design and control of ventilation systems - seventhwave · march 15 & 16 power quality...
TRANSCRIPT
The ‘V’ in HVAC: design and control of
ventilation systems
Presenter: John Murphy
February 16, 2017 in La Crosse
Upcoming courses
www.seventhwave.org/education/events
Commercial courses
March 15 & 16 Power quality management and arc flash safety
May 17 & 18 Power quality management and arc flash safety
On-demand webinars
www.seventhwave.org/education/webinars
Course description
Ventilation is critical for making a building safe and
comfortable. This full-day course will begin with a
discussion of ventilation fundamentals, the
requirements of ASHRAE Standard 62.1 and an
overview of the various types of ventilation
systems. Then we will dig deeper into energy
saving ventilation strategies, such as demand
controlled ventilation and exhaust air energy
recovery. Finally, we will discuss the design and
control of dedicated outdoor air systems.
Learning objectives
EXPLAIN the requirements of ASHRAE Standard 62.1 that impact the
design and control of ventilation systems
DESCRIBE how ASHRAE 62.1 relates to meeting LEED prerequisites and
earning credit points
DISCUSS demand controlled ventilation strategies for single zone
systems, dedicated outdoor air systems and multiple zone VAV systems
DESCRIBE how to properly apply exhaust air energy recovery in building
ventilation systems
EXPLAIN how to design and control dedicated outdoor air systems that
balance indoor air quality and energy efficiency
American Institute of Architects
Seventhwave is a Registered Provider with The American Institute of
Architects Continuing Education Systems (AIA/CES). Credit(s) earned
on completion of this program will be reported to AIA/CES for AIA
members. Certificates of Completion for both AIA members and non-
AIA members are available upon request.
This program is registered with AIA/CES for continuing professional
education. As such, it does not include content that may be deemed or
construed to be an approval or endorsement by the AIA of any material
of construction or any method or manner of handling, using, distributing,
or dealing in any material or product.
Questions related to specific materials, methods, and services will be
addressed at the conclusion of this presentation.
Provider #: G175
Course #: COM346
This course has been registered with
GBCI for CE hours.
REGISTERED
FOR:
BY
NUMBER OF
CE HOURS:
COURSE NAME
PROVIDER NAME
The ‘V’ in HVAC: design and control of ventilation
systems
Seventhwave
6
The 'V' in HVAC:Design and Control of Ventilation Systems
John Murphy, LEED® AP BD+C
Applications Engineer
Trane
Ingersoll Rand
La Crosse, Wisconsin
February 16, 2017
La Crosse, WI
Design and Control of Ventilation Systems2
Design and Control of Ventilation Systems
Learning Objectives
1. Recognize the requirements of ASHRAE Standard 62.1
that impact the design and control of ventilation systems.
2. Understand how ASHRAE 62.1 relates to meeting LEED
prerequisites and earning credit points.
3. Apply various demand-controlled ventilation (DCV)
strategies to single-zone systems, dedicated outdoor-air
systems, and multiple-zone VAV systems.
4. Properly apply exhaust-air energy recovery in building
ventilation systems.
5. Understand how to design and control dedicated outdoor-
air systems that balance indoor air quality and energy use.
Design and Control of Ventilation Systems3
Design and Control of Ventilation Systems
Agenda
8:30 – 10:15 Ventilation Fundamentals, ASHRAE 62.1
Break
10:30 – noon Dynamic Ventilation Reset Strategies
Lunch
12:45 – 2:15 Exhaust-Air Energy Recovery
Break
2:30 – 4:00 Dedicated Outdoor-Air Systems
Design and Control of Ventilation Systems4
Ventilation Fundamentals and ASHRAE Standard 62.1
Ventilation Fundamentals and ASHRAE Standard 62.15
ventilation fundamentals and ASHRAE Standard 62.1
Agenda
• Ventilation as part of indoor air quality (IAQ)
• Types of ventilation systems
• ASHRAE Standard 62.1
– General overview
– Ventilation Rate Procedure
• Relationship between ASHRAE 62.1 and LEED
Ventilation Fundamentals and ASHRAE Standard 62.16
eight objectives
ASHRAE Indoor Air Quality Guide
1. Manage the design and construction
process to achieve good IAQ
2. Control moisture in building assemblies
3. Limit entry of outdoor contaminants
4. Control moisture and contaminants
related to mechanical systems
5. Limit contaminants from indoor sources
6. Capture and exhaust contaminants from
building equipment and activities
7. Reduce contaminant concentrations
through ventilation, filtration, and air cleaning
8. Apply more advanced ventilation approaches
Ventilation Fundamentals and ASHRAE Standard 62.17
ventilation fundamentals and ASHRAE Standard 62.1
Agenda
• Ventilation as part of indoor air quality (IAQ)
• Types of ventilation systems
• ASHRAE Standard 62.1
– General overview
– Ventilation Rate Procedure
• Relationship between ASHRAE 62.1 and LEED
Ventilation Fundamentals and ASHRAE Standard 62.18
zone
Natural Ventilation
No fan is used to deliver OA to the zone
EA OA
Ventilation Fundamentals and ASHRAE Standard 62.19
zone
Single-Zone Ventilation System
One AHU brings in OA through one intake
and distributes it to a single zone
packagedrooftop unit
EA
OA
RA
RASA
Ventilation Fundamentals and ASHRAE Standard 62.110
100% Outdoor-Air Ventilation System
One AHU brings in OA through one intake
and distributes only OA to multiple zones
dedicatedOA unit
EA
OA
SA
RAfan-coil
OA OAOA
SA
RA
SA
RA
zone 1 zone 2 zone 3
Ventilation Fundamentals and ASHRAE Standard 62.111
Multiple-Zone Recirculating System
One AHU brings in OA through one intake, mixes it with
recirculated air (RA), and distributes the mixture to multiple zones
EA
OA
PA PAPARA
VAV VAV VAV
RA RA
RA
zone 1 zone 2 zone 3
VAV air-handling unit
Ventilation Fundamentals and ASHRAE Standard 62.112
ventilation fundamentals and ASHRAE Standard 62.1
Agenda
• Ventilation as part of indoor air quality (IAQ)
• Types of ventilation systems
• ASHRAE Standard 62.1
– General overview
– Ventilation Rate Procedure
• Relationship between ASHRAE 62.1 and LEED
Ventilation Fundamentals and ASHRAE Standard 62.113
The Importance of Standard 62.1
ASHRAE Standard 62.1 is…
• The basis for many building codes
• A prerequisite for LEED certification
Ventilation Fundamentals and ASHRAE Standard 62.114
ASHRAE Standard 62.1-2013
1. Purpose
2. Scope
3. Definitions
4. Outdoor Air Quality
5. Systems and Equipment
6. Procedures
• Ventilation Rate Procedure
• IAQ Procedure
• Natural Ventilation Procedure
7. Construction and System Start-Up
8. Operations and Maintenance
Ventilation Fundamentals and ASHRAE Standard 62.115
ASHRAE Standard 62.1, Section 4
Outdoor Air Quality
• 4.1 Regional Air QualityAssess regional air quality compliance with the
National Ambient Air Quality Standard (NAAQS)
• 4.2 Local Air QualityAssess local air quality by checking for local sources
• 4.3 DocumentationReview findings with building owner
Ventilation Fundamentals and ASHRAE Standard 62.116
ASHRAE Standard 62.1, Section 5
System and Equipment Requirements
• Ventilation air distribution
• System controls
• Airstream surfaces
• Outdoor-air intakes
• Filtration
• Moisture management
– Dehumidification
– Drain pans
– Cooling coils and
humidifiers
• Access for cleaning
• Building envelope and
interior surfaces
• Air recirculation
• Exhaust and
combustion air
– Parking garage exhaust
• Environmental tobacco
smoke
Ventilation Fundamentals and ASHRAE Standard 62.117
ASHRAE Standard 62.1, Section 6
Procedures
• Ventilation Rate Procedure (Section 6.2)
– Prescriptive
– Dictates ventilation rates and calculations based on
“typical” spaces
• IAQ Procedure (Section 6.3)
– Performance-based, mass balance analysis
– Must ventilate to achieve specific concentration limits
for all contaminants of concern
• Natural Ventilation (Section 6.4)
– Generally requires a “mixed-mode” system design
Ventilation Fundamentals and ASHRAE Standard 62.118
ASHRAE Standard 62.1, Section 6.2
Ventilation Rate Procedure
• Outdoor air treatment
• Zone calculations
– Determine breathing-zone outdoor airflow for each zone
• System calculations
– Calculate outdoor-air intake flow for entire system
Ventilation Fundamentals and ASHRAE Standard 62.119
ASHRAE Standard 62.1, Section 6.2.1
Outdoor Air Treatment
If outdoor air is judged to be unacceptable in accordance
with Section 4.1, each ventilation system shall include:
– MERV 6 filter in locations where the national standard for
particulates < 10 micrometers (PM10) is exceeded
– MERV 11 filter in locations where the national standard for
particulates < 2.5 micrometers (PM2.5) is exceeded
– 40% efficient ozone-removal device in locations where the
average ozone concentration is exceeded
www.epa.gov/green-book
Ventilation Fundamentals and ASHRAE Standard 62.120
PM10 Non-Attainment Areas
Ventilation Fundamentals and ASHRAE Standard 62.121
PM2.5 Non-Attainment Areas
Ventilation Fundamentals and ASHRAE Standard 62.122
Ozone Non-Attainment Areas
Ventilation Fundamentals and ASHRAE Standard 62.123
ASHRAE Standard 62.1, Section 6.2
Ventilation Rate Procedure
• Outdoor air treatment
• Zone calculations
– Determine breathing-zone outdoor airflow for each zone
• System calculations
– Calculate outdoor-air intake flow for entire system
Ventilation Fundamentals and ASHRAE Standard 62.124
ventilation rate procedure
Zone Calculations
1. Calculate breathing-zone outdoor airflow (Vbz)
using Table 6.2.2.1 rates
Vbz = Rp × Pz + Ra × Az
2. Determine zone air-distribution effectiveness (Ez)
Look up Ez in Table 6.2.2.2
3. Calculate zone outdoor airflow (Voz)
Voz = Vbz/Ez
Ventilation Fundamentals and ASHRAE Standard 62.125
excerpt from Table 6.2.2.1
Minimum Ventilation Rates
Office 5.0 0.06
Conference room 5.0 0.06
Classroom 10.0 0.12
Lecture classroom 7.5 0.06
Retail sales 7.5 0.12
Auditorium 5.0 0.06
Rp Ra
Occupancy category cfm/p cfm/ft²
Ventilation Fundamentals and ASHRAE Standard 62.126
ventilation rate procedure
Zone Calculations
1. Calculate breathing-zone outdoor airflow (Vbz)
using Table 6.2.2.1 rates
Vbz = Rp × Pz + Ra × Az
where,
Rp = outdoor airflow rate required per person, cfm/person
Ra = outdoor airflow rate required per unit area, cfm/ft²
Pz = zone population (number of people during typical usage)
Az = zone floor area (net occupiable floor area), ft²
Ventilation Fundamentals and ASHRAE Standard 62.127
Vbz = Rp × Pz + Ra × Az
= 5 × 5 + 0.06 × 1000= 25 cfm + 60 cfm
Breathing-Zone Outdoor Airflow
Example: office space
Rp = 5 cfm/person
Ra = 0.06 cfm/ft²
Pz = 5 people
Az = 1000 ft²
breathing zone
Vbz
85 cfm
= 85 cfm
Ventilation Fundamentals and ASHRAE Standard 62.128
Vbz = Rp × Pz + Ra × Az
= 5 × 17 + 0.06 × 1000= 85 cfm + 60 cfm
Breathing-Zone Outdoor Airflow
Example: conference room
Rp = 5 cfm/person
Ra = 0.06 cfm/ft²
Pz = 17 people
Az = 1000 ft²
breathing zone
145 cfm
= 145 cfm
Vbz
Ventilation Fundamentals and ASHRAE Standard 62.129
ventilation rate procedure
Zone Calculations
1. Calculate breathing-zone outdoor airflow (Vbz)
using Table 6.2.2.1 rates
Vbz = Rp × Pz + Ra × Az
2. Determine zone air-distribution effectiveness (Ez)
Look up Ez in Table 6.2.2.2
3. Calculate zone outdoor airflow (Voz)
Voz = Vbz/Ez
Ventilation Fundamentals and ASHRAE Standard 62.130
Ceiling Ceiling or floor Cool 1.0
Ceiling Floor Warm 1.0
Ceiling Ceiling Warm (< Tspace + 15°F) 1.0
Ceiling Ceiling Hot ( Tspace + 15°F) 0.8
Floor Ceiling Cool 1.0
Floor Ceiling Cool (displacement) 1.2
Floor Ceiling Warm 0.7
Floor Floor Warm 1.0
Supply Return SA temperature Ez
Makeup air drawn in,return/exhaust at opposite side of room 0.8
Makeup air drawn in,return/exhaust near supply 0.5
Table 6.2.2.2
Zone Air-Distribution Effectiveness (Ez)
Ventilation Fundamentals and ASHRAE Standard 62.131
Voz = Vbz / Ez
= 85 / 1.0= 85 cfm
Zone Outdoor Airflow
Example: office space
ceiling supply of cool air
Ez = 1.0
breathing zone
85 cfm
Vbz
Voz
0 cfm
RA
85 cfm
Ventilation Fundamentals and ASHRAE Standard 62.132
Voz = Vbz / Ez
= 85 / 0.8= 106 cfm
Zone Outdoor Airflow
Example: office space
ceiling supply of hot air
Ez = 0.8
breathing zone
85 cfm
Vbz
Voz
21 cfm
RA
106 cfm
Ventilation Fundamentals and ASHRAE Standard 62.133
ventilation rate procedure
Zone Calculations
1. Calculate breathing-zone outdoor airflow (Vbz)
using Table 6.2.2.1 rates
Vbz = Rp × Pz + Ra × Az
2. Determine zone air-distribution effectiveness (Ez)
Look up Ez in Table 6.2.2.2
3. Calculate zone outdoor airflow (Voz)
Voz = Vbz/Ez
Ventilation Fundamentals and ASHRAE Standard 62.134
ASHRAE Standard 62.1, Section 6.2
Ventilation Rate Procedure
• Outdoor air treatment
• Zone calculations
– Determine breathing-zone outdoor airflow for each zone
• System calculations
– Calculate outdoor-air intake flow for entire system
Ventilation Fundamentals and ASHRAE Standard 62.135
ventilation rate procedure
System Calculations
• Single-zone system
– One air-handling unit serving one zone
• 100% outdoor-air system
– One air-handling unit serving many zones
(no recirculation)
• Multiple-zone recirculating system
– One air-handling unit serving many zones
(with recirculation)
Ventilation Fundamentals and ASHRAE Standard 62.136
system calculations
Single-Zone Systems
Calculate required outdoor-air
intake flow (Vot) for each system:
Vot = Voz
EA
zone 1Voz = 300
zone 3Voz = 500
zone 2Voz = 400
RA RA RA
Vot = 300 cfm
OA
SA
RA
Vot = 400 cfm
OA
SA
RA
Vot = 500 cfm
OA
SA
RA
Ventilation Fundamentals and ASHRAE Standard 62.137
system calculations
100% Outdoor-Air System
Calculate required outdoor-air
intake flow (Vot) for the system:
Vot = Σ Voz
dedicatedOA unit Vot = 1200 cfm
EA
OA
SA
RAfan-coil
zone 1Voz = 300
zone 3Voz = 500
zone 2Voz = 400
OA OAOA
SA
RA
SA
RA
Ventilation Fundamentals and ASHRAE Standard 62.138
system calculations
Multiple-Zone Recirculating System
Calculate required outdoor-air
intake flow (Vot) for the system:
Vot = ???
EA
OA
PA PAPARA
VAV VAV VAV
RA RA
RA
some excess(unused) OA
leaves building
zone 1Voz = 300Vpz = 1000
zone 2Voz = 400Vpz = 1000
zone 3Voz = 500Vpz = 1000
VAV air-handling unit
Ventilation Fundamentals and ASHRAE Standard 62.139
multiple-zone recirculating system
System Calculations
1. Zone primary outdoor-air fraction (Zpz)
2. Uncorrected outdoor-air intake (Vou)
3. System ventilation efficiency (Ev)
4. System outdoor-air intake (Vot)
Ventilation Fundamentals and ASHRAE Standard 62.140
Primary Outdoor-Air Fraction (Zpz)
Zpz = Voz / Vpz
EA
OA
zone 1Voz = 300Vpz = 2600Vpz-min = 650
Zpz = 0.46
PA PAPARA
VAV VAV VAV
RA RA
RA
zone 2Voz = 400Vpz = 3400Vpz-min = 850
Zpz = 0.47
zone 3Voz = 500Vpz = 4000Vpz-min = 1000
Zpz = 0.50
6.2.5.1 Note: For VAV system design purposes,
Vpz is the lowest zone primary airflow value
expected at the design condition analyzed.
VAV air-handling unit
highest
Ventilation Fundamentals and ASHRAE Standard 62.141
multiple-zone recirculating system
System Calculations
1. Zone primary outdoor-air fraction (Zpz)
2. Uncorrected outdoor-air intake (Vou)
3. System ventilation efficiency (Ev)
4. System outdoor-air intake (Vot)
Ventilation Fundamentals and ASHRAE Standard 62.142
Uncorrected Outdoor-Air Intake (Vou)
Vou = D × ∑(Rp × Pz) + ∑(Ra × Az)
where,
D = occupant diversity = Ps / ∑Pz
Ps = peak system population
∑Pz = sum of design zone populations
Ventilation Fundamentals and ASHRAE Standard 62.143
example
Occupant Diversity (D)
∑Pz = 120
EA
OA
zone 1Pz = 30
PA PAPARA
VAV VAV VAV
RA RA
RA
D = Ps / ΣPz
= 80 / 120 = 0.66
zone 2Pz = 40
zone 3Pz = 50
Ps = 80 people
VAV air-handling unit
Ventilation Fundamentals and ASHRAE Standard 62.144
1 5 × 30 = 150 0.06 × 2500 = 150
2 5 × 40 = 200 0.06 × 3340 = 200
3 5 × 50 = 250 0.06 × 4170 = 250
∑(Rp × Pz) = 600 ∑(Ra × Az) = 600
zone Rp × Pz Ra × Az
Uncorrected Outdoor-Air Intake (Vou)
Vou = D × ∑(Rp × Pz) + ∑(Ra × Az)
= 0.66 × 600 + 600
= 1000 cfm
Ventilation Fundamentals and ASHRAE Standard 62.145
multiple-zone recirculating system
System Calculations
1. Zone primary outdoor-air fraction (Zpz)
2. Uncorrected outdoor-air intake (Vou)
3. System ventilation efficiency (Ev)
4. System outdoor-air intake (Vot)
Ventilation Fundamentals and ASHRAE Standard 62.146
System Ventilation Efficiency (Ev)
Find system ventilation efficiency (Ev) using either:
Table 6.2.5.2 (“default Ev” method)
or
Appendix A (“calculated Ev” method)
Ventilation Fundamentals and ASHRAE Standard 62.147
Primary Outdoor-Air Fraction (Zpz)
Zpz = Voz / Vpz
EA
OA
zone 1Voz = 300Vpz = 2600Vpz-min = 650
Zpz = 0.46
PA PAPARA
VAV VAV VAV
RA RA
RA
zone 2Voz = 400Vpz = 3400Vpz-min = 850
Zpz = 0.47
zone 3Voz = 500Vpz = 4000Vpz-min = 1000
Zpz = 0.50
6.2.5.1 Note: For VAV system design purposes,
Vpz is the lowest zone primary airflow value
expected at the design condition analyzed.
VAV air-handling unit
highest
Ventilation Fundamentals and ASHRAE Standard 62.148
max Zpz Ev
≤ 0.15 1.0
≤ 0.25 0.9
≤ 0.35 0.8
≤ 0.45 0.7
≤ 0.55 0.6
> 0.55 use Appendix A
Table 6.2.5.2, “default Ev” method
System Ventilation Efficiency (Ev)
Determine Ev based on the
zone with the highest Zpz
(interpolation is allowed)
max Zpz = 0.50
Ev = 0.65
Ventilation Fundamentals and ASHRAE Standard 62.149
multiple-zone recirculating system
System Calculations
1. Zone primary outdoor-air fraction (Zpz)
2. Uncorrected outdoor-air intake (Vou)
3. System ventilation efficiency (Ev)
4. System outdoor-air intake (Vot)
Ventilation Fundamentals and ASHRAE Standard 62.150
System Outdoor-Air Intake (Vot)
Calculate required outdoor-air intake flow (Vot) for the system:
Vot = Vou / Ev
= 1000 / 0.65 = 1540 cfm
Vot = 1540 cfm
EA
OA
PA PAPARA
VAV VAV VAV
RA RA
RA
zone 1Voz = 300
zone 2Voz = 400
zone 3Voz = 500
VAV air-handling unit
Ventilation Fundamentals and ASHRAE Standard 62.151
System Ventilation Efficiency (Ev)
Find system ventilation efficiency (Ev) using either:
Table 6.2.5.2 (“default Ev” method)
or
Appendix A (“calculated Ev” method)
Ventilation Fundamentals and ASHRAE Standard 62.152
Appendix A, “calculated Ev” method
System Ventilation Efficiency (Ev)
1. Zone primary outdoor-air fraction (Zpz)
2. Uncorrected outdoor-air intake (Vou)
3. System ventilation efficiency (Ev)a. Average OA fraction (Xs)
Xs = Vou / Vps
b. Zone ventilation efficiency (Evz)Evz = 1 + Xs – Zpz (for single-supply systems)
Evz = (Fa + Xs × Fb – Zpz × Ep × Fc)/Fa (for secondary recirculation systems)
c. System ventilation efficiency (Ev)Ev = smallest Evz
4. System outdoor-air intake (Vot)
Ventilation Fundamentals and ASHRAE Standard 62.153
Multiple-Zone Recirculating Systems
• Single-supply system
– All air supplied to each zone is a mixture of outdoor air
and system-level (centralized) recirculated air
Constant-volume reheat system
Single-duct VAV system
Single-fan, dual-duct VAV system
Multizone system
• Secondary recirculation system
– Some (or all) of the air supplied to each zone is
recirculated from other zones, and not directly mixed
with outdoor air
Dual-fan, dual-duct VAV system
Fan-powered VAV system
Ventilation Fundamentals and ASHRAE Standard 62.157
example: single-path VAV system
Default vs. Calculated Ev Methods
Appendix A generally results in a lower Vot than Table 6.2.5.2
Table 6.2.5.2 1.0 0.50 0.65 1540 cfm
Appendix A 1.0 0.50 0.67 1490 cfm
Ev method Ez Zpz Ev Vot
Ventilation Fundamentals and ASHRAE Standard 62.158
example: single-path VAV system
Heating vs. Cooling Modes
Table 6.2.5.2 1.0 0.50 0.65 1540 cfm
Appendix A 1.0 0.50 0.67 1490 cfm
Appendix A 0.8 0.63 0.77 1300 cfm
Ev method Ez Zpz Ev Vot
Ez = 0.8 in heating results in larger Zpz, but Xs is higher because Vps is lower,so Ev is actually higher
Ventilation Fundamentals and ASHRAE Standard 62.159
Tools Available from ASHRAE
Ventilation Fundamentals and ASHRAE Standard 62.160
example (cooling mode)
Comparison of Ventilation Systems
19% lower Vot than VAV
single zone 1200
100% outdoor air 1200
single-path VAV 1490 0.67(single-supply system)
series FPVAV 1180 0.85(secondary recirculation system)
ventilation system Vot Ev
0.83
0.83
Ventilation Fundamentals and ASHRAE Standard 62.161
ASHRAE Standard 62.1, Section 6
Procedures
• Ventilation Rate Procedure (Section 6.2)
– Prescriptive
– Dictates ventilation rates and calculations based on
“typical” spaces
• IAQ Procedure (Section 6.3)
– Performance-based, mass balance analysis
– Must ventilate to achieve specific concentration limits
for all contaminants of concern
• Natural Ventilation (Section 6.4)
– Generally requires a “mixed-mode” system design
Ventilation Fundamentals and ASHRAE Standard 62.162
ASHRAE Standard 62.1, Section 6.3
IAQ Procedure
1. Identify all contaminants of concern, and mixtures of
concern, for the zone.
2. Identify indoor and outdoor sources for each pollutant.
3. Determine emission rate for each pollutant from each
identified source.
4. Specify concentration limit, and exposure time, for each
contaminant, citing an appropriate cognizant authority.
5. Specify limit for perceived IAQ, based on a minimum
percentage of occupants or visitors expressing satisfaction.
6. Using mass balance calculations, determine minimum
breathing zone OA rate (Vbz) to meet concentration limits
established (in step 4) for each contaminant and mixture.
• Can make use of various air cleaning technologies
Ventilation Fundamentals and ASHRAE Standard 62.163
ASHRAE Standard 62.1, Appendix D
IAQ Procedure: Mass Balance Calculations
Ventilation Fundamentals and ASHRAE Standard 62.164
ASHRAE Standard 62.1, Section 6.3
IAQ Procedure
7. Conduct a post-occupancy subjective evaluation to ensure
breathing zone OA rate (Vbz) meets the perceived IAQ
criteria (in step 5).
• Can use results from a “substantially similar” zone
8. Set the breathing zone OA rate (Vbz) to the largest of that
determined by mass balance or by subjective evaluation.
9. Calculate system-level outdoor air intake flow (Vot) based
on the breathing zone OA rate found for each zone:
• Single-zone system: Appendix D
• 100% outdoor-air system: Section 6.2.4
• Multiple-zone recirculating system: Section 6.2.5
Ventilation Fundamentals and ASHRAE Standard 62.165
ASHRAE Standard 62.1, Section 6.3
IAQ Procedure
Ventilation Fundamentals and ASHRAE Standard 62.166
ASHRAE Standard 62.1, Section 6
Procedures
• Ventilation Rate Procedure (Section 6.2)
– Prescriptive
– Dictates ventilation rates and calculations based on
“typical” spaces
• IAQ Procedure (Section 6.3)
– Performance-based, mass balance analysis
– Must ventilate to achieve specific concentration limits
for all contaminants of concern
• Natural Ventilation (Section 6.4)
– Generally requires a “mixed-mode” system design
Ventilation Fundamentals and ASHRAE Standard 62.167
ASHRAE Standard 62.1, Section 6.4
Natural Ventilation Procedure
• Naturally ventilated spaces must be permanently open to,
and within minimum distance of, operable wall openings
• Depends on configuration of openings (single-sided or
adjacent walls, cross-ventilation) and ceiling height
• Free, unobstructed area of the openings must be ≥ 4% of
the net occupiable floor area being ventilated
• Operable opening controls
must be readily accessible
to building occupants
Ventilation Fundamentals and ASHRAE Standard 62.168
ASHRAE Standard 62.1, Section 6.4
Natural Ventilation Procedure
A “mixed-mode” ventilation system is typically required:
…unless either:
• Openings are permanently open or controls prevent closing
during periods of expected occupancy, or
• Zone is not served by heating or cooling equipment
6.4 Natural Ventilation Procedure. Natural ventilation systems shall be
designed in accordance with this section and shall include mechanical
ventilation systems designed in accordance with Section 6.2 (Ventilation
Rate Procedure) and/or Section 6.3 (IAQ Procedure.
Ventilation Fundamentals and ASHRAE Standard 62.169
ASHRAE Standard 62.1
Further Reading
• American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc.
2011. 62.1-2016 User’s Manual. Atlanta, GA: ASHRAE.
• Ventilation Rate Procedure
– Stanke, D. 2004. “Single-Zone and Dedicated-OA Systems,” ASHRAE Journal
(October): pp. 12-20.
– Stanke, D. 2005. “Single-Path, Multiple-Zone Systems,” ASHRAE Journal
(January): pp. 28-35.
– Stanke, D. 2005. “Dual-Path, Multiple-Zone Systems,” ASHRAE Journal
(May): pp. 20-30.
– Stanke, D. 2008. “Potential ASHRAE Standard Conflicts: Indoor Air Quality
and Energy Standards” Engineers Newsletter (ADM-APN030-EN).
La Crosse, WI: Trane.
– Trane. 2013. “ASHRAE Standard 62.1-2010” Engineers Newsletter Live
program (DVD: APP-CMC047-EN). La Crosse, WI: AVS Group.
• IAQ Procedure
– Stanke, D. 2012. “Minimum Outdoor Airflow Using the IAQ Procedure”
ASHRAE Journal (June): pp. 26-34.
Ventilation Fundamentals and ASHRAE Standard 62.170
ventilation fundamentals and ASHRAE Standard 62.1
Agenda
• Ventilation as part of indoor air quality (IAQ)
• Types of ventilation systems
• ASHRAE Standard 62.1
– General overview
– Ventilation Rate Procedure
• Relationship between ASHRAE 62.1 and LEED
Ventilation Fundamentals and ASHRAE Standard 62.171
Leadership in Energy and Environmental Design
LEED
Voluntary, point-based rating system based on
sustainability goals in the following categories:
Sustainable Sites
Water Efficiency
Energy & Atmosphere
Materials & Resources
Indoor Environmental Quality
Innovation in Design
Ventilation Fundamentals and ASHRAE Standard 62.172
EQ prerequisite (LEED v4)
Minimum IAQ Performance
Requirements
Mechanically-ventilated spaces
• Meet the minimum requirements of ASHRAE Standard 62.1-2010,
Sections 4 through 7, and
• Determine the minimum outdoor air intake flow (Vot) using the
Ventilation Rate Procedure (Section 6.2) from ASHRAE 62.1-2010
Naturally-ventilated spaces
• Determine the minimum outdoor air opening and space
configuration requirements using the Natural Ventilation Procedure
(Section 6.4) from ASHRAE 62.1-2010
The IAQ Procedure (Section 6.2) defined in ASHRAE 62.1-2010 may
not be used to comply with this prerequisite.
Ventilation Fundamentals and ASHRAE Standard 62.173
LEED v4 prerequisite changes
Minimum IAQ Performance
ASHRAE 62.1-2007, Sections 4–7
(ASHRAE 170-2008 for healthcare)
• Mechanically ventilated spaces:
• Must use Ventilation Rate
Procedure or local code
• Naturally ventilated spaces:
• Must comply with Section 5.1
• IAQ Procedure not allowed
• Except via pilot prerequisite
• ASHRAE 62.1-2010, Sections 4–7
(ASHRAE 170-2008 for healthcare)
• Mechanically ventilated spaces:
• Use Ventilation Rate Procedure
• Monitor OA intake flow
• Naturally ventilated spaces:
• Use Natural Vent. Procedure
• Monitor NV openings, exhaust
airflow, or CO2 concentrations
• IAQ Procedure not allowed
• Except via pilot prerequisite
LEED v3 (2009) LEED v4
Ventilation Fundamentals and ASHRAE Standard 62.174
EQ prerequisite (LEED v4)
Minimum IAQ Performance
Monitoring
For mechanically ventilated spaces (and for mixed-mode systems when the
mechanical ventilation is activated), monitor outdoor air intake flow as follows:
• For variable air volume systems, provide a direct outdoor airflow
measurement device capable of measuring the minimum outdoor air intake
flow. This device must measure the minimum outdoor air intake flow with an
accuracy of +/–10% of the design minimum outdoor airflow rate, as defined
by the ventilation requirements above. An alarm must indicate when the
outdoor airflow value varies by 15% or more from the outdoor airflow
setpoint.
• For constant-volume systems, balance outdoor airflow to the design
minimum outdoor airflow rate defined by ASHRAE 62.1-2010, or higher.
Install a current transducer on the supply fan, an airflow switch, or similar
monitoring device.
Ventilation Fundamentals and ASHRAE Standard 62.175
EQ prerequisite (LEED v4)
Minimum IAQ Performance
Monitoring
For naturally ventilated spaces (and for mixed-mode systems when the
mechanical ventilation is inactivated), comply with at least one of the following:
• Provide a direct exhaust airflow measurement device capable of
measuring exhaust airflow. This device must measure airflow with an
accuracy of +/–10% of design minimum exhaust airflow. An alarm must
indicate when airflow varies by 15% or more from exhaust airflow setpoint.
• Provide automatic indication devices on all natural ventilation openings
intended to meet the minimum opening requirements. An alarm must
indicate when any one of the openings is closed during occupied hours.
• Monitor carbon dioxide (CO2) concentrations within each thermal zone.
CO2 monitors must be between 3 and 6 feet above the floor and within the
thermal zone. CO2 monitors must have an audible or visual indicator or alert
the building automation system if the sensed CO2 concentration exceeds the
setpoint by more than 10%. Calculate appropriate CO2 setpoints using the
methods in ASHRAE 62.1-2010, Appendix C.
Ventilation Fundamentals and ASHRAE Standard 62.176
alternate compliance path for EQ prerequisite
EQ Pilot Prerequisite: IAQ Procedure
Requirements
• Meet the minimum requirements of ASHRAE Standard 62.1-2010,
Sections 4 through 7, and
• Determine the minimum outdoor air intake flow (Vot) for mechanical
ventilation systems using the IAQ Procedure (Section 6.3) from
ASHRAE 62.1-2010 (combining the IAQP and VRP is not an
acceptable means of compliance with this pilot prerequisite), and
• Prohibit smoking in the building
www.usgbc.org/pilotcredits
Ventilation Fundamentals and ASHRAE Standard 62.177
Indoor Environmental Quality (EQ) section (LEED v4)
Credits
Enhanced IAQ Strategies 1-2 points
Low-Emitting Materials 1-3 points
Construction IAQ Management Plan 1 point
IAQ Assessment 1-2 points
Thermal Comfort 1 point
Interior Lighting 1-2 points
Daylight 1-3 points
Quality Views 1-2 points
Acoustic Performance 1-2 points
EQ credit
EQ credit
EQ credit
EQ credit
EQ credit
EQ credit
EQ credit
EQ credit
EQ credit
Ventilation Fundamentals and ASHRAE Standard 62.178
LEED v4 credit changes
Enhanced IAQ Strategies
Outdoor Air Delivery Monitoring (1 pt)
Increased Ventilation (1 pt)
Indoor Source Control (1 pt)
Enhanced IAQ Strategies (1-2 pts)
• Option 1 (1 pt), implement all:
• Entryway systems, and
• Local exhausts, and
• MERV 13 filtration of outdoor air
• Option 2 (1 pt), choose:
• Prevent pollutants from outside, or
• Increased ventilation, or
• CO2 monitoring, or
• Monitor other contaminants
LEED v3 LEED v4
Ventilation Fundamentals and ASHRAE Standard 62.179
EQ credit (LEED v4)
Enhanced IAQ Strategies (Option 2)
1.3 × Vbz = 1.3 × (Rp × Pz + Ra × Az)
Increased Ventilation
Increase breathing zone outdoor air ventilation rates (Vbz) to all occupied
spaces by at least 30% above the minimum rates as determined in EQ
Prerequisite, Minimum IAQ Performance.
Ventilation Fundamentals and ASHRAE Standard 62.180
EQ credit (LEED v4)
Enhanced IAQ Strategies (Option 2)
Carbon Dioxide Monitoring
Monitor CO2 concentrations within all densely occupied spaces. CO2
monitors must be between 3 and 6 feet above the floor. CO2 monitors must
have an audible or visual indicator or alert the building automation system if
the sensed CO2 concentration exceeds the setpoint by more than 10%.
Calculate appropriate CO2 setpoints using methods in ASHRAE 62.1-2010,
Appendix C.
“an area with a design occupant density ≥ 25 people per 1000 ft2”
(LEED Reference Guide for Building Design and Construction, 2013 Edition, page 600)
Ventilation Fundamentals and ASHRAE Standard 62.181
LEED
Further Reading
• U.S. Green Building Council. 2013. LEED v4 Reference Guide for
Building Design and Construction. Washington, DC: USGBC.
• American Society of Heating, Refrigeration and Air-Conditioning
Engineers, Inc. 2010. ASHRAE Standard 62.1-2010, Ventilation for
Acceptable Indoor Air Quality. Atlanta, GA: ASHRAE.
• American Society of Heating, Refrigeration and Air-Conditioning
Engineers, Inc. 2011. 62.1-2010 User’s Manual. Atlanta, GA: ASHRAE.
• Trane. 2014. “LEED v4” Engineers Newsletter Live program
(DVD: APP-CMC050-EN). La Crosse, WI: AVS Group.
Part 1: Ventilation Fundamentals and ASHRAE Standard 62.1
Self-Assessment Quiz
1. Why is it important to be familiar with ASHRAE Standard 62.1?
a. It is the basis for many local building codes.
b. Compliance with it is a prerequisite for LEED certification.
c. All of the above
2. True or False: The Ventilation Rate Procedure of ASHRAE Standard
62.1 is prescriptive in nature, dictating ventilation rates and
calculation procedures given the space and system type.
3. True or False: For many occupancy categories, ASHRAE Standard
62.1 prescribes two ventilation rates; one for people-related
contaminant sources plus one for building-related sources.
4. True or False: The project team can earn a credit point for LEED (v4)
by increasing the ventilation rates above the minimum rates required
by ASHRAE Standard 62.1.
Design and Control of Ventilation Systems83
Design and Control of Ventilation Systems
Agenda
8:30 – 10:15 Ventilation Fundamentals, ASHRAE 62.1
Break
10:30 – noon Dynamic Ventilation Reset Strategies
Lunch
12:45 – 2:15 Exhaust-Air Energy Recovery
Break
2:30 – 4:00 Dedicated Outdoor-Air Systems
Design and Control of Ventilation Systems84
Dynamic Ventilation Reset Strategies
Dynamic Ventilation Reset Strategies85
ASHRAE Standard 62.1-2013
Section 6.2.7
Examples mentioned include:
• Variations in zone population
(“demand-controlled ventilation”)
• Variations in ventilation efficiency due to changes in airflow
(“ventilation optimization” or “ventilation reset”)
• Variations in intake airflow due to economizer operation
(“VAV box minimum reset”)
6.2.7 Dynamic Reset. The system may be designed to reset the outdoor
air intake flow (Vot) and/or space or ventilation zone airflow (Voz) as
operating conditions change.
Dynamic Ventilation Reset Strategies86
dynamic ventilation reset strategies
Agenda
• Ventilation reset in VAV systems
– VAV box minimum reset
• Demand-controlled ventilation
– Common technologies
– Implementing DCV is various types of systems
• Requirements of ASHRAE Standard 90.1
• Summary of suggestions for cost-effective application
of demand-controlled ventilation
Dynamic Ventilation Reset Strategies87
ASHRAE Standard 62.1-2013, Section 6.2.7.2
Ventilation Reset
6.2.7 Dynamic Reset. The system may be designed to reset the outdoor air
intake flow (Vot) and/or space or ventilation zone airflow (Voz) as operating
conditions change.
…
6.2.7.2 Ventilation Efficiency. Variations in the efficiency with which outdoor
air is distributed to the occupants under different ventilation system airflows
and temperatures shall be permitted as an optional basis of dynamic reset.
Dynamic Ventilation Reset Strategies88
Ventilation Rate Procedure
Multiple-Zone Recirculating System
1. Zone primary outdoor-air fraction (Zpz)
2. Uncorrected outdoor-air intake (Vou)
3. System ventilation efficiency (Ev)
4. System outdoor-air intake (Vot)
Dynamic Ventilation Reset Strategies89
Ventilation Reset in a VAV System
• Required outdoor airflow (Voz)
• Current primary airflow (Vpz)• Current OA fraction (Zpz)
DDC VAV controllers
SA RA
AHU or rooftop unit withOA flow measurement
• Reset intake airflow (Vot)
Building Automation System
• Find highest OA fraction (Zpz)
• Calculate current systemventilation efficiency (Ev)
• Calculate current system
intake airflow (Vot)
Dynamic Ventilation Reset Strategies90
dynamic reset based on
Variations in System Ventilation Efficiency
• Each VAV controller measures current primary airflow (Vpz) and
can calculate that zone’s OA fraction (Zpz = Voz/Vpz)
• BAS polls all VAV controllers to collect current from each:
– Zone outdoor airflow (Voz) and primary airflow (Vpz)
– Zone OA fraction (Zpz)
• BAS solves multiple-zone equations to calculate:
– Current system ventilation efficiency (Ev)
– Current system-level OA intake flow (Vot) required
• BAS communicates new OA intake flow setpoint (Vot)
to AHU or rooftop controller
Dynamic Ventilation Reset Strategies91
Zone 1 Zone 2 Zone 3
Zone OA flow Voz 500 600 700 = 1800
Primary airflow Vpz 1500 2000 1500 = 5000
OA fraction Zpz = Voz/Vpz 0.33 0.30 0.47
Avg OA fraction Xs = Vou/Vps = 1800/5000 0.36
Sys vent effic Ev = 1 + Xs – max Zpz = 1 + 0.36 – 0.47 0.89
Sys OA intake Vot = Vou/Ev = 1800/0.89 2020
System
ventilation reset
Example: Operating Condition #1
Dynamic Ventilation Reset Strategies92
Zone 1 Zone 2 Zone 3
Zone OA flow Voz 500 600 700 = 1800
Primary airflow Vpz 700 1500 1800 = 4000
OA fraction Zpz = Voz/Vpz 0.71 0.40 0.39
Avg OA fraction Xs = Vou/Vps = 1800/4000 0.45
Sys vent effic Ev = 1 + Xs – max Zpz = 1 + 0.45 – 0.71 0.74
Sys OA intake Vot = Vou/Ev = 1800/0.74 2430
System
Compared to
0.89 and 2020 cfm
at condition #1
ventilation reset
Example: Operating Condition #2
Dynamic Ventilation Reset Strategies93
dynamic ventilation reset strategies
Agenda
• Ventilation reset in VAV systems
– VAV box minimum reset
• Demand-controlled ventilation
– Common technologies
– Implementing DCV is various types of systems
• Requirements of ASHRAE Standard 90.1
• Summary of suggestions for cost-effective application
of demand-controlled ventilation
Dynamic Ventilation Reset Strategies94
ASHRAE Standard 62.1-2013, Section 6.2.7.3
VAV Box Minimum Reset
6.2.7 Dynamic Reset. The system may be designed to reset the outdoor air
intake flow (Vot) and/or space or ventilation zone airflow (Voz) as operating
conditions change.
…
6.2.7.3 Outdoor Air Fraction. A higher fraction of outdoor air in the air supply
due to intake of additional outdoor air for free cooling [economizing] or
exhaust air makeup shall be permitted as an optional basis of dynamic reset.
Dynamic Ventilation Reset Strategies95
VAV box minimums set to avoid overly-high zone OA fractions (Zpz)
ONOFF
Zone 1
ON
Zone 2 Zone 3
Zone OA flow Voz 500 600 700 = 1800
Primary airflow Vpz 1000 850 1000 = 2850
VAV box minimum setting 700 850 1000
OA fraction Zpz = Voz/Vpz 0.50 0.70 0.70
Avg OA fraction Xs = Vou/Vps = 1800/2850 0.63
Sys vent effic Ev = 1 + Xs – max Zpz = 1 + 0.63 – 0.70 0.93
Sys OA intake Vot = Vou/Ev = 1800/0.93 1940
Actual OA intake flow (economizing) 2850
VAV box minimum reset
Example: Airside Economizing (Full)
55°F 59°F 60°F
55°F OA
RA
O
F
F 55°F
100% OA
Dynamic Ventilation Reset Strategies96
OFF OFF
Zone 1 Zone 2 Zone 3
VAV box minimum reset
Example: Airside Economizing (Full)
55°F 55°F 55°F
55°F OA
RA
O
F
F 55°F
Zone OA flow Voz 500 600 700 = 1800
Primary airflow Vpz 1000 680 750 = 2430
VAV box minimum setting 500 600 700
OA fraction Zpz = Voz/Vpz 0.50 0.88 0.93
Avg OA fraction Xs = Vou/Vps = 1800/2430 0.74
Sys vent effic Ev = 1 + Xs – max Zpz = 1 + 0.74 – 0.93 0.81
Sys OA intake Vot = Vou/Ev = 1800/0.81 2220
Actual OA intake flow (economizing) 2430
allow Zpz as high as 1.0
100% OA
Resetting VAV box minimums downward during airside economizing
reduces both fan and reheat energy use
OFF
Dynamic Ventilation Reset Strategies98
dynamic reset based on
Variations in Intake Airflow (Economizing)
• AHU or rooftop controller modulates OA damper for
airside economizing
• When OA damper opens for economizing, the BAS
directs all VAV controllers to lower their minimum
airflow setpoints and allow zone OA fractions (Zpz) to
be as high as the current system OA percentage
(e.g., 100% during full economizing)
Dynamic Ventilation Reset Strategies99
dynamic ventilation reset strategies
Agenda
• Ventilation reset in VAV systems
– VAV box minimum reset
• Demand-controlled ventilation
– Common technologies
– Implementing DCV is various types of systems
• Requirements of ASHRAE Standard 90.1
• Summary of suggestions for cost-effective application
of demand-controlled ventilation
Dynamic Ventilation Reset Strategies100
Demand-Controlled Ventilation
A control strategy that responds to the actual
“demand” (need) for ventilation in a zone by varying
the rate at which outdoor air is delivered to that zone.
cfm required = cfm/person number of peoplelocal code,
ASHRAE 62.1
Dynamic Ventilation Reset Strategies101
Purpose of DCV
• DCV is an energy-saving strategy
… it is not an IAQ-improvement strategy.
– The goal of DCV is to reduce ventilation airflow during
periods of reduced occupancy, thereby reducing the
energy needed to condition that ventilation air.
– If the goal was to improve IAQ, you would keep
ventilation airflow high at all times, rather than reducing
it during periods of reduced occupancy.
Dynamic Ventilation Reset Strategies102
ASHRAE Standard 62.1-2013, Section 6.2.7.1
Demand-Controlled Ventilation
6.2.7.1 Demand Control Ventilation. DCV shall be permitted as an optional
means of dynamic reset. Exception: CO2 -based DCV shall not be applied in
zones with indoor sources of CO2 other than occupants or with CO2 removal
mechanisms, such as gaseous air cleaners.
6.2.7.1.1 The breathing zone outdoor airflow (Vbz) shall be reset in response to
current occupancy and shall be no less than the building component
(Ra × Az) of the DCV zone. Note: Examples of reset methods or devices
include population counters, carbon dioxide (CO2) sensors, timers, occupancy
schedules, or occupancy sensors.
6.2.7.1.2 The ventilation system shall be controlled such that at steady-state it
provides each zone with no less than the breathing zone outdoor airflow (Vbz)
for the current zone population.
6.2.7.1.3 The current total outdoor air intake flow with respect to the coincident
total exhaust airflow for the building shall comply with Section 5.9.2.
Dynamic Ventilation Reset Strategies103
Common DCV Technologies
• Time-of-day schedules
• People counters
• Occupancy (motion) sensors
• Carbon dioxide (CO2) sensors
Dynamic Ventilation Reset Strategies104
Time-of-Day (TOD) Schedules
• Scheduling function of the BAS is used to define the
amount of outdoor air required in a zone for each
hour … based on estimated population
Dynamic Ventilation Reset Strategies105
0
50
100
150
zo
ne
po
pu
lati
on
, P
z
midnight 6 a.m. noon 6 p.m. midnight
example: high school cafeteria
Occupancy/Ventilation TOD Schedule
200estimated Pz
each hour
Dynamic Ventilation Reset Strategies106
0
10
20
30
40
50
60
70
zo
ne
po
pu
lati
on
, P
z
example: university lecture classroom
Occupancy/Ventilation TOD Schedule
80
estimated Pz
each hour
midnight 6 a.m. noon 6 p.m. midnight
Dynamic Ventilation Reset Strategies107
Common DCV Technologies
• Time-of-day schedules
• People counters
• Occupancy (motion) sensors
• Carbon dioxide (CO2) sensors
Dynamic Ventilation Reset Strategies108
People Counters
Dynamic Ventilation Reset Strategies109
Common DCV Technologies
• Time-of-day schedules
• People counters
• Occupancy (motion) sensors
• Carbon dioxide (CO2) sensors
Dynamic Ventilation Reset Strategies110
Occupancy Sensor / Motion Detector
• Sensor is used to determine if people are present
– Simple, binary input
• When a zone is occupied:
– Zone ventilation setpoint is set to design outdoor airflow
• When a zone is unoccupied:
– Zone ventilation setpoint is set to zero or
an “occupied standby” ventilation setpoint
Dynamic Ventilation Reset Strategies111
“occupied standby” mode
Example Conference Room
• Floor area (Az) = 1000 ft2
• Design population (Pz) = 50 people
• Calculate required outdoor airflow at design population
Vbz-design = Rp Pz + Ra Az
= 5 cfm/p 50 people + 0.06 cfm/ft2 1000 ft2
= 310 cfm
• Calculate required outdoor airflow at zero population
Vbz-standby = 5 cfm/p 0 people + 0.06 cfm/ft2 1000 ft2
= 60 cfm
6.2.7.1.1 The breathing zone outdoor airflow (Vbz) shall be reset in response to current
occupancy and shall be no less than the building component (Ra × Az) of the DCV zone.
8.3 Systems shall be operated such that spaces are ventilated in accordance with
Section 6 when they are expected to be occupied.
ASHRAE Standard 62.1-2013
Dynamic Ventilation Reset Strategies112
“occupied standby” mode
Example Conference Room
Lights on off
Zone cooling setpoint 75°F 77°F
Ventilation setpoint 310 cfm 60 cfm
(Vbz-design) (Vbz-standby)
occupied
mode
occupied standby
mode
Dynamic Ventilation Reset Strategies113
“occupied-standby” mode
Change Made to ASHRAE 62.1-2016
6.2.7.1.2 For DCV zones in the occupied mode, breathing zone outdoor airflow
(Vbz) shall not be less than the building component (Ra × Az) for the zone.
Exception: Breathing zone outdoor airflow shall be permitted to be reduced
to zero for zones in occupied-standby mode for the occupancy categories
indicated in Table 6.2.2.1 provided that airflow is restored to Vbz whenever
occupancy is detected.
Section 3. Definitions
occupied mode: when a zone is scheduled to be occupied
occupied-standby mode: when a zone is scheduled to be occupied and
an occupancy sensor indicates zero population within the zone
Dynamic Ventilation Reset Strategies114
Common DCV Technologies
• Time-of-day schedules
• People counters
• Occupancy (motion) sensors
• Carbon dioxide (CO2) sensors
Dynamic Ventilation Reset Strategies115
Production of CO2 is
related to the person’s
level of activity.
Therefore, CO2 can be
used as a "tracer gas"
for occupancy.
physical activity level, MET
0 1 2 3 4 5
0.5
0
1.0
1.5
2.0
CO
2p
ro
du
cti
on
, L/
min off
ice w
ork
sle
epin
g
walk
ing
lt m
achin
e w
ork
very light moderatelight
Source: ASHRAE Standard 62.1-2013, Figure C-2
Dynamic Ventilation Reset Strategies116
mass balance
CO2-Based DCV
0
200
400
600
800
1000
1200
1400
1600
CO
2con
cen
trati
on
, p
pm
steady state conditions
time
CO2 outdoors
15 cfm/p
20 cfm/p
10 cfm/p
CO2 indoors
Dynamic Ventilation Reset Strategies117
mass balance
CO2-Based DCV
0
200
400
600
800
1000
1200
1400
1600
CO
2con
cen
trati
on
, p
pm
time
CO2 indoors
COA = 350 ppm
Cspace = 1050 ppm
Cspace – COA = N / VOA
N = CO2 generation rate, cfm/person VOA = ventilation rate, cfm/person
Dynamic Ventilation Reset Strategies118
Setpoints Vary by Application
• CO2 generation rate (N) varies with activity level
– See Appendix C of ASHRAE 62.1
• Ventilation rate (VOA) differs by space type and
cfm/person varies as zone population changes
• Outdoor CO2 concentration (COA) varies by location
– Most designers use a one-time reading from the site or
a conservative value from historical local data
"Unless combustion fumes are present, the outdoor CO2
concentration in most locations seldom varies more than
100 ppm from the nominal value."ASHRAE Transactions, 1998
Dynamic Ventilation Reset Strategies119
minimum ventilation rates
ASHRAE Standard 62.1
Office 20 5.0 0.06
Classroom 15 10.0 0.12
Lecture classroom 15 7.5 0.06
Retail sales 0.3 7.5 0.12
Auditorium 15 5.0 0.06
1989-2001 2004-current
Rp Ra Rp Ra
Occupancy category cfm/p cfm/ft² cfm/p cfm/ft²
Beginning with the 2004 version, ASHRAE 62.1
prescribes both per-person and per-area rates
Dynamic Ventilation Reset Strategies120
Example: University Lecture Classroom
• Floor area (Az) = 1000 ft2
• Design population (Pz) = 65 people
• Assumed CO2 generation rate (N) = 0.0105 cfm/person
• Outdoor CO2 concentration (COA) = 350 ppm
• Breathing-zone outdoor airflow at design population
Vbz-design = Rp Pz + Ra Az
= 7.5 cfm/p 65 people + 0.06 cfm/ft2 1000 ft2
= 490 cfm + 60 cfm
= 550 cfm
• Breathing-zone outdoor airflow at a population of 20 people
Vbz-min = 7.5 cfm/p 20 people + 0.06 cfm/ft2 1000 ft2
= 150 cfm + 60 cfm
= 210 cfm
Dynamic Ventilation Reset Strategies121
Example: University Lecture Classroom
10 20
200
400
600
800
1000
zone population, Pz
30 40 50 600
0
1200
Vbz-design = 550 cfm
Vbz-min = 210 cfm
6.2.7.1.1 The breathing zone outdoor airflow (Vbz) shall be reset in response to
current occupancy and shall be no less than the building component (Ra × Az)
of the DCV zone.
6.2.7.1.2 The ventilation system shall be controlled such that at steady-state it
provides each zone with no less than the breathing zone outdoor airflow (Vbz)
for the current zone population.ASHRAE Standard 62.1-2013
bre
ath
ing
-zo
ne o
utd
oo
r air
flo
w (
Vb
z),
cfm
1400
Dynamic Ventilation Reset Strategies122
Example: University Lecture Classroom
• At design population, VOA-design is 8.5 cfm/person
Vo-design = Vbz-design / Pz-design = 550 cfm / 65 people = 8.5 cfm/person
…and Cs-design is 1600 ppm
Cs-design = COA + N / (Vbz-design/Pz-design)
= 350 ppm + 0.0105 / (550 cfm/65 people) = 1600 ppm
• At a population of 20 people, VOA-min is 10.5 cfm/person
Vo-min = Vbz-min / Pz-min = 210 cfm / 20 people = 10.5 cfm/person
…and Cs-min is 1350 ppm
Cs-min = COA + N / (Vbz-min/Pz-min)
= 350 ppm + 0.0105 / (210 cfm/20 people) = 1350 ppm
Dynamic Ventilation Reset Strategies123
Example: University Lecture Classroom
10 20
200
400
600
800
1000
zone population, Pz
30 40 50 60
600
800
1000
1200
1400
1600
40000
1200
desire
d s
pace C
O2
co
ncen
tratio
n (C
s ), pp
m
bre
ath
ing
-zo
ne o
utd
oo
r air
flo
w (
Vb
z),
cfm
Cs-min = 1350 ppm
Cs-design = 1600 ppm
18001400
Dynamic Ventilation Reset Strategies124
CO2-Based DCV and ASHRAE 62.1
• As zone population (Pz) decreases, cfm/person (VOA)
increases and the desired indoor CO2 concentration
(Cs) decreases…
…so CO2-based DCV is not as easy as setting a
single space CO2 setpoint
Dynamic Ventilation Reset Strategies125
dynamic ventilation reset strategies
Agenda
• Ventilation reset in VAV systems
– VAV box minimum reset
• Demand-controlled ventilation
– Common technologies
– Implementing DCV is various types of systems
• Requirements of ASHRAE Standard 90.1
• Summary of suggestions for cost-effective application
of demand-controlled ventilation
Dynamic Ventilation Reset Strategies126
Implementing DCV in Various Systems
• Single-zone system
• Dedicated (100%) outdoor-air system
• Multiple-zone recirculating system
Dynamic Ventilation Reset Strategies127
DCV in Single-Zone Systems
SAOA
RAEA
space
CO2
CO2
alternate
unit controller
Dynamic Ventilation Reset Strategies128
implementing DCV in single-zone systems
ASHRAE 62.1 User’s Manual (Appendix A)
Example: University lecture classroom
• Floor area (Az) = 1000 ft2
• Peak population (Pz) = 65 people
• CO2 generation rate (N) = 0.0105 cfm/person
(light desk work)
• Outdoor CO2 concentration (COA) = 350 ppm
For this occupancy classification, Table 6-1 of
ASHRAE Standard 62.1 requires:
• Rp = 7.5 cfm/person
• Ra = 0.06 cfm/ft2
Dynamic Ventilation Reset Strategies129
implementing DCV in single-zone systems
ASHRAE 62.1 User’s Manual (Appendix A)
1) Calculate breathing-zone outdoor airflow (Vbz)
for both design population and with zero people
Vbz = Rp × Pz + Ra × Az
Vbz-design = 7.5 × 65 + 0.06 × 1000 = 550 cfm
Vbz-DCVmin = 7.5 × 0 + 0.06 × 1000 = 60 cfm
Dynamic Ventilation Reset Strategies130
implementing DCV in single-zone systems
ASHRAE 62.1 User’s Manual (Appendix A)
2) Calculate steady-state indoor CO2 concentration (Cs)
for both design population and with zero people
Cs = COA + N / ( Vbz / Pz )
Cs-design = 350 + 0.0105 / (550 cfm / 65 people) = 1600 ppm
Cs-DCVmin = 350 + 0.0105 / (60 cfm / 0 people) = 350 ppm
Dynamic Ventilation Reset Strategies131
implementing DCV in single-zone systems
ASHRAE 62.1 User’s Manual (Appendix A)
Vbz-design = 550 cfm
indoor CO2 concentration, ppm
Vbz-DCVmin = 60 cfm
ou
tdo
or
airflo
w, cfm
set position of OA damper to bring in
Vot-DCVmin when indoor CO2 equals Cs-DCVmin
set position of OA damper to bring in
Vot-design when indoor CO2 equals Cs-design
For single-zone system, Vot = Voz = Vbz/Ez (assumes Ez = 1.0)
Cs-design = 1600 ppmCs-DCVmin = 350 ppm
Dynamic Ventilation Reset Strategies132
control coordination issues
DCV in Single-Zone Systems
zone
SAOA
EA RA
CO2
1. Economizer operation should override DCV2. Don’t forget about building pressure control
P
Dynamic Ventilation Reset Strategies133
ASHRAE Standard 62.1-2013, Section 6.2.7.3
DCV and Building Pressure Control
6.2.7.1 Demand Control Ventilation
…
6.2.7.1.3 The current total outdoor air intake flow with respect to the coincident
total exhaust airflow for the building shall comply with Section 5.9.2.
5.9.2 Exfiltration. For a building, the ventilation system(s) shall be designed
to ensure that the minimum outdoor air intake equals or exceeds the
maximum exhaust airflow.
Exceptions:
1. Where excess exhaust is required by process considerations and approved
by the authority having jurisdiction, such as in certain industrial facilities
2. When outdoor air dry-bulb temperature is below the indoor space dew-point
design temperature
Dynamic Ventilation Reset Strategies134
Implementing DCV in Various Systems
• Single-zone system
• Dedicated (100%) outdoor-air system
• Multiple-zone recirculating system
Dynamic Ventilation Reset Strategies135
implementing DCV in a dedicated OA system
OA Delivered Directly to Each Zone
SAlocal
HVAC unit
CACA
EA
VAV
dedicatedOA unitOA
VFD
CO2
RA CA
SA
CO2
RA
Dynamic Ventilation Reset Strategies136
implementing DCV in a dedicated OA system
OA Delivered to Single-Zone Units
RA
CA CA
SARA
CA
EA
dedicatedOA unitOA
VFD
RA
CO2 CO2
SA
VAV
SA
local
HVAC unit
Dynamic Ventilation Reset Strategies137
control coordination issues
DCV in a Dedicated OA Systems
• Requires pressure-independent OA dampers for
any non-DCV zones
• Requires variable airflow at the dedicated OA unit
• Don’t forget about building pressure control
Dynamic Ventilation Reset Strategies138
Implementing DCV in Various Systems
• Single-zone system
• Dedicated (100%) outdoor-air system
• Multiple-zone recirculating system
Dynamic Ventilation Reset Strategies139
implementing DCV in multiple-zone recirculating systems
CO2 Sensor in Every Zone?
SA
OA
RAEA
space
space
CO2
CO2
Dynamic Ventilation Reset Strategies140
implementing DCV in multiple-zone recirculating systems
CO2 Sensor in Every Zone?
• Requires a CO2 sensor in every zone
– CO2 level doesn’t change much in many of the zones
– Non-critical zones will always be overventilated
– Increases installed cost, maintenance, and risk of energy waste
• Requires BAS to poll all sensors and then determine
required OA damper position
• Requires method to ensure minimum outdoor airflow
6.2.7.1.1 The breathing zone outdoor airflow (Vbz) shall be reset in response
to current occupancy and shall be no less than the building component
(Ra × Az) of the DCV zone.
Dynamic Ventilation Reset Strategies141
implementing DCV in multiple-zone recirculating systems
CO2 Sensor in Common Return-Air Duct?
SAOA
RAEA
space
space
CO2
Under-ventilates some zones while over-ventilating others
Dynamic Ventilation Reset Strategies142
implementing DCV in a multiple-zone recirculating system
CO2 Sensor in Common Return Duct?
6.2.7.1.2 The ventilation system shall be controlled such that at steady-state it
provides each zone with no less than the breathing zone outdoor airflow (Vbz)
for the current zone population.ASHRAE Standard 62.1-2013
Dynamic Ventilation Reset Strategies143
implementing DCV in a multiple-zone recirculating system
DCV at Zone Level + Ventilation Reset
lounge restroom
storage office
office conference rm computer roomreception area ele
vato
rs
vestibule corridor
CO2
CO2
OCC
OCC
TOD TOD
building automation system (BAS)
Dynamic Ventilation Reset Strategies144
DCV at Zone Level
• Use all zone-level DCV approaches,
each where it best fits
– CO2 sensors: densely-occupied zones with highly-
variable population
– Occupancy sensors: low-density offices or densely-
occupied zones where population varies only minimally
– Time-of-day schedules: zones with predictable patterns
Dynamic Ventilation Reset Strategies145
Ventilation Reset at System Level
CO2 OCC
SA RA
CO2TOD TODOCC
• Current required outdoor airflow (Voz)
(TOD schedule, OCC sensor, CO2 sensor)• Current primary airflow (Vpz)
• Current OA fraction (Zpz)
communicating VAV controllers
AHU or rooftop unit withflow-measuring OA damper
• Reset intake airflow (Vot)
Building Automation System
• Find highest OA fraction (Zpz)
• Calculate current systemventilation efficiency (Ev)
• Calculate current system
intake airflow (Vot)
Dynamic Ventilation Reset Strategies146
DCV at zone level + ventilation reset at system level
Benefits
• Saves energy during partial occupancy
• Lower installed cost, less maintenance, and more
reliable than installing a CO2 sensor in every zone
– Use zone-level DCV approaches where they best fit
(CO2 sensor, occupancy sensor, time-of-day schedule)
– Combine with ventilation reset at the system level
• Earn LEED (v4) EQ credit: Enhanced IAQ Strategies
Carbon Dioxide Monitoring
Monitor CO2 concentrations within all densely occupied spaces. CO2 monitors
must be between 3 and 6 feet above the floor. Calculate appropriate CO2
setpoints using methods in ASHRAE 62.1-2010, Appendix C.
Dynamic Ventilation Reset Strategies147
implementing DCV in a multiple-zone recirculating system
DCV + VAV Box Reset + Ventilation Reset
CO2
SA RA
CO2TOD TODOCC
• Current required outdoor airflow (Voz)
(TOD schedule, OCC sensor, CO2 sensor)• Current primary airflow (Vpz)
• Current OA fraction (Zpz)
• OA fraction limit (max Zpz)
communicating VAV controllers
AHU or rooftop unit withflow-measuring OA damper
• Reset intake airflow (Vot)
Building Automation System
• Find highest OA fraction (Zpz)
• Calculate current systemventilation efficiency (Ev)
• Calculate current system
intake airflow (Vot)
OCC
Dynamic Ventilation Reset Strategies148
CO2-Based DCV for Multiple-Zone HVAC Systems
ASHRAE Research Project 1547
• Compares various control sequences
• Further enhances control sequences
and setpoints for multiple-zone
recirculating ventilation systems
Dynamic Ventilation Reset Strategies149
Implementation of RP-1547 CO2-Based DCV Control Sequences
ASHRAE Research Project 1747
“Valid logic was developed in Research Project 1547, but it is not readily
implemented in real control systems.”
“This project will develop practical control sequences, then test them in a
real-world building environment with a commercial-grade DDC system.”
RFP for ASHRAE Research Project 1747
• Project began in September 2015
… with expected completion by mid-2017
Dynamic Ventilation Reset Strategies150
Seventhwave (2015) field study of DCV in Minnesota
DCV Control Sequences Implemented
Dynamic Ventilation Reset Strategies151
Seventhwave (2015) field study of DCV in Minnesota
Measured/Calculated Energy Savings
Dynamic Ventilation Reset Strategies152
dynamic ventilation reset strategies
Agenda
• Ventilation reset in VAV systems
– VAV box minimum reset
• Demand-controlled ventilation
– Common technologies
– Implementing DCV is various types of systems
• Requirements of ASHRAE Standard 90.1
• Summary of suggestions for cost-effective application
of demand-controlled ventilation
Dynamic Ventilation Reset Strategies153
ASHRAE Standard 90.1-2013 (prescriptive requirement)
Ventilation Reset
6.5.3.3 Multiple-Zone VAV System Ventilation Optimization Control.
Multiple-zone VAV systems with DDC of individual zone boxes reporting to a
central control panel shall include means to automatically reduce outdoor air
intake flow (Vot) below design rates in response to changes in system
ventilation efficiency (Ev) as defined by Appendix of ASHRAE Standard 62.1.
Exceptions:
a. VAV systems with zonal transfer fans that recirculate air from other zones
without directly mixing it with outdoor air, dual-duct dual-fan VAV
systems, and VAV systems with fan-powered terminal units.
b. Systems required to have the exhaust air energy recovery complying with
Section 6.5.6.1.
c. Systems where total design exhaust airflow is more than 70% of total
design outdoor air intake flow requirements.
Dynamic Ventilation Reset Strategies154
ASHRAE Standard 90.1-2010 (mandatory requirement)
Demand-Controlled Ventilation
6.4.3.9 Ventilation Controls for High-Occupancy Areas.
Demand control ventilation (DCV) is required for spaces larger than 500 ft2
and with a design occupancy for ventilation of > 40 people per 1000 ft2 of
floor area and served by systems with one or more of the following:
a. an air-side economizer,
b. automatic modulating control of the outdoor air damper,
or
c. a design outdoor airflow > 3000 cfm.
Exceptions:
a. Systems with exhaust air energy recovery complying with Section 6.5.6.1.
b. Multiple-zone systems without DDC of individual zones communicating with a
central control panel.
c. Systems with a design outdoor airflow < 1200 cfm.
d. Spaces where the supply airflow rate minus any makeup or outgoing transfer air
requirement is less than 1200 cfm.
Dynamic Ventilation Reset Strategies155
ASHRAE Standard 90.1-2013 (mandatory requirement)
Demand-Controlled Ventilation
6.4.3.8 Ventilation Controls for High-Occupancy Areas.
Demand control ventilation (DCV) is required for spaces larger than 500 ft2
and with a design occupancy for ventilation of ≥ 25 people per 1000 ft2 of
floor area and served by systems with one or more of the following:
a. an air-side economizer,
b. automatic modulating control of the outdoor air damper,
or
c. a design outdoor airflow > 3000 cfm.
Exceptions:
1. Systems with exhaust air energy recovery complying with Section 6.5.6.1.
2. Multiple-zone systems without DDC of individual zones communicating with a
central control panel.
3. Systems with a design outdoor airflow < 750 cfm.
4. Spaces where > 75% of the space design outdoor airflow is required for
makeup air that is exhausted from the space or transfer air that is required
for makeup air that is exhausted from other space(s).
5. Correctional cells, daycare sickrooms, science labs, beauty and nail salons,
and bowling alley seating.
Dynamic Ventilation Reset Strategies156
impact of
90.1-2013
• Correctional waiting room
• Lecture classroom
• Lecture hall
• Multi-use assembly
• Restaurant dining room
• Cafeteria / fast food dining
• Bars, cocktail lounge
• Conference / meeting
• Break room
• Telephone / data entry
• Transportation waiting
• Auditorium seating area
• Place of religious worship
• Courtroom
• Legislative chambers
• Lobby
• Spectator area
• Disco / dance floor
• Gambling casino
• Stage / studio
• Correctional waiting room
• Daycare
• Classroom (ages 5-8)
• Classroom (age 9+)
• Lecture classroom
• Lecture hall
• Computer lab
• Media center
• Music / theater / dance
• Multi-use assembly
• Restaurant dining room
• Cafeteria / fast food dining
• Bars, cocktail lounge
• Conference / meeting
• Lobby / pre-function
• Break room
• Reception area
• Telephone / data entry
• Transportation waiting
• Auditorium seating area
• Place of religious worship
• Courtroom
• Legislative chambers
• Lobby
• Museum / gallery
• Spectator area
• Disco / dance floor
• Health club / aerobics room
• Gambling casino
• Stage / studio
≥ 2
5 p
eo
ple
/ 1
00
0 f
t2
> 4
0 p
eo
ple
/ 1
00
0 f
t2
Dynamic Ventilation Reset Strategies157
dynamic ventilation reset strategies
Agenda
• Ventilation reset in VAV systems
– VAV box minimum reset
• Demand-controlled ventilation
– Common technologies
– Implementing DCV is various types of systems
• Requirements of ASHRAE Standard 90.1
• Summary of suggestions for cost-effective application
of demand-controlled ventilation
Dynamic Ventilation Reset Strategies158
dynamic ventilation reset strategies
Summary
• ASHRAE Standard 62.1 allows dynamic reset of
ventilation air as operating conditions change
– Ventilation reset in VAV systems
– VAV box minimum reset in VAV systems
– Demand-controlled ventilation in any system
• Consider CO2-based DCV in densely-occupied zones
with widely-varying population
• Use other DCV technologies (occupancy sensors,
time-of-day schedules) where they make sense
• Combine DCV with ventilation reset in a VAV system
to avoid the need to sense CO2 in every zone
Dynamic Ventilation Reset Strategies159
dynamic ventilation reset strategies
Further Reading
• American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc.
2011. 62.1 User’s Manual. Atlanta, GA: ASHRAE.
– Appendix A: CO2-Based Demand-Controlled Ventilation
– Appendix B: Ventilation Reset Control
• Murphy, J. 2008. “CO2-Based Demand-Controlled Ventilation with ASHRAE
Standard 62.1,” HPAC Engineering (Sep): pp. 36-47.
• Seventhwave. 2015. “Energy Savings from Implementing and Energy Savings from
Implementing and Commissioning Demand Control Ventilation.”
• Stanke, D. 2006. “Standard 62.1 System Operation: Dynamic Reset Options”,
ASHRAE Journal (December): pp. 18-32.
• Stanke, D. 2010. “Dynamic Reset for Multiple-Zone Systems,” ASHRAE Journal
(March): pp. 22-35.
• ASHRAE Research Project 1547. CO2-Based Demand-Controlled Ventilation for
Multiple-Zone HVAC Systems.
• ASHRAE Research Project 1747 (in progress). Implementation of
RP-1547 CO2-based DCV for Multiple-Zone Systems in DDC Systems.
Part 2: Dynamic Ventilation Reset Strategies
Self-Assessment Quiz
1. Which of the following are possible technologies for implementing demand-
controlled ventilation? Circle all that apply.
a. Carbon dioxide (CO2) sensors
b. Temperature sensors
c. Time-of-day schedules in a building automation system
d. Occupancy sensors / motion detectors
2. True or False: Demand-controlled ventilation in certain densely-occupied
spaces is a mandatory requirement of ASHRAE Standard 90.1.
3. Which of the following are concerns when implementing demand-controlled
ventilation? Circle all that apply.
a. Allowing the OA damper to open further for economizing, when applicable
b. Sensor inaccuracy and the associated risk to energy use or IAQ
c. Maintaining proper building pressurization
d. Cross-leakage between the exhaust and outdoor air streams
4. True or False: The primary motivation for implementing demand-controlled
ventilation is to improve indoor air quality.
Design and Control of Ventilation Systems161
Design and Control of Ventilation Systems
Agenda
8:30 – 10:15 Ventilation Fundamentals, ASHRAE 62.1
Break
10:30 – noon Dynamic Ventilation Reset Strategies
Lunch
12:45 – 2:15 Exhaust-Air Energy Recovery
Break
2:30 – 4:00 Dedicated Outdoor-Air Systems
Design and Control of Ventilation Systems162
Exhaust-Air Energy Recovery
Exhaust-Air Energy Recovery163
exhaust-air energy recovery
Agenda
• Psychrometrics of exhaust-air recovery
• Proper control and integration into HVAC systems
• Common technologies
• Requirements of ASHRAE 90.1
• Summary of suggestions for cost-effective application
of exhaust-air energy recovery
Exhaust-Air Energy Recovery164
Exhaust-Air Energy Recovery
space
SA
RAEA
OA
air-to-airheat exchanger
Exhaust-Air Energy Recovery165
Example: Total-Energy Wheel
Exhaust-Air Energy Recovery166
Sensible vs. Total Recovery
• Sensible energy recovery
– Transfers sensible heat
– Changes the dry-bulb temperature of air
• Total energy recovery
– Transfers sensible heat and water vapor (latent heat)
– Changes the dry-bulb temperature and humidity of air
Exhaust-Air Energy Recovery167
example: coil runaround loop
Sensible-Energy Recovery
EA'
OA
coil loop
7,000 cfm
10,000 cfm
EA
OA'
OA
EA
OA'
92°F DBT,
75°F WBT,
104 gr/lb
78°F DBT,
67 gr/lb
87.4°F DBT,
104 gr/lb
EA
OAOA'
saves 50 MBH (4.2 tons)
sensible-energy recovery • Chicago
EA'
EA' 84.7°F DBT,
67 gr/lb
EA
OA OA'
EA'
sensible-energy recovery • Chicago
OA
EA
OA'
-4°F DBT,
3 gr/lb
70°F DBT,
37 gr/lb,
40°F DPT
20.3°F DBT,
3 gr/lb
EA' 36°F DBT,
31 gr/lb,
100% RH
water vapor condensing
on exhaust-side coil
Exhaust-Air Energy Recovery170
Frosting
EA
OA
–4°F DBT
70°F DBT
37 gr/lb
40°F DPT
20.3°F DBT
36°F DBT
31 gr/lb
17°F
condensate freezes if the
surface temperature of the
exhaust-side coil is < 32°F
Exhaust-Air Energy Recovery171
coil runaround loop
Frost Prevention
EA
OA
–4°F DBT
70°F DBT
37 gr/lb
40°F DPT
14.9°F DBT
42°F DBT
37 gr/lb
40°F DPT 39°F
17°F
32°F
3-way mixing valve
Exhaust-Air Energy Recovery172
EA
OA OA'
saves 205 MBh EA'
sensible-energy recovery • Chicago
OA
EA
OA'
-4°F DBT,
3 gr/lb
70°F DBT,
37 gr/lb,
40°F DPT
14.9°F DBT,
3 gr/lb
EA' 42°F DBT,
37 gr/lb
Exhaust-Air Energy Recovery173
example: total-energy (enthalpy) wheel
Total-Energy Recovery
total-energy wheel
EA'
OA
7,000 cfm
10,000 cfm
EA
OA'
Exhaust-Air Energy Recovery174
saves 243 MBh (20.3 tons)
OA'
OA
EA
OA'
92°F DBT,
75°F WBT,
104 gr/lb
78°F DBT,
67 gr/lb
83.6°F DBT,
83 gr/lb
OA
EA
total-energy recovery • Chicago
EA' 90°F DBT,
97 gr/lb
EA'
EAOA'
EA'
total-energy recovery • ChicagoOA
OA
EA
OA'
-4°F DBT,
3 gr/lb
70°F DBT,
37 gr/lb
58°F DBT,
32 gr/lb
EA' 8°F DBT,
100% RH
if EA' reaches 100% RH,
condensation freezes if
the exhaust-side surface
temperature is < 32°F
Exhaust-Air Energy Recovery176
total-energy wheel
Frost Prevention
Frost prevention options
• Turn wheel off
• Modulate OA
bypass dampers
• Preheat OA
• Preheat EA
OA
EA
OA bypassdampers
Exhaust-Air Energy Recovery177
EAsaves 452 MBh (sensible)
132 MBh (latent)OA'
EA'PH
total-energy recovery • ChicagoOA
OA
EA
OA'
-4°F DBT,
3 gr/lb
70°F DBT,
37 gr/lb
42°F DBT,
22 gr/lb
EA' 10°F DBT,
9 gr/lb,
97% RH
PH 0°F DBT,
3 gr/lb
Exhaust-Air Energy Recovery178
cooling plant 50 MBh
reduction (4.2 tons)
heating plant 205 MBh
reduction
cooling plant 243 MBh
reduction (20.3 tons)
heating plant 452 MBh
reduction (latent) (132 MBh)
sensible-energy
recovery
total-energy
recovery
example (Chicago)
Summary of Plant Downsizing
Exhaust-Air Energy Recovery179
Exhaust-Air Energy Recovery
Impact on installed cost
• Cooling and heating plant
downsizing
• Increased fan motor sizes
– Added static pressure of
energy-recovery device
• Additional exhaust ductwork
Impact on operating cost
• Cooling and heating
energy savings
• Increased fan energy use
• Proper control of the device
maximizes energy savings
Exhaust-Air Energy Recovery180
exhaust-air energy recovery
Other Considerations
• Frost prevention
• Acceptable cross-leakage?
EA
total-energy
recovery
sensible-energy
recovery
Exhaust-Air Energy Recovery181
exhaust-air energy recovery
Agenda
• Psychrometrics of exhaust-air recovery
• Proper control and integration into HVAC systems
• Common technologies
• Requirements of ASHRAE 90.1
• Summary of suggestions for cost-effective application
of exhaust-air energy recovery
Exhaust-Air Energy Recovery182
exhaust-air energy recovery
Control During Mild Weather
SA
RA
OA
10,000 cfm
7,000 cfm
30,000 cfm
68°F65°F
70°F
20,000 cfmwheel ON(full capacity)
EA
cooling coil ON(438 MBh)
55°F55°F
RRA
Exhaust-Air Energy Recovery183
exhaust-air energy recovery
Control During Mild Weather
SAOA
10,000 cfm
7,000 cfm
30,000 cfm
65°F55°F
70°F
20,000 cfmwheel OFF
EA
cooling coil ON(308 MBh)
55°F55°F
RRA
RA
Exhaust-Air Energy Recovery184
exhaust-air energy recovery
Control During Mild Weather
SAOA
30,000 cfm
27,000 cfm
30,000 cfm
55°F55°F
70°F
0 cfmwheel OFF
EA
cooling coil OFF(0 MBh)
55°F55°F
RRA
RA
airside economizing
Exhaust-Air Energy Recovery185
exhaust-air energy recovery
Capacity Control During Heating
SAOA
10,000 cfm
7,000 cfm
18,000 cfm
64°F60°F
70°F
8,000 cfmwheel ON(full capacity)
EA
cooling coil ON(87 MBh)
60°F
(SAT reset)
40°F
RRA
RA
Exhaust-Air Energy Recovery186
exhaust-air energy recovery
Capacity Control During Heating
SAOA
10,000 cfm
7,000 cfm
18,000 cfm
53°F40°F
70°F
8,000 cfmwheel OFF
EA
heating coil ON(131 MBh)
60°F
(SAT reset)
40°F
RRA
RA
Exhaust-Air Energy Recovery187
exhaust-air energy recovery
Capacity Control During Heating
SAOA
10,000 cfm
7,000 cfm
18,000 cfm
60°F52°F
70°F
8,000 cfmwheel ON(partial capacity)
EA
both coils OFF
60°F
(SAT reset)
40°F
modulate EA bypass dampers
RRA
RA
Exhaust-Air Energy Recovery188
exhaust-air energy recovery
VAV Mixed-Air System
SA
RAEA
OA
space
EAspace
total-energywheel heating
coilcoolingcoil
VAV terminalunits
bypassdampers
bypassdampers
Exhaust-Air Energy Recovery189
180
160
140
120
100
80
60
40
20
hu
mid
ity ra
tio, g
rain
s/lb
of d
ry a
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
80
70
50
40
30
60
30
40
50
55
60
65
70
75
80
de
w p
oin
t tem
pe
ratu
re, °F
EA
DBTSA
wheel on (cooling)
bypass dampers closed
wheel off
bypass dampers open
wheel on (heating)
modulate bypass damperto avoid overheating
frost
prevention
468
MinneapolisJacksonville
annual operating hours
1111
496
481
44
wheel on (full cooling)
wheel on (partial heating)
wheel off
0
1585
953
62
0 wheel on (full heating)
wheel on (frost)
14891647 wheel on
mixed-air VAV system
Exhaust-Air Energy Recovery190
exhaust-air energy recovery
Dedicated Outdoor-Air System
CA
EAEA
OA
space
space
total-energywheel heating
coilcoolingcoil
bypassdampers
bypassdampers
SA
RA
SA
RA
Exhaust-Air Energy Recovery191
180
160
140
120
100
80
60
40
20
hu
mid
ity ra
tio, g
rain
s/lb
of d
ry a
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
80
70
50
40
30
60
30
40
50
55
60
65
70
75
80
de
w p
oin
t tem
pe
ratu
re, °F
CA
EA
DPTCA
wheel on (cooling)
bypass dampers closed
wheel off
bypass dampers open
wheel on (heating)
modulate bypass damperto avoid overheating or
over-humidifying
DBTCA
frost
prevention
dedicated OA system
Exhaust-Air Energy Recovery192
exhaust-air energy recovery
Agenda
• Psychrometrics of exhaust-air recovery
• Proper control and integration into HVAC systems
• Common technologies
• Requirements of ASHRAE 90.1
• Summary of suggestions for cost-effective application
of exhaust-air energy recovery
Exhaust-Air Energy Recovery193
Coil Runaround Loop
• 35% – 55% sensible
effectiveness
• 0.2 – 0.7 in. H2O pressure drop
• Very flexible
• No cross-leakage
• Capacity modulation using
variable-speed pump or
mixing valve
• Compact
expansion tank
pump
three-waymixing valve
EA
OA
Exhaust-Air Energy Recovery194
Heat Pipe
• 30% – 55% sensible
effectiveness
• 0.2 – 0.8 in. H2O pressure drop
• Capacity modulation using
bypass dampers or tilt control
• Very low cross-leakage
Exhaust-Air Energy Recovery195
Heat Pipe
Exhaust-Air Energy Recovery196
Fixed-Plate Heat Exchanger
EA
OA
• 55% – 70% sensible
effectiveness
• 0.3 – 1.0 in. H2O pressure drop
• Capacity modulation using
face-and-bypass dampers
• Little or no cross-leakage
• Most susceptible to frosting
Exhaust-Air Energy Recovery197
Exhaust-Air Energy Recovery198
fixed-plate heat exchanger
Exhaust-Air Energy Recovery
EA
center bypass
face-and-bypass
dampers
OA
Exhaust-Air Energy Recovery199
Fixed-Membrane Heat Exchanger
• 65% – 75% sensible effectiveness
• 45% – 65% latent effectiveness
• 0.6 – 1.2 in. H2O pressure drop
• Capacity modulation using
external bypass dampers
• Little or no cross-leakage
• Less susceptible to frost
than other technologies
EAOA
Exhaust-Air Energy Recovery200
Cross-Flow HX Frosting
• Fixed-plate heat exchangers
(sensible-energy recovery)
begin to experience frosting when
entering OA drops below 32°F
• Fixed-membrane heat exchangers
(total-energy recovery) can operate
well below 0°F without frosting
Exhaust-Air Energy Recovery201
Total-Energy Wheel
• 65% – 80% sensible effectiveness
• 60% – 70% latent effectiveness
• 0.8 – 1.1 in. H2O pressure drop
• Capacity modulation using
bypass dampers
• Some cross-leakage
• Self cleaning (dry particles)
• Less susceptible to frost than
sensible energy-recovery
technologies
bypass dampers
Exhaust-Air Energy Recovery202
total-energy wheels
Cross-Leakage and Fan Placement
Exhaust-Air Energy Recovery203
total-energy wheels
Purge Section
Exhaust-Air Energy Recovery204
comparison of energy-recovery technologies
Typical Performance
effectiveness, %
30 60 805040 70
coil loop
fixed-plateheat exchanger
heat pipe
sensible heat wheel
total-energy wheel
fixed-membraneheat exchanger
sensible
sensible
sensible
sensible
sensiblelatent
sensiblelatent
Exhaust-Air Energy Recovery205
comparison of energy-recovery technologies
Typical Performance
airside pressure drop (per side), in. H2O
0.2 0.8 1.20.60.4 1.0
coil loop
fixed-plateheat exchanger
heat pipe
sensible heat wheel
total-energy wheel
fixed-membraneheat exchanger
Exhaust-Air Energy Recovery206
comparison of energy-recovery technologies
Typical Frosting Conditions
outdoor temperatures at which frosting typically occurs, °F
-50°F 10°F 50°F-10°F-30°F 30°F
coil loop
fixed-plateheat exchanger
heat pipe
sensible heat wheel
total-energy wheel
fixed-membraneheat exchanger
557 hrs
(1788 hrs)12 hrs
(79 hrs)
7 hrs
(25 hrs)
Chicago, IL6 AM – 6 PM, weekdays
(all hours, all days)
Exhaust-Air Energy Recovery207
AHRI 1060 Certification
• Industry standard rating and
certification program for air-to-air
energy recovery components
– Rotary heat exchangers (wheels)
– Heat pipes
– Fixed-plate heat exchangers
– Does not cover coil loops
(coils certified by AHRI 410)
• Exhaust-air energy recovery
applications only
Exhaust-Air Energy Recovery208
AHRI 1060
Certified Rating Points
Summer Winter
Summer Winter
Summer Winter
Summer Winter
Summer Winter
Summer Winter
100%
Rated Flow
75%
Rated Flow
Sensible
Latent
Total
Effectiveness
• Airside pressure drop at all rating points
• Two cross-leakage measurements at three
different deck-to-deck pressures
Exhaust-Air Energy Recovery209
AHRI 1060
Cross-Leakage Measurements
exhaust-air
transfer rate
EATR
outdoor-air
correction factor
OACF
EA'
OA
EA
OA'
Exhaust-Air Energy Recovery210
www.ahridirectory.org
Exhaust-Air Energy Recovery211
exhaust-air energy recovery
Agenda
• Psychrometrics of exhaust-air recovery
• Proper control and integration into HVAC systems
• Common technologies
• Requirements of ASHRAE 90.1
• Summary of suggestions for cost-effective application
of exhaust-air energy recovery
Exhaust-Air Energy Recovery212
Section 6.5.6.1
ASHRAE Standard 90.1-1999 thru -2007
6.5.6.1 Exhaust Air Energy Recovery. Individual fan systems that have both
a design supply air capacity of 5000 cfm or greater and have a minimum
outdoor air supply of 70% or greater of the design supply air quantity
shall have an energy recovery system with at least 50% recovery
effectiveness.
Fifty percent energy recovery effectiveness shall mean a change in the
enthalpy of the outdoor air supply equal to 50% of the difference between the
outdoor air and return air at design conditions. Provision shall be made to
bypass or control the heat recovery system to permit air economizer operation
as required by Section 6.5.1.1.
Exhaust-Air Energy Recovery213
Section 6.5.6.1
ASHRAE Standard 90.1-2010
6.5.6.1 Exhaust Air Energy Recovery. Each fan system shall have an
energy recovery system when the system’s supply air flow rate exceeds the
value listed in Table 6.5.6.1 based on the climate zone and percentage of
outdoor air flow rate at design conditions.
Exhaust-Air Energy Recovery214
Exhaust-Air Energy Recovery215
Section 6.5.6.1
ASHRAE Standard 90.1-2013
6.5.6.1 Exhaust Air Energy Recovery. Each fan system shall have an
energy recovery system when the system’s supply airflow rate exceeds the
value listed in Tables 6.5.6.1-1 and 6.5.6.1-2, based on the climate zone and
percentage of outdoor airflow rate at design conditions.
Exhaust-Air Energy Recovery216
Section 6.5.6.1
ASHRAE Standard 90.1-2013
Exhaust-Air Energy Recovery217
Section 6.5.6.1
Only Minor Changes to the Exceptions
Standard 90.1-2007 Standards 90.1-2010 and -2013
Exhaust-Air Energy Recovery218
Section 6.5.6.1
ASHRAE 90.1-2010 and -2013
Energy recovery systems required by this section shall have at least 50%
energy recovery effectiveness. Fifty percent energy recovery effectiveness
shall mean a change in the enthalpy of the outdoor air supply equal to 50% of
the difference between the outdoor air and return air enthalpies at design
conditions.
Provision shall be made to bypass or control the energy recovery system to
permit air economizer operation as required by Section 6.5.1.1.
Exhaust-Air Energy Recovery219
Energy recovery systems required by this section shall have at least 50%
energy recovery effectiveness. Fifty percent energy recovery effectiveness
shall mean a change in the enthalpy of the outdoor air supply equal to 50% of
the difference between the outdoor air and return air enthalpies at design
conditions.
Section 6.5.6.1
Exhaust-Air Energy Recovery
OA
RA
92°F DBT75°F WBT38.4 Btu/lb
78°F DB64°F WB29.2 Btu/lb
hleaving ≤ 33.8 Btu/lb
Be careful of
this term!
Exhaust-Air Energy Recovery220
defined by ASHRAE Standard 84 and AHRI Standard 1060
Effectiveness
Sensible effectiveness
Total effectiveness
S = (T1 – T2)
(T1 – T3)ṁmin
ṁOA
T = (h1 – h2)
(h1 – h3)ṁmin
ṁOA
ṁmin = smallest of ṁOA or ṁEA
X4 X3
X2X1
ṁOA
ṁEA
Exhaust-Air Energy Recovery221
Equal Airflows
QT = 4.5 10,000 cfm (38.4 – 32.8 Btu/lb) = 252,000 Btu/hr
T = (38.4 – 32.8)
(38.4 – 29.2)10,000 cfm= 61%
10,000 cfm
10,000 cfm
10,000 cfm
92°F DBT75°F WBT38.4 Btu/lb
78°F DB64°F WB29.2 Btu/lb
83°F DBT69°F WBT32.8 Btu/lb
Exhaust-Air Energy Recovery222
Unequal Airflows
QT = 4.5 10,000 cfm (38.4 – 34.0 Btu/lb) = 198,000 Btu/hr
T = (38.4 – 34.0)
(38.4 – 29.2)6,000 cfm
10,000 cfm= 80%
compared to
61% with
equal airflows
compared to
252,000 Btu/hr with
equal airflows
Does not meet
ASHRAE 90.1(h2 ≤ 33.8 Btu/lb)
6,000 cfm
10,000 cfm
92°F DBT75°F WBT38.4 Btu/lb
78°F DB64°F WB29.2 Btu/lb
85°F DBT70°F WBT34.0 Btu/lb
samewheel
Exhaust-Air Energy Recovery223
“As-Applied” vs. “Rated” Effectiveness
• Be careful not to confuse “as-applied” effectiveness
(required by ASHRAE 90.1) with “rated” effectiveness
per AHRI 1060
• Confusing term was replaced in 2016 version of 90.1
• Strive for balanced airflows
– Bring back as much exhaust air as possible
Energy recovery systems required by this section shall result in an
enthalpy recovery ratio of at least 50%. A 50% enthalpy recovery ratio
shall mean a change in the enthalpy of the outdoor air supply equal to
50% of the difference between the outdoor air and entering exhaust air
enthalpies at design conditions.
excerpt from ASHRAE Standard 90.1-2016, Section 6.5.6.1
Exhaust-Air Energy Recovery224
exhaust-air energy recovery
Using Restroom Exhaust
VFD
Balancing
Damper
SA OA
RA
EAtoilet
EA
RA
Exhaust-Air Energy Recovery225
ASHRAE Standard 62.1-2013
Recirculation of Restroom Exhaust
OA
EA
V1 V2
V4 V3
V3-to-2EATR ≤ 10%
Exhaust Air Transfer Ratio (EATR) is defined
by ASHRAE Standard 84 and certified byAHRI Standard 1060
5.16.3.2.5 Class 2 air [which includes restrooms] shall not be recirculated
or transferred to Class 1 spaces.
Exception: When using any energy recovery device, recirculation from
leakage, carryover, or transfer from the exhaust side of the energy
recovery device is permitted. Recirculated Class 2 air shall not exceed
10% of the outdoor air intake flow.
Exhaust-Air Energy Recovery226
exhaust-air energy recovery
Agenda
• Psychrometrics of exhaust-air recovery
• Proper control and integration into HVAC systems
• Common technologies
• Requirements of ASHRAE 90.1
• Summary of suggestions for cost-effective application
of exhaust-air energy recovery
Exhaust-Air Energy Recovery227
exhaust-air energy recovery
Summary
• Total-energy recovery transfers both sensible heat and
water vapor (latent heat)
– Allows for larger reductions in cooling plant capacity
– Less susceptible to frost (greater heating energy savings)
• Maximize energy recovery effectiveness
– Centralize exhaust to better balance airflows and
maximize recovery
– Minimize cross-leakage with proper fan placement
– Proper control is very important (integrate with airside
economizer, modulate capacity to prevent over-heating,
frost prevention)
• Specify AHRI-certified components
Exhaust-Air Energy Recovery228
exhaust-air energy recovery
Further Reading
• American Society of Heating, Refrigeration and Air-Conditioning
Engineers, Inc. (ASHRAE). 2012. ASHRAE Handbook–HVAC
Systems and Equipment (Chapter 26, “Air-to-Air Energy
Recovery Equipment”). Atlanta, GA: ASHRAE.
• Mumma, S. 2001. Dedicated outdoor air-dual wheel system
control requirements. ASHRAE Transactions 107(1). Atlanta, GA:
ASHRAE.
• Murphy, J. and Bradley, B. 2011. Air-to-Air Energy Recovery in
HVAC Systems (SYS-APM003-EN). La Crosse, WI: Trane.
• Murphy, J. March 2012. “Total Energy Wheel Control in a
Dedicated OA System.” ASHRAE Journal 54(3): 46-58.
Part 3: Exhaust-Air Energy Recovery
Self-Assessment Quiz
1. True or False: A total-energy recovery device (such as an enthalpy
wheel) transfers both sensible heat and water vapor (latent heat)
between two airstreams.
2. During cold weather, frosting can occur on the exhaust-air energy
recovery device. On which side of the device does it occur?
a. supply side (through which outdoor air enters the building)
b. exhaust side (through which exhaust air leaves the building)
3. True or False: A total-energy wheel should be controlled to rotate
whenever the supply fan is on.
4. True or False: Sensible-energy recovery devices begin to
experience frosting at higher ambient temperatures than total-
energy recovery devices.
Design and Control of Ventilation Systems230
Design and Control of Ventilation Systems
Agenda
8:30 – 10:15 Ventilation Fundamentals, ASHRAE 62.1
Break
10:30 – noon Dynamic Ventilation Reset Strategies
Lunch
12:45 – 2:15 Exhaust-Air Energy Recovery
Break
2:30 – 4:00 Dedicated Outdoor-Air Systems
Design and Control of Ventilation Systems231
Dedicated Outdoor-Air Systems
Dedicated Outdoor-Air Systems232
AHRI Standard 920
What is a Dedicated OA System?
“[A dedicated OA unit] operates in combination
with a separate sensible cooling system to
satisfy the entire building humidity load. The
system is sized to maintain a prescribed
ventilation rate under any load condition. The
ventilation rate can be constant or varied based
on the building operation or occupancy schedule
or in response to the actual occupancy.
It may pre-condition outdoor air by containing an enthalpy wheel,
sensible wheel, desiccant wheel, plate heat exchanger, heat pipes
or other heat or mass transfer apparatus. It may reheat the
ventilation air by containing a reheat refrigerant circuit, sensible
wheel, heat pipe, or other heat or mass transfer apparatus.”
Dedicated Outdoor-Air Systems233
dedicatedOA unit
CA
SA CA
EA
OADelivers prescribed
(typically minimum)
ventilation rate Satisfies entire building
humidity (latent) load
May reheat dehumidified
ventilation air
May pre-condition
outdoor air using
air-to-air energy recovery
SA
RA
RA
CA
CA
Operates in combination
with a separate sensible
cooling/heating system
What is a Dedicated OA System?
Dedicated Outdoor-Air Systems234
dedicated outdoor-air systems
Agenda
• Determining the required leaving-air dew point
• Cold versus neutral air
• Optimized control strategies
• Common methods for delivering conditioned OA
• Requirements of ASHRAE 90.1 related to dedicated
OA systems
• Summary of suggestions for cost-effective application
of dedicated outdoor-air systems
Dedicated Outdoor-Air Systems235
180
160
140
120
100
80
60
40
20
hu
mid
ity ra
tio, g
rain
s/lb
of d
ry a
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
80
70
50
40
30
60
30
40
50
55
60
65
70
75
80
de
w p
oin
t tem
pe
ratu
re, °F
CA
dry enough toremove spacelatent load
OA
space
Determining Required Leaving-Air DPT
Dedicated Outdoor-Air Systems236
180
160
140
120
100
80
60
40
20
hu
mid
ity ra
tio, g
rain
s/lb
of d
ry a
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
80
70
50
40
30
60
30
40
50
55
60
65
70
75
80
de
w p
oin
t tem
pe
ratu
re, °F
CA
OA
space
Determining Required Leaving-Air DPT
Wca
Wspace
Qspace,latent
Qspace,latent = 0.69 × Voz × (Wspace – Wca)
Dedicated Outdoor-Air Systems237
Determining Required Leaving-Air DPT
1. Calculate outdoor airflow required for each zone (Voz)
2. Define target space humidity level (Wspace)
50% RH, 55%, 60%, 65%, other?
3. Determine latent load for each zone (Qspace,latent)
People, infiltration, indoor moisture sources
4. Calculate required humidity ratio of the
conditioned OA delivered to each zone (Wca):
Qspace,latent = 0.69 × Voz × (Wspace – Wca)
Dedicated Outdoor-Air Systems238
Example Wing of K-12 Classrooms
Classroom
101
Classroom
102
Classroom
103
Classroom
104
Wspace
(75°F, 50% RH,
55°F DPT)
64.7 gr/lb 64.7 gr/lb 64.7 gr/lb 64.7 gr/lb
Qspace,latent 5250 Btu/hr 5470 Btu/hr 5700 Btu/hr 5250 Btu/hr
Voz 450 cfm 450 cfm 480 cfm 435 cfm
Wca 47.7 gr/lb 47.0 gr/lb 47.4 gr/lb 47.2 gr/lb
Dedicated Outdoor-Air Systems239
Calculate Wca for Each Space
Qspace,latent = 0.69 Voz (Wspace – Wca)
For Classroom 102:
Qspace,latent = 5,470 Btu/hr
Voz = 450 cfm
Wspace = 64.7 gr/lb (75°F DBT, 50% RH, 55°F DPT)
5,470 Btu/hr = 0.69 450 cfm (64.7 gr/lb – Wca)
Wca = 47.0 gr/lb (~47°F DPT)
Dedicated Outdoor-Air Systems240
Impact of Wspace
Classroom 102 60% RH 55% RH 50% RH
Wspace
(75°F DBT)
77.8 gr/lb 71.2 gr/lb 64.7 gr/lb
Wca 60.2 gr/lb 53.6 gr/lb 47.0 gr/lb
DPTca 53°F 50°F 47°F
Dedicated Outdoor-Air Systems241
dedicated outdoor-air systems
Agenda
• Determining the required leaving-air dew point
• Cold versus neutral air
• Optimized control strategies
• Common methods for delivering conditioned OA
• Requirements of ASHRAE 90.1 related to dedicated
OA systems
• Summary of suggestions for cost-effective application
of dedicated outdoor-air systems
Dedicated Outdoor-Air Systems242
180
160
140
120
100
80
60
40
20
hu
mid
ity ra
tio, g
rain
s/lb
of d
ry a
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
80
70
50
40
30
60
30
40
50
55
60
65
70
75
80
de
w p
oin
t tem
pe
ratu
re, °F
CA
OA
RA/spaceSA
dedicated OA system(“neutral” air)
OA 95°F DB78°F WB
CA 70°F DB47°F DPT(450 cfm)
RA 75°F DB50% RH55°F DPT
SA 60°F DB(1500 cfm)
local unit
local unit:
1500 cfm, 2.0 tons
Dedicated Outdoor-Air Systems243
180
160
140
120
100
80
60
40
20
hu
mid
ity ra
tio, g
rain
s/lb
of d
ry a
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
80
70
50
40
30
60
30
40
50
55
60
65
70
75
80
de
w p
oin
t tem
pe
ratu
re, °F
CA
OA
deh
um
idific
atio
nsensible cooling
space
wasted cooling
dedicated OA system(“neutral” air)
Dedicated Outdoor-Air Systems244
180
160
140
120
100
80
60
40
20
hu
mid
ity ra
tio, g
rain
s/lb
of d
ry a
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
80
70
50
40
30
60
30
40
50
55
60
65
70
75
80
de
w p
oin
t tem
pe
ratu
re, °F
CA
OA
RA/spaceSA
dedicated OA system(“cold” air)
OA 95°F DB78°F WB
CA 48°F DB47°F DPT(450 cfm)
RA 75°F DB50% RH55°F DPT
SA 60°F DB(840 cfm)
local unit
local unit:
840 cfm, 1.1 tons
Dedicated Outdoor-Air Systems245
1950 cfm
CA
1500 cfm at 60°F
450 cfm at 70°F
neutral air delivereddirect to space
CA SARA
SA
1290 cfm
CA
840 cfm at 60°F
RA
cold air delivereddirect to space
CA
450 cfm at 48°F
840 cfm
1500cfm
Dedicated Outdoor-Air Systems246
Cold vs. Neutral
• Less overall cooling capacity
– Sensible cooling provided by cold conditioned OA
reduces required cooling capacity of local HVAC units
– Cooling (dehumidification) capacity of the dedicated
OA unit is the same in either case
• Less overall cooling energy
– Sensible cooling provided by cold conditioned OA
reduces cooling required from local HVAC units
Dedicated Outdoor-Air Systems247
SA
1290 cfm
CA
840 cfm at 60°F
450 cfmat 48°F
RA
cold air delivereddirect to space
CA
1500 cfm
1500 cfm at 60°F
cold air deliveredto local HVAC unit
SARA
CA
450 cfm at 48°F
840 cfm
1050 cfm
Dedicated Outdoor-Air Systems248
Cold vs. Neutral
• Less overall fan energy, if OA is delivered cold
directly to spaces
– Cold conditioned OA removes some of the space
sensible cooling load, which reduces the airflow
needed from local HVAC units
– Airflow delivered by the dedicated OA unit is the same
in either case
Dedicated Outdoor-Air Systems249
Cold vs. Neutral
dedicated OA unit
cooling capacity, tons 3.9 3.9 3.9
reheat capacity, MBh 11.4 0 0
fan airflow, cfm 450 450 450
local HVAC unit
cooling capacity, tons 2.0 1.1 1.1
fan airflow, cfm 1500 840 1500
cold tospace
neutral tospace/unit
cold tolocal unit
Dedicated Outdoor-Air Systems250
Won’t Cold OA Overcool the Space?
Qsens,space = 26,780 Btu/h (design load)
Qsens,ca = 1.085 450 cfm (75°F – 48°F)
= 13,180 Btu/h
Space sensible cooling load
must be < 50% of design
before overcooling will occur!
Dedicated Outdoor-Air Systems251
When Should OA Be Reheated?
• Applications where space sensible cooling loads
differ greatly at any given time (e.g., hotels, dorms)
• Applications requiring lower-than-normal dew points
(ex. engineer may want to reheat 48°F air to 55°F)
• To avoid condensation when conditioned OA is
delivered to the ceiling plenum
• To avoid overcooling zones at part-load conditions
Dedicated Outdoor-Air Systems252
to avoid overcooling
Demand-Controlled Ventilation
RA
SA
dedicatedOA unit
CA
EACA
local HVAC units
CA
RA
SA
VAV
CO2 CO2
Dedicated Outdoor-Air Systems253
to avoid overcooling
Activate Heat in Local Unit
RA
SA
dedicatedOA unit
CA
EACA
• only a few zones?• WSHPs
CA
RA
SA
Dedicated Outdoor-Air Systems254
to avoid overcooling
Reheating Dehumidified OA
RA
SA
dedicatedOA unit
CA
EACA
local HVAC units
CA
RA
SA
T
Dedicated Outdoor-Air Systems255
to avoid overcooling
Reheating Dehumidified OA
RA
SA
dedicatedOA unit
CA
EACA
CA
RA
SAT T
BAS
Dedicated Outdoor-Air Systems256
When Should OA Be Reheated?
• Applications where space sensible cooling loads
differ greatly at any given time (e.g., hotels, dorms)
• Applications requiring lower-than-normal dew points
• To avoid condensation when conditioned OA is
delivered to the ceiling plenum
• To avoid overcooling zones at part-load conditions
– Implement demand-controlled ventilation to
reduce outdoor airflow as population changes
– Activate heat in the local HVAC unit
(few zones, WSHPs)
– Reheat dehumidified air in dedicated OA unit
(consider using recovered energy)
Dedicated Outdoor-Air Systems257
dedicated outdoor-air systems
Agenda
• Determining the required leaving-air dew point
• Cold versus neutral air
• Optimized control strategies
• Common methods for delivering conditioned OA
• Requirements of ASHRAE 90.1 related to dedicated
OA systems
• Summary of suggestions for cost-effective application
of dedicated outdoor-air systems
Dedicated Outdoor-Air Systems258
common methods for
Delivering Conditioned OA to Zones
1. Direct to each zone
2. To intake of each local unit
3. To supply-side of each local unit
4. To ceiling plenum, near each local unit
Dedicated Outdoor-Air Systems259
Direct to Each Zone
RA
SA
dedicatedOA unit
CA• fan-coils
• WSHPs
• PTAC units
• VRF terminals
• passive chilled beams
• radiant cooling panels
EACA
CA
Dedicated Outdoor-Air Systems260
Direct to Each Zone
Advantages
• Easier to ensure required
outdoor airflow reaches each
zone (separate diffusers)
• Opportunity to cycle off local
fan because OA is not
distributed through it
• Allows dedicated OA system
to operate during
unoccupied periods without
needing to operate local fans
• Opportunity to downsize
local equipment (if OA
delivered at a cold temp)
Drawbacks
• Requires installation of
additional ductwork and
separate diffusers
• May require multiple
diffusers to ensure that
outdoor air is adequately
dispersed throughout the
zone
Dedicated Outdoor-Air Systems261
To Intake of Local Units
• fan-coils
• WSHPs
• small rooftop units
• VRF terminals
• sensible-cooling terminals
SA SARA RA
EACA
dedicatedOA unit
Dedicated Outdoor-Air Systems262
To Intake of Local Units
Advantages
• Helps ensure required OA
reaches each zone (ducted
directly to each unit)
• Avoids cost and space to
install additional ductwork
and separate diffusers
• Easier to ensure that OA is
adequately dispersed
throughout zone because it
is distributed by local fan
Drawbacks
• Measurement and balancing
is more difficult than if OA
delivered directly to zone
• May require field-fabricated
plenum to connect OA duct
• May need to increase OA in
heating mode (Ez < 1.0)
• Local fan must operate
continuously to provide OA
during scheduled occupancy
• Local fan must operate if
dedicated OA system
operates during unoccupied
period
Dedicated Outdoor-Air Systems263
To Supply-Side of Local Units
• fan-coils
• WSHPs
• small rooftop units
• active chilled beams
SARA
EACA
SA
RA
dedicatedOA unit
Dedicated Outdoor-Air Systems264
To Supply-Side of Local Units
Advantages
• Helps ensure required OA
reaches each zone (ducted
directly to each unit)
• Avoids cost and space to
install additional ductwork
and separate diffusers
• Easier to ensure that OA is
adequately dispersed
throughout zone because it
is distributed by local fan
• Opportunity to downsize
local equipment (if OA
delivered at a cold temp)
Drawbacks
• Measurement and balancing
is more difficult than if OA
delivered directly to zone
• May need to increase OA in
heating mode (Ez < 1.0)
• Local fan typically must
operate continuously to
provide OA during scheduled
occupancy (unless a
pressure-independent
damper is used)
Dedicated Outdoor-Air Systems265
To Plenum, Near Local Units
• fan-coils
• WSHPs
• VRF terminalsSA SARA RA
EACA
dedicatedOA unit
Dedicated Outdoor-Air Systems266
To Plenum, Near Local Units
Advantages
• Avoids cost and space to
install additional ductwork
and separate diffusers
Drawbacks
• More difficult to ensure
required OA reaches each zone
(not ducted directly)
– Refer to Figure 5-D and 5-E,
ASHRAE 62.1-2010 User’s Manual
• May need to increase OA in
heating mode (Ez < 1.0)
• Local fan must operate
continuously to provide OA
during scheduled occupancy
• Conditioned OA not able to be
delivered at a cold temperature
due to concerns about
condensation
Dedicated Outdoor-Air Systems267
conditioned OA delivered to plenum, near local units
Excerpt from 62.1-2010 User’s Manual
Dedicated Outdoor-Air Systems268
dedicated outdoor-air systems
Agenda
• Determining the required leaving-air dew point
• Cold versus neutral air
• Optimized control strategies
• Common methods for delivering conditioned OA
• Requirements of ASHRAE 90.1 related to dedicated
OA systems
• Summary of suggestions for cost-effective application
of dedicated outdoor-air systems
Dedicated Outdoor-Air Systems269
ASHRAE Standard 90.1-2013
Dedicated OA Systems
• Minimum equipment efficiencies
• Fan power limitation
• Economizer
• Limitation on simultaneous
heating and cooling (reheat)
Dedicated Outdoor-Air Systems270
Section 6.4.1, ASHRAE 90.1-2013
Minimum Equipment Efficiencies
Equipment efficiency levels defined in this section [Section 6.4.1] and Tables
6.8.1-1 through 6.8.1-13 are based on industry rating standards, such as
those of the Air-Conditioning, Heating, and Refrigeration Institute (AHRI).
Although Sections 6.4.1.1 and 6.4.1.2 include many types of HVACR
equipment, not every type of HVACR equipment that might be used in a
project is covered. This section [Section 6.4.1.3] clarifies that the use of
HVACR equipment not covered by these sections does not prohibit
compliance with the Standard. Equipment not covered by these sections is
not regulated by this standard, but may be regulated by other standards,
codes, or federal regulations.
Standard 90.1-2013 User's Manual, pages 6-14 and 6-18
Dedicated Outdoor-Air Systems271
Section 6.4.1, ASHRAE 90.1-2013
Minimum Equipment Efficiencies
• Until AHRI Standard 920 was published (June 2013)
there was no rating standard for DX dedicated OA
equipment, so ASHRAE 90.1 did not include minimum
efficiency requirements for this class of equipment
• Minimum efficiency requirements were added to
Standard 90.1 in the 2016 version
Dedicated outdoor air systems (DOAS) ... are used in many buildings
covered by ASHRAE 90.1. However, the current ASHRAE 90.1 standard
has no minimum energy efficiency requirements for this equipment.
Through AHRI, manufacturers of DOAS developed Standard 920 to
establish common rating conditions for these products. This proposal
establishes for the first time a product class for DOAS.
addendum CD to ASHRAE Standard 90.1-2013
Dedicated Outdoor-Air Systems272
ASHRAE Standard 90.1-2016
Minimum Equipment Efficiencies
Dedicated Outdoor-Air Systems273
Section 6.5.3.1.1, ASHRAE 90.1-2013
Fan Power Limitation
6.5.3 Air System Design and Control. Each HVAC system having a total
fan system motor nameplate hp exceeding 5 hp shall meet the provisions of
Sections 6.5.3.1 through 6.5.3.5.
6.5.3.1 Fan System Power and Efficiency
6.5.3.1.1 Each HVAC system at fan system design conditions shall not
exceed the allowable fan system motor nameplate hp (Option 1) or fan
system bhp (Option 2) as shown in Table 6.5.3.1-1. This includes supply
fans, return/relief fans, exhaust fans, and fan-powered terminal units
associated with systems providing heating or cooling capability. Single zone
VAV systems shall comply with the constant volume fan power limitation.
Exceptions:
1. Hospital, vivarium, and laboratory systems that utilize flow control devices
on exhaust and/or return to maintain space pressure relationships
necessary for occupant health and safety or environmental control may
use variable-volume fan power limitation.
2. Individual exhaust fans with motor nameplate horsepower of 1 hp or less.
Dedicated Outdoor-Air Systems274
Section 6.5.3.1.1, ASHRAE 90.1-2013
Fan Power Limitation
What is a “fan system”?
“fan system bhp: the sum of the fan brake horsepower
(bhp) of all fans that are required to operate at fan system
design conditions to supply air from the heating or cooling
source to the conditioned space(s) and return it to the
source or exhaust it to the outdoors” (Section 3.2)
Dedicated Outdoor-Air Systems275
example 6-CCC
User’s Manual for 90.1-2013
QUESTION: A wing of an elementary school building is served by
eight WSHPs, each equipped with a ¾-hp fan motor and serving a
single classroom. Ventilation air is supplied directly to each
classroom by a dedicated outdoor-air system. Each classroom
requires 500 cfm of outdoor air, so the DOAS delivers the total of
4000 cfm of conditioned outdoor air using a 5-hp fan. Does this
system need to comply with section 6.5.3.1?
ANSWER: Each WSHP is a separate fan system because
each has a separate cooling and heating source. The power of
the DOAS fan must be allocated to each heat pump on a
cfm-weighted basis.
Dedicated Outdoor-Air Systems276
example 6-CCC
User’s Manual for 90.1-2013
DOAS delivers 500 cfm to each classroom, so
1/8th (500 cfm / 4000 cfm) of the DOAS fan power is
added to the fan power for each WSHP:
• 1/8th of 5 hp = 5/8 hp
• 3/4 hp (WSHP) + 5/8 hp (allocated DOAS) = 1 3/8 hp
ANSWER [continued]:
…
In this instance, even with the DOAS fan allocated, each heat pump
fan system is less than the 5 hp threshold in Section 6.5.3, so the
system does not need to comply with Section 6.5.3.1.
Dedicated Outdoor-Air Systems277
Section 6.5.1, ASHRAE 90.1-2013
Economizers
Most notable exceptions:
1. Individual fan-cooling units < 54,000 Btu/hr (4.5 tons)
2. Systems that use non-particulate air treatment as
required by ASHRAE Standard 62.1
4. Systems with condenser heat recovery
5. Residential with cooling capacity < 270,000 Btu/hr
7. Systems that operate < 20 hours/week
9. Install higher-efficiency cooling equipment
6.5.1 Economizers. Each cooling system that has a fan shall include
either an air or water economizer meeting the requirements of
Sections 6.5.1.1 through 6.5.1.6.
Dedicated Outdoor-Air Systems278
Section 6.5.1, ASHRAE 90.1-2013
Economizers
Climate Zone 1
includes south
Florida, Hawaii,
Guam, Puerto
Rico, and the
Virgin Islands
Economizer required if
individual fan-cooling unit
54,000 Btuh (4.5 tons)
The requirement is based on the [capacity of the] fan-coil unit and
not the capacity of a central chilled-water plant or VRF system
condensing unit capacity.
ASHRAE 90.1-2013 User’s Manual, page 6-57
Dedicated Outdoor-Air Systems279
If an Economizer is Required…
• An airside economizer will likely be difficult to implement
with a dedicated OA system (typically sized for minimum
ventilation only)
• Implement a waterside economizer(fan-coils, WSHPs, chilled beams, radiant cooling)
• Install higher-efficiency cooling equipment (Exception 9)
• Comply using the Energy Cost Budget (Section 10)
method, rather than the prescriptive requirements
6.5.1.1.1 Air economizer systems shall be capable of modulating
outdoor air and return air dampers to provide up to 100% of the
design supply air quantity as outdoor air for cooling.
Dedicated Outdoor-Air Systems280
Section 6.5.2, ASHRAE 90.1-2013
Simultaneous Heating and Cooling
6.5.2.3 Dehumidification. Where humidity controls are provided, such
controls shall prevent reheating, mixing of hot and cold airstreams, or
other means of simultaneous heating and cooling of the same
airstream.
Exceptions:
1. The system is configured to reduce supply air volume to 50% or
less of the design airflow rate or the minimum outdoor air
ventilation rate specified in ASHRAE Standard 62.1 or other
applicable federal, state, or local code or recognized standard,
whichever is larger, before simultaneous heating and cooling takes
place.
…
Dedicated Outdoor-Air Systems281
example 6-SS
User’s Manual for 90.1-2013
QUESTION: A large 100% outdoor air, constant-volume system
provides minimum ventilation to hotel guest rooms in a Florida
hotel. The system includes a cooling coil and reheat coil
controlled by a supply air dew-point sensor. Does this system
comply with the Standard?
ANSWER: Yes. Exception 1 to Section 6.5.2.3 allows this
system, provided that the supply air rate is equal to the minimum
ventilation rate.
Dedicated Outdoor-Air Systems282
dedicated outdoor-air systems
Agenda
• Determining the required leaving-air dew point
• Cold versus neutral air
• Optimized control strategies
• Common methods for delivering conditioned OA
• Requirements of ASHRAE 90.1 related to dedicated
OA systems
• Summary of suggestions for cost-effective application
of dedicated outdoor-air systems
Dedicated Outdoor-Air Systems283
dedicated outdoor-air systems
Summary
• Dehumidify OA to a dew point drier than the space
• Deliver conditioned OA “cold” (not “neutral”), if possible
• Deliver conditioned OA directly to occupied spaces
• Use communicating controls to optimize system
– Reset DBTca to reheat only when necessary
– Reset DPTca based on space humidity
• Consider exhaust-air energy recovery
Dedicated Outdoor-Air Systems284
dedicated outdoor-air systems
Further Reading
• American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc.
2017. Dedicated Outdoor Air System Design Guide. Atlanta, GA: ASHRAE.
(available mid-2017)
• Morris, W. 2003. “The ABCs of DOAS: Dedicated Outdoor Air Systems.”
ASHRAE Journal (May).
• Murphy, J. 2006. “Smart Dedicated Outdoor Air Systems.” ASHRAE Journal
(July).
• Murphy, J. and Bradley, B. 2002. Dehumidification in HVAC Systems (SYS-
APM004-EN). La Crosse, WI: Trane.
• Murphy, J. and Harshaw, J. 2002. “AHRI 920: Rating Standard for DX Dedicated
Outdoor-Air Units” (ADM-APN060-EN). La Crosse, WI: Trane.
• Mumma, Stanley A. 2008. “DOAS Supply Air Conditions.” ASHRAE IAQ
Applications 9(2):18–20.
• Shank, K. and S. Mumma. 2001. “Selecting the Supply Air Conditions for a
Dedicated Outdoor Air System Working in Parallel with Distributed Sensible
Cooling Terminal Equipment.” ASHRAE Transactions 107(1).
• Trane. 2012. Dedicated Outdoor Air Systems, SYS-APG001-EN.
Part 4: Dedicated Outdoor-Air Systems
Self-Assessment Quiz
1. True or False: For a dedicated outdoor-air system to remove space latent loads, the
outdoor air must be dehumidified to a dew point that is drier than the desired space dew
point.
2. True or False: ASHRAE Standard 90.1 requires an airside economizer on every dedicated
outdoor-air system.
3. Which of the following are benefits of having the dedicated OA unit deliver the
dehumidified outdoor air cold, rather than reheating it to neutral? Circle all that apply.
a. The cold, dehumidified outdoor air results in better dehumidification than warm, dehumidified air.
b. The cold, dehumidified outdoor air removes more of the space sensible cooling loads, often allowing the local HVAC equipment to be downsized and use less energy.
c. Delivering the dehumidified outdoor air at a cold, rather than neutral, temperature avoids (or reduces)
the need to reheat this air in the dedicated OA unit.
d. Delivering the dehumidified outdoor air at a cold temperature eliminates the concern about
overcooling the spaces.
4. Which of the following impact the required dew point temperature delivered by the
dedicated OA equipment, if the goal is to remove the entire space latent load with the
dehumidified outdoor air? Circle all that apply.
a. The desired space humidity level.
b. The outdoor airflow delivered to the space by the dedicated OA unit.
c. The design space latent load.
d. The design space sensible cooling load.
Design and Control of Ventilation Systems286
Thank you for attending