ct theory and testing

42
1 CT Theory and Testing William H. Hardy, PhD Chief Engineer 10737 Lexington Drive Knoxville, TN 37932 Phone: (865) 966-5856 www.powermetrix.com

Upload: hisham-el-deeb

Post on 08-Oct-2014

55 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: CT Theory and Testing

1

CT Theory and Testing

William H. Hardy, PhD Chief Engineer

10737 Lexington Drive Knoxville, TN 37932

Phone: (865) 966-5856

www.powermetrix.com

Page 2: CT Theory and Testing

2

Current Transformers (CT’s)

• CT’s allow the measurement of high currents at potentially high voltages.

• They come in many shapes and sizes for different applications

• They are potentially extremely dangerous.

They can kill you!

Page 3: CT Theory and Testing

3

Current Transformers (CT’s)

Page 4: CT Theory and Testing

4

Current Transformers (CT’s)Basic Theory

• Basic formula: Is = Ip (Np/Ns) = Ip/Ns• Open Circuit Voltage:• Where:

Zb = Burden ImpedanceIp = Primary CurrentNs = Number of Secondary Turns (Ratio to 1)

spb NIZV /5.3 ••=

VV 1320200/1000105.3 5 =••=Tests have shown values ranging from 500 to 11,000 volts.

Page 5: CT Theory and Testing

5

CT – Accuracy Class/Burden

• Most CTs used in North America are 0.3 (0.3 percent) Class devices.

• When an accuracy class is specified the maximum burden for which the device meets the class accuracy is also specified.

Page 6: CT Theory and Testing

6

CT – Class 0.3

• Metering error shall be less than 0.3% when the CT is used at FULL RATED LOAD and with rated burden.

• Metering error shall be less than 0.6% when the CT is used between 10% and 100% of full rated load.

• Error is a combination of amplitude and phase error.

Page 7: CT Theory and Testing

7

CT – Accuracy – Burden - Load

Meets Accuracy Spec

Meets 0.6 Spec

No Spec

Page 8: CT Theory and Testing

8 Slide Courtesy Kent Jones, GE

0.3% ACCURACY

AC

CU

RA

CY

CLA

SS

RATING

SECONDARY

FACTOR

CURRENT20

4.0

15

3.02.0

10

1.0

5.02.51.00.5

.25

0.1

5%10%

50% 100% 200 300 400

0.60

0.30

0.15

0.15

0.30

0.600.6% ACCURACY REGION

NO ACCURACY GUARANTEED IN FRONT OF THIS LINE

0.3% @ BX.X RF 4.0

X CT TEST POINTC20 METER TEST POINT

X X

ACTUAL

IEEE C57.13 ACCURACY

MAXIMUM CONTINUOUSAMPS (RF=4.0)

X

Burden Class 0.3

Page 9: CT Theory and Testing

9

0.15% ACCURACY

AC

CU

RA

CY

CLA

SS

RATING

SECONDARY

FACTOR

CURRENT20

4.0

15

3.02.0

10

1.0

5.02.51.00.5

.25

0.1

5%10%

50% 100% 200 300 400

0.60

0.30

0.15

0.15

0.30

0.60 0.3% ACCURACY REGION

NO ACCURACY GUARANTEED IN FRONT OF THIS LINE

0.15 @ E0.04, 0.15 @ E0.20, 0.15 @ BX.X RF 4.0

X CT TEST POINTC20 METER TEST POINT

X X

ACTUAL

PROPOSED IEEE C57.13.6 ACCURACY

CURRENT (RF=4.0)MAXIMUM CONTINUOUS

Slide Courtesy Kent Jones, GE

Burden Class 0.15

Page 10: CT Theory and Testing

10 Slide Courtesy Kent Jones, GE

AC

CU

RA

CY

CLA

SS

RATING

SECONDARY

FACTOR

CURRENT20

4.0

15

3.02.0

10

1.0

5.02.51.00.5

.25

0.1

5%

10%

50% 100% 200 300 400

0.60

0.30

0.15

0.15

0.30

0.600.15% ACCURACY REGION

NO ACCURACY GUARANTEED IN FRONT OF THIS LINE

0.15S @ E0.04, 0.15S @ E0.20, 0.15S @ BX.X RF 4.0

X CT TEST POINTC20 METER TEST POINT

X X

ACTUAL

PROPOSED IEEE C57.13.6 ACCURACY

CURRENT (RF=4.0)MAXIMUM CONTINUOUS

X

Burden Class 0.15S

Page 11: CT Theory and Testing

11

Errors with Current Transformers

Page 12: CT Theory and Testing

12

Errors with Current Transformers

• CTs require a lot of care to insure accurate metering.

Burden – Over burden reduces CT accuracy.Wiring – Faulty or improper wiring reduces accuracy by increasing burden.Shunt – Failure to remove the safety shunt will not keep the CT from operating but it will reduce the readings by 50-80%

Page 13: CT Theory and Testing

13

Errors with Current Transformers

• When you see a CT spec sheet it will give you the burden at which the CT meets a specific accuracy Class

Page 14: CT Theory and Testing

14

Errors with Current Transformers

• Many CTs are only rated at B0.1 and B0.2

• #16 wire is 4.5 mΩ/ft• #14 wire is 2.8 mΩ/ft• #12 wire is 1.8 mΩ/ft• #10 wire is 1.1 mΩ/ft• #8 wire is 0.7 mΩ/ft• 50 ft of #12 wire is

nearly 100 mΩ

Page 15: CT Theory and Testing

15

Errors with Instrument Transformers CT - Shunt

• Leaving the shunt in the wrong position produces wrong readings not no readings.

SHUNT CLOSED SHUNT OPEN

Page 16: CT Theory and Testing

16

Errors with Instrument TransformersCT - Polarity

• Polarity of the connection matters.

• Wrong polarity means totally wrong metering.

• When PF≠0, reversed polarities may not be obvious.

Page 17: CT Theory and Testing

17

CT Rating FactorThe MOST Misunderstood Spec

• Rating Factor has absolutely nothing to do with burden.

• If a CT has a rating factor of 4 it means that at 30°C it can be used up to 4X its label current and maintain its accuracy Class.

Page 18: CT Theory and Testing

18

CT Rating Factor• Rating Factor is a strong

function of temperature.• If a CT has a rating factor

of 4 it means that at 30°C it can be used up to 4X its label current and maintain its accuracy Class.

• Operating temperature affects Rating Factor significantly.

A CT with RF=4 at 30°C is only RF=3 at 55°C

Page 19: CT Theory and Testing

19

CT Testing

• Three Approaches in use todayDirect RATIO measurement with applied burden

Most accurate approach tells us exactly what we want to knowMeasures directly the quantity we care about CT RatioIs more complicated to perform.

Page 20: CT Theory and Testing

20

CT Testing• Alternate Approaches

Burden only A compromise: tells us if circuit is stable under excess burdenCan’t give us the ratio which is what we really care about.

Admittance TestingAllows us to look for changes from previous measurements.Doesn’t directly give ratioAccuracy typically ±5%

Page 21: CT Theory and Testing

21

On Site CT Testing• The meter measures ONLY the voltage and current reaching the

meter terminals.

• To verify that the CT is working at the site we have to test the entire circuit.

Page 22: CT Theory and Testing

22

CT TransformersField Verification – Full Ratio Measurement

Measure Here

Measure Here

Page 23: CT Theory and Testing

23

CT Ratio with Burden Testing• Ratio Testing is the

preferred approach when we can gain access to the CT primary.

• Various types of probes can be used for primary side.

FlexHV

Page 24: CT Theory and Testing

24

CT Ratio with Burden Testing• Secondary

connection is made through the test switch

• Same connection that is used for the rest of the site testing.

Ratio Testing with applied burden is the most accurate and complete approach for testing at CT in service.

Page 25: CT Theory and Testing

25

Testing Current TransformersRatio vs Applied Burden

• CT testing can be done with very high accuracy

Reference CT measured using PowerMaster with 752 clamp-on probes. Essentially NO ratio error, phase shift, or change in secondary current versus applied burden.

Page 26: CT Theory and Testing

26

Testing Current TransformersRatio vs Applied Burden

Reference CT measured using PowerMaster with 752 clamp-on probes. Essentially NO ratio error, phase shift, or change in secondary current versus applied burden.

• CT testing can be done with very high accuracy

Page 27: CT Theory and Testing

27

Testing Current TransformersRatio vs Applied Burden

Reference CT measured using PowerMaster with 752 clamp-on probes. Essentially NO ratio error, phase shift, or change in secondary current versus applied burden.

• CT testing can be done with very high accuracy

Page 28: CT Theory and Testing

28

Testing Current TransformersRatio vs Applied Burden

• CTs installations can be fully verified in the field

We can verify that the ratio is correct and constant as burden changes.

Burden Class 0.1 CTs various issues: too small gauge wire, bad connections, high harmonic content.

Page 29: CT Theory and Testing

29

Testing Current TransformersRatio vs Applied Burden

• CTs installations can be fully verified in the field

We can verify that the ratio is correct and constant as burden changes.

Burden Class 0.1 CTs various issues: too small gauge wire, bad connections, high harmonic content.

Page 30: CT Theory and Testing

30

Testing Current TransformersRatio vs Applied Burden

• CTs installations can be fully verified in the field

CT Phase C highly harmonic load. CT Phase C harmonic load removed.

Same CT in BOTH cases.

Page 31: CT Theory and Testing

31

Testing Current TransformersRatio vs Applied Burden

• CTs installations can be fully verified in the field

These are the waveforms and harmonics when the CT falied.

Page 32: CT Theory and Testing

32

Testing Current TransformersRatio vs Applied Burden

• CTs installations can be fully verified in the field

Without the harmonic load this CT passed it’s test.

Page 33: CT Theory and Testing

33

Testing Current TransformersBurden Test Only

• If we cannot get to the primary side of the CT we can check that the output is constant as burden changes.

Burden Class 0.2 CTs can look quite bad but actually be within specs.

Page 34: CT Theory and Testing

34

Testing Current TransformersBurden Test Only

• If we cannot get to the primary side of the CT we can check that the output is constant as burden changes.

Same performance from Burden Class 0.5 CTs is well out of specification.

Page 35: CT Theory and Testing

35

CT – Accuracy – Burden - Load

Meets Accuracy Spec

Meets 0.6 Spec

No Spec

Page 36: CT Theory and Testing

36

Testing Current TransformersWhat’s Wrong?

• Same site as above: What went wrong???

Page 37: CT Theory and Testing

37

Testing Current TransformersWhat’s Wrong?

• Same site as above: What went wrong???

Page 38: CT Theory and Testing

38

Testing Current TransformersWhat’s Wrong?

• Same site as above: What went wrong???

Page 39: CT Theory and Testing

39

Testing Current TransformersWhat’s Wrong? Power Theft

A simple piece of wire wrapped around the CT.

Page 40: CT Theory and Testing

40

Testing Current TransformersWhat’s Wrong?

Phase A CT reversed.

Page 41: CT Theory and Testing

41

Testing Current TransformersWhat’s Wrong?

Phase A & B CTs swapped.

Page 42: CT Theory and Testing

42

PowerMaster