csc-101 line protection ied protection guide

Upload: phani-kumar

Post on 03-Apr-2018

443 views

Category:

Documents


26 download

TRANSCRIPT

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    1/76

    CSC-101

    Line Protection IEDProduct Guide

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    2/76

    VersionV1.00Doc. Code: 0SF.492.050(E)

    Issued Date2010.12Copyright owner: Beijing Sifang Automation Co., Ltd

    Note: the company keeps the right to perfect the instruction. If equipments do not agree with

    the instruction at anywhere, please contact our company in time. We will provide you with

    corresponding service.

    is registered trademark of Beijing Sifang Automation Co., Ltd.

    We reserve all rights to this document, even in the event that a patent is issued and a differentcommercial proprietary right is registered. Improper use, in particular reproduction anddissemination to third parties, is not permitted.

    This document has been carefully checked. If the user nevertheless detects any errors, he isasked to notify us as soon as possible.

    The data contained in this manual is intended solely for the IED description and is not to be

    deemed to be a statement of guaranteed properties. In the interests of our customers, weconstantly seek to ensure that our products are developed to the latest technological standardsas a result; it is possible that there may be some differences between the hardware/softwareproduct and this information product.

    Manufacturer:Beijing Sifang Automation Co., Ltd.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    3/76

    1

    Overview

    CSC-101 is selective, reliable and high

    speed comprehensive transmission line

    protection IED (Intelligent Electronic

    Device) for overhead lines, cables or

    combination of them. It is a proper

    solution for following applications:

    Overhead lines and cables up to

    1000kV voltage level

    All type of station arrangement, such

    as 1.5 breakers arrangement, double

    bus arrangement, etc.

    Extremely long lines

    Short lines

    Heavily loaded lines

    Satisfy the requirement for single and

    /or three pole tripping

    Communication with station automation

    system

    The IED provides a highly sensitive and

    reliable distance protection with

    innovative and proven quadrilateral

    characteristic. In addition to separatedzone extension functionality, five

    distance zones have fully independent

    measuring and setting values which

    gives high flexibility for all types of lines

    and fault resistances. Many other

    functions are integrated to provide a

    complete backup protection library.

    The wide application flexibility makes the

    IED an excellent choice for both newinstallations and retrofitting of the

    existing stations.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    4/76

    2

    Features

    Protection and monitoring IED with

    extensive functional library, user

    configuration possibility and

    expandable hardware design to meet

    with users special requirements

    Redundant A/D sampling channels and

    interlocked dual CPU modules

    guarantee the high security and

    reliability of the IED

    Single and/or three tripping/reclosing

    Highly sensitive startup elements,

    which enhance the IED sensitivity in all

    disturbance conditions and avoid

    maloperation

    Current sudden-change startup

    element

    Zero sequence current startupelement

    Over current startup element

    Undervoltage startup element for

    weak-infeed end of line

    Three kinds of faulty phase selectors

    are combined to guarantee the

    correction of phase selection:

    Current sudden-change phase

    selector

    Zero sequence and negative

    sequence phase selector

    Undervoltage phase selector

    Four kinds of directional elements

    cooperate each other so as to

    determine the fault direction correctly

    and promptly:

    Memory voltage directional

    element

    Zero sequence component

    directional element

    Negative sequence component

    directional element

    Impedance directional element

    Full scheme phase-to-phase andphase-to-earth distance protection with

    five quadrilateral protection zones and

    additional extension zone characteristic

    (21, 21N)

    Power swing function (68)

    Proven and reliable principle of

    power swing logic

    Unblock elements during powerswing

    All useful types of tele-protection

    communication scheme (85)

    Permissive Underreach Transfer

    Trip (PUTT) scheme

    Permissive Overreach Transfer

    Trip (POTT) scheme

    Blocking scheme

    Inter-tripping scheme

    Phase segregated tele-protection

    communication scheme

    Particular logic for tele-protection

    communication scheme

    Current reversal

    Weak-infeed end

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    5/76

    3

    Evolving fault logic

    Sequence tripping logic

    Contacts and/or up to two fiber optical

    ports can be used for tele-protection

    communication scheme

    A complete protection functions library,

    include:

    Distance protection with

    quadrilateral characteristic

    (21,21N)

    Power swing function (68)

    Tele-protection communicationscheme for distance protection

    (85-21,21N)

    Tele-protection communication

    scheme with dedicated earth fault

    protection (85-67N)

    Overcurrent protection (50, 51,

    67)

    Earth fault protection (50N, 51N,67N)

    Emergency/backup overcurrent

    protection (50, 51)

    Emergency/backup earth fault

    protection (50N, 51N)

    Switch-onto-fault protection

    (50HS)

    Overload protection (50OL)

    Overvoltage protection (59)

    Undervoltage protection (27)

    Circuit breaker failure protection

    (50BF)

    Poles discordance protection

    (50PD)

    Dead zone protection (50SH-Z)

    STUB protection (50STUB)

    Synchro-check and energizing

    check (25)

    Auto-recloser function for single-

    and/or three-phase reclosing (79)

    Voltage transformer secondary

    circuit supervision (97FF)

    Current transformer secondary

    circuit supervision

    Self-supervision to all modules in the

    IED

    Complete IED information recording:tripping reports, alarm reports, startup

    reports and general operation reports.

    Any kinds of reports can be stored up

    to 2000 and be memorized in case of

    power disconnection

    Remote communication

    Tele-protection contacts for power

    line carrier protection interface

    Up to two fiber optical ports for

    remote communication applied to

    protection function, like

    tele-protection

    Vast range fiber internal modem,

    applied singlemode optical fiber

    cable

    External optical/electrical

    converter, which support

    communication through SDH or

    PCM, for G.703 (64kbit/s) and

    G.703E1 (2048kbit/s)

    Up to three electric /optical Ethernet

    ports can be selected to communicate

    with substation automation system by

    IEC61850 or IEC60870-5-103

    protocols

    Up to two electric RS-485 ports can be

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    6/76

    4

    selected to communicate with

    substation automation system by

    IEC60870-5-103 protocol

    Time synchronization via

    network(SNTP), pulse and IRIG-Bmode

    Configurable LEDs (Light Emitting

    Diodes) and output relays satisfied

    users requirement

    Versatile human-machine interface

    Multifunctional software tool CSmart for

    setting, monitoring, fault recording

    analysis, configuration, etc.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    7/76

    5

    Functions

    Protection functions

    Description ANSI Code

    IEC 61850

    Logical Node

    Name

    IEC 60617

    graphical symbol

    Distance protection

    Distance protection 21, 21N PDIS Z

    3I >>

    3I >>>

    Earth fault protection 50N, 51N, 67N PEFM

    I0INV>

    I0>>

    I0>>>

    Emergency/backup overcurrent protection 50,51 PTOC3IINV>

    3I >

    Emergency/backup earth fault protection 50N,51N PTOCI0INV>

    I0 >

    Switch-onto-fault protection 50HS PSOF3I >HS

    I0>HS

    Overload protection 50OL PTOC 3I >OL

    Voltage protection

    Overvoltage protection 59 PTOV3U>

    3U>>

    Undervoltage protection 27 PTUV3UBF

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    8/76

    6

    I2>BF

    Dead zone protection 50SH-Z

    STUB protection 50STUB PTOC 3I>STUB

    Poles discordance protection 50PD RPLD

    3I< PD

    I0>PD

    I2>PD

    Synchro-check and energizing check 25 RSYN

    Auto-recloser 79 RREC OI

    Single- and/or three-pole tripping 94-1/3 PTRC

    Secondary system supervision

    CT secondary circuit supervision

    VT secondary circuit supervision 97FF

    Monitoring functions

    Description

    Redundant A/D sampling data self-check

    Phase-sequence of voltage and current supervision

    3I0 polarity supervision

    The third harmonic of voltage supervision

    Synchro-check reference voltage supervision

    Auxiliary contacts of circuit breaker supervision

    Broken conductor check

    Self-supervision

    Logicality of setting self-check

    Fault locator

    Fault recorder

    Station communication

    Description

    Front communication port

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    9/76

    7

    Isolated RS232 port

    Rear communication port

    0-2 isolated electrical RS485 communication ports

    0-3 Ethernet electrical/optical communication ports

    Time synchronization port

    Communication protocols

    IEC 61850 protocol

    IEC 60870-5-103 protocol

    Remote communication

    Description

    Communication port

    Contact(s) interface for power line carrier

    0 2 fiber optical communication port(s)

    Communication distance

    Up to 100kM

    Connection mode

    Direction fiber cable connection

    Digital communication network through converter

    IED software tools

    Functions

    Reading measuring value

    Reading IED report

    Setting

    IED testing

    Disturbance recording analysis

    IED configuration

    Printing

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    10/76

    8

    Function arrangement

    Figure 1 Function arrangement

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    11/76

    9

    Protection functions

    Startup elements

    The startup elements basically work as

    sensitive detector to all type of faults. As

    soon as fault or disturbance happens,

    the highly sensitive startup elements will

    operate immediately and initiate all

    necessary protection functions for

    selective clearance of the fault.

    The control circuit of tripping relays is

    controlled by the startup elements. Only

    when one of the startup elements is

    triggered, the tripping relays can be

    energized to trip. Thus, the maloperation,

    due to fatal internal hardware fault, is

    avoided in this way.

    Based on different principle, there arefour kinds of startup elements listed

    below, which are used to enhance the

    sensitivity, and to guarantee the security

    in case of IEDs internal hardware faults.

    Sudden-change currentstartup element

    Sudden-change phase to phase or zero

    sequence current elements are the main

    startup element that can sensitively

    detect most of faults. The criteria are as

    follows: _or _

    where:

    i=|| i (K) - i (K-T) | - |i (K-T) - i

    (K-2T) ||

    : AB,BC or CA, e.g. iAB= iA-iB

    K: The present sample

    T: The sample quantity of one power cycle

    3i0: Sudden-change zero sequence

    current

    I_Abrupt: The setting value of current

    sudden-change elements

    Zero sequence current startupelement

    Zero sequence current startup element is

    applied to improve the fault detection

    sensitivity at the high resistance earth

    faults. As an auxiliary startup element, it

    operates with a short time delay.

    Overcurrent startup element

    If overcurrent protection function is

    enabled, over current startup element is

    used to improve the fault detection

    sensitivity. As an auxiliary startup

    element, it operates with short timedelay.

    Low-voltage startup element

    When one end of the protected line is a

    weak-source system, and the fault

    sudden-change phase to phase current

    is too low to startup the IED, low-voltage

    startup element can be in service to

    startup the tele-protection

    communication scheme with weak-echo

    logic.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    12/76

    10

    Phase selector

    The IED applies different phase

    selectors to determine the faulty phase tomake tripping or auto-recloser initiation

    correctly. There are three kinds of phase

    selectors based on different principle for

    different fault stages.

    Sudden-change currentphase selector

    It operates as soon as the

    sudden-change current startup elementstarts up. It makes a phase selection for

    fast tripping by comparison amongst

    changes of phase-phase currents, iAB,

    iBC and iCA.

    Symmetrical componentphase selector

    During the whole period of fault, the

    phase selector checks the angle

    between negative sequence current andzero sequence current vectors to

    determine faulty phases. In addition,

    phase to phase faults will be

    discriminated through impedance

    characteristic.

    Low voltage phase selector

    Both current sudden-change phase and

    symmetric component phase selector

    are not applicable for weak-infeed end of

    protected line, so low-voltage phase

    selector is employed in this condition

    without VT failure. Theoretically, when

    one, two or three phase voltages reduce,

    the relevant phase(s) is selected as

    faulty phase.

    Directional elements

    Four kinds of directional elements are

    employed for reliable determination of

    various faults direction. The related

    protection modules, such as distance

    protection, tele-protection schemes and

    overcurrent and earth fault protections,

    utilize the output of the directional

    elements as one of their operating

    condition. All the following directional

    elements cooperate with the mentioned

    protection functions.

    Memory voltage directionalelement

    The IED uses the memory voltage and

    fault current to determine the direction of

    the fault. Therefore transient voltage ofshort circuit conditions doesnt influence

    the direction detection. Additionally, it

    improves the direction detection

    sensitivity for symmetrical or

    asymmetrical close-in faults with

    extremely low voltage. Butit should be

    noted that the memory voltage cannot be

    effective for a long time. Therefore, the

    following directional elements work as

    supplement to detect direction correctly.

    Zero sequence componentdirectional element

    Zero-sequence directional element has

    efficient features in the solidly grounded

    system. The directional characteristic

    only relates to zero sequence impedance

    angle of the zero sequence network ofpower system, regardless of the quantity

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    13/76

    11

    of load current and/or fault resistance

    throughout the fault. The characteristic of

    the zero sequence directional element is

    illustrated in Figure 2.

    Figure 2 Direction detection characteristic of

    zero sequence directional element

    where:

    0_Char: The settable characteristic angle

    Negative sequencecomponent directionalelement

    Negative sequence directional element

    can make an accurate directional

    discrimination in any asymmetric fault.

    The directional characteristic only relates

    to negative sequence impedance angle

    of the negative sequence network of

    power system, regardless the quantity of

    load current and/or fault resistance

    throughout the fault. The characteristic of

    the negative sequence directional

    element is illustrated in Figure 3.

    Figure 3 Direction detection characteristic of

    negative sequence directional element

    where:

    2_Char: The settable characteristic angle

    Impedance directionalelements

    The characteristic of the impedance

    directional element (shown in Figure 4) is

    same with that of distance protection.

    Figure 4 Direction detection characteristic of

    impedance directional element

    where:

    RSET: The resistance setting of relevant

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    14/76

    12

    zone of distance protection

    XSET: The reactance setting of relevant zone

    of distance protection

    n: Multiplier for reverse directional element,

    which make the reverse directional

    element more sensitive than forward

    one

    Distance protection (21, 21N)

    The transmissionline distance protection

    provides a five zones full scheme

    protection with all phase to phase faults

    and phase to earth fault loops

    independently for each zones. Zone

    arrangement illustrated in Figure 5.

    Additionally, one extension zone is

    employed to co-operate with

    auto-recloser and tele-protection

    schemes.

    R

    Zone 1

    X

    Zone 2

    Zone 3

    Zone 4

    Zone 5

    Zone 4 Reverse

    (optional)

    Zone 5 Reverse

    (optional)

    Zone Ext.

    Figure 5 Distance protection zones

    arrangement

    Individual settings of resistive and

    reactive reach for phase to phase and

    phase to earth fault of each zone give

    flexibility for application on overhead

    lines and cables of different types and

    lengths, considering different fault

    resistance for phase to phase and phase

    to ground short circuits.

    Characteristic of distance

    protection

    The IED utilizes quadrilateral characteristic

    as shown in Figure 6.

    X

    R

    X_ZSet

    R_ZSet

    _ZTop

    _ZBottom

    _ZLeft_ZRight

    Figure 6 Characteristics of distance protection

    where:

    R_ZSet: R_ZnPP or R_ZnPE;

    X_ZSet: X_ZnPP or X_ZnPE;

    R_ZnPP: Resistance reach setting for

    phase to phase faultSubscript n means

    the number of protection zone.

    Subscript PP means phase to phase

    fault

    R_ZnPE: Resistance reach setting for

    phase to earth fault. Subscript X means

    the number of protection zone.

    Subscript PE means phase to earth fault

    X_ZnPP: Reactance reach setting for phase

    to phase fault

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    15/76

    13

    X_ZnPE: Reactance reach setting for phase

    to earth fault

    _ZTop: The upper boundary angle of the

    characteristic in the first quadrant is

    designed to avoid distance protection

    overreaching when a close-in fault

    happens on the adjacent line

    _ZBottom: The bottom boundary angle of

    the characteristic in the fourth quadrant

    improves the reliability of the relay to

    operate reliably for close-in faults with

    arc resistance

    _ZRight: The right boundary angle of

    characteristic in the first quadrant is

    used to deal with load encroachment

    problems

    _ZLeft: The left boundary angle of the

    characteristic in the second quadrant

    considers the line impedance angle

    which generally is not larger than 90.

    Thus this angle guarantees the correct

    operation of the relay

    Extended operatingcharacteristic

    To ensure the correct operation at close-in

    faults, a rectangle zone covering the

    original point is added to the quadrilateral

    characteristic. The rectangular offset

    characteristic (illustrated in Figure 7) is

    calculated automatically according to the

    related distance zones settings.Furthermore, the memory voltage direction

    element, the zero sequence directional

    element, and the negative sequence

    direction element are applied to determine

    the direction together.

    Figure 7 Extended polygonal distance protection

    zone characteristic

    Reverse zone characteristic

    In addition to the forward characteristic

    zones mentioned above, the IED

    provides two optional reverse zone

    characteristics to protect connected

    busbar as a backup protection. The

    reverse zone characteristic can be set for

    zones 4 and 5 individually. This reverse

    characteristic has been shown in Figure

    8.

    Figure 8 Characteristic distance protection

    reverse zone

    Switch-onto- fault protection

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    16/76

    14

    function

    Under either auto reclosing or manual

    closing process, the protection function

    is able to discriminate these conditions to

    give an instantaneous tripping once the

    circuit breaker is closed on permanent

    faulty line.

    Power swing function (68)

    The IED provides a high reliable power

    swing detector which discriminates

    between fault and power swing with

    different algorithm.

    Power swing blocking logic

    According to the slow behavior of power

    swing phenomenon, once one of the two

    following conditions is met, the protection

    program will switch to power swing logic

    process:

    Without operation of sudden-change

    current startup element, all

    phase-to-phase impedances, ZAB,

    ZBC

    and ZCA

    enter into the largest

    zone of distance protection

    Without operation of sudden-change

    current startup element, all phase

    currents are bigger than the power

    swing current setting

    In addition, according to the

    experimental results of power swing, it is

    not possible for impedance vector to

    come into protected zones in 150 msafter triggering of the current

    sudden-change startup element. After

    150 ms, the protection program will be

    switched to power swing logic process if

    no tripping is issued.

    Therefore, according to the above

    condition, the IED program enters the

    power swing logic process and the

    distance protection is blocked until

    removing of the mentioned conditions or

    until a fault occurrence in the protected

    line.

    Power swing unblockinglogic

    The unblocking logic provides possibility

    for selective tripping of faults on

    transmission lines during system

    oscillations, when the distance protection

    function is normally blocked. In order to

    unblock distance protection and

    therefore, fast clearing of the faults, the

    following elements are in service to

    discriminate between an internal fault

    and power swing conditions.

    Asymmetric faults detection element

    The zero and negative sequence

    current are always the key features of

    the asymmetric fault. By comparison

    amongst the positive, negative and

    zero sequence component of phase

    current, the element distinguishes the

    asymmetric fault from power swing.

    Three phase fault detection element

    Based on the experimental results

    and practical proof, the change rate

    of measuring resistance and the

    change vector of measuring

    impedance are combined to detect

    the three phase fault during the

    power swing.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    17/76

    15

    Tele-protection communication scheme fordistance protection (85-21)

    To achieve non-delayed and selectivetripping on 100 % of the line length for all

    faults, the communication scheme logic

    is provided for distance protection. The

    communication schemes are as follows:

    Permissive Overreach Transfer Trip

    (POTT)

    Permissive Underreach Transfer Trip

    (PUTT)

    Blocking scheme

    Following protection logic are used to

    ensure correct operation under some

    special fault conditions:

    Current reversal logic

    Weak-infeed end and echo logic

    Evolving fault logic

    Sequence tripping logic

    Direct Transfer Trip

    The function is provided to cooperate

    with related local protection IED, such as

    busbar protection, breaker failure

    protection, etc., to trip the opposite end

    circuit breaker.

    Phase segregated

    communication scheme

    To guarantee correct phase selection at

    all times for simultaneous faults on the

    parallel lines, the phase segregated

    communication scheme logic can be

    employed to support single-pole tripping

    for faults occurring anywhere at all times

    on entire length of the parallel lines.

    Tele-protection communication scheme forearth fault protection (85-67N)

    To achieve highly sensitive and selective

    tripping on 100 % of the line length for all

    faults, especially at the high resistance

    earth faults. It always works as

    complement to tele-protection fordistance protection with a short time

    delay. Permissive transfer trip

    communication scheme is applied

    The protection provides dedicated

    current and time elements independent

    of the earth fault protection.

    Following protection logic are used to

    ensure correct operation under some

    special fault conditions.

    Current reversal logic

    Weak-infeed end logic

    Sequence tripping logic

    Direct Transfer Trip

    The function is provided to cooperate

    with related local protection IED, such as

    busbar protection, breaker failure

    protection, etc., to trip the remote end

    circuit breaker.

    Phase segregatedcommunication scheme

    To guarantee correct phase selection at

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    18/76

    16

    all times for simultaneous faults on the

    parallel lines, the phase segregated

    communication scheme logic can be

    employed to support single-pole tripping

    for faults occurring anywhere at all times

    on entire length of the parallel lines

    Overcurrent protection (50, 51, 67)The protection provides following

    features:

    Two definite time stages

    One inverse time stage

    11 kinds of IEC and ANSI inverse time

    characteristic curves as well as

    optional user defined characteristic

    Settable directional element

    characteristic angle, to satisfy the

    different network conditions and

    applications

    Each stage can be set individually as

    directional/non-directional

    Each stage can be set individually for

    inrush restraint

    Cross blocking function for inrush

    detection

    Settable maximum inrush current

    VT secondary circuit supervision for

    directional protection. Once VT failure

    happens, the directional stage can be

    set to be blocked

    Inrush restraint function

    The protection relay may detect large

    magnetizing inrush currents during

    transformer energizing. In addition to

    considerable unbalance fundamental

    current, inrush current comprises large

    second harmonic current which does not

    appear in short circuit current. Therefore,

    the inrush current may affect the protection

    functions which operate based on the

    fundamental component of the measured

    current. Accordingly, inrush restraint logic

    is provided to prevent overcurrent

    protection from maloperation.

    Furthermore, by recognition of the inrush

    current in one phase, it is possible to set

    the protection in a way that not only the

    phase with the considerable inrush current,

    but also the other phases of theovercurrent protection are blocked for a

    certain time. This is achieved by

    cross-blocking feature integrated in the

    IED.

    The inrush restraint function has a

    maximum inrush current setting. Once the

    measuring current exceeds the setting, the

    overcurrent protection will not be blocked

    any longer.

    Characteristic of directionelement

    The direction detection is performed by

    determining the position of current vector

    in directional characteristic. In other word,

    it is done by comparing phase angle

    between the fault current and the

    reference voltage, Figure 9 illustrates the

    direction detection characteristic for

    phase A element.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    19/76

    17

    Forward

    Ph_Char

    Bisector

    Figure 9 Direction detection characteristic of

    overcurrent protection directional element

    where:

    Ph_Char: The settable characteristic angle

    The assignment of the applied measuring

    values used in direction determination has

    been shown in Table 1for different types of

    faults.

    Table 1 Assignment of applied current and

    reference voltage for directional element

    Phase Current Voltage

    AaI

    bcU

    BbI

    caU

    CcI

    abU

    For three-phase short-circuit fault,

    without any healthy phase, memoryvoltage values are used to determine

    direction clearly if the measured voltage

    values are not sufficient. The detected

    direction is based on the memory voltage

    of previous power cycles.

    Earth fault protection (50N, 51N, 67N)

    The earth fault protection can be used to

    clear phase to earth faults as system

    back-up protection.

    The protection provides following

    features:

    Two definite time stages

    One inverse time stage

    11 kinds of the IEC and ANSI inversetime characteristic curves as well as

    optional user defined characteristic

    Zero sequence directional element

    Negative sequence directional element

    is applied as a complement to zero

    sequence directional element. It can be

    enabled/disabled by setting

    Each stage can be set individually asdirectional/non-directional

    Settable directional element

    characteristic angle, to satisfy the

    different network conditions and

    applications

    Each stage can be set individually for

    inrush restraint

    Settable maximum inrush current

    VT secondary circuit supervision for

    directional protection function. Once

    VT failure happens, the directional

    stage can be set to be blocked

    CT secondary circuit supervision for

    earth fault protection. Once CT failure

    happens, all stages will be blocked

    Zero-sequence current is measured

    from earth phase CT

    Directional element

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    20/76

    18

    The earth fault protection adopts zero

    sequence directional element which

    compares the zero sequence system

    quantities:

    3I0, current is measured from earthphase CT

    3U0, the voltage is used as reference

    voltage. It is calculated from the sum of

    the three phase voltages

    Forward

    0_Char

    Bisector

    0_Ref3U

    0

    -3I0

    3I 090

    Figure 10 Direction detection characteristic of

    zero sequence directional element

    where:

    0_Char: The settable characteristic angle

    For earth fault protection, users can

    choose negative sequence directional

    element as the complement of zero

    sequence directional element. It can be

    used in case of too low zero sequencevoltage due to some fault condition e.g.

    the unfavorable zero-sequence voltage.

    The negative sequence directional

    element characteristic is shown in Figure

    11.

    Figure 11 Direction detection characteristic of

    negative sequence directional element

    where:

    2_Char: The settable characteristic angle

    Furthermore, under the VT failure

    situation, it can be set to block directional

    earth fault protection.

    Inrush restraint function

    The protection relay may detect large

    magnetizing inrush currents during

    transformer energizing. In addition to

    considerable unbalance fundamental

    current, Inrush current comprises large

    second harmonic current which doesnt

    appear in short circuit current. Therefore,

    the inrush current may affect the protection

    functions which operate based on the

    fundamental component of the measuredcurrent. Accordingly, inrush restraint logic

    is provided to prevent earth fault protection

    from mis-tripping.

    Since inrush current cannot be more than a

    specified value, the inrush restraint

    provides an upper current limit in which

    blocking does not occur.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    21/76

    19

    Emergency/backup overcurrent protection(50, 51)

    In the case of VT Fail condition, alldistance zones and protection functions

    related with voltage input are out of

    service. In this case, an emergency

    overcurrent protection comes into

    operation.

    Additionally, the protection can be set as

    backup non directional overcurrent

    protection according to the users

    requirement.

    The protection provides following

    features:

    One definite time stage

    One inverse time stage

    11 kinds of IEC and ANSI inverse

    characteristics curve as well as

    optional user defined characteristic

    Inrush restraint function can be set for

    each stage separately

    Cross blocking of inrush detection

    Settable maximum inrush current.

    Emergency/backup earth fault protection(50N, 51N)

    In the case of VT Fail condition, all

    distance zones and protection functionsrelated with voltage input are out of

    operation. An emergency earth fault

    protection comes into operation.

    Additionally, the protection can be set as

    backup non directional earth fault

    protection according to the users

    requirement.

    The protection provides following

    features:

    One definite time stage

    One inverse time stage

    11 kinds of IEC and ANSI inverse

    characteristics curve as well as

    optional user defined characteristic

    Inrush restraint can be selected

    individually for each stage

    Settable maximum inrush current

    CT secondary circuit supervision for

    earth fault protection. Once CT failure

    happens, all stages will be blocked

    Zero-sequence current is measured

    from 3-phase currents summation

    Switch-onto-fault protection (50HS)

    The protection gives a trip when the

    circuit breaker is closed manually onto ashort circuited line.

    The protection provide following

    features:

    One definite time overcurrent stage

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    22/76

    20

    One definite time earth fault protection

    stage

    Inrush restraint can be selected

    Cross blocking for inrush detection

    Settable maximum inrush current

    Manual closing binary input detection

    Overload protection (50OL)

    The IED supervises load flow in real time.

    If each phase current is greater than the

    dedicated setting for a set delay time, the

    protection will issue alarm.

    Overvoltage protection (59)

    The overvoltage protection detects

    abnormally network high voltageconditions. Overvoltage conditions may

    occur possibly in the power system during

    abnormal conditions such as no-load,

    lightly load, or open line end on long line.

    The protection can be used as open line

    end detector or as system voltage

    supervision normally.

    The protection provides following features:

    Two definite time stages

    Each stage can be set to alarm or trip

    Measuring voltage between

    phase-earth voltage and phase-phase

    (selectable)

    Settable dropout ratio

    Undervoltage protection (27)

    One voltage reduction can occur in the

    power system during faults or abnormal

    conditions.

    The protection provides following

    features:

    Two definite time stages

    Each stage can be set to alarm or trip

    Measuring voltage between

    phase-earth voltage and phase-phase

    selectable.

    Current criteria supervision

    Circuit breaker aux. contact

    supervision

    VT secondary circuit supervision, the

    undervoltage function will be blocked

    when VT failure happens

    Settable dropout ratio

    Breaker failure protection (50BF)

    The circuit breaker failure protection is

    designed to detect failure of the circuit

    breaker during a fault clearance. It

    ensures fast back-up tripping of

    surrounding breakers by tripping relevant

    bus sections.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    23/76

    21

    The protection can be single- or

    three-phase started to allow use with

    single or three-phase tripping

    applications.

    Once a circuit breaker operating failureoccurs on a feeder/transformer, the bus

    section which the feeder/transformer is

    connected with can be selectively

    isolated by the protection. In addition a

    transfer trip signal is issued to trip the

    opposite end circuit breaker of the

    feeder.

    In the event of a circuit breaker failure

    with a busbar fault, a transfer trip signalis issued to trip the remote end circuit

    breaker of the feeder.

    The current criteria are in combination

    with three phase current, zero and

    negative sequence current to achieve a

    higher security.

    The function can be set to give single- or

    three phase re-tripping of the local breaker

    to avoid unnecessary tripping of

    surrounding breakers in the case of the

    circuit breaker with two available trip coils.

    Additionally, during single pole tripping,stage 1 is able to re-tripping three phase

    with settable delay time after single phase

    re-tripping failure.

    Two trip stages (local and surrounding

    breaker tripping)

    Transfer trip command to the remote

    line end in second stage

    Internal/ external initiation

    Single/three phase CBF initiation

    Selectable CB Aux contacts checking

    Current criteria checking (including

    phase current, zero and negative

    sequence current)

    Dead zone protection (50SH-Z)

    The IED provides this protection function

    to protect dead zone, namely the area

    between circuit breaker and CT in the

    case that CB is open. Therefore, by

    occurrence of a fault in dead zone, the

    short circuit current is measured by

    protection relay while CB auxiliary

    contacts indicate the CB is open.

    Internal/external initiation

    Self-adaptive for bus side CT or line

    side CT

    When one bus side CT of feeder is

    applied, once a fault occurs in the dead

    zone, the IED trips the relevant busbar

    zone. Tripping logic is illustrated in

    Figure 12.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    24/76

    22

    Figure 12 Tripping logic when applying bus

    side CT

    When one line side CT is applied, when

    a fault occurs in the dead zone,protection relay sends a transfer trip to

    remote end relay to isolate the fault.

    Tripping logic is illustrated in Figure 13.

    Figure 13 Tripping logic when applying line

    side CT

    STUB protection (50STUB)

    The VT is mostly installed at line side of

    transmission lines. Therefore, for the cases

    that transmission line is taken out of

    service and the line disconnector is

    opened, the distance protection will not be

    able to operate and must be blocked.

    The STUB protection protects the zone

    between the CTs and the open

    disconnector. The STUB protection is

    enabled when the open position of the

    disconnector is connected to IED binary

    input. The function supports one definite

    stage which related concept is shown in

    Figure 14.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    25/76

    23

    Figure 14 Tripping logic of STUB protection

    Poles discordance protection (50PD)

    The phase segregated operating circuit

    breakers can be in different positions

    (close-open) due to electrical or

    mechanical failures during the systemnormal operation.

    The protection operates based on

    information from auxiliary contacts of the

    circuit breaker with additional criteria.

    The protection performs following

    features:

    3 phase CB Aux contacts supervision

    Current criteria checking (including

    phase current, zero and negative

    sequence current)

    Synchro-check and energizing check (25)

    The synchro-check function checks theboth side voltages of the circuit breakerfor synchronism conditions.

    The synchronization function ensures the

    stability of the network in three phase

    reclosing condition. To do this, the two

    side voltages of the circuit breaker are

    compared in terms of magnitude, phase

    angle and frequency differences.

    Additionally, closing can be done safely

    in conditions that at least one side of the

    CB has dead voltage.

    Available for automatic reclosing

    (internally or externally)

    Based on voltage/ angle/ frequency

    difference

    Synchro-check modes:

    Synch-check

    Energizing check, and synch-check ifenergizing check failure

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    26/76

    24

    Override

    Modes of energizing check:

    Dead V4 and dead V3Ph

    Dead V4 and live V3Ph

    Live V4 and dead V3Ph

    Synchro-check reference

    voltage supervision

    If the automatic reclosing is set for

    synchronization check or energizing

    check, during the automatic reclosing

    period, the synchronization condition of

    the voltages between both sides of CB

    cannot be met, an alarm will be issued

    after default time delay.

    Auto-recloser (79)

    For restoration of the normal service

    after a fault an auto reclosing attempt is

    mostly made for overhead lines.

    Experiences show that about 85% of

    faults have transient nature and will

    disappear after an auto reclosing attempt

    is performed. This means that the line

    can be re-energized in a short period.

    The reconnection is accomplished after a

    dead time via the automatic reclosing

    function. If the fault is permanent or short

    circuit arc has not been extinguished, theprotection will re-trip the breaker. Main

    features of the auto-recloser are as

    follows:

    4 shots automatic recloser (selectable)

    Individually settable dead time for three

    phase and single phase fault and for

    each shot

    Internal/external AR initiation

    Single/three phase AR operation

    CB status supervision

    CB Aux. contact supervision

    Cooperation with internal synch-check

    function for reclosing command

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    27/76

    25

    Secondary system supervision

    Current transformer secondarycircuit supervision

    Open or short circuited CT cores can

    cause unwanted operation of some

    protection functions such as earth fault

    current and negative sequence current

    functions.

    Interruption of the CT secondary circuit is

    detected based on zero-sequence current.

    Once CT failure happens, each stage of

    earth fault protection is blocked.

    Voltage transformer secondarycircuit supervision

    A measured voltage failure, due to a

    broken conductor or a short circuit fault in

    the secondary circuit of voltage transformer,

    may result in unwanted operation of the

    protection functions which work based on

    voltage criteria. VT failure supervision

    function is provided to block these

    protection functions and enable the backup

    protection functions. The features of the

    function are as follows:

    Symmetrical/asymmetrical VT failure

    detection

    3-phase AC voltage MCB monitoring

    1-phase AC voltage MCB monitoring

    Zero and negative sequence current

    monitoring

    Applicable in solid grounded,

    compensated or isolated networks

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    28/76

    26

    Monitoring functions

    Phase-sequence of voltage andcurrent supervision

    The phase-sequence of three phase

    voltage and current are monitored in the

    normal condition to determine that the

    secondary circuit of CT or VT is connected

    with IED correctly.

    3I0 polarity supervision

    The IED compare the magnitude and

    phase angle of the calculated zero

    sequence current with the measured one

    to determine that the polarity is connected

    in a right way.

    The third harmonic of voltagesupervision

    If the third harmonic voltage is excessive,

    the alarm without blocking protection willbe given with delay time for checking of the

    secondary circuit of voltage transformer.

    Auxiliary contacts of circuitbreaker supervision

    Current flowing through the transmission

    line and connected CB aux. contacts are

    monitored in phase segregated. Therefore,

    the conflict condition is reported as alarm.

    For example, If CB aux. contacts indicate

    that CB is open in phase A and at the same

    time flowing current is measured in this

    phase, related alarm is reported.

    Broken conductor detection

    The main purpose of the broken conductor

    detection function is to detect the broken

    conductors on protected transmission lines

    and cables. Detection can initiate an alarmor tripping.

    Self-supervision

    All modules can perform self-

    supervision to its key hardware

    components and program, as soon as

    energizing. Parts of the modules are

    self-supervised in real time. All internal

    faults or abnormal conditions will

    initiate an alarm. The fatal faults among

    them will result in the whole IED

    blocked

    The sampled data from the redundant

    A/D sampling channels compare with

    each other in real time. If the difference

    exceeds the specified threshold, it will

    be considered as analog input channel

    fault and the protection will be blocked

    immediately

    CPU module and communication

    module perform real time

    inter-supervision. Therefore

    communication interruption between

    them is detected and related alarm will

    be given

    CRC checks for the setting, program

    and configuration, etc.

    Fault locator

    The built-in fault locator is an impedance

    measuring functiongiving the distance

    from the IED measuring location to the

    fault position in km. The IED reports fault

    location after the IED tripping.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    29/76

    27

    Station communication

    Overview

    The IED is able to connect to one or

    more substation level systems or

    equipments simultaneously, through the

    communication ports with

    communication protocols supported.

    (Shown in Figure 15)

    Front communication port

    There is a serial RS232 port on the front

    plate of all the IEDs. Through this port,

    the IED can beconnected to the

    personal computer for setting, testing,

    and configuration using the dedicated

    Sifang software tool.

    RS485 communication ports

    Up to 2 isolated electrical RS485

    communication ports are provided to

    connect with substation automation

    system. These two ports can work in

    parallel for IEC60870-5-103.

    Ethernet communicationports

    Up to 3 electrical or optical Ethernet

    communication ports are provided to

    connect with substation automation system.

    These two out of three ports can work in

    parallel for protocol, IEC61850 or

    IEC60870-5-103.

    Figure 15 Connection example for multi-networks of station automation system

    Note: All four ports can work in parallel

    Communication protocol

    The IED supports station communication

    with IEC 61850-8 and IED60870-5-103

    protocols.

    By means of IEC61850, GOOSE peer- to

    peer communication make it possible that

    bay IEDs can exchange information to

    each other directly, and a simple

    master-less system can be set up for bay

    and system interlocking and other

    interactive function.

    Time synchronization port

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    30/76

    28

    AllIEDs feature a permanently integrated

    electrical time synchronization port. It can

    be used to feed timing telegrams in IRIG-B

    or pulse format into the IEDs via time

    synchronization receivers. The IED can

    adapt the second or minute pulse in the

    pulse mode automatically.

    Meanwhile, SNTP network time

    synchronization can be applied.

    The Figure 16 illustrates the optional time

    synchronization modes.

    SNTP IRIG-B Pulse

    Ethernet port IRIG-B port Binary input

    Figure 16 Time synchronizing modes

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    31/76

    29

    Remote communication

    Binary signal transfer

    The binary signals can be exchanged

    through remote communication channels

    between the two IEDs on the two end of

    the transmission line or cable respectively.

    This functionality is mainly used for the line

    Tele-protection communication schemes,

    e.g., POTT or PUTT schemes, blocking

    scheme and inter trip and so on.

    Remote communicationchannel

    The IEDs are able to communicate with

    each other in two types:

    Directly fiber-optical cable connection

    mode at distances up to 100 km (see

    Figure 17 and Figure 18)

    Through the communication converter

    with G.703 or G.703E1 interface

    through the public digital

    communication network (see Figure 19

    and Figure 20)

    Because there are up to two selectable

    fiber-optical remote communication ports,the IED can work in the redundant

    communication channel mode, with

    advantage of no time-delay channel switch

    in case of the primary channel broken

    (Figure 18, Figure 20 and Figure 21).

    Figure 17 Single channel, communication through dedicated fiber optical cable

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    32/76

    30

    Figure 18 Double channels, communication through dedicated fiber optical cable

    Communication converter

    The link between the IED and a

    multiplexed communication network is

    made by dedicated communication

    converters (CSC186). They have a

    fiber-optic interface with 1310 nm and 2 FC

    connectors to the protection IED. The

    converter can be set to support an

    electrical G703-64 kbit/s or G703-E1

    2Mbit/s interface, according the

    requirement of the multiplexed

    communication network.

    Figure 19 Single Channel, communication through digital communication network

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    33/76

    31

    Figure 20 Double channels, communication through digital communication network

    Figure 21 Double channels, one channel through digital communication network, one channel

    through dedicated fiber optical cables

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    34/76

    32

    Software tools

    CSmart protection manager is a

    user-friendly software tool for engineering,

    parameter setting, disturbance handling

    and monitoring. It provides versatile

    functionalities required throughout the life

    cycle of protection IEDs. Its features are as

    follows:

    Device administration in projects with

    freely configurable hierarchies for any

    substation and electrical power station

    topology

    Modification, import and export of

    parameter sets sorted by protection

    functions,withsetting logicality check

    Precise fault analysis by Fisewave

    software: visualization of fault records

    in curves over time, circle diagrams,

    vector diagrams, bar charts and data

    sheet

    Intelligent plausibility checks rule out

    incorrect input

    Graphical visualization of

    characteristics and zone diagrams with

    direct manipulation of the curves

    Password-protected access for

    different jobs such as parameter setting,

    commissioning and controlling

    (authorized staff only)

    Testing and diagnostic functions

    decisive support in the commissioning

    phase

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    35/76

    33

    Hardware

    Human-machine Interface(HMI)

    The human-machine interface is simple

    and easy to understand the whole front

    plate is divided into zones, each of them

    with a well-defined functionality:

    Figure 22 IED front plate

    1 Liquid crystal display (LCD)

    2 LEDs

    3 Shortcut function keys

    4 Arrow keys

    5 Reset key

    6 Quit key

    7 Set key

    8 RS232 communication port

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    36/76

    34

    Analogue Input Module (AIM)

    The analogue input module is used to

    galvanically separate and transform the

    secondary currents and voltages

    generated by the measuring transformers.

    CPU Module (CPU)

    The CPU module handles all protection

    functions and logic. There are two CPU

    modules in the IED, CPU1 and CPU2, with

    the same software and hardware. They

    work in parallel and interlock each other to

    prevent maloperation due to the internal

    faults of one CPU modules.

    Moreover, the redundant A/D sampling

    channels are equipped. By comparing the

    data from redundant sampling channels,

    any sampling data errors and the channel

    hardware faults can be detected

    immediately and the proper alarm and

    blocking is initiated in time.

    Communication Module (COM)

    The communication module performs

    communication between the internal

    protection system and external equipments

    such as HMI, engineering workstation,

    substation automation system, RTU, etc.,

    to transmit remote metering, remote

    signaling, SOE, event reports and record

    data.

    Up to 3 channels isolated electrical or

    optical Ethernet ports and up to 2 channels

    RS485 serial communication ports can be

    provided in communication module to meet

    the communication demands of different

    substation automation system and RTU at

    the same time.

    The time synchronization port is equipped,

    which can work in pulse mode or IRIG-B

    mode. SNTP mode can be applied through

    communication port.

    In addition, a series printer port is also

    reserved.

    Binary Input Module (BIM)

    The binary input module is used to connectthe input signals and alarm signals such as

    the auxiliary contacts of the circuit breaker

    (CB), etc.

    Binary Output Module (BOM)

    The binary output modules mainly provide

    tripping output contacts, initiating output

    contacts and signaling output contacts. All

    the tripping output relays have contacts

    with a high switching capacity and are

    blocked by protection startup elements.

    Each output relay can be configured to

    satisfy the demands of users.

    Power Supply Module (PSM)

    The power supply module is used to

    provide the correct internal voltages and

    full isolation between the terminal and the

    battery system.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    37/76

    35

    Layout and dimension

    Figure 23 4U, 19 case with rear cover

    Table 2 Dimension of the IED case

    Legend A B C D E

    Dimension 177 482.6 265 320 437.2

    Unit: mm

    Figure 24 Cut-out on the panel

    Table 3 Dimension of the cutout for IED mounting

    Legend A B C D E

    Dimension 450 465 101.6 178 6.5

    Unit: mm

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    38/76

    36

    Typical connection

    A. For one breaker of single or double busbar arrangement

    Figure 25 Typical connection diagram for one breaker of single or double busbar arrangement

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    39/76

    37

    B. For one and half breaker arrangement

    * **

    IA

    IB

    IC

    UB

    UA

    UC

    U4

    IN

    UN

    Protection IED

    a01

    a02

    a03

    a04

    b01

    b02

    b03

    b04

    a10

    a09

    b09

    b10

    a07

    b07

    A

    B

    C

    AB

    C

    * **

    Figure 26 Typical connection diagram for one and half breaker arrangement

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    40/76

    38

    C. For parallel lines

    IA

    IB

    IC

    UB

    UA

    UC

    U4

    IN

    UN

    Protection IED

    A

    B

    C

    * * *

    a01

    a02

    a03

    a04

    b01

    b02

    b03

    b04

    a10

    a09

    b09

    b10

    a07

    b07

    ***

    INM

    a05

    b05

    Figure 27 Typical connection diagram for parallel lines

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    41/76

    39

    Rear terminals

    The rear view of the protection IED

    Figure 28 Rear view of the protection IED

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    42/76

    40

    Terminals of Analogue Input Module (AIM)

    The Analogue Input Module E

    Figure 29 Terminals arrangement of AIM E

    Table 4 Description of terminals of AIM E

    TerminalAnalogue

    InputRemark

    a01 IA Star point

    b01 IA

    a02 IB Star point

    b02 IB

    a03 IC Star point

    b03 IC

    a04 IN

    b04 IN Star point

    a05 INM

    b05 INM Star point

    a06 Null

    b06 Null

    a07 U4 Star point

    b07 U4

    a08 Null

    b08 Null

    a09 UB Star point

    b09 UC Star point

    a10 UA Star point

    b10 UN

    a11 Null

    b11 Null

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    43/76

    41

    Terminals of Binary Output Module (BOM)

    Binary Output Module A

    The module provides 16 output relays for tripping or initiating, with total 16 contacts.

    a02

    R

    1

    a04

    a06

    a08

    a10

    a12

    a14

    a16

    a18

    a20

    a22

    a24

    a26

    a28

    a30

    a32

    ac

    c02

    c04

    c06

    c08

    c10

    c12

    c14

    c16

    c18

    c20

    c22

    c24

    c26

    c28

    c30

    c32

    R

    3

    R

    5

    R

    7

    R

    9

    R

    11

    R

    13

    R

    15

    R

    16

    R

    2

    R

    4

    R

    6

    R

    8

    R

    10

    R

    12

    R

    14

    Figure 30 Terminals arrangement of BOM A

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    44/76

    42

    Table 5 Definition of terminals of BOM A

    Terminal Definition Related relay

    a02 Trip contact 1-0 Output relay 1

    c02 Trip contact 1-1 Output relay 1

    a04 Trip contact 2-0 Output relay 2

    c04 Trip contact 2-1 Output relay 2

    a06 Trip contact 3-0 Output relay 3

    c06 Trip contact 3-1 Output relay 3

    a08 Trip contact 4-0 Output relay 4

    c08 Trip contact 4-1 Output relay 4

    a10 Trip contact 5-0 Output relay 5

    c10 Trip contact 5-1 Output relay 5

    a12 Trip contact 6-0 Output relay 6

    c12 Trip contact 6-1 Output relay 6

    a14 Trip contact 7-0 Output relay 7

    c14 Trip contact 7-1 Output relay 7

    a16 Trip contact 8-0 Output relay 8

    c16 Trip contact 8-1 Output relay 8

    a18 Trip contact 9-0 Output relay 9

    c18 Trip contact 9-1 Output relay 9

    a20 Trip contact 10-0 Output relay 10

    c20 Trip contact 10-1 Output relay 10

    a22 Trip contact 11-0 Output relay 11

    c22 Trip contact 11-1 Output relay 11

    a24 Trip contact 12-0 Output relay 12

    c24 Trip contact 12-1 Output relay 12

    a26 Trip contact 13-0 Output relay 13

    c26 Trip contact 13-1 Output relay 13

    a28 Trip contact 14-0 Output relay 14

    c28 Trip contact 14-1 Output relay 14

    a30 Trip contact 15-0 Output relay 15

    c30 Trip contact 15-1 Output relay 15

    a32 Trip contact 16-0 Output relay 16

    c32 Trip contact 16-1 Output relay 16

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    45/76

    43

    Binary Output Module C

    The module provides 16 output relays for signal, with total 19 contacts.

    a02

    a04

    a06

    a08

    a10

    a12

    a14

    a16

    a18

    a20

    a22

    a24

    a26

    a28

    a30

    a32

    ac

    c02

    c04

    c06

    c08

    c10

    c12

    c14

    c16

    c18

    c20

    c22

    c24

    c26

    c28

    c30

    c32

    R

    4

    R

    5

    R

    1

    R

    2

    R

    3

    R

    6

    R

    7

    R

    16

    R

    9

    R

    10

    R

    11

    R

    12

    R

    13

    R

    14

    R

    15

    R

    8

    Figure 31 Terminals arrangement of BOM C

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    46/76

    44

    Table 6 Definition of terminals of BOM C

    Terminal Definition Related relay

    a02 Signal 1-0, Common terminal of signal contact group 1

    c02 Signal 2-0, Common terminal of signal contact group 2

    a04 Signal contact 1-1 Output relay 1

    c04 Signal contact 2-1 Output relay 1

    a06 Signal contact 1-2 Output relay 2

    c06 Signal contact 2-2 Output relay 2

    a08 Signal contact 1-3 Output relay 3

    c08 Signal contact 2-3 Output relay 3

    a10 Signal 3-0, Common terminal of signal contact group 3

    c10 Signal 4-0, Common terminal of signal contact group 4

    a12 Signal contact 3-1 Output relay 4

    c12 Signal contact 4-1 Output relay 7

    a14 Signal contact 3-2 Output relay 5

    c14 Signal contact 4-2 Output relay 6

    a16 Signal contact 5-0 Output relay 8

    c16 Signal contact 5-1 Output relay 8

    a18 Signal contact 6-0 Output relay 9

    c18 Signal contact 6-1 Output relay 9

    a20 Signal contact 7-0 Output relay 10

    c20 Signal contact 7-1 Output relay 10

    a22 Signal contact 8-0 Output relay 11

    c22 Signal contact 8-1 Output relay 11

    a24 Signal contact 9-0 Output relay 12

    c24 Signal contact 9-1 Output relay 12

    a26 Signal contact 10-0 Output relay 13

    c26 Signal contact 10-1 Output relay 13

    a28 Signal contact 11-0 Output relay 14

    c28 Signal contact 11-1 Output relay 14

    a30 Signal contact 12-0 Output relay 15

    c30 Signal contact 12-1 Output relay 15

    a32 Signal contact 13-0 Output relay 16

    c32 Signal contact 13-1 Output relay 16

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    47/76

    45

    Terminals of Binary Input Module (BIM )

    Binary Input Module A

    Figure 32: Terminals arrangement of BIM A

    Table 7 Definition of terminals of BIM A

    Terminal Definition Remark

    a02 BI1 BI group 1

    c02 BI2 BI group 2

    a04 BI3 BI group 1

    c04 BI4 BI group 2

    a06 BI5 BI group 1

    c06 BI6 BI group 2

    a08 BI7 BI group 1

    c08 BI8 BI group 2

    a10 BI9 BI group 1

    c10 BI10 BI group 2

    a12 BI11 BI group 1

    c12 BI12 BI group 2

    a14 BI13 BI group 1

    c14 BI14 BI group 2

    a16 BI15 BI group 1

    c16 BI16 BI group 2

    a18 BI17 BI group 1

    c18 BI18 BI group 2

    a20 BI19 BI group 1

    c20 BI20 BI group 2

    a22 BI21 BI group 1

    c22 BI22 BI group 2

    a24 BI23 BI group 1

    c24 BI24 BI group 2

    a26 BI25 BI group 1

    c26 BI26 BI group 2

    a28 BI27 BI group 1

    c28 BI28 BI group 2

    a30 BI29 BI group 1

    c30 BI30 BI group 2

    a32 DC - Input

    Common terminal

    of BI group 1

    c32 DC - InputCommon terminal

    of BI group 2

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    48/76

    46

    Terminals of Communication Module (COM)

    Figure 33 Terminals arrangement of COM

    Table 8 Definition of terminals of COM

    Terminal Definition

    01 Null

    02 Null

    03 Null

    04 Null

    05 Optional RS485 port - 2B

    06 Optional RS485 port - 2A

    07 Optional RS485 port - 1B

    08 Optional RS485 port - 1A

    09 Time synchronization

    10 Time synchronization GND

    11 Null

    12 Null

    13 Null

    14 Null

    15 Null

    16 Null

    Ethernet

    Port A

    Optional optical fiber or RJ45

    port for station automation

    system

    Ethernet

    Port B

    Optional optical fiber or RJ45

    port for station automation

    system

    Ethernet

    Port C

    Optional optical fiber or RJ45

    port for station automation

    system

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    49/76

    47

    Communication ports of CPU module (CPU)

    RX

    TX

    RX

    TX

    Ch A

    Ch B

    Figure 34 Communication ports arrangement of

    CPU module

    Table 9 Definition of communication ports of

    CPU module

    Ports Definition

    Ch A RX Remote communication channel

    A optical fiber data receiving

    port

    Ch A TX Remote communication channel

    A optical fiber data transmitting

    port

    Ch B RX Remote communication channel

    B optical fiber data receiving

    port

    Ch B TX Remote communication channel

    B optical fiber data transmitting

    port

    Note:These ports are optional.

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    50/76

    48

    Terminals of Power Supply Module (PSM)

    Figure 35 Terminals arrangement of PSM

    Table 10 Definition of terminals of PSM

    Terminal Definition

    a02 AUX.DC 24V+ output 1

    c02 AUX.DC 24V+ output 2

    a04 AUX.DC 24V+ output 3

    c04 AUX.DC 24V+ output 4

    a06 Isolated terminal, not wired

    c06 Isolated terminal, not wired

    a08 AUX.DC 24V- output 1

    c08 AUX.DC 24V- output 2

    a10 AUX.DC 24V- output 3

    c10 AUX.DC 24V- output 4

    a12 AUX.DC 24V- output 5

    c12 AUX.DC 24V- output 6

    a14 Alarm contact A1, for AUX.DC

    power input failure

    c14 Alarm contact A0, for AUX.DC

    power input failure

    a16 Alarm contact B1, for AUX.DCpower input failure

    c16 Alarm contact B0, for AUX.DC

    power input failure

    a18 Isolated terminal, not wired

    c18 Isolated terminal, not wired

    a20 AUX. power input 1, DC +

    c20 AUX. power input 2, DC +

    a22 AUX. power input 3, DC +

    c22 AUX. power input 4, DC +

    a24 Isolated terminal, not wired

    c24 Isolated terminal, not wired

    a26 AUX. power input 1, DC -

    c26 AUX. power input 2, DC -

    a28 AUX. power input 3, DC -

    c28 AUX. power input 4, DC -

    a30 Isolated terminal, not wired

    c30 Isolated terminal, not wired

    a32 Terminal for earthing

    c32 Terminal for earthing

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    51/76

    49

    Technical data

    Basic data

    Frequency

    Item Data

    System rated frequency 50 Hz or 60Hz

    Internal current transformer

    Item Data

    Rated current Ir 1 or 5 A

    Nominal current range (0.2 40)x Ir

    Power consumption (per phase)

    at Ir= 1 A 0.5 VA

    at Ir= 5 A 1 VA

    Thermal overload capability

    at Ir= 1 A 100 x Ir for 1 s

    30 x Ir for 10 s

    3 x Ircontinuous

    at Ir= 5 A 40 x Ir for 1 s

    30 x Ir for 10 s

    3 x Ircontinuous

    Internal voltage transformer

    Item Data

    Rated voltage Vr(ph-ph) 100 V /110 V

    Nominal range (ph-e) 0.4 V to 120 V

    Power consumption

    at Vr= 110 V 0.5 VA per phase

    Thermal overload capability in voltage path

    (phase-neutral voltage)

    2Vr, for 10s

    1.5Vr, continuous

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    52/76

    50

    Auxiliary voltage

    Item Data

    Rated auxiliary voltage Vaux 100~125V DC

    195~250V DC

    Permissible tolerance %20 Uaux

    Power consumption

    Normal operation 30 W

    Tripping condition 50 W

    Binary inputs

    Item Data

    Input voltage range 24 V DC

    110/125 V DC

    220/250 V DC

    Response time/dropout time Software provides de-bounce time

    Power consumption, energized 2mA

    Binary outputs

    Item Data

    Max. system voltage 250V DC/AC

    Current carrying capacity 5 A continuous

    30 A for 0.5s making current

    2000 switching cycles

    Making capacity at inductive load with L/R>10 ms 1100 W(DC)

    1250 VA(AC)

    Breaking capacity 250 mA, 100 W resistive, for AC, cos > 0.4

    50W, for DC at L/R < 40 ms

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    53/76

    51

    Type tests

    Insulation test

    Item Data

    Standards IEC 60255-5:2000

    GB/T 15145-2001

    DL/T 478-2001

    Voltage test (100 % test)

    All circuits besides auxiliary voltage and

    RS485/RS232 and time synchronization

    2KV,50Hz,1min

    IEC 60255-5:2000

    GB/T 15145-2001

    DL/T 478-2001

    Auxiliary voltage 3.5 kV DC

    IEC 60255-5:2000

    GB/T 15145-2001

    DL/T 478-2001

    Communication ports and time synchronization

    terminals

    500V,50Hz,1min

    IEC 60255-5:2000

    GB/T 15145-2001

    DL/T 478-2001

    Impulse voltage test

    all circuits, except communication ports and time

    synchronization

    5kV (Ui63V) /1kV (Ui100 M at 500 VDC

    IEC 60255-5:2000

    GB/T 15145-2001

    DL/T 478-2001

    Electromagnetic compatibility tests

    Item Data

    Standards GB/T 14598.9-2002

    identify IEC 60255-22-3:2000, for radiatedelectromagnetic field disturbance test

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    54/76

    52

    GB/T 14598.10-2007

    identify IEC 60255-22-4:2002, for electrical fast

    transient/burst immunity test

    GB/T 14598.13-2008

    Modify from IEC 60255-22-1:2007, for 1MHz

    burst immunity test

    GB/T 14598.14-1998

    identify IEC 60255-22-2:1996, for electrostatic

    discharge test

    GB/T 14598.17-2005

    Identify with IEC 60255-22-6:2002, for

    Conducted electromagnetic field disturbance

    tests

    GB/T 14598.18-2007

    Identify with IEC 60255-22-5:2002, for surge

    immunity test

    GB/T 14598.19-2007

    Identify with IEC 60255-22-7:2003, for power

    frequency immunity test

    GB/T 14598.20-2007

    Identify with IEC 60255-26:2004, for

    electromagnetic compatibility requirements

    High-frequency burst disturbance test 2.5 kV (peak value); 1 MHz

    test duration 2 s

    IEC 60255-22-1, class III

    and VDE 0435 Part 303, class III

    Electrostatic discharge 8 kV contact discharge

    15 kV air gap discharge

    both polarities; 150 pF; Ri = 330

    IEC 60255-22-2; class IV

    and EN 61000-4-2; class IV

    Radio-frequency electromagnetic field disturbance

    non-modulated

    10V/m, 80 to 1000 MHz

    IEC 60255-22-3, class III

    Radio-frequency electromagnetic field disturbance

    amplitude-modulated

    10 V/m, 80MHz to 2.7GHz

    80%AM; 1 kHz

    IEC 61000-4-3, class III

    Radio-frequency electromagnetic field disturbance

    pulse-modulated

    10 V/m, 900 MHz; repetition rate 200 Hz, on

    duration 50 %

    IEC 61000-4-3/ENV 50204, class IIIFast transient disturbance 4KV

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    55/76

    53

    IEC 60255-22-4 and IEC 61000-4-4, class IV

    High-energy surge voltages (Surge)

    Auxiliary voltage

    2KV

    IEC 61000-4-5, class III

    radio-frequency line-conducted disturbance,

    amplitude-modulated

    10 V; 150 kHz to 80 MHz

    AM 80 %; 1 kHz

    IEC 61000-4-6, class III

    Power frequency magnetic field test 30 A/m; 50 Hz, continuous

    300 A/m; 50 Hz, 3 s

    0.5 mT, 50 Hz

    IEC 61000-4-8, class IV

    IEC 60255-6

    Oscillatory surge withstand capability test 2.5kV, 1 MHz

    ANSI/IEEE C37.90.1

    Fast transient surge withstand capability test 4KV

    5kHz

    ANSI/IEEE C37.90.1

    Radiated electromagnetic field disturbance 10 V/m; 25 to 1000 MHz

    amplitude and pulse-modulated

    ANSI/IEEE C37.90.2

    Damped wave 2.5 kV (peak value, polarity alternating)

    100 kHz, 1 MHz, 10 and 50 MHz, Ri = 200

    IEC 60694 / IEC 61000-4-12

    Radiated emission 30MHz to 1GHz ( IT device may up to 5 GHz)

    CISPR11, class A

    EN61000-6-4:2005

    Conducted emission 0.15MHz to 80MHz

    CISPR11, class A

    EN61000-6-4:2005

    Mechanical tests

    Item Data

    During operation

    Standards IEC 60255-21-1:1988

    IEC 60255-21-2

    Vibration Sinusoidal

    10 to 50 Hz; +/- 0.035 mm amplitude

    50 to 150 Hz

    IEC 60255-21-1, class 2

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    56/76

    54

    IEC 60068-2-6

    Shock Semi-sinusoidal

    Acceleration 5 g, duration 11 ms; 6 shocks in both

    directions of 3 axes

    IEC 60255-21-2, class 1

    IEC 60068-2-27

    During transportation

    Standards IEC 60255-21-2

    Vibration Sinusoidal

    5 to 8 Hz: 7.5 mm amplitude

    8 to 150 Hz; 2 g acceleration

    frequency sweep 1 octave/min

    20 cycles in 3 perpendicular axes

    IEC 60255-21-1, class 2

    IEC 60068-2-6

    Shock Semi-sinusoidal

    Acceleration 15 g, duration 11 ms

    6 shocks in both directions of 3 axes

    IEC 60255-21-2, Class 1

    IEC 60068-2-27

    Continuous shock Semi-sinusoidal

    Acceleration 10 g, duration 16 ms

    2000 shocks in both directions

    of 3 axes

    IEC 60255-21-2, class 1

    IEC 60068-2-29

    Environmental tests

    Item Data

    Temperatures

    Type-tested , test Bd, for 16 h -25 C to +70 C

    IEC 60068-2-1

    IEC 60068-2-2

    Recommended permanent operating temperature -10 C to +55C

    IEC 60255-6

    (Legibility of display may be impaired above

    +55 C /+131 F)

    Storage and transport temperature limit -25C~+70C

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    57/76

    55

    Humidity

    Permissible humidity 95 % of relative humidity

    IED design

    Item Data

    Case size 4U19inch

    Dimensions See outline and installation dimension

    drawing

    Weight 10kg

    Protection level IP20 class I

    EN 60529

    IEC 60529

    CE certificate

    Item Data

    EMC DirectiveEN 61000-6-2 and EN61000-6-4 (EMC Council

    Directive 2004/108/EC)

    Low voltage directive EN 60255-27 (Low-voltage directive 2006/95 EC)

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    58/76

    56

    Station communication ports

    Front communication port

    Item Data

    Number 1

    Connection Isolated, RS232; front panel

    9-pin subminiature connector, for CSmart

    Communication speed 9600 baud

    Max. length of communication cable 15 m

    RS485 communication port

    Item Data

    Number 0~2

    Connection 2-wire connector

    Rear port in communication module

    Max. length of communication cable 1.0 km

    IEC 60870-5-103 protocol

    Communication speed Factory setting 9600 baud

    Min. 1200 baud, Max. 19200 baud

    Ethernet communication port

    Item Data

    Electrical communication port

    Number 0 ~ 3

    Connection RJ45 connector

    Rear port in communication module

    Max. length of communication cable 100m

    IEC 61850 protocol

    Communication speed 100 Mbit/s

    IEC 60870-5-103 protocol

    Communication speed 100 Mbit/s

    Optical communication port ( optional )

    Number 0 ~ 3

    Connection SC connector

    Rear port in communication module

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    59/76

    57

    Optical cable type Multi-mode

    Max. length of communication cable 2.0km

    IEC 61850 protocol

    Communication speed 100 Mbit/s

    IEC 60870-5-103 protocol

    Communication speed 100 Mbit/s

    Time synchronization

    Item Data

    Mode Pulse mode

    IRIG-B signal format IRIG-B000

    Connection 2-wire connector

    Rear port in communication module

    Voltage levels differential input

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    60/76

    58

    Remote communication

    Fiber optic communication ports

    Item Data

    Number 1 ~ 2

    Fiber optic cable type Single-mode

    Optic wavelength 1310nm, when the transmission distance 60km

    Optic received sensitivity -38dBm

    Emitter electric level >-8dBm; (the transmission distance -4dBm; (the transmission distance 40~60km)

    >-3dBm; (the transmission distance >60km)

    Fiber optic connector type FC or SC, when the transmission distance 60km

    Data transmission rate 64 kbit/s, G703

    2,048 kbit/s, G703-E1

    Max. transmission distance 100km

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    61/76

    59

    Functions

    NOTE:Ir: CT rated secondary current, 1A or 5A

    In: nominal current of the reference side of transformer

    Distance protection (ANSI 21, 21N)

    Setting range

    Number of settable zone 5 zones

    Distance characteristic Polygonal

    Resistance setting range 0.01120, step 0.01, when Ir=5A

    0.05600, step 0.01, when Ir=1A

    Reactance setting range 0.01120, step 0.01, when Ir=5A

    0.05600, step 0.01, when Ir=1A

    Delay time of distance zones 0.00 ~ 60.00s, step 0.01s

    Time

    Best Operation time 20ms for zone 1 of distance when fault occurs

    within 0.7 time setting value

    Operation time 30ms for zone 1 of distance when fault occurs

    within 0.7 time setting value

    Tolerance

    Dynamic overreaching for zone 1 of distance

    protection

    5%

    Tolerance of time 1% or +20 ms for other zones, when setting

    time > 60ms

    Measuring tolerance of fault locator (not including

    errors caused by factors outside product)

    +3% when fault current is greater than 0.01 Ir at

    metal fault, error will become bigger when fault

    occurs with greater path fault resistance

    Power-swing logic (ANSI 68)

    Setting range

    Range of sudden-change current 0.05 A to 20 A , when Ir=1A

    0.25 A to 100 A when Ir=5A

    Current range of power swing detection 0.05 A to 20 A , when Ir=1A

    0.25 A to 100 A when Ir=5A

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    62/76

    60

    Tele-protection (ANSI 85 21, 21N, 67N)

    Time

    Best operation time

    Operation time

    25ms Permission mode for 21/21N

    30ms for 21/21N

    Overcurrent protection (ANSI 50, 51, 67)

    Setting range

    Current pickup 0.05 A to 20.00 A, when Ir=1A

    0.25 A to 100.00 A, when Ir=5A

    Definite time delay 0.00 to 60.00s, step 0.01s

    Directional element

    Operating area range 85 of characteristic bisector

    Characteristic angle 0 to 90, step 1

    Directional element voltage threshold 5V

    Inverse time characteristics

    IEC standard Normal inverse

    Very inverse

    Extremely inverse

    Long inverse

    ANSI InverseShort inverse

    Long inverse

    Moderately inverse

    Very inverse

    Extremely inverse

    Definite inverse

    user-defined characteristic

    A

    i

    I_SETP

    1

    B

    k

    Time factor of inverse time, A 0.001 to 200.0s, step 0.001s

    Delay of inverse time, B 0.000 to 60.00s, step 0.01s

    Index of inverse time, P 0.005 to 10.00, step 0.005

    set time Multiplier for step n: k 0.05 to 999.0, step 0.01

    Time of definite time stage

    Operating time 40ms, at 1.2 times of set value

    Time of inverse time stage

    Minimum operating time 20ms

    Maximum operating time 100s

    Tolerance of definite time stage

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    63/76

    61

    Current pickup 3% of set value or 0.02Ir

    Angle 3

    Time delay 1% set value or 40ms

    Tolerance of inverse time stage

    Current pickup 3% of set value or 0.02Ir

    Angle 3

    Time delays 5% set value + 40ms

    Earth fault protection (ANSI 50N, 51N, 67N)

    Setting range

    Current pickup 0.05 A to 20.00 A, when Ir=1A

    0.25 A to 100.00 A, when Ir=5A

    Definite time delay 0.00 to 60.00s, step 0.01s

    Directional element

    Operating area range 80 from characteristic bisector

    Characteristic angle 0 to 90, step 1

    Voltage threshold of zero-sequence directional

    element3U0= 1 V

    Voltage threshold of Negative-sequence directional

    element3U2 =2 V

    Current threshold of zero-sequence directional

    element3I0= 0.08In

    Current threshold of Negative-sequence directional

    element3I2= 0.08In

    Inverse time characteristics

    IEC standard Normal inverse

    Very inverse

    Extremely inverse

    Long inverse

    ANSI Inverse

    Short inverse

    Long inverse

    Moderately inverse

    Very inverse

    Extremely inverse

    Definite inverse

    user-defined characteristic A iI_SETP 1 B k

    Time factor of inverse time, A 0.001 to 200.0s, step 0.001s

    Delay of inverse time, B 0.000 to 60.00s, step 0.01s

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    64/76

    62

    Index of inverse time, P 0.005 to 10.00, step 0.005

    set time Multiplier for step n: k 0.05 to 999.0, step 0.01

    Time of definite time stage

    Operating time 40ms, at 1.2 times of set value

    Time of inverse time stage

    Minimum operating time 20ms

    Maximum operating time 100s

    Tolerance of definite time stage

    Current pickup 3% of set value or 0.02Ir

    Angle 3

    Time delay 1% set value or 40ms

    Tolerance of inverse time stage

    Current pickup 3% of set value or 0.02Ir

    Angle 3

    Time delays 5% set value + 40ms

    Emergency/backup overcurrent protection (ANSI 50, 51)

    Setting range

    Current pickup 0.05 A to 20.00 A, when Ir=1A

    0.25 A to 100.00 A, when Ir=5A

    Definite time delay 0.00 to 60.00s, step 0.01s

    Inverse time characteristics

    IEC standard Normal inverse

    Very inverse

    Extremely inverse

    Long inverse

    ANSI Inverse

    Short inverse

    Long inverse

    Moderately inverse

    Very inverse

    Extremely inverse

    Definite inverse

    user-defined characteristic A iI_SETP 1 B k

    Time factor of inverse time, A 0.001 to 200.0s, step 0.001s

    Delay of inverse time, B 0.000 to 60.00s, step 0.01s

    Index of inverse time, P 0.005 to 10.00, step 0.005

    set time Multiplier for step n: k 0.05 to 999.0, step 0.01

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    65/76

    63

    Time of definite time stage

    Operating time 40ms, at 1.2 times of set value

    Time of inverse time stage

    Minimum operating time 20ms

    Maximum operating time 100sTolerance of definite time stage

    Current pickup 3% of set value or 0.02Ir

    Time delay 1% set value or 40ms

    Tolerance of inverse time stage

    Current pickup 3% of set value or 0.02Ir

    Time delays 5% set value + 40ms

    Emergency/backup earth fault protection (ANSI 50N, 51N)

    Setting range

    Current pickup 0.05 A to 20.00 A, when Ir=1A

    0.25 A to 100.00 A, when Ir=5A

    Definite time delay 0.00 to 60.00s, step 0.01s

    Inverse time characteristics

    IEC standard Normal inverse

    Very inverse

    Extremely inverse

    Long inverse

    ANSI Inverse

    Short inverse

    Long inverse

    Moderately inverse

    Very inverse

    Extremely inverse

    Definite inverse

    user-defined characteristic

    A

    iI_SETP 1 B kTime factor of inverse time, A 0.001 to 200.0s, step 0.001s

    Delay of inverse time, B 0.000 to 60.00s, step 0.01s

    Index of inverse time, P 0.005 to 10.00, step 0.005

    set time Multiplier for step n: k 0.05 to 999.0, step 0.01

    Time of definite time stage

    Operating time 40ms, at 1.2 times of set value

    Time of inverse time stage

    Minimum operating time 20ms

    Maximum operating time 100s

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    66/76

    64

    Tolerance of definite time stage

    Current pickup 3% of set value or 0.02Ir

    Time delay 1% set value or 40ms

    Tolerance of inverse time stage

    Current pickup 3% of set value or 0.02IrTime delays 5% set value + 40ms

    Inrush restraint function

    Setting range

    Upper function limit (setting range)

    Max current for inrush restraint

    0.25 A to 20 A , when Ir=1A

    1.25 A to 100 A, when Ir=5A

    Ratio of 2nd

    harmonic current to fundamental

    component current

    0.10 to 0.45, step 0.01

    Cross-block (IL1, IL2, IL3) (settable time) 0.00s to 60.00 s, step 0.01s

    Switch-onto-fault protection (ANSI 50HS)

    Setting range

    Range of phase overcurrent 0.05 A to 20 A , when Ir=1A

    0.25 A to 100 A when Ir=5A

    Range of zero-sequence current 0.05 A to 20 A , when Ir=1A

    0.25 A to 100 A when Ir=5A

    Delay time of phase overcurrent 0.00s to 60.00s, step 0.01s

    Delay time of zero-sequence current 0.00s to 60.00s, step 0.01s

    Tolerance of definite time stage

    Current pickup 3% setting or 0.02Ir

    Time delays 1% setting or +40ms

    Breaker failure protection (ANSI 50 BF)

    Setting range

    Pickup of

    phase current

    Negative sequence current

    zero sequence current

    0.05 A to 20 A , when Ir=1A

    0.25 A to 100 A when Ir=5A

    Delay time of stage 1 0.00s to 32.00 s, step 0.01s

    Delay time of stage 2 0.10s to 32.00 s, step 0.01s

    Tolerances

    Pickup 3% of set value or 0.02Ir

  • 7/28/2019 CSC-101 Line Protection IED Protection Guide

    67/76

    65

    D