Current Transformers:
Ratio and Burden Testing
Prepared by Rob Reese,TESCOFor the Heartland Metermans Conference - March 31, 2014
![Page 2: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/2.jpg)
2
Self Contained vs. Transformer Rated
1S, 2S, 3S, 4S, 9S, 12S, 16S, 45S, etc., etc.
What’s the Difference?
Different Forms for Different Services and Applications
![Page 3: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/3.jpg)
3
Self Contained vs. Transformer Rated
Self Contained
(direct)
Transformer Rated
(indirect)
![Page 4: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/4.jpg)
4
Self Contained
Primarily Residential
(1S, 2S, 12S)
Relatively Low Current
Example: 100A
![Page 5: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/5.jpg)
5
Transformer Rated
Primarily Commercial/Industrial
(9S, 16S)Relatively High Current
Example: 400A
![Page 6: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/6.jpg)
6
Transformer Rated
Primarily Commercial/Industrial
(9S, 16S)Relatively High Current
Example: 400A
400:5
5A
![Page 7: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/7.jpg)
7
CT’s – Functions and Terminology
Ratio
Equivalent Circuit w/ losses
Conceptual Picture of a CT
As current is applied in the primary, it produces a magnetic flux in the core. This flux flows through the core and induces a current in the secondary
windings and circuit that is proportional to the number of turns.
![Page 8: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/8.jpg)
8
CT’s – Functions and Terminology
Ratio
For instance, a CT with a 400:5 ratio will produce 5A on the secondary, when 400A are applied to
the primary.
![Page 9: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/9.jpg)
9
CT’s – Functions and Terminology
Thermal Rating factor
A value representing the amount by which the primary current can be increased without exceeding the allowable temperature rise.
For instance, a RF of 4.0 at 30° ambient on a 400:5 ratio CT would allow for a primary current
up to 1600A.
![Page 10: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/10.jpg)
10
CT’s – Functions and Terminology
Accuracy Classifications and Burden
All CT’s fall within an accuracy class.
IEEE Standards have defined accuracy classes.
![Page 11: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/11.jpg)
11
CT’s – Functions and Terminology
Accuracy Classifications and Burden
Example: 0.3% @ B0.1, B0.2, B0.5
![Page 12: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/12.jpg)
12
CT’s – Functions and Terminology
Faceplate
![Page 13: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/13.jpg)
13
Transformer Rated
9S Meter Installation
5A
PHASE A
SOURCE
PHASE C
PHASE B
LOAD
400A
400A
400A
5A5A
![Page 14: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/14.jpg)
14
Transformer Rated
9S Meter Installation
5A
PHASE A
SOURCE
PHASE C
PHASE B
LOAD
400A
400A
400A
5A5A
![Page 15: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/15.jpg)
15
Meter Testing
9S Meter Installation
5A
PHASE A
SOURCE
PHASE C
PHASE B
LOAD
400A
400A
400A
5A5A
Isolate the Meter
from the Service
![Page 16: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/16.jpg)
16
Meter Testing
9S Meter Installation
5A
PHASE A
SOURCE
PHASE C
PHASE B
LOAD
400A
400A
400A
5A5A
? ? ?
![Page 17: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/17.jpg)
17
Meter Testing
9S Meter Installation
5A
PHASE A
SOURCE
PHASE C
PHASE B
LOAD
400A
400A
400A
5A5A
What if?
355:5
405:5
200:5
Shorted
etc.
![Page 18: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/18.jpg)
18
CT Testing
CT Testing is Important!
1) Test for correct ratio
2) Test for functionality at rated burdens
![Page 19: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/19.jpg)
19
Ratio Testing
Ratio of Primary Current to Secondary Current
5A
PHASE A
SOURCE LOAD
400A
400A
400A
5A5A
Calculate Ratio
![Page 20: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/20.jpg)
20
Burden Testing
Functionality with Burden Present on the Secondary Loop
PHASE A
Some burden will always be present – junctions, meter coils,
test switches, cables, etc.
CT’s must be able to maintain an accurate ratio with burden on
the secondary.
![Page 21: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/21.jpg)
21
Burden Testing
Functionality with Burden Present on the Secondary Loop
PHASE A
Some burden will always be present – junctions, meter coils,
test switches, cables, etc.
CT’s must be able to maintain an accurate ratio with burden on
the secondary.
![Page 22: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/22.jpg)
22
Burden Testing
Functionality with Burden Present on the Secondary Loop
Example Burden Spec:
0.3% @ B0.1, B0.2, B0.5or
There should be less than the 0.3% change in secondary current from initial
(“0” burden) reading, when up to 0.5Ohms of burden is applied
![Page 23: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/23.jpg)
23
Burden Testing
Functionality with Burden Present on the Secondary Loop
ANSI Burden Values0.1 Ohms
0.2 Ohms
0.5 Ohms
1 Ohms
2 Ohms
4 Ohms
8 Ohms
![Page 24: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/24.jpg)
24
Burden Testing
0.0000
1.0000
2.0000
3.0000
4.0000
5.0000
6.0000
0 2 4 6 8
0.3% @ B0.1, B0.2, B0.5Initial Reading = 5Amps
0.3% x 5A = 0.015A
5A – 0.015 = 4.985A
Burden Reading
0 5.0000
0.1 4.9999
0.2 4.9950
0.5 4.9900
1 4.9800
2 4.9500
4 4.0000
8 0.8000
![Page 25: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/25.jpg)
25
Burden Testing
4.9500
4.9600
4.9700
4.9800
4.9900
5.0000
5.0100
5.0200
5.0300
5.0400
5.0500
0 0.2 0.4 0.6 0.8 1
0.3% @ B0.1, B0.2, B0.5Initial Reading = 5Amps
0.3% x 5A = 0.015A
5A – 0.015 = 4.985AAt 0.5Ohms of Burden
the secondary current is still at 4.990A – Less than 0.3% change –
Good CT!Burden Reading
0 5.0000
0.1 4.9999
0.2 4.9950
0.5 4.9900
1 4.9800
2 4.9500
4 4.0000
8 0.8000
![Page 26: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/26.jpg)
26
Analog Testing
Application of Burden and Calculation
Manual reading of initial and post-burden secondary currents
![Page 27: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/27.jpg)
27
Digital Testing
Application of Burden and Calculation
Reads the initial current immediately prior to applying the selected burden
Applies the selected burden to the secondary
Reads the current immediately following current application
Calculates the percentages change
![Page 28: Current Transformers: Ratio & Burden Testing](https://reader035.vdocuments.site/reader035/viewer/2022062300/557599a9d8b42aff598b479f/html5/thumbnails/28.jpg)
28
Questions?