cto csls charm cabinets (european standards)

10
September 2020 Product Data Sheet DeltaV SIS Process Safety System CTO CSLS CHARM Cabinets (European Standards) Front View Rear View CTO CSLS CHARM Cabinet. Delivers “Electronic Marshalling” enabled by CHARMs technology Reduce system footprint Eliminate I/O home run cables Significantly reduce cabinet design engineering Fully documented package Introduction The DeltaV SIS Configure-To-Order (CTO) CHARMs Smart Logic Solver (CSLS) Cabinets provide an off-the-shelf solution for faster project execution and reduced installation costs. CTO CSLS Cabinets are factory tested and ready for installation in technical rooms. Electronic Marshalling eliminates traditional I/O design tasks and allows field wiring to start long before safety strategies are finalized.

Upload: others

Post on 27-Nov-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CTO CSLS CHARM Cabinets (European Standards)

September 2020Product Data SheetDeltaV SIS Process Safety System

CTO CSLS CHARM Cabinets (European Standards)

Front View Rear View

CTO CSLS CHARM Cabinet.

� Delivers “Electronic Marshalling” enabled by CHARMs technology

� Reduce system footprint

� Eliminate I/O home run cables

� Significantly reduce cabinet design engineering

� Fully documented package

Introduction

The DeltaV SIS™ Configure-To-Order (CTO) CHARMs Smart Logic Solver (CSLS) Cabinets provide an off-the-shelf solution for faster project execution and reduced installation costs.

CTO CSLS Cabinets are factory tested and ready for installation in technical rooms. Electronic Marshalling eliminates traditional I/O design tasks and allows field wiring to start long before safety strategies are finalized.

Page 2: CTO CSLS CHARM Cabinets (European Standards)

September 2020CTO CSLS CHARM Cabinets (European Standards)

www.emerson.com/deltav 2

Benefits

Delivers “Electronic Marshalling” enabled by CHARMs technology: The CTO CSLS Cabinets offer the full benefits of Electronic Marshalling. The individual channels can be defined for any combination of field signal type, as required by the safety equipment. This allows for 100 % utilization of channels, regardless of the I/O signal mix. Late changes are easily accommodated with minimal reengineering and no rewiring.

Reduced system footprint: Equipment room footprint is reduced by eliminating the traditional marshalling cabinets with cross wiring to traditional I/O cards.

Significantly reduce cabinet design engineering: The CTO CSLS cabinets are pre-engineered, and factory tested. The I/O flexibility allows the same design to serve a wide variety of I/O signals, conditioned individually by the CHARM. Field wiring design is complete at the terminal block.

Fully documented package: Each cabinet is supplied with full documentation and engineering drawings showing internal lay- out, bill of materials and internal wiring. They are designed to meet local building code and industry best practices in order to deliver proven functionality with minimal costs.

Product Description

The CTO CSLS Cabinets offering comprises a range of pre-engineered solutions based on industry standard, preinstalled with CHARM I/O and related equipment, ready to be installed in an equipment room and connected to safety instrumentation or equipment.

The cabinets are typical, free standing enclosures intended for floor mounting in equipment room areas, where temperature and humidity are controlled within the requirements for computer/electronic equipment. They come ready to receive incoming plant AC power. All internal wiring to power distribution components and grounding conductors has been tested at the factory.

Before delivery, each cabinet undergoes a full in-house inspection, to assure that it is fully operational before shipping directly to site. Electronic Marshalling eliminates the need for any internal cross wiring and I/O rationalization there is typically no need for FAT at a staging facility.

These cabinets can be ordered and delivered directly together with the DeltaV SIS electronic marshalling equipment and LS CHARM I/O to site to begin field wiring (FAT may be optional).

The CTO CSLS Cabinets are configured by selecting a base enclosure model and required options to meet specific project needs.

Base enclosure models are available:

� For different cabinet sizes / entry (Front Access or Front and Rear access).

� For different power distribution needs : AC powered.

� For different world area design standards and regulations: EUR (Europe).

Each base model is further explained in the coming sections.

Configurable options examples: The type of LS CHARMS (I.S. or non I.S.), side panels, cabinet light, nameplate engraving and injected power.

� All CTO CSLS cabinets come with following equipment installed: Primary and secondary 24VDC power distribution for LS CHARM I/O Cards and field instrumentation.

� Wire ducts or wire basket.

� Grounding bars.

� Wiring plan pocket.

� Emerson Name Plate Holder and blank name plate insert.

� DeltaV LS CHARM I/O equipment based on your configuration (and priced separately): including CSLS carriers, CHARM base plates, standard terminal blocks, address plugs and terminals.

z The CSLS cards and LS CHARMs are not included and are to be ordered separately.

z The required number of (redundant) LS CHARM I/O cards and CSLS cards depends on the actual number and types of I/O that will be wired into the cabinet.

The following sections provide a more detailed specification for the CTO CSLS Cabinets and available options.

Page 3: CTO CSLS CHARM Cabinets (European Standards)

September 2020

www.emerson.com/deltav 3

CTO CSLS CHARM Cabinets (European Standards)

Overview of CSLS Cabinets – Base Models (EUROPEAN Standards)

Base Model Number Description#

CHARM IO

Incoming Power Requirements (Prim and Sec)

Permitted Location /

World Area

EU-CAB-800F-192-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 192 LS CHARM I/O; 800mm W x 600mm D; Front Access; Cable Entry - Bottom

192 230V ACSafe Area

EUR

EU-CAB-800FR-480-AC-CSLSAC Powered SIS Electronic Marshalling cabinet for 480 LS CHARM I/O; 800mm W x 800mm D; Front and Rear Access; Cable Entry - Bottom

480 230V ACSafe Area

EUR

Overview of CSLS Cabinets.

The CTO base model reference for cabinets uses the following naming convention: “EU-CAB-XXXYY-ZZZIO-IP-CSLS”, where:

• EU = Europe Design Standards and Regulations.

•XXX = Cabinet width (mm), e.g. “800”, “1200”.

•YY = “F” for Front only access (600 mm deep), “FR” for Front and Rear access (800 mm deep).

•ZZZ = Maximum I/O’s count in this CTO.

•IP = AC / DC Incoming Power, DC = 24V DC or AC = 230V AC.

•DDDD = Short description of content and purpose.

Page 4: CTO CSLS CHARM Cabinets (European Standards)

September 2020

www.emerson.com/deltav 4

CTO CSLS CHARM Cabinets (European Standards)

Overview of CTO CSLS Cabinets models and Options

LEGENDS:

• Default option setting

o Configure to option setting.

(Different from Default)

NA Option setting not possible

for Base Enclosure Model

Intentionally kept blank for user

to fill as per configuration choice

Base Model

EU-C

AB

-800

F-19

2-A

C-C

SLS

EU-C

AB

-800

FR-4

80-A

C-C

SLS

World Area EUR EUR

Power Input (DC: 24VDC, AC: 230VAC) AC AC

Enclosure Access (F: Front, FR: Front-Rear) F F/R

# LS CHARMI/O 192 480

Enclosure Options Option Setting

Type of LS CHARMS A

0 LS 192 I/O Non-IS • •

1 LS 192 I/O IS o o

2 LS 120 I/O Non-IS + LS 72 I/O IS o o

3 LS 60 I/O Non-IS + LS 132 I/O IS o o

4 LS 288 I/O Non-IS

NA

5 LS 288 I/O IS o

6 LS 192 I/O Non-IS + LS 96 I/O IS o

7 LS 96 I/O Non-IS + LS 192 I/O IS o

8 LS NIS BUNDLE o o

9 LS IS BUNDLE o o

Side Panels B0 Yes o o

1 No • •

Cable Clamp Rail C0 No • •

1 Yes o o

Field Cable Routing D0 Cable Duct • •

1 Wire Basket o o

CSLS Injected Power Distribution**(Applicable only for LS NIS CHARMS)

F0 Yes • •

1 No o o

**Standard CHARM terminal blocks will be available with NIS baseplates. Fused injected power terminal blocks need to be ordered separately during project execution as per inj. power requirements of CHARMs.

Page 5: CTO CSLS CHARM Cabinets (European Standards)

September 2020

www.emerson.com/deltav 5

CTO CSLS CHARM Cabinets (European Standards)

Door Fans H 0 Thermostat controlled 30°C • •

High Temperature Alarm I 0 Yes @ 35 Deg C • •

Enclosure Light J0 Light with motion sensor • •

1 None o o

Utility Feed for Utility Socket K0 No • •

1 Yes o o

Certification L0 CE • •

1 None o o

Following more detailed options can be specified upon order (if applicable) contact local i-Center- Cluj

� Type of utility socket: German-Russia / France-Poland / Switzerland / UK-Ireland / Italy

� Wiring color scheme different from default: EUR (L- Brown, N- Blue)

� Input Voltage different from default: EUR (230VAC)

Page 6: CTO CSLS CHARM Cabinets (European Standards)

September 2020

www.emerson.com/deltav 6

CTO CSLS CHARM Cabinets (European Standards)

Cabinet SpecificationsSpecifications for EU-CAB-800F-192-AC-CSLS. For other available configuration options refer to CSLS Base model and available configurable option.

EU-CAB-800F-192-AC-CSLS

Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth

Access Front Access – single door, right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~200 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fans With thermostat control - Set point 30°C

High Temperature Alarm Thermostat set point 35 Deg C

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 25°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Configurable: None

Input Power Default: Primary and Secondary 230 VAC Feeder

Configurable: Utility feeder for Utility Socket

Surge Protection Device SPD with 20 A rating for each Primary and Secondary 230 VAC

Power Supply Rating Default: DeltaV CSLS System Bulk Power Supplies 2 X 40A.

Configurable: Separate Injected Power for Non IS baseplates 2 x 20A.

Internal Power Distribution AC Incoming power through lockable disconnect switch subassembly.

Fully redundant 24VDC distribution for LS CHARM I/O cards through fused terminals. Injected Power 24 V DC for Non IS LS CHARM base plates Distribution through fused terminals.

AC powered fan on Primary Feeder.

AC powered light on secondary Feeder.

Local Safety Network Redundant 100BASE-FX, RJ45 connectors, to be connected to each CSLS carrier. Primary and Secondary Local Safety Network to 2 CSLS carriers is included.

Example Layout and Installed Equipment:

Front Internal View

Example BOM

� 2 LS CHARM IO rails, for total of 192 LS I/O, 2 x CSLS Carrier with redundant Copper Ethernet connectors

� 16 x CHARM Base Plate

� 16 x CHARM Address Plug

� 192 x CHARM terminal blocks - Screw type

� 2 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No Active DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 7: CTO CSLS CHARM Cabinets (European Standards)

September 2020

www.emerson.com/deltav 7

CTO CSLS CHARM Cabinets (European Standards)

Specifications for EU-CAB-800FR-480-AC-CSLS. For other available configuration options refer to CSLS Base model and available configurable option.

EU-CAB-800FR-480-AC-CSLS

Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm Plinth

Access Front and Rear Access, single doors, Right hand hinged, latch type lock and 2 sets of keys (key N°3524E)

Protection Category IP54 – NEMA 12

Approximate Weight ~300 kg

Color Cabinet RAL7035, Plinth RAL7022

Door Fan With thermostat control - Set point 30°C for each side

High Temperature Alarm Thermostat set point 35 Deg C

Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye bolts on top, bottom cable entry, removable gland plate

Environmental Specifications Equipment/rack room installation (HVAC controlled), 25°C Max.

Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Configurable: None

Input Power Default: Primary and Secondary 230 VAC Feeder

Configurable: Utility feeder for Utility Socket

Surge Protection Device SPD with 20 A rating for each Primary and Secondary 230 VAC

Power Supply Rating Default: DeltaV CSLS System Bulk Power Supplies 2 X 40A for each side Front / Rear.

Configurable: Separate Injected Power for Non IS baseplates 2 x 20A for each side Front / Rear.

Internal Power Distribution AC Incoming power through lockable disconnect switch subassembly.

Fully redundant 24VDC distribution for LS CHARM I/O cards through fused terminals. Injected Power 24 V DC for Non IS LS CHARM base plates Distribution through fused terminals.

AC powered fan Front on Primary Feeder and fan Rear on Secondary Feeder.

AC powered light Front on Primary Feeder and Rear on Secondary Feeder

Local Safety Network Redundant 100BASE-FX, RJ45 connectors, to be connected to each CSLS carrier. Primary and Secondary Local Safety Network to 2 CSLS carriers is included.

Example Layout and Installed Equipment:

Front / Rear Internal View

Example BOM Front and Rear

� 5 LS CHARM IO rails, for total of 480LS I/O, 5 x CSLS Carrier with redundant Copper Ethernet connectors

� 40 x CHARM Base Plate

� 40 x CHARM Address Plug

� 480 x CHARM terminal blocks - Screw type

� 5 x CHARM I/O bus termination

� Base Plate and Channel Identifier Labels

No Active DeltaV equipment is included in the base model. All DeltaV equipment is to be configured separately through the Emerson quoting tools.

Page 8: CTO CSLS CHARM Cabinets (European Standards)

September 2020

www.emerson.com/deltav 8

CTO CSLS CHARM Cabinets (European Standards)

External Views for Cabinets

External View for Front only and Front / Rear Cabinet External Top View for Front only Cabinet

External Top View for Front / Rear Cabinet

Page 9: CTO CSLS CHARM Cabinets (European Standards)

September 2020CTO CSLS CHARM Cabinets (European Standards)

www.emerson.com/deltav 9

How to order a CTO Cabinet?

CTO CSLS Cabinets are pre-engineered solutions developed by Emerson’s Project Management Office (PMO) and made available from Emerson Supply Chain.

Please follow the steps below to configure and order a CTO CSLS Cabinet:

1. Specify the CTO Cabinet by selecting the base model and the options required for the project. A configuration tool is available to aid in the selection of the right combination of optioned CTOs.

2. Based on the specification, you will then receive:

� A quotation for the fully assembled Cabinet.

� The detailed specification (drawing package) matching your configuration, including the Bill of Materials.

3. Approve the drawing package for construction.

4. Order the CTO Cabinet as per provided quotation and approved drawings.

5. The CTO Cabinet is assembled, factory tested and delivered to site. The delivery includes the as-built drawing package (AutoCAD).

For questions related to specific project quotations or order processing, please contact your local Emerson Sales office or your regional Emerson assembly center:

For US/Canada St. Louis iCenter: [email protected]

For Europe Cluj iCenter: [email protected]

For Asia Pacific Singapore iCenter: [email protected]

For Middle East and Africa iCenter: [email protected]

Project Customizations

“…What if a CTO Cabinet is 90% what I need, but I really need my Cabinet to have…”

Minor customizations as a variation or addition to the standard CTO offering can often be developed in such a way that the additional effort is incremental.

In case your project would require a customer witnessed Factory Acceptance Test, this can also be accommodated.

Please work with your local Emerson Sales office or regional Emerson assembly center to evaluate any impacts of requested customizations to cost, delivery time and certifications.

System Compatibility

CSLS Cabinets are compatible with DeltaV version 12.3 and above.

CSLS cards require DeltaV SZ Controllers.

Certifications

The CTO CHARMs Cabinet designs are designed to meet CE personal safety and EMC requirements. The designs have been submitted for the following certifications:

� Conformity to the relevant European directives, including EMC (CE Marking)

For Europe Design Standards and Regulations, the cabinet default comes with CE Certification. Optionally, no certification can be specified.

Refer to the DeltaV SIS with Electronic Marshalling or to the DeltaV SIS with IS Electronic Marshalling Product Data Sheet for certification information on the DeltaV SIS system components.

Page 10: CTO CSLS CHARM Cabinets (European Standards)

September 2020

EmersonNorth America, Latin America:

+1 800 833 8314 or +1 512 832 3774

Asia Pacific: +65 6777 8211

Europe, Middle East:

+41 41 768 6111

www.emerson.com/deltav

©2020, Emerson. All rights reserved.

The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.

The contents of this publication are presented for informational purposes only, and while diligent efforts were made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice.

CTO CSLS CHARM Cabinets (European Standards)

Related Products

� CSLS cards must be ordered separately

� LS CHARMs must be ordered separately

� LS CHARMS requiring other terminal blocks than the standard terminal block should be ordered with the non-standard terminal block

� LSN Switches must be ordered separately