ABB SACE L.V.
Low-voltage current-limitingmoulded-case circuit-breakers
SACE Isomax S
690 V 125-630 A 200 kA (380/415 V)
Technical catalogue
649294/011 enJune '98
Annex to SACE Isomax S technical catalogue 649240
-
8/12/2019 Current Limiting En
2/66
GENERAL INDEX
Ordering codesSA C E Isomax S3X 48
SA C E Isomax S4X 52
SA C E Isomax S6X 54
A ccessories 56
Overalldimensions and
circuit diagramsSAC E Isomax
S3X-S4X 30
SA C E Isomax S6X 38
Required distances 46
C ircuit diagrams 46
Characteristiccurves
C urrent-limi tingcurves 24
Specific let-through
energy curves 26
Maincharacteristics
Electrical and generalcharacteristics of SA C E
Isomax S current-
limiting circuit-breakers
in accordance with IEC
947-2 standard 6
O vercurrent releases 8
Versions and
connections 10
A ccessories 14
C onstruction
characteristics 16
C onditions of use andpower loss values 18
Backup protection
(backup table) 20
PresentationSA C E Isomax S current-
limiting circuit-breakers:more solutions for every
possible need 2
Efficiency and flexibility
in very application 4
-
8/12/2019 Current Limiting En
3/66
Altitude[
m]
Ratedservice
voltage,
Ue[V~]
Ratedun
interruptedcur
rent,Iu
[A]
S4X2
50Iu
(4
Micropr
ocesso
r-based
PR211
code
release
3poles
S4X250
WMP
In=100
I
46779
S4X250
WMP
LI
46782
S4X250
WMP
In=160
I
46780
S4X250
WMP
LI
46783
S4X250
WMP
In=250
I
46781
S4X250
WMP
LI
46784
Presentatio
n
Ch
aracte
risti
cs
Cod
es
Dim
ensio
ns
CONTENTS
C
urves
Presentation
Main characteristics
Characteristic curves
Overall dimensions
Ordering codes
and circuit diagrams
-
8/12/2019 Current Limiting En
4/66
2
entation
G
SIL9101
SACE Isomax S current-limiting circuit-breakers:more solutions for every possible need
SACE Isomax S3X, S4X and S6Xcurrent-limiting circuit-breakers
The SAC E S3X - S4X - S6X models form a new range
of current limiting circuit-breakers, developed within
the SA C E Isomax S series of moulded-case circuit-
breakers.
These units are characterised by a rated service
voltage U e of 690 V a.c. , rated uninterrupted cur-
rents of 125 A to 630 A, service currents up to 630 A
and a rated limit short-circuit breaking capacity of
200 kA at 380/415 V a .c. and 75 kA at 690 V a .c.
T he circuit-break ers comply with the IE C 947-2
standards and are available in three and four-pole
fixed, plug-in and withdrawable versions.
The function of a current-limi ting circuit-breaker is to
the limit the specific let-through energy to a mini-
mum in the event of short-circuits, protecting the cir-
cuits and equipment downstream.
The breaking system adopted, which features two
fixed contacts for each pole, makes it possible to
provide extremely fast breaking for very high short-
circuit currents.In addition, the special shape of the breaking com-
ponents makes it possible to limit the peak fault cur-
rent to values that are significantly lower than those
of the short-circuit current in the point of installation.
Three models of circuit-
breakers conforming tothe IEC 947- 2 international
product standards
-
8/12/2019 Current Limiting En
5/66
3
Present
ISIS0001
that differ from those used for the corresponding au-
tomatic circuit-breakers and are listed in the chapter
entitled O rdering codes.
C onversely, the fixed parts of plug-in and withdraw-
able current-limiting circuit-breakers can be used
both for the current-limiting circuit-breakers them-
selves and for the corresponding SA C E S3 - S4 - S6
automatic circuit-breakers.
The same applies to the accessories. The S3X, S4X
and S6X current-limiting circuit-breakers can use the
same accessories as the corresponding automaticcircuit-break ers, which naturally retain the same elec-
trical characteristics.
The only exceptions are as follows:
the mechanical interlock plate for two vertically-
installed circuit-breakers
the bracket for mounting on a D IN channel.
The circuit diagrams for the SAC E S3X, S4X and S6X
circuit-breakers are the same as the corresponding
SA C E S3, S4 and S6 automatic circuit-breakers.
The current-limiting ci rcuit-break ers share the fol-
lowing characteristics with the automatic circuit-
breakers: the same standardised depth of 103.5 mm,
the same standardised widths of 105 (S3X-S4X) / 210
(S6X) mm for the three-pole versions and 140 (S3X-
S4X) / 280 (S6X) mm for the four-pole versions, the
same mounting holes for the plug-in and withdraw-
able versions and the same mounting holes on the
compartment door for all versions and all accesso-
ries.
The high opening speed significantly reduces the
electrodynamic stresses to which the circuit-break-
ers downstream are exposed in the event of a fault.
Integration with the SACE Isomax Sfamily
This range of current-limi ting circuit-breakers has
been conceived as a dedicated product for a spe-
cific use while at the same time being integrated in
the general SA C E Isomax S design.
This brings the user significant benefits, enabling
them to optimise stocks, standardise their support
and installation structures and rationalise circuit-
breaker selection thanks to a versatility that mak es it
possible to cover all their low-voltage application
requirements.
The new current-limi ting ci rcuit-break ers offer the
same benefits of modular construction as the SAC E
Isomax S series.
A ll the other versions can be created from the ba-
sic version using special conversion kits.
The conversion of the current-limi ting circuit-breaker
from a fixed part to a moving part for a plug-in orwithdrawable circuit-breaker uses conversion kits
Limited
let-thr
ough
current Prospectiv
e
short-
circuit
curren
t
Short-circuitcurrent
The increased contact
opening speed, dynamic
hiss action exerted by themagnetic field and the
structure of the arcing
chamber contribute to
extinguishing the arc in
the shortest possible time,
limiting the specific let-
through energy I2t and the
current peak
-
8/12/2019 Current Limiting En
6/66
4
entation
LN 160 S3X 200
G
SIL9103
G
SIL9102
G
SIL9104
G
SIL9105
Efficiency and flexibility in every application
Applications
These current-limiting circuit-breakers are suitable
for installation in all types of civi l, industrial and serv-
ice sector installations, as well as for electrical in-
stallations on board ships, in mines or on oil rigs, as
well as, generally speaking, in any installations where
high power generators and transformers make it pos-
sible for very high short-circuit currents of up to 200kA
at 380/415 V~ , 180 kA at 440 V~ and 75 kA at 690 V~
to occur.
The circuit-breakers can be positioned downstream
of the power supply either to provide general protec-
tion (installations, multi-user systems and electrical
lines) or for protecting electrical equipment (motors,
generators, transformers and capacitors).
They can also be fitted in systems where back-up
protection is required that allows the use of circuit-
breakers downstream which have a lower breaking
capacity than the prospective short-circuit current in
the point of installation.
The breaking capacities of the SAC E Isomax S cur-
rent-limiting circuit-breakers are higher than the bestvalues achieved by other units of this type.
SACE Limitor SACE Isomax S
LN 100 / LN 125 S3X 125
LN 160 / LN 200 S3X 200
LN 320 (setting 250 A) S4X 250
LN 320 S6X 400
LN 500 / LN 630 S6X 630
The electrical characteristics of SA C E Isomax S
current-limiting circuit-breakers make it
possible to establish equivalents and
comparisons with the circuit-breakers in the old
SA C E Limitor series to determine replacements
for the latter when upgrading an installation.
The construction characteristics of these circuit-breakers
enable them to offer outstanding reliability, an essential
requisite to guarantee continuity of service under even
the most severe installation conditions.
-
8/12/2019 Current Limiting En
7/66
5
Ch
aracte
Electrical and general characteristics of
SACE Isomax S - IEC 947-2 current-limiting circuit-breakers 6
Overcurrent releases 8
Versions and connections 10
Accessories 14
Construction characteristics 16
Conditions of use and power loss values 18
Backup protection 20
CONTENTS
Main characteristics
-
8/12/2019 Current Limiting En
8/66
6
acteristi
c
SACE Isomax S - IEC 947-2current-limiting circuit-breakers
Notes
1) The value of Ics is 25% lower at 500/690 V ( excluding S3X with setting R 32).2) For S3X with setting R 32, Icu (690 V~ ) = 50 kA and Ics = 100% Icu.
3) For three-pole circuit-breakers only.
4) Please ask for the related technical catalogue if you require further information on the motor-protection
circuit-breakers with PR212/M P releases.
Rated uninterrupted current, Iu [A]
Number of poles No.
Rated service voltage,Ue (a.c.) 50-60 Hz [V~]
Rated impulse withstand voltage, Uimp [kV]
Rated insulation voltage, Ui [V]
Test voltage at industrial frequency for 1 minute [V]
Rated limit short-circuit breaking capacity, Icu
(a.c.) 50-60 Hz 220/230 V~ [kA]
(a.c.) 50-60 Hz 380/415 V~ [kA]
(a.c.) 50-60 Hz 440 V~ [kA]
(a.c.) 50-60 Hz 500 V~ [kA]
(a.c.) 50-60 Hz 690 V~ [kA]
Rated duty short-circuit breaking capacity,Ics(1)
%Icu
Rated short-circuit making capacity (415 V~), Icm [kA]
Tripping time (440 V~ / 180 kA) [ms]
Use category (EN 60947-2)
Isolation behaviour
IEC 947-2, EN 60947-2
Releases thermomagnetic M fixed 10 lth, T adjustable (0.7 ... 1Ith)
magnetic only(3)
M only, adjustable (4 ... 12 Ith)
microprocessor-based PR211/P (I - LI)
PR212/P (LSI - LSIG)
PR212/MP (LRIU)(3)(4)
Interchangeability
Terminals(5)
F - fixed
P - plug-in
W - withdrawable(6)
Mechanical life No. operations / Operations per hour No.
Electrical life (415 V~) No. operations / Operations per hour No.
Basic dimensions F - fixed Width (3 / 4 poles) [mm]
Depth [mm]
Height [mm]
Weights F - fixed 3 / 4 poles [kg]
P - plug-in 3 / 4 poles [kg]
W - withdrawable 3 / 4 poles [kg]
-
8/12/2019 Current Limiting En
9/66
7
Ch
aracte
C
S
IL9107
C
S
IL9108
C
S
IL9106
S3X S4X S6X
125 - 200 250 400 - 630
3-4 3-4 3-4
690 690 690
8 8 8
800 800 800
3000 3000 3000
300 300 300
200 200 200
180 180 180
150 150 150
75 (2) 75 75
100% 100% 100%
440 440 440
3.5 3.5 3.5
A A A
yes yes yes
F - EF - ES - FCCu- FCCuAl- R - RC F - EF - ES - FCCu- FCCuAl- R - RC F - EF - FCCuAl- R - RC
EF - R EF - R
EF - R EF - R EF - HR - VR
25000 / 120 20000 / 120 20000 / 120
10000(125A)- 8000(200A)/ 120 8000 / 120 7000 / 60
105 / 140 105 / 140 210 / 280
103.5 103.5 103.5
255 339 406
3.6 / 4.8 5 / 7 15 / 20
6.3 / 8.7 8.2 / 10.7
7.1 /9.5 9 / 11.5 25.4 / 33.8
5) Please see pages 10-11 if you require further information on the types of terminals.6) Withdrawable circuit-breakers must be fitted with the front flange for the operating lever mechanism or
the accessories which are an alternative to it such as the rotary handle operating mechanism or motor
operator.
-
8/12/2019 Current Limiting En
10/66
8
acteristi
c
G
SIL9109
Thermomagnetic or magnetic onlyovercurrent releases
The characteristics of the thermomagnetic, magnetic
only and microprocessor-based electronic overcur-
rent releases are the same as those described in the
technical catalogue for the SA C E Isomax S circuit-
breakers (code number 649240).
The tables below show the values for the following
parameters for the different types of releases:
Thermomagnetic overcurrent releases
Circuit-breaker Phases L1 - L2 - L3 Neutral
S3X 125 S3X 200 Setting Thermal adjustment [A] Magnetic tripping [A] Setting[A] 0.7 ... 1 x Ith Im = 10 x Ith - min. 500 A [A]
R 32 19 ... 32 500 R 32
R 50 30 ... 50 500 R 50
R 80 48 ... 80 800 R 80
R 100 70 ... 100 1000 R 100
R 125 87.5 ... 125 1250 R 80
R 160 112 ... 160 1600 R 100
R 200 140 ... 200 2000 R 125
Magnetic only overcurrent releases (for three-pole circuit-breakers only)
Circuit-breaker Phases L1 - L2 - L3
S3X 125 S3X 200 Setting Magnetic adjustment [A][A] Im = 4 ... 12 x Ith
R 3 12 ... 36
R 5 20 ... 60
R 10 40 ... 120
R 25 100 ... 300
R 50 200 ... 600
R 100 400 ... 1200
R 125 500 ... 1500
R 160 640 ... 1920
R 200 800 ... 2400
SA C E S3X circuit-breaker
with thermomagnetic
overcurrent release
Ith - rated current of the thermomagnetic release at
a room temperature of 40C
Im - magnetic trip current
In - rated current of the electronic release
-
8/12/2019 Current Limiting En
11/66
9
Ch
aracte
G
SIL9110
Microprocessor-based electronicovercurrent releases
L = O verload protection function with related setting current (I1= 0.4-0.5-0.6-0.7-0.8-0.9-0.95-1 x In)
S = Short-circuit protection function with time-delay trip and related setting current ( I2= 1-2-3-4-6-8-10 x In - t2= 0.05 ... 0.5 s)
I = Short-circuit protection function with instantaneous trip and related setting current (I3= 1.5-2-4-6-8-10-12 x In)
G = Earth fault protection function with time-delay trip and related setting current (I4= 0.2-0.3-0.4-0.6-0.8-0.9-1 x I n - t4= 0.1 ... 0.8 s)
(1) Available upon request: neutral protection to 100% of phase L protection (ordering code 1SD A 0 37505 R1) .
SACE PR211/P - PR212/P microprocessor-based electronic overcurrent releases
Circuit-breaker Rated current Phases L1 - L2 - L3 Neutral (1)
S4X 250 S6X 400 S6X 630 of release L S I GIn [A] I1 [A] I2 [A] I3 [A] I4 [A] [A]
100 40 ... 100 100 ... 1000 150 ... 1200 20 ... 100 20 ... 50
160 64 ... 160 160 ... 1600 240 ... 1920 32 ... 160 32 ... 80
250 100 ... 250 250 ... 2500 375 ... 3000 50 ... 250 50 ... 125
320 128 ... 320 320 ... 3200 480 ... 3840 64 ... 320 64 ... 160
400 160 ... 400 400 ... 4000 600 ... 4800 80 ... 400 80 ... 200
630 252 ... 630 630 ... 6300 945 ... 7560 126 ... 630 126 ... 315
L = O verload protection function with related setting current (I1= 0.5-0.6-0.7-0.8-0.85-0.9-0.95-1 x In)
R = M otor lock protection function with related setting current (I5= 3-4-5-6-7-8-10 x I1 - t5= 1-4-7-10 s)
I = Short-circuit protection with related setting current ( I3= 6-7-8-9-10-11-12-13 x In)
U = Phase failure or unbalance protection function with related setting current ( Iu= 0.4 x I1 - t= 4 s)
(2) Please ask for the related technical catalogue if you require further information on the motor-protection circuit-breakers with SAC E
PR 212/MP releases.
SA C E S4X, S6X circuit-
breakers with SA C E
PR211/P, PR 212/P or
SAC E PR212/M P
microprocessor-based
overcurrent releases
SACE PR212/MP (2)microprocessor-based electronic motor-protectionovercurrent releases (for three-pole circuit-breakers only)
Circuit-breaker Rated current Phases L1 - L2 - L3S4X 250 S6X 400 S6X 630 of release L R I U
In [A] I1 [A] I5 [A] I3 [A] Iu [A]
100 50 ... 100 600 ... 1300
160 80 ... 160 960 ... 2080
200 100 ... 200 1200 ... 2600
320 160 ... 320 1920 ... 4160
400 200 ... 400 2400 ... 5200
630 315 ... 630 3780 ... 8190
3 ... 10 x I1 0,4 x I1
-
8/12/2019 Current Limiting En
12/66
10
acteristi
c
FC CuESEFF
front (1) extended spreaded front
front (2) extended for Cu cablesfront (4)
fixed (F) LTC
SACE S3X plug-in (P) LTC
withdrawable (W) LTC
fixed (F) LTC
SACE S4X plug-in (P) LTC
withdrawable (W) LTC
SACE S6Xfixed (F)
withdrawable (W) (3)LTC
Versions and connections
SA C E S3X, S4X and S6X current-limiting circuit-break-
ers are available in three-pole and four-pole fixed
(F), plug-in (P) and withdrawable (W) versions. It
should be noted that the fixed parts in the plug-in and
withdrawable versions are the same as the corre-
sponding S3, S4 and S6 automatic circuit-breakers.
In addition, as with the latter, the withdrawable cir-
cuit-breakers are always fitted with the front flange
for locks with a lever operating mechanism or, alter-
natively, with a rotary handle operating mechanismor motor operator.
The current-limiting circuit-breakers are character-
ised by a varied range of terminals that enable the
circuit-breaker to be connected to the installation in
the manner best suited to the installation require-
ments.
For some versions and type of terminals the supply
foresees the fitting of terminal covers (high or low).
These terminal covers form part of the circuit-break-
ers standard equipment.
In particular, low terminal covers are always required
for:
the fixed parts of plug-in or withdrawable circuit-
breakers
fixed circuit-breakers with threaded rear terminals
or spreaded extended front terminals,
and high terminal covers for:
fixed circuit-breakers with rear terminals for C u/A lcables.
The table below shows the basic version (fixed cir-
cuit-breaker with front terminals) and the various types
of terminals available with their related terminal cov-
ers.
If the terminal covers are not specified they must be
ordered separately.
HTC = high terminal covers, LTC = low terminal covers
( 1) Basic version of the fixed circuit-breaker
( 2) Basic version of fixed part for plug-in or withdrawable circuit-breakers
-
8/12/2019 Current Limiting En
13/66
11
Ch
aracte
VRHRRCRFC CuAI
G
SIL9111
G
SIL9112
G
SIL9113
F WP
SACE S3X
SACE S4X
SACE S6X
FIXED WITHDRAWABLEPLUG-IN
front threaded rear horizontal flat bar vertical flat bar
for Cu/Al cables rear for Cu/Al cables rear rear
LTC HTC
LTC
LTC
LTC HTC
LTC
LTC
LTC HTC
LTC LTC
( 3) The extended front terminals can only be fitted on the bottom of the fixed part of the withdrawable S6X circuit-breaker.
( 4) The terminal covers supplied for fixed S3X and S4X circuit-breakers with spreaded extended front terminals are always
supplied complete with separating partitions between the phases.
-
8/12/2019 Current Limiting En
14/66
12
acteristi
c
Versions and connections
The different types of terminals, which can be com-
bined in different ways with one another (top of one
type, bottom of another), enable one to connect the
circuit-breaker to the installation in the most suitable
way to meet the installations requirements.
We can distinguish between:
front terminals that allow one to connect cables
or busbars, working directly from the front of the
circuit-breaker.
rear terminalswhich enable the circuit-breakersto be installed in switchboards with rear access to
either cable or busbar connections.
Terminals are available for connecting busbars or
cables terminated with cable terminals, as are termi-
nals for connecting bare wires directly. T he informa-
tion required to make the connections is summa-
rised for each type of terminal. D ifferent flat bar di-
mensions and compositions are recommended for
busbar connections. The minimum depth required
of flat bars with different compositions from those rec-
ommended are also specified. For bare cable con-
nections, the minimum and maximum cable cross-
section areas that can be clamped in the terminals
are shown together with the terminal diameter.The tightening torque values for the screws on cable
terminals and the screws for connecting busbars to
flat bar terminals are also shown.
S3X-S4X
S3X-S4X S6X S6XS3X-S4X
S3X-S4X (fixed part) S6X (fixed part)
S3X-S4X
Front terminals, extended front terminals and spreadedfront terminals
Enable busbars or cables terminated with cable terminals to be connected.
versions flat bar tightening
pieces width [mm] thickness [mm] [Nm]
S3X 125 F-P-W 1 20 6 M8 9
S3X 200 F-P-W 1 20 6 M8 9
S4X 250 F-P-W 1 20 6 M8 9
S6X 400 F-W 2 40 5 (minimum) M10 9
S6X 630 F-W 2 40 5 (minimum) M10 9
Front terminals for copper cables
Enable bare copper cables to be connected directly to the circuit-breaker.
versions cross-section area ofcable terminal tightening
cables [mm2] [mm] [Nm]
S3X 125 F 1 6 ... 185 18 16
S3X 200 F 1 6 ... 185 18 16
S4X 250 F 1 6 ... 185 18 16
-
8/12/2019 Current Limiting En
15/66
13
Ch
aracte
S6X (fixed part)
S3X-S4X (fixed part)
S6X
S3X-S4X S6X
S3X-S4X S6X
AB
Front terminals for copper or aluminium cables
Enable copper or aluminium cables to be connected directly to the circuit-breaker.
versions cross-section area of cable terminal tightening
cables [mm2] [mm] [Nm]
S3X 125 F 1 35 ... 95 13.5 13.5
S3X 200 F 1 25 ... 150 17 31
S4X 250 F 1 25 ... 150 17 31
S6X 400 F 2 120 ... 240 21.5 31
S6X 630 F 2 120 ... 240 21.5 31
Rear terminals for copper or aluminium cables
Enable copper or aluminium cables to be connected directly to the circuit-breaker.
versions cross-section area of cable terminal tightening
cables minmax [mm2] [mm] [Nm]
S3X 125 F 1 50 ... 120 16 31
S3 X200 F 1 50 ... 120 16 31
S4X 250 F 1 50 ... 120 16 31
S6X 400 F 2 50 ... 150 21 31
S6X 630 F 2 50 ... 150 21 31
Threaded rear terminals
Enable busbars to be connected from behind.
versions length studs thread max flat bar cross-section area tightening
[mm] [mm] width [mm] thickness [mm] A [Nm] B [Nm]
S3X 125 F 55 100 M12 20 6 10 20
P - W 48 100 M12 20 6 10 20
S3X 200 F 55 100 M12 20 6 10 20
P - W 48 100 M12 20 6 10 20
S4X 250 F 55 100 M12 20 6 10 20
P - W 48 100 M12 20 6 10 20
S6X 400 F 68 68 M24 x 2 40 2 x 5 60 120
S6X 630 F 68 68 M24 x 2 40 2 x 5 60 120
Horizontal and vertical flat bar rear terminals
flat bar tightening
versions pieces width [mm] thickness [mm] [Nm]
S6X 400 W 2 40 5 M12 30
S6X 630 W 2 40 5 M12 30
S3X-S4X
-
8/12/2019 Current Limiting En
16/66
14
acteristi
c
G
SSC0
402
Accessories
The SA C E I somax S3X - S4X - S6X current-limiting
circuit-breakers can be fitted with all the accesso-
ries available for the corresponding SA C E I somax
S3 - S4 - S6 circuit-breakers described in the related
technical catalogue (code 649240). The only excep-
tions are the mechanical interlock plate for two verti-
cally-installed circuit-breakers and the bracket for
mounting on a DI N rail.
-
8/12/2019 Current Limiting En
17/66
15
Ch
aracte
-
8/12/2019 Current Limiting En
18/66
16
acteristi
c
C
SIS9027
G
SIL9114
G
SIL9115
C
SIS9031
Construction characteristics
SA C E S3X, S4X and S6X current-limiting circuit-break-
ers offer the highest standards of safety and operat-
ing reliability. T hanks to A BB SA C Es extensive expe-
rience in the field of L .V. moulded-case circuit-break-
ers and the tried and tested characteristics of the
SA C E Isomax S series from which the current-limit-
ing circuit-breakers have been developed.
The main construction characteristics of the current-
limiting circuit-breakers are listed below.
D ouble insulation with total segregation of the power
circuits and auxiliary circuits.
Easy to inspect, simply requiring one to remove the
cover with the circuit-breaker out of service, reduc-
ing operating times and installation down times.
M icroprocessor-based electronic releases ( for types
S4X and S6X) that meet the European Directives on
electromagnetic compatibility (EM C ) .
C ircuit-breaker can be racked in and out with the
compartment door closed, offering maximum opera-
tor safety and the possibility of building internal-arc-
proof switchboards.
-
8/12/2019 Current Limiting En
19/66
17
Ch
aracte
Conces. S.M .A. N 12/137 P.H. EDY C O LO R M onfalcone
C
SIL911
6
C
SIS9112
C
SIL9118
C
SIL9117
Isolation behaviour. In the open position, the circuit-
breaker guarantees isolation of the circuit in compli-
ance with IEC Standard 947-2.
The insulation distances are ample, ensuring there
are no leakage currents and guaranteeing the di-
electric strength against any overvoltages across the
input and output.
Vibration resistance and possibility of using the cir-
cuit-breaker for naval and aseismatic installations.
The rated characteristics of the circuit-breaker re-
main unchanged irrespective of its installation posi-
tion.
A fibreglass-reinforced synthetic resin moulded in-
sulating case, corrosion-proofed main metal com-
ponents and appropriate galvanising enable use in
damp - saline climates.
Protection grade IP20 for all versions (excluding the
terminals) and IP30 for the front parts of circuit-break-
ers installed in switchboards.
Possibility of achieving protection grade IP54 for cir-
cuit-breakers installed in switchboards with compart-
ment door-mounted crank handle operating mecha-
nisms by using special seals available to order.
-
8/12/2019 Current Limiting En
20/66
18
acteristi
c
C
SIL9119
Operating temperature
Conditions of use and power loss values
SA C E Isomax S3X - S4X - S6X current-limiting circuit-
breakers can be used in ambient conditions in which
the temperature of the surrounding atmosphere is
between -25 C and + 70 C.
C ircuit-breakers fitted with a thermomagnetic over-
current release have the thermal element set for a
reference temperature of +40 C .
The thermal tripping threshold for a given setting falls
at temperatures between + 40 C and + 70 C due to
the behaviour of the releases bimetal strip in relationto temperature.
C onversely, one needs to take an increase in the
thermal tripping threshold into account for tempera-
tures below +40 C (see table) .
The microprocessor-based electronic overcurrent re-
leases do not undergo any changes in performance
with changes in temperature. But one does need to
reduce the maximum overload protection setting (L)
to take into account the phenomena that occur in the
copper parts of the circuit breakers through which
the phase current passes (moving contacts, fixed
contacts and connection terminals) and which lead
to a fall in the rated uninterrupted current.
C ircuit-break er performance is not guaranteed for
temperatures above + 70 C .
In order to ensure continuity of operation for an in-stallation, one needs to carefully evaluate how to
keep the temperature within acceptable levels for
the operation of all the various devices concerned
and not just the circuit breakers by, for example, us-
ing forced ventilation in the switchboards and in the
rooms where they are installed.
R [A] 10 C 20 C 30 C 40 C 50 C 60 C 70 C
R 32 26 43 24 39 22 36 19 32 16 27 14 24 11 21
R 50 37 62 35 58 33 54 30 50 27 46 25 42 22 39
R 80 59 98 55 92 52 86 48 80 44 74 40 66 32 58
R 100 83 118 80 113 74 106 70 100 66 95 59 85 49 75
R 125 103 145 100 140 94 134 88 125 80 115 73 105 63 95
R 160 130 185 124 176 118 168 112 160 106 150 100 140 90 130
R 200 162 230 155 220 147 210 140 200 133 190 122 175 107 160
Temperature performance of S3X circuit-breaker
-
8/12/2019 Current Limiting En
21/66
19
Ch
aracte
C
S
IL9120
A ltitude [m] 2000 3000 4000
R ated service voltage, Ue [V~ ] 690 600 500
R ated uninterrupted current, Iu % Iu 100% 95% 90%
SA C E S3X - S4X - S6X circuit-breakers do not undergo any change in their rated
performance up to a height of 2000 m.
A s the height increases, changes occur in the properties of the atmosphere
regarding its composition, d ielectric capaci ty, cooling power and pressure.
The performance of the circuit-breakers therefore undergoes derating that can
essentially be measured in terms of the changes in the main parameters such as
the maximum rated operating voltage and rated uninterrupted current.
Power loss and voltage drop values
Altitude
Circuit-breaker Setting Current Power Voltage droploss per pole
[A] [W] [mV]
SACE S3Xwith thermomagnetic R 125 125 30.8 82release R 200 200 48 80
SACE S4Xwith PR211/LI R 250 250 60 80electronic release
SACE S6X
with PR211/LI R 400 400 80.4 67electronic release R 630 630 126.6 67
Note
The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and
four-pole fixed version apparatus. For the latter, the current of the neutral is nil by definition.
-
8/12/2019 Current Limiting En
22/66
20
acteristi
c
Backup protection(backup table at Ue = 400 V~)
Backup protection is required by C EI EN Standards
60947-2, A nnex A. C oordination can be used when
there are no selectivity requirements, enabling sav-
ings to be made (above all by using current-limiting
circuit-breakers upstream) with sizing the circuit-
breakers downstream.
CIRCUIT-BREAKER UPSTREAM
S270 S280/20 S280/25 S290 S500 LNA S1B S2B S1N S2N S3N S4N S5N S6N S2S S6S
In [A] < 32/63/100 125 160 125 160 250 250 630 800 160 800
Icu[kA] 15 20 25 15 50 50 16 16 25 35 35 35 35 35 50 50CIRCUIT-BREAKER DOWNSTREAM
10 S240 S240 S240 S240 S240
15S240 S240
S250 S250
16 S250 S250 S250 S250
S240 S250 S250 S270 S1B S1B S250 S1B
20 S250 S2B S2B S2B
S270
S240 S270 S270 S270 S280/20 S270
25S250 S280/20 S280/20 S1B
S270 S280/25 S2B
S1B
30S240 S240 S280/20 S280/25 S280/25 S280/20
S280/25 S1B S1N S1N S1N S280/25
35S1B S1N
S1N S2B
S2B
S250 S250 S1N
40
S270 S270 S1B S2NS280/20 S280/20 S1N S3N
50 S280/25 S280/25 S2B S4NS1B S1B S2N S5N
S1N S1N
65
85
100
130
150
170
200
-
8/12/2019 Current Limiting En
23/66
21
Ch
aracte
S250::::: S 250, S260, S270KS270::::: S270 (B-C-D ) , S280 ( In = 3 . .. 8 A ) ,
S280 (In = 50 ... 63 A) , S290
S280/20::::: S280 (In = 32 ... 40 A)S280/25::::: S280 (In = 10... 25 A)
The table below shows the backup protection avail-
able, with the related breaking capacities for the rated
voltage Ue= 400 V~ , between AB B moulded-case and
air low voltage circuit-breakers (SA C E I somax S ,
SA C E Limitor LN A and SAC E Emax) and pro Msys-
tem modular circuit-breakers.
In the interest of facilitating clear representation, the latter
must be read using the follow key:
S7S S3H S4H S5H S6H S7H S3L S4L S5L S6L S7L S3X S3X S4X S6X E2L E3L
1600 250 250 630 800 1600 250 250 630 800 1600 125 200 250 630 1600 2500
50 65 65 65 65 65 85 100 100 100 100 200 200 200 200 130 130
S240
S250 S250 S250 S250
S270 S1B S1B S270 S1B S1B S250 S250 S250 S1B
S2B S2B S2B S2B S2B
S270 S280/20 S270 S280/20 S270 S270 S270
S280/20 S280/20 S280/20 S280/20
S280/25 S280/25 S280/25 S280/25 S280/20 S280/25
S1B
S2B S280/25 S280/25
S3N S1B S1N S1N S3N S1B S1N S1N S3N S5N S6N
S4N S2B S4N S2B S4N
S5N S5N S5N
S6N S6N
S1N S2B S6N S1N S6NS1B
S1N S2N S2N S2N S2N S2N S1B S6S
S2N S2S S2S S2S S3N S3N S2B
S2S S3N S3N S3N S4N S4N
S3N S4N S4N
S5N
S1N S1N S5N S5H S1B
S2N S6S
S2S S6H
S3N
S3H
S2N S2S S2S S2B S2N S5H S6H
S2S S3H S3H S3N S6S S7SS3N S3L S3L S4N S6H S7H
S3H S4H S4H S7S
S3L S5H S7H
S1B S1N S2S S5L S6L
S2B S6L S7L
S7L
S1N
S1N S5N
S500 S500 LNA S3H
LNA LNA S2N S3L
S2N S2N S2S S4H
S2S S2S S3N S4L
S3N S3H S5H
S3H S3L S5L
S3L S6S
S6H
S6L
-
8/12/2019 Current Limiting En
24/66
22
acteristi
c
-
8/12/2019 Current Limiting En
25/66
23
Curves
Current-limiting curves 24
Specific let-through energy curves 26
CONTENTS
Characteristic curves
Note
For the time-current curves of SA C E S3X - S4X - S6X
current-limiting circuit-breakers please see the
information for the corresponding S3 - S4 - S6 types
in the technical catalogue for SAC E I somax S circuit-
breakers (code number 649240).
-
8/12/2019 Current Limiting En
26/66
24
s
Ip[ kA]
10
100
1
10 1001 Is[ kA]
S6X
S4X
S3X R160, R200
S3X R80, R100, R125
S3X R50
S3X R32
C
SIL8003
Current-limiting curves at 440 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers
The current-limiting and specific let-through energy
curves are shown below.
The characteristic of an automatic current-limi ting
circuit-breaker is represented by two distinct curves
that indicate the following respectively:
Current-limiting curves
the peak value Ip [k A ] of the limited current in
relation to the prospective symmetrical short-cir-
cuit current Is
the value of the specific let-through energy I2t[A 2s]
let through by the circuit-breaker in relation to the
uninterrupted symmetrical short-circuit current
Prospectivepeakcurrent
-
8/12/2019 Current Limiting En
27/66
25
Curves
10
100
1
Is[ kA]1
Ip[ kA]
S6X
S4X
S3X R50
S3X R32
S3X R80, R100, R125
S3X R160, R200
C
SIL8004
10 100
Current-limiting curves at 690 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers
Prospectivepeakcurrent
-
8/12/2019 Current Limiting En
28/66
26
s
I2t[A2s]
10 6
10 7
10 5
10 1001 Is[ kA]
S6X
S4X
S3X R50
S3X R32
S3X R80, R100, R125
S3X R160, R200
C
SIL8001
Specific let-through energy curves at 440 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers
Specific let-through energy curves
-
8/12/2019 Current Limiting En
29/66
27
Curves
10 1001 Is[ kA]
I2t[A2s]
10 6
10 7
10 5
S6X
S4X
S3X R50
S3X R32
S3X R160, R200
S3X R80, R100, R125
C
SIL8002
Specific let-through energy curves at 690 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers
-
8/12/2019 Current Limiting En
30/66
28
s
-
8/12/2019 Current Limiting En
31/66
29
Dim
ensi
SACE Isomax S3X - S4X 30
SACE Isomax S6X 38
Required distances 46
CONTENTS
Overall dimensions and circuit diagrams
Note
The information provided in the technical catalogue
for SA C E Isomax S circuit-breakers (code number
649240) also applies for the circuit and power
diagrams for the corresponding SA C E S3X - S4X -
S6X current-limiting circuit-breakers and the circuit
diagrams for connecting the releases and
accessories.
-
8/12/2019 Current Limiting En
32/66
-
8/12/2019 Current Limiting En
33/66
31
Dim
ensi
A B C D E F G H I L M N
S3X 35 70 224 156.75 17.5 179.75 270 R15 105 158.5 24 228
S4X 35 70 303,5 194.75 17.5 218 350 R15 105 196.75 24 307.5
Y
Y
X X
D
A
B
C
E
M5/5.5
X C
Y
A
B
E
X
F
G
Y
A
IB
H
Y
Y
M5/5.5
ACX
L
N
M
A A
D
X
M5/5.5
A A A
Y
Y
C
L
NXE
B
M
X
Y
Y
XX
80= =
112= =
112
=
=
142
=
=
7
DD
(3 POL)
(4 POL)
(3 POL)
(4 POL)
(3 POL)
(4 POL)
(3 POL) (4 POL)
CSIL0101
Mounting parts for fixed circuit-breaker
For terminals:Front for flat bars,Extended front,Front for cables,Spreaded extended front
Template for drilling sheet metal(minimum thickness of sheet metal: 3 mm)
For terminals for rear Cu/Alcables
For rear threaded terminals
Template for drilling compartment door and fitting flange(thickness of sheet metal: 2 mm)
-
8/12/2019 Current Limiting En
34/66
32
ensions
1
2
3
4
5
Y
Y
X
= =
161
=
=
117
3
105
=
=
X
1532
156.5
184.5
(4 POL)
(3 POL)
I
O
o
off
B
D
E EE
F
GC
1
3
2
3
A
5
5
(4 POL)
(3 POL)
161 X
= =
Y
Y
1.755.5
9674
B
A
G
E E E
F
H
D
105
=
=
X
27.5
3
167
1902
195.5
1
2
4
3
C5
5
AP
R
Q
S
31
83
N
I
L
M
A B C D E F G H I L M N O P Q R S
S3X 105 140 260 174.5 35 52.5 228 84 10 17.5 8.2 20 5 16 48 M12 100
S4X 105 140 344 212.75 35 52.5 307.5 84 10 13 8.2 20 5 20.5 48 M12 100
CSIL0102
Overall dimensionsSACE S3X - S4X
Plug-in circuit-breaker - withdrawable circuit-breaker
Fixed part
Moving part complete with IP20 protection class terminal covers
Flange for compartment door included in supply
Lock for compartment door (available upon request)
Tightening torque 1,1 Nm
Plug-in Withdrawable
Isolating distance
View A
Front for flat bars (up to 400 A) Threaded rear
NoteThe withdrawable circuit-breaker must be completed withone of the following accessories:- front flange for lever operating mechanism- rotary handle operating mechanism- motor operator
Plug-in - withdrawable terminals
-
8/12/2019 Current Limiting En
35/66
33
Dim
ensi
Y
Y
X
D
A
B
C
E
F
Y
Y
XX
80= =
112= =
112
=
=
142
=
=
7
(3 POL)
(4 POL)
Y
Y
X
D
I
E
G
HC
A
B
L
M
N
(3 POL)
(4 POL)
(3 POL)
(4 POL)
F
X
80
4
Y
Y
X
135
4563
81
125
126
=
=
72.5
Nr. 5 7
142
=
=
R min. 200
27.5
94
16
A B C D E F G H I L M N
S3X 70 105 100 52.25 25 M4-5 73.75 143 35 70 105 R14
S4X 82 117 135 65.75 41 M4-5 107.25 218 35 70 105 R14
CSIL0103
Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker
Template for drilling sheet metal support(minimum thickness of sheet metal: 3 mm)
For extended frontterminals
Template for drilling compartment door and fitting flange(thickness of sheet metal: 2 mm)
For rear threadedterminals
For plug-in circuit-breaker For withdrawable circuit-breaker
-
8/12/2019 Current Limiting En
36/66
-
8/12/2019 Current Limiting En
37/66
35
Dim
ensi
Y
B B B C B B B
A
E
105
F
G
Y
H
65
103.5
27.5
275
15 4 2
3
Y
Y
X X
M
N P N
O
Q
R
L
I
7
1
2
3
4
5
X D
A B C D E F G H I L M N O P Q R
S3X 350 35 66 265 135 172 255 12 227.5 116 324 95 R30 76 80.5 155
S4X 350 35 66 350 173.5 210 339 12 315 156 324 95 R30 76 113.5 230
CSIL0105
NoteSee the different versions for thedimensions of the circuit-breakers
Interlock between two horizontally-installed circuit-breakers
Isolating distance
Interlock device for S3-S4 circuit-breakers.It can also be used for horizontally-installedS3X-S4X circuit-breakers in fixed version withfront terminals or plug-in/withdrawable versionwith rear terminals
Template for drilling mounting holes in sheetmetal
Drilling template for all versions with rearterminals
Dimensions with four-pole withdrawableversion mounted on right
Tightening torque 3,7 Nm
-
8/12/2019 Current Limiting En
38/66
-
8/12/2019 Current Limiting En
39/66
-
8/12/2019 Current Limiting En
40/66
-
8/12/2019 Current Limiting En
41/66
39
Dim
ensi
Y
Y
XX
115= =
147= =
112
=
=
142
=
=
7
Y
Y
X X
M5/5.5
35
375
247.75
70
140
Y
Y
70
140
35
375
279.75
439
84
168
238
R18
M5/5.5
Y
Y
X 375
247.75
8
M5/5.5 35
379
249.75
70 70
70
X
Y
247.75
(3 POL)
(4 POL)
(3 POL)
(4 POL)
(3 POL)
(4 POL)
3 POL
X
109.75
109.75
Y
X375
247.75
M5/5.5
379
249.75
105 35
70 70 70
4 POL
8
35
109.75
109.75
CSIL0109
Mounting parts for fixed circuit-breaker
For terminals:Front for flat bars,Front extended,Front for cables
Template for drilling sheet metal support(minimum thickness of sheet metal: 3 mm)
For terminals for rear Cu/Al cables
Template for drillingcompartment door andfitting flange(thickness of sheet metal: 2 mm)For threaded rear terminals
-
8/12/2019 Current Limiting En
42/66
-
8/12/2019 Current Limiting En
43/66
41
Dim
ensi
Y
Y
X X
140
210
70
120
214
284
107
45.557.5
77.5
86.5
77.5
8.5 (M8)
Y
Y
X X
45
80.5
170
161
90
Nr. 7 7
177
39
9
=
=
R min 200
162.5101
19.75
= =
121
16
80
4(3 POL)
(4 POL
(3 POL)
(4 POL)
CSIL0111
Mounting parts for withdrawable circuit-breaker
Template for drilling sheet metal support(minimum thickness of sheet metal: 3 mm)
Template for drilling compartment door andfitting flange (thickness of sheet metal: 2 mm)
-
8/12/2019 Current Limiting En
44/66
42
ensions
Y
650
6
Y
1
2
3
4
61
5
70 70 70 120 70 70 70 5555
375
87
10.5
288
27.5
411
==
65
103.5
274.5
46
92.5
73
Y
525
X
233
73
X 350
9
R30
2843
X X
Y
Y
2 4
350
=
=
525= =
9
R30
331
=
=
101
28446
5
2
CSIL0112
Overall dimensionsSACE S6X
Accessories
Isolating distance
Interlock device
Drilling template for fittinginterlock plate
Drilling template for fixedversion with rear terminals
Drilling template for withdrawableversion with rear terminals
Dimensions with withdrawableversion mounted on right
Tightening torque 9 Nm
NoteSee the different versions fordimensions of the circuit-breakers
Interlock between two horizontally-installed circuit-breakers
-
8/12/2019 Current Limiting En
45/66
-
8/12/2019 Current Limiting En
46/66
-
8/12/2019 Current Limiting En
47/66
-
8/12/2019 Current Limiting En
48/66
46
ensions
I
O
o
off
C
B
D
E E
A F
CSIL0116
Installation of current-limiting circuit-breakers in compartment
Required distances
Circuit-breaker A B C D E F
3 POLE 4 POLE
S3X 161 196 340 51 30 25.5 112
S4X 161 196 430 58 29 25.5 112
S6X 275 345 500 60 30 30.5 152
A - B - F = Distances outside compartment
C - D - E = Distances inside compartment walls
-
8/12/2019 Current Limiting En
49/66
47
Cod
es
CONTENTS
Ordering codes
SACE Isomax S3X 48
SACE Isomax S4X 52
SACE Isomax S6X 54
Accessories 56
-
8/12/2019 Current Limiting En
50/66
48
es
C
SIL9106
S3X 125 Iu(40 C) = 125 A Icu(415 V) = 200 kA
Thermomagnetic code 1SDA0 R1
release 3 poles 4 polesF = Front terminals
S3X125 FF R 32 Im 500A 45197 45207
S3X125 F F R 50 Im 500A 45199 45209
S3X125 FF R 80 Im 800A 45201 45211
S3X125 FF R 100 Im 1000A 45203 45213
S3X125 F F R 125 Im 1250A 45205 45215
EF = Extended frontterminals
S3X125 F EF R 32 Im 500A 45217 45267
S3X125 F EF R 50 Im 500A 45219 45269
S3X125 F EF R 80 Im 800A 45221 45271
S3X125 F EF R 100 Im 1000A 45223 45273
S3X125 F EF R 125 Im 1250A 45225 45275
FC Cu = Front terminalsfor copper cables
S3X125 F FC Cu R 32 Im 500A 45227 45277
S3X125 F FC Cu R 50 Im 500A 45229 45279
S3X125 F FC Cu R 80 Im 800A 45231 45281
S3X125 F FC Cu R 100 Im 1000A 45233 45283
S3X125 F FC Cu R 125 Im 1250A 45235 45285
FC CuAl = Front terminalsfor copper/aluminium cables
S3X125 F FC CuAl R 32 Im 500A 45237 45287
S3X125 F FC CuAl R 50 Im 500A 45239 45289
S3X125 F FC CuAl R 80 Im 800A 45241 45291
S3X125 F FC CuAl R 100 Im 1000A 45243 45293
S3X125 F FC CuAl R 125 Im 1250A 45245 45295
R = Threaded rearterminals
S3X125 F R R 32 Im 500A 45257 45307
S3X125 F R R 50 Im 500A 45259 45309S3X125 F R R 80 Im 800A 45261 45311
S3X125 F R R 100 Im 1000A 45263 45313
S3X125 F R R 125 Im 1250A 45265 45315
RC = Rear terminalsfor cables
S3X125 FRC R 32 Im 500A 45247 45297
S3X125 F RC R 50 Im 500A 45249 45299
S3X125 F RC R 80 Im 800A 45251 45301
S3X125 F RC R 100 Im 1000A 45253 45303
S3X125 F RC R 125 Im 1250A 45255 45305
F= FIXED
Ordering codes
SACE Isomax S3Xcircuit-breaker
Magnetic only code 1SDA0 R1release 3 poles
F = Front terminalsS3X125 FF R 3 Im 12 ... 36A 45384
S3X125 F F R 5 Im 20 ... 60A 45385
S3X125 FF R 10 Im 40 ... 120A 45386
S3X125 FF R 25 Im 100 ... 300A 45387
S3X125 F F R 50 Im 200 ... 600A 45388
S3X125 F F R 100 Im 400 ... 1200A 45389
S3X125 F F R 125 Im 500 ... 1500A 45390
NoteThe S3X ci rcuit-break er with magnetic only release in the plug-in and withdrawable version are taken from the corresponding fixed version by
means of the conversion k its indicated on page 60 and cannot be ordered configured directly.
Im
Im
-
8/12/2019 Current Limiting En
51/66
49
Cod
es
C
SIL9106
S3X 200 Iu(40 C) = 200 A Icu(415 V) = 200 kA
Thermomagnetic code 1SDA0 R1
release 3 poles 4 polesF = Front terminals
S3X200 F F R 125 Im 1250A 46039 46045
S3X200 F F R 160 Im 1600A 46041 46047
S3X200 F F R 200 Im 2000A 46043 46049
EF = Extended frontterminals
S3X200 F EF R 125 Im 1250A 46051 46081
S3X200 F EF R 160 Im 1600A 46053 46083
S3X200 F EF R 200 Im 2000A 46055 46085
FC Cu = Front terminalsfor copper cables
S3X200 F FC Cu R 125 Im 1250A 46057 46087
S3X200 F FC Cu R 160 Im 1600A 46059 46089
S3X200 F FC Cu R 200 Im 2000A 46061 46091
FC CuAl = Front terminalsfor copper/aluminium cables
S3X200 F FC CuAl R 125 Im 1250A 46063 46093
S3X200 F FC CuAl R 160 Im 1600A 46065 46095
S3X200 F FC CuAl R 200 Im 2000A 46067 46097
R = Threaded rearterminals
S3X200 F R R 125 Im 1250A 46075 46105
S3X200 FR R 160 Im 1600A 46077 46107
S3X200 F R R 200 Im 2000A 46079 46109
RC = Rear terminalsfor cables
S3X200 F RC R 125 Im 1250A 46069 46099
S3X200 F RC R 160 Im 1600A 46071 46101
S3X200 F RC R 200 Im 2000A 46073 46103
Ordering codes
SACE Isomax S3Xcircuit-breaker
F= FIXED
Magnetic only code 1SDA0 R1release 3 poles
F = Front terminals
S3X200 FF R 125 Im 500 ... 1500A 46135
S3X200 F F R 160 Im 640 ... 1920A 48659
S3X200 F F R 200 Im 800 ... 2400A 48660
NoteThe S3X circuit-breaker with magnetic only release in the plug-in and withdrawable version are taken from the corresponding fixed version by
means of the conversion kits indicated on page 60 and cannot be ordered configured directly.
Im
Im
-
8/12/2019 Current Limiting En
52/66
50
es
C
SIL9106
C
SIL902
2
S3X 125 Iu(40 C) = 125 A Icu(415 V) = 200 kAThermomagnetic code 1SDA0 R1release 3 poles 4 poles
S3X125 P MP R32 Im 500A 45317 45327
S3X125 P MP R50 Im 500A 45319 45329
S3X125 P MP R80 Im 800A 45321 45331
S3X125 P MP R100 Im 1000A 45323 45333
S3X125 P MP R125 Im 1250A 45325 45335
S3X 200 Iu(40 C) = 200 A Icu(415 V) = 200 kA
Thermomagnetic code 1SDA0 R1release 3 poles 4 poles
S3X200 P MP R125 Im 1250A 46111 46117
S3X200 P MP R160 Im 1600A 46113 46119
S3X200 P MP R200 Im 2000A 46115 46121
Fixed parts
code 1SDA0 R13 poles 4 poles
EF = Extended frontterminals
S3 P FP EF 13539 13548
R = Threaded rearterminals
S3 P FP R 13547 13554
Ordering codes
SACE Isomax S3Xcircuit-breaker
P= PLUG -IN Moving part
Im
Im
-
8/12/2019 Current Limiting En
53/66
51
Cod
es
C
SIL9121
C
SIL902
1
Ordering codes
SACE Isomax S3Xcircuit-breaker
S3X 125 Iu (40 C) = 125 A Icu (415 V) = 200 kAThermomagnetic code 1SDA0 R1release 3 poles 4 poles
S3X125 W MP R32 Im 500A 45337 45347
S3X125 W MP R50 Im 500A 45339 45349
S3X125 W MP R80 Im 800A 45341 45351
S3X125 W MP R100 Im 1000A 45343 45353
S3X125 W MP R125 Im1250A 45345 45355
S3X 200 Iu (40 C) = 200 A Icu (415 V) = 200 kA
Thermomagnetic code 1SDA0 R1release 3 poles 4 poles
S3X200 W MP R125 Im1250A 46123 46129
S3X200 W MP R160 Im1600A 46125 46131
S3X200 W MP R200 Im2000A 46127 46133
Fixed parts
Im Max code 1SDA0 R13 poles 4 poles
EF = Extended frontterminals
S3 W FP EF 13555 13564
R = Threaded rearterminals
S3 W FP R 13563 13572
W= WITHDRAWABLE Moving part
Im
Im
-
8/12/2019 Current Limiting En
54/66
52
es
C
SIL9111
S4X 250 Iu(40 C) = 250 A Icu(415 V) = 200 kA
Microprocessor-based code 1SDA0 R1 code 1SDA0 R1
release 3 poles 4 poles 3 poles 4 polesF = Front terminals
S4X250 F F In=100 I 46582 46592 LSI 46586 46596
LI 46584 46594 LSIG 46588 46598
S4X250 F F In=160 I 46583 46593 LSI 46587 46597
LI 46585 46595 LSIG 46589 46599
S4X250 F F In=250 I 46524 46528 LSI 46526 46530
LI 46525 46529 LSIG 46527 46531
EF = Extended frontterminals
S4X250 F EF In=100 I 46657 46707 LSI 46663 46713
LI 46660 46710 LSIG 46668 46716
S4X250 F EF In=160 I 46658 46708 LSI 46664 46714
LI 46661 46711 LSIG 46669 46717
S4X 250 F EF In=250 I 46659 46709 LSI 46665 46715
LI46662 46712
LSIG46670 46718FC Cu = Front terminals
for copper cables
S4X250 F FC Cu In=100 I 46671 46719 LSI 46677 46725
LI 46674 46722 LSIG 46680 46728
S4X250 F FC Cu In=160 I 46672 46720 LSI 46678 46726
LI 46675 46723 LSIG 46681 46729
S4X250 F FC Cu In=250 I 46673 46721 LSI 46679 46727
LI 46676 46724 LSIG 46682 46730
FC CuAl = Front terminalsfor copper/aluminium cables
S4X 250 F FC CuAl In=100 I 46830 46842 LSI 46836 46848
LI 46833 46845 LSIG 46839 46851
S4X250 F FC CuAl In=160 I 46831 46843 LSI 46837 46849
LI 46834 46846 LSIG 46840 46852
S4X250 F FC CuAl In=250 I 46832 46844 LSI 46838 46850
LI 46835 46847 LSIG 46841 46853R = Threaded rearterminals
S4X250 F R In=100 I 46695 46743 LSI 46701 46749
LI 46698 46746 LSIG 46704 46752
S4X250 FR In=160 I 46696 46744 LSI 46702 46750
LI 46699 46747 LSIG 46705 46753
S4X 250 F R In=250 I 46697 46745 LSI 46703 46751
LI 46700 46748 LSIG 46706 46754
RC = Rear terminalsfor cables
S4X250 F RC In=100 I 46683 46731 LSI 46689 46737
LI 46686 46734 LSIG 46692 46740
S4X250 F RC In=160 I 46684 46732 LSI 46690 46738
LI 46687 46735 LSIG 46693 46741
S4X250 F RC In=250 I 46685 46733 LSI 46691 46739
LI 46688 46736 LSIG 46694 46742
Ordering codes
SACE Isomax S4Xcircuit-breaker
F= FIXEDPR212PR211
-
8/12/2019 Current Limiting En
55/66
53
Cod
es
C
SIL9111
C
SIL9122
C
SIL9024
C
S
IL9023
S4X 250 Iu(40 C) = 250 A Icu(415 V) = 200 kAMicroprocessor-based code 1SDA0 R1 code 1SDA0 R1release 3 poles 4 poles 3 poles 4 poles
S4X250 P MP In=100 I 46755 46767 LSI 46761 46773
LI 46758 46770 LSIG 46764 46776
S4X250 P MP In=160 I 46756 46768 LSI 46762 46774
LI 46759 46771 LSIG 46765 46777
S4X250 P MP In=250 I 46757 46769 LSI 46763 46775
LI 46760 46772 LSIG 46766 46778
Fixed parts
code 1SDA0 R13 poles 4 poles
EF = Extended frontterminals
S4 P FP EF 13612 13621
R =Threaded rearterminals
S4 P FP R 13620 13629
Ordering codes
SACE Isomax S4Xcircuit-breaker
P= PLUG -IN
W= WITHDRAWABLE
S4X 250 Iu(40 C) = 250 A Icu(415 V) = 200 kA
Microprocessor-based PR211 code 1SDA0 R1 PR212 code 1SDA0 R1release 3 poles 4 poles 3 poles 4 poles
S4X250 W MP In=100 I 46779 46791 LSI 46785 46797
LI 46782 46794 LSIG 46788 46800
S4X250 W MP In=160 I 46780 46792 LSI 46786 46798
LI 46783 46795 LSIG 46789 46801
S4X 250 W MP In=250 I 46781 46793 LSI 46787 46799
LI 46784 46796 LSIG 46790 46802
Fixed parts
code 1SDA0 R13 poles 4 poles
EF = Extended frontterminals
S4 W FP EF 13630 13639
R =Threaded rearterminals
S4 W FP R 13638 13647
Moving part
Moving part
PR212PR211
PR212PR211
-
8/12/2019 Current Limiting En
56/66
54
es
C
S
IL9108
S6X 400 Iu(40 C) = 400 A Icu(415 V) = 200 kA
Microprocessor-based code 1SDA0 R1 code 1SDA0 R1
release 3 poles 4 poles 3 poles 4 polesF = Front terminals
S6X400 FF In=320 I 47595 47601 LSI 47597 47603
LI 47596 47602 LSIG 47598 47604
S6X400 F F In=400 I 46534 46538 LSI 46536 46540
LI 46535 46539 LSIG 46537 46541
EF = Extended frontterminals
S6X400 F EF In=320 I 47661 47693 LSI 47665 47697
LI 47663 47695 LSIG 47667 47699
S6X400 F EF In=400 I 47660 47692 LSI 47664 47696
LI 47662 47694 LSIG 47666 47698
FC CuAl =Front terminalsfor copper/aluminium cables
S6X400 F FC CuAl In=320 I 47669 47701 LSI 47673 47704
LI 47671 47703 LSIG 47675 47707
S6X400 F FC CuAl In=400 I 47668 47700 LSI 47672 47705
LI 47670 47702 LSIG 47674 47706
R = Threaded rearterminals
S6X400 F R In=320 I 47685 47717 LSI 47689 47721
LI 47687 47719 LSIG 47691 47723
S6X 400 F R In=400 I 47684 47716 LSI 47688 47720
LI 47686 47718 LSIG 47690 47722
RC = Rear terminalsfor cables
S6X400 F RC In=320 I 47677 47709 LSI 47681 47713
LI 47679 47711 LSIG 47683 47715
S6X400 F RC In=400 I 47676 47708 LSI 47680 47712
LI 47678 47710 LSIG 47682 47714
S6X 630 Iu(40 C) = 630 A Icu(415 V) = 200 kA
Microprocessor-based code 1SDA0 R1 code 1SDA0 R1release 3 poles 4 poles 3 poles 4 poles
F = Front terminals
S6X 630 FF In=630 I 46560 46564 LSI 46562 46566
LI 46561 46565 LSIG 46563 46567
EF = Extended frontterminals
S6X630 F EF In=630 I 47724 47744 LSI 47726 47746
LI 47725 47745 LSIG 47727 47747
FC CuAl =Front terminalsfor copper/aluminium cables
S6X630 F FC CuAl In=630 I 47729 47749 LSI 47731 47751
LI 47730 47750 LSIG 47732 47752
R = Threaded rearterminals
S6X630 F R In=630 I 47739 47759 LSI 47741 47761
LI 47740 47760 LSIG 47742 47762
RC =Rear terminalsfor cables
S6X630 F RC In=630 I 47734 47754 LSI 47736 47756
LI 47735 47755 LSIG 47737 47757
Ordering codes
SACE Isomax S6Xcircuit-breaker
F= FIXEDPR212PR211
PR212PR211
-
8/12/2019 Current Limiting En
57/66
55
Cod
es
C
S
IL9123
PSIS9618
PSIS9619
S6X 400 Iu (40 C) = 400 A Icu (415 V) = 200 kAMicroprocessor-based PR211 code 1SDA0 R1 PR212 code 1SDA0 R1release 3 poles 4 poles 3 poles 4 poles
S6X400 W MP In=320 I 47633 47643 LSI 47637 47647
LI 47635 47645 LSIG 47641 47649
S6X400 W MP In=400 I 47632 47642 LSI 47636 47646
LI 47634 47644 LSIG 47640 47648
S6X 630 Iu(40 C) = 630 A Icu(415 V) = 200 kA
Microprocessor-based PR211 code 1SDA0 R1 PR212 code 1SDA0 R1release 3 poles 4 poles 3 poles 4 poles
S6X630 W MP In=630 I 47650 47655 LSI 47652 47657
LI 47651 47656 LSIG 47653 47658
Fixed parts
Im Max code 1SDA0 R13 poles 4 poles
VR = Vertical flat-barrear terminals
S6 W FP VR 13972 13981
HR = Horizontal flat-barrear terminals
S6 W FP HR 13968 13977
Ordering codes
SACE Isomax S6Xcircuit-breaker
W= WITHDRAWABLE Moving part
PR212
PR212
PR211
PR211
-
8/12/2019 Current Limiting En
58/66
56
es
C
SIS9034
C
SIS9033
PSIS9661
PSIS9634
Ordering codes
SACE Isomax S accessories
Auxiliary releases
Shunt opening releasesType code 1SDA0 R1
S3X-S4X S6X
12 V d.c. 23403 23404
24 V a.c. / d.c. 13781 14136
48 V a.c. / d.c. 13782 14137
60 V a.c. / d.c. 23405 23406
110...120 V a.c. - 110...125 V d.c. 13783 14138
220...240 V a.c. - 220...250 V d.c. 13785 14140
380...400 V a.c. 13786 14141
480 V a.c. 37512 37514
Undervoltage releases
Type code 1SDA0 R1S3X-S4X S6X
24 V a.c. 13842 14188
48 V a.c. 13843 14189
60 V a.c. 23346 23347
110...127 V a.c. 13844 14190
220...250 V a.c. 13846 14192
380...440 V a.c. 13847 14193
480 V a.c. 37513 37515
24 V d.c. 13833 14179
48 V d.c. 13835 14181
60 V d.c. 13836 14182
110...125 V d.c. 13838 14184
220...250 V d.c. 13839 14185
Time-lag undervoltage releases
Type code 1SDA0 R1
S3X-S4X S6X
110 - 220 V a.c. (release + time-lag device) 13840 14186
Connectors for auxiliary releases
Type code 1SDA0 R1
S3X-S4X-S6X
for fixed circuit-breaker - L=1m 13865
for fixed circuit-breaker - L=2m 37523
for plug-in or withdrawable circuit-breaker - L=1m 13866
extension for testing auxiliary circuits with the circuit-breaker racked out 25552
-
8/12/2019 Current Limiting En
59/66
57
Cod
es
PSIS9630
PSIS9631
PSIS9632
PSIS9633
PSIS9629
Ordering codes
SACE Isomax S accessories
Electrical signalling
Auxiliary contactsType code 1SDA0 R1
S3X-S4X S6X
2 open/closed change-over contacts 13856 23366
1 open/closed change-over contact and 1 tripped release signal 13575 23332
2 open/closed change-over contacts and 1 tripped release signal 25773
Auxiliary contacts for digital signals
Type code 1SDA0 R1
S3X-S4X S6X
2 open/closed change-over contacts 25544 25774
1 open/closed change-over contact and 1 tripped release signal 25545 25775
2 open/closed change-over contacts and 1 tripped release signal 25776
Accept contacts and connectors
Type code 1SDA0 R1
S3X-S4X-S6X
accept contact and connector for undervoltage release 25551
Connectors for auxiliary contacts
Type code 1SDA0 R1
S3X-S4X-S6X
for fixed circuit-breaker - L=1m 13863
for fixed circuit-breaker - L=2m 37522
for plug-in or withdrawable circuit-breaker - L=1m 13864
extension for testing auxiliary circuits with the circuit-breaker racked out 25553
Motor operating mechanism
Direct action
Type code 1SDA0 R1
S3X-S4X
24 V d.c. 13873
48...60 V d.c. 13874
100...127 V a.c. - 100...125 V d.c. 13875
220...240 V a.c. - 220...250 V d.c. 13876
380 V a.c. 13877
440 V a.c. 14545
Stored energy
Type code 1SDA0 R1
S6X
24 V d.c. 14029
48 V d.c. 14030
60 V d.c. 23348
110 V a.c. / d.c. 23349
120...127 V a.c. / d.c. 14031
220...250 V a.c. / d.c. 14032
380 V a.c. 14033
Connectors for motor operating mechanism and auxiliary contacts
Type code 1SDA0 R1
S3X-S4X-S6Xfor fixed circuit-breaker - L=1m 13857
for fixed circuit-breaker - L=2m 37524
for plug-in or withdrawable circuit-breaker - L=1m 13858
extension for testing auxiliary circuits with the circuit-breaker racked out 25554
-
8/12/2019 Current Limiting En
60/66
58
es
PSIS9635
PSIS9636
PSIS9637
PSIS9645
PSIS9640
Ordering codes
SACE Isomax S accessories
Operating mechanism and locks
Direct-mounted rotary-handle operating mechanism
Type code 1SDA0 R1
S3X-S4X S6Xfor fixed/plug-in circuit breakers 13867 14026
for withdrawable circuit breakers 13868 14027
emergency for fixed or withdrawable circuit-breakers 13870
Rotary handle operating mechanism with transmission
Type code 1SDA0 R1
S3X-S4X S6X
compartment door, adjustable depth (Lmax= 300 mm) for fixed or plug-in 13869
compartment door, adjustable depth (Lmax= 500 mm) for fixed or withdrawable 14028
compartment door, emergency, adjustable depth (Lmax= 300 mm) for fixed or plug-in 13871
compartment door, emergency, adjustable depth (Lmax= 500 mm) for fixed 46569
remote transmission rod with adjustable depth (Lmax= 500 mm) 25427
Front flange for operating lever mechanism
Type code 1SDA0 R1
S3X-S4X S6X
for fixed or plug-in 13889 14035
for withdrawable 13890 14036
Key lock for locking in the open position
Type code 1SDA0 R1S3X-S4X S6X
for motor operating mechanism - a different key for each circuit-breaker 13883 13885
for motor operating mechanism - the same key for sets of circuit-breakers 13884 13886
for motor operating mechanism against manual operation
(a different key for each circuit-breaker) 36245
for front flange / rotary handle - a different key for each circuit-breaker 13881 13881
for front flange / rotary handle - the same key for sets of circuit-breakers 13882 13882
Locks
Type model code 1SDA0 R1
Compartment door lock for front flange for locks / rotary handle oper. mech. S3X-S4X-S6X 13880
Tamper-proof lock for thermal releases S3X 25548
Mechanical interlock across two circuit-breakers
Type model code 1SDA0 R1
for horizontal installation (excluded ES terminals) S3X 23330
for horizontal installation (excluded ES terminals) S4X 13690
for horizontal installation (excluded ES terminals) S6X 14024
-
8/12/2019 Current Limiting En
61/66
59
Cod
es
PSIS9663
PSIS9641
PSIS9642
PSIS9643
PSIS9632
Connection terminalsType code 1SDA0 R1
3 pieces 4 pieces 6 pieces 8 piecesEF = Extended front terminals
S3X-S4X 23353 23359 13596 13597
S6X 23379 23389 13920 13921
ES = Spreaded extended front terminals
S3X-S4X 46517 46518 46515 46516
FC Cu = Front terminals for copper cables
S3X-S4X 23354 23360 13598 13599
FC CuAl = Front terminals for copper - aluminium cables
S3X 125 (1x95 mm2) 23356 23362 13602 13603
S3X 200 - S4X 250 (1x150 mm2) 23357 23363 20293 20294
S6X (2x240 mm2) 23380 23390 13922 13923
R = Threaded rear terminals
S3X-S4X 23352 23365 13606 13607
S6X 23382 23392 13960 13961
R Res.Cur. = Threaded rear terminals for residual-current release in vertical installationS3X 25543
RC = Rear terminals for copper or aluminium cables
S3X-S4X (1x120 mm2) 23358 23364 13604 13605
S6X (2x150 mm2) 23381 23391 13924 13925
Insulating terminal covers
Type code 1SDA0 R1
3 poles 4 poles
high for fixed
S3X-S4X 13695 13696
S6X 14040 14041
low for fixed and moving part of plug-in or withdrawable
S3X-S4X 13693 13694S6X 14038 14039
Screws for sealing terminal covers
Type code 1SDA0 R1
S3X-S4X-S6X 13699
Ordering codes
SACE Isomax S accessories
-
8/12/2019 Current Limiting En
62/66
60
es
PSIS9648
PSIS9650
PSIS9649
PSIS9647
PSIS9651
PSIS
9652
Ordering codes
SACE Isomax S accessories
Accessories for microprocessor-basedovercurrent releaseType model code 1SDA0 R1
Signalling unit SACE PR212/K S4X 13854
Signalling unit SACE PR212/K S6X 14200
Dialog unit SACE PR212/D + Actuator unit SACE PR212/T S4X 48003
Dialog unit SACE PR212/D + Actuator unit SACE PR212/T S6X 48004
Current transformer for neutral conductor outside circuit-breaker S4X (In = 100A) 37114
Current transformer for neutral conductor outside circuit-breaker S4X (In = 160A) 37115
Current transformer for neutral conductor outside circuit-breaker S4X (In = 250A) 37117
Current transformer for neutral conductor outside circuit-breaker S6X (In = 630A) 25777
X3 connector for tripped release signal
and neutral protection for fixed circuit-breaker with PR211/P, PR212/P - LSI S4X-S6X 13702X3, X4 connector for tripped release signal
and neutral protection for f ixed circuit-breaker with PR212/P - LSIG S4X-S6X 13704
X3 connector for tripped release signal and neutral protection
for plug-in or withdrawable circuit-breaker with PR211/P, PR212/P - LSI S4X-S6X 13703
X3, X4 connector for tripped release signal and neutral protection
for plug-in or withdrawable circuit-breaker with PR212/P - LSIG S4X-S6X 13705
SACE TT1 test unit S4X-S6X 37121
Conversion kits (for current-limiting circuit-breakers only)
Kit for converting from fixed circuit-breaker to moving part of
plug-in circuit-breaker
Type code 1SDA0 R1
3 poles 4 poles
S3X 46519 46520
S4X 46511 46512
Kit for converting from fixed circuit-breaker to moving part of
withdrawable circuit-breaker
Type code 1SDA0 R1
3 poles 4 poles
S3X 46521 46522
S4X 46514 46513
S6X 47619 47620
Notes The contact isolators on the fixed parts of S3-S4 circuit-breakers (p lug-in and withdrawable versions) have been modified (during 1997) to
make them suitable for the movi ng pa rts of S3X-S4X current-limiting circuit-breakers.
The new contact isolators are supplied in the conversion ki t for S3X-S4X models (used for converting them into moving parts) . T he operation
is simple to perform and can be carried out by the user with the help of the instructions supplied. It enables one to maintain the compatibility
of S3X-S4X models and S3-S4 fixed parts that are already stored in the warehouse or installed.
The modification is not required on S3X or S4X current-limiting ci rcuit-breakers that are supplied complete with fixed parts or on fixed parts
purchased after February 1998.
The contact isolators can be supplied as spare parts if required.
The existing fixed parts for S3-S4 circuit-break ers are not compatible with current-limi ting apparatus if they are fitted with front terminals for
copper cables FC C u.
-
8/12/2019 Current Limiting En
63/66
61
Cod
es
PSIS9655
PSIS9654
PSIS9656
PSIS9664
Accessories for fixed part of plug-in or withdraw-
able circuit-breakers
Rails
Type code 1SDA0 R1
S3X-S4X
Rail for preparing the fixed part of a plug-in circuit-breaker for use
as the fixed part of a withdrawable circuit-breaker 13692
Terminals for the fixed parts of plug-in or withdrawable circuit-
breakers
Type code 1SDA0 R1
3 pieces 4 piecesEF = Extended front terminals
S3X-S4X 13650 13651
S6X (with terminals mounted only below) 13984 13985
R = Threaded rear terminals
S3X-S4X 13654 13655
HR = Horizontal flat-bar rear terminals
S6X 13986 13987
VR = Vertical flat-bar rear terminals
S6X 13988 13989
Position contacts
Type code 1SDA0 R1
S3X-S4X-S6X
contacts for signalling circuit-breaker racked out 13859
contacts for signalling circuit-breaker racked out for digital signals 25546
contacts for signalling circuit-breaker racked in 13860
contacts for signalling circuit-breaker racked in for digital signals 25547
Lock for fixed part of withdrawable circuit-breakers
Type code 1SDA0 R1
S3X-S4X-S6X
key lock for locking in racked in / out position - different key for each c.b. 25434
key lock for locking in racked in / out position - same key for sets of c.bs. 25435
padlock device 13872
Ordering codes
SACE Isomax S accessories
-
8/12/2019 Current Limiting En
64/66
62
es
PSIS9657
PSIS9665
PSIS9660
PSIS9659
Ordering codes
SACE Isomax S accessories
Installation accessories
Bracket for mounting on DIN rail
Type code 1SDA0 R1
3 poles 4 poles
For DIN rail DIN EN 50023 (complete with DIN front flange H=45 mm)
S3X 13576 13577
S4X 13700 13701
IP54 protection
Type code 1SDA0 R1
S3X-S4X-S6X
for adjustable-depth rotary handle operating mechanism on door 13891
Residual-current releases
SACE RC211, SACE RC212
Type code 1SDA0 R1
RC211/3 RC212/3
For S3X circuit-breaker (horizontal installation) 20288 20290
For S3X circuit-breaker (vertical installation) 20289 20291
SACE RCQ
Type code 1SDA0 R1
release and closed toroid - diameter 60 mm 37388
release and closed toroid - diameter 110 mm 37389
release and opening toroid - diameter 110 mm 37390
release and opening toroid - diameter 180 mm 37391
release and opening toroid - diameter 230 mm 37392
release only 37393
closed toroid only - diameter 60 mm 37394
closed toroid only - diameter 110 mm 37395
opening toroid only - diameter 110 mm 37396
opening toroid only - diameter 180 mm 37397
opening toroid only - diameter 230 mm 37398
-