CSP1-F Combined Protection and Control SystemPerformance and functional outline

SYSTEM LINE

MV-Switchboard

RS 232

RS 232

SCADA

CSP1: Protection and control unit

Operation and display via CMP1

CAN-BUS

Operation and display viaNotebook

Page 2: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

2 LF CSP1-F 05.99 E

Contents

1 Outline and Applications ............................................................................................ 32 CSP1-F � central, intelligent protection......................................................................... 4

2.1 Scope of capacity and functions ................................................................................................42.2 Design ..................................................................................................................................42.3 Protection functions ..................................................................................................................72.4 Controlling and Monitoring.......................................................................................................72.5 Measuring functions.................................................................................................................92.6 Statistical measuring values .......................................................................................................92.7 Data recording .....................................................................................................................10

2.7.1 Event recorder ................................................................................................................102.7.2 Fault recorder.................................................................................................................102.7.3 Disturbance recorder (optional)..........................................................................................10

3 CMP1 ....................................................................................................................... 113.1 Operating the CMP1.............................................................................................................113.2 Operating elements of the CMP1.............................................................................................123.3 Functions of the operating elements ..........................................................................................123.4 The operating modes .............................................................................................................133.5 Controlling the switching devices .............................................................................................143.6 Programming & Parameter Setting ............................................................................................14

4 SYSTEM-LINE-SOFT .................................................................................................... 154.1 Scope of functions and performance.........................................................................................15

5 Technical Data .......................................................................................................... 185.1 Auxiliary voltage ...................................................................................................................18

5.1.1 Voltage supply CMP1 .....................................................................................................185.1.2 Voltage supply CSP1.......................................................................................................18

5.2 Measuring inputs ..................................................................................................................195.2.1 Current inputs.................................................................................................................195.2.2 Voltage inputs (optional in CSP1-L) .....................................................................................195.2.3 Measuring precision........................................................................................................20

5.3 Function and signal inputs.......................................................................................................205.4 Outputs ...............................................................................................................................21

5.4.1 Power outputs ................................................................................................................215.4.2 Signal relays..................................................................................................................22

5.5 Communication interfaces.......................................................................................................235.6 Standards............................................................................................................................24

5.6.1 General regulations.........................................................................................................245.6.2 High-voltage tests (EN 60255-6 [11.94]) ...........................................................................245.6.3 EMC Emission test I .........................................................................................................245.6.4 EMC Emission test II ........................................................................................................255.6.5 Mechanical stress ...........................................................................................................255.6.6 Climatic stress ................................................................................................................255.6.7 Dimensions and weights...................................................................................................26

6 Order Form .............................................................................................................. 27

Page 3: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 3

1 Outline and Applications

The top-quality digital protection and control sytems ofthe »SYSTEM LINE« fulfil all demands and requirementsfor protection and control at medium-voltage level.

Pro

tect

ion r

equir

em

ents

Functionality

SYSTEM LINE

CSP1-B

Busbar protection

CSP1-L

Line/cable differentialprotection

CSP1-F

Feeder management

Figure 1.1: Range of SYSTEM-LINE devices

The combined protection and control system CSP1-F isa feeder management system for the medium-voltagelevel. It complies with the latest state of the art of mo-dern digital secondary technology.

Development work focussed primarily on the followinggoals:

•� User-friendly operation,•� Flexibility,•� Ease of integration into switchboards,•� Freely selectable functions,•� Large range of applications and•� Standardized communication.

� Cost optimization at the medium-voltage level

The systems each comprise two separate devices, thebase unit CSP1-F and the operating and display unitCMP1:

•� In the CSP1-F, which is capable of working self-suffiently, all protection and control functions are in-tegrated. The base unit is installed into the low-voltage niche (mounted on mounting plate). Thewide-range power part permits connection of allaux. voltage equipment commonly used in MVsystems.

� One device for all switchgears and applications

The compact operating and display unit CMP1 is de-centralilzed and installed in the front door of the circuitbreaker field. The simple, menu-guided operation, thelarge display with illuminated background as well asthe ergonomically designed surface ensure fast andcomprehensive information of the operating personnelat all times. A single bus/line replaces the conventio-nal cable tree.

MV-Switchboard

RS 232

RS 232

SCADA

CSP1: Protection and control unit

Operation and display via CMP1

CAN-BUS

Operation and display viaNotebook

Figure 1.2: CSP1-F Control and Protection System

Page 4: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

4 LF CSP1-F 05.99 E

2 CSP1-F � central, intelligent protection

The base module CSP1-F, which is capable of working self-sufficiently, comprises the complete protection andcontrol technology.

DIP-SWITCHES DIGITAL INPUTSAUX.VOLTAGE

SUPPLY

LEDs

VOLTAGE

INPUTS

SIGNAL RELAY

CONTROL

OUTPUTS

CURRENT

INPUTS

Figure 2.1: CSP1-F3

2.1 Scope of capacity and functions

The base unit CSP1-F features the following specialcharacteristics:

•� Compact design in robust aluminium/plastic hou-sing in accordance with protection class IP50,

•� Wide-range power part,•� Wide range of protection and control functions,•� Flexible management of inputs and outputs,•� Power outputs directly driving the switch elements

(circuit breakers, isolators, earthing switches),•� Communication with host computers via VDEW-

interface with fibre optic conductor (optional)(as per EC 870-5-103),

•� Various communication interfaces: CAN-Bus,RS232 for parameter setting,

•� Highly efficient fault recording function on PC-Card(optional),

•� Comprehensive self-monitoring and•� No maintenance required.

MIDDLE VOLTAGE PANEL

CSP1-Feeder management

Supervision

Signal/indication

Statistics

Measurement

Disturbancerecorder

Protection

Interlock

Control

NOTEBOOK

Display Communication

MASTER SYSTEM

&$1�

%86

)2

,QSXW

2XWSXW

56 ���

RS 232optional

Figure 2.2: CSP1-F as Feeder Management System

2.2 Design

The compact CSP1-F incorporates all components re-quired for:

Page 5: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 5

•� Measured value recording and evaluation,•� Signal and command output,•� Entry and evaluation of binary signals,•� Data transmission and storage and•� Aux. voltage supply.

The housing of the CSP1-F is a very robust, extrudedaluminium/plastic profile which meets the exacting re-quirements set by environmental influences such as vib-ration, shock, EMV, etc.

The upper circuit board tightly seals the housing, and� at the same time � serves as connection level. Moun-ted on this conductor plate are all external connectionsfor the transformers and the control inputs and outputs.Below the cover of this conductor plate are the internalcurrent and voltage transformers, opto-couplers and re-lays.The housing is designed in such a manner that the pro-tection class IP50 is achieved for the electronics. Allexternal connections, except the measuring transformerand control outputs, are screw- or plug-type. Thissimplifies fast installation. Connection cables can bepre-fabricated in advance.The base unit CSP1-F is supplied with the currents em-bossed by the main current transformers and the ana-logous input signals provided by the voltage transfo-mers via separate input transformers. These input sig-nals are galvanically decoupled, analogously filteredand finally transmitted to the analog/digital converter.The CSP1-F is equipped with a 24-Bit signal processorfor the protection functions and a high-power 16-Bitcontroller for processing the control and communicati-on functions. Thanks to the digital signal processing,the influences of higher frequency compensation pro-cesses and DC components are suppressed.

Irrespective of the complexity of the protection andcontrol tasks, the SYSTEM LINE offers the right solution.The CSP1-F (Feeder Management System) is avai-lable in three need-oriented power categories.

Q0

Q9

Q8

Figure 2.3: Example Feeder Configuration CSP1-F1

•� CSP1-F1: This reasonably priced system starter ispredominantly used in simple feeders. The protecti-on functions are designed for non-directional phaseand earth current protection. The CSP1-F1 is de-signed for controlling one circuit breaker and forrecording 3 switching devices.

Q0 Q8

Q1 Q2

BB1

BB2

Figure 2.4: Example Feeder Configuration CSP1-F3

•� CSP1-F3: The main field of application for theCSP1-F3 lies in meshed networks for selective direc-tional protection and/or for controlling several swit-ching devices. The number of measuring inputs hasbeen extended by four voltage measuring inputs(UL1, UL2, UL3, UE), for directional protection. Thanksto an integrated voltage measuring function it offerseven more comprehensive protection and measuringfunctions than the CSP1-F1. The CSP1-F3 is de-signed for controlling three switching devices (e.g.circuit breaker, isolator and earthing switch) andcan record 5 switching devices

Q0 Q8

Q1 Q2

BB1

BB2

Figure 2.5: Example Feeder Configuration CSP1-F5

•� CSP1-F5: The CSP1-F5 is the feeder managementsystem with the highest capacity. It can controland record up to five switching devices. Thenumber of measuring inputs is the same as withthe CSP1-F3. The CSP1-F5 has, just like theCSP1-F3, a highly efficient fault recorder function.In addition, it is possible to store the fault recordsfail-safe on a PC memory card (optional).

Page 6: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

6 LF CSP1-F 05.99 E

Figure 2.6: Connection diagramm

Page 7: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 7

2.3 Protection functions

The combined protection and control system CSP1-F isequipped with a great number of protection functionswhich cover nearly all protection tasks in the medium-voltage range.All protection functions are fully accessible to the ope-rator and can be activated as desired. Parameter set-ting of the protection functions can either be done viathe operating and display unit CMP1 or by means ofPC/Laptop via the »SYSTEM LINE SOFT«.

There are four parameter sets available for each pro-tection function.

The protection parameter can be changed as follows:

•� By parameter setting,•� by means of a digital input signal or•� by means of data protocol as per IEC 870-5-103

(VDEW).

For the purpose of integrating external protection devi-ces into the monitoring and control process, theCSP1-F is equipped with manifold functions.

No. Protection Functions ANSI CSP1-F1 CSP1-F3 CSP1-F5

1 Time overcurrent protection non directional 51 9

2 Over-load with therm. replica 49 9 9 9

3 Time overcurrent protection directional andnon-directional

51 + 67 9 9

4 Short circuit protection non-directional 50 9

5 Short circuit protection directionaland non-directional

50 + 67 9 9

6 Earth fault protection non-directional 50/51G 9

7 Earth fault protection directionaland non-directional

50/51G+ 67G

9 9

8 Supervision of the residual voltage 59N 9 9

9 Over-/undervoltage 27/59 9 9

10 Over-/underfrequency 81 9 9

11 Auto reclosing 79 9 9 9

12 Power direction 32 9 9

13 Unbalanced load protection 46 9 9 9

14 Programable protection logics (Functi-on/Blocking/Trip blocking)

9 9 9

15 Trip circuit supervision 9 9 9

16 Circuit breaker failure protection 50/62BF 9 9 9

17 Backward interlocking 9 9 9

18 Voltage transformer supervision(fuse failure)

9 9

Table 2.1: Outline of the protection functions of the different CSP1-F Models

2.4 Controlling and Monitoring

For controlling and monitoring tasks the CSP1-F-Systemis equipped with the following functions:

•� Graphic display of the status of the switchingdevices.

•� The switching devices can be controlled via the o-perating keys, digital inputs or the serial inter-face.

•� Direct selection of the circuit breaker coils and iso-lator motors.

•� Interlinking of different switching devices at feederor station level.

•� Protocolling of switching actions and changes inswitch positions.

The switching device positions are recorded via twoopto-decoupled inputs each for »OFF« and »ON« onthe CSP1-F. The position signals of the various swit-ching devices (up to 5) are shown on the LC graphic

Page 8: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

8 LF CSP1-F 05.99 E

display of the CMP1 in the form of a single-line. Faultand differential positions are indicated by a dottedswitching symbol in centre position. The single linediagram is pre-set at the factory in accordance withcustomer requirements. It can be easily adjusted tospecific applications thanks to a configuration soft-ware. In addition to status recording it is possible torecord, protocol and transmit external protection sig-nals, monitoring messages, external control commandsand interlocking functions with varying functionalitiesvia the freely adjustable inputs.

Q0

Q9

Q8

Figure 2.7: Example Feeder Configuration

In addition to the functional assignments, it is also pos-sible to set parameters for rebouncing time and signallogics for each input.

By means of potential-free signal relays it is possible totransmit binary signals for protection and monitoring(e.g. CB failure, backward interlocking).

CB = Circuit Breaker

No. Control functions CSP1-F1 CSP1-F3 CSP1-F5

1 Controllable switching devices 1 3 5

2Recordable switching devices (No of switching devices,that can be shown on the display of the CMP1)

3 5 5

3 Power outputs for control coils L-Type (circuit breaker) 2 2 3(4)

Power outputs for motor control M-Type (Earthing/isolator) - 2 4(3)

5 Signal relays 6 6 10

6 Digital inputs 8 12 16

7Operation signal output with adjustable operation times andsustained operation command

9 9 9

No. Supervision functions CSP1-F1 CSP1-F3 CSP1-F5

8 Visual display »Switching device in fault position« 9 9 9

9 CB withdrawn 9 9 9

10 Spring winded up 9 9 9

11 Programmable feeder interlocking 9 9 9

Table 2.2: Outline of the control and monitoring functions of the various CSP1-F Models

Page 9: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 9

2.5 Measuring functions

In addition to the recorded measuring values currentand voltage, further measuring values such as activeand reactive power etc. are calculated and displayedas primary values. The measured values can be called

up cyclically and transmitted via the CMP1, a laptopor a PC, or via communication with the host computer.The measuring error rate is < 1% in the operating ran-ge and up to 40 x IN < 3%.

No. Measuring functions CSP1-F1 CSP1-F3 CSP1-F5

1 Phase currents IL1, IL2, IL3 9 9 9

2 Earth current IE 9 9 9

3 Phase-to-neutral voltageUL1, UL2, UL3

9 9

4 Phase-to-phase voltageU12, U23, U31

9 9

5 Residual Voltage UE 9 9

6 Frequency f 9 9

7 Active power P 9 9

8 Reactive power Q 9 9

9 Power factor cos ϕ 9 9

10 Thermal load Θ 9 9 9

11 Energy counter active part Wp +/- 9 9

12 Energy counter reactive part Wq +/- 9 9

13 Unbalanced current I2 9 9 9

Table 2.3: Outline of the measuring functions of the various CSP1-F Models

2.6 Statistical measuring values

In addition to measuring value recording, the CSP1-F

offers statistical functions. Maximum und average va-lue as well as counting functions can be called up viathe CSP1-F.

The maximum and average values can be called upvia a variable time window. The counting functionssuch as operating hours or switching cycle counter areresettable.

No. Statistical Data CSP1-F1 CSP1-F3 CSP1-F5

1 Current max. value 9 9 9

2 Current mean value 9 9 9

3 Voltage max. value 9 9

4 Voltage mean value 9 9

5 Voltage max. value 9 9

6 Mean value phase-to-phase voltage 9 9

7 Frequency max. value 9 9

8 Frequency mean value 9 9

9 Active power max. value 9 9

10 Active power mean value 9 9

11 Reactive power max. value 9 9

12 Reactive power mean value 9 9

13 SG operation counter 9 9 9

14 Number of switched off circuits 9 9 9

15 Operation hours 9 9 9

Table 2.4: Statistical data

Page 10: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

10 LF CSP1-F 05.99 E

2.7 Data recording

The CSP1-F offers various protocolling and recordingmethods for events, fault values and fault records,which are stored in the CSP1-F and can be called upvia the CMP1, a PC or the communication interface.This way, the operator has all data for fault analysisand fault elimination locally at his disposal.

2.7.1 Event recorder

The event recorder protocols and stores the last 50 e-vents in the CSP1-F. The recorded messages are filedwith running number and real time stamp, safe againstdevice failure, in a non-volatile memory. Each event isstored with date, time, cause, event and informationwith a resolution of 1 ms. This includes all messageswhich are related to protection, control, the configu-rable inputs, parameter setting and internal system su-pervision of the device. In case of a fault, the protecti-on messages are additionally marked with a clear anddefinite failure case number.

2.7.2 Fault recorder

The fault recorder stores the last 5 faults failure-safe inthe CSP1-F in accordance with the failure case num-ber. In addition to the triggering event, all effectivemeasuring values as stored and displayed as primaryvalues. In case of damage, this permits evaluation andanalysis at a later date by means of the protectionmessages stored in the event recorder.

2.7.3 Disturbance recorder (optional)

The analogous and digital information is stored in thedisturbance recorder for the purpose of evaluatingmains interferences. Up to 8 digitalized measuring va-lues (phase currents, earth current, conductor voltages,residual voltage) are recorded. Simultaneously, binaryinput and output signals can be recorded. The maxi-mum recording time amounts to 10 s, with a pre-running and extra running time being adjustable. Themeasured values are recorded in the form of momen-tary values.

Page 11: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 11

3 CMP1

The CMP1 is easy to operate and ergonomicallydesigned. The CMP1 is installed in the front door ofthe medium-voltage compartment as separate opera-ting and control unit. It informs the operating personnelabout the momentary status of the feeder and controlsthe switching devices connected to the CSP1-F. A sin-gle cable establishes the connection to the base unitCSP1-F and thus replaces the conventional cable tree.This cable can be easily laid jointly with the aux. vol-tage supply.

Figure 3.1: CMP1

The most significant features of the CMP1 include:

•� Flat, compact design,•� Wide-range voltage supply,•� Large LC graphic display with illuminated back-

ground (128 x 240 Pixel),•� Foil keyboard as per protection class IP54,•� Multi-coloured function keys for menu guidance,

control and emergency OFF function,•� Two key switches for fixing the various switching

authorizations,•� 11 multi-coloured LEDs (8 freely configurable),•� Two RS232 interfaces for parameter setting and

readout of data via PC.

The large LC-graphic display permits:

•� Display of a freely configurable single line dia-gram.

•� Display of switch positions, measuring values andoperating instructions.

•� Protocolling of events with real-time stamp.•� Protocolling of interference events with effective

values.•� Comprehensive commissioning support and mani-

fold testing possibilities.

3.1 Operating the CMP1

Control of the medium-voltage feeder and parametersetting can be effected via the CMP1. All entries aremade via the foil keyboard. Check-backs and statusindications are shown on the large graphic displaywith illuminated background. The display shows switchpositions graphically, messages as texts and parame-ters or measured values in table form.

Page 12: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

12 LF CSP1-F 05.99 E

3.2 Operating elements of the CMP1

Display LEDassignment

Single line

R.H.: Select menu pointMove cursor to the rightL.H.: ReverseMove cursor to the left

Up/Down

scrolling/changingparameters

+=more/-=less

Main Menu

Switch over:Local/Remote

Reset: e.g. LEDs

Switch over:Parameter setting/

Control

Switching On/Off

Mode 2 following changes:Starting storing otherwise

select menu point (like R.H.)Acknowledge popup-messages

Danger Off

Figure 3.2: Operating elements of the CMP1

3.3 Functions of the operating elements

Display LEDassignment

Single line

R.H.: Select menu pointMove cursor to the rightL.H.: ReverseMove cursor to the left

Up / Down

Scrolling/changingvalues

+ = more/- = less

Main menu

Switch over:Local/Remote

Reset e.g. LEDs

Switch over:Parameter setting/

Control

Control keysON/OFF

Mode2 following changes:Starting storing otherwise

select menu point (like R.H.)Acknowledge popup-messages

Danger OFF

Figure 3.3: Functions of the operating elements

Page 13: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 13

3.4 The operating modes

Two key switches serve to fix the various switching authorizations:

•� Local control (Mode 1),•� Local parameter setting (Mode 2) and•� Remote control (Mode 3).

Depending on their position, they will either permit or block controlling or parameter setting of the CSP1-F.

SwitchingChange ofparameters

Remote operationvia interface

Options in mode 2

Options in mode 3

MODE 2Local parameter

setting

MODE 3Remote control

MODE 1Local control

Read out data andparameters

Read out data andparameters

Read out data andparameters

Key positions atCMP1-1

Key positions atCMP1-1

Key positions atCMP1-1

Options in mode 1

Figure 3.4: The operating modes

Page 14: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

14 LF CSP1-F 05.99 E

3.5 Controlling the switching devices

The switching elements shown in the single line dia-gram can be selected and controlled via the operatingunit CMP1.

Every control command to be issued is first checked bythe internal, preprogrammed interlocking logics beforeit is carried out. Switching actions via the CMP1 canonly be carried out in Mode 1 � LOCAL control.

The switching positions of the switching devices, e.g.those of the circuit breakers, are recorded and monito-red via their auxiliary switches. In this procedure thecontact bounce of the auxiliary switches is suppressedvia software. The integrated control logic processesand evaluates the available switch positions as well asthe readiness of the switch (spring tensioned) and is-sues the »OFF« or »ON« switching command if thepre-programmed interlocking conditions have been ful-filled. The switch-on and switch-off coils resp. motors ofthe switching device to be controlled are controlled viathe power outputs. A switch-on command will onlytake place if the switch-off position has been clearlysignalled beforehand, and vice versa. Switching ac-tions are carried out one after the other, i.e. sequenti-ally. All issued control commands have a time limit. Ifthe control commands are not carried out within aspecified time, the CSP1-F will release a fault signal.Monitoring of the position signals of the switching de-vice to be controlled takes place by way of the maxi-mum control and reaction times of the switching devi-ce.

3.6 Programming & Parameter Setting

There are 4 complete parameter sets available for theprotection functions. Thus it is possible to select, setparameters and switch over between four protectionparameter sets. There is always one of the four para-meter sets active or in operation.Each parameter set can be edited in the backgroundand stored at the end without influencing the activelyoperating protection and control functions. A changedparameter set, even if only one single parameter hasbeen changed, will only become active upon confir-mation of the storing function (acknowledgement). Thefundamental parameter set serves to fix the basic con-figuration of the device such as rated feeder data,control times, configuration of the inputs and outputsand communication.Locally, parameter setting of the CSP1-F can be effec-ted menu-guided via the operating surface of theCMP1 or by means of a PC via the serial interface.

Page 15: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 15

4 SYSTEM-LINE-SOFT

Operating and evaluation programme/Functions

The software for setting the parameters of the CSP1-F

via PC and interface is still in preparation.

The »System-Line-Soft« permits evaluation and para-meter setting of the CSP1 family of devices. It willwork on any PC with the operating systems Windows95/98 or Windows NT. Communication takes placevia the RS232 interface or via the internal CAN-BUS.It permmits operation by the use of the mouse (Win-dows surface) and has a user-guided window techno-logy. The »System-Line-Soft« is easy to instal and is a-vailable in different languages.

4.1 Scope of functions and performance

•� Available for all devices of the »System-Line«,•� Setting of parameters for all device-specific data,•� Window technology with operating and status

line,•� Menu-guided plausibility checks,•� Comprehensive help functions,•� Readout, readin, comparison with the device pos-

sible,•� Archiving, editing such as copying or erasing da-

ta sets,•� Logbook function,•� Reading out the messages,•� Cyclic readout of measured values,•� Further processing of measured values (recording,

displaying),•� Controlling possible with single line diagram

display,•� Query to inputs and outputs,•� Commissioning support (e.g. diff- und stability va-

lues in case of DIFF), functioning support as wellas VDEW-Test,

•� Evaluation of fault records, curve-type illustration,editability, additional information such as Trigger,

•� Initiation of test fault records and•� Time synchronization from the PC.

LAPTOP

RS 232

CAN-BUS

RS 232 (in Vorbereitung)

Figure 4.1: Connection example CSP1-F/CMP1-PC via RS 232

Page 16: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

16 LF CSP1-F 05.99 E

Figure 4.2: Display event recorder

Figure 4.3: Display fault recorder

Page 17: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 17

Figure 4.4: Read out of the digital inputs

Figure 4.5: Parameter setting

Page 18: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

18 LF CSP1-F 05.99 E

5 Technical Data

5.1 Auxiliary voltage

5.1.1 Voltage supply CMP1

Voltage ranges Power consumption in idle state Max. power consumption19 - 395 VDC 5 W 10 W22 - 280 VAC 5 VA 10 VA

Frequency range f = 40-70 Hz

5.1.2 Voltage supply CSP1

Voltage ranges Power consumption in idle state Max. power consumption19 - 395 VDC 14 W 26 W22 - 280 VAC 14 VA 26 VA

Frequency range f = 40-70 Hz

Fixed aux. voltages (EN 60255-6):

DC 24 V, 48 V, 60 V, 110 V, 220 VAC 24 V, 100 V, 110 V, 230 V

The power supply part furthermore covers the following commonly used aux. voltages (among others in the UK)with limited tolerance ranges:

240 VAC with the tolerance range -20% / +15%254 VAC with the tolerance range -20% / +10%

The permissible voltage deviations refer to the fixed rated aux. voltages.

Buffering of the aux. voltage supply:= 50 ms at Uemin.

In case of aux. voltage failure functioning of the device is ensured for at least 50 ms.

The fuse for the aux. voltage supply (230) must be dimension min. 4 A, lag.

Page 19: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 19

5.2 Measuring inputs

5.2.1 Current inputs

Quantity: 3 phase currents + 1 summing current (for earth, e.g. cable-type CT)

Measuring method: conventional transformers (other sensors in preparation)

Rated currents: 1 A and 5 A

Connectionsper current input: 3 (1S1(1 A), 1S2(5 A), 1S3)

Measuring range: 0...40 x IN (AC) phase currents0...20 x IN (AS) summing current

Power consumptionin the power path: = 0.1 VA at I = IN

Thermal load capacity:Rated peak short-circuitcurrent: 250 x IN (dynamic half period of sinus oscillation)

Rated short-term current 100 x IN (for 1 s)

Permanent load capacity: 4 x IN

5.2.2 Voltage inputs (optional in CSP1-L)

Quantity: 3 x phase voltage (P-P, P-N) +1 x residual voltage

Measuring method: conventional transformers(other sensors in preparation)

Rated voltages: 100, 110 VAC

Connections per voltageinput: 2 (1A1, 1A2)

Measuring range: 0...230 VAC

Thermal load capacity: 2 x UN permanent load capacity

Power consumption: = 0.1 VA at U = 230 V

Rated frequencies: 50 Hz; 60 Hz (parameter adjustable)

Page 20: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

20 LF CSP1-F 05.99 E

5.2.3 Measuring precision

Current (at rated frequency): 0.1 � 1.5 x IN < 1% of IN1.5 - 40 x IN< 3% of Measured value

Frequency influence: < 2% / Hz

Voltage in relation to rated voltage(at rated frequency): 10 - 50 V < 2%

50 - 220 V ...< 1%

Frequency influence: < 2% / Hz

Frequency: 40 - 70 Hz < 0.05%

Power: PN < 2%

5.3 Function and signal inputs

Opto-decoupler inputs

Quantity: 14 (CSP1-F1)22 (CSP1-F3)26 (CSP1-F5)14 (CSP1-L)

Input voltage range: 0 - 350 VDC

0 - 270 VAC

Threshold value recognition:low set range: Uon = 8.5 VDC/8.5 VAC (50/60 Hz)(code plug plugged in) Uoff = 5.5 VDC/4.5 VAC (50/60 Hz)high set range: Uon = 35 VDC/35 VAC (50/60 Hz)(code plug open) Uoff = 20 VDC/19 VAC (50/60 Hz)

Input current: < 2 mADC (depending on input voltage)< 2 mAAC (depending on input voltage)

Adjustable rebouncingtime: 0 ...100 ms per dig. input

(1 ms pitch)

Page 21: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 21

5.4 Outputs

5.4.1 Power outputs

Maximum load: motor drive: 500 WDC

UH = 24 V, I = 22 ADC for t = 30 s (Is = 1.5*I, t = 100 ms)UH = 60 V, I = 5 ADC for t = 30 s (Is = 1.5*I, t = 100 ms)

Operating current tripping coil (CB): 300 WDC for t = 150 ms

Number of outputs:Operating current tripping coil OL: 2 (CSP1-F1)

2 (CSP1-F3)3 (CSP1-F5)2 (CSP1-L)

Motor drive OM: - (CSP1-F1)2 (CSP1-F3)4 (CSP1-F5)

The following data apply for the outputs OM and OL: Low supply voltage range power circuit (range L)Switching voltage: 18-40 VDC

Permissible permanent current: 24 A continiously

Rated peak connection current: 40 A (1 s)

Current resistance: short-circuit resistant

Shut-down power: 24 A with load shedding measures (idle current circuit)

High supply voltage range power circuit (range H):Switching voltage: 30 - 390 VDC

Permissible permanent current: 15 A continiously

Rated peak connection current: 30 A (1 s)

Current resistance: short-circuit resistant

Shut-down power: 24 A with load shedding measures (idle current circuit)

Page 22: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

22 LF CSP1-F 05.99 E

5.4.2 Signal relays

Number: 6 CSP1-F1/F3/L, 10 CSP1-F5

Switching voltage: 250 VAC

220 VDC, ohmic load Imax. = 0.2 Ainductive load Imax. = 0.1 A L/R < 50 ms24 VDC inductive load Imax. = 5 A

Switching power: ohmic 1250 VAAC or 120 WDC, respectivelyinductive 500 VAAC or 75 WDC, respectively

Min. switching load: 18 V/2 mA

Max rated current: 5 A

Switching current: (16 ms): 20 A

Insulation: 4 kV

Contact material: AgNi + Au

Contact service life: mechanical: 100 x 10^6 operating cycle

Page 23: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 23

5.5 Communication interfaces

RS232 X9 (PC interface)Parameter setting locally by means of PCGalvanically seperated via opto-coupler (2.5 kV).Transmission rate: 9600, 19200 Baud (adjustable)9-pole SUB-D bushing

CAN BUS 1 X10X11 System interface to the CMP1

CAN Specification V2.0 part B (extended frame)Siemens 80C167C on chip CAN ModuleGalvanically separated via opto-coupler (2.5 kV).9-pole SUB-D bushing

FO Interfaces (optional)

CSP1-F1,3,5 X7/X7 Optic fibre conductor connection as per IEC 870-5-103(RxD/TxD) (VDEW recommendation)

Setting of slave No.(0-255)Via 8-pol. DIP switch on the CSP1 or parameter setting CMP1

Wave length 820-860 nmFibre type 62,5 (core diameter)/125 µm (sleeve diameter) (Multimode/multi-gradientfibre) 2 fibres (transmitting/receiving)Plug type BFOC 2.5 (ST)max. dampening 8 dBmax. cable length 2 km

CSP1-L Wave length 1300 nm9/125 µm Monomode fibre (ST)max. dampening 7 dBmax. length 20 km

Page 24: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

24 LF CSP1-F 05.99 E

5.6 Standards

5.6.1 General regulations

Generic standard DIN EN 50082-2 [02.96]DIN EN 50081-1 [03.93]

Product standard DIN EN 60255-6 [11.94]BS 142DIN EN 50178 [04.98]

5.6.2 High-voltage tests (EN 60255-6 [11.94])

Voltage testIEC 60255-5 [01.77]DIN EN 50178 [04.98]

All electric circuits against other elect-ric circuits and touchable surfaces.

2.5 kV (eff.)/50 Hz, 1 min.

Peak-voltage testIEC 60255-5 [01.77] 5 kV/0.5 J, 1.2/50 µs

High-frequency testDIN EN 60255-22-1[05.91]Class 3

Within a electric circuitElectric circuit against earthElectric circuit against electric circuit

1 kV/2 s2.5 kV/2 s2.5 kV/2 s

5.6.3 EMC Emission test I

Disturbance resistance against fast transient disturbance values (Burst)DIN IEC 60255-22-4[10.93]DIN EN 61000-4-4 [03.96]Class 4

Current supply, mains inputs

Other in- and outputs

±4 kV, 2.5 kHz

±2 kV, 5 kHz

Disturbance resistance against the discharge of electricityDIN EN 60255-22-2[05.97]DIN EN 61000-4-2 [03.96]Class 3

Air discharge

Contact discharge

8 kV

6 kV

Disturbance resistance against peak voltagesDIN EN 61000-4-5 [09.96]Class 4

Within an electric circuit

Electric circuit against earth

2 kV

4 kV

Disturbance resistance high-frequency electromagnetic fieldsDIN EN 61000-4-3 [08.97]Class 3

10 V/m

Disturbance resistance against cable-conducted disturbance values induced by high-frequency fieldsDIN ENV 50141 [04.96]Class 3

10 V/m

Disturbance resistance against magnetic fields with energy-technological frequenciesDIN EN 61000-4-8 [05.94]Class 5

continuous3 sec.

100 A/m1000 A/m

Page 25: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 25

5.6.4 EMC Emission test II

Measuring of radio interference voltageDIN EN 55011 [10.97] Limit value Class B

Measuring of radio interference radiationDIN EN 55011 [10.97] Limit value Class B

5.6.5 Mechanical stress

Vibration testsDIN EN 60255-21-1[05.96]Class 1

Vibration test for proper functioningContinuous vibration testing

0,035 mm, 0,5 gn, 1 run-through ineach direction

1,0 gn, 20 run through in each directi-on

Shock and continuous shock testsDIN EN 60255-21-2[05.96]Class 1

Shock test for proper functioningShock test for resistanceContinuous shock test

5 gn, 11 ms, 3 Impulses in each direc-tion15 gn, 11 ms, 3 Impulses in each di-rection

10 gn, 16 ms, 1000 Impulses in eachdirection

5.6.6 Climatic stress

Climatic stressTemperature range for storage/in case of emergency (max. 2h) thedevice must be in operation.Temperature range during operation

-25 oC - +70 oC

-10 oC - +55 oC

Humidity stressDIN 40040DIN IEC 68-2-3 [12.86]

Class F over 56 days at 40 °C and 95% rela-tive humidity

Page 26: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

26 LF CSP1-F 05.99 E

5.6.7 Dimensions and weights

Basic unit CSP1 W 368 mm ⋅ H 264 mm ⋅ D 155 mmDisplay unit CMP1 W 307 mm ⋅ H 246 mm ⋅ D 55 mm

Weight:Basic unit CSP1-F approx. 8 kgBasic unit CSP1-L approx. 7 kgDisplay unit CMP1 2.2 kg

Page 27: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

LF CSP1-F 05.99 E 27

6 Order Form

Protection- and control system (Base unit)

CSP1-

1 switching device (CB), DC controlled,with current protection- and measurementfunctions, disturbance recorder

F1

3 switching devices (CB, isolator, earthingswitch), DC controlled, current-/voltage protecti-on / measurement functions, disturbance re-corder

F3

5 switching devices (CB, isolator, earthingswitch), DC controlled, current-/voltage protecti-on / measurement functions, disturbance re-corder

F5

Transformer technologyConventional 1 A and 5 A, 100/110 V AC C

Auxiliary voltage supply; power circuitDC 18 - 40 VDC 30 - 390 V

LH

Communication interfacewithoutProtocol IEC 870-5-101Protocol IEC 870-5-103, fibre optic(FH-ST plug type connector;820 nm 62.5/125 µm)Protocol Profibus

00V1V3

P1

on request

on request

LanguageEnglishGerman

EG

Options (only for CSP1-F3 and -F5 types)PC-card for local disturbance recording K

Protection- and Control system (Indication and operation unit)

CMP1-

Frontplate IP 54; key switchesLCD-Display and control functions 1

InterfaceRS 232 + CAN-Bus, fixed wired 2

User identification (Logo)StandardOEM

01

Page 28: CSP1-F Combined Protection and Control System … · CSP1-F Combined Protection and Control System Performance and functional outline S ... Operation and display via CMP1 ... robust

28 LF CSP1-F 05.99 E

This Manual undergoes continuous further development and is subject to changes.

We reserve the right to include such changes in future editions of the manual, withoutprior notice.

Status: 05/99