dee module 4.3 all
TRANSCRIPT
-
8/2/2019 Dee Module 4.3 All
1/15
Advanced Diploma of Electrical Engineering
Module 4: Circuit Breakers and Switchgears
Module 4.3
E-mail: [email protected] Web Site: www.idc-online.com
AUSTRALIA CANADA IRELAND NEW ZEALAND SINGAPORE SOUTH AFRICA UNITED KINGDOM UNITED STATES
-
8/2/2019 Dee Module 4.3 All
2/15
7
Medium Voltage Switchgear
In this chapter, we will learn about medium voltage switchgear of indoor and outdoor types, theirmajor components and safety features
Learning objectives
Indoor and outdoor switchgear
Comparison
Metal enclosed switchgear basics
Major components
Safety features
Protection
Switchgear ratings Typical switchgear example
7.1 Switchgear options
7.1.1 Definition of Switchgear
Assembly which houses the equipment used for isolation, switching or control of electrical circuits
7.1.2 Meaning of medium voltage in this text
All voltages above 1000V AC are classified as High Voltage (HV). Medium voltage (MV) is a sub-class of HV and is generally used for representing Voltages above 1000V and up to and including
36000V.
7.1.3 Varieties of MV switchgear
Medium voltage switchgear is available in the following types of executions based on the location
where the switchgear is installed:
Indoor type
Outdoor type
Whichever method of installation is adopted, the design and construction of the switchgear must
take into account the following: Safety of personnel (those concerned with operation and maintenance and where the
switchgear is placed in areas open to public, any person who can gain access to the
equipment)
-
8/2/2019 Dee Module 4.3 All
3/15
104 Switchgear and Distribution Systems104
Ease of operation
Adequate clearances for maintenance
Access to internal components of the switchgear
Protection against external influences
7.2 Outdoor MV switchgearOutdoor switchgear is mostly of open type construction, with the switchgear and associated
equipment mounted on specially designed structures. The clearances of live parts to ground must
be out of arms-reachof persons standing close to the equipment and adequate to prevent arcing
or electrocution. (This translates to the minimum phase-to-ground clearance for the voltage
concerned + 2.5 meters in the vertical plane). Most utility distribution equipment placed along
public roads is designed using this type of construction. This construction is also adopted in
switchyards where the entire distribution equipment such as busbars, isolators, circuit breakers,
power transformers, current/voltage transformers etc. are placed on structures and interconnected
using bare conductors and connector hardware. A typical MV circuit breaker of outdoor
construction is shown in Figure 7.1.
Figure 7.1An outdoor circuit breaker with its mounting structure
The circuit breaker interrupter is placed within a housing made of porcelain and the operating
mechanism and auxiliary components are within the control unit in a sheet steel enclosure just
below the circuit breaker. This enclosure must be of weatherproof construction and protectedagainst ingress of rain water and dust. The advantages of this construction are:
Easier to locate and repair faults
Lower capital cost
However, there are several drawbacks in this design, these being:
Equipment are exposed to weather
More prone to ingress of water and dust and associated problems
Exposure to lightning strike (can be prevented by proper shielding)
Higher/more frequent need for maintenance
Unauthorized access and danger of electrocution
Must be designed to withstand seismic activity where applicable (because of elevatedmounting)
-
8/2/2019 Dee Module 4.3 All
4/15
Medium Voltage Switchgear105
An alternative to the above method is to place the entire equipment in a weatherproof enclosure and
with some form of access protection such as fencing. In addition, the internal parts of the
switchgear can be accessed only by the use of a special purpose key or handle thus preventing the
chances of unsafe condition even if some unauthorized person were to enter the fenced area. A
typical switchgear cubicle designed for outdoor use is shown in Figure 7.2.
Figure 7.2An outdoor vacuum circuit breaker within a metal enclosure
Note that even though the equipment is within an enclosure, the terminals are accessible so as to
facilitate connection of overhead connections to other outdoor equipment.
This type of construction avoids the drawbacks of the open execution discussed earlier. The
advantages are: Well protected against weather action and dust
Better safety against accidental contact
Not exposed to direct lightning strike because of grounded metal enclosure
Easier access for maintenance
There are however certain drawbacks in this construction too such as:
Higher capital cost
Will require additional protection against unauthorized access (fencing)
Higher degree of protection against dust and water ingress
The advantages however far outweigh the drawbacks and situations where a greater degree of
continuity of power is desired, this option offers a good choice.
7.3 Indoor MV switchgear
The practice of using outdoor switchgear and in particular open type design is generally limited to
utility distribution circuits. In certain specific industrial applications such as EHV switchyards,
open type HV switchgear design is adopted. Also, in large yards such as raw material open storage
facilities where most equipment is of outdoor type MV distribution equipment of outdoor metal
enclosed design is preferred. Otherwise, indoor switchgear is the norm in most cases, since
industrial distribution schemes require absolute continuity of power supply.
Indoor switchgear come in two types: the metal-enclosed and metal clad varieties. Metal clad type
is a subset of metal enclosed type. In both types, external earthed metal enclosure is a must. Inmetal clad type, there must be segregation of specified internal parts by earthed metal barriers (for
example, control compartments, busbar chamber, and cable chambers must have earthed metal
-
8/2/2019 Dee Module 4.3 All
5/15
106 Switchgear and Distribution Systems106
barriers between them). In the case of metal enclosed design, the barriers may be of insulating
material. For example, IEC standard provides for metal enclosed switchgear to have non-metallic
barriers and such switchgear is referred to as metal enclosed, compartmentalized switchgear.
The important components of metal clad/metal enclosed switchgear are:
Outer enclosure and internal barriers
Power circuit components
Bus bars
Switching element (CB or Isolator) or MV fuses
Cable chamber
CT and PT
Auxiliary devices, power supply and wiring
Earthing arrangement
Figure 7.3 shows an example of metal enclosed type switchgear. The different chambers have
barriers of insulating sheet, thus fulfilling the need for compartmentalization. The entire panel is
provided with sheet steel enclosure which will be connected to the plant earthing system for
protection from environmental influence, access prevention and safety against accidental contact.
Figure 7.3An indoor metal enclosed switchgear panel
Figure 7.4 shows a vacuum circuit breaker panel of metal clad type. The arrangement is of 2-tier
construction. Barriers between circuit breaker and other chambers are made of metal. A step-down
control supply transformer and a potential transformer form a part of the switchgear. Busbars run in
separate chambers and are supported with insulating barriers between each panel.
-
8/2/2019 Dee Module 4.3 All
6/15
Medium Voltage Switchgear107
Figure 7.4An indoor metal clad vacuum circuit breaker panel
Figures 7.5 and 7.6 show the internals of the panel illustrated earlier in Figure 7.4. The 2-tier
arrangement of circuit breakers is clearly visible in Figure 7.5. The breakers are of horizontal draw
out type and can slide out of the panel on horizontal retractable support rails. The busbar chamber
runs in the central portion of the cubicle and the circuit breakers slide into the module and connect
to the busbars. The lower sliding contact of the top tier and the upper sliding contact of the bottom
tier provide connection to the bus bars. The outgoing cables get connected through the upper
sliding contact of the top tier and the lower sliding contact of the bottom tier. These sliding contacts
are insulated by bushings fixed to the metal barrier between the breaker chamber and the bus/cable
chambers. Current transformers can be seen in Figure 7.6 from the front with the breaker removed.
Figure 7.5An indoor metal clad vacuum circuit breaker panel shown with side covers open
A self-retracting metal shutter provides safety against accidental contact and can be locked in the
closed position (refer to Figure 7.6) when work has to be carried out in the panel. The breaker can
-
8/2/2019 Dee Module 4.3 All
7/15
108 Switchgear and Distribution Systems108
be racked-in and out of the panel without opening the panel door by a mechanism in the front of the
panel. This mechanism is linked to the shutter opening mechanism and thus provides safety while
opening the panel for removal of the circuit breaker. An earth bus is provided in the panel and earth
connection to the circuit breaker assembly is obtained by means of a scraping earth contact. The
earth bus of all the panels are interconnected and earthed to the facilitys protective earth conductor
system. In many designs, an earth switch is also provided and enables the outgoing cable terminals
to be connected to the ground thus ensuring safety.
Figure 7.6Internal view of vacuum circuit breaker module (with breaker drawn out)
Control schemes on the breaker trolley connect to the panel control circuit by sliding control
contacts. In most panels, there are three distinct positions of the circuit breaker assembly:
SERVICE position where power sliding contacts and control sliding contacts makecontact (between panel and breaker trolley)
Breaker DRAWN OUT position where both sets of contacts do NOT make contact.
TEST position where only control sliding contacts make contact.
Thus, in the TEST position, it is possible to operate the breaker without the power circuit getting
energized.
Several safety interlocks (mechanical in most cases) are also provided to ensure that O&M
personnel are not exposed to unsafe conditions. A few of these are:
Panel door cannot be opened when the breaker is in SERVICE position
The breaker cannot be racked in/out when it is on
If racking out a breaker which is on, it will trip before the power sliding contactsseparate.
If the earth switch is on, then breaker cannot be racked in.
There may be other specific interlocks depending on the constructional features of the panel.
-
8/2/2019 Dee Module 4.3 All
8/15
Medium Voltage Switchgear109
7.4 MV switchgear panel configurations
Switchgear panels may be of different configurations. Sectionalized panels have busbars arranged
in more than one section and connected through a bus coupler circuit-breaker. Double busbar
configurations are also possible with a breaker circuit capable of being connected to either busbar
through a set of isolators. Ring main units (RMU) are often adopted where ring/mesh type
distribution is used. A typical ring main circuit has two isolators which connect the RMU to the
ring and a circuit breaker for feeding the load. In some cases, the circuit breaker may be substitutedwith a fused isolator with the fuse providing short circuit protection. Some of the RMUs may have
more than one outgoing feeder and some may connect to radial take-off connections and to
diagonal mesh arms and thus incorporate more than two isolators. A typical RMU is shown in
Figure 7.7. Facilities for padlocking are also provided for the purpose of safety during operation.
Figure 7.7
A typical RMU
Some of the RMU designs use SF6 gas as the insulation medium. Normally insulation between live
components and to earth is by air (air-insulated switchgear). Use of SF6 as insulation medium
provides many advantages. These being: Compactness (lower clearances due to better dielectric strength of SF6)
Switchgear sealed hermetically and not affected by external environment
Reliable performance with no possibility of faults due to external objects, vermin etc.
Such a unit incorporating vacuum interrupters is shown in Figure 7.8.
-
8/2/2019 Dee Module 4.3 All
9/15
110 Switchgear and Distribution Systems110
Figure 7.8SF6 insulated RMU with door open
7.5 MV switchgear auxiliary devices
Commonly used auxiliary devices in MV switchgear include the following:
Auxiliary AC and DC power supply and wiring
Control terminal blocks
Control and protection elements
Measuring elements (CT and PT) secondary circuits
Utility elements (panel lightning, anti-condensation heater and utility socket andpanel ventilation where applicable)
Protection elements
Auxiliary DC supply is for the purpose of control of the switchgear. Protection circuits require DC
battery source or some form of stored energy supply. Trip coils are usually of dc so that failsafe
tripping is possible even though the voltage in the associated power circuit may drop to a very low
value during a short circuit fault. Auxiliary AC supply is normally required for spring charging
motors of circuit breakers and for supply to the panel utilities such as socket outlet, panel lamp,
space heater, etc.
Internal wiring of the panel is done through control wiring ducts and in some of the designs, a
control bus arrangement is provided at the top of the panel to provide through connection. Such
buses are provided for auxiliary dc and ac power supply, PT secondary wiring and other special
purpose connections such as common trip signals. Clearly segregated control terminal blocks are
provided in each panel for intra-panel and external wire connections. The segregation is on the
basis of the control functions for which the terminals are used. The terminals for different purposes
may be sized suitably based on the circuit current likely to be handled. CT wiring terminals are
usually provided with special shorting-type terminals which can be used to short CT terminals
before devices such as meters and relays are disconnected from the CT secondary circuit.
Any switchgear deploys several control elements for its operation. Some of them are:o Command switch/pushbuttons for operation of switchgear
o Other operation selectors (Remote/Local etc.)o Auxiliary contacts of switching deviceo Protection relays/releases
-
8/2/2019 Dee Module 4.3 All
10/15
Medium Voltage Switchgear111
o Status indicating lampso Annunciation devices (visual, audio)
In some of the installations one or more of these devices can be placed external to the switchgear in
a separate control panel.
Measuring elements in the form of current transformers and potential transformers are provided as
a part of the switchgear panels. Other associated devices include: All secondary wiring from PT/CT
Protection of PT output (breaker/fuse)
PT fuse failure detecting device
Indicating instruments, recorders, transducers, switches for selective measurement (ofa given phase).
Switchgear and the outgoing feeders fed by it require various protection devices for safe
disconnection in the event of short circuits, earth faults and other abnormal operating conditions.
These include:
Relays for sensing faults in individual circuits
Protection for other internal (busbar) faults Inter-trip (sending and receiving ends)
Protection of equipment fed by a circuit (motor or transformer)
We will deal with protection in detail in a later chapter.
7.6 MV switchgear ratings
Manufactured Medium Voltage (MV) switchgear panels are rated according to the following main
specifications:
7.6.1 Nominal voltageThis designed average voltage of a system, e.g. 11kV.The actual voltage will typically fluctuate
between 10.5 and 11.5kV (95 to 105%).
7.6.2 Rated voltage
This is the voltage level at which the equipment will be expected to perform at continuously under
normal operating conditions, e.g. 12 kV for a system with a nominal voltage of 11kV.
The rated voltage will determine the insulation properties of the panel. Each main component,
including individual circuit-breakers, busbars, cable terminations, etc, must be rated to this voltage,
or higher. (Main components refer to those components that form part of the main voltage circuit
of the panel, as opposed to the control circuit.) For example, if a 7.2 kV circuit-breaker is installedin a 12 kV panel, it will mean that the whole panel is rated only 7.2 kV.
The normal practice is to rate switchgear panels 10 % higher than the required nominal voltage,
e.g. 12 kV for a 11 kV system, 36 kV for a 33 kV system, etc.
7.6.3 Power frequency withstand voltage
This is the 50 or 60 Hz voltage that the switchgear can with stand for 1 minute. For 12kV, related
equipment the applied test voltage is 28kV. Switchgear manufacturers use this test to prove the
insulation of their equipment after manufacture in routine testing.
Commissioning engineers also use this test to prove the integrity of the equipment before switchingon the power. This test is also known as a pressure test.
-
8/2/2019 Dee Module 4.3 All
11/15
112 Switchgear and Distribution Systems112
7.6.4 Impulse voltage
This is the highest peak voltage the equipment will be able to withstand for a very short period of
time, as in the case of a voltage peak associated with lightning, switching or other transients, e.g.
95 kV for 12Kv equipment.
BIL standards are set by IEC 60.
The same principle as above applies, i.e. the impulse voltage rating of the panel is equal to the
rating of the lowest rated main component.
The impulse level that a panel will experience may be controlled by installing surge suppressers,
which will limit the peak voltage to a certain level. This is illustrated in Figure 7.9.
In limiting the peak voltage, e.g. 45 kV, the surge arrestor will conduct a large current, say 10 kA
to earth.
Figure 7.9Impulse voltage
7.6.5 Surge arrestor
Surge arrestors are installed at the transition point between e.g., an overhead line and a transformer,
and as close to the transformer terminals as possible.
Surge arrestors are also installed as motor terminals and on the ends of overhead lines. They are
unusually connected between phases and earth.
Three types of surge arrestors are used:
Rod spark gapped
Multiple gapped arrestors
Zinc (metal) oxide surge arrestors
In applying surge arrestors the voltage rating, lighting density and the surge rating should beconsidered in determining the insulation coordination of the power system.
7.6.6 Full load current
This is the maximum load current that may pass continuously through the switchgear panel.
Contrary to the voltage rating, not every main component needs to have the same current rating.
Every individual circuit breaker or switch will be rated according to the maximum load current that
will pass through it.
The incoming circuit-breaker/disconnector and the main busbars will usually be rated the same.
This value is obtained by adding all the individual feeder ratings, multiplied by a load or diversity
factor. This factor is smaller than one, and is determined by the types of loads connected to thepanel. Individual loads will not run at full capacity simultaneously, hence the load factor. This
calculation can be illustrated as shown in Table 7.1.
-
8/2/2019 Dee Module 4.3 All
12/15
Medium Voltage Switchgear113
Table 7.1Evaluation of switchgear current rating
Feeder No. Current Rating (A)
1 200
2 100
3 3504 600
5 150
6 250
Total 1650
Load factor 60%
Required Incomer/Busbars 990A
A good estimate of the load factor can be done by looking at the historical values recorded for the
relevant feeders, if available.
Due to economy of scale, MV circuit-breakers/disconnectors are manufactured in a few standardsizes, for example 630 A, 1250 A, 1600 A, 2000 A and 2500 A according to IEC standards.
7.6.7 Fault current
The magnitude of fault current that a switchgear panel must withstand is not determined by the load
connected to it, but by the properties of the supply to it. Usually, a MV panel will be supplied via a
HV/MV transformer(s). This transformer will then determine the magnitude of the fault currents
that may flow through the panel.
Electrical faults usually occur due to breakdown of the insulating media between live conductors or
between a live conductor and earth. This breakdown may be caused by any one or more of several
factors, e.g. mechanical damage, overheating, voltage surges (caused by lightning or switching),ingress of a conducting medium, ionisation of air, deterioration of the insulating media due to an
unfriendly environment or old age, or misuse of equipment.
Faults are classified into two major groups: symmetrical and unbalanced (asymmetrical).
Symmetrical faults involve all three phases and cause severe fault currents and system
disturbances. Unbalanced faults include phase-to-phase, phase-to-ground, and phase-to-phase-to-
ground faults. They are not as severe as symmetrical faults because not all three phases are
involved. The least severe fault condition is a single phase-to-ground fault with the transformer
neutral earthed through a resistor or reactor. However, if not cleared quickly, unbalanced faults will
usually develop into symmetrical faults. These different types of faults are illustrated in Figure
7.10.
In distribution systems with / (HV/mV) connection and the star point solidly earthed the singlephase fault current may be higher than the 3-phase symmetrical fault current due to the zero
sequence reactance of the transformer being lower than the positive sequence reactance.
-
8/2/2019 Dee Module 4.3 All
13/15
114 Switchgear and Distribution Systems114
Figure 7.10Electrical fault types
Switchgear needs to be rated to withstand and break the worst possible fault current, which is a
solid three-phase short-circuit close to the switchgear. Solid means that there is no arc resistance.
Normally arc resistance will be present, but this value is unpredictable, as it will depend on where
exactly the fault occurs, the actual arcing distance, the properties of the insulating medium at that
exact instance (which will be changing all the time due to the heating effect of the arc), etc.
Arc resistance will decrease the fault current flowing.
Exact calculations of prospective fault currents can be quite complex, and are usually performed
with the aid of computer simulation software (see Chapter 5). However, when a few allowable
assumptions are made, approximate fault currents can be determined quite easily and quickly with
pen and paper (plus calculator, preferably!). These approximate values will be conservative, giving
the worst case, and can therefore be confidently used for the ratings of switchgear panels.
These assumptions are the following:
Assume the fault occurs very close to the switchgear. This means that the cableimpedance between the switchgear and the fault may be ignored.
Ignore any arc resistance
Ignore the cable impedance between the transformer secondary and the switchgear, ifthe transformer is located in the vicinity of the substation. If not, the cable impedance
may reduce the possible fault current quite substantially, and should be included for
economic considerations (a lower rated switchgear panel, at lower cost, may be
installed)
When adding cable impedance, assume the phase angle between the cable impedanceand transformer reactance are zero, hence the values may be added without complex
algebra, and values readily available form cable manufacturers tables may be used
Ignore complex algebra when calculating and using transformer internal impedance
7.6.8 DC offset
The phenomenon called DC Offset should be taken into account when rating circuit breakers.This is illustrated in Figure 7.11. This phenomenon occurs due to the presence of inductive
reactance in the system.
-
8/2/2019 Dee Module 4.3 All
14/15
Medium Voltage Switchgear115
Figure 7.11Illustration of DC offset
The peak current value will depend on the power factor of the system at the time of the fault. This
maximum practical value of this peak current is 2.55 times the RMS fault current, as determined by
the system impedance. This relationship is illustrated in Figure 7.12.
Figure 7.12Asymmetry factor chart
Although the peak currents associated with the DC Offset is of relative short duration, they must be
taken into consideration when rating switchgear panels, as additional mechanical stresses arecaused by the electromagnetic forces associated with these high peak currents.
-
8/2/2019 Dee Module 4.3 All
15/15
116 Switchgear and Distribution Systems116
The rate of decay of the DC Offset, as illustrated in Figure 7.12, is depended on the relationship
L/R of the system. The higher the inductance, the slower the rate of decay. Normally, the DC
Offset will decay to zero within the first 3 to 4 cycles. Therefore, at the instant that the circuit
breaker opens, these peaks have all but disappeared, and it will not be a cause for concern.
However, when a circuit breaker is installed close to high inductive sources, like generators and
large induction motors, the current waveform may still be substantially asymmetrical at the instant
of the circuit breaker opening. This may cause the breaker to interrupt a higher current value than itwas rated for, and the DC Offset may cause an extended arcing period within the breaker. The
resultant thermal energy may be higher than the breaker can withstand, with the result that the
breaker may blow up.
Therefore, for these applications, a specialized generator circuit breaker should be installed, which
is designed to withstand these factors.
The switching device shall be capable of performing at least the following operating functions:
Make and break full-load current
Carry the prospective fault current
Make prospective fault currentIf fitted with protection devices, also break prospective fault current
A manually operated switch need not be capable of breaking the prospective fault current.
A switch which will not make prospective fault current may be approved where satisfactory
interlocking is provided.
Standard fault current ratings for switchgear include:
16 kA
20 kA
25 kA 31.5 kA
40 kA
50 kA
60 kA