cronfa - swansea university open access repository · efficient operating point when their input...
TRANSCRIPT
Cronfa - Swansea University Open Access Repository
_____________________________________________________________
This is an author produced version of a paper published in :
IEEE Transactions on Energy Conversion
Cronfa URL for this paper:
http://cronfa.swan.ac.uk/Record/cronfa29262
_____________________________________________________________
Paper:
Egwebe, A., Fazeli, M., Igic, P. & Holland, P. (2016). Implementation and Stability Study of Dynamic Droop in
Islanded Microgrids. IEEE Transactions on Energy Conversion, 31(3), 821-832.
http://dx.doi.org/10.1109/TEC.2016.2540922
_____________________________________________________________ This article is brought to you by Swansea University. Any person downloading material is agreeing to abide by the
terms of the repository licence. Authors are personally responsible for adhering to publisher restrictions or conditions.
When uploading content they are required to comply with their publisher agreement and the SHERPA RoMEO
database to judge whether or not it is copyright safe to add this version of the paper to this repository.
http://www.swansea.ac.uk/iss/researchsupport/cronfa-support/
1
Abstract—This paper presents a dynamic droop load
sharing scheme based on the available generation capacity
of the distributed generation (DG) units. Since
conventional droop schemes share loads proportional to
units’ ratings, they suffer from the inability to maintain an
efficient operating point when their input renewable power
varies; without imposing their new operating point on
other connected DGs in the microgrid. This problem is
mainly due to the insensitivity of the droop scheme to the
varying nature of the renewable resources used including
wind and solar photovoltaic. A control method is proposed
for PV systems; however, it is applicable for all types of
droop-controlled renewable DG. A stability analysis of the
proposed scheme on DG units is also presented to identify
theoretical and practical limits. The proposed scheme
identifies the DC operating zone of the inverter-based
source as irradiance level changes and conditions the
droop parameters appropriately for an efficient load
sharing based on available generation while the rating of
each unit is also taken into account. The proposed scheme
provides energy saving; since energy demand from a local
auxiliary generator is reduced. The proposed method is
validated using MATLAB/SIMULINK simulations.
Index Terms—Droop control, Distributed Generation, Stability
analysis, Photovoltaic, Microgrids
I. INTRODUCTION
istributed generation (DG) is a term commonly used to
describe small renewable power generators and storage
facilities that are located as close as possible to users. DG
continues to gain numerous applications in modern day power
system engineering - it flourishes from the fact that
advancement in distributed energy technologies enhances the
further implementation of distributed generation systems
(DGS) on the Grid/microgrid networks [1]-[3]. Rapidly
Submission Date: “This work was supported by the Electronics System
Design Centre, College of Engineering, Swansea University, Wales”.
A. M. Egwebe is a PhD student with the Electrical/Electronic Engineering
Department, Swansea University, Wales, (e-mail: [email protected]).
M. Fazeli is a Lecturer with the Electrical/Electronic Engineering Department,
Swansea University, Wales, (e-mail: [email protected]). P. Igic is a Reader with the Electrical/Electronic Engineering Department,
Swansea University, Wales, (e-mail: [email protected]).
P. Holland is an Associate Professor with the Electrical/Electronic Engineering Department, Swansea University, Wales, (e-mail:
growing technologies and enhanced penetration of DGs aids
their potential to provide local energy as well as more
advanced ancillary services to the National Grid (NG)
including operating reserves, spinning reserve, frequency and
voltage regulation [4].
One of the main challenges facing the use of renewable
energy sources globally is how they can be efficiently
interfaced with the existing NG. The NG was designed for a
centralized distribution model characterized by large fossil-
fuelled thermal power plants at the centre and a one way
directional flow of electrical energy from high to low voltage
at the point of use. Renewable generation requires a
distributed generation model where the grid can accept
generation from any point in the transmission or distribution
network without causing technical issues for the equipment
used to control it or cause supply issues due to the large
amount of intermittent generation encountered with wind and
solar [5]. An intermediate solution to the problem highlighted
above is the concept of the microgrid - an interactive customer
friendly cluster of distributed energy resources, loads and
energy storage. It can operate in grid-connected mode or
islanded mode (without NG) to improve power quality and
network reliability. Modern approaches to microgrids promote
autonomous control in a peer-to-peer and plug-and-play
operation model for each DG on the microgrid [3], [6]-[7].
The concept of peer-to-peer ensures there is no master
controller or central storage unit that is critical for the
operation of the microgrid; hence the microgrid will continue
to operate with loss of any DG [1], [6]. Plug-and-play implies
that the DG can seamlessly operate when placed or mounted at
any point in the microgrid network without re-engineering the
control scheme [8].
In Grid-connected mode, control measures are relatively
easy to be implemented since voltage and frequency are
regulated by the utility grid for loads within the microgrid;
whereas in islanded-mode voltage and frequency must be
actively controlled for the continuous and stable performance
of the network [7], [9]. In order to balance generated energy
with demand in a microgrid, renewable energy generation are
often supplemented with dispatchable resources such as
energy storage system and local auxiliary generation (AG) [7]
;absence of such resources can result in the possibility of
stressing the inverter-based sources leading to excessive
voltage rise due to over-modulation, yielding poor power
sharing and circulating current among the inverters that can
harm the switching components and result in overloading and
excessive total harmonic distortion (THD) on the AC-side [6],
[10]-[12].
Implementation and stability study of Dynamic
Droop in islanded MicroGrids Augustine M. Egwebe, Student Member, IEEE, Megdad Fazeli, Member, IEEE, Petar Igic, Senior
Member, IEEE and Paul Holland, Member, IEEE
D
2
In islanded network, DGs as well as fossil-fuel sources must
be able to operate autonomously in balancing generation and
demand, voltage and frequency regulation, cost minimization,
while ensuring system stability [13]-[16]. The droop-sharing
scheme is usually employed in a microgrid for voltage and
frequency control between the available DGs, this scheme
adopts an autonomous load sharing approach, where each
connected DG uses their local parameters for accurate load
sharing. Therefore droop method provides higher flexibility
and reliability when compared to master-slave techniques [2],
[17]-[18].
It is noted that in a microgrid, most line can be mainly
resistive. In these cases, two main methods are proposed in
literature: (1) it is shown in [18]-[19] that in resistive lines,
droops are active power-voltage and reactive power-frequency
slopes. (2) References [19]-[21] proposed a method called
“Virtual Impedance” to reduce the coupling between real and
reactive power flow in low-voltage distribution network due to
non-trivial feeder impedances. Both approaches are applicable
to the method proposed in this paper. However, this paper
considers the classic active power-frequency droop in order to
emphasise that the method is not limited to resistive
microgrids. Moreover; inductive microgrid is studied in many
literatures such as [10], [12], [16], [22]-[24].
Different aspects of droop control have been investigated in
different references such as [1], [6], [13], [14], [20], [25] to
curb the drawbacks with droop-based control i.e. instability
issues due to sudden load perturbation, poor transient
response, inaccurate load sharing, steady state error of voltage
and frequency [26]. Reference [13] proposed the angular
droop method to perform load sharing with minimum
frequency variation; real power droop coefficient can thus be
chosen depending on the maximum/minimum value of load
demand and load sharing ratio [13]. Numerous researches
have also been carried to improved droop sharing scheme
while maintaining a relatively steady frequency and voltage
[13], [25]-[28]. For example [29] highlights the droop control
and average power control via two independent control
variables on each DG for accurate sharing of active and
reactive power- hence eliminating the sensitivity of the droop
method to measurement error and wire mismatches. Reference
[28] proposed a three stage mutually interactive droop scheme
based on DC link voltage variation, for power regulation
between the DG and the AC bus. The scheme operates by the
introduction of a power offset to the calculated power from the
conventional droop scheme, in order to modify voltage
reference to the inverter. The scheme was tested to show
power balance based on variation in load without
consideration for scenario when demand exceeds generation.
Modern approach towards improving the flexibility and
reliability of the microgrid favours a hybrid DG networks
(compromising of renewable sources, energy storage systems
(ESS) and fossil-fuelled AG), with adaptive hierarchy
controller schemes employed for power conditioning and
management [3], [17], [30]. However, the systems studied in
these literatures do not include an auxiliary generator whereas
in any practical microgrid a fossil-fuelled AG is necessary to
supply the critical loads in case of shortage of energy. It is
noted that the role of the AG is not similar to that of a master
unit (in a master-slave paradigm) since unlike in a master-
slave control, the operation of other units are not dependent on
the AG. The ESS often provides power deficit compensation
when all connected DG are fully utilized, with droop
techniques employed for accurate load sharing. For example,
in reference [30] the frequency droop was regulated using
power reference from the ESS. The approach presented in [30]
relies mainly on proper understanding of the state of Charge
(SOC) of the battery in defining operating conditions for
charging the battery and for load sharing. However, the
current paper considers networks without battery storage (in
order to comply with current UK regulations on distributed PV
systems). Moreover, unlike in previous literatures, the control
of an auxiliary generator (AG) is presented and the droop gain
is properly tuned to minimize the energy required from the
AG. Reference [16] proposed a complex multi-stage
optimization scheme to minimize fuel consumption in
microgrids. Beside the fact the proposed method in [16] is
very complex, it does not consider the intermittent nature of
renewable-bases DG units which is a common issue with all of
these studies. This drawback is illustrated in Fig.1:
1f
P2P1P1'
P2'
2
f*
Fig. 1: Steady-state characteristic of traditional droop
The conventional static active power-frequency (P-f) and
reactive power-voltage (Q-V) droop sharing scheme (shown in
Fig. 1) sets a fixed frequency/voltage droop gain irrespective
of the available energy from the renewable source. The
frequency thus only changes due to load change; it is
constrained within the allowable frequency droop gain [14]. In
such cases, a drop in the available power of one of the DG
from P1 to P’1 (e.g. due to a reduction in solar irradiation)
will
shift its frequency (f) to a new operating point (f*). Since the
other DG must comply with the new operating frequency (f*),
its power reduces from P2 to P’2 (even though it might have
the capacity to generate more power).
In order to mitigate this problem references [7] and [22],
[31] proposed a droop scheme for wind turbine generation to
control local demand. Besides the fact that the method was
proposed only for wind generation, the stability analysis of the
scheme was not presented while the authors admitted that the
method may affect the system stability.
The current paper proposes a dynamic droop scheme for
Photovoltaic (PV) systems. The proposed scheme uses the PV
array’s current vs voltage characteristics in defining an
operating range for the inverter-based source to ensure an
efficient load sharing interaction with other DG(s); as the DC
link voltages varies due to varying irradiance of solar energy.
The practical and theoretical stability of the proposed method
is also investigated for one DG unit. This study will be based
on PV sources but it is necessary for all renewable energy
sources i.e. wind, wave, etc.
3
To the best of our knowledge, there is no prior work that
precisely focuses on the intermittent nature of the renewable
source(s) in configuring the droop scheme i.e. droop gain
sensitive to source variation, in order to minimise the energy
required from an auxiliary generator. This is especially useful
in cases where ESS is not allowed, hence energy support is
often provided from utility side or a centralized auxiliary
generator within the microgrid.
II. MICROGRID NETWORK UNDER STUDY
Paux*
L1
P1 Q1
VDC1
PL QL LoadVt δt
V1 δ1
VDC1
AG
PEC
+
-
D1P1, Q1
ω,V P1
Q1
ω
V
L2
P2 Q2
VDC2V2 δ2
+
-
D2P2, Q2
ω,V P2
Q2
ω
V
VDC2
+
DG2
DG1
Paux Qaux
PV Array
Lline1
Lline2
PV Array
Fig. 2: MicroGrid Network Under study
Fig. 2 shows a microgrid network in islanded connection
with 3- phase inverter-based DGs (DG1, DG2). The power
electronic controller (PEC) is used to control the flow of
energy from local auxiliary generator (AG) using local
information from the DGs. This study aims to analyze the load
sharing interaction between these DG sources in the islanded
microgrid network.
The three phase inverter-based sources above are PWM
controlled with PQ, voltage and current controllers. The
traditional PQ controller uses the droop scheme (f vs P and V
vs Q) to autonomously respond to changes in connected loads.
In the absence of maximum power tracking, the PV operating
point is usually determined by the AC-side load demand;
hence the DC link voltage (VDC) will be perturbed
continuously from the minimum operating voltage (VDC-min) to
the PV array’s open circuit voltage (VOC) as the irradiance
level or load varies.
The proposed dynamic droop scheme uses the variation in
irradiance (i.e. VDC) in conditioning the conventional droop
scheme for an efficient load sharing while constraining VDC
within VDC-min to VOC (since inverter output voltage, Vinv ≈
0.5DVDC for a three phase system, where D is the modulation
index [6]). This will involve a linear approximation of the PV
maximum power point characteristic curve and the subsequent
droop gain tracking of irradiance variation within the DG’s
operating zone.
The current study does not consider reactive power sharing;
hence reactive power compensation control is not considered
in the AG control scheme [32].
A. Inverter Operating Zone in DG Application
The mathematical model of a PV array is described in [33]
with P-V characteristic shown in Fig. 3. It was also shown in
[10], [34] that a three-phase inverter (with sinusoidal PWM)
can averagely be modelled using d-q frame transformation
techniques:
DCdqdq VDV
2
1 (1)
Where Vdq is the d-q frame park transform of the AC bus
voltage, Ddq is the modulating index (in d-q frame) and VDC is
the DC link voltage. When there is a reduction in solar
irradiance level (hence decreasing VDC), D must increase to
maintain (1). At D =1; a constant Vdq depends solely on VDC.
Further reduction in VDC due to irradiance perturbation will
reduce Vdq. Generally VDC perturbs in response to irradiance
level and demanded load. Hence, in order to accurately control
AC bus voltage (Vdq), minimum DC voltage VDC-min must
ensure (1) while D = 1; e.g. for a nominal RMS 240V DG(s)
system explained in section II, VDC ≥ 678.8-V (i.e. operating
point limit with modulating index, D = 1). Thus, the PV array
must be designed such that the DC voltage of the maximum
power at a small irradiation (say 0.05 pu) = VDC-min= 678.8 V
(see Fig. 3).
Fig. 3: PV curve for varying irradiance level. (Curve B): Maximum point
curve; (PLoad): Constant Load demand curve
B. Conventional Static Droop Load Sharing Scheme
Using droop control, two or more parallel wired DGs can be
controlled to deliver the required real and reactive power. In
published droop schemes, two systems independent
parameters are controlled to achieve load sharing with
minimal communication between the sources [6], [13], [17],
[30]. The real and reactive powers injected from the DG to
the microgrid are sensed and averaged; the resulting signals
are used to adjust the frequency and voltage amplitude of the
DG [6], [14], [20].
The averaged real and reactive power (P and Q) of the DG(s)
(deduced in [6]) shown in Fig. 2 is given below:
4
X
VV
X
VVP tt sin (2)
)(cos2
tt VV
X
V
X
VVVQ
(3)
Equation (2) and (3) shows P varies with the phase angle
difference (ϕ) between the inverter output voltage (V) and the
common AC bus voltage (Vt) while Q varies with the
amplitude difference (V - Vt). Where X is the output reactance
of the inverter.
The P-ω and Q-V droop are strictly computed to ensure that
accurate load sharing is possible without a significant steady
state frequency and voltage drop across the overall system
[14].
The droop block (defined by ((4) and (5)) is used for
proportional sharing of P & Q; where P varies with system
frequency and Q with system voltage.
rating
prefprefP
mPPm
);( (4)
rating
qrefqrefdQ
VnQQnVV
);( (5)
Where ω, Vd, P and Q are the DG’s angular frequency,
terminal voltage, active and reactive power; ωref and Vref are
the rated angular frequency and voltage of the DG. ∆ω and ∆V
are the allowed frequency and voltage deviation. mp and nq are
the droop coefficients (i.e. the gradient of droop lines in Fig.
4) – which ensures the desired proportional power sharing
based on the DG’s rating (i.e. Prating and Qrating) [13], [23],
[29].
ω*
ω
PratingP
Δω ω = ω* - mpP
V
QratingQ
ΔVV = V
* - nqQ V
*
Fig. 4: Steady-state characteristic of traditional droop
Using (4) and (5), it was shown in [6, 13]:
2
1
1
2
2
1
rating
rating
p
p
P
P
m
m
P
P (6)
A problem arises if the available energy of one DG is not
enough to meet the demanded load. A new frequency
operating point will surface, which forces all other DG on the
network to its new operating point irrespective of the
generating capacity of the other DG(s) as shown in Fig. 1 and
Fig. 3. In other words, a drop in generation of one unit (due to
a reduction in irradiation) causes reductions in all the other
units’ generation (see simulation results in Fig. 8). The
shortage of supply is compensated by the energy stored in the
DC-links’ capacitors (or a local energy storage) which causes
a drop in the DC link voltage. Hence, the DC-link voltage (or
the energy level of the energy storage) can be used to trigger
an auxiliary generator (AG) via a Power Electronic Converter
(PEC) to compensate for the shortage of energy. It is noted
that since the other DGs are forced to reduce their generation,
the energy demanded from the AG will not be optimized. This
is due to the insensitivity of a static droop control to the input
solar energy (Fig. 8).
C. Proposed Dynamic Droop Scheme
This section proposes a dynamic droop control in which the
droop coefficient varies as solar irradiation changes without
the need to measure the irradiation. The method also ensures
that the maximum power from each unit is generated if
required by the load.
Fig. 3 depicts the PV curve of a DG as irradiance level varies.
When available solar power is more than the load power, the
system operates normally within its operating zone (right hand
side of curve B). As solar irradiation (S) drops, the DG will
continue to supply the load, until the available solar power is
not enough to meet the demand (point O); AG is thus
triggered on (when VDC becomes less than a threshold) to
compensate for the shortage in power.
Fig.5: Steady-state characteristic of PV operating zone
The maximum power of a PV system varies according to S. In
order to increase the efficiency of droop controlled PV
systems and ensure proportional load sharing, the maximum
power curve for various level of S can be used to define a
reference for the droop gain. The maximum power points
curve (curve B in Fig. 3) of the PV array can be accurately
approximated by (7) [10] (shown in Fig. 5):
dcVbVaVP DCDCDCDC 23
max (7)
Where a, b, c, and d were deduced using the Matlab “polyfit”
command, VDC is calculated from the Ppv - Vpv characteristics
of the array (as given by the PV manufacturer).
The operating zone is the area specified by VDC-min, PPV-rated
and VOC in Fig.5. As S drops, the operating point (for a given
load) moves towards the PDC-max curve (Fig. 5). At the
intersection of PLoad and PDC-max (point O), for any reduction in
S, the AG is turned on (when VDC becomes less than a
threshold) to compensate for the shortage of energy. In cases
with conventional static droop, drops in S of one unit causes
reductions in power output of all other units (to comply with
the new operating frequency), regardless of their available
generation capacities. As a result, more energy will be
demanded from AG. To solve this problem, the droop gains
5
p = b(VdIgd + VqIgq )
q = b(VqIgd – VdIgq)
δ = ω dt
Vα = V.cosδ
Vβ = V.sinδ
P ω
QV
Vd*
Vq*
Dd
Iabc
Vabcp
q Vd
Vq
Igq
Igd abc
dq
Vdq Ii-dq
+-
ω
P(W)
ω0
ω
P0 P
V
Q(VAR)
V0
V
Q0 Q
P-ω Droop
(mp)
Q-V Droop
(nq)
LPF
Dq
Vd Ii-d
Ii-d* +
--
+Kp
i( )s + ai
s
VqIi-q
Ii-q* +
--
+
Control Block
AC Bus
Transform Block
Kpi( )s + ai
sKp
v( )s + av
s
Kpv( )s + av
s
Plant
Fig. 6: Control block for DG in d-q frame
must vary according to the maximum power point curve of
their associated PV array (i.e. PDC-max):
(8)
Where n is number of PV array = 1, 2,…, N
Although (7) can be used in denominator of (8), it will impose
an unnecessary complexity. After all, it is only needed to have
an inverse relationship between mp and VDC (which in turns
varies with S). So (7) can be approximated as PDC-max≈kVDC+c
where, k and c are constants which are used to get a linear
approximation of (7). Please note that the idea is to make the
droop mechanism sensitive to the available solar power.
However, since droop mechanism is based on the relative ratio
between units, it is not necessary to use (7) and a linear
approximation of it works satisfactorily. This equation
describes the simplest maximum power point tracking method
explained in literature [35]. Droop gains must still be
proportional to the rating of their associated units. Therefore,
(7) is approximated for each PV unit as:
nnDCnnDC cVkP max (9)
where kn and cn are gains to get a linear approximation of the
PDC-max (i.e. (7)) of the nth
PV array. Therefore, the allowed
frequency variation will be:
NNDCNpN
DCpDCp
cVkm
cVkmcVkm
...
22221111 (10)
Doing so, when S is the same on the units, the load is shared
proportional to their ratings which is the same as conventional
units (see result in Fig. 8). However, any reduction in S of one
unit (e.g. unit 1 in Fig. 7), does not force the other units to
reduce their generation as mp is now sensitive to VDC.
Moreover, as illustrated in Fig. 7, the other units will increase
their generation through reducing mp (provided that enough S
is available) to compensate for the power reduction from the
first unit. This significantly reduces the energy demanded
from AG compared to conventional static droop method (see
Fig. 9 for results).
Fig. 7. Dynamic droop operation
D. Three-Phase System Control Scheme
The diagrammatic description of the control scheme of each
inverter-based DG can be approximated using the direct PI
control approach (i.e. ignoring feed forward path for axis
decoupling) as shown in Fig. 6. Synchronous reference frame
parameters are generated using the Park and Clarke
transforms. The droop block is used for accurate sharing of P
& Q; where P varies with system frequency and Q with
system voltage. Where b = 1.5 for a three phase system. The
low pass filter (LPF) is used to deduce average values of P
and Q respectively. The voltage controller regulates the
terminal voltage and generates reference for the current
controller [9], [17], [27], [36]-[37].
A voltage feed forward approach was employed in the current
controller to combat bus voltage disturbance and for voltage
drop compensation; with the bus voltage used as reference.
Compensation terms are added to erode coupling effects. The
current controller generates the control signal for the PWM.
Hard limit block sets the current limit to protect the system
from over current (i.e. restrict the upper and lower limits of
allowable reference voltage). The d & q components are
controlled independently. Where‘d’ regulates active power (P)
and ‘q’ regulates the reactive power (Q) [37]-[38].
The dynamics of the control scheme depends mainly on the
bandwidth of the PQ controller, since the bandwidth of the
current and voltage controller are much higher than that of the
nDCnp
Pm
max
f
PP1' P1 P2 P2'
6
PQ controller [37]. The instantaneous active and reactive
power is given by (11).
)(2
3
)(2
3
gqdgdq
gqqgdd
IVIVq
IVIVp
(11)
LC filter is interfaced at the output of the inverter to reduce
switching harmonics of the output voltage (THD < 5%); filter
parameters were chosen as discussed in [10].
E. Auxiliary Generator Control
The DC link voltage of DGs is an indicator for regulating the
AG (see Fig. 2). When the DC link voltage of either DG
decreases below a threshold (here 0.85pu), AG is switched ON
to compensate for the energy shortage in order to maintain the
demand power. The AG reference power (Fig. 2) is:
N
nnDCaux VP
1
*3 (12)
The proposed method in this paper studies the active power
sharing not reactive power. Thus the PQ control scheme was
adopted in the AG control [32], [39] for injecting active power
into the network when needed, Where Qref for the PQ
controller is zero and Pref is set by (12). The load reactive
power is shared appropriately using the classical Q-V droop.
III. SIMULATION RESULTS
TABLE I
SYSTEM’S PARAMETER
Variable Value
Prating1 0.64 pu
k1 and c1 (Eq. 9) 76.48 and -50692.01
Prating2 0.36 pu
k2 and c2 (Eq. 9) 43.05 and -28442.60
Δf and ΔV 2% and 5%
PLoad 0.75 pu
DC link capacitor, C0 800 μF
Line to line voltage VL-L 415 V
LCL line parameters
10mH/6 μF/0.2mH
LPF bandwidth (ωf) 45 rad/s
The test model consists of two DGs and one AG feeding a 3-
phase load. Each DG has its own control scheme as shown in
Fig. 2 and the load sharing scheme is simulated for both
conventional static droop gain and the proposed dynamic
droop gain.
Various testing scenario were observed in
MATLAB/SIMULINK to analyze the test network depicted in
Fig. 2. Note that all results are presented in pu based on the
total system rating (not each PV system).
A. Conventional Static Droop Scheme
Conventional static droop load sharing was tested for two
PV DG sources shown in Fig. 2, with droop gain set by (4) &
(5) using values for Prating1 and Prating2 given in Table I. The result in Fig. 8 shows load sharing between the DGs
where solar irradiation of DG2 drops in 4 steps and the load- is
constant at 0.75pu. Up to 20s, the load is appropriately shared
based on their rating since the available solar power (Pa1 and
Pa2) on both systems is the same (i.e. 1pu based on their own
ratings). However, as the available power in DG2 (Fig. 8 (b))
drops due to drops in irradiance level, its frequency changes to
a new operating point resulting in a reduction in power
contribution to the load (Fig. 8 (a)). Therefore, DG1 complies
with this new operating point and reduces its power
contribution (Fig. 8 (a)) although its solar irradiance is
constant (Fig. 8 (b)). As a result, the total generation becomes
less than the load which leads to reduction in VDC. When VDC <
0.85 pu, the AG is turned on to supply the shortage (according
to (12)). It is important to note that over the entire simulation
the total available solar power (Pa1+Pa2) > PLoad i.e. there
should not be any need for AG. Hence it can be seen from the
simulation results that the conventional droop scheme does not
make an optimized used of an AG.
Fig. 8: Simulation results of two DG systems using conventional static droop
(a) active power in pu, 1-PLoad , 2-P1 , 3-P2, 4-Paux , (b) available solar power in pu 1-Pa1, 2-Pa2
7
B. Proposed Dynamic Droop Implementation
The simulation was repeated with droop gains set by (10)
using the available solar power for load sharing. Fig. 9(a)
shows that the power is shared appropriately (i.e. based on
rating) - when the solar irradiances are the same. As the
available power on DG2 begins to reduce, its droop gain
increases which in turn reduces the power contribution of DG2
to the overall load. However, the droop gain of DG1
proportionally reduces to compensate for the power drop in
DG2 (since DG1 has extra capacity to compensate for DG2).
The DGs are hence within their ‘operating zone’, since DG1
compensates for the power reduction in DG2 without the need
for the AG (power contribution from AG = 0 as shown in Fig.
9 (a)). The flexibility of the proposed scheme ensures
complementary energy support between the DG(s)-for
instance at time 30 - 40s, the DG(s) fully supply the demanded
power since the combined total available power (0.86pu) is
more than total load (0.75pu).
The dynamic droop when compared with the conventional
droop scheme saves energy, since DGs compensate for one
another which minimize the energy demanded from AG.
Fig. 9: Simulation results of two DG systems using the available solar power
for dynamic load sharing (a) active power in pu, 1-PLoad , 2-P1 , 3-P2, 4-Paux ,
(b) available solar power in pu 1-Pa1, 2-Pa2.
C. Simulation Results with Real-Time Solar Irradiance
Variation
The proposed scheme was also tested using real-time solar
irradiation profile measured at the College of Engineering
Swansea University, Swansea, U.K. (at 51.6100 northern
latitude and 3.9797 western longitudes) as shown in Fig. 10
(a). Fig.10 (b) shows that the contribution of DG1 is reduced
as DG2 reduces when conventional scheme is employed;
hence more energy support is required from the AG. Compare
to the proposed scheme in Fig.10 (c) where the DGs
compensate for each other and thereby provides energy saving
from AG. Fig. 10 (d) shows the AG energy profile of the
conventional and dynamic droop scheme. It can be seen that
the proposed scheme provides energy saving up to 74%
compared to the conventional droop sharing scheme for the
data set studied.
Fig. 10: Simulation results of two DG systems using the real-time solar data
(a) available solar power in pu 1-Pa1, 2-Pa2 (b) active power using
conventional droop in pu, 1-PLoad , 2-P1 , 3-P2, 4-Paux , (c) active power using proposed dynamic droop in pu, 1-PLoad , 2-P1 , 3-P2, 4-Paux , (d) AG Energy
profile for Conventional and Dynamic droop in pu, 1-Conventional Droop, 2-
Proposed Dynamic droop.
8
ωf
sPower
Eqn. 11
P,Qp,q
-
+ Droop
Eqn. 14
Vd
Vq
Igd
Igq
1s
2
VDCD
ω0 ω0t
V
Vd*
Vq* = 0
TFv , TFi
Vidq*
[mp ,nq]VDC
Droop Power Controller
Trans.
Eqn. 15-17
Fig. 11: Control model of power droop controlled PV system
IV. STABILITY ANALYSIS OF THE PROPOSED
SCHEME
For a linear stable operation the modulation index D must be
kept less than 1. This section investigates the effect of the
variation of p-f droop gain (mp) on the operation of a 3-phase
inverter. It has been shown in various literatures [12], [16],
[37], [40] that the dynamics (low-frequency poles) of the DG
is mainly determined by the bandwidth of the droop power
sharing control model shown in Fig. 11. However, in order to
ensure completeness, this study will be based on the entire
linearized state-model of the DG.
qs
sQ
ps
sP
f
f
f
f
)(
)(
(13)
Eq. (4), (5), (11), and (13) is combined and linearized around
an operating point:
Q
Pn
m
V
V
V
I
I
IIVV
IIVV
Q
P
m
Q
P
q
p
q
d
qg
dg
gdgqdq
gqgdqdf
f
f
p
0
00
0
0000
2
3...
00
00
00
0
.
.
.
(14)
The output of the power droop controller (v(t)) is transformed
to d-q components to yield Vqd* for the voltage controller [13]:
Using Clarke transform, v(t) can be rewritten as:
sin
cos
sin
cos)(
0
0
*
*
0
V
V
tV
tV
V
V
Vtv (15)
Parke Transformation representation equals:
*
*
*
*
cossin
sincos
V
V
V
V
q
d (16)
Vdq* is linearized and simplified using (14) and (16):
V
V
V
V
q
d
10
0*
*
(17)
The DG plant model is described by:
][][][ 21
.
dqtdgdqdgdgdgdg VDxx BBA (18)
Where ∆Ddq from fig.11 is given as:
][2
][2
][2
...
][)(22
][
1
*
11
212
*
dqc
dc
dqcv
dc
dqcv
dc
dgvcc
dc
idq
dc
dq
JV
EV
VV
xV
VV
D
CDCDD
DDD
(19)
‘xdg’ is the state variables of the DG converter model; Adg, Bdg-
1 and Bdg-2 are matrixes from the DG plant; Cv, Dv-1 and Dv-2 are
matrixes from voltage controller; Cc, Dc-1 and Dc-2 are matrixes
from current controller, EՓ-dq and JՓ-dq are integration terms of
the voltage and current controllers respectively, Vt is the
terminal AC bus voltage.
Equation (14), (17), (18) and (19) is combined to yield:
][][...
][][][
43
21
.
tdq
dqdqdgdg
VPQ
EJxx
BB
BBA1
(20)
Hence, all the state variables in (20) can be merged to deduce
the linearized complete state-space small signal dynamic
model of the DG in fig. 6 interfaced to a common reference
frame (as shown in [12], [13], [24]):
].[].[ uxdt
d BAx (21)
Tdqddqgidqdqi EVIJIPx
;;00001
000000
00000000000
0010000000
00001
0001
00
000000000
001
000000
00001000
0000010
000000
00000
00000000
0000000000
0
0
0
dt
T
g
p
ff
gd
g
gq
ivf
ivpv
p
gddf
p
VuL
Vm
CC
I
LI
KCF
KKFk
fhdcb
fedcbam
gIgV
m
B
A
;;;;;i
pvpi
i
pi
i
ii
i
pi
i
pvpi
L
KKe
L
FKd
L
Kc
L
Kb
L
KVKa
9
.;;2
3;
0
ppv
i
piff
i
ivpimVKk
L
KChg
L
KKf
Where Q = Vq = 0 , Li is the filter inductance, Lg is the line
impedance, Cf is the filter capacitance, F is feedforward gain
term for the voltage controller, K-terms are the proportional
and integral gains of the current and voltage controller, Δ
implies a small perturbation around the operating point. The
angular perturbation (δ0) in the reference frame is considered
to be very small in this study, i.e. δ0 ≈ 0.
The open loop poles of the system are the eigenvalues of
matrix A. Hence the stability of the inverter can be analyzed
as the droop gain changes using matrix A.
A. Variation of open loop poles for different active and
reactive powers
Fig. 12: Variation of Open loop poles as output power (p) varies with q = 0
The system has five pairs of complex conjugate open loop
poles. There are four pole pairs far to the left from the
imaginary axis whose dynamics has minimal effect on the
stability (hence not shown in Fig. 12). It can be seen that as
contributed power (p) reduces, two poles moves towards
instability (towards the jω axis). The system poles were also
observed as q, nq and VDC changes. Variation in either of them
does not influence system open loop poles. VDC was set to
VDC-min to account for the worst case scenario when D =1.
Fig. 13: Open loop plot of droop controller gain variation showing the
dominant low-frequency poles with p = 0.05pu (worst case scenario), q = 0,
nq = 6.7 x 10-4 and VDC = VDC-min
B. Variation for different mp
As discussed, the open loop poles moves towards instability as
active power p reduces. So in this section in order to study the
worst case scenario, p=0.05pu while mp varies from 0.11 to
0.13.
Fig. 13 has five pairs of complex conjugate poles. Four pole
pair is far to the left (not shown) whose dynamics has minimal
effect on stability and they move away from the imaginary
axis as mp increases. The other pair, shown in Fig. 13, moves
towards instability as mp increases, and crosses the imaginary
axis at a certain value (mp-limit = 0.122).
Therefore the system’s eigenvalue moves towards instability
for large f-P droop gain. For mp greater than mp-limit, system
becomes unstable as shown in Fig. 13.
A drop in VDC due to a decrease in irradiance level causes an
increase in droop gain (mp) to reduce the power contribution
from the DG. On the other hand, a reduction in VDC also
increases the modulation index D to comply with (1). D is
limited to 1 where VDC=VDC-min (see Fig.14). This point defines
a practical stability limit for mp (mp-max) where using (1):
VDC-min ≈ 2Vd; hence using (8) and (9), mp-max for the nth
PV
systems is:
nDCnnp
cVkm
minmax
;
The practical stability limits for the PV systems simulated in
this study are: 4
2max
4
1max 1061.1;1003.1
pp mm
Therefore, it can be concluded that mp-limit>>mp-max which is
illustrated in Fig. 14. Note that mp-max-n is the practical limit
that the droop gain can be reduced to. This happens when the
solar irradiation is very low and Vdc=Vdc-min, D=1.
Fig. 14: Stability limit of the proposed dynamic droop
This study demonstrates that the practical stability limit which
is imposed by modulation index of the inverter is much less
than the theoretical stability limit which is imposed by a very
large droop gain mp. In other words, the dynamic droop
method does not add a further limitation on the operation of an
inverter-based unit.
V. CONCLUSION
Dynamic droop load sharing based on the available solar
power was studied in this paper. The proposed dynamic droop
scheme was validated in MATLAB/SIMULINK. Simulation
results show that the proposed dynamic droop based on the
available solar capacity of DGs can be used for optimum load
sharing.
f
P
mp-max (D=1) mp-limit
10
The presented scheme was validated for multiple PV array
with various irradiance conditions; and it was shown that
power sharing is proportional to the units’ ratings when the
irradiance levels are the same. However, if the solar available
power on one PV array drops, the other inverter-based sources
can generate more power (if the capacity is available) to
compensate for the load demand, without the need for energy
support from local connected auxiliary generators and thereby
providing significant energy saving compared with
conventional static droop control. The scheme was also
validated with real-time (measured) solar irradiation.
A stability analysis was also presented to determine the
theoretical and practical stability limit of the proposed scheme.
It was shown that the dominant low-frequency eigenvalues of
the system are mainly influenced by the parameters of the
active power controller (i.e. the frequency-droop gain, mp). It
was also demonstrated that the proposed dynamic droop will
not make the system unstable as the practical stability limit
(which is defined by modulation index D=1) is much less than
that which is defined by a very large f-p droop gain.
REFERENCES
[1] J. M. Guerrero, H. Lijun, and J. Uceda, "Decentralized Control for Parallel Operation of Distributed Generation Inverters Using
Resistive Output Impedance," IEEE Trans. Ind. Electron., vol. 54,
no. 2, pp. 994-1004, Apr. 2007. [2] K. T. Tan, X. Y. Peng, P. L. So, Y. C. Chu, and M. Z. Q. Chen,
"Centralized Control for Parallel Operation of Distributed
Generation Inverters in Microgrids," IEEE Trans. Smart Grid, vol. 3, no. 4, pp. 1977-1987, Dec. 2012.
[3] K. Jong-Yul, J. Jin-Hong, K. Seul-Ki, C. Changhee, P. Jine-Ho, K.
Hak-Man, and N. Kee-Young, "Cooperative Control Strategy of Energy Storage System and Microsources for Stabilizing the
Microgrid during Islanded Operation," IEEE Trans. Power
Electronics, vol. 25, no. 12, pp. 3037-3048, Dec. 2010. [4] R. Arghandeh, M. Brown, A. Del Rosso, G. Ghatikar, E. Stewart,
A. Vojdani, and A. von Meier, "The Local Team: Leveraging
Distributed Resources to improve Resilence," IEEE PES vol. 12, no. 5, pp. 76-83, Aug. 2014.
[5] N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and G. Strbac,
Embedded Generation. London: The Institute of Electrical Engineers, 2000.
[6] J. M. Guerrero, H. Lijun, and J. Uceda, "Control of Distributed
Uninterruptible Power Supply Systems," IEEE Trans. Ind.
Electron. , vol. 55, no. 8, pp. 2845-2859, Jul. 2008.
[7] M. Fazeli, G. M. Asher, C. Klumpner, and L. Yao, "Novel
Integration of DFIG-Based Wind Generators Within Microgrids," IEEE Trans. Energy Conversion, vol. 26, no. 3, pp. 840-850, Aug.
2011. [8] P. Paigi and R. H. Lasseter, "Autonomous Control of Microgrids,"
IEEE PES Meeting, Monreal,, Jun. 2006.
[9] J. Rocabert, G. M. S. Azevedo, A. Luna, J. M. Guerrero, J. I. Candela, and P. Rodriguez, "Intelligent Connection Agent for
Three-Phase Grid-Connected Microgrids," IEEE Trans. Power
Electronics, vol. 26, no. 10, pp. 2993-3005, Oct. 2011. [10] M. Fazeli, J. B. Ekanayake, P. M. Holland and P. Igic, "Exploiting
PV Inverters to Support Local Voltage:A Small-Signal Model,"
IEEE Trans. on Energy Conversion, , vol. 29, no. 2,pp. 453-462, May 2014.
[11] S. R. Nandurkar and M. Rajeev, "Design and Simulation of three
phase Inverter for grid connected Photovoltaic systems," Proceed. Of Third Biennial National Conf., NCNTE,, pp. 80-83, Feb. 2012.
[12] Y. Mohamed and E. F. El-Saadany, "Adaptive Decentralized
Droop Controller to Preserve Power Sharing Stability of Paralleled Inverters in Distributed Generation Microgrids," IEEE Trans.
Power Electron., vol. 23, no. 6,pp. 2806-2816, Nov. 2008.
[13] R. Majumder, C. Balarko, G. Arindam, M. Rajat, L. Gerard and Z. Firuz, "Improvement of stability and load sharing in an
autonomous microgrid using supplementary droop control loop,"
IEEE Trans. Power Sys., vol. 25,no. 2, pp. 796-808, May. 2010.
[14] R. Majumder, A. Ghosh, G. Ledwich, and F. Zare, "Load sharing
and power quality enhanced operation of a distributed microgrid,"
IET Renewable Power Generation, vol. 3, pp. 109-119, Mar. 2009. [15] S. Anand, B. G. Fernandes, and M. Guerrero "Distributed Control
to Ensure Proportional Load Sharing and Improve Voltage
Regulation in Low-Voltage DC Microgrids," IEEE Trans. Power Electron. , vol. 28, no. 4, pp. 1900-1913, Oct. 2013.
[16] P. H. Divshali, S. H. Hosseinian, and M. Abedi, "A novel multi-
stage fuel cost minimization in a VSC-based microgrid considering stability, frequency, and voltage constraints," IEEE Trans. Power
Sys. , vol. 28, no. 2,pp. 931-939, May 2013.
[17] R. G. Wandhare, S. Thale, and V. Agarwal, "Design of a photovoltaic power conditioning system for hierarchical control of
a microgrid," in IEEE 40th Photovoltaic Specialist Conference
(PVSC), 2014, pp. 3144-3149. [18] Z. Yixin, Z. Fang, and S. Hongtao, "Accurate power sharing
strategy for complex microgrid based on droop control method," in
IEEE ECCE Asia Downunder (ECCE Asia), 2013, pp. 344-350. [19] Z. Yixin, Z. Fang, L. Baoquan, and Y. Hao, "An enhanced load
power sharing strategy for low-voltage microgrids based on
inverse-droop control method," in Power Electronics 2014 International Conference (IPEC-Hiroshima 2014 - ECCE-ASIA) ,
pp. 3546-3552.
[20] K. Jaehong, J. M. Guerrero, P. Rodriguez, R. Teodorescu, and N. Kwanghee, "Mode Adaptive Droop Control With Virtual Output
Impedances for an Inverter-Based Flexible AC Microgrid," IEEE Trans. Power Electronics, vol. 26, no.3,pp. 689-701, 2011.
[21] H. Jinwei and L. Yun Wei, "An Enhanced Microgrid Load
Demand Sharing Strategy," IEEE Trans. Power Electron., vol. 27, no. 9,pp. 3984-3995, Sept. 2012.
[22] M. Fazeli, G.M. Asher, C. Liangzhong, and M. Bazargan, "Novel
Integration of Wind Generator-Energy Storage Systems Within
Microgrids," IEEE Trans. Smart Grid vol. 3, no. 2, pp. 728-737,
May 2012.
[23] I. U. Nutkani, L. Poh Chiang, and F. Blaabjerg, "Cost-based droop scheme with lower generation costs for microgrids," IEEE ECCE
Asia Downunder (ECCE Asia),pp. 339-343,no.5, Jun. 2013.
[24] N. Pogaku, M. Prodanovic, T.C. Green, "Modeling, Analysis and Testing of Autonomous Operation of an Inverter-Based
Microgrid," IEEE Trans. Power Electron., vol. 22, no. 2, pp. 613-
625, 2007. [25] J. C. Vasquez, R.A. Mastromauro, J.M. Guerrero, and M. Liserre,
"Voltage Support Provided by a Droop-Controlled Multifunctional
Inverter," IEEE Trans. Ind. Electronics, vol. 56, no. 11,pp. 4510-4519, Oct. 2009.
[26] A. H. Etemadi, E.J. Davison, and R. Iravani, "A Generalized
Decentralized Robust Control of Islanded Microgrids," IEEE Trans. Power Systems vol. 29, no. 6,pp. 3102-3113, Nov. 2014.
[27] C. Trujillo Rodriguez, D. Velasco de la Fuente, G. Garcera, E.
Figueres and J.A. Guacaneme Moreno, "Reconfigurable Control Scheme for a PV Microinverter Working in Both Grid-Connected
and Island Modes," IEEE Trans. Ind. Electronics, vol. 60, no.4, pp.
1582-1595, Nov. 2013. [28] F. Luo, Y.M. Lai, K.H. Loo, C.K. Tse, and R. Xinbo, "A
generalized droop-control scheme for decentralized control of
inverter-interfaced microgrids," IEEE International Symposium Circuits and Systems (ISCAS), pp. 1320-1323, May 2013.
[29] M. N. Marwali, J. Jin-Woo, and A. Keyhani, "Stability Analysis
of Load Sharing Control for Distributed Generation Systems," IEEE Trans. Energy Conversion, vol. 22, pp. 737-745, Sep. 2007.
[30] H. Mahmood, D. Michaelson, and J. Jin "A Power Management
Strategy for PV/Battery Hybrid Systems in Islanded Microgrids," IEEE Emerging and Selected Topics in Power Electron. , vol. 2,
no. 4, pp. 870-882, Oct. 2014.
[31] M. Fazeli, G. Asher, C. Klumpner, L. Yao, M. Bazargan, and M. Parashar, "Novel control scheme for wind generation with energy
storage supplying a given demand power," Power Electronics and
Motion Control Conference (EPE/PEMC), vol. 14, pp. S14-15-S14-21, Sept. 2010.
[32] Z. Bo, Z. Xuesong, and C. Jian, "Integrated Microgrid Laboratory
System," IEEE Trans. Power Systems, , vol. 27, no.4, pp. 2175-2185, 2012.
11
[33] A. Yazdani and P. P. Dash, "A Control Methodology and
Characterization of Dynamics for a Photovoltaic (PV) System
Interfaced With a Distribution Network," IEEE Trans. Power
Delivery, vol. 24, pp. 1538-1551, Jun. 2009.
[34] D. Mohan, T.M. Undeland, and W. P. Robbins, Power Electronics Converters, Applications, and Design, 3 ed.: John Wiley and Sons,
2003.
[35] M. Fazeli, P. Igic, P. Holland, R.P. Lewis, and Z. Zhou, "Novel Maximum Power Point Tracking with classical cascaded voltage
and current loops for photovoltaic systems," IET Conf. Ren. Power
Gen. , pp. 1-5, Sept. 2011. [36] B. Saritha and P. A. Jankiraman, "Observer based current control
of single-phase inverter in DQ rotating frame," Inter. Conf. Power
Electron. Drives and Energy Sys. , pp. 1-5, Dec. 2006. [37] V. F. Pires, J.F. Martins, and H. Chen, "Dual-inverter for grid-
connected photovoltaic system: Modeling and sliding mode
control," ScienceDirect: Solar Energy, vol. 86, no. 7, pp. 2106-2115, Jul. 2012.
[38] K. Kelesidis, G. Adamidis, and G. Tsengenes, "Investigation of a
control scheme based on modified p-q theory for single phase single stage grid connected PV system," Inter. Conf. Clean Elect.
Power pp. 535-540, Jun. 2011.
[39] Z. Shuben, Y. Jian, W. Xiaomin, and Z. Ruiyi, "Dynamic power provisioning for cost minimization in islanding micro-grid with
renewable energy," in Innovative Smart Grid Technologies
Conference (ISGT), IEEE PES, 2014, pp. 1-5. [40] S. Hongtao, Z. Fang, H. Lixiang, Y. Xiaolong, and Z. Dong,
"Small-signal stability analysis of a microgrid operating in droop control mode," IEEE ECCE Asia Downunder (ECCE Asia), pp.
882-887, Jun. 2013.
Augustine M. Egwebe (M’13) received
the B.Eng. degree (with first class Hons.)
in electronic and electrical Engineering
from Swansea University, Wales, in 2012.
He is currently working towards his Ph.D.
degree in Electrical and Electronic
Engineering at Swansea University, with
core focus in renewable energy systems
and control schemes optimization for large scale integration
with smart grids. His current research interest includes
renewable energy power generation systems, distributed
generation, microgrid, energy management systems, power
electronics and power quality.
He is also a student member with the Institute of Electrical
Technology (IET). He obtained the best graduating student
award from the College of Engineering, Swansea University
and the IET best student award in 2012.
Meghdad Fazeli (M’13) received the B.Sc.
degree in electrical engineering from the
Chamran University of Ahwaz, Iran, in
2004, the M.Sc. degree in electrical
engineering and the Ph.D. degree in wind
generator energy storage control schemes
for autonomous grids both from
Nottingham University, U.K., in 2006 and 2010, respectively.
Since January 2011, he has been with the Swansea University,
U.K. He was appointed as a Lecturer in Electrical Power
Engineering in September 2013. His current research is mainly
concentrated on grid integration of photovoltaic systems. His
main research interests include the integration of renewable
energy resources with grids, smartgrids, and distributed
generation.
Petar Igic (SM’15) is Head/Director of the
Electronic System Design Centre and
Director of the EEE Board of Studies at the
College of Engineering, Swansea
University, UK. He also held the esteemed
EPSRC Advanced Fellowship for his study
in the field of High Power IC technology
development. Petar has 20 year experience of research in
power semiconductor devices and technologies, electro-
thermal compact modelling, modelling and characterization of
microelectronic power semiconductor devices and power
electronics and systems. Dr. Igic has been leading Swansea
University’s contribution to the £50M Low Carbon Research
Institute, a pan-Wales university initiative amongst other.
Petar has also done some of the pioneering work in the
development of the compact models for power bipolar
semiconductor devices. He worked on industrial projects or
has been a consultant to several major Japanese, European and
American multinationals, such as TOYOTA, HITACHI,
Vishay SILICONIX, IR, ALSTOM. He has published over
100 scientific papers in journals and international conferences
and technical reports.
Paul M. Holland (M’12–M’14)
received the B.Sc. degree (with Hons.)
in engineering physics from Sheffield
Hallam University, U.K., in 1993, and
the Ph.D. degree in power integrated
circuit technology development at
Swansea University, U.K., in 2007.
He spent the first ten years of his career
working in the U.K. semiconductor industry for GEC Plessey
and ESM Ltd., as a Senior Process and a Device Engineer.
After working as a Researcher at Swansea University from
2002, he was appointed as a Lecturer in 2008 in the College of
Engineering and is now an Associate Professor. His research
interests include the application of CMOS technologies in the
areas of power ICs and Lab-On-A-Chip development which
has been funded by the Engineering and Physical Sciences
Research Council. He has published and presented more than
30 scientific papers in journals and international conferences.