data sheet 3va2216-5mn32-0aa0 · adjustable response value current / lg min. 4 adjustable response...

4
Data sheet 3VA2216-5MN32-0AA0 CIRCUIT BREAKER 3VA2 IEC FRAME 250 BREAKING CAPACITY CLASS M ICU=55KA @ 415 V 3-POLE, MOTOR PROTECTION ETU350M, LSI, IN=160A OVERLOAD PROTECTION IR=63A ...160A SHORT CIRCUIT PROTECTION ISD=3... 15 X IR, II=15 X IN BUSBAR CONNECTION Model product brand name SENTRON Product designation Molded case circuit breaker Design of the product Motor protection Design of the overcurrent release ETU350M Protective function of the overcurrent release LSI Number of poles 3 General technical data Mechanical service life (switching cycles) / typical 20 000 Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz 10 000 Electrical endurance (switching cycles) / at AC-3 / at 380/415 V 50/60 Hz 5 000 Neutral conductors / upgradeable/retrofittable No Ground fault monitoring version Without Switching capacity Switching capacity class of the circuit breaker M Adjustable parameters 3VA2216-5MN32-0AA0 Changes preserved Page 1/ 4 08.04.2016 © Copyright Siemens AG

Upload: others

Post on 20-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Data sheet 3VA2216-5MN32-0AA0 · Adjustable response value current / lg min. 4 Adjustable response value current / lg min. 17 Short-term delayed / tripping switchable / I2t=ON/OFF

Data sheet 3VA2216-5MN32-0AA0CIRCUIT BREAKER 3VA2 IEC FRAME 250 BREAKING CAPACITYCLASS M ICU=55KA @ 415 V 3-POLE, MOTOR PROTECTIONETU350M, LSI, IN=160A OVERLOAD PROTECTION IR=63A...160A SHORT CIRCUIT PROTECTION ISD=3... 15 X IR, II=15 X INBUSBAR CONNECTION

Modelproduct brand name SENTRONProduct designation Molded case circuit breakerDesign of the product Motor protectionDesign of the overcurrent release ETU350MProtective function of the overcurrent release LSINumber of poles 3

General technical dataMechanical service life (switching cycles) / typical 20 000Electrical endurance (switching cycles) / at AC-1 / at380/415 V 50/60 Hz

10 000

Electrical endurance (switching cycles) / at AC-3 / at380/415 V 50/60 Hz

5 000

Neutral conductors / upgradeable/retrofittable NoGround fault monitoring version Without

Switching capacitySwitching capacity class of the circuit breaker M

Adjustable parameters

3VA2216-5MN32-0AA0 Changes preservedPage 1/4 08.04.2016 © Copyright Siemens AG

Page 2: Data sheet 3VA2216-5MN32-0AA0 · Adjustable response value current / lg min. 4 Adjustable response value current / lg min. 17 Short-term delayed / tripping switchable / I2t=ON/OFF

Adjustable response value current / lg min. 4Adjustable response value current / lg min. 17Short-term delayed / tripping switchable /I2t=ON/OFF

No

Ground fault protection / tripping switchable /I2t=ON/OFF

No

ConnectionsArrangement of electrical connectors / for maincurrent circuit

Front terminal

Type of electrical connection / for main current circuit Lug terminalType of connectable conductor cross-section,connection screw, width x thickness , min.

13 x 1 mm

Type of connectable conductor cross-section,connection screw, width x thickness , max.

25 x 8.5

AccessoriesProduct extension / optional / motor drive Yes

Environmental conditionsProtection class IP / on the front IP40

CertificatesGeneralProductApproval

EMC Declaration ofConformity

TestCertificates

other

RCM sonstig sonstig

Further informationInformation- and Downloadcenter (Catalogs, Brochures,…)http://www.siemens.com/lowvoltage/catalogs

Industry Mall (Online ordering system)https://eb.automation.siemens.com/mall/en/WW/Catalog/Product/3VA22165MN320AA0

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)http://support.automation.siemens.com/WW/view/en/3VA22165MN320AA0/all

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VA22165MN320AA0

CAx-Online-Generatorhttp://www.siemens.com/cax

Tender specificationshttp://ausschreibungstexte.siemens.com/tiplv

3VA2216-5MN32-0AA0 Changes preservedPage 2/4 08.04.2016 © Copyright Siemens AG

Page 3: Data sheet 3VA2216-5MN32-0AA0 · Adjustable response value current / lg min. 4 Adjustable response value current / lg min. 17 Short-term delayed / tripping switchable / I2t=ON/OFF

52.5

105

181

157

35

35

1212

20

19

38

18

18

83

93

107

70

81

22.5

136

22.523

22.6

17.5

35

73

146

17.5

4.5

Format / Size: Hybrid quer

Siemens 3VA2xxx-xMN3x-0AA0

I>

I>>

I>

I>>

I>

I>>

-Q 1 3 5

2 4 6EFB RCDN-CT

SIEMENS

I>

I>>

L

S

I

ETU350M

-X2 -X3-X1

3VA2216-5MN32-0AA0 Changes preservedPage 3/4 08.04.2016 © Copyright Siemens AG

Page 4: Data sheet 3VA2216-5MN32-0AA0 · Adjustable response value current / lg min. 4 Adjustable response value current / lg min. 17 Short-term delayed / tripping switchable / I2t=ON/OFF

last modified: 21.03.2016

3VA2216-5MN32-0AA0 Changes preservedPage 4/4 08.04.2016 © Copyright Siemens AG