SS-DCG3 www.daikinac.com 7/17Supersedes 4/17
DRAFT
6 Ton Packaged Gas/ Electric Units up to 15.5 IEER
80% AFUE
DCG Commercial
■ ContentsNomenclature ........................................ 2Product Specifications ........................... 4Expanded Cooling Data ......................... 7Airflow Data ......................................... 11 Crankcase Heater................................. 12 Electrical Data ...................................... 13Dimensions .......................................... 14Wiring Diagrams ................................. 18 – for Models with DDC Controls .............. 23Accessories .......................................... 32
■ Standard Features• Patented tubular heat exchanger• High-efficiency scroll compressor• High and low-pressure switches• Copper tube / aluminum fin coils• Contactor with lugs• High-capacity, steel-cased filter drier• 24-volt terminal strip• Convertible airflow orientation• Easy to service• Built-in filter rack with standard 2" filters• Bottom utility entry
■ Cabinet Features• Heavy-gauge, galvanized-steel cabinet
with UV-resistant powder-paint finish• Full Perimeter Rail• Sloped drain pan
• Complies with California Low NOx emissions standards• Single speed blower motor units meet the performance
specified in Table 6.8.1A of ASHRAE Standard 90.1-2010• AHRI Certified; ETL Listed• Two-speed blower motor, TXV and two-stage
compressor meet the performance specified as of 1/1/2016 in Table 6.8.1-1 of ASHRAE Standard 90.1-2013
* Complete warranty details available from your local distributor or manufacturer’s representative or at www.daikincomfort.com.
Cooling Capacity: Up to 71,000 BTU/hHeating Input: 138,000 BTU/h
2 www.daikinac.com SS-DCG3
Nomenclature
D C G 060 090 3 B * * * A *1 2 3 4,5,6 7,8,9 10 11 12 13 14 15 16
Revision LevelsMajor & Minor
Brand Factory-Installed OptionsD Daikin X No Options
A Non-powered convenience outletConfiguration B Powered convenience outletC Standard Efficiency (6 - 25 Tons) C Low-ambient kitS Standard Efficiency (3 - 5 Tons) D Return air smoke detectorT High Efficiency (3 - 5 Tons) E Supply air smoke detector
F Non-powered convenience outlet; Application Low-ambient kitC Cooling1 G Non-powered convenience outlet; G Gas Heat Return air smoke detectorH Heat Pump1 H Non-powered convenience outlet;
Supply air smoke detectorNominal Cooling Capacity J Non-powered convenience outlet;036 3 Tons 102 8½ Tons 300 25 Tons Return & Supply air smoke detectors048 4 Tons 120 10 Tons K Non-powered convenience outlet;060 5 Tons 150 12½ tons Low-ambient kit; Supply air smoke detector072 6 Tons 180 15 Tons L Non-powered convenience outlet; 090 7½ Tons 240 20 Tons Low-ambient kit
Return & Supply air smoke detectorsNominal Heating Capacity M Powered convenience outlet;
Gas/Electric A/C H/P Factory-Installed Electric Heat Low-ambient kit045 45,000 BTU/h XXX No Heat N Powered convenience outlet;070 70,000 BTU/h 010 10 kW 030 30 kW Return air smoke detector090 90,000 BTU/h 015 15 kW 031 30 kW O Powered convenience outlet;115 115,000 BTU/h 016 15 kW 045 45 kW Return & Supply air smoke detectors140 140,000 BTU/h 018 18 kW 046 45 kW P Powered convenience outlet;210 210,000 BTU/h 020 20 kW 060 60 kW Supply air smoke detector350 350,000 BTU/h 025 25 kW Q Powered convenience outlet; Low-ambient400 400,000 BTU/h kit; Return air smoke detector
See product specifications for heat size(s) available for each capacity. R Powered convenience outlet; Low-ambientVoltage kit; Supply air smoke detector1 208-230/1/60 4 460/3/60 T Powered convenience outlet; Low-ambient3 208-230/3/60 7 575/3/60 kit; Return & Supply air smoke detectors
U Non-powered convenience outlet;Supply Fan/Drive Type/Motor Low-ambient kit; Return air smoke detectorB Belt Drive (single speed) V Two-Speed Belt Drive (also designates 6-Ton V Low-ambient kit; Return air smoke detectorD Direct Drive (3-5 Tons) with two-stage compressor) W Low-ambient kit; Supply air smoke detector
H High Static (single-speed Belt Drive models only) Y Low-ambient kit; Return & SupplyFactory-Installed Options air smoke detectorsA Ultra Low-Leak Downflow Economizer R Ultra Low-Leak Downflow Economizer; Z Return & Supply air smoke detectorsB DDC-BACnet protocol DDC-BACnet protocol; F Ultra Low-Leak Downflow Economizer; Disconnect Switch (non-fused)
DDC-BACnet protocol V Low-Leak Downflow Economizer Factory-Installed OptionsH Disconnect Switch (non-fused) W Low-Leak Downflow Economizer X Standard Aluminized Heat ExchangerJ Ultra Low-Leak Downflow Economizer; Disconnect Switch (non-fused) S Stainless-Steel Heat Exchanger
Disconnect Switch (non-fused) X No Options D Hinged PanelsM Disconnect Switch (non-fused); DDC-BACnet protocol K Stainless-Steel Heat Exchanger;
Hinged PanelsNote: Not all options available for all products. B Phase Monitor
1X= No Options in character 13th J Stainless Steel Heat Exchanger; Phase MonitorM Hinged Panel; Phase MonitorL Stainless-Steel Heat Exchanger;
Hinged Panels; Phase Monitor
SS-DCG3 www.daikinac.com 3
Factory-Installed Options• Stainless-Steel Heat Exchanger (Gas only units): A tubular heat exchanger made of 409-type stainless steel is installed in the unit.• Low-Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3- to 6-ton units, cooling operation is extended
from 60°F ambient temperature to 35°F outside air temperature. On 7½ -20 ton units, cooling operation is extended from 35°F ambient temperature to 0°F outside air temperature. For 25 ton units, cooling operation is extended from 24°F ambient temperature to 0°F outside air temperature.
• Economizers (Downflow): Based on air conditions, can provide outside air to cool the space.• Electric Heat Kits (heat pump and cooling units only): Available in all voltage options.• Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs
power to the outlet.• Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit. When a factory-installed powered
convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.
• Disconnect Switch (non-fused; 3-phase units only): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the unit. Please note that for air conditioning and heat pump models, the appropriate electric heat kit must be ordered to be factory-installed along with the disconnect switch (non-fused) when it is ordered. Please note that for models with a powered con-venience outlet option and a disconnect switch (non-fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-fused) is in the off position.
• Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.• Hinged Access Panels: Allows access to unit’s major components. Combined with latches for easy access to control box, compressor,
filters and blower motor. Available on all units.• Two-speed indoor fan blower models are available on 6, 7½, 8½, 10, 12½, 15, 20 & 25 ton units. Section 6.4.3.10.b of ASHRAE Standard
90.1-2010 and Section 6.5.3.2.1.a of ASHRAE Standard 90.1-2013 require a minimum of two fan speeds. Section 140.4(m)1 of California Energy Commission Title 24 2013 contains a similar provision. When the units with the two-speed indoor fan blowers operate on a call for the first stage of cooling, the fan operates at low speed, which is 66% of full speed. When the units operate on a call for the second stage of cooling, the fan operates at full speed. In heating operation, the fan operates at full speed. During ventilation operation, the fan operates at low speed.
• Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.• Hinged Access Panels: Allows access to unit’s major components. Combined with latches for easy access to control box, compressor,
filters and blower motor. Available on all models.• Phase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series models. Phase monitor shall provide protection
for motors and compressors against problems caused by phase loss, phase reversal and phase unbalance. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.
• DDC Controller: DDC communicating controller, available for 3 - 25 ton DS, DC and DT series models with on-board BACnet® communication interface.
4 www.daikinac.com SS-DCG3
Product Specifications — 6 Tons
DCG0720903V***A*
DCG0720904V***A*
DCG0720907V***A*
Cooling CapacityTotal BTU/h 69,000 69,000 69,000
Sensible BTU/h 51,000 51,000 51,000
EER / IEER 11.2/15.5 11.2/15.5 11.2/15.5
Decibels 78 78 78
AHRI Number 8952850 8952850 8952850
Heating CapacityHigh Input / Output KBTU/h 92 / 73.6 92 / 73.6 92 / 73.6
Low Input/ Output KBTU/h 69 / 55 69 / 55 69 / 55
Steady State Efficiency 80 80 80
Temperature Rise Range (°F) 20-50 / 5-35 20-50 / 5-35 20-50 / 5-35
No. of Burners 4 4 4
Evaporator Motor / CoilMotor Type 2-speed Belt Drive 2-speed Belt Drive 2-speed Belt Drive
# of Wheels (D x W) 1 (11" x 10") 1 (11" x 10") 1 (11" x 10")
Indoor Nominal CFM 2,350 2,350 2,350
Indoor Motor FLA (Cooling) 6.0 2.9 2.4
Horsepower - RPM 2.0-1,725 2.0-1,725 2.0-1,725
Piston Size (Cooling) TXV TXV TXV
Filter Size (Qty) (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"
Drain Size (NPT) ¾" ¾" ¾"
R-410A Refrigerant Charge (oz.) 146.0 146.0 146.0
Evaporator Coil Face Area (ft²) 8.9 8.9 8.9
Rows Deep/ Fins per Inch 4/16 4/16 4/16
Motor Sheave VL44 X 7/8 VL44 X 7/8 VL44 X 7/8
Blower Sheave AK59 X 1 AK59 X 1 AK59 X 1
Condenser Fan / CoilQuantity of Condenser Fan Motors 1 1 1
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter/ # Fan Blades 22/ 4 22/ 4 22/ 4
Outdoor Nominal CFM 4,200 4,200 4,200
Face Area (ft²) 19 19 19
Rows Deep/ Fins per Inch 2/27 2/27 2/27
CompressorQuantity / Stage 1 / Two 1 / Two 1 / Two
Type Scroll Scroll Scroll
Compressor RLA / LRA 17.6/136 8.5/66.1 6.3/55.3
Electrical DataVoltage/ Phase/ Frequency 208-230/ 3/ 60 460/ 3/ 60 575/ 3/ 60
Outdoor Fan FLA 2.0 0.85 0.67
Total Unit Amps 25.6 12.3 9.4
Min. Circuit Ampacity¹ 30.0 14.3 11.0
Max. Overcurrent Protection² 45.0 20.0 15.0
Entrance Power Supply 1.125" 1.125" 1.125"
Entrance Control Voltage ½" ½" ½"
Operating Weight (lbs) 680 680 680Ship Weight (lbs) 695 695 695
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.² May use fuses or HACR-type circuit breakers of the same size as noted.Notes• Always check the S&R plate for electrical data on the unit being installed. • When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by
7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.
SS-DCG3 www.daikinac.com 5
Product Specifications — 6 Tons (cont.)
DCG0721153V***A*
DCG0721154V***A*
DCG0721157V***A*
Cooling CapacityTotal BTU/h 69,000 69,000 69,000
Sensible BTU/h 51,000 51,000 51,000
EER / IEER 11.2/15.5 11.2/15.5 11.2/15.5
Decibels 78 78 78
AHRI Number 8952850 8952850 8952850
Heating CapacityHigh Input / Output KBTU/h 115 / 92 115 / 92 115 / 92
Low Input/ Output KBTU/h 86 / 69 86 / 69 86 / 69
Steady State Efficiency 80 80 80
Temperature Rise Range (°F) 25-55 / 10-40 25-55 / 10-40 25-55 / 10-40
No. of Burners 5 5 5
Evaporator Motor / CoilMotor Type 2-speed Belt Drive 2-speed Belt Drive 2-speed Belt Drive
# of Wheels (D x W) 1 (11" x 10") 1 (11" x 10") 1 (11" x 10")
Indoor Nominal CFM 2,350 2,350 2,350
Indoor Motor FLA (Cooling) 6.0 2.9 2.4
Horsepower - RPM 2.0-1,725 2.0-1,725 2.0-1,725
Piston Size (Cooling) TXV TXV TXV
Filter Size (Qty) (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"
Drain Size (NPT) ¾" ¾" ¾"
R-410A Refrigerant Charge (oz.) 146.0 146.0 146.0
Evaporator Coil Face Area (ft²) 8.9 8.9 8.9
Rows Deep/ Fins per Inch 4/16 4/16 4/16
Motor Sheave VL44 X 7/8 VL44 X 7/8 VL44 X 7/8
Blower Sheave AK59 X 1 AK59 X 1 AK59 X 1
Condenser Fan / CoilQuantity of Condenser Fan Motors 1 1 1
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter/ # Fan Blades 22/ 4 22/ 4 22/ 4
Outdoor Nominal CFM 4,200 4,200 4,200
Face Area (ft²) 19 19 19
Rows Deep/ Fins per Inch 2/27 2/27 2/27
CompressorQuantity / Stage 1 / Two 1 / Two 1 / Two
Type Scroll Scroll Scroll
Compressor RLA / LRA 17.6/136 8.5/66.1 6.3/55.3
Electrical DataVoltage/ Phase/ Frequency 208-230/ 3/ 60 460/ 3/ 60 575/ 3/ 60
Outdoor Fan FLA 2.0 0.85 0.67
Total Unit Amps 25.6 12.3 9.4
Min. Circuit Ampacity¹ 30.0 14.3 11.0
Max. Overcurrent Protection² 45.0 20.0 15.0
Entrance Power Supply 1.125" 1.125" 1.125"
Entrance Control Voltage ½" ½" ½"
Operating Weight (lbs) 685 685 685Ship Weight (lbs) 700 700 700
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.² May use fuses or HACR-type circuit breakers of the same size as noted.Notes• Always check the S&R plate for electrical data on the unit being installed. • When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by
7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.
6 www.daikinac.com SS-DCG3
Product Specifications — 6 Tons (cont.)
DCG0721403B***A*
DCG0721403V***A*
DCG0721404B***A*
DCG0721404V***A*
DCG0721407B***A*
DCG0721407V***A*
Cooling CapacityTotal BTU/h 71,000 69,000 71,000 69,000 71,000 69,000
Sensible BTU/h 49,800 51,000 49,800 51,000 49,800 51,000
EER / IEER 11.0 / 11.2 11.2/15.5 11.0 / 11.2 11.2/15.5 11.0 / 11.2 11.2/15.5
Decibels 78 78 78 78 78 78
AHRI Number 6345695 8952850 6345695 8952850 6345695 8952850
Heating CapacityHigh Input / Output KBTU/h 138 / 110.4 138 / 110.4 138 / 110.4 138 / 110.4 138 / 110.4 138 / 110.4
Low Input/ Output KBTU/h 103 / 83 103 / 83 103 / 83 103 / 83 103 / 83 103 / 83
Steady State Efficiency 80 80 80 80 80 80
Temperature Rise Range (°F) 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45
No. of Burners 6 6 6 6 6 6
Evaporator Motor / CoilMotor Type Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive
# of Wheels (D x W) 1 (11" x 10") 1 (11" x 10") 1 (11" x 10") 1 (11" x 10") 1 (11" x 10") 1 (11" x 10")
Indoor Nominal CFM 2,350 2,350 2,350 2,350 2,350 2,350
Indoor Motor FLA (Cooling) 5.0 6.0 2.5 2.9 2.3 2.4
Horsepower - RPM 1.5-1,725 2.0-1,725 1.5-1,725 2.0-1,725 1.5-1,725 2.0-1,725
Piston Size (Cooling) 0.094 TXV 0.094 TXV 0.094 TXV
Filter Size (Qty) (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
R-410A Refrigerant Charge (oz.) 146.0 146.0 146.0 146.0 146.0 146.0
Evaporator Coil Face Area (ft²) 8.9 8.9 8.9 8.9 8.9 8.9
Rows Deep/ Fins per Inch 4/ 16 4/ 16 4/ 16 4/ 16 4/ 16 4/ 16
Motor Sheave VL44 X 7/8 VL44 X 7/8 VL44 X 7/8 VL44 X 7/8 VL44 X 7/8 VL44 X 7/8
Blower Sheave AK59 X 1 AK59 X 1 AK59 X 1 AK59 X 1 AK59 X 1 AK59 X 1
Belt AX53 AX53 AX53 AX53 AX53 AX53
Condenser Fan / CoilQuantity of Condenser Fan Motors 1 1 1 1 1 1
Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075
Fan Diameter/ # Fan Blades 22/ 4 22/ 4 22/ 4 22/ 4 22/ 4 22/ 4
Outdoor Nominal CFM 4,200 4,200 4,200 4,200 4,200 4,200
Face Area (ft²) 19 19 19 19 19 19
Rows Deep/ Fins per Inch 2/ 27 2/ 27 2/ 27 2/ 27 2/ 27 2/ 27
CompressorQuantity / Stage 1 / Single 1 / Two 1 / Single 1 / Two 1 / Single 1 / Two
Type Scroll Scroll Scroll Scroll Scroll Scroll
Compressor RLA / LRA 19/ 123 17.6/136 9.7/ 62 8.5/66.1 7.4/ 50 6.3/55.3
Electrical DataVoltage/ Phase/ Frequency 208-230/ 3/ 60 208-230/ 3/ 60 460/ 3/ 60 460/ 3/ 60 575/ 3/ 60 575/ 3/ 60
Outdoor Fan FLA 1.90 2.00 1.20 0.90 0.90 0.70
Total Unit Amps 25.9 25.6 13.4 12.3 10.6 9.4
Min. Circuit Ampacity¹ 31 30 16 14.4 12 11.0
Max. Overcurrent Protection² 45 45 25 20 15 15
Entrance Power Supply 1.125" 1.125" 1.125" 1.125" 1.125" 1.125"
Entrance Control Voltage ½" ½" ½" ½" ½" ½"
Operating Weight (lbs) 690 690 690 690 690 690Ship Weight (lbs) 715 715 715 715 715 715
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.² May use fuses or HACR-type circuit breakers of the same size as noted.Notes• Always check the S&R plate for electrical data on the unit being installed. • When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units, increase by
3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.
SS-DCG3 www.daikinac.com 7
Expanded Cooling Data — 6 Tons Single Speed
Out
door
Am
bien
t Te
mpe
ratu
re65
7585
9510
511
5En
teri
ng In
door
Wet
Bul
b Te
mpe
ratu
reID
BAi
rflo
w59
6367
7159
6367
7159
6367
7159
6367
7159
6367
7159
6367
71
70
2650
MBh
69.6
72.1
79.0
-68
.070
.477
.2-
66.3
68.8
75.3
-64
.767
.173
.5-
61.5
63.7
69.8
-57
.059
.064
.7-
S/T
0.75
0.63
0.44
-0.
780.
650.
45-
0.80
0.67
0.46
-0.
830.
690.
48-
0.86
0.72
0.50
-0.
860.
720.
50-
∆T18
1612
-18
1612
-18
1612
-19
1612
-18
1612
-17
1511
-
kW5.
105.
205.
35-
5.47
5.58
5.75
-5.
795.
916.
09-
6.08
6.21
6.40
-6.
326.
466.
66-
6.53
6.67
6.89
-
HI P
R23
525
326
7-
263
283
299
-29
932
234
0-
341
367
388
-38
441
343
6-
424
456
482
-LO
PR
108
115
125
-11
412
113
2-
118
126
137
-12
413
214
4-
130
138
151
-13
514
315
6-
2350
MBh
67.5
70.0
76.7
-66
.068
.474
.9-
64.4
66.8
73.1
-62
.865
.171
.4-
59.7
61.9
67.8
-55
.357
.362
.8-
S/T
0.72
0.60
0.42
-0.
740.
620.
43-
0.76
0.64
0.44
-0.
790.
660.
46-
0.82
0.68
0.47
-0.
820.
690.
48-
∆T19
1612
-19
1713
-19
1713
-19
1713
-19
1713
-18
1512
-
kW5.
065.
165.
31-
5.43
5.54
5.70
-5.
755.
876.
05-
6.03
6.16
6.35
-6.
276.
416.
61-
6.48
6.62
6.83
-
HI P
R23
225
026
4-
261
281
296
-29
731
933
7-
338
363
384
-38
040
943
2-
420
452
477
-LO
PR
107
113
124
-11
312
013
1-
117
125
136
-12
313
114
3-
129
137
150
-13
314
215
5-
2050
MBh
62.3
64.6
70.8
-60
.963
.169
.2-
59.4
61.6
67.5
-58
.060
.165
.9-
55.1
57.1
62.6
-51
.052
.958
.0-
S/T
0.69
0.58
0.40
-0.
720.
600.
42-
0.74
0.61
0.43
-0.
760.
630.
44-
0.79
0.66
0.46
-0.
800.
660.
46-
∆T19
1713
-20
1713
-20
1713
-20
1713
-19
1713
-18
1612
-
kW4.
955.
055.
19-
5.30
5.41
5.57
-5.
615.
735.
90-
5.89
6.01
6.20
-6.
126.
256.
45-
6.33
6.46
6.67
-
HI P
R22
524
325
6-
253
272
287
-28
831
032
7-
328
353
372
-36
939
741
9-
407
438
463
-LO
PR
103
110
120
-10
911
612
7-
114
121
132
-11
912
713
9-
125
133
145
-12
913
815
0-
75
2650
MBh
70.8
72.8
78.9
84.6
69.1
71.2
77.0
82.7
67.5
69.5
75.2
80.7
65.8
67.8
73.3
78.7
62.5
64.4
69.7
74.8
57.9
59.6
64.5
69.3
S/T
0.86
0.77
0.58
0.37
0.89
0.79
0.60
0.39
0.91
0.81
0.62
0.40
0.94
0.84
0.64
0.41
0.97
0.87
0.66
0.42
0.98
0.88
0.67
0.43
∆T21
1916
1121
2016
1121
2016
1121
2016
1121
1916
1120
1815
10
kW5.
145.
245.
405.
565.
515.
625.
795.
975.
845.
966.
146.
346.
136.
266.
456.
666.
376.
516.
726.
936.
596.
736.
947.
17
HI P
R23
725
526
928
126
628
630
231
530
332
634
435
934
537
139
240
838
841
744
145
942
846
148
750
8LO
PR
109
116
126
135
115
122
133
142
119
127
139
148
125
133
146
155
131
140
153
163
136
145
158
168
2350
MBh
68.7
70.7
76.6
82.2
67.1
69.1
74.8
80.3
65.5
67.4
73.0
78.3
63.9
65.8
71.2
76.4
60.7
62.5
67.7
72.6
56.2
57.9
62.7
67.3
S/T
0.82
0.73
0.55
0.36
0.85
0.76
0.57
0.37
0.87
0.78
0.59
0.38
0.90
0.80
0.61
0.39
0.93
0.83
0.63
0.40
0.94
0.84
0.63
0.41
∆T22
2017
1122
2017
1222
2017
1222
2117
1222
2017
1221
1916
11
kW5.
105.
205.
365.
525.
475.
585.
755.
935.
795.
916.
106.
296.
086.
216.
406.
616.
326.
466.
666.
886.
546.
686.
897.
11
HI P
R23
525
326
727
826
328
329
931
230
032
234
035
534
136
7.1
388
404
384
413
436
455
424
456
482
503
LO P
R10
811
512
513
311
412
113
214
111
812
613
714
612
413
214
415
413
013
815
116
113
514
315
616
7
2050
MBh
63.4
65.3
70.7
75.8
61.9
63.8
69.0
74.1
60.5
62.2
67.4
72.3
59.0
60.7
65.7
70.5
56.0
57.7
62.4
67.0
51.9
53.4
57.8
62.1
S/T
0.79
0.70
0.53
0.34
0.82
0.73
0.55
0.36
0.84
0.75
0.57
0.36
0.86
0.77
0.58
0.38
0.90
0.80
0.61
0.39
0.90
0.81
0.61
0.39
∆T22
2117
1223
2117
1223
2117
1223
2117
1223
2117
1221
1916
11
kW4.
995.
085.
235.
395.
345.
455.
615.
795.
665.
775.
956.
145.
946.
066.
256.
456.
176.
306.
506.
716.
386.
516.
726.
94
HI P
R22
824
525
927
025
527
529
030
329
131
333
034
433
135
637
639
237
240
142
344
141
144
346
748
8L O
PR
104
111
121
129
110
117
128
136
115
122
133
142
120
128
140
149
126
134
147
156
131
139
152
162
IDB
= En
terin
g In
door
Dry
Bul
b Te
mpe
ratu
reSh
aded
are
a re
flect
s AC
CA (T
VA) R
ating
con
ditio
nskW
= T
otal
sys
tem
pow
erH
igh
and
low
pre
ssur
es a
re m
easu
red
at th
e liq
uid
and
sucti
on s
ervi
ce v
alve
s.Am
ps =
out
door
uni
t am
ps (c
omp.
+fan
)
8 www.daikinac.com SS-DCG3
Expanded Cooling Data — 6 Tons Single Speed (cont.)
Out
door
Am
bien
t Te
mpe
ratu
re65
7585
9510
511
5En
teri
ng In
door
Wet
Bul
b Te
mpe
ratu
reID
BAi
rflo
w59
6367
7159
6367
7159
6367
7159
6367
7159
6367
7159
6367
71
80
2650
MBh
72.0
73.6
78.6
84.0
70.3
71.9
76.8
82.1
68.7
70.2
75.0
80.1
67.0
68.4
73.1
78.2
63.6
65.0
69.5
74.3
58.9
60.2
64.4
68.8
S/T
0.94
0.88
0.72
0.54
1.00
0.91
0.74
0.56
1.00
0.94
0.76
0.57
1.00
0.97
0.79
0.59
1.00
1.00
0.82
0.61
1.00
1.00
0.82
0.62
∆T23
2220
1624
2320
1624
2320
1623
2320
1622
2320
1620
2118
15
kW5.
185.
285.
445.
605.
555.
675.
846.
025.
886.
016.
196.
396.
186.
316.
516.
716.
436.
566.
776.
996.
646.
787.
007.
23
HI P
R23
925
827
228
426
928
930
531
830
632
934
736
234
837
539
641
339
242
144
546
443
346
649
251
3LO
PR
110
117
128
136
116
123
135
144
121
128
140
149
127
135
147
157
133
141
154
164
137
146
160
170
2350
MBh
69.9
71.4
76.3
81.6
68.3
69.8
74.6
79.7
66.7
68.1
72.8
77.8
65.0
66.5
71.0
75.9
61.8
63.1
67.5
72.1
57.2
58.5
62.5
66.8
S/T
0.90
0.84
0.68
0.51
0.93
0.87
0.71
0.53
0.95
0.89
0.73
0.54
0.98
0.92
0.75
0.56
1.00
0.96
0.78
0.58
1.00
0.96
0.78
0.59
∆T24
2320
1625
2421
1725
2421
1725
2421
1724
2421
1622
2219
15
kW5.
145.
245.
405.
565.
515.
625.
795.
975.
845.
966.
146.
346.
136.
266.
456.
666.
386.
516.
726.
936.
596.
736.
947.
17
HI P
R23
725
526
928
126
628
630
231
530
332
634
435
934
537
139
240
838
841
744
145
942
846
148
750
8LO
PR
109
116
126
135
115
122
133
142
119
127
139
148
125
133
146
155
131
140
153
163
136
145
158
168
2050
MBh
64.5
65.9
70.4
75.3
63.0
64.4
68.8
73.6
61.5
62.9
67.2
71.8
60.0
61.3
65.5
70.1
57.0
58.3
62.3
66.6
52.8
54.0
57.7
61.6
S/T
0.86
0.81
0.66
0.49
0.89
0.84
0.68
0.51
0.92
0.86
0.70
0.52
0.95
0.89
0.72
0.54
0.98
0.92
0.75
0.56
0.99
0.93
0.76
0.57
∆T25
2421
1725
2421
1725
2421
1726
2421
1725
2421
1723
2320
16
kW5.
025.
125.
275.
435.
385.
495.
665.
835.
705.
826.
006.
195.
986.
116.
306.
506.
226.
356.
556.
766.
436.
576.
776.
99
HI P
R23
024
726
127
325
827
829
330
629
331
633
434
833
436
038
039
637
640
542
744
641
544
747
249
2LO
PR
106
112
123
130
111
119
129
138
116
123
135
143
122
129
141
151
128
136
148
158
132
140
153
163
85
2650
MBh
73.3
74.7
78.2
83.5
71.6
73.0
76.4
81.5
69.9
71.2
74.6
79.6
68.2
69.5
72.8
77.6
64.7
66.0
69.1
73.7
60.0
61.1
64.0
68.3
S/T
0.98
0.95
0.86
0.7
1.00
0.98
0.89
0.7
1.00
1.00
0.91
0.7
1.00
1.00
0.94
0.8
1.00
1.00
0.98
0.8
1.00
1.00
0.98
0.8
∆T25
2523
2025
2524
2024
2524
2024
2424
2122
2323
2021
2122
18.9
kW5.
215.
325.
485.
65.
595.
715.
886.
15.
936.
056.
246.
46.
236.
366.
566.
86.
486.
626.
837.
06.
696.
847.
067.
3
HI P
R24
226
027
528
6.7
271
292
308
321.
730
933
235
136
5.8
352
378
399
416.
639
542
644
946
8.7
437
470
497
517.
9LO
PR
111
118
129
137.
211
712
513
614
5.0
122
130
141
150.
712
813
614
915
8.3
134
143
156
165.
913
914
816
117
1.6
2350
MBh
71.1
72.5
75.9
81.0
69.5
70.8
74.2
79.1
67.8
69.1
72.4
77.3
66.2
67.5
70.6
75.4
62.9
64.1
67.1
71.6
58.2
59.4
62.2
66.3
S/T
0.94
0.91
0.82
0.7
0.97
0.94
0.85
0.7
1.00
0.96
0.87
0.7
1.00
0.99
0.90
0.7
1.00
1.00
0.93
0.8
1.00
1.00
0.94
0.8
∆T26
2624
2126
2625
2126
2625
2126
2625
2125
2524
2123
2323
19.8
kW5.
185.
285.
445.
65.
555.
675.
846.
05.
886.
016.
196.
46.
186.
316.
516.
76.
436.
566.
777.
06.
646.
787.
007.
2
HI P
R23
925
827
228
3.8
269
289
305
318.
530
632
934
736
2.2
348
375
396
412.
539
242
144
546
4.1
433
466
492
512.
8LO
PR
110
117
128
135.
911
612
313
514
3.6
121
128
140
149.
212
713
514
715
6.7
133
141
154
164.
213
714
616
016
9.9
2050
MBh
65.7
66.9
70.1
74.8
64.1
65.4
68.5
73.0
62.6
63.8
66.8
71.3
61.1
62.3
65.2
69.6
58.0
59.1
61.9
66.1
53.7
54.8
57.4
61.2
S/T
0.91
0.87
0.79
0.6
0.94
0.91
0.82
0.7
0.96
0.93
0.84
0.7
0.99
0.96
0.86
0.7
1.00
0.99
0.90
0.7
1.00
1.00
0.91
0.7
∆T27
2625
2127
2725
2227
2725
2227
2725
2226
2625
2224
2523
20.2
kW5.
065.
165.
315.
55.
425.
535.
705.
95.
755.
876.
056.
26.
036.
166.
356.
66.
276.
416.
616.
86.
486.
626.
837.
1
HI P
R23
225
026
427
5.3
261
280
296
308.
929
631
933
735
1.3
338
363
384
400.
138
040
943
245
0.2
420
452
477
497.
4L O
PR
107
113
124
131.
811
312
013
113
9.3
117
124
136
144.
712
313
114
315
2.0
129
137
150
159.
313
314
215
516
4.8
IDB
= En
terin
g In
door
Dry
Bul
b Te
mpe
ratu
reSh
aded
are
a re
flect
s AH
RI R
ating
con
ditio
nskW
= T
otal
sys
tem
pow
erH
igh
and
low
pre
ssur
es a
re m
easu
red
at th
e liq
uid
and
sucti
on s
ervi
ce v
alve
s.Am
ps =
out
door
uni
t am
ps (c
omp.
+fan
)
SS-DCG3 www.daikinac.com 9
Expanded Cooling Data — 6 Tons (2 Speed)
Out
door
Am
bien
t Te
mpe
ratu
re65
7585
9510
511
5En
teri
ng In
door
Wet
Bul
b Te
mpe
ratu
reID
BAi
rflo
w59
6367
7159
6367
7159
6367
7159
6367
7159
6367
7159
6367
71
70
2525
MBh
67.6
70.1
76.8
-66
.068
.575
.0-
64.5
66.8
73.2
-62
.965
.271
.4-
59.8
61.9
67.9
-55
.357
.462
.9-
S/T
0.72
0.60
0.42
-0.
750.
630.
43-
0.77
0.64
0.44
-0.
790.
660.
46-
0.82
0.69
0.48
-0.
830.
690.
48-
Del
ta T
1815
12-
1816
12-
1816
12-
1816
12-
1816
12-
1714
11-
KW4.
894.
985.
13-
5.23
5.34
5.50
-5.
545.
655.
82-
5.81
5.93
6.11
-6.
046.
166.
36-
6.24
6.37
6.57
-
HI P
R23
124
826
2-
259
279
294
-29
431
733
5-
335
361
381
-37
740
642
9-
417
449
474
-LO
PR
110
117
128
-11
612
413
5-
121
129
140
-12
713
514
7-
133
142
155
-13
814
616
0-
2250
MBh
65.6
68.0
74.5
-64
.166
.572
.8-
62.6
64.9
71.1
-61
.163
.369
.3-
58.0
60.1
65.9
-53
.755
.761
.0-
S/T
0.69
0.58
0.40
-0.
710.
600.
41-
0.73
0.61
0.42
-0.
760.
630.
44-
0.79
0.66
0.45
-0.
790.
660.
46-
Del
ta T
1916
12-
1916
12-
1916
12-
1916
12-
1916
12-
1715
11-
KW4.
854.
955.
09-
5.19
5.30
5.46
-5.
505.
615.
78-
5.76
5.88
6.06
-5.
996.
126.
31-
6.19
6.32
6.51
-H
I PR
228
246
260
-25
627
629
1-
292
314
331
-33
235
737
7-
374
402
424
-41
344
446
9-
LO P
R10
911
612
7-
115
123
134
-12
012
713
9-
126
134
146
-13
214
015
3-
136
145
158
-
1991
MBh
62.4
64.6
70.8
-60
.963
.169
.2-
59.5
61.6
67.5
-58
.060
.165
.9-
55.1
57.1
62.6
-51
.152
.958
.0-
S/T
0.66
0.55
0.38
-0.
680.
570.
40-
0.70
0.59
0.41
`0.
720.
610.
42-
0.75
0.63
0.44
-0.
760.
630.
44-
Del
ta T
1916
12-
1917
13-
1917
13-
1917
13-
1917
13-
1815
12-
KW4.
784.
875.
01-
5.12
5.22
5.37
-5.
415.
525.
69-
5.67
5.79
5.97
-5.
906.
026.
21-
6.09
6.22
6.41
-
HI P
R22
424
125
4-
251
270
285
-28
630
732
5-
325
350
370
-36
639
441
6-
404
435
460
-L O
PR
107
114
124
-11
312
013
1-
117
125
136
-12
313
114
3-
129
137
150
-13
414
215
5-
75
2525
MBh
68.8
70.8
76.6
82.2
67.2
69.1
74.8
80.3
65.6
67.5
73.1
78.4
64.0
65.9
71.3
76.5
60.8
62.6
67.7
72.7
56.3
58.0
62.7
67.3
S/T
0.82
0.74
0.56
0.36
0.85
0.76
0.58
0.37
0.87
0.78
0.59
0.38
0.90
0.81
0.61
0.39
0.94
0.84
0.63
0.41
0.94
0.84
0.64
0.41
Del
ta T
2119
1611
2119
1611
2119
1611
2119
1611
2119
1611
1918
1510
KW4.
925.
025.
175.
325.
275.
385.
545.
715.
585.
705.
876.
055.
855.
986.
166.
356.
096.
216.
416.
616.
296.
426.
626.
83
HI P
R23
325
126
527
626
228
129
731
029
732
033
835
333
936
538
540
238
141
043
345
242
145
347
949
9LO
PR
111
118
129
138
118
125
136
145
122
130
142
151
128
136
149
159
134
143
156
166
139
148
161
172
2250
MBh
66.8
68.7
74.4
79.8
65.2
67.1
72.7
78.0
63.7
65.5
70.9
76.1
62.1
63.9
69.2
74.3
59.0
60.7
65.7
70.6
54.6
56.3
60.9
65.4
S/T
0.78
0.70
0.53
0.34
0.81
0.73
0.55
0.35
0.83
0.75
0.56
0.36
0.86
0.77
0.58
0.37
0.89
0.80
0.60
0.39
0.90
0.81
0.61
0.39
Del
ta T
2120
1611
2220
1611
2220
1611
2220
1611
2220
1611
2019
1510
KW4.
894.
985.
135.
285.
235.
345.
505.
665.
545.
655.
826.
005.
815.
936.
116.
306.
046.
166.
366.
566.
246.
376.
576.
78
HI P
R23
124
826
227
425
927
929
430
729
431
733
534
933
536
138
139
837
740
642
944
741
744
947
449
4LO
PR
110
117
128
136
116
124
135
144
121
129
140
150
127
135
148
157
133
142
155
165
138
146
160
170
1991
MBh
63.4
65.3
70.7
75.9
61.9
63.8
69.0
74.1
60.5
62.3
67.4
72.3
59.0
60.7
65.7
70.6
56.0
57.7
62.5
67.0
51.9
53.5
57.9
62.1
S/T
0.75
0.67
0.51
0.33
0.78
0.70
0.53
0.34
0.80
0.71
0.54
0.35
0.82
0.74
0.56
0.36
0.86
0.76
0.58
0.37
0.86
0.77
0.58
0.38
Del
t a T
2220
1711
2220
1712
2221
1712
2221
1712
2220
1712
2119
1611
KW4.
824.
915.
055.
205.
165.
265.
415.
585.
465.
575.
735.
915.
725.
846.
026.
205.
946.
076.
266.
456.
146.
276.
466.
67
AMPS
10.5
10.8
11.1
11.4
11.3
11.5
11.9
12.3
12.2
12.4
12.8
13.3
12.9
13.2
13.6
14.1
13.7
14.0
14.5
15.0
14.5
14.8
15.3
15.8
HI P
R22
624
325
726
825
427
328
830
128
931
132
834
232
935
437
439
037
039
842
043
840
944
046
448
4LO
PR
108
115
125
133
114
121
132
141
118
126
138
147
124
132
145
154
130
139
151
161
135
144
157
167
IDB
= En
terin
g In
door
Dry
Bul
b Te
mpe
ratu
reLO
PR
Shad
ed a
rea
refle
cts
ACCA
(TVA
) Rati
ng c
ondi
tions
kW =
Tot
al s
yste
m p
ower
Hig
h an
d lo
w p
ress
ures
are
mea
sure
d at
the
liqui
d an
d su
ction
ser
vice
val
ves.
Amps
= o
utdo
or u
nit a
mps
(com
p.+f
an)
10 www.daikinac.com SS-DCG3
Expanded Cooling Data — 6 Tons (2 Speed) (cont.)
Out
door
Am
bien
t Te
mpe
ratu
re65
7585
9510
511
5En
teri
ng In
door
Wet
Bul
b Te
mpe
ratu
reID
BAi
rflo
w59
6367
7159
6367
7159
6367
7159
6367
7159
6367
7159
6367
71
80
2525
MBh
70.0
71.5
76.4
81.7
68.4
69.8
74.6
79.8
66.7
68.2
72.8
77.9
65.1
66.5
71.1
76.0
61.8
63.2
67.5
72.2
57.3
58.5
62.5
66.9
S/T
0.90
0.85
0.69
0.51
0.93
0.88
0.71
0.53
0.96
0.90
0.73
0.55
1.00
0.93
0.75
0.56
1.00
0.96
0.78
0.59
1.00
0.97
0.79
0.59
Del
ta T
2322
1915
2322
1915
2322
1916
2422
2016
2322
1915
2121
1814
KW4.
965.
065.
215.
365.
315.
425.
585.
755.
635.
745.
916.
105.
906.
026.
216.
406.
136.
266.
466.
666.
346.
476.
676.
89
HI P
R23
525
326
827
926
428
430
031
330
032
334
135
634
236
838
940
638
541
443
745
642
545
848
350
4LO
PR
112
120
130
139
119
126
138
147
123
131
143
153
130
138
150
160
136
144
158
168
140
149
163
174
2250
MBh
67.9
69.4
74.2
79.3
66.4
67.8
72.5
77.4
64.8
66.2
70.7
75.6
63.2
64.6
69.0
73.8
60.0
61.4
65.6
70.1
55.6
56.8
60.7
64.9
S/T
0.86
0.81
0.66
0.49
0.89
0.84
0.68
0.51
0.91
0.86
0.70
0.52
0.94
0.88
0.72
0.54
0.98
0.92
0.75
0.56
0.99
0.93
0.75
0.56
Del
ta T
2423
2016
2423
2016
2423
2016
2423
2016
2423
2016
2222
1915
KW4.
925.
025.
175.
325.
275.
385.
545.
715.
585.
705.
876.
055.
855.
986.
166.
356.
096.
216.
416.
616.
296.
426.
626.
83
HI P
R23
325
126
527
626
228
129
731
029
732
033
835
333
936
538
540
238
141
043
345
242
145
347
949
9LO
PR
111
118
129
138
118
125
136
145
122
130
142
151
128
136
149
159
134
143
156
166
139
148
162
172
1991
MBh
64.5
66.0
70.5
75.3
63.0
64.4
68.8
73.6
61.5
62.9
67.2
71.8
60.0
61.4
65.6
70.1
57.0
58.3
62.3
66.6
52.8
54.0
57.7
61.7
S/T
0.82
0.77
0.63
0.47
0.85
0.80
0.65
0.49
0.88
0.82
0.67
0.50
0.90
0.85
0.69
0.52
0.94
0.88
0.72
0.54
0.95
0.89
0.72
0.54
Del
ta T
2524
2016
2524
2117
2524
2117
2524
2117
2524
2116
2322
1915
KW4.
854.
955.
095.
245.
195.
305.
465.
625.
505.
615.
785.
965.
765.
886.
066.
255.
996.
126.
316.
506.
196.
326.
516.
72
HI P
R22
824
626
027
125
627
629
130
429
231
433
134
633
235
737
739
437
440
242
444
341
344
446
948
9LO
PR
109
116
127
135
115
123
134
142
120
127
139
148
126
134
146
156
132
140
153
163
136
145
158
169
85
2525
MBh
71.2
72.6
76.0
81.1
69.5
70.9
74.3
79.2
67.9
69.2
72.5
77.3
66.2
67.5
70.7
75.4
62.9
64.1
67.2
71.7
58.3
59.4
62.2
66.4
S/T
0.95
0.91
0.82
0.67
0.98
0.95
0.85
0.69
1.00
0.97
0.87
0.71
1.00
1.00
0.90
0.73
1.00
1.00
0.94
0.76
1.00
1.00
0.94
0.77
Del
ta T
2524
2320
2524
2320
2524
2320
2425
2320
2323
2320
2122
2119
KW5.
005.
095.
245.
405.
355.
465.
625.
805.
675.
785.
966.
155.
956.
076.
266.
466.
186.
316.
516.
726.
396.
526.
736.
94
HI P
R23
825
627
028
226
728
730
331
630
332
734
536
034
637
239
341
038
941
844
246
143
046
248
850
9LO
PR
113
121
132
140
120
128
139
148
125
133
145
154
131
139
152
162
137
146
159
170
142
151
165
175
2250
MBh
69.1
70.5
73.8
78.7
67.5
68.8
72.1
76.9
65.9
67.2
70.4
75.1
64.3
65.6
68.7
73.2
61.1
62.3
65.2
69.6
56.6
57.7
60.4
64.5
S/T
0.90
0.87
0.79
0.64
0.93
0.90
0.81
0.66
0.96
0.92
0.83
0.68
0.99
0.95
0.86
0.70
1.00
0.99
0.89
0.73
1.00
1.00
0.90
0.73
Del
ta T
2525
2420
2625
2421
2625
2421
2626
2421
2525
2421
2324
2219
KW4.
965.
065.
215.
365.
315.
425.
585.
755.
635.
745.
916.
105.
906.
026.
216.
406.
136.
266.
466.
666.
346.
476.
676.
89
HI P
R23
525
326
827
926
428
430
031
330
032
334
135
634
236
838
940
638
541
443
745
642
545
848
350
4LO
PR
112
120
130
139
119
126
138
147
123
131
143
153
130
138
150
160
136
144
158
168
140
149
163
174
1991
MBh
65.7
66.9
70.1
74.8
64.1
65.4
68.5
73.1
62.6
63.8
66.9
71.3
61.1
62.3
65.2
69.6
58.0
59.2
62.0
66.1
53.8
54.8
57.4
61.2
S/T
0.86
0.83
0.75
0.61
0.89
0.86
0.78
0.63
0.92
0.89
0.80
0.65
0.95
0.91
0.82
0.67
0.98
0.95
0.86
0.69
0.99
0.96
0.86
0.70
Del
t a T
2626
2421
2726
2521
2726
2521
2726
2522
2626
2421
2524
2320
KW4.
894.
985.
135.
285.
235.
345.
505.
665.
545.
655.
826.
005.
815.
936.
116.
306.
046.
166.
366.
566.
246.
376.
576.
78
HI P
R23
124
826
227
325
927
929
430
729
431
733
534
933
536
138
139
737
740
642
944
741
744
947
449
4LO
PR
110
117
128
136
116
124
135
144
121
129
140
150
127
135
147
157
133
142
155
165
138
146
160
170
IDB
= En
terin
g In
door
Dry
Bul
b Te
mpe
ratu
reSh
aded
are
a re
flect
s AH
RI R
ating
con
ditio
nskW
= T
otal
sys
tem
pow
erH
igh
and
low
pre
ssur
es a
re m
easu
red
at th
e liq
uid
and
sucti
on s
ervi
ce v
alve
s.Am
ps =
out
door
uni
t am
ps (c
omp.
+fan
)
SS-DCG3 www.daikinac.com 11
Airflow Data — 6 Tons
DCG072 Standard Belt Drive and Two-Speed Standard Belt Drive At High Speed - Horizontal
ESP (In W.C.)
0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 --- --- --- --- --- --- 2749 1.18 2573 0.96 2402 0.79
0.4 --- --- --- --- 2680 1.22 2544 1.06 2346 0.84 2164 0.68
0.6 --- --- 2655 1.31 2498 1.10 2306 0.92 2094 0.72 1890 0.57
0.8 2703 1.47 2486 1.20 2263 0.97 2076 0.81 --- --- --- ---
1 2515 1.34 2272 1.07 2002 0.83 --- --- --- --- --- ---
1.2 2253 1.16 2028 0.93 --- --- --- --- --- --- --- ---
DCG072 Standard Belt Drive and Two-Speed Standard Belt Drive At High Speed - Down Shot
ESP (In W.C.)
0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 --- --- --- --- 2625 1.18 2486 1.02 2322 0.83 2152 0.68
0.4 2765 1.52 2596 1.28 2476 1.09 2327 0.94 2159 0.75 1938 0.59
0.6 2650 1.43 2452 1.18 2325 1.00 2070 0.80 1898 0.64 --- ---
0.8 2443 1.29 2251 1.06 2068 0.86 1868 0.71 --- --- --- ---
1 2258 1.17 2040 0.94 1806 0.73 --- --- --- --- --- ---
1.2 2021 1.02 --- --- --- --- --- --- --- --- --- ---
High Static Belt Drive — Horizontal
ESP (In W.C.)
0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 --- --- --- --- --- --- --- --- 2677 1.29 2486 1.07
0.8 --- --- --- --- --- --- 2690 1.42 2529 1.20 2263 0.94
1 --- --- --- --- 2740 1.60 2471 1.27 2246 1.02 1972 0.79
1.2 --- --- 2748 1.74 2518 1.44 2255 1.13 1970 0.87 --- ---
1.4 2797 1.87 2562 1.59 2273 1.27 2025 0.99 --- --- --- ---
1.6 2556 1.67 2314 1.40 2035 1.11 --- --- --- --- --- ---
1.8 2342 1.50 2037 1.21 --- --- --- --- --- --- --- ---
2 2137 1.35 --- --- --- --- --- --- --- --- --- ---
High Static Belt Drive — Down Shot
ESP (In W.C.)
0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 --- --- --- --- 2793 1.64 2575 1.37 2407 1.15 2250 0.96
0.8 --- --- 2775 1.76 2638 1.53 2407 1.25 2226 1.04 2011 0.84
1 2821 1.89 2660 1.67 2407 1.36 2194 1.12 2012 0.92 --- ---
1.2 2696 1.79 2497 1.54 2228 1.23 1977 0.98 --- --- --- ---
1.4 2455 1.59 2236 1.35 2013 1.10 --- --- --- --- --- ---
1.6 2262 1.44 2032 1.20 --- --- --- --- --- --- --- ---
1.8 2069 1.30 --- --- --- --- --- --- --- --- --- ---
Note: Tables represent dry coil without filter; to compensate for filter, add 0.08" to measured E.S.P.
Air Flow Pressure Drop of Down Flow Economizer
Airflow Pressure Drop of Downflow Economizer for 3 to 6 Ton Rofftop Units (100% Return Air)
SCF, 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
in WG 0.02 0.04 0.05 0.07 0.09 0.12 0.14 0.17 0.21 0.24 0.28
12 www.daikinac.com SS-DCG3
Crankcase Heater Selection TableZP/ZPS… Compressor Diameter Compressor Voltage Crankcase
Heater Watts230V 460V 575V16-31 5.5" 0163R00002S 0163R00031S 0163R00032S 40
39-83 6.58/7.3" 0130L00017S 0130L00018S 0130L00019S 70
103-137 9.14” 0130L00020S 0130L00021S 0130L00022S 90
DC*,DT* & DS* Tonnage Compressor Voltage Crankcase Heater Watts230V 460V 575V
3 Ton 0163R00002S 0163R00031S 0163R00032S 40
4 Ton-12.5 Ton 0130L00017S 0130L00018S 0130L00019S 70
15-20 Ton** 0130L00017S 0130L00018S 0130L00019S 70
25 Ton 0130L00020S 0130L00021S 0130L00022S 90
*Includes C,G&H models. **If Compressor Diameter is 9.14” then use 25 Ton Crankcase heaters.
0.00
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
0 700600500400300200100
Air Velocity (FPM)
Resi
stan
ce (i
n. w
.g.)
2" Deep
Flanders Pre Pleat M13Air Velocity vs Resistance
(Test Size: 24" x 24" x 2" High Capacity)
Tonnage: Filter Nominal Size: Part Number: Order QTY:
3 24 x 24 x 2 0160L00203 1
4 14 x 20 x 2 0160L00204 4
5, 6, 7.5 16 x 20 x 2 0160L00205 4
7.5(HP), 8.5, 10 16 X 24 X 2 0160L00206 4
12.5 20 x 25 x 2 0160L00202 4
15, 20 20 x 25 x 2 0160L00202 6
25 20 X 20 X 2 0160L00201 8
High Efficiency MERV 13 Air Filter Option
Crankcase Heater, High Efficiency MERV 13 Air Filter Option
SS-DCG3 www.daikinac.com 13
Electrical Data - 6 ton
Model Number Electrical Rating
Compressor Circuit 1 Compressor Circuit 2 Outdoor Fan Motor Indoor Fan Motor Optional Powered Convienience Outlet Power Supply
RLA LRA RLA LRA QTY HP FLA Type HP FLA FLA MCA MOP
DCG072XXX3B 208/230-3-60 19.0 123.0 1 0.33 2.00Standard - Belt
Drive1.50 4.80
- 30.6 / 30.6 45 / 45
7.2 / 6.5 37.8 / 37.1 50 / 50
DCG072XXX3H 208/230-3-60 19.0 123.0 1 0.33 2.00High Static - Belt
Drive2.00 6.40
- 32.2 / 32.2 50 / 50
7.2 / 6.5 39.4 / 38.7 50 / 50
DCG072XXX3V 208/230-3-60 17.6 136.0 1 0.33 2.00Standard - Belt
Drive (High Speed)
2.00 6.00- 30.0 / 30.0 45 / 45
7.2 / 6.5 37.2 / 36.5 50 / 50
DCG072XXX4B 460-3-60 9.7 62.0 1 0.33 0.85Standard - Belt
Drive1.50 2.40
- 15.4 25
3.3 18.7 25
DCG072XXX4H 460-3-60 9.7 62.0 1 0.33 0.85High Static - Belt
Drive 2.00 3.00
- 16.0 25
3.3 19.3 25
DCG072XXX4V 460-3-60 8.5 66.1 1 0.33 0.85Standard - Belt
Drive (High Speed)
2.00 2.90- 14.3 20
3.3 17.6 25
DCG072XXX7B 575-3-60 7.4 50.0 1 0.33 0.90Standard - Belt
Drive1.50 2.30
- 12.5 15
2.6 15.1 20
DCG072XXX7H 575-3-60 7.4 50.0 1 0.33 0.90High Static - Belt
Drive2.00 2.50
- 12.7 20
2.6 15.3 20
DCG072XXX7V 575-3-60 6.3 55.3 1 0.33 0.90Standard - Belt
Drive (High Speed)
2.00 2.40- 11.2 15
2.6 13.8 20
14 www.daikinac.com SS-DCG3
Dimensions
11.2
65
33.8
05
73.9
4548
.196
6.19
610
.060
12.0
00
7.16
517
.000
31.5
4011
.000
20.8
53
4.47
5
ALL
DIM
EN
SIO
NS
GIV
EN
AR
E IN
INC
HE
SA
LL D
IME
NS
ION
S A
ND
SP
EC
IFIC
AT
ION
S A
RE
SU
BJE
CT
TO
CH
AN
GE
WIT
HO
UT
NO
TIC
E
DC
G07
2***
6 T
ON
CO
MM
ER
CIA
L
GA
S L
INE
EN
TR
AN
CE
CO
MB
US
TIO
N A
IR IN
LET
(G
AS
UN
ITS
)
FLU
E/V
EN
T O
UT
LET
FR
ON
T V
IEW
TO
P V
IEW
FO
RK
HO
LES
BO
TH
SID
ES
A
ND
BO
TH
EN
DS
CO
ND
EN
SA
TE
DR
AIN
OU
TLE
T
LIF
TIN
G S
HA
CK
LE
HO
LES
BO
TH
SID
ES
A
ND
EN
DS
SU
PP
LY A
IR D
UC
T
RE
TU
RN
AIR
DU
CT
RIG
HT
EN
D V
IEW
SS-DCG3 www.daikinac.com 15
Dimensions (cont.)
7.984
"C"
"B"
10.372
5.872
8.55511.000
17.000
6.192
23.442
48.312
20.905
5.104 12.000
19.470
5.558 25.000
74.061
"A"
LINE WIRE ENTRANCE
TSTAT WIRE ENTRANCE
LEFT END VIEW
SUPPLY AIR DUCT
CONDENSATEDRAINBOTTOM EXIT
RETURN AIR DUCT
BASE PAN VIEW(VIEWED FROM TOP)
MODEL TONNAGES "A" "B" "C"3 TON COMMERCIAL
GAS, HT PUMP, AIR CONDITIONER 38.840 16.555 26.055
4 TON COMMERCIALGAS, HT PUMP, AIR CONDITIONER 38.840 16.555 26.055
5 TON COMMERCIALGAS, HT PUMP, AIR CONDITIONER 38.840 16.555 26.055
6 TON COMMERCIALGAS, HT PUMP, AIR CONDITIONER 42.840 20.555 30.055
7.984
30.055
20.555
10.372
5.872
8.55511.000
17.000
6.192
23.442
48.312
20.905
5.104 12.000
19.470
5.558 25.000
74.061
42.840
LINE WIRE ENTRANCE
TSTAT WIRE ENTRANCE
LEFT END VIEW
SUPPLY AIR DUCT
CONDENSATEDRAINBOTTOM EXIT
RETURN AIR DUCT
BASE PAN VIEW(VIEWED FROM TOP)
16 www.daikinac.com SS-DCG3
Unit Clearances
Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for possible compressor removal or service access, and to ensure proper ventilation and condenser airflow. Do not install the unit Beneath any obstruction. Install the unit away from all building exhausts to inhibit ingestion of exhaust air into the unit’s fresh-air intake.
Electrical Entrance Locations
30¼”
12⅜”
Low-Voltage Entrance
(Remove Plug)High-Voltage Entrance
3½” Dia.
47½”7½”
Power Thru the Curb
Low-Voltage Entrance
Corner & Center-of-Gravity Locations
30”
Compressor
Return
Evaporator Coil
Supply
CondenserCoil
37”
Unit Weights
6-Ton Weights
Corner Weight (A) 130
Corner Weight (B) 215
Corner Weight (C) 130
Corner Weight (D) 215
Unit Shipping Weight 715
Unit Operating Weight 690
Note: Weights are calculated without accessories installed.
SS-DCG3 www.daikinac.com 17
Roof Curb Installation — Rigging
Provisions for forks have been included in the unit base frame. No other fork locations are approved.
• Unit must be lifted by the four lifting holes located at the base frame corners.
• Lifting cables should be attached to the unit with shackles.
• The distance between the crane hook and the top of the unit must not be less than 60”.
• Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are in-tended to protect unit base frame from fork lift damage. To remove the struts, ex-tract the sheet metal retainers and pull the struts through the base of the unit. Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-work should be attached to the curb prior to installing the unit. Duct-work dimensions are shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower than the supply air end.
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care to center the unit. Check for proper alignment and orientation of supply and return openings with duct.
To assist in determining rigging requirements, unit weights are shown below.
Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors Association.Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is responsible for field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory package.• Determine sufficient structural support before locating and mounting the curb and package unit.• Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb before mounting
the package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered-type curbs are not available from the factory.
• Contractor furnishes curb insulation, cant strips, flashing, and general roofing material.• Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot penetrate supply
and return duct openings.Note: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct installation after unit placement is not recommended.See the manual shipped with the roof curb for assembly and installation instructions.
3-D View
14 x 20Supply Opening
31⅝ x 14Return Opening
70¾ 40¼
14
15⁄6
¾
14
1⅜
Insulated Panels
Top View
18 www.daikinac.com SS-DCG3
Wiring Diagram — DCG 6 Tons (230V, Three-Phase, Belt Drive)
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
INSTALLER/SERVICEMAN
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
FALSE FLAME SENSED
OPEN LIMIT SWITCHWITHOUT INDUCER ON
PRESSURE SWITCH CLOSED
PRESSURE SWITCH
NORMAL OPERATION
3 BLINKS
6 BLINKS
4 BLINKS
5 BLINKS
OUTPUT DELAYCOMPRESSOR
OFF
ON
1 BLINK
2 BLINKS
STATUS LIGHT
OPEN AUX. LIMIT
IGNITION FAILURE
OPEN ROLLOUT
SWITCH
OPEN
SWITCH
NO POWER ORINTERNAL CONTROL
EQUIP. STATUS
CHECK
ANTI-CYCLE TIMER
MAIN LIMIT OPEN
STICKING GAS VALVEBAD SWITCH
3 MIN. COMP.
PRESSURE SWITCH
GAS PRESSURE
FLAME ROLLOUT
AUX. LIMIT OPEN
FLAME SENSOR
BAD SWITCH
GAS VALVE
REPLACE CONTROLGAS FLOW
PRESSURE SWITCHCHECK
CHECK FUSE ON CONTROLCHECK INPUT POWER
-
CHECK
TRANSFORMERTR
ALS
COMP
COMPONENT LEGEND
COMPRESSOR
EM
IICIGN
GNDFS
GV
C
F FUSEFC
EVAPORATOR MOTOR
FLAME SENSOREQUIPMENT GROUND
IGNITOR
GAS VALVE
CONTACTOR
FAN CAPACITOR
RSTB1
PLFPS
VMVMR
ROLLOUT SWITCHTERMINAL BLOCK (24V SIGNAL)
PRESSURE SWITCH
VENT MOTORVENT MOTOR RELAY
LIMIT SWITCHLS
CONDENSER MOTORCM
INTEGRATED IGNITION CONTROL
FEMALE PLUG/CONNECTOR
AUXILIARY LIMIT SWITCH
IBR INDOOR BLOWER RELAY
GND
T3
RD
L3
POWER SUPPLY
YL
BK
208-240/3/60
YL
IIC
T1 T2BKPU
YL
BK
RD
CL1 L2BL
BL
RD RD
BK
T3 T2 T1
PU
COMP
CM
BR BK
RD
RDLS
WH
GR
1079 12
8 11
ECON
BLPU
RDRD
13
26
54
WH
L1BR
FS
YL
RDDI
BL
RDYL
YL
GR
YL
PU
YLPU
PS
541
2
NOTE 2PLF
63
YL
RS
ALS
GR
HEATCOOLUNUSED
BL
BL L2
BL
YL
MV
MV
PU
PU W. R.GAS VALVE
GV
BR
BL
(ALT.) HONEYWELLGAS VALVE
GV
GR
OR
RD
BK
OR
EM
WH
VMR
BL
24VTR
BLBL
1240
2 3C
BK
OR
RD
OR
BL
GR
BC BLOWER CONTACTOR
SEENOTE 3
BC
FS
IGN
BK
VM
OR
RD
L2 L3
C
L2
L3
CMT3
C
FC
208-240/3/60
T2
T3
T2T1
T1 COMP
L1
CL1
SUPPLY VOLTAGE
3VMR
BCIIC
VMR
FSIGN
NOTE 3L2
C
RSGV
3
6
PLF2
5
NOTE 2
1
EM
LS
H CD1
FSF
5
4
L1NOTE 3
ALS
PS
10ECON
3
6
8
12
11
9
IIC
7
TR
FCRDBR
1
4
208-240/3/60 0140L05401-A
LPS HPS
LPS LOW PRESSURE SWITCH
HPS HIGH PRESSURE SWITCH
RD
T2T3
T1
C
BC
BK
BC
BC
208
L3L2
L1
YL
HPS
LPS
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
USE NEC CLASS 2 WIRE.
2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY).
NOTES
PK
SMOKE/FIREDETECTORREPLACESJUMPER WIRE
BR
LOW VOLTAGE
LINE VOLTAGE
FIELD WIRING
LOW VOLTAGE OPTIONAL HIGH VOLTAGE
FACTORY WIRING
HIGH VOLTAGE
BL
RDY1
YL
W
BL
GR
W
NO ECONOMIZER
G
YL
RD
Y2
Y1
PK
WH
W
R RD
WHGR
C
RYL
GR
Y1
GWH
WITH ECONOMIZER OPTION
C
GR
THERMOSTATFIELD WIRING
BL
C
2 STAGE COOLING
TB1
GR
W
Y
C
TB1
TB1
Y
W
RG
C
W
Y2
GR
C
Y1
STAT
STAT
STAT
YL/PK
BL/PK
BL/PK BLUE WITH PINK STRIPYL/PK YELLOW WITH PINK STRIP
GR GREEN
WIRE CODE
BL BLUE
PU PURPLEPK PINK
WH WHITE
BK BLACK
RD RED
BR BROWN
OR ORANGE
YL YELLOW
GR
SEE UNIT RATING PLATE FOR TYPE AND SIZEOF OVER CURRENT PROTECTION
4. USE COPPER CONDUCTORS ONLY.
6. FOR LOW STAGE OPERATION ONLY, REMOVE WHITE JUMPER. FOR 2 STAGE OPERATION, REMOVE JUMPER AND CONNECT W2 TO W2 ON THERMOSTAT.
BL
RD
YL
RD
TO THERMOSTAT
GR
BL
PU
WH
BR
SEE NOTE 6
3
1
2
OR
OR
WH
SEE NOTE 4
3 1 VM
BK
BK
BK
5. FOR 208 VOLT TRANSFORMER OPERATION, MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
87
9
BL
9 8 7
GR Y2Y1 CGR W1 Y1 CW2S1 S2
TO THERMOSTATTERMINAL BLOCK
Y2Y1S1S2 RC W1 GW2
WH
PUPK
RD
GR
Y2
Y2
SS-DCG3 www.daikinac.com 19
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
Wiring Diagram — DCG 6 Ton (460V/ 575V, Three-Phase, Belt Drive)
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.
USE NEC CLASS 2 WIRE.4. USE COPPER CONDUCTORS ONLY.
2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY).
INSTALLER/SERVICEMAN
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO
FALSE FLAMESENSED
OPEN LIMIT SWITCHWITHOUT INDUCER ONPRESSURE SWITCH CLOSED
PRESSURE SWITCH
NORMAL OPERATION
INTERNAL CONTROL
3 BLINKS
6 BLINKS
4 BLINKS5 BLINKS
OUTPUT DELAYCOMPRESSOR
OFF
ON
1 BLINK
2 BLINKS
STATUS LIGHT
OPEN AUX. LIMIT
IGNITION FAILUREOPEN ROLLOUT
SWITCH
OPEN
SWITCH
NO POWER OR
EQUIP. STATUS
CHECK
ANTI-CYCLE TIMER
MAIN LIMIT OPEN
STICKING GAS VALVEBAD SWITCH
3 MIN. COMP.
PRESSURE SWITCH
GAS PRESSURE
FLAME ROLLOUT
AUX. LIMIT OPEN
FLAME SENSOR
BAD SWITCH
GAS VALVE
REPLACE CONTROLGAS FLOW
PRESSURE SWITCHCHECK
CHECK FUSE ON CONTROLCHECK INPUT POWER
-CHECK
NOTES
TRANSFORMERTR
LOW VOLTAGE
FACTORY WIRING LINE VOLTAGE
LOW VOLTAGE
FIELD WIRING HIGH VOLTAGE
OPTIONAL HIGH VOLTAGE
ALS
COMP
COMPONENT LEGEND
COMPRESSOR
EM
IICIGN
GNDFS
GV
C
F FUSEFC
EVAPORATOR MOTOR
FLAME SENSOREQUIPMENT GROUND
IGNITOR
GAS VALVE
CONTACTOR
FAN CAPACITOR
RSTB1
PLFPS
VMVMR
ROLLOUT SWITCHTERMINAL BLOCK (24V SIGNAL)
PRESSURE SWITCH
VENT MOTORVENT MOTOR RELAY
LIMIT SWITCHLS
CONDENSER MOTORCM
INTEGRATED IGNITION CONTROL
FEMALE PLUG/CONNECTOR
AUXILLARY LIMIT SWITCH
IBR INDOOR BLOWER RELAY
GND
T3
RD
OR
L3
YL
BK
GR
YL
IIC
T1 T2BKPU
YL
BKRD
CL1 L2BL
BL
RD
ORBK
BK
T3 T2 T1
PU
COMP
CM
BR BK
RD
RDLS
WH
GR
1079 12
8 11
ECON
BLPU
RDRD
RD
13
26
54
WH
L1BR
FSYL
RDDI
BL
YL
YL
BL
YL
PU
YLPUPS
541
2
NOTE 2PLF
63
YL
RS
ALS
GR
HEATCOOLUNUSED
BL
BL L2
BL
YL
MV
MV
PU
PU W. R.GAS VALVE
GV
BL
BL
(ALT.) HONEYWELLGAS VALVE
GV
GR
OR
RD
BK
OR
EM
RD WH
2
1
3
VMR
BL
24VTR
BLBL
1460
2 3C
460/575TR240
BK OR
BC BLOWER CONTACTOR
PUSEENOTE 3
BC
FS
IGN
BK
VM
OR
RD
L2 L3
C
L2
L3
CMT3
C
FC
T2
T3
T2T1
T1 COMP
L1
CL1
13
3
VMR
BC IIC
VMR
FSIGN
NOTE 3L2
C
RSGV
3
6
PLF 2
5
NOTE 2
1
EM
VM
LS
H CD1
FSF
5
4
L1NOTE 3
ALS
PS
10ECON
3
6
8
12
11
9
IIC
7
TR
FCRDBR
1
4
460-575/3/60 0140L05402-A
LPS HPS
LPS LOW PRESSURE SWITCH
HPS HIGH PRESSURE SWITCH
SMOKE/FIRE DETECTORREPLACES JUMPER WIRE
RD
PK
T2T1
T3
C
BC
BK
BC
BC
RD
OR
HPS
LPS
L1L2
L3
ORBK
WH
ORBKRD
OR
BL
RDY1
YL
W
BL
GR
W
NO ECONOMIZER
G
YL
RD
Y2
Y1
PK
WH
W
R RD
WHGR
C
RYL
GR
Y1
GWH
WITH ECONOMIZER OPTION
C
GR
THERMOSTATFIELD WIRING
BL
C
2 STAGE COOLING
TB1
GR
W
Y
C
TB1
TB1
Y
W
RG
C
W
Y2
GR
C
Y1
STAT
STAT
STAT
BL/PK
YL/PK
BL/PK BLUE WITH PINK STRIPYL/PK YELLOW WITH PINK STRIP
GR GREEN
WIRE CODE
BL BLUE
PU PURPLEPK PINK
WH WHITE
BK BLACK
RD RED
BR BROWN
OR ORANGE
YL YELLOW
GR
POWER SUPPLY
SEE NOTE 4
460/3/60575/3/60
575
TO THERMOSTAT
YL BL RDWH
GR
SEENOTE 5
BR
BR
5. FOR LOW STAGE OPERATION ONLY, REMOVE WHITE JUMPER. FOR 2 STAGE OPERATION, REMOVE JUMPER AND CONNECT W2 TO W2 ON THERMOSTAT.
460-575/3/60SUPPLY VOLTAGE
SEE UNIT RATING PLATE FOR TYPE AND SIZEOF OVER CURRENT PROTECTION.
OR
RD
BL
BK
87
9
9 8 7
TO THERMOSTATTERMINAL BLOCK
GR Y1 CGR W1 Y2Y1 CW2S1 S2
Y2Y1S1S2 RC W1 GW2
GR
WH
PU
RD
Y2
Y2
20 www.daikinac.com SS-DCG3
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡
Wiring Diagram — DCG Control Diagram DCG072 - 2 Speed (All Voltages)
BL
PU
BL
BLYL
BLBK
BLBR
YL BL
BL
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).
2 IF OPTIONAL ECONOMIZER IS INSTALLED, REMOVE ECON SHRT PLM AND CONNECT ECON PLM TO ECON PLF.
3 WHEN SPEED-UP PINS ARE SHORTED, THE COMPRESSOR DELAY IS BYPASSED; BYPASS FOR TESTING/TROUBLESHOOTING ONLY
4 CONNECTIONS SHOWN ARE FOR 1-STAGE HEAT OPERATION. WHEN 2-STAGE OPERATION IS REQIRED REMOVE JUMPER WIRE CONNECTING W2 TO W1 ON TB1.
5 IF OPTIONAL SMOKE DETECTOR(S) ARE INSTALLED, REMOVE JUMPER WIRE CONNECTING S1 TO S2 ON TB1. WIRE CONNECTIONS FROM ACCESSORY KIT: CONNECT RD WIRE TO TB1-S1. CONNECT BR WIRE TO TB1-S2. CONNECT BL TO TB1-C (24V COM).
6 IIC FAN OFF-DELAY: - COOL OFF-DELAY IS 60 SECONDS AFTER COOL OR FAN CALL IS REMOVED - HEAT OFF-DELAY IS SELECTABLE, A MOVABLE JUMPER IS PROVIDED; 120, 135, OR 150 SECOND DELAY MAY BE SELECTED. THE FACTORY SETTING IS 150 SEC
CO
NT
RO
LS
DIA
GR
AM
DC
G0
72
2 S
PE
ED
EM
2 S
TA
GE
CO
MP
BL
CC
BC1
BC2
CSPU
PK
AU
X B
AU
X A
8187
YYRB
SE
NS
OR
2
YYRB
SE
N2
PK
OPTIONAL SMOKE DETECTOR
YYRB
24
VA
C/D
C
SE
NS
OR
1
910
YYRB
166
17
SE
N1
RD
BR
BL
5
BL
CRS2S1
RDBK RD
RDCLASS 2
Y1W2 Y2W1G O
YL PUWHGR BR
WH4
FIELDCONTROL WIRING
TR1 SUPPLY (LINE) VOLTAGE
24 VAC
GR
BK BL
5
BKBLBR
RD
GR
HEAT FANCOOL FAN
3A
PS IN
COM
456
123
4
56
1
23
LMT OUTGV
LMT IN
24V
IIC
L1L1
12
987
1110
12
987
1110
R
COMP IN
GPS OUT
W
COMP OUT
YL
WH
YLYL
RD
GR
GR
GR
YL RDYLPU
PU
PU
YL
YL
YL
WH
WH
WH
RD
RD
RD RD
GR
GR
WH
YL
YLYL
YL
GR
RD
RDRD
RD
RD
BL
BLPU
FSD1
L2L2L2L2 BL
BRGY
PU PUALS
PUPU
RS
RD
LSRD
RD
PS
YL
YL
YL
BR
BR
FSVMR
GY
GY
BL
BL
TB1
BR
BR
YL
PU
YL
WH
BLYL1 3
42
5 6
BR2
YLWHPU
GR
YL
RD
YL
GR
YL
RD
YL
BL
BR1
GR
BL
BRBK
BR
BK
YL
BR
1 3
42
5 6
GRBK
YL
BKBR
BK
BR
BL
BR
BL
BR
BL
BL
BL
BL BL
BL BLCOMHIGH
LOW
GV
123
123
PU
PU
GRWH
YL
PU
2
RDECON PLF
ECON SHRTPLM
YL
321
PUPU
4YLBL
765
GR
8WH
9RD
YL
321
4 YL
765
PUPU
89
BL
YL BLYL
WH
PU
YL
RD
BL
PU
BL
BLBL
BL/PK
YL/PK
BL/PK
HP
S
YL/PK
LP
S
YL
MATMAT
IAQ 2-10IAQ COM
IAQ 24V
ACT COMACT 24V
ECON PLM
AUX1-O
OCCAUX2-I
E-GND
EXH1
OPTIONAL ECONOMIZER
OAT
Y2-I
S-BUS
321
4
Y1-IY2-O
Y1-O32
4
1
21
RC
21 6
54321
654321
S-BUS
OAT-t°
MAS
YLYL
PUPU
RD
ORGR
BL
PKPK
MAS
ENTH
WH
WHWH
BR
GRD
24V-PWR24V-COM
4321
S-BUSS-BUS
ECON ACT
BK
BKRD
BLGR
ORRD
PUPU
YL
YL
98
567
4
123
2
SPEED-UP
12
01
35
15
0
P3
3
6
0140L04969-A
SS-DCG3 www.daikinac.com 21
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡
Wiring Diagram — DCG Power Diagram DCG072 - 2 Speed (230v)
RDBK
POWER DIAGRAMDCG072***32 SPEED EM
2 STAGE COMP
5. SEE ACCESSORY KIT LITERATURE FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM.
4 SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
3 208/230V SUPPLY POWER UNITS ARE FACTORY CONNECTED TO THE CONTROL TRANSFORMER 240V TAP. MOVE WIRE CONNECTION FROM 240V TAP TO 208V TAP WHEN 208V POWER SUPPLY IS USED.
2 THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS. ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY). UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT
NOTES:
0140L04973-A
GND
L1 L2 L3
LINE VOLTAGE
BK
RD
RD
RD
PU
BK
RD
OR
BK
RD
BK
YL
FC
BK(12)
BK(13)
BK(11)
BK
OR
RD
BK
RD
BK
OR
RD
OR
BK
RDOR
L1
L2
L3
T1
T2
T3
BC1
BK
BK
WH
OR
WHRD1 3
WH
BK
RD
L1
L2
L3
T1
T2
T3
BC2
RD OR
L1
L2
L3
T1
T2
T3
CC
OR
RD
BK
OR
RD
YL
BKT1
T3
COMPT2
EM
OR
RD
BK
WH
OR
BL
GY
BL
YL
GY
BL
YL
VMR
RD
OR
RD
VM
GR
GR
RD BK
2,3
4
24V CNTLVOLTAGE
LINEVOLTAGE
TR1
IIC DIAGNOSTIC BLINK CODES
-------
ANTI-CYCLE TIMER3 MIN. COMP.
STICKING GAS VALVE
BAD SWITCHMAIN LIMIT OPEN
SWITCHCHECK PRESSURE
SWITCHCHECK PRESSURE
AUX.LIMIT OPENBAD SWITCH
FLAME ROLLOUTFLAME SENSER
GAS VALVEGAS PRESSURE
GAS FLOWREPLACE CONTROL
CHECK FUSE ON CONTROLCHECK INPUT POWER
DELAYCOMPRESSOR OUTPUT
FALSE FLAME SENSED
OPEN LIMIT SWITCH
WITHOUT INDUCER ONPRESSURE SWITCH CLOSED
PRESSURE SWITCH OPEN
OPEN AUX LIMIT SWITCHOPEN ROLLOUT SWITCH
IGNITION FAILURE
INTERNAL CONTROLNO POWER OR
NORMAL OPERATION
6 BLINKS
5 BLINKS
4 BLINKS
3 BLINKS
2 BLINKS
1 BLINK
OFF
ON
CHECKEQUIPMENT STATUSSTATUS LIGHT
LOW VOLTAGE
FIELD WIRING
HIGH VOLTAGE
Y22ND STAGECOOL CALL(OUTPUT)
Y11ST STAGECOOL CALL(OUTPUT)
W22ND STAGEHEAT CALL(OUTPUT)
W11ST STAGEHEAT CALL(OUTPUT)
G
C
R
TB1 CONNECTION
24VAC-PWR(INPUT)
THERMOSTATIN / OUT
24VAC - COM(INPUT)
FAN CALL(OUTPUT)
THERMOSTAT CONNECTIONS
YELLOW/PINK STRIPE
YELLOW
YL/PK
BL/PK
BK
WIRE CODE
BLACKBL BLUEBR BROWNGR GREENGY GRAYOR ORANGEPK PINKPU PURPLERD REDWH WHITEYL
BLUE/PINK STRIPE
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE
HIGH VOLTAGEOPTIONAL
BK
RD
OR
BK
RD
OR
COMPRESSOR 2ND STAGE SOLENOIDCS
TERMINAL BLOCK 3, LOW VOLTAGE
PLUG / CONNECTOR, MALEPLM
ECONOMIZER
EVAPORATOR MOTOR
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PLUG / CONNECTOR, FEMALE
TERMINAL BLOCK 1, LOW VOLTAGE
TRANSFORMER 1, CONTROLS(LINE VOLTAGE / 24VAC)
ECON
EM
HPS
LPS
PLF
TB1
TR1
TB3
INTEGRATED IGNITION CONTROL
IGNITOR
GAS VALVE
IIC
IGN
GV
LIMIT SWITCH
EQUPIMENT GROUND
LS
GND
ROLLOUT SWITCHRS
TRANSFORMER 2, PWR - VENT MOTOR(LINE VOLTAGE / 230VAC)
TR2
VENT MOTOR
IIC 24V POWER FUSEF7
VENT MOTOR RELAYVMR
FLAME SENSORFS
VM
BLOWER CONTACTORBC
BLOWER RELAY
COMPRESSOR CONTACTOR
CONDENSER MOTOR
COMPRESSOR
CC
CM
COMP
COMPONENT LEGEND
CRANK CASE HEATER
BR
CCH
CONDENSER MOTOR CONTACTORCMC
CONDENSER MOTOR RELAYCMR
AUXILLARY LIMIT SWITCHALS
IIC
IGN IGN
6
6 2 SPEED EVAPORATOR MOTOR: BLACK LEADS FOR HIGH SPEED OPERATION, AND WHITE / BLUE / ORANGE LEADS FOR LOW SPEED OPERATION.
PU
CM
PU
BR
BK
PU
BR
BK
GRBR
BK
22 www.daikinac.com SS-DCG3
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡
Wiring Diagram — DCG Power Diagram DCG072 - 2 Speed (460/575v)
RD
BK
POWER DIAGRAMDCG072***(4/7)2 SPEED EM
2 STAGE COMP
4. SEE ACCESSORY KIT LITERATURE FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM.
3 SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
2 THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS. ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY). UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT
NOTES:
0140L04974-B
GND
L1 L2 L3
LINE VOLTAGE
BK
RD
RD
RD
PU
BK
RD
OR
BK
RD
BK
YL
FC
BK(12)
BK(13)
BK(11)
BK
OR
RD
BK
RD
BK
OR
RD
OR
BK
RD
OR
L1
L2
L3
T1
T2
T3
BC1
BK
BK
WH
OR
WHRD1 3
WH
BK
RD
L1
L2
L3
T1
T2
T3
BC2
RD OR
L1
L2
L3
T1
T2
T3
CC
OR
RD
BK
OR
RD
YL
BKT1
T3
COMPT2
EM
BR
OR
RD
BK
WH
OR
BL
GY
BL
YL
GY
BL
YL
VMR
RD
RD
VM
GR
GR
RD BK
2
3
24V CNTLVOLTAGE
LINEVOLTAGE
TR1
IIC DIAGNOSTIC BLINK CODES
-------
ANTI-CYCLE TIMER3 MIN. COMP.
STICKING GAS VALVE
BAD SWITCHMAIN LIMIT OPEN
SWITCHCHECK PRESSURE
SWITCHCHECK PRESSURE
AUX.LIMIT OPENBAD SWITCH
FLAME ROLLOUTFLAME SENSER
GAS VALVEGAS PRESSURE
GAS FLOWREPLACE CONTROL
CHECK FUSE ON CONTROLCHECK INPUT POWER
DELAYCOMPRESSOR OUTPUT
FALSE FLAME SENSED
OPEN LIMIT SWITCH
WITHOUT INDUCER ONPRESSURE SWITCH CLOSED
PRESSURE SWITCH OPEN
OPEN AUX LIMIT SWITCHOPEN ROLLOUT SWITCH
IGNITION FAILURE
INTERNAL CONTROLNO POWER OR
NORMAL OPERATION
6 BLINKS
5 BLINKS
4 BLINKS
3 BLINKS
2 BLINKS
1 BLINK
OFF
ON
CHECKEQUIPMENT STATUSSTATUS LIGHT
LOW VOLTAGE
FIELD WIRING
HIGH VOLTAGE
Y22ND STAGECOOL CALL(OUTPUT)
Y11ST STAGECOOL CALL(OUTPUT)
W22ND STAGEHEAT CALL(OUTPUT)
W11ST STAGEHEAT CALL(OUTPUT)
G
C
R
TB1 CONNECTION
24VAC-PWR(INPUT)
THERMOSTATIN / OUT
24VAC - COM(INPUT)
FAN CALL(OUTPUT)
THERMOSTAT CONNECTIONS
YELLOW/PINK STRIPE
YELLOW
YL/PK
BL/PK
BK
WIRE CODE
BLACKBL BLUEBR BROWNGR GREENGY GRAYOR ORANGEPK PINKPU PURPLERD REDWH WHITEYL
BLUE/PINK STRIPE
FACTORY WIRING
LOW VOLTAGE
HIGH VOLTAGE
HIGH VOLTAGEOPTIONAL
BK
RD
OR
BK
RD
OR
IIC
IGN IGN
OR
RD
TR2 COM230V
460V OR575V
ORBK
RD
RD
BK
RD
BK
RD
OR
OR
OR
COMPRESSOR 2ND STAGE SOLENOIDCS
TERMINAL BLOCK 3, LOW VOLTAGE
PLUG / CONNECTOR, MALEPLM
ECONOMIZER
EVAPORATOR MOTOR
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
PLUG / CONNECTOR, FEMALE
TERMINAL BLOCK 1, LOW VOLTAGE
TRANSFORMER 1, CONTROLS(LINE VOLTAGE / 24VAC)
ECON
EM
HPS
LPS
PLF
TB1
TR1
TB3
INTEGRATED IGNITION CONTROL
IGNITOR
GAS VALVE
IIC
IGN
GV
LIMIT SWITCH
EQUPIMENT GROUND
LS
GND
ROLLOUT SWITCHRS
TRANSFORMER 2, PWR - VENT MOTOR(LINE VOLTAGE / 230VAC)
TR2
VENT MOTOR
IIC 24V POWER FUSEF7
VENT MOTOR RELAYVMR
FLAME SENSORFS
VM
BLOWER CONTACTORBC
BLOWER RELAY
COMPRESSOR CONTACTOR
CONDENSER MOTOR
COMPRESSOR
CC
CM
COMP
COMPONENT LEGEND
CRANK CASE HEATER
BR
CCH
CONDENSER MOTOR CONTACTORCMC
CONDENSER MOTOR RELAYCMR
AUXILLARY LIMIT SWITCHALS
5
5 2 SPEED EVAPORATOR MOTOR: BLACK LEADS FOR HIGH SPEED OPERATION, AND WHITE / BLUE / ORANGE LEADS FOR LOW SPEED OPERATION.
CM
PU
BR
BKGR
PU
BR
BK
SS-DCG3 www.daikinac.com 23
WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLSFor complete information and installation instructions for models
with DDC controls, see manual DK-DDC-TGD-XXX
24 www.daikinac.com SS-DCG3
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
Wiring Diagram with DDC — DCG072140 (208-230V/3/60) B***
412 5
3 6
GN
D
LDS
BPSW
BI1
BI2
BI3
RS
S
AI1
CO2VO
UT
DC
GN
D
24V
AC
CO
M
GN
D
VO
UT
DC
EC
ON
24V
TR1
124
02
3C
208
TR2
12
3
CEM
L3
BK
CO
MP
SMK
/EM
G
PO
WE
R S
UPP
LY20
8-24
0/3/
60SE
E N
OTE
4
CFS
YL/P
KB
L/PK
BKB
R
RD
PK
GR
YL
GR
GR
BL
BC
CC
OARH SPCRH
STPT
OFF
SET
GN
D
TEM
P
SPCTEMP
BL
BL
BL/ PK
DA
T
OA
T
BI4
BI5
BI6
BI7
BI8
AI2
AI3
AI4
AI5 AI6
AI7
AI8 GN
D
AG
ND
24V
AC
AG
ND
GN
DG
ND
CO
M3-
8R
L8 AO
4
CO
M2
AO
3
AO
2
AO
1
CO
M3-
8
RL7
RL6RL5
RL4
RL3
RL2
RL1CO
M1
AG
C
VO
UT
DC
GN
D
BL
WH
WH
WH
WH
+ - + -HG
RH
EXF
GR
ALR
M+ -
RD YL
T3 T2 T1
L2 L1
BL
RD B
K
BL
BL
RD
BK
BK R
D
WH
PK
L3T3 T2 T1
L2 L1 C
YL RD
SEE
NO
TE 4
240
C20
8
24V
RD
24V
T5T4
T3T2
T1
SEE
NO
TE 5
CS
PS
ES
XS
RD
RD
HP
SLP
S
TB1
RD
BK
YL
PU
PU
PK
YLPK
VM
VMR 3 1
2
PS
RS
ALS
MV
MV
PU
W.R
.G
AS
VA
LVE
GV
BL(A
LT.)
HO
NEY
WE
LLG
AS
VA
LVE
GV
FS IGN
SE
E N
OTE
6
IIC
LS
10
7 9
12
8
11
ECO
N
1 32654
L1FS
DIHEAT COOLUNUSED
L2
SE
EN
OTE
3
CM
BR
RC
CF
PU
BK
BK
RD
FC
OR
GR
OR
RD
BK
WH
BK
BK
BK
PK
RD
PU
PU
BR
RD
OR
BL
BL
BL
BL
BL
BLPK
WH
YL
YLYLP
UBL
RD
RD
RD
RD
RD
OR
RD
GR
GR
PU
RD
WH
BR
BKB
L
BL
WH
BR
OR
WH B
L
PU
RD
BK
BL
BL
WH
BL
BK
GR
BK
GR
BR
YL/
PK
YL
GR
TB2
0140
L050
12-A
208-
240/
3/60
OR
OR
DA
PU
RD
PU
WH
RD
BKR
D
BK
24 V
AC
SS-DCG3 www.daikinac.com 25
Wiring Diagram with DDC —DCG072140 (208-230V/3/60) B***
0140
L051
33-A
208-
240/
3/60
BL/
PK
B
LUE
WIT
H P
INK
STR
IP
PK
P
INK
YL/
PK
Y
ELLO
W W
ITH
PIN
K S
TRIP
WIR
E C
OD
ELIN
E V
OLT
AG
E
OP
TIO
NAL
HIG
H V
OLT
AG
E
LOW
VO
LTA
GE
RD
R
EDFAC
TOR
Y W
IRIN
G
LOW
VO
LTA
GE
BL
BLU
EB
K
BLA
CK
NO
TES
:
1. R
EPL
AC
EM
EN
T W
IRE
MU
ST
BE
SA
ME
SIZ
E A
ND
T
YP
E IN
SULA
TIO
N A
S O
RIG
INAL
(AT
LEA
ST
105°
C)
U
SE
CO
PP
ER
CO
ND
UC
TOR
ON
LY.
2. U
SE
CO
PP
ER
CO
ND
UC
TOR
S O
NLY
+
+ U
SE
N.E
.C. C
LAS
S 2
WIR
E3.
EC
ON
OM
IZE
R P
LUG
LO
CA
TED
IN T
HE
RET
UR
N A
IR
CO
MP
AR
TME
NT.
RE
MO
VE
MAL
E P
LUG
AN
D A
TTA
CH
F
EM
ALE
PLU
G T
O T
HE
EC
ON
OM
IZE
R A
CC
ES
SOR
Y.
4. F
OR
208
VO
LT T
RA
NS
FOR
ME
R O
PE
RAT
ION
MO
VE
B
LAC
K W
IRE
FR
OM
TE
RM
INAL
3 T
O T
ER
MIN
AL 2
O
N
TR
AN
SFO
RM
ER
.5.
RE
MO
VE J
UM
PE
R IF
SM
OK
E D
ETE
CTO
R O
R E
MER
GE
NC
Y
SH
UTD
OW
N D
EV
ICE
IS IN
STA
LLE
D.
6. C
RA
NK
CA
SE H
EAT
ER
AN
D C
RAN
KC
ASE
HEA
TER
S
WIT
CH
FA
CTO
RY
EQ
UIP
PE
D W
HE
N R
EQ
UIR
ED
.
OR
O
RA
NG
E
AGN
DAI
LAL
RM
BC BCC
BHS
BIL
BLS
BPSW
C CC
CC
RC
FC
FCC
FSC
HC
HR
CH
SC
MC
OM
CO
MP
CS
DFT
ECO
NE
MES EX
FG
ND
HG
RH
HP S
LDS
LPS
OAT
OAR
HPL
FPS R
CC
FR
LR
SSR
VCSA
T/D
A TSM
K/EM
GSP
CTE
MP
SPC
RH
T1-T
5TB
1-2
TR1-
2XS
DC
GR
OU
ND
FO
R A
NAL
OG
SEN
SOR
S ("
AG" O
N T
B2)
8 AN
ALO
G IN
P UTS
ALAR
MBL
OW
ER C
ON
TAC
TOR
BLO
WER
CO
NTA
CTO
RBL
OW
ER H
I GH
SPE
E D8
BIN
A RY
INP U
TSBL
OW
ER L
OW
SP
EED
BLO
WER
PR
OVI
NG
SW
ITC
HC
ON
TAC
TOR
CO
MPR
ESSO
R C
ON
TAC
TOR
CO
MPR
ESSO
R C
ON
TAC
TOR
REL
AYC
ON
DEN
SOR
FAN
CO
ND
ENSO
R F
A N C
ON
TAC
TOR
CLO
GG
ED
FIL
TER
SW
ITC
HC
RAN
KCA S
E H
EATE
RC
RAN
KCA S
E H
EATE
R R
ELA Y
CR
ANKC
A SE
HEA
TER
SW
ITC
HC
ON
DEN
SER
MO
TOR
CO
MM
ON
("C
" ON
TB
2)C
OM
PR
ESS
OR
CO
M1
AND
SM
OK E
DET
ECTO
RD
EFR
OST
TH
ERM
OST
ATEC
ON
OM
IZE
REV
APO
RAT
OR
MO
TOR
ECO
N C
OM
3 -8
AND
SM
OKE
DET
ECT O
REX
HA U
ST F
A NEQ
UIP
MEN
T G
RO
UN
DH
OT
GAS
REH
EAT
HIG
H P
RE S
SUR
E SW
ITC
HLO
AD S
HE D
DIN
GLO
W P
RES
S UR
E SW
ITC
HO
UTD
OO
R A
I R T
EM
PER
ATU
RE
OU
TDO
OR
AIR
REL
ATIV
E H
UM
IDIT
YFE
MAL
E P
L UG
/ C
ON
NEC
TOR
HPS
, LPS
& S
MO
KE D
ETEC
T OR
RU
N C
APA
CIT
OR
FO
RC
ON
DE N
SER
FAN
REL
AY
RE M
OTE
STA
RT
STO
PR
EVE
RSI
NG
VAL
V E C
OIL
SUPP
L Y /
DIS
CH
ARG
E AI
R T
EMPE
RAT
UR
ESM
OKE
OR
EM
ERG
E NC
Y SH
UTD
OW
NSP
ACE
TEM
PER
ATU
RE
SPAC
E R
ELAT
IVE
HU
MID
ITY
MO
T OR
SP E
ED T
APS
1-5
(DIR
E CT
DR
IVE N
MO
TOR
ON
LY)
TER
MI N
AL B
LOC
K (2
4V S
IGN
AL)
TRA N
SFO
RM
ER
24 V
AC T
RAN
SFO
RM
ER &
SM
OKE
DET
ECTO
RS
EE
UN
IT R
ATIN
G P
LATE
FO
RTY
PE
AN
D S
IZE
OF
OV
ER
CU
RR
EN
T P
RO
TEC
TIO
N
YL
YEL
LOW
GR
G
RE
EN
WH
W
HIT
E
BR
B
RO
WN
CO
MPO
NE
NT
LEG
EN
D
FIEL
D W
IRIN
G
HIG
H V
OLT
AG
E
PU
P
UR
PLE
FIEL
D S
PLIC
E
SW
ITC
H (T
EM
P)
OP
TIO
NAL
LO
W V
OLT
AG
E
SW
ITC
H (P
RE
SS
.)
OV
ER
CU
RR
EN
TP
RO
T. D
EV
ICE
TER
MIN
AL
PLU
G C
ON
NE
CTI
ON
FIEL
D G
RO
UN
D
IGN
ITE
R
JUN
CTI
ON
INTE
RN
AL T
OIN
TEG
RA
TED
CO
NTR
OL
SC
HE
MAT
IC S
YM
BO
L
LDS
RS
S
BPS
W
3
24V
TR
1
BC
C/B
LS
HPS
3
24V
TR
1
LPS
BI1
BI2
BI3 BI5
BI6 BI7
BI8 AI1 AI2 AI4
AI5
AI6 AI7
AI8 AG
ND
OA
TD
AT
OA
RH
431 2
CO
2
SP
CTE
MP
CO
M
SEN
SOR
OFF
SET
SPC
RH
CO
M1
RL1
RL2
CO
M2
CO
M3-
8
AI3
RL3
RL4
RL5
CC
1
RL6 RL7
RL8
24VA
CG
ND
EC
ON
PLF
+ - + - + -HG
RH
EX
F
ALR
M
SMK
/EM
G
AO
1
AO
2
AO
3A
O4
VM
R
FSIGN
NO
TE 3
L2
RS
GV
LS
H
D1
FSF
54L1N
OTE
3
ALS
PS
103 6 8
IIC
D D C
L2
T1C
OM
P
T2
SU
PPL
Y V
OLT
AG
E
CM
EM
L1
CC
T3
BC
208-
240/
3/60
BC
BC
CC
CC
VM
R3
1V
M
BI4
208-
240/
3/60
208-
240/
3/60
SE
E N
OTE
5
RC
CF
FC
CFS
L3
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
26 www.daikinac.com SS-DCG3
Wiring Diagram with DDC — DCG072140 (460V,575V/3/60) B***
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
GN
D
LDS
BI1
BI2
BI3
RS
S
AI1
24V
TR1
157
52
3C
460
TR2
12
3
CE
M
L3
BK
CO
MP
SM
K/E
MG
PO
WE
R S
UP
PLY
460/
575/
3/60
SE
E N
OTE
4
CFS BK
BR
RD
PK
GR
GR
BL
BC
CC
BL
BL
DA
T
OA
T
BI4
BI5
BI6
BI7
BI8
AI2
AI3
AI4
AI5
AI6
AI7
AI8
GN
D
AGN
D
24V
AC
AGN
D
GN
DG
ND
CO
M3-
8R
L8 AO
4
CO
M2
AO
3
AO
2
AO
1
CO
M3-
8
RL7
RL6RL5
RL4
RL3
RL2
RL1CO
M1
AG
CB
L
+ - + -HG
RH
EXF
GR
ALR
M+ -
RD YL
T3 T2 T1
L2 L1
BL
RD B
K
BL
BL
RD BK
BK R
D
WH
PK
L3T3 T2 T1
L2 L1 C
YL RD
SE
E N
OTE
4
575
C46
0 BL
24V
RD
24V
T5T4
T3T2
T1
SE
E N
OTE
5
CS
PS
ES
XS
RD
TB1
RD
BK
PU
PU
PK
YL
PK
VM
VM
R 3 1
2
PS
RS
ALS
MV
MV
PU
W.R
.G
AS
VA
LVE
GV
BL(A
LT.)
HO
NE
YW
ELL
GA
S V
ALV
E
GV
FS IGN
SEE
NO
TE 6
IIC
LS
10
7 9
12
8
11
ECO
N
1 32654
L1FS
DIHEAT COOLUNUSED
L2
SEE
NO
TE 3
OR
GR
OR
RD
BK
WH
BK
BK
PK
RD
PU
PU
BR
RD
OR
BL
BL
BL
BL
BL
BLPK
WH
YL
YL
YL
PUBL
RD
RD
RD
RD
RD
OR
RD
GR
GR
PU
WH
BK
BL
BL
WH
BR
OR
WH B
L
RD
BK
BL
BL
460/
575
TR 240O
RB
KO
RB
K
RD
RD
YL/
PK
BL/
PK
BL/ PK
WH
WH
WH
HP
SLP
SR
D
YL
BK
GR
YL/
PK
YL
BL
GR
CM
BR
RC
CF
PU
BK
BK
RD
FC
PU
BR
GN
D
VO
UT
DC
OARH SPCRH
STP
TO
FFS
ET
GN
D
TEM
P
SPCTEMP VO
UT
DC
GN
D
CO2VO
UT
DC
GN
D24
VA
C
CO
M
0140
L050
13-A
460/
575/
3/60
GR
RD
BP
SW
GR
BK
TB2
DA
PU
PU
WH
412 5
3 6
EC
ON
BK
BR
WH
RD
RD
WH
YL
RD
BK
RD
BK
24 V
AC
SS-DCG3 www.daikinac.com 27
Wiring Diagram with DDC—DCG072140 (460V,575V/3/60) B***
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
0140
L051
34-A
460/
575/
3/60
BL/
PK
B
LUE
WIT
H P
INK
STR
IP
PK
PIN
K
YL/P
K
YELL
OW
WIT
H P
INK
STR
IP
WIR
E C
OD
ELIN
E V
OLT
AG
E
OP
TIO
NA
L H
IGH
VO
LTA
GE
LOW
VO
LTA
GE
RD
R
ED
F AC
TOR
Y W
IRIN
G
LOW
VO
LTA
GE
BL
BLU
EBK
BL
AC
K
NO
TES
:
1. R
EP
LAC
EM
EN
T W
IRE
MU
ST
BE
SAM
E S
IZE
AN
D
TYP
E IN
SU
LATI
ON
AS
OR
IGIN
AL
(AT
LEA
ST 1
05°C
)
US
E C
OP
PE
R C
ON
DU
CTO
R O
NLY
.2.
US
E C
OP
PE
R C
ON
DU
CTO
RS
ON
LY
++
US
E N
.E.C
. CLA
SS 2
WIR
E3.
EC
ON
OM
IZE
R P
LUG
LO
CA
TED
IN T
HE
RE
TUR
N A
IR
CO
MP
AR
TME
NT.
RE
MO
VE
MA
LE P
LUG
AN
D A
TTA
CH
F
EMAL
E P
LUG
TO
TH
E E
CO
NO
MIZ
ER
AC
CE
SSO
RY.
4. F
OR
460
VO
LT T
RA
NS
FOR
ME
R O
PE
RA
TIO
N M
OV
E
BLA
CK
WIR
E F
RO
M T
ER
MIN
AL
3 T
O T
ER
MIN
AL
2
ON
T
RA
NS
FOR
ME
R.
5.R
EM
OV
E J
UM
PER
IF S
MO
KE
DE
TEC
TOR
OR
EM
ER
GE
NC
Y
SH
UTD
OW
N D
EV
ICE
IS IN
STA
LLE
D.
6. C
RA
NK
CA
SE
HE
ATE
R A
ND
CR
AN
KC
AS
E H
EA
TER
S
WIT
CH
FA
CTO
RY
EQ
UIP
PE
D W
HE
N R
EQ
UIR
ED
.
OR
O
RA
NG
E
AG
ND
AIL
ALR
MB
CB
CC
BH
SB
ILB
LSB
PSW
C CC
CC
RC
FC
FCC
FSC
HC
HR
CH
SC
MC
OM
CO
MP
CS
DFT
EC
ON
EM
ES
EXF
GN
DH
GR
HH
PS
LDS
LPS
OA
TO
AR
HP
LFP
SR
CC
FR
LR
SS
RV C
SA
T/D
AT
SM
K/E
MG
SPC
TEM
PS
PCR
HT1
-T5
TB1-
2TR
1-2
XS
DC
GR
OU
ND
FO
R A
NA
L OG
SE N
SOR
S("
AG" O
N T
B2)
8 A
NA
L OG
INP
UTS
ALA
RM
BLO
WER
CO
NTA
CTO
RB
LOW
ER
CO
NTA
CTO
RB
LOW
ER
HIG
H S
PEE
D8
BIN
AR
Y IN
PU
TSB
LOW
ER L
OW
SP
EE
DB
LOW
ER
PR
OVI
NG
SW
ITC
HC
ON
TAC
TOR
CO
MP
RE
SS
OR
CO
NTA
CT O
RC
OM
PR
ES
SO
R C
ON
TAC
T OR
RE
LAY
CO
ND
ENS
OR
FA
NC
ON
DEN
SO
R F
AN
CO
NTA
CTO
RC
LOG
GE
D F
ILTE
R S
WIT
CH
CR
AN
KC
A SE
HE
ATE
RC
RA
NK
CA S
E H
EA
TER
RE
LAY
CR
AN
KC
A SE
HE
ATE
R S
WIT
CH
CO
ND
ENS
ER
MO
TOR
CO
MM
ON
("C
" ON
TB
2)C
OM
PR
ES
SO
RC
OM
1 A
ND
SM
OK
E D
ETE
CTO
RD
EFR
OS
T TH
ER
MO
STA
TE
CO
NO
MIZ
E RE
VAP
OR
ATO
R M
OTO
RE
CO
N C
OM
3-8
AND
SM
OK
E D
ET E
CTO
RE
XHA
US
T FA
NE
QU
IPM
ENT
GR
OU
ND
HO
T G
AS
RE
HE
AT
HIG
H P
RE S
SUR
E S
WIT
CH
LOA
D S
HE
DD
ING
LOW
PR
ESS
UR
E SW
ITC
HO
UTD
OO
R A
IR T
EM
PER
ATU
RE
OU
TDO
OR
AIR
RE
LAT I
VE H
UM
IDIT
YFE
MAL
E P
LUG
/ C
ON
NE
CTO
RH
PS
, LP
S &
SM
OKE
DE
TEC
TOR
RU
N C
AP
ACIT
OR
FO
RC
ON
DEN
SE
R F
AN
RE
LAY
RE
MO
TE S
TAR
T S
TOP
RE
VE
RS
ING
VA
LVE
CO
ILS
UP
PL Y
/ D
ISC
HA
RG
E A
IR T
EM
PER
ATU
RE
SM
OK
E O
R E
ME R
GE
NC
Y S
HU
TDO
WN
SPA
CE
TEM
PER
ATU
RE
SPA
CE
RE
LATI
VE
HU
MID
ITY
MO
TOR
SP
EED
TA
PS
1-5
(DI R
EC
T D
RIV
EN
MO
TOR
ON
LY)
TER
MIN
AL
BLO
CK
(24 V
SIG
NAL
)TR
AN
S FO
RM
E R24
VA
C T
RA
NS F
OR
ME
R &
SM
OK
E D
ET E
CTO
RS
EE
UN
IT R
ATI
NG
PLA
TE F
OR
TYP
E A
ND
SIZ
EO
F O
VE
RC
UR
RE
NT
PR
OTE
CTI
ON
YL
YELL
OW
GR
G
RE
EN
WH
W
HIT
E
BR
B
RO
WN
CO
MP
ON
EN
T LE
GE
ND
FIE
LD W
IRIN
G
HIG
H V
OLT
AG
E
PU
P
UR
PLE
FIE
LD S
PLIC
E
SW
ITC
H (T
EM
P)
OP
TIO
NA
L LO
W V
OLT
AG
E
SW
ITC
H (P
RE
SS
.)
OV
ER
CU
RR
EN
TP
RO
T. D
EV
ICE
TER
MIN
AL
PLU
G C
ON
NE
CTI
ON
FIEL
D G
RO
UN
D
IGN
ITE
R
JUN
CTI
ON
INTE
RN
AL
TOIN
TEG
RA
TED
CO
NTR
OL
SC
HE
MA
TIC
SYM
BO
L
LDS
RS
S
BP
SW
3
24V
TR
2
BC
C/B
LS
HP
S
3
24V
TR
1
LPS
BI1
BI2
BI3 BI5
BI6 BI7
BI8 AI1 AI2 AI4 AI 5
AI6
AI7
AI8 AG
ND
OA
TD
AT
431 2
CO
M1
RL1
RL2
CO
M2
CO
M3-
8
AI3
RL3
RL4
RL5
CC
1
RL6
RL7
RL8
24V
AC
GN
D
EC
ON
PLF
+ - + - + -HG
RH
EX
F
ALR
M
SMK
/EM
G
AO
1
AO
2
AO
3A
O4
VM
R
FSIGN
NO
TE 3
L2
RS
GV
LS
H
D1
FSF
54L1N
OTE
3
ALS
PS
103 6 8
IIC
D D C
L2
T1C
OM
P
T2
SU
PP
LY V
OLT
AG
E
CM
EM
L1
CC
T3
BC
460/
575/
3/60
BC
BC
CC
CC
BI4
460/
575/
3/60
460/
575/
3/60
SEE
NO
TE 5
RC
CF
FC
CFS
L3
VM
R3
1V
M
31
12
OA
RH
CO
2
SP
CTE
MP
CO
M
SE
NS
OR
OFF
SE
T
SP
CR
H
28 www.daikinac.com SS-DCG3
Wiring Diagram with DDC - DCG072140 (208-230/3/60)V***
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
412 5
3 6
GN
D
LDS
BPSW
BI1
BI2
BI3
RSS
AI1
CO2VOUT
DC
GN
D
24VA
C
CO
M
GN
D
VOUT
DC
ECO
N
24V
TR1
124
02
3C
208
TR2
12
3C
EM
L3
BK
COM
P
SMK/
EMG
POW
ER S
UPP
LY20
8-24
0/3/
60SE
E NO
TE 4
CFS
YL/P
KBL
/PK
BKBR
PK
GR
YL
GR
GR
BL
BC1
CC
OARH SPCRH
STPT
OFF
SET
GN
D
TEM
P
SPCTEMP
BL
BL
BL/
PK
DAT
OAT
BI4
BI5
BI6
BI7
BI8
AI2
AI3
AI4
AI5
AI6
AI7
AI8
GN
D
AGND
24VA
C
AGND
GND
GND
COM
3-8
RL8 A
O4
COM
2
AO
3
AO
2 A
O1
COM
3-8
RL7
RL6
RL5
RL4
RL3
RL2
RL1
CO
M1
AGC
VOUT
DC
GN
D
BL
WH
WH
WH
WH
+ - + -HGRH EX
F
GR
ALRM
+ -
RD YL
T3 T2 T1
L2 L1
BL
RD
BK
BLBL RD
BK
BK
RD
WHPK
L3T3 T2 T1
L2 L1
C
YL
RD
SEE
NOTE
4
240
C20
8
24V
RD
24V
T5T4
T3T2
T1
SEE
NOTE
5
CS
PSES
XS
RD
RD
HPS
LPS
TB1
RD
BK
YL
PU
PUPK
YLPK
VMVM
R 3 1
2
PS RS
ALS
MV MV
PU
W.R
.G
AS V
ALVE
GV
BL
(ALT
.) H
ON
EYW
ELL
GAS
VAL
VE
GV
FS IGN
SEE
NOTE
6
IICLS
107 9
12811EC
ON
1 32654
L1FS
DIHEAT COOLUNUSED
L2
SEE
NOTE
3
CM
BR
RCCF
PU B
KBK
RD
FC
GR
OR
RD
BK
WH BK
BK
BK
PK
RD
PU
PU
BR
RD OR
BL
BLBL
BL
BLBLPKWH
YLYLYLPUBLRDRD
RD
OR
RD GR
GR
PU
RD
WH
BRBK
BL
BL
WH
BR
OR
WH
BL
PU
RDBK BL
BL
WH
BL
BK GR
BK
GR
BR
YL/
PKYL
GR
TB2
0140
L066
19-A
208-
240/
3/60
OR
OR
DA
PU
RDPU
WH
RD
BKR
D
BK
24 V
AC
L3L2
L1
PHAS
E M
ONI
TOR
C
BC2
L3T3 T2 T1
L2 L1
PU
OR
BK R
D OR
BL
BL
RD
RD
PUBL
OR
RD
BK
BK
YL
YL
YL
BR
BR
BRPU
RD
PU
YL
GR
GR
GR
GR
BR
WH
GR
BL
WH
WH
WH
BL BL
BL
OR
OR
BR
PK
WH
GR
GR
WH
RD
BL
PK
GR
POW
ER &
CO
NTR
OL
WIR
ING
DIA
GR
AMDC
G 0
72**
*(3)
(V) B
DDC
NO
TES:
1. R
EPLA
CEM
ENT
WIR
E M
UST
BE
SAM
E
SIZ
E AN
D T
YPE
INSU
LATI
ON
AS
OR
IGIN
AL
(AT
LEA
ST 1
05°C
) USE
CO
PPER
C
OND
UCTO
R O
NLY
. 2
. USE
CO
PPER
CO
NDU
CTO
RS
ONL
Y
++
USE
N.E
.C. C
LASS
2 W
IRE.
3. E
CONO
MIZ
ER P
LUG
LO
CAT
ED IN
TH
E
RET
URN
AIR
CO
MPA
RTM
ENT.
REM
OVE
M
ALE
PLUG
AND
ATT
ACH
FEM
ALE
PLUG
T
O T
HE
ECO
NOM
IZER
AC
CES
SORY
. 4
. FO
R 2
08 V
OLT
TR
ANSF
OR
MER
OPE
RAT
ION
,
MO
VE B
LAC
K W
IRE
FRO
M T
ERM
INAL
3
TO
TER
MIN
AL 2
ON
TR
ANSF
ORM
ER.
5. R
EMO
VE J
UMPE
R IF
SM
OKE
D
ETEC
TOR
/EM
ERG
ENCY
SHU
TDO
WN
D
EVIC
E O
R P
HAS
E M
ON
ITO
R IS
INST
ALLE
D.
BK
BL
BL
PU
GY
BL
YL
OR
RD B
K
BK
BK
BK B
L WH
OR
RD
CS
YLG
R
YL
GR
YL
SS-DCG3 www.daikinac.com 29
Wiring Diagram with DDC - DCG072140 (208-230/3/60)V***
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
0140
L066
20-A
208-
240/
3/60
BL/P
K B
LUE
WIT
H P
INK
STR
IP
PK
PIN
K
YL/P
K Y
ELLO
W W
ITH
PIN
K ST
RIP
WIR
E C
OD
ELIN
E VO
LTAG
E
OPT
ION
AL H
IGH
VO
LTAG
E
LOW
VO
LTAG
E
RD
R
EDFAC
TOR
YW
IRIN
G
LOW
VO
LTAG
E
BL
BLU
EBK
BL
ACK
NO
TES :
1. R
EPLA
CEM
ENT
WIR
E M
UST
BE
SAM
E SI
ZE A
ND
TYPE
INSU
LATI
ON
AS
OR
IGIN
AL (A
T LE
AST
105°
C)
USE
CO
PPER
CO
NDU
CTO
R O
NLY
.2.
USE
CO
PPER
CO
NDU
CTO
RS
ON
LY +
+ U
SE N
.E.C
. CLA
SS 2
WIR
E3.
EC
ON
OM
IZER
PLU
G L
OC
ATED
IN T
HE
RET
UR
N A
IR C
OM
PAR
TMEN
T. R
EMO
VE M
ALE
PLU
G A
ND
ATT
ACH
FEM
ALE
PLU
G T
O T
HE
ECO
NO
MIZ
ER A
CC
ESSO
RY.
4. F
OR
208
VO
LT T
RAN
SFO
RM
ER O
PER
ATIO
N M
OVE
BLAC
K W
IRE
FRO
M T
ERM
INAL
3 T
O T
ERM
INAL
2
ON
TRAN
SFO
RM
ER.
5.R
EMO
VE J
UM
PER
IF S
MO
KE D
ETEC
TOR
OR
EM
ERG
ENC
Y
SHU
TDO
WN
DEV
ICE
IS IN
STAL
LED
.
OR
O
RAN
GE
AGND
AIL
ALR
MBC
1BC
2BI
LBP
SWCC C
SC
FC
FCC
FSCH C
HR
CHS
CM CO
MC
OM
PD
FTEC
ON
EM ES EXF
GN
DH
GR H
HPS
LDS
LPS
OAT
OAR
HPL
FPS RC
C FR
LR
SSR
V CSA
T/D
ATSD SM
K/EM
GSP
CTE
MP
SPC
R HTB
1-2
TB1-
T3TR
1-2
XS PM
DCG
ROUN
DFO
RAN
ALO
GSE
NSO
RS("A
G"O
NTB
2)8
ANAL
OG
INPU
T SAL
ARM
BLO
WER
HIG
HSP
EED
CON
TAC
TOR
BLO
WER
LOW
SPEE
DC O
NTAC
TOR
8BI
NAR
YIN
PUT S
BLO
WER
PRO
VIN
GS W
ITC
HC
OM
P RES
SOR
CON
TAC
T OR
CO
MPR
ESSO
R2N
DST
AGE
SOLE
N OID
CON
DE N
SER
F AN
CO
ND
ENSE
RF A
NC
ON
TAC
TOR
CLO
GG
EDFI
LTER
S WIT
CH
CRAN
KCAS
EH
EATE
RC R
ANKC
ASE
HEA
TER
REL
A YC
RAN
KCAS
EH
EATE
RSW
I TC
HC
ON D
ENSE
RM
OTO
RC
OM
MO
N(" C
"ON
T B2)
CO
MP R
ESSO
RD
EFR
OST
THER
MO
STAT
ECO
NO
MIZ
EREV
APO
RATO
RM
OT O
REC
ON
C OM
3 -8
AND
SMO
KED
E TEC
TOR
EXH
AUS T
FAN
EQUI
PMEN
TG
RO
UN
DH
OT
GAS
RE H
EAT
HIG
HP R
ESSU
RE
SWIT
CH
LOAD
SHE D
DIN
GLO
WPR
ESSU
RE
S WIT
CH
OU
TDO
OR
AIR
TEM
PER
A TU
RE
OU
TDO
OR
AIR
REL
A TIV
EH
UMID
ITY
FEM
ALE
PLU
G/C
ONN
ECTO
RPR
ESS U
RE
SWIT
CH
R UN
CAPA
CI T
OR
FOR
CO
NDE N
SER
F AN
REL
AYR
EMO
T EST
ART
STO
PR
EVER
SIN
GVA
LVE
COI L
SUPP
L Y/D
ISC
HA R
GE
AIR
TEM
PER
ATU
RE
SMO
KED
ETEC
TOR
SMO
KEO
REM
ERG
ENCY
SHU
TDO
WN
SPAC
ETE
MPE
RAT
URE
SPAC
ER
E LAT
IVE
HUM
IDIT
YTE
RM
INA L
BLO
CK(2
4VSI
GN
AL)
PHAS
EM
ON
ITO
RTE
RM
INAL
(PM
)TR
ANSF
ORM
ER24
VAC
TRAN
S FO
RM
ER&
SMO
KED
E TEC
TOR
PHAS
EM
ON
ITO
RSE
E U
NIT
RAT
ING
PLA
TE F
OR
TYPE
AN
D S
IZE
OF
OVE
RCU
RREN
T PR
OTE
CTI
ON
YL
YELL
OW
GR
G
REE
N
WH
W
HIT
E
BR
BRO
WN
CO
MP O
NEN
T LE
GEN
D
FIEL
DW
IRIN
GH
IGH
VO
LTAG
E
PU
PUR
PLE
FIEL
D S
PLIC
E
SWIT
CH
(TEM
P)
OPT
ION
AL L
OW
VO
LTAG
E
SWIT
CH
(PR
ESS.
)
OVE
RCUR
REN
TPR
OT.
DEV
ICE
TER
MIN
AL
PLU
G C
ON
NEC
TIO
N
FIEL
D G
RO
UND
IGN
ITER
JUNC
TIO
N
INTE
RN
AL T
OIN
TEG
RAT
EDC
ON
TRO
L
SCH
EMAT
IC S
YMBO
L
LDS
RSS
BPSW
3
24V
TR
1
BC2
HPS
3
24V
TR
1
LPS
BI1
BI2
BI3
BI5
BI6
BI7
BI8
AI1
AI2
AI4
AI5
AI6
AI7
AI8
AGN
D
OAT
DAT
OAR
H
431 2
CO2
SPC
TEM
PC
OM
SEN
SOR
OFF
SET
SPCR
H
COM
1RL
1
RL2
COM
2
COM
3-8
AI3
RL3
RL4
RL5
CC
RL6
RL7
RL8
24VA
CG
ND
ECO
NPL
F
+ - + - + -HGR
H
EXF
ALRM
SMK/
EM
G
AO1
AO2
AO3
AO4
VMR
FSIGN
NO
TE 3
L2
RSG
V
LS
H
D1
FSF
54L1N
OTE
3
ALS
PS
103 6 8
IIC
D D C
L2
T1CO
MP
T2
SUPP
LY V
OLT
AGE
CM
EM
L1
CC
T3
208-
240/
3/60
BC1
CC
CC
VMR
31
VM
BI4
208-
240/
3/60
208-
240/
3/60
SEE
NO
TE 5
RC
CF
FC
CFS
L3
POW
ER &
CO
NTR
OL
WIR
ING
DIA
GR
AMDC
G 0
72**
*(3)
(V) B
DDC
PMSD
CS BC
1
BC1
BC1
BC2
BC2
BC2
30 www.daikinac.com SS-DCG3
Wiring Diagram with DDC - DCG072140 (460, 575/3/60)V***
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
GN
D
LDS
BI1
BI2
BI3
RSS
AI1
24V
TR1
157
52
3C
460
TR2
12
3
L3
BK
CO
MP
SMK/
EMG
POW
ER S
UPP
LY46
0/57
5/3/
60
CFS BK
BR
RD
PK
GR
GR
BL
BC1
CC
BL
BL
DAT
OAT
BI4
BI5
BI6
BI7
BI8
AI2
AI3
AI4
AI5
AI6
AI7
AI8
GN
D
AGN
D
24VA
C
AGN
D
GN
DG
ND
CO
M3-
8R
L8 AO
4
COM
2
AO
3
AO
2
AO
1
COM
3-8
RL7
RL6
RL5
RL4
RL3
RL2
RL1
COM
1
AGC
BL
+ - + -HG
RH EXF
GR
ALR
M+ -
RD YL
T3 T2 T1
L2 L1
BL
RD BK
BKRD BL
BKRD
WH
PK
C
YL RD
SEE
NO
TE 4
575
C46
0 BL24V
RD
24V
T5T4
T3T2
T1
SEE
NO
TE 5
CS
PSES
XS
RD
TB1
RDBK
PU
PUPK
YLPK
PS RS
ALS
MV MV
PU
W.R
.G
AS V
ALVE
GV
BL
(ALT
.) HO
NEY
WEL
LG
AS V
ALVE
GV
FS IGN
IIC
LS
10
7 912
8
11
ECON
1 32654
L1FS
DIHEAT COOLUNUSED
L2
SEE
NO
TE 3
OR
GR
OR
PK
RD
PU PU
BR
RD
OR
BL
BLBL
BL
BLBLPKWH
YL
YLYLPUBLRDRD
RD
RD
RD
OR
RD GR
GR
PU
WH
BKBL
BL
WH
BR
OR
RDBK BL
BL
460/
575
TR 240O
RBK
OR
BK
RD
RD
YL/P
KBL
/PK
BL/
PK
WH
WH
WH
HPS
LPS
RD
YL
BK GR
YL/
PKYL
BL
GR
GN
D
VOUT
DC
OARH SPCRH
STPT
OFF
SET
GN
D
TEM
P
SPCTEMP VOUT
DC
GN
D
CO2VOUT
DC
GN
D24
VAC
CO
M
0140
L066
07-A
460/
575/
3/60
GR
RD
BPSW
GR
BK
TB2
DA
PU
PU
WH
412 5
3 6EC
ON
BKBR
WH
RD
RD
WH
YL
RDBK
RD
BK
24 V
AC
CM
BRRC
CF
PU
BK
BK
RD
FC
PU
BR
CS
GR
GR
GR
GR
YL
YL
GR
BR
BR
Yout
YC
L1L2
L3 OR
BKR
D
BLR
DPU
VMR 3 1
2
WH
BKBK
WH BL
L3T3 T2 T1
L2 L1C
BC2
L3T3 T2 T1
L2 L1C
EMRD
BK
RD
VM
BLBL
BL
BL
BL
OR
RD BK
GY BL YL
WH
BLO
RBR
BL
BRO
R
RD
BK
YL
YL
BL
YL
SS-DCG3 www.daikinac.com 31
Wiring Diagram with DDC - DCG072140 (460, 575/3/60)V***
Wiri
ng i
s su
bjec
t to
cha
nge.
Alw
ays
refe
r to
the
wiri
ng d
iagr
am o
n th
e un
it fo
r th
e m
ost
up-t
o-da
te w
iring
.⚠
War
ning
High
Vol
tage
: D
isco
nnec
t al
l po
wer
bef
ore
serv
icin
g or
ins
talli
ng t
his
unit.
Mul
tiple
pow
er
sour
ces
may
be
pres
ent.
Failu
re to
do
so m
ay c
ause
pro
pert
y da
mag
e, p
erso
nal i
njur
y, o
r de
ath.⚡
0140
L066
08-A
460/
575/
3/60
BL/P
K B
LUE
WIT
H P
INK
STR
IP
PK
PIN
K
YL/P
K Y
ELLO
W W
ITH
PIN
K ST
RIP
WIR
E C
OD
ELIN
E VO
LTAG
E
OPT
ION
AL H
IGH
VO
LTAG
E
LOW
VO
LTAG
E
RD
R
EDFAC
TOR
YW
IRIN
G
LOW
VO
LTAG
E
BL
BLU
EBK
BL
ACK
NO
TES:
1.R
EPLA
CEM
ENT
WIR
E M
UST
BE
SAM
E SI
ZE A
ND
TYP
E IN
SULA
TIO
N A
S O
RIG
INAL
(AT
LEAS
T 10
5°C
)U
SE C
OPP
ER C
ON
DUC
TOR
ON
LY.
2.U
SE C
OPP
ER C
ON
DUC
TOR
S O
NLY
++ U
SE N
.E.C
. CLA
SS 2
WIR
E3.
ECO
NO
MIZ
ER P
LUG
LO
CAT
ED IN
TH
E R
ETU
RN
AIR
CO
MPA
RTM
ENT.
REM
OVE
MAL
E PL
UG
AN
D A
TTAC
H F
EMAL
E PL
UG
TO
TH
E EC
ON
OM
IZER
AC
CES
SOR
Y.4.
FOR
460
VO
LT T
RAN
SFO
RM
ER O
PER
ATIO
N M
OVE
BLA
CK
WIR
E FR
OM
TER
MIN
AL 3
TO
TER
MIN
AL 2
O
N T
RAN
SFO
RM
ER.
5.R
EMO
VE J
UM
PER
IF S
MO
KE D
ETEC
TOR
OR
EM
ERG
ENC
Y S
HU
TDO
WN
DEV
ICE
IS IN
STAL
LED
.
OR
O
RAN
GE
AGND
AIL
ALR
MBC
1BC
2BI
LBP
SWCC C
FCC
FC
FCC
FSCH C
HR
CH
SC M C
OM
CO
MP
CS
DFT
ECO
NEM ES E X
FG
ND
HG
R HH
PSLD
SLP
SO
A TO
ARH
PLF
PM PS RC
CFR
LR
SSR
VCSA
T/D
A TSD SM
K/EM
GSP
CTE
MP
SPC
RH
TB1-
2TR
1-2
TB1-
T3XS
DC
GRO
UND
FOR
ANAL
OG
SEN
SORS
("AG
" ON
TB2)
8AN
ALO
GIN
P UTS
ALAR
MBL
OW
ERH
IGH
SPEE
DC
ONT
ACTO
RBL
OW
ERL O
WSP
EED
CO
NTA
CTO
R8
BINA
RY
INPU
T SBL
OW
ERPR
OVI
NG
S WIT
CH
CO
MPR
ESSO
RC
ON T
ACT O
RC
ON
DEN
SER
FAN
COIL
CO
NDEN
SER
FAN
CO
N DEN
SER
FAN
CON
TAC
TOR
CLO
GG
EDFI
LTER
SWIT
CH
CR
ANKC
ASE
HEA
TER
CR
ANKC
ASE
HE A
TER
REL
A YC R
ANKC
ASE
HEA
TER
SWIT
CH
CO
NDEN
SER
MO
T OR
CO
MM
ON
("C"O
NTB
2)C
OM
PRES
SOR
CO
MPR
ESSO
R2N
DS T
AGE
SOLE
N OID
DEF
RO
STTH
ERM
OST
ATEC
ON
OM
IZER
EVAP
ORA
TOR
MO
TOR
ECO
NC
OM
3-8
A ND
SMO
KEDE
TEC
TOR
EXH
AUS T
FAN
EQUI
PMEN
TG
RO
UND
HO
TG
ASR
EHEA
TH
IGH
P RES
SUR
ES W
ITC
HLO
ADSH
E DD
ING
LOW
PRES
SUR
ESW
ITC
HO
UTD
OO
RAI
RT E
MPE
RAT
UR
EO
UTD
OO
RAI
RRE
LATI
VEH
UMID
ITY
FEM
ALE
PLU
G/ C
ONN
ECTO
RPH
ASE
MO
NIT
OR
PRES
SUR
ES W
I TC
HR U
NC
APAC
ITO
RFO
RC
ON
DEN
SER
FAN
REL
AYR
EMO
T EST
ART
STO
PR
EVER
SIN
GVA
L VE
COIL
SUPP
L Y/D
I SC
HAR
GE
A IR
TEM
P ER
ATU
RE
SMO
KED
ETEC
T OR
SMO
KEO
REM
ERG
ENC Y
SHU
TDO
WN
SPAC
ETE
MPE
RAT
UR
ESP
ACE
RE L
ATIV
EHU
MID
ITY
TER
MIN
A LBL
OC
K(2
4VSI
GN
AL)
TRAN
SFO
RMER
PHAS
EM
ON
ITO
RTE
RM
INAL
(PM
)24
VAC
TRAN
S FO
RM
ER&
SMO
KED
ETEC
T OR
SEE
UN
IT R
ATIN
G P
LATE
FO
RTY
PE A
ND
SIZ
EO
F O
VER
CUR
REN
T PR
OTE
CTI
ON
YL
YELL
OW
GR
G
REE
N
WH
W
HIT
E
BR
BRO
WN
CO
MP O
NEN
TLE
GEN
D
FIEL
DW
IRIN
GH
IGH
VO
LTAG
E
PU
PUR
PLE
FIEL
D S
PLIC
E
SWIT
CH
(TEM
P)
OPT
ION
AL L
OW
VO
LTAG
E
SWIT
CH
(PR
ESS.
)
OVE
RCU
RREN
TPR
OT.
DEV
ICE
TER
MIN
AL
PLU
G C
ON
NEC
TIO
N
FIEL
D G
RO
UND
IGN
ITER
JUNC
TIO
N
INTE
RN
AL T
OIN
TEG
RAT
EDC
ON
TRO
L
SCH
EMAT
ICSY
MBO
L
LDS
RSS
BPSW
3
24V
TR
2
BC2
HPS
3
24V
TR
1
LPS
BI1
BI2
BI3
BI5
BI6
BI7
BI8
AI1
AI2
AI4
AI5
AI6
AI7
AI8
AGN
D
OAT
DAT
431 2
COM
1R
L1 RL2
COM
2
COM
3-8
AI3
RL3
RL4
RL5
CC
RL6 RL7
RL8
24VA
CG
ND
ECO
NPL
F
+ - + - + -HG
RH
EXF
ALRM
SMK/
EMG
AO1
AO2
AO3
AO4
VMR
FSIGN
NO
TE 3
L2
RSG
V
LS
H
D1
FSF
54L1N
OTE
3
ALS
PS
103 6 8
IIC
D D C
L2
T1CO
MP
T2
SUPP
LY V
OLT
AGE C
M
L1
CC
T3
460/
575/
3/60
CC
CC
BI4
460/
575/
3/60
460/
575/
3/60
SEE
NO
TE 5
RCC
FFC
CFS
L3
VMR
31
VM
31
12
OAR
HCO
2
SPC
TEM
PCO
M
SENS
OR
OFF
SET
SPCR
H
CS
BC1PM
BC2
BC2
SD
EMBC
1
BC1
BC1
BC2
32 www.daikinac.com SS-DCG3
Accessories
Daikin MasterItem # Description Fits
Model SizesField-
InstalledFactory-Installed
Operating Weight (lbs)
Curb14CURB3672B 14” Roof Curb 3-6 tons √ 86
18CURB3672B 18” Roof Curb 3-6 tons √ 100
24CURB3672B 24” Roof Curb 3-6 tons √ 128
GHRC-3672 Hurricane Restraint Clips 3-6 tons √ 2
Ultra Low-Leak Economizer & Power Exhaust110-365-09C Ultra Low-Leak Downflow Economizer w/ Dry Bulb 3-6 tons √ 71
10-366-09C Ultra Low-Leak Downflow Economizer w/ Enthalpy 3-6 tons √ √ 71
10-395-09 Ultra Low-Leak Horizontal Economizer w/ Dry Bulb 3-6 tons √ 71
10-396-09 Ultra Low-Leak Horizontal Economizer w/ Enthalpy 3-6 tons √ 71
10-455-09*-23 Centrifugal Power Exhaust 230v 3-6 tons √ 55
10-455-09*-33 Centrifugal Power Exhaust 460v 3-6 tons √ 55
10-455-09*-43 Centrifugal Power Exhaust 575v 3-6 tons √ 55
10-457-09xA-23 Modulating Power Exhaust 208-230v 3-6 tons √ 55
10-457-09xA-33 Modulating Power Exhaust 460v 3-6 tons √ 55
10-465-09-21 Prop Power Exhaust 230v 3-6 tons √ 55
10-465-09-31 Prop Power Exhaust 460v 3-6 tons √ 55
10-465-09-41 Prop Power Exhaust 575v 3-6 tons √ 55
Low-Leak Economizer & Power Exhaust2DDNECNJ3672C Low-Leak Downflow Economizer 3-6 tons √ √ 82
DPE36722 Downflow Power Exhaust (208/230 Volt) 3-6 tons √ 55
DPE36724 Downflow Power Exhaust (460 Volt) 3-6 tons √ 55
DPE36727 Downflow Power Exhaust (575v) 3-6 tons √ 55
DHZECNJ3672 Horizontal Economizer 3-6 tons √ 70
DHPE36722 Horizontal Power Exhaust (208/230 Volt) 3-6 tons √ 55
DHPE36724 Horizontal Power Exhaust (460 Volt) 3-6 tons √ 55
DHPE36727 Horizontal Power Exhaust (575 Volt) 3-6 tons √ 55
Downflow AccessoriesD25FD3672 25% Manual Fresh Air Damper 3-6 tons √ 12
D25MFD3672 25% Motorized Fresh Air Damper 3-6 tons √ 16
DDNBBS3672 Burglar Bar Sleeves with Supply & Return 3-6 tons √ 30
DDNECNJ3672NR Downflow Economizer2 w/o Barometric Relief 3-6 Tons √ 77
DDNSQRD3616 Downflow Square-to-Round Adapter (16” Round) 3 tons √ 45
DDNSQRD487218 Downflow Square-to-Round Adapter (18” Round) 4-6 tons √ 35
Horizontal AccessoriesDBRD3672 Barometric Relief Damper 3-6 tons √ 15
Concentrics
CDK36 Concentric Duct Kit 3 tons √ 27
CDK4872 Concentric Duct Kit 4-6 tons √ 27
DDC Accessories3DDC communicating controller (built-in BACnet® MS/TP) includes Standard Room Sensor to be installed in field
3-6 tons √ 2
SS-DCG3 www.daikinac.com 33
Accessories
Daikin MasterItem # Description Fits
Model SizesField-
InstalledFactory-Installed
Operating Weight (lbs)
10366D09C DDC Ultra Low-Leak Downflow Economizer 3-6 tons √ √ 71
10366D09 DDC Ultra Low-Leak Horizontal Economizer 3-6 tons √ 71
10465DDC Power Exhaust kit used with DDC Ultra Low-Leak Economizer
3-6 tons √ 1
DLAKT01 Low-Ambient 3-6 tons √ √ 2
LONKT01 LonWorks® card 3-6 tons √ 1
3PMK01 Phase Monitor (3-Phase Only) 3-6 tons √ √ 2
DFSKT01 Dirty Filter Switch 3-6 tons √ 1
High-Static Kits4HSKT036B High-Static Kit (230/460v) 3 tons √ √ 41
HSKT036B-7 High-Static Kit (575v) 3 tons √ √ 5
HSKT048B High-Static Kit (230/460v) 4 tons √ √ 38
HSKT048B-7 High-Static Kit (575v) 4 tons √ √ 27
HSKT060B High-Static Kit (230/460v) 5 tons √ √ 38
HSKT060B-7 High-Static Kit (575v) 5 tons √ √ 28
HSKT072B High-Static Kit (230/460v) 6 tons √ √ 38
HSKT072B-7 High-Static Kit (575v) 6 tons √ √ 15
Crankcase Heater Kits0163R00002S 40W 230V 3 tons √ 1
0163R00031S 40W 460V 3 tons √ 1
0163R00032S 40W 575V 3 tons √ 1
0130L00017S 70W 230V 4 - 6 tons √ 1
0130L00018S 70W 460V 4 - 6 tons √ 1
0130L00019S 70W 575V 4 - 6 tons √ 1
High Efficiency Filters0160L00203 High Efficiency MERV 13 Air Filter Nom.
Size: 24x24x2; (Order Qty 1)3 tons √ 2
0160L00204 High Efficiency MERV 13 Air Filter Nom. Size: 14x20x2; (Order Qty 4)
4 tons √ 4
0160L00205 High Efficiency MERV 13 Air Filter Nom. Size: 16x20x2; (Order Qty 4)
5 & 6 tons √ 4
Misc AccessoriesHAILGD03D Condenser Coil Hail Guard 3-5 tons √ 19
HAILGD04D Condenser Coil Hail Guard 6 tons √ 22
Convenience Outlet: Non Powered 3-6 Tons √ 2
Convenience Outlet: Powered 3-6 Tons √ 42
Disconnect Switch 3-6 Tons √ 5
HA-02 High-Altitude Kit 3-6 tons √ 1
LAKT12 Low Ambient Kit, 208-230V - non-DDC 3-6 tons √ √ 14
LAKT15 Low Ambient Kit, 460V - non-DDC 3-6 tons √ √ 14
LAKT16 Low Ambient Kit, 575V - non-DDC 3-6 tons √ √ 14
34 www.daikinac.com SS-DCG3
Our continuing commitment to quality products may mean a change in specifications without notice. © 2017 • Houston, Texas • Printed in the USA.
Accessories
Daikin MasterItem # Description Fits
Model SizesField-
InstalledFactory-Installed
Operating Weight (lbs)
LPM-07 LP Conversion Kit (For DCG036045 unit only) 3 Ton √ 1
LPM-08 LP Conversion Kit 3-6 Ton √ 1
3PMNDK01 Phase Monitor - Non DDC 3-6 tons √ √ 2
Smoke Detector (supply and/or return air) 3-6 tons √ 11
Hinged Panels 3-6 tons √ 101 Use Economizer & Power Exhaust listed within Ultra Low-Leak section 2 Use Economizer & Power Exhaust listed within Low-Leak section 3 For a full list of DDC accessories, please refer to DDC Controller Technical Guide manual (DK-DDC-TGD-01B)4 HSKT High-Static Kits are for use with standard single-speed belt-drive units only.
Note: Where multiple variations are available, the heaviest combination is listed.