dau01-mod2008-4ai+4ao specification · 2020. 2. 13. · dau01-mod2008-4ai+4ao winsonic provide the...
TRANSCRIPT
-
Specification
No.290-1, Wen Zhong Rd., Taoyuan City, Taoyuan County 33056, Taiwan (R.O.C.) Tel : +886-3-370-4789 Fax: +886-3-370-4722 E-mai l : sales@ewinsonic .com
Winsonic Electronics Co., Ltd.
DAU01-MOD2008-4AI+4AO
Winsonic provide the three control ports MODBUS remote I/O products with the Ethernet, USB and RS485/RS422 interface for industrial control and is flexible to implement by customer’s application . These interfaces also can be the spare of the control port each other to increase the safety.
Analog Input
Channels
Type
Resoulation
Sampling Rate
Bandwidth
Common Mode Rejection
Normal Mode Rejection
Input Impedance
ESD Protection
Analog Output
Channels
Type
Resoulation
Accuracy
Voltage Output Capability
Current Load Resistance
Open Wire for Current Output
Power
Input Voltage Range
Power Consumption
Mechanism
Installation
Dimension
Environment
Operating Temperature
Storage Temperature
Relative Humidity
4
0 to 10VDC, 0 to 20 mA, 4 to 20 mA (burn-out mode)
16-bit
19.86 Samples/Sec
19.79Hz
90 dB Min.
60 dB Min.
100KΩ
4 kV Contact for each terminal and 8 kV Air for random points
4
+0 mA ~ +20 mA, +4 mA ~ +20 mA
12-bit
+/- 1% of PSR
10 V @ 20 mA
500 Ohms
0 mA ~ 20 mA
12V~48V DC(+- 10%)
Max 2.7W(24VDC)
DIN-Rail
115mmx110mmx30mm
-25℃ ~75℃
-30℃~80℃
10~90%, No Condensation