data sheet plate heat exchanger xgm032 - danfoss...

4
1 VD.GS.U2.02 © Danfoss 03/2014 DEN-SMT/SI Plate Heat Exchanger XGM032 Data sheet Description Danfoss XGM plate heat exchangers have been developed specifically for District Energy applications like District Heating and Cooling ensuring you a reliable high efficient plate heat exchanger fulfilling your needs. Main data: Min. temperature −10 °C Max. temperature 150 °C Max. working pressure 16 bar (25 bar on request) Standard range is 1 pass version (2 pass version on request) Circulation water / glycolic water up to 50 % Connection size DN 32 Approvals: Pressure Equipment Directive (PED) 97/23/EC GOST/Russia Ordering 1-pass gasketed heat exchangers type XGM032 Picture No. of plates Connection XGM032L XGM032M XGM032H (n) Code No. 20 Thread G 1¼ 004H7096 004H7087 004H7078 30 004H7097 004H7088 004H7079 40 004H7098 004H7089 004H7080 50 004H7099 004H7090 004H7081 60 004H7100 004H7091 004H7082 70 004H7101 004H7092 004H7083 80 004H7102 004H7093 004H7084 90 004H7103 004H7094 004H7085 100 004H7104 004H7095 004H7086 Note: Brackets has to be ordered separately. XGM 032 H – 1 – 10 Number of plates Number of Passes (1 = 1-pass) Channel type (L-M-H) Connection size (DN 32) Micro plate™ plates Gasketed heat exchanger

Upload: ngonga

Post on 06-Feb-2018

313 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Data sheet Plate Heat Exchanger XGM032 - Danfoss Heatingheating.danfoss.com/PCMPDF/VDGSU202_Plate_heat_exchanger_XG… · Plate Heat Exchanger XGM032 Data sheet Description Danfoss

1VD.GS.U2.02 © Danfoss 03/2014DEN-SMT/SI

Plate Heat ExchangerXGM032

Data sheet

Description Danfoss XGM plate heat exchangers have been developed specifically for District Energy applications like District Heating and Cooling ensuring you a reliable high efficient plate heat exchanger fulfilling your needs.

Main data:• Min.temperature−10°C• Max.temperature150°C• Max.workingpressure16bar(25baronrequest)• Standardrangeis1passversion

(2passversiononrequest)• Circulationwater/glycolicwaterupto50%• ConnectionsizeDN32

Approvals:• PressureEquipmentDirective(PED)97/23/EC• GOST/Russia

Ordering

1-pass gasketed heat exchangers type XGM032

PictureNo. of plates

ConnectionXGM032L XGM032M XGM032H

(n) Code No.

20

Thread G 1¼

004H7096 004H7087 004H7078

30 004H7097 004H7088 004H7079

40 004H7098 004H7089 004H7080

50 004H7099 004H7090 004H7081

60 004H7100 004H7091 004H7082

70 004H7101 004H7092 004H7083

80 004H7102 004H7093 004H7084

90 004H7103 004H7094 004H7085

100 004H7104 004H7095 004H7086

Note: Brackets has to be ordered separately.

XGM 032 H – 1 – 10

Numberofplates NumberofPasses(1=1-pass)

Channeltype(L-M-H)

Connectionsize(DN32)

Micro plate™ plates

Gasketed heat exchanger

Page 2: Data sheet Plate Heat Exchanger XGM032 - Danfoss Heatingheating.danfoss.com/PCMPDF/VDGSU202_Plate_heat_exchanger_XG… · Plate Heat Exchanger XGM032 Data sheet Description Danfoss

2 VD.GS.U2.02 © Danfoss 03/2014 DEN-SMT/SI

Data sheet Plate Heat Exchanger XGM032

Accessories - BracketType Code No.

Brackets 004H7222

Accessories - EPDM GasketType Code No.

Gasket for XGM032, I-pack 10 pcs 004H7128

GasketforXGM032,I-pack250pcs 004H7129

Ordering - continuous

Accessories for gasketed heat exchanger type XGM Type Code No.

PlatesforXGM032HPN16,I-pack10pcs 004H7186

PlatesforXGM032MPN16,I-pack10pcs 004H7187

PlatesforXGM032LPN16,I-pack10pcs 004H7188

PlatesforXGM032HPN16,I-pack250pcs 004H7189

PlatesforXGM032MPN16,I-pack250pcs 004H7190

PlatesforXGM032LPN16,I-pack250pcs 004H7191

XGM032H:spec.plates1-passversions,includinggaskets.PN16 004H7204

XGM032M:spec.plates1-passversions,includinggaskets.PN16 004H7205

XGM032L:spec.plates1-passversions,includinggaskets.PN16 004H7206

XGM032H:spec.plates2-passversion,includinggasketsPN16 004H7219

XGM032M:spec.plates2-passversion,includinggasketsPN16 004H7220

XGM032L:spec.plates2-passversion,includinggasketsPN16 004H7221

Tailpieces for gasketed heat exchanger type XG Picture Description Connection Code No.¹⁾

Soldertailpieces G1¼A/22mm,28mm 004B1358

Weld-on tailpiecesG1¼A/DN25 003H6910

G1¼A/DN32 004B1343

1) One set contains 2 tailpieces with union nuts and gaskets

Accessories - InsulationsType coverage (plate nos) Code No.

20-40 004H7117

40-70 004H7118

70-100 004H7119

Technical data Max.workingpressure PN(bar) 16

Max.operatingtemperatureoC

150

Min.operatingtemperature1) −10

Flowmedium Circulationwater/glycolicwaterupto50%

Heattransferareaperplate,HTA m2 0,067

Max. no of plates pcs 100

Volume/Channel

Ltr

0,097

Primarysidevolume: (n/2)-1xvolume/channel

Secondarysidevolume: (n/2)xvolume/channel

Connection type Cylindricalexternalthreadacc.toDINISO228/1

Connectionsize G 1¼

Platematerial Stainlesssteel,mat.no.EN1.4401

Platethickness mm 0,3

Gasket type Glue free

Gasketmaterial,rubber EPDM

1) At flow temp. below 2 °C glycolic water must be used

Insulation properties

Type Coated steel sheet

and polyester insulation

Heat conductivity, λ W/mK 0,042

Max temperature

Permanent°C

150

Shorttermpeak 180

Wall thickness mm 30

Note:For more details about insulation please contact your Danfoss sales representative.

Page 3: Data sheet Plate Heat Exchanger XGM032 - Danfoss Heatingheating.danfoss.com/PCMPDF/VDGSU202_Plate_heat_exchanger_XG… · Plate Heat Exchanger XGM032 Data sheet Description Danfoss

3VD.GS.U2.02 © Danfoss 03/2014DEN-SMT/SI

T11

T21

T12

T22

Data sheet Plate Heat Exchanger XGM032

Design and function

1-pass heat exchanger

T11-Primarysidein

T12-Primarysideout

T21-Secondarysidein

T22-Secondarysideout

Theheatexchangersaremadeofshape-pressedheatplatesbetweenwhichtheflowchannelsarecreated.Gasketsbetweentheplatesseparatetheflowchannelsfromeachothersothattheflowsdonotmix.Theheavyturbulenceandcounter-flowprincipleenablesefficientheattransfer.Thetaskoftheheatexchangeristotransferheatfromtheprimarytosecondaryflowthrough a heat transfer plate thus preventing theflowsfrommixingwitheachother.Theplateheatexchangerwithgasketscanbeopenedforcleaningandforreplacementofplatesandgaskets.Asteeplesoutputadjustmentcanbecarriedoutbychangingthenumberofplates.

Thechoiceofheatexchangerisdeterminedbythedesiredheatoutput,requiredtemperaturesandthepermittedpressurelosses.

Sizing DimensioningandselectionofheatexchangersshouldbecarriedoutwiththesupportoftheDanfossdimensioningprogramforheatexchangers.

Mounting Theheatexchangermustbemountedinverticalposition. Preparethefoundationfortheheatexchangerifnecessary,alwaysaccordingtolocalregulations.Itisrecommendedthatallpipesconnectedtotheheatexchangerareequippedwithshut-offvalvesformaintenancepurposes.

Thepipestobeconnectedmustbemountedsothatthestraincausedbythethermalexpansion,forinstance,doesnotharmtheheatexchanger.

Thepipesmustbeequippedwithbracketstoprevent any torsional stress concentration at the heat exchanger’s pipe connections.

Itisrecommendedthattheheatexchangerisequippedwithinsulation.

Asafetyvalvemustbeinstalledbetweentheheatexchangerandtheshut-offvalvesonthesecondary side of the heat exchanger. If the safetyvalveisnotinstalled,thermalexpansionoffluidmightdestroytheheatexchangerwhentheshut-offvalvesareclosed.

Dimensions

B

G

D

AE

C

Heat exchanger

Plate No. G B D C E HWeight

(kg)

20

570 180 470 63 65

48 32

30 71 34

40 94 37

50 117 39,5

60 140 41,5

70 163 44,5

80 186 46,5

90 209 48,5

100 232 50,5

Page 4: Data sheet Plate Heat Exchanger XGM032 - Danfoss Heatingheating.danfoss.com/PCMPDF/VDGSU202_Plate_heat_exchanger_XG… · Plate Heat Exchanger XGM032 Data sheet Description Danfoss

4 VD.GS.U2.02 ProducedbyDanfossA/S©03/2014

Data sheet Plate Heat Exchanger XGM032

Dimensions (continuous)

B

H

I

G

Insulation

Code No. G B I HWeight

(kg)

004H7117

615 270 50

360 10

004H7118 460 12

004H7119 560 14

154

Ø14

180

146

159

121

130

20

5290

122

91910

Bracket