.71 20% 3.42 30% 4.13 40% 4.8

4(default) 50% 5.55 60% 6.26 70% 6.97 80% 7.6— 90% 8.3

— 100%(Localmaxflowrate) 9.0

When the unit stop or thermo-off, the DC output is 2.0 V.

[Example]Whenthelocal100%flowrate= 39.6 gpm (150 L/min) usingwater,Whenthewaterflowoperatesinproportion to the voltage. 2.0 V: 0%- 9.0 V: 100% Lower limit case 13.2 gpm (50 L/min) for using water.

(b)13.2 gpm (lower limit water volume)

(a)39.6 gpm (local 100% flow rate)= 0.33 33%

Please select the closest setting with a value of 33% or more. set to [2-25-3] (40%)So,lowerflowratewillbe(c)15.8gpm(60L/min)And DC output range is (d) 4.8-9.0 V

100% Water (brine) volume

9.0 V

DC Output(2-9 V)

0%

2.0 V

5.5 V

80%

7.6 V

50%

(Default) DC output range5.5-9.0 V

Water volume39.615.8

(a)(b)

100%

9.0 V

0%

2.0 V

4.8 V

40%13.233%

(c)

(d)DC output range4.8-9.0 V

(gpm)

DC Output(2-9 V)

lower limit

Page 101: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

99

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

22. Caution for Refrigerant Leaks22.1 Introduction

Points to note in connection with refrigerant leaks

The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant.Neverthelesscaremustbetakentoensurethatairconditioningfacilitiesareinstalledinaroomwhichissufficientlylarge.Thisassuresthat the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.

Maximum concentration levelThe maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is lb./1000 ft.³ (the weight in Ibs. of the refrigerant gas in 1 ft.³ volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.

Direction of therefrigerant flow

Room where refrigerant leak has occurred(outflow of all the refrigerant from the system)

Pay special attention to places, such as basements, etc. where refrigerant can stay, since refrigerant is heavier than air.

Page 102: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

100

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

22.2 Procedure for Checking Maximum Concentration

Check the maximum concentration in accordance with steps 1 to 4 below and take whatever action is necessary.

Step1: Calculate the amount of refrigerant (lbs.) charged to each system separately.

Note:Where a single refrigerant facility is divided onto 2 entirely independent refrigerant systems then use the amounts of refrigerant with which each separate system of charged.

Step 2: Calculate the smallest room volume (ft.³)In case like the following, calculate the volume of (a), (b) as a single room or as the smallest room.(a) Where there are no smaller room divisions.

(b)Wherethereisaroomdivisionbutthereisanopeningbetweentheroomssufficientlylargetopermitafreeflowofairbackandforth.

(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15% or moreofthefloorarea.)

(c) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target.

Page 103: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

101

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Step 3: Calculate the refrigerant density using the results of the calculations in step 1 and 2 above.

Total volume of refrigerantin the refrigerant system

≤Maximumconcentrationlevel(lbs./ft.³)Size (ft.³) of the smallest room inwhich there is an indoor unitinstalled

If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so on until the result falls short of the concentration level.

Step 4: Dealing with the situations where the result exceeds the maximum concentration level.Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system design.Please consult Daikin supplier.

Page 104: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

102

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

23. Safety Devices Setting23.1 FXFQ-T

Model FXFQ07TVJU FXFQ09TVJU FXFQ12TVJU FXFQ15TVJU FXFQ18TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F (°C) – – – – –Fan motor thermal protector °F (°C) – – – – –Fan motor thermal fuse °F (°C) – – – – –

Model FXFQ24TVJU FXFQ30TVJU FXFQ36TVJU FXFQ48TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F (°C) – – – –Fan motor thermal protector °F (°C) – – – –Fan motor thermal fuse °F (°C) – – – –

C: 3D086932B

23.2 FXZQ-TA

Model FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F (°C) – – – – – –Fan motor thermal protector °F (°C) – – – – – –Drain pump fuse °F (°C) – – – – – –

C: 4D110603

23.3 FXUQ-P

Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F (°C) – – – –Fan motor thermal protector °F (°C) – – – –Fan motor thermal fuse °F (°C) – – – –

C: 3D090213

23.4 FXEQ-P

Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJUPrinted circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A

Fan motor thermal protector °F (°C)OFF: 223±9

(106±5)ON: 205±27

(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9 (106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

C: 4D098709

Page 105: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

103

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

23.5 FXDQ-M

Model FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJUPrinted circuit board fuse A1P 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

C: 3D051758

23.6 FXSQ-TA

Model FXSQ05TAVJU FXSQ07TAVJU FXSQ09TAVJU FXSQ12TAVJU FXSQ15TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) — — — — —

Model FXSQ18TAVJU FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) — — — — — —

3D112398

23.7 FXMQ-PB

Model FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

Model FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F (°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

C: 3D086916B

23.8 FXMQ-M

Model FXMQ72MVJU FXMQ96MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – –

Fan motor thermal protector °F OFF: 275±14(ON: 189±27)

OFF: 275±14(ON: 189±27)

Page 106: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

104

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

23.9 FXHQ-M

Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – – –

Fan motor thermal protector °F OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

C: 3D049334A

23.10 FXAQ-P

Model FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F – – – – –Fan motor thermal protector °F – – – – –

C: 4D047085D

23.11 FXLQ-M, FXNQ-M

Model FXLQ07MVJUFXNQ07MVJU

FXLQ09MVJUFXNQ09MVJU

FXLQ12MVJUFXNQ12MVJU

FXLQ18MVJUFXNQ18MVJU

FXLQ24MVJUFXNQ24MVJU

Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F (°C)OFF: 275±18

(135±18)ON: 248 (120)

or less

OFF: 275±18(135±18)

ON: 248 (120)or less

OFF: 275±18(135±18)

ON: 248 (120)or less

OFF: 275±18(135±18)

ON: 248 (120)or less

OFF: 275±18(135±18)

ON: 248 (120)or less

C: 3D045646B

23.12 FXTQ-TA

Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUAModel (with factory disconnect) FXTQ09TAVJUD FXTQ12TAVJUD FXTQ18TAVJUD FXTQ24TAVJUD FXTQ30TAVJUD

Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

Model FXTQ36TAVJUA FXTQ42TAVJUA FXTQ48TAVJUA FXTQ54TAVJUA FXTQ60TAVJUAModel (with factory disconnect) FXTQ36TAVJUD FXTQ42TAVJUD FXTQ48TAVJUD FXTQ54TAVJUD FXTQ60TAVJUD

Printed circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

Page 107: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

105

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Appendix

1. Introduction .............................................................................................1061.1 ED Book List .................................................................................1061.2 Publication List of Engineering Data for VRV Products ................107

2. GuideSpecifications ...............................................................................1092.1 GuideSpecifications .....................................................................109

Page 108: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

106

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

1. Introduction1.1 ED Book List

Design Manual ..................................................... RWEQ-TA ........ EDUS301864-D (This booklet)

Indoor Units

Ceiling Mounted Cassette Type (Round Flow with Sensing) ....... FXFQ-T ..... EDUS391400A-F14

VISTA™ 2 × 2 Cassette Unit .................................. FXZQ-TA .......... EDUS391776-F9

4-Way Blow Ceiling-Suspended Type ...................... FXUQ-P ........ EDUS391437-F15

One Way Blow Cassette Type ................................ FXEQ-P ........ EDUS391533-F16

Slim Ceiling Mounted Duct Type ............................. FXDQ-M ........... EDUS39-600-F2

MSP Concealed Duct Unit ..................................... FXSQ-TA ........ EDUS391777-F17

Ceiling Mounted Duct Type .................................... FXMQ-PB ........ EDUS391503A-F4

Ceiling Mounted Duct Type .................................... FXMQ-M ....... EDUS39-900A-F11

Ceiling Suspended Type ....................................... FXHQ-M ........... EDUS39-600-F5

Wall Mounted Type .............................................. FXAQ-P .......... EDUS391100-F6

Floor Standing Type / Concealed Floor Standing Type ........ FXLQ-MFXNQ-M .......... EDUS391502-F7

Air Handling Unit .................................................. FXTQ-TA ....Engineering Data FXTQ-TA

Air Treatment Equipment

Outdoor Air Processing Unit ................................... FXMQ-MF ....... EDUS39-900A-F10

Energy Recovery Ventilator .................................... VAM-G ............. EDUS711116A

Outdoor Units Capacity Table Book

Heat Pump ......................................................... RWEQ-TA ............ EDUS301864-C

Controls ............................................................................................. (Coming soon)

Remote Controller

Navigation Remote Controller ................................. BRC1E73 ............... EDUS721438

Page 109: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

107

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

1.2 Publication List of Engineering Data for VRV Products

Refrigerant Type Product Series Book No. Type Hz Volts Model name Area Note Published in

R410A

Air cooled

Inverter T, PC

EDUS371435-M H/R 60 Hz460 V208/230 V460 V208/230 V

REYQ72-456TYDNREYQ72-456TTJUREYQ72-120PCYDREYQ72-144PCTJ

USA Generalinformation Aug. 2015

EDUS371435-N H/R 60 Hz460 V208/230 V460 V208/230 V

REYQ72-456TYDNREYQ72-456TTJUREYQ72-120PCYDREYQ72-144PCTJ

USA Installation Jul. 2015

EDUS371435-R3 H/R 60 Hz 460 V REYQ72-120PCYD USA Specification Mar. 2015EDUS371435-R4 H/R 60 Hz 208/230 V REYQ72-144PCTJ USA Specification Mar. 2015

Inverter TA

EDUS341703-M H/P 60 Hz 460 V208/230 V

RXYQ72-408TAYDURXYQ72-408TATJU USA General

information Jun. 2017

EDUS341703-N H/P 60 Hz 460 V208/230 V

RXYQ72-408TAYDURXYQ72-408TATJU USA Installation Jul. 2017

EDUS341703A-R1 H/P 60 Hz 460 V RXYQ72-408TAYDU USA Specification Sep. 2018EDUS341703A-R2 H/P 60 Hz 208/230 V RXYQ72-408TATJU USA Specification Sep. 2018

EDUS371704-M H/R 60 Hz 460 V208/230 V

REYQ72-456TAYDUREYQ72-456TATJU USA General

information Jun. 2017

EDUS371704-N H/R 60 Hz 460 V208/230 V

REYQ72-456TAYDUREYQ72-456TATJU USA Installation Jul. 2017

EDUS371704B-R1 H/R 60 Hz 460 V REYQ72-456TAYDU USA Specification Dec. 2018EDUS371704B-R2 H/R 60 Hz 208/230 V REYQ72-456TATJU USA Specification Nov. 2018EDUS341824-D H/P 60 Hz 575 V RXYQ72-384TAYCU Canada Design manual Jun. 2018

EDUS341824-C H/P 60 Hz 575 V RXYQ72-384TAYCU Canada Capacity table book Jun. 2018

EDUS371706-M H/R 60 Hz 575 V REYQ72-384TAYCU Canada General Information Jun. 2017

EDUS371706-N H/R 60 Hz 575 V REYQ72-384TAYCU Canada Installation Jul. 2017EDUS371706B-R H/R 60 Hz 575 V REYQ72-384TAYCU Canada Specification Dec. 2018

EDUS371705A-M H/R 60 Hz208/230 V460 V

RELQ72-240TATJURELQ72-240TAYDU

USACanada General

Information Oct. 2017575 V RELQ72-240TAYCU Canada

EDUS371705A-N H/R 60 Hz208/230 V460 V

RELQ72-240TATJURELQ72-240TAYDU

USACanada Installation Oct. 2017

575 V RELQ72-240TAYCU Canada

EDUS371705B-R H/R 60 Hz208/230 V460 V

RELQ72-240TATJURELQ72-240TAYDU

USACanada Specification Sep. 2018

575 V RELQ72-240TAYCU Canada

EDUS341819-D H/P 60 Hz208/230 V460 V

RXLQ72-240TATJURXLQ72-240TAYDU

USACanada Design manual Jun. 2018

575 V RXLQ72-240TAYCU Canada

EDUS341819-C H/P 60 Hz208/230 V460 V

RXLQ72-240TATJURXLQ72-240TAYDU

USACanada Capacity table

book Jun. 2018575 V RXLQ72-240TAYCU Canada

EDUS331608B-M H/P 60 Hz 208/230 V RXTQ36TAVJ9RXTQ48/60TAVJU USA General

information Feb. 2018

EDUS331608B-N H/P 60 Hz 208/230 V RXTQ36TAVJ9RXTQ48/60TAVJU USA Installation Jan. 2018

EDUS331608B-R H/P 60 Hz 208/230 V RXTQ36TAVJ9RXTQ48/60TAVJU USA Specification Jan. 2018

Water cooled

EDUS301716-M H/P,H/R 60 Hz 208/230 V

460 VRWEQ96-432TATJURWEQ96-432TAYDU USA General

information Mar. 2018

EDUS301716A-N H/P,H/R 60 Hz 208/230 V

460 VRWEQ96-432TATJURWEQ96-432TAYDU USA Installation Dec. 2018

EDUS301716-R H/P,H/R 60 Hz 208/230 V

460 VRWEQ96-432TATJURWEQ96-432TAYDU USA Specification Mar. 2018

EDUS301864-D H/P, H/R 60 Hz

208/230 V 460 V

RWEQ96-432TATJU RWEQ96-432TAYDU

USACanada Design manual Dec. 2018

575 V RWEQ96-432TAYCU Canada

EDUS301864-C H/P, H/R 60 Hz

208/230 V 460 V

RWEQ96-432TATJU RWEQ96-432TAYDU

USACanada Capacity table

book Nov. 2018575 V RWEQ96-432TAYCU Canada

Page 110: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

108

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

Refrigerant Type Product Series Book No. Type Hz Volts Model name Area Note Published in

R410A

VRV Indoor units

EDUS391400A-F14 – 60 Hz – FXFQ07-48TVJU USA

Ceiling Mounted Cassette (Round Flow with Sensing) Type

May 2018

EDUS391776-F9 – 60 Hz – FXZQ05-18TAVJU USA VISTA™ 2 x 2 Cassette Unit Mar. 2018

EDUS391437-F15 – 60 Hz – FXUQ18-36PVJU USA4-Way Blow Ceiling-Suspended Type

May 2015

EDUS391533-F16 – 60 Hz – FXEQ07-24PVJU USA One Way Blow Cassette Type Oct. 2015

EDUS39-600-F2 – 60 Hz – FXDQ07-24MVJU USASlim Ceiling Mounted Duct Type

Sep. 2006

EDUS391777-F17 – 60 Hz – FXSQ05-54TAVJU USAMSP Concealed Ducted Unit

Mar. 2018

EDUS391503A-F4 – 60 Hz – FXMQ07-54PBVJU USA

Ceiling Mounted Duct Type (Middle and High Static Pressure)

May 2018

EDUS39-900A-F11 – 60 Hz – FXMQ72/96MVJU USACeiling Mounted Duct Type

May 2010

EDUS39-600-F5 – 60 Hz – FXHQ12-36MVJU USACeiling Suspended Type

Sep. 2006

EDUS391100-F6 – 60 Hz – FXAQ07-24PVJU USA Wall Mounted Type Jan. 2012

EDUS391502-F7 – 60 Hz – FXLQ07-24MVJUFXNQ07-24MVJU USA

Floor Standing TypeConcealed Floor Standing Type

Jul. 2015

Engineering Data FXTQ-TA – 60 Hz – FXTQ09-60TAVJUA

FXTQ09-60TAVJUD USA Air Handling Unit Sep. 2016

EDUS39-900A-F10 – 60 Hz – FXMQ48-96MFVJU USAOutdoor Air Processing Unit

May 2010

EDUS391434-B – 60 Hz – BSQ36-96TVJ USA Single Branch Selector Unit Aug. 2015

EDUS391434-B – 60 Hz – BS4-12Q54TVJ USA Multi Branch Selector Unit Aug. 2015

Controls and networks

EDUS721867-T – – –

BRC1E73, BRC4C/7C/7E, BRC2A71DCS302C71, DCS301C71,DST301BA61, DCS601C71KRP1C74/75

USA

Remote controllerControl devices

Adaptor

Coming soon

EDUS721438 – – – BRC1E73 USANavigation remote controller

Apr. 2015

EDUS721212 – – – DCM601A71DCM601A72 USA

intelligent Touch Manager

Oct. 2012

EDUS72-608 – – – DCS601C71 USAintelligent Touch Controller

Dec. 2006

EDUS72-749 – – – DMS502B71 USAInterface for use in BACnet®

Oct. 2007

Option for all type OHUS07-1 – – – For indoor and outdoor units USA Option

handbook Nov. 2007

Energy Recovery Ventilator (VAM) EDUS711116A – 60 Hz – VAM300-1200GVJU USAEnergy Recovery Ventilator

Jun. 2017

EDUS301864-D, C as shown by .C/O : Cooling onlyH/P : Heat pumpH/R : Heat recovery

Page 111: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

109

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

2. Guide Specifications2.1 Guide Specifications

GeneralUnit shall be air cooled, split type multi-system air conditioner consisting of one outside unit and plural indoor units, each having capability to cool or heat independently for the requirements of the rooms.Up to 13 different type indoor units can be connected to one refrigerant circuit and controlled individually. Compressor shall be equipped with inverter controller, and capable of changing the rotating speed to follow variations in cooling and heating load.Outside unit shall be suitable for mix-match connection of following models.

�� Ceiling Mounted Cassette Type (Round Flow with Sensing)�� VISTA™ 2 × 2 Cassette Unit�� 4-Way Blow Ceiling-Suspended Type�� One Way Blow Cassette Type�� Slim Ceiling Mounted Duct Type�� MSP Concealed Ducted Unit�� Ceiling Mounted Duct Type (Middle and High Static Pressure)�� Ceiling Mounted Duct Type�� Ceiling Suspended Type�� Wall Mounted Type�� Floor Standing Type�� Concealed Floor Standing Type�� Air Handling Unit

�� Refrigerant : R410A

2.1.1 TA Series Outside Unit

The actual refrigerant piping length shall be extended up to 540 ft. (165 m) with 164 ft. (50 m) *1 level difference without any oil traps.�� Air conditioner shall operate continuously at the inlet water temperature from 50°F (10°C) to 113°F (45°C) in cooling and heating.

Both indoor unit and outside unit are assembled, tested, and charged with refrigerant at the factory. *1. The value is based on the case where the outside unit is located above indoor unit. Where the outside unit is located under the indoor unit, the level difference is a maximum of 130 ft. (40 m). It is possible to be used at low water temperature by using brine, satisfying installation condition.

Outside UnitThe outside unit shall be a factory assembled unit with frameless casing structure. The outside units should be installed in indoors.

CompressorThecompressorshallbeofhighlyefficienthermeticscrolltypeandequippedwithinvertercontrolcapableofchangingthespeedinaccordancetothe cooling or heating load requirement.�� Theoutsideunitshallhavethemulti-stepofcapacitycontroltomeetloadfluctuationandindoorunitindividualcontrol.

Heat ExchangerStainless plate type heat exchanger.

Refrigerant CircuitThe refrigerant circuit shall include liquid, suction gas and high & low pressure gas shut off valves and a solenoid valves.All necessary safety devices shall be provided to ensure the safety operation of the system.

Safety DevicesThe following safety devices shall be part of the outside unit.High Pressure Switch, Inverter Overload Protector, Fusible Plugs, Leak Detecting Device, Overcurrent Fuse.

Oil Recovery SystemUnit shall be equipped with an oil recovery system to ensure stable operation with long refrigerant piping.

Page 112: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

110

RWEQ-TATJU / RWEQ-TAYDU / RWEQ-TAYCU EDUS301864-D

2.1.2 Indoor Units

Each indoor unit shall be of the Ceiling Mounted Cassette Type (Round Flow with Sensing), VISTA™ 2 × 2 Cassette Unit, 4-Way Blow Ceiling-Suspended Type, One Way Blow Cassette Type, Slim Ceiling Mounted Duct Type, MSP Concealed Ducted Unit, Ceiling Mounted Duct Type (Middle and High Static Pressure), Ceiling Mounted Duct Type, Ceiling Suspended Type, Wall Mounted Type, Floor Standing Type, Concealed FloorStandingType,orAirHandlingUnit.Itshallhaveelectroniccontrolvalvewhichcontrolsrefrigerantflowrateinrespondtoloadvariationsofthe room. The fan shall be of the multi blade type and statically and dynamically balanced to ensure low noise and vibration free operation.�� The address of the indoor unit shall be set automatically in case of individual and group control.�� In case of centralized control, it shall be set by remote controller.

ControlComputerized PID control shall be used to maintain a correct room temperature.Unit shall be equipped with a self-diagnosis for easy and quick maintenance and service.The LCD (Liquid Crystal Display) remote controller shall memorize the latest malfunction code for easy maintenance.�� Itshallbeabletocontrolupto16indoorunitsandchangefanspeedandangleofswingflapindividuallyinthegroup.

Central Remote Controller (Option)A multi-functional centralized control equipment (central remote controller) shall be supplied as optional accessory.�� It shall be able to control up to 64 Zones of 64 indoor unit groups (each group consists of max. 16 indoor units) or 128 indoor units with the following

functions. a) Temperature setting for each Zone, or group, or indoor unit. b) ON/OFF as a Zone or individual unit. c) Indication of operating condition. d) Select one of 10 operation modes for each Zone.�� The controller shall have wide screen LCD and can be wired by a non-polar 2-wire transmission cable to a distance of 3280 ft. (1000 m) away from

the indoor unit.

Unified ON / OFF Controller (Option)UnifiedON/OFFcontrollershallbesuppliedasoptionalaccessory.It shall be able to control up to 16 indoor unit groups (each group consists of max. 16 indoor units) or 128 indoor units with the following functions.a) ON/OFF as a zone or individual unit.b) Indication of operation condition of each group.c) Select one of 4 operation modes.

It shall be wired by a non-polar 2-wire transmission cable to a distance of 3280 ft. (1000 m) away from indoor unit.

Schedule Timer (Option)A schedule timer shall be supplied as optional accessory.�� It shall be able to set operation schedule of up to 128 indoor units.

The operation schedule shall include twice ON/OFF a day and holiday.�� It shall be able to set 8 patterns of schedule combined with centralized controller.

intelligent Touch Controller (Option)Air-conditioning management system that can be controlled by a compact all-in-one unit.

intelligent Touch Manager (Option)Air-conditioning management system that can be controlled by a compact all-in-one unit.

Page 113: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …
Page 114: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …
Page 115: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …
Page 116: Design Manual...Design Manual RWEQ-TATJU, 208 / 230 V RWEQ-TAYDU, 460 V RWEQ-TAYCU, 575 V EDUS301864-D 201812 Engineering Data Heat Pump 60 Hz Heat Recovery 60 Hz 1 RWEQ-TATJU / …

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any inquiries, please contact your local importer, distributor and/or retailer.

©All rights reserved 12/18 FS

●Specifications, designs and other content appearing in this brochure are current as of December 2018 but subject to change without notice.

EDU

S301864-DENG

INEERING DATA VRV T-SERIES W

ATER COO

LED SYSTEM RW

EQ-TATJU RW

EQ-TAYDU RW

EQ-TAYCU H/P 60 Hz H/R 60 Hz DESIG

N MANUAL