DEHUMIDIFERTemperatureProcessOut:Tpo=Tpi+.68(MpiMpo)+.05(TriTpi)ReactivationOutletMoisture:Mro=Mri+Vp/Vr(MpiMpo)TemperatureReactivationOut:Tro=Tri[(TpoTpi)xVp/Vr]ReactivationEnergy:BTU/H=1.08xVrx(TriTru)MISCELLANEOUSFORMULASMoistureRemoval: =4.47xCFMxgr.(Lbs/hr) 7000 CFM: =7000[lbs/hr] (4.47xGR)ENERGYFORMULASKW =CFMx1.08xTorBTU/H
34123412
Temperaturerise =BTU/H CFMx1.08BTU/H =KWHx3412 HPx2545 CFMx1.08xT
LEGEND
Tpo TempProcessOut(F) Vp ProcessAirVolume(CFM)Tpi TempProcessIn(F) Vr ReactAirVolume(CFM)Tru TempReactInUnheated(F) Mpo MoistureProcessOut(GR)Tro TempReactOut(F) Mpi MoistureProcessIn(GR)Tri TempReactIn(F) Mro MoistureReactOut(GR)CFM CubicFeet/Minute Mri MoistureReactIn(GR)BTU/H BritishThermalUnits/Hour HP HorsepowerGR DifferenceinGrains KWH KilowattHoursT DifferenceinTemperature
DehumidifierFormulas
-
8425 Hazelbrand Road Covington, GA 30014 Ph# 770-788-6744 Fx# 770-788-6745