D1204016 060604-P-004
sheet 1 of 3
B
A
REV DATE DESCRIPTION PREPARED REVIEWED
RKK DC
03.10.07REVISED AS PER CUSTOMER
COMMENTS DTD 17.09.07RKK DC
27.08.07 ISSUED FOR APPROVAL
RESPONSIBILIT IES OR LIABILITIES UNDER PURCHASE ORDER.
SIGNED BY : DATE :
DAELIM'S PERMISSION TO PROCEED OR REVIEW TAKEN ON
VENDOR PRINTS SHALL NOT RELIEVED VENDOR FROM ITS
RFC - RETURN FOR CORRECTION
NA - NOT APPLICABLE
A - APPROVED WITHOUT COMMENT
AAN - APPROVED AS NOTED
DOCUMENT TITLE :
DAELIM INDUSTRIAL CO.,LTD
JOB NO. 060604
CT/PT DETAILS AND CALCULATIONS
FOR 440V SWITCHGEAR & MCC
P/O NO. PO-060604-0200-304-001-A01 V/P NO.VP-PO-060604-0200-304-001-A01
-105-MCC-101-009-B
VENDOR AL-AHLEIA SWITCHGEAR CO.,KUWAIT ITEM NO. 105-MCC-101A,B
OWNER Kuwait Oil Company (K.S.C) INQ. NO. 060604-0200-304-01
JOB TITLE Replacement of 9 Crude Oil Filling Lines Project DIC JOB NO. 060604
BJ
APPROVED
BJ
8/12/2019 d 1204016
http://slidepdf.com/reader/full/d-1204016 2/3
D1204016 CT/PT DETAILS AND CALCULATION(PROJECT: REPLACEMENT OF 9 CRUDE FILLING LINES IN STATE OF KUWAIT)
060604-P-004
sheet 2 of 3
440V SWITCHGEAR/MCC 105-MCC-101A,B
1. CURRENT TRANSFORMERS:
a. Metering:
Incomers & Bus Tie:
Connected equipments Burden (VA)
Ammeter 1.5
Connecting wires 0.1
1.6
Characteristics of CT : 1000/1A,CL-1,15VA
b. Over current and E/F:
Incomers:
Connected equipment is P127 of Areva
Recommended CT requirements by relay manufacturer: 5 VA, Class 5P10
Characteristics of CT: 1000/1A, CL-5P10, 15VA
Bus Tie:
Connected equipment is P123 of ArevaRecommended CT requirements by relay manufacturer: 5 VA, Class 5P10
Characteristics of CT: 1000/1A, CL-5P10, 15VA
c. Restricted E/F:
Connected equipment is P120 of Areva
Transformer Secondary Voltage (V) 457 V
KVA rating of Transformer 630 KVA
Impedance of Transformer (Z) 6 %
CT Resistance (RCT) 6 Ω
Length of 2.5sq.mm cable between Transformer Neutral CT and relay. (assumed) 20 mtr
Resistance of 2.5 sq.mm cable (assumed) 7.41 Ω /km
Lead Resistance (2R) 20*7.41*2/1000 = 0.2964 Ω
CT Ratio (CTR) 1000 /1A
Relay setting range (IR) 0.1
0.4
Fault current in CT secondary (IF) = [KVA*1000 / (√3*V*Z)]/CTR 13.3 A
Stability Voltage (VS) = K*IF*(RCT+2R) 83.5 V
K=1 for REF application
Knee point voltage of CT (VK) = 2*VS 167.1 V
VK/VS=2
Characteristics of CT: 1000/1A, CL-X, Vk ≥ 170V, Rct ≤ 6Ω
Stabilizing Resistor minimum (RST-max) = VS / Relay setting min. 835.3 Ω
Stabilizing Resistor maximum (RST-min) = VS / Relay setting max. 208.8 Ω
Max unsaturated voltage (VF) = IF*(RCT+2R+RST-max) 11164.0 V
2*√[2*VK*(VF-VK)] 3834.0 V
Since Vp is greater 3000V peak, non-linear resistor (Metrosils) will be used.
Stabilizing Resistor = 0 to 1500Ω
Characteristics of CT: 1000/1A, CL-5P10, 15VA
Peak voltage developed by CT under
internal fault condition (VP) =
I:\USERS\DESIGN\FILES\KUWAIT\KOC\12704907\SUBMITTAL REV.2\D1204016.xls
8/12/2019 d 1204016
http://slidepdf.com/reader/full/d-1204016 3/3
D1204016 CT/PT DETAILS AND CALCULATION(PROJECT: REPLACEMENT OF 9 CRUDE FILLING LINES IN STATE OF KUWAIT)
060604-P-004
sheet 3 of 3
2. VOLTAGE TRANSFORMERS:
Connected equipments Burden (VA)
P127 0.25
Voltmeter 4.5
Connecting wires 0.1
4.85
Characteristics of PT: 440/√3/110/√3, CL-1/3P, 200VA