d 1204014

2

Click here to load reader

Upload: sanjeevchhabra1

Post on 03-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: d 1204014

8/12/2019 d 1204014

http://slidepdf.com/reader/full/d-1204014 1/2

  D1204014  060604-P-004

Sheet 1 of 2

B

 A

REV

 OWNER Kuwait Oil Company (K.S.C) INQ. NO. 060604-0200-304-01

 JOB TITLE Replacement of 9 Crude Oil Filling Lines Project DIC JOB NO. 060604

 AL-AHLEIA SWITCHGEAR CO., KUWAIT ITEM NO. 105-MCC-101A,B

 P/O NO. PO-060604-0200-304-001-A01 V/P NO.VP-PO-060604-0200-304-001-A01-105-MCC-101-007-B

 VENDOR

DOCUMENT TITLE :

DAELIM INDUSTRIAL CO.,LTD

TECHNICAL SPECIFICATION FOR 440V SWITCHGEAR & MCC

JOB NO. 060604

  A - APPROVED WITHOUT COMMENT

  AAN - APPROVED AS NOTED

  RFC - RETURN FOR CORRECTION

  NA - NOT APPLICABLE

 SIGNED BY : DATE :

  DAELIM'S PERMISSION TO PROCEED OR REVIEW TAKEN ON

  VENDOR PRINTS SHALL NOT RELIEVED VENDOR FROM ITS

  RESPONSIBILITIES OR LIABILITIES UNDER PURCHASE ORDER.

BJ

27.08.07 ISSUED FOR APPROVAL RKK DC BJ

03.10.07REVISED AS PER CUSTOMER

 COMMENTS DTD 17.09.07RKK DC

 APPROVEDDATE DESCRIPTION PREPARED REVIEWED

Page 2: d 1204014

8/12/2019 d 1204014

http://slidepdf.com/reader/full/d-1204014 2/2

 

D1204014 060604-P-004

sheet 2 of 2 

TECHNICAL SPECIFICATION FOR 440V SWITCHGEAR & MCC(REF: KOC PROJECT FOR REPLACEMENT OF 9 CRUDE OIL FILLING LINES) 

I:\USERS\DESIGN\FILES\KUWAIT\KOC\12704907\SUBMITTAL REV.2\D1204014-2.doc

440V LV Switchboards offered are cellular cubicle type, constructed from zinc coated,

 phosphated and chromated sheet steel of thickness 2 mm. Outgoing unit rated up to 400A

will be housed in individual drawout cell of the Switchboard and feeders rated more than

400A will be housed in fixed cell. The door of each cell is provided with pad lockable rotary

handle which is interlocked with the controlling switch in the cell in such a way that the door

can be opened only when the switch is in "OFF" position. The board will be totally enclosed,

dust and vermin proof. The Switchboard is front operated and rear accessible for cable

termination. Incoming and outgoing cable entry/exit will be at bottom.

All metal work would be cleaned to remove scale, oil and grease before painting. The steel

work would be painted using electrostatic guns and powder paint of Light Grey Shade 10-A-

03 to BS 4800. 

Busbars offered are hard drawn high conductivity electrolytic copper, tinned and insulated

with heat shrinkable PVC sleeves.

ACB’s & MCCBs offered are type tested by the manufacturer of the switching unit. Our

 busbar system is type tested for short circuit withstand capacity at KEMA Lab., Netherlands

and also our offered switchboard will be tested at our works for all routine tests as per

BS/IEC. No other tests are envisaged in our offer.

The switchboard is designed for indoor use (Degree of Protection: IP42). Bolts, screws etc.

are of Zinc Plated finish only.

Approximate Overall Dimension of Switchboards will be:

Item no. Description Width x Depth x Height (in mm)

1. 440V Switchboard for CMM 8680 x 900 x 2500

(105-MCC-101A,B)

**********