correlating committee on automatic sprinkler systems...ave. ernesto t. lefevre parque lefevre panama...

268
Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: November 3, 2014 TO: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems FROM: Matt Klaus, Principal Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AUT-AAC AGENDA PACKAGE A2015 Second Draft Meeting ________________________________________________________________________ Enclosed is the agenda for the Second Draft meeting for the NFPA Correlating Committee on Automatic Sprinkler Systems. NFPA 13, 13R, 13D, 24 and 291 have entered the Annual 2015 revision cycle and will produce 2016 Editions. For administrative questions, please feel free to contact Elena Carroll at (617) 984-7952. For technical questions, please feel free to contact Matt Klaus at (617) 984-7448. You can also reach either of us via e-mail at [email protected] or [email protected]. We look forward to meeting everyone in Chicago.

Upload: others

Post on 05-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • Correlating Committee

    on Automatic Sprinkler Systems

    M E M O R A N D U M

    DATE: November 3, 2014 TO: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems FROM: Matt Klaus, Principal Fire Protection Engineer/NFPA Staff Liaison

    SUBJECT: AUT-AAC AGENDA PACKAGE – A2015 Second Draft Meeting ________________________________________________________________________

    Enclosed is the agenda for the Second Draft meeting for the NFPA Correlating Committee on

    Automatic Sprinkler Systems. NFPA 13, 13R, 13D, 24 and 291 have entered the Annual 2015

    revision cycle and will produce 2016 Editions.

    For administrative questions, please feel free to contact Elena Carroll at (617) 984-7952.

    For technical questions, please feel free to contact Matt Klaus at (617) 984-7448. You can

    also reach either of us via e-mail at [email protected] or [email protected]. We look forward to

    meeting everyone in Chicago.

    mailto:[email protected]:[email protected]

  • Table of Contents

    Part 1 - Meeting Agenda

    Part 2 - Committee Address List

    Part 3 – New Process Worksheets

    Part 4 – A2015 First Draft Meeting Minutes

    Part 5 - A2015 Key Dates

    Part 6- Second Revisions w/ Ballot Comments

  • Part 1 – Meeting Agenda

  • Correlating Committee on Automatic Sprinkler Systems

    Second Draft Meeting

    November 12-13

    Chicago Marriott Suites O’Hare

    6155 North River Road

    Rosemont, IL 60018

    Tel: (800) 228-9290

    AGENDA

    Wednesday November 12, 2014

    1. Call to Order – 1:00 PM 2. Introductions of Members and Staff 3. Review and Approval of A2015 First Draft Meeting Minutes 4. Review of A2015 Revision Cycle 5. Review of Distributed Material and Workload 6. TC Chair Reports

    a. AUT-PRI (Wagoner) b. AUT-SSI (Noble) c. AUT-SSD (Leavitt) d. AUT-RSS (Pilette) e. AUT-HBS (Biggins)

    7. New Business a. Additional Correlating Items b. NFPA 13 Redundancy and Reorganization c. NFPA Sprinkler Project Task Group Work d. NFPA 13D Scope – Height Limitation e. Assignments for A2018 Cycle

    8. Adjourn (TBD on Thursday, November 13)

  • Part 2 – Correlating Committee Roster

  • Address List No PhoneAutomatic Sprinkler Systems AUT-AAC

    Matthew J. Klaus10/29/2014

    AUT-AACKenneth W. LinderChairSwiss Re2 Waterside Crossing, Suite 200Windsor, CT 06095

    I 10/10/1997AUT-AAC

    Jose R. BazPrincipalJRB Associates Group Inc.2725 SW 102nd AvenueMiami, FL 33165NFPA Latin American SectionAlternate: Donato A. Pirro

    M 11/14/1997

    AUT-AACKerry M. BellPrincipalUL LLC333 Pfingsten RoadNorthbrook, IL 60062-2096Alternate: Jeff Hebenstreit

    RT 10/10/1997AUT-AAC

    Tracey D. BellamyPrincipalTelgian Corporation900 Circle 75 Parkway, Suite 680Atlanta, GA 30339The Home DepotAlternate: Ralph E. Bless, Jr.

    U 10/29/2012

    AUT-AACRussell P. FlemingPrincipalNational Fire Sprinkler Association, Inc.40 Jon Barrett RoadPatterson, NY 12563-2164Alternate: Kenneth E. Isman

    M 10/10/1997AUT-AAC

    Scott T. FransonPrincipalThe Viking Corporation210 North Industrial Park RoadHastings, MI 49058Alternate: Scott T. Martorano

    M 1/18/2001

    AUT-AACMichael J. FriedmanPrincipalFriedman Consulting, Inc.1 Bluestone RoadLutherville, MD 21093-4512

    SE 3/21/2006AUT-AAC

    Raymond A. GrillPrincipalArup1120 Connecticut Avenue, NW, Suite 1110Washington, DC 20036Alternate: Jeffrey E. Harper

    SE 10/10/1997

    AUT-AACLuke HiltonPrincipalLiberty Mutual Property13830 Ballantyne Corporate Place, Suite 525Charlotte, NC 20277-2711Alternate: James P. Carroll

    I 4/16/1999AUT-AAC

    Alex HoffmanPrincipalViking Fire Protection Inc.7885 North Fraser Way, Unit 140Burnaby, BC V5J 5M7 CanadaCanadian Automatic Sprinkler Association

    IM 9/30/2004

    AUT-AACRoland J. HugginsPrincipalAmerican Fire Sprinkler Association, Inc.12750 Merit Drive, Suite 350Dallas, TX 75251Alternate: Donald D. Becker

    IM 10/10/1997AUT-AAC

    Sultan M. JaveriPrincipalSC Engineering2 Impasse Du GuernehlieLa Trinite, Surzur, 56190 France

    IM 10/10/1997

    1

  • Address List No PhoneAutomatic Sprinkler Systems AUT-AAC

    Matthew J. Klaus10/29/2014

    AUT-AACCharles W. KetnerPrincipalNational Automatic Sprinkler Fitters LU 669Joint Apprenticeship & Training Committee7050 Oakland Mills RoadColumbia, MD 20732United Assn. of Journeymen & Apprentices of thePlumbing & Pipe Fitting Industry

    L 1/10/2008AUT-AAC

    Andrew KimPrincipalNational Research Council of CanadaInstitute for Research in Construction1200 Montreal Road, Building M-59Ottawa, ON K1A 0R6 CanadaAlternate: Joseph Su

    RT 10/10/1997

    AUT-AACJohn A. LeBlancPrincipalFM Global1151 Boston-Providence TurnpikePO Box 9102Norwood, MA 02062-9102Alternate: David B. Fuller

    I 07/29/2013AUT-AAC

    David O. LowreyPrincipalCity of Boulder Fire Rescue1805 33rd StreetBoulder, CO 80301

    E 10/29/2012

    AUT-AACJeannene Yvonne MeismanPrincipalReedy Creek Fire Department37117 Lightwood DriveZephyrhills, FL 33541-7531

    E 07/29/2013AUT-AAC

    Brock MitchellPrincipalExtended Stay Hotels11525 N Community House RdSuite 100Charlotte, NC 28277

    U 10/29/2012

    AUT-AACGarner A. PalenskePrincipalAon Fire Protection Engineering Corporation11770 Bernardo Plaza Court, Suite 116San Diego, CA 92128Alternate: James G. Gallup

    I 4/17/2002AUT-AAC

    J. William SheppardPrincipalSheppard & Associates, LLC24756 Tudor LaneFranklin, MI 48025

    SE 10/10/1997

    AUT-AACDouglas Paul StultzPrincipalUS Department of the NavyNAVFAC MIDLANT, Code CI459742 Maryland AvenueBuilding Z-140, Room 126Norfolk, VA 23508Alternate: Brian Paul Carnazza

    E 3/15/2007AUT-AAC

    J. Michael ThompsonPrincipalThe Protection Engineering Group, PC14585 Avion Parkway, Suite 150Chantilly, VA 20151Alternate: John G. O'Neill

    SE 4/17/2002

    AUT-AACLynn K. UnderwoodPrincipalAxis US Property303 West Madison Street, Suite 500Chicago, IL 60606Alternate: Adam Seghi

    I 10/10/1997AUT-AAC

    Donald D. BeckerAlternateRJC & Associates, Inc.PO Box 398Dallas Center, IA 50063-0398American Fire Sprinkler AssociationPrincipal: Roland J. Huggins

    IM 10/10/1997

    2

  • Address List No PhoneAutomatic Sprinkler Systems AUT-AAC

    Matthew J. Klaus10/29/2014

    AUT-AACRalph E. Bless, Jr.AlternateTelgian Corporation900 Circle 75 Parkway, Suite 680Atlanta, GA 30339The Home DepotPrincipal: Tracey D. Bellamy

    U 10/29/2012AUT-AAC

    Brian Paul CarnazzaAlternateUS Department of the NavyNAVFAC Mid-Atlantic9742 Maryland Ave., Bldg. Z-140, Room 103Norfolk, VA 23511Principal: Douglas Paul Stultz

    E 03/05/2012

    AUT-AACJames P. CarrollAlternateLiberty Mutual Insurance18018 Java Isle DriveTampa, FL 33647-2708Principal: Luke Hilton

    I 08/11/2014AUT-AAC

    David B. FullerAlternateFM Global1151 Boston Providence TurnpikePO Box 9102Norwood, MA 02062-9102Principal: John A. LeBlanc

    I 7/26/2007

    AUT-AACJames G. GallupAlternateAon Fire Protection Engineering Corporation2810 North Tippecanoe AvenueTucson, AZ 85745Principal: Garner A. Palenske

    I 10/29/2012AUT-AAC

    Jeffrey E. HarperAlternateHughes Associates/RJA Group600 West Fulton Street, 5th FloorChicago, IL 60661-1241Principal: Raymond A. Grill

    SE 08/11/2014

    AUT-AACJeff HebenstreitAlternateUL LLC484 Tamarach DriveEdwardsville, IL 62025-5246Underwriters Laboratories Inc.Principal: Kerry M. Bell

    RT 08/11/2014AUT-AAC

    Kenneth E. IsmanAlternateNational Fire Sprinkler Association, Inc.40 Jon Barrett RoadPatterson, NY 12563-2164Principal: Russell P. Fleming

    M 10/10/1997

    AUT-AACScott T. MartoranoAlternateThe Viking Corporation210 North Industrial Park RoadHastings, MI 49058Principal: Scott T. Franson

    M 3/1/2011AUT-AAC

    John G. O'NeillAlternateThe Protection Engineering Group, PC14900 Bogle Drive, Suite 200Chantilly, VA 20151Principal: J. Michael Thompson

    SE 1/1/1977

    AUT-AACDonato A. PirroAlternateElectro Sistemas De Panama, S.A.Ave. Ernesto T. LefevreParque LefevrePanama City, PanamaNFPA Latin American SectionPrincipal: Jose R. Baz

    M 11/14/1997AUT-AAC

    Adam SeghiAlternateCoda Risk Analysis9624 Vista View DriveAustin, TX 78750Principal: Lynn K. Underwood

    I 10/29/2012

    3

  • Address List No PhoneAutomatic Sprinkler Systems AUT-AAC

    Matthew J. Klaus10/29/2014

    AUT-AACJoseph SuAlternateNational Research Council of Canada1200 Montreal Road, M-59Ottawa, ON K1A 0R6 CanadaPrincipal: Andrew Kim

    RT 10/29/2012AUT-AAC

    James B. BigginsNonvoting MemberGlobal Risk Consultants Corporation15732 West Barr RoadManhattan, IL 60442-9012TC on Hanging & Bracing of Water-Based Systems

    SE 7/28/2006

    AUT-AACRobert G. CaputoNonvoting MemberFire & Life Safety AmericaConsolidated Fireprotection, Inc.657 Cantara LaneVista, CA 92081TC on Foam-Water Sprinklers

    SE 10/29/2012AUT-AAC

    William E. KoffelNonvoting MemberKoffel Associates, Inc.8815 Centre Park Drive, Suite 200Columbia, MD 21045-2107Safety to Life Correlating Committee

    SE 10/10/1997

    AUT-AACRussell B. LeavittNonvoting MemberTelgian Corporation2615 South Industrial Park AvenueTempe, AZ 85282-1821TC on Sprinkler System Discharge Criteria

    U 10/28/2008AUT-AAC

    Joe W. NobleNonvoting MemberNoble Consulting Services, LLC6345 South Jones Blvd., #100Las Vegas, NV 89130TC on Sprinkler System Installation Criteria

    E 4/17/1998

    AUT-AACMaurice M. PiletteNonvoting MemberMechanical Designs Ltd.19 Erie DrivePO Box 2188Natick, MA 01760TC on Residential Sprinkler Systems

    SE 7/28/2006AUT-AAC

    Kenneth W. WagonerNonvoting MemberParsley Consulting Engineers350 West 9th Avenue, Suite 206Escondido, CA 92025-5053TC on Private Water Supply Piping Systems

    SE 03/02/2010

    AUT-AACJohn J. WalshMember EmeritusUA Joint Apprenticeship Committee Local 669502 Kings Farm Blvd., #302Rockville, MD 20850United Assn. of Journeymen & Apprentices of thePlumbing & Pipe Fitting Industry

    SE 1/1/1974AUT-AAC

    Matthew J. KlausStaff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

    12/16/2010

    4

  • Part 3 – New Process Worksheet

  • NEW PROCESS ACTIONS AND MOTIONS

    Possible Action #1: Accept Public Comment (exactly as it is)

    Action Required Sample motion

    Create a Second Revision I move to create a Second Revision using PC #

    ______.

    Possible action #2: Reject but see (revise submitted text)

    Action Required Sample motion

    Step 1 Create a Second Revision based on a

    Public Comment

    I move to create a Second Revision based on PC # _____with the following changes to the text . .

    .

    Step 2 If the revision is related to multiple PCs,

    respond to all of them together using the cart function

    I move to create a Second Revision based on PC # ____and incorporating PC #s _____with the

    following changes to the text . . .

    Possible action #3: Reject (no change to the standard)

    Action Required Sample motion

    Generate a statement (substantiation) I move to reject PC # ____ with the following

    substantiation . . .

    Possible Action #4: Reject but hold (new material)

    Action Required Sample motion

    Reject Public Comment for this cycle, but

    save for next revision cycle

    I move to reject PC # ____ but hold it for consideration during the First Draft meeting next

    cycle.

  • Part 4 – First Draft Meeting Minutes

  • Correlating Committee on Automatic Sprinkler Systems First Draft Meeting

    Renaissance Blackstone Hotel Chicago, Illinois

    December 11, 2013

    Attendees:

    See attached sign-in sheet.

    1. Ken Linder (CC Chair) called the meeting to order at 8:00 am and began introductions.

    2. The A2012 ROC minutes were approved with a single revision (Add Ray Grill to attendance sheet).

    3. Matt Klaus gave the staff report and a presentation on the meeting procedures.

    4. Ken Linder discussed the logistics for the meeting and the order of the task group reporting.

    5. The technical committee (TC) chairs for the 5 TCs representing the sprinkler project presented their reports of correlation issues. The CC members acted on

    these reports by preparing First Correlating Notes and First Correlating Revisions

    where appropriate. See First Draft Report for details.

    6. The CC encourages the HBS TC to continue to communicate with other technical committees that inappropriately reference the NFPA 13 hanging and bracing

    chapter.

    7. The CC encourages the PRI TC to review section 5.9.4.4 to look at the potentially redundant sections.

    8. The CC encourages the SSI TC to review the new venting language. The new venting requirements require the vent to remove the “majority” of air. This

    language is unenforceable and may lead to a NITMAM eliminating what is

    otherwise a concept that was looked at favorably by the TC. Furthermore, the TC

    should review the concept of “ganged venting” to make sure that the proposed

    language adequately addresses this potential application.

    9. The CC encourages each of the TCs to come up with a plan(s) for streamlining

    the standard and making it easier to follow. There are redundancies throughout

    the standard that have increased the length of the document without adding any

  • clarity. Action items should be presented to the CC for their SD meeting this

    cycle with potential implementation for the A2018 Revision Cycle.

    10. The extract task group (SSD) is encouraged to add language to the beginning of the extract chapter explaining when and how the extracts apply. Do these

    requirements apply to all systems or only when the referenced standard is

    applicable in the jurisdiction where work is being performed?

    11. The Second Draft meeting is scheduled for Fall/Winter 2014 at a date and location to be determined.

    12. Meeting adjourned at 5:00 pm on December 11.

  • ATTENDANCE FOR CORRELATING COMMITTEE FD MEETING – DEC 11, 2013

    Attendees

    Principals:

    Kenneth Linder, Chair

    Kerry Bell

    Tracey Bellamy

    Russell Fleming

    Raymond Grill

    Alex Hoffman

    Sultan Javeri

    John LeBlanc

    Jeannene Meisman

    Brock Mitchell

    J. Sheppard

    Lynn Underwood

    Alternates:

    David Fuller

    Kenneth Isman

    Donato Pirro

    Adam Seghi

    Nonvoting Members:

    Robert Caputo

    William Koffel

    Russell Leavitt

    Joe Noble

    Maurice Pilette

    Kenneth Wagoner

    Matthew Klaus, NFPA Staff Liaison

    Guests:

    Peter Thomas

    Cecil Bilbo

    Rita Neiderheiser

    Ketih Woller

  • Part 5 – A2015 Key Dates

  • 2015 ANNUAL REVISION CYCLE *Public Input Dates may vary according to standards and schedules for Revision Cycles may change.  Please check the NFPA Website for the most up‐to‐date information on Public Input Closing Dates and schedules at 

    www.nfpa.org/document # (i.e. www.nfpa.org/101) and click on the Next Edition tab. 

    Process Stage 

     Process Step 

     Dates for 

    TC 

    Dates forTC with CC 

      Public Input Closing Date*  7/8/2013  7/8/2013   Final Date for TC First Draft Meeting  12/13/2013  9/13/2013 

    Public Input  Posting of First Draft and TC Ballot  1/31/2014  10/25/2013 Stage  Final date for Receipt of TC First Draft ballot  2/21/2014  11/15/2013 

    (First Draft)  Final date for Receipt of TC First Draft ballot ‐ recirc  2/28/2014  11/22/2013   Posting of First Draft for CC Meeting    11/29/2013   Final date for CC First Draft Meeting    1/10/2014   Posting of First Draft and CC Ballot    1/31/2014   Final date for Receipt of CC First Draft ballot    2/21/2014   Final date for Receipt of CC First Draft ballot ‐ recirc    2/28/2014   Post First Draft Report for Public Comment  3/7/2014  3/7/2014 

         Public Comment Closing Date for Paper Submittal*  4/11/2014  4/11/2014   Public Comment Closing Date for Online Submittal (e‐PC)*   5/16/2014  5/16/2014   Final Date to Publish Notice of Consent Documents (Standards that 

    received no Comments) 5/30/2014  5/30/2014 

      Appeal Closing Date for Consent Standards (Standards that received no Comments) 

    6/13/2014  6/13/2014 

      Final date for TC Second Draft Meeting  10/31/2014  7/25/2014 Comment  Posting of Second Draft and TC Ballot  12/12/2014  9/5/2014 Stage    Final date for Receipt of TC Second Draft ballot  1/2/2015  9/26/2014 

    (Second  Final date for receipt of TC Second Draft ballot ‐ recirc  1/9/2015  10/3/2014 Draft)  Posting of Second Draft for CC Meeting    10/10/2014 

      Final date for CC Second Draft Meeting    11/21/2014   Posting of Second Draft for CC Ballot    12/12/2014   Final date for Receipt of CC Second Draft ballot    1/2/2015   Final date for Receipt of CC Second Draft ballot ‐ recirc    1/9/2015   Post Second Draft Report for NITMAM Review  1/16/2015  1/16/2015 

     Tech Session  Notice of Intent to Make a Motion (NITMAM) Closing Date  3/6/2015  3/6/2015 Preparation  Posting of Certified Amending Motions (CAMs) and Consent 

    Standards 5/1/2015  5/1/2015 

    (& Issuance)  Appeal Closing Date for Consent Standards  5/16/2015  5/16/2015   SC Issuance Date for Consent Standards  5/26/2015  5/26/2015 

     Tech Session  Association Meeting for Standards with CAMs  6/22‐25/2015  6/22‐25/2015  Appeals and  Appeal Closing Date for Standards with CAMs  7/15/2015  7/15/2015 Issuance  SC Issuance Date for Standards with CAMs  8/20/2015  8/20/2015 

     

    Approved___  October 18, 2011       _                                              Revised__March 7, 2013_____________ 

  • Part 6 – Second Revisions TC Ballot Finals

  • National Fire Protection Association

    1 Batterymarch Park, Quincy, MA 02169-7471

    Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

    M E M O R A N D U M

    To: NFPA Technical Committee on Private Water Supply Piping Systems

    From: Elena Carroll, Administrator, Technical Projects

    Date: October 8, 2014

    Subject: NFPA 24 Second Draft TC FINAL Ballot Results (A2015 Cycle)

    According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

    31 Members Eligible to Vote

    3 Not Returned (Laguna, Mowrer, Sanchez)

    26 Affirmative on All Revisions

    2 Negatives (Asp, Schwab)

    0 Abstentions

    The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of

    the vote for each second revision.

    There are two criteria necessary for each second revision to pass ballot: (1) simple majority and (2) affirmative 2/3 vote. The mock examples below show how the calculations are determined.

    (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes

    are required to pass ballot. (Sample calculation: 20 members eligible to vote ÷ 2 = 10 + 1 = 11)

    (2) Example for Affirmative 2/3: Assuming there are 20 vote eligible committee members and 1 member did not

    return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample

    calculation: 20 members eligble to vote – 1 not returned – 2 abstentions = 17 x 0.66 = 11.22 = 12 )

    As always please feel free to contact me if you have any questions.

  • Second Revision No. 15-NFPA 24-2014 [ Global Comment ]

    Revise the metric values throughout the standard to follow the soft conversions provided by themetric task group.

    Supplemental Information

    File Name DescriptionMetrification_AUT-PRI.xlsx

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 13:43:08 EDT 2014

    Committee Statement

    CommitteeStatement:

    For the 2016 edition of NFPA 13, the technical committees responsible for the standard chose tomove from hard conversions to soft conversions. Chapter 10 of NFPA 24 is extracted into NFPA13, and as such, NFPA 24 was included in the soft conversion review.

    ResponseMessage:

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    1 of 41 10/17/2014 8:56 AM

  • Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    2 of 41 10/17/2014 8:56 AM

  • English (in.) Metric (mm) SI Unit Eng. Unit Factor

    1/4 6 L gal 1 gal = 3.785 L

    3/8 10 mm/min gpm/ft2 1 gpm/ft2 = 40.746 mm/min

    1/2 15 dm3 gal 1 gal = 3.785 dm3

    3/4 20 Pa psi 1 psi = 6894.757 Pa

    1 25 bar psi 1 psi = 0.0689 bar

    1 1/4 32 Pa --> bar - 1 bar = 1E5 Pa

    1 1/2 40

    1 3/4 45

    2 50 SI Unit Eng. Unit Factor

    2 1/2 65 m ft 1 ft = 0.3048 m

    3 80 m in 1 in = 0.0254 m

    3 1/2 90 mm in 1 in = 25.4 mm

    4 100

    5 125

    6 150 SI Unit Eng. Unit Factor

    8 200 m2 ft2 1 ft2 = 0.0929 m2

    10 250 m2 in2 1 in2 = 0.0006452 m2

    12 300 mm2 in2 1 in2 = 645.15 mm2

    14 350 m3 ft3 1 ft3 = 0.02832 m3

    16 400 mm3 in3 1 in3 = 16387 mm3

    18 450

    20 500

    24 600 SI Unit Eng. Unit Factor

    kJ/kg Btu/lb 1 Btu/lb = 2.326 kJ/kg

    g oz. 1 oz = 28.35 g

    kJ/m2 Btu/ft2 1 Btu/ft2 = 11.356 kJ/m2

    Piping Equivalents Conversion Factors (T.1.6.1.3)

    Length

    Area, Volume

    Other

  • Second Revision No. 2-NFPA 24-2014 [ Section No. 2.3.1 ]

    2.3.1 ASME Publications.American Society of Mechanical Engineers, Three Two Park Avenue, New York, NY 10016-5990.

    ASME B1.20.1, Pipe Threads, General Purpose (Inch), 2001.

    ASME B16.1, Gray Iron Pipe Flanges and Flanged Fittings, Classes 12, 125, and 250 , 2010.

    ASME B16.3, Malleable Iron Threaded Fittings, Classes 150 and 300, 2006.

    ASME B16.4, Gray Iron Threaded Fittings, Classes 125 and 250, 2006.

    ASME B16.5, Pipe Flanges and Flanged Fittings NPS 1⁄2 through 24, 2003 2013 .

    ASME B16.9, Factory-Made Wrought Steel Buttweld Fittings, 2007.

    ASME B16.11, Forged Steel Fittings, Socket Welded and Threaded, 2005.

    ASME B16.18, Cast Bronze Solder Joint Pressure Fittings, 2001.

    ASME B16.22, Wrought Copper and Bronze Solder Joint Pressure Fittings, 2001.

    ASME B16.25, Buttwelding Ends, 2007.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 11:30:50 EDT 2014

    Committee Statement

    Committee Statement: Updated the edition date for the standard.Response Message:

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    3 of 41 10/17/2014 8:56 AM

  • Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    4 of 41 10/17/2014 8:56 AM

  • Second Revision No. 19-NFPA 24-2014 [ Section No. 2.3.2 ]

    2.3.2 ASTM Publications.ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

    ASTM A 234 A234/A234M , Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel forModerate and Elevated Temperatures, 2007 2013e1 .

    ASTM A 53 A53/A53M Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated,Welded and Seamless, 2001 2012 .

    ASTM A 135 A135/A135M Standard Specification for Electric-Resistance- Welded Steel Pipe,2001 09(2014) .

    ASTM A 795 A795/A795M Standard Specification for Black and Hot-Dipped Zinc-Coated(Galvanized)Welded and Seamless Steel Pipe for Fire Protection Use, 2000 2013 .

    ASTM B 16.5 Cast Bronze Threaded Fittings , 1985.

    ASTM B 43 B43 Specification for Seamless Red Brass Pipe, 2009.

    ASTM B 75 B75 , Specification for Seamless Copper Tube, 2002 2011 .

    ASTM B 88 B88 , Specification for Seamless Copper Water Tube, 2003 2009 .

    ASTM B 251 B251 , Requirements for Wrought Seamless Copper and Copper-Alloy Tube, 2002 2010 .

    IEEE/ASTM-SI-10, Standard for Use of the International System of Units (SI): The Modern Metric System,2002 2010 .

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Sun Jun 29 09:24:03 EDT 2014

    Committee Statement

    Committee Statement: Update year dates. The deleted standard is an ASME Standard, not an ASTM Standard.Response Message:Public Comment No. 20-NFPA 24-2014 [Section No. 2.3.2]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    5 of 41 10/17/2014 8:56 AM

  • Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    6 of 41 10/17/2014 8:56 AM

  • Second Revision No. 3-NFPA 24-2014 [ Section No. 2.3.3 ]

    2.3.3 AWWA Publications.American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235.

    AWWA C104, Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water, 2008.

    AWWA C105, Polyethylene Encasement for Ductile Iron Pipe Systems, 2005.

    AWWA C110, Ductile Iron and Gray Iron Fittings, 2008.

    AWWA C111, Rubber-Gasket Joints for Ductile Iron Pressure Pipe and Fittings, 2000.

    AWWA C115, Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron Threaded Flanges, 2005.

    AWWA C116, Protective Fusion-Bonded Epoxy Coatings for the Interior and Exterior Surfaces ofDuctile-Iron and Gray-Iron Fittings for Water Supply Service , 2003.

    AWWA C150, Thickness Design of Ductile Iron Pipe, 2008.

    AWWA C151, Ductile Iron Pipe, Centrifugally Cast for Water, 2002.

    AWWA C153, Ductile-Iron Compact Fittings for Water Service, 2006.

    AWWA C200, Steel Water Pipe 6 in. and Larger , 2005.

    AWWA C203, Coal-Tar Protective Coatings and Linings for Steel Water Pipelines Enamel and Tape —Hot Applied , 2002.

    AWWA C205, Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in. and Larger —Shop Applied , 2007.

    AWWA C206, Field Welding of Steel Water Pipe , 2003.

    AWWA C207, Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in., 2007.

    AWWA C208, Dimensions for Fabricated Steel Water Pipe Fittings, 2007.

    AWWA C300, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, 2004.

    AWWA C301, Prestressed Concrete Pressure Pipe, Steel-Cylinder Type, 2007.

    AWWA C302, Reinforced Concrete Pressure Pipe, Non-Cylinder Type, 2004.

    AWWA C303, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned, 2002.

    AWWA C400, Standard for Asbestos-Cement Distribution Pipe, 4 in. Through 16 in. (100 mm through 400mm), for Water Distribution Systems, 2003.

    AWWA C600, Standard for the Installation of Ductile Iron Water Mains and Their Appurtenances, 2005.

    AWWA C602, Cement-Mortar Lining of Water Pipe Lines 4 in. and Larger — in Place, 2006.

    AWWA C603, Standard for the Installation of Asbestos-Cement Pressure Pipe, 2005.

    AWWA C900, Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in., for Water Distribution, 2007.

    AWWA C905, AWWA Standard for Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 in.Through 48 in. (350 mm Through 1200 mm), 2010.

    AWWA C906, Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) forWater Distribution, 2007.

    AWWA C909, Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 in. through 24 in. (100mm through 600 mm), for Water, Wastewater, and Reclaimed Water Service, 2010.

    AWWA M11, A Guide for Steel Pipe Design and Installation , 4th edition, 2004.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    7 of 41 10/17/2014 8:56 AM

  • Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 11:31:51 EDT 2014

    Committee Statement

    CommitteeStatement:

    Reference is made to the statement of problem and substantiation of Public Comment No.2-NFPA 24-2014.

    Response Message:Public Comment No. 16-NFPA 24-2014 [Section No. 2.3.3]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    8 of 41 10/17/2014 8:56 AM

  • Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    9 of 41 10/17/2014 8:56 AM

  • Second Revision No. 20-NFPA 24-2014 [ Section No. 2.4 ]

    2.4 References for Extracts in Mandatory Sections.NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 2016 edition.

    Submitter Information Verification

    Submitter Full Name: Sonia BarbosaOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Mon Aug 18 09:51:05 EDT 2014

    Committee Statement

    Committee Statement: Updated edition date.Response Message:

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    10 of 41 10/17/2014 8:56 AM

  • Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    11 of 41 10/17/2014 8:56 AM

  • Second Revision No. 17-NFPA 24-2014 [ New Section after 5.1.2 ]

    5.1.3 Water Supply Adjustments.5.1.3.1* Where a waterflow test was conducted, the volume and pressure available for use for a fire protectionsystem shall be determined from the following formula:

    [5.1.3.1]

    5.1.3.1.1 The pressure, P , shall be what is considered available from the water supply to use for a fire protectionsystem that will be calculated for a given flow demand of Q .5.1.3.1.2 The flow, Q , shall be demand flow of the fire protection system that will be used to calculate theavailable pressure from the water supply, P .5.1.3.1.3* The variable P 1 shall be the residual pressure measured during the waterflow test while the flow Q 1was discharging from the water supply reduced by the specifying engineer or the water utility for dailyand seasonal fluctuations.5.1.3.1.3.1 The reduction shall not be based on 100-year droughts or other extreme conditions.5.1.3.1.4* The variable P 2 shall be the static pressure measured during the waterflow test reduced by thespecifying engineer or the water utility for daily and seasonal fluctuations.5.1.3.1.4.1 The reduction shall not be based on 100-year droughts or other extreme conditions.5.1.3.1.5 The variable Q 1 shall be the flow associated with P 1 .5.1.3.1.6* Where the specifying engineer or the water utility does not provide the value for P 1 and P 2 , see5.1.3.2 .5.1.3.2* Where a waterflow test has been conducted and the specifying engineer or the water authority does notprovide a value for P 1 and P 2 , the value for P 1 and P 2 shall be calculated by taking the staticpressure and residual pressure results from the flow test and reducing them by 5 percent.5.1.3.2.1 Where the authority having jurisdiction has adopted a requirement for an adjustment different from 5percent, that adjustment shall be applied.

    Supplemental Information

    File Name DescriptionSR_17_equation_and_number.docx Equation 5.1.3.1 SR_17_A.5.1.3.docx Annex material

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    12 of 41 10/17/2014 8:56 AM

  • City:State:Zip:Submittal Date: Wed Jun 18 16:18:40 EDT 2014

    Committee Statement

    CommitteeStatement:

    The NFPA 13 technical committees have been discussing the need for adjusting waterflow data forseveral revision cycles. This revision aims to make the adjustment to the data from a waterflow testrequired instead of recommended. If the adjustment is not required, contractors that do the right thingand adjust the data from tests are at a disadvantage from contractors that don't make anyadjustment. It is fundamentally wrong to not make an adjustment to the data due to daily andseasonal fluctuations. This makes makes a simple and easy to understand adjustment that isstandardized so that there is no argument over what is supposed to happen. It is the intent to havethis be the only adjustment. If the water utility has already performed the adjustment, or if the AHJhas already mandated a safety margin or safety factor to the waterflow data obtained from the test,this adjustment would not apply.

    ResponseMessage:Public Comment No. 17-NFPA 24-2014 [Section No. A.5.1.2]Public Comment No. 18-NFPA 24-2014 [New Section after 5.1.2]Public Comment No. 19-NFPA 24-2014 [New Section after A.5.1.2]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    26 Affirmative All0 Affirmative with Comments2 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllBiggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, Jeff

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    13 of 41 10/17/2014 8:56 AM

  • Lake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    Negative with CommentAsp, Roland A. While it is important to adjust water flow test results to reflect a possible "worse case" scenario of the watersupply based upon time of day, seasonal variations, large simultaneous industrial use and other conditions thatmay affect the water supply, this negative ballot is being submitted based upon the following: 1. The SprinklerSystem Discharge Criteria Committee did not accept this Second Revision. Although the Residential Committeeand the Private Water Supply Piping Systems Committee did accept this SR, all affected committees should havea consensus on this issue. 2. The Fire Protection Research Foundation is sponsoring a research project on thistopic and the results of this project should be taken into consideration once available.Schwab, Peter T. Adjustments for water supply fluctuation is a complicated topic. This approach to mandate an arbitrary 5%cushion is too simplistic and cannot encompass all the possibilities encountered in the real world. Also, the SSDCommittee rejected a similar comment. The FPRF is in the process of conducting a project on this subject. Thisconcept should be put on hold for the next edition.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    14 of 41 10/17/2014 8:56 AM

  • 2

    85.1

    1

    21 PQ

    QPPP

    [5.1.3.1] Formatted: Font: Bold

  • NFPA 24 SR 17 Annex

    A.5.1.3.1

    Consider the following example. A waterflow test is conducted at a location where a city water

    main is going to be tapped for a new sprinkler system. During the test, the static pressure is

    measured at 70 psi; the residual pressure is measured at 50 psi while 1300 gpm was discharging

    from a nearby hydrant. The water utility is contacted, and they indicate that a reasonable low-

    static pressure accounting for typical daily and seasonal fluctuations in this area is 55 psi, and a

    reasonable low-residual pressure accounting for typical daily and seasonal fluctuations in this

    area at a flow of 1300 gpm is 35 psi. The equation that describes the water supply available for a

    fire sprinkler system would be:

    551300

    5535

    85.1

    QP

    [A.5.1.3(a)]

    There are two ways to use this formula. One would be to assume two different values for Q,

    calculate P and then draw a graph on log 1.85 paper. Any fire sprinkler system demand falling

    on or below the line on this graph would be acceptable in accordance with NFPA 13 to work

    with this water supply.

    In this case, the two easiest flows to pick for Q would be 0 and 1300 gpm. When Q = 0, P is

    simply 55 psi. When Q = 1300 gpm, P = 35 psi. These two points can be plotted on log 1.85

    paper as shown in Figure A.5.1.3.1.

    The second way to use this formula would be to calculate the fire protection system and

    determine the flow necessary to make the system work. Plug this flow into the formula above

    and see what the available pressure from the water supply will be at that flow.

    For example, if a sprinkler system connected to this water supply had a demand of 580 gpm, the

    available pressure from the water supply would be:

    551300

    5805535

    85.1

    P

    P = (−20)(0.225) + 55

    P = 50.5 psi

    [A.5.1.3(b)]

    So, as long as the sprinkler system has a pressure demand less than or equal to 50.5 psi, it will

    work with this water supply.

  • Figure A.5.1.3.1 Available Water Supply Curve Example.

    A.5.1.3.1.3

    The purpose of the adjustment required by this section is to take into account reasonable

    fluctuations that occur on a daily and seasonal basis but not to burden the building owner with

    extreme conditions. During an extreme condition such as a water main break or a severe drought,

    the impaired system provisions of NFPA 25 can be employed to mitigate the circumstances of

    the extreme condition.

    The intent of this section is to apply the adjustment to the raw data obtained by the flow test and

    not to apply adjustments to values that have already been adjusted by water utilities. If a water

    utility has already provided flow and pressure data for use in the design of fire protection

    systems that already include adjustments for daily and seasonal water usage, there is no need to

    make any additional adjustments to this data.

    A.5.1.3.1.4

    See A.5.1.3.1.3.

    A.5.1.3.1.6

    Water utilities are the entities that know their own supplies the best and know what appropriate

    adjustments need to be made to flow test data to provide reasonable fire protection. In a situation

    in which the water utility will not make a definite statement about an adjustment, the fire

    protection engineer would supply such a statement about adjustments to the raw data from a flow

    test.

    Due to the level of judgment involved in making such a decision, licensing laws in most of the

    United States require the fire protection engineer to make this determination rather than the fire

    protection system contractor. It is expected that the engineer would make these statements in the

    specifications provided to the fire protection system contractor. In the absence of any

    information from any authority, 5.1.3.2 provides a standardized method of making a decision.

    A.5.1.3.2

    Subsection 5.1.3.2 provides a standardized method of making a decision regarding the reduction

    of the results from a waterflow test to determine what pressure and flow are available from a

  • water supply when the specifying engineer and the water utility have not provided adjustment

    information. An example of using this standardized method is the following:

    If a waterflow test is conducted at a location where a city water main is going to be tapped for a

    new sprinkler system, and the static pressure is measured at 70 psi, with the residual pressure

    measured at 50 psi while 1300 gpm was discharging from a nearby hydrant. If there is no

    information from the specifying engineer or water utility about appropriate adjustments, the

    value of the static pressure and residual pressure need to be reduced by 5 percent.

    The static pressure would be adjusted from 70 psi to 66.5 psi (70 x 0.95 = 66.5).

    The residual pressure at 1300 gpm would be reduced from 50 psi to 47.5 psi (70 x 0.95 = 47.5).

    The results would be plotted on log 1.85 graph paper, as shown in the lower curve on Figure

    A.5.1.3.2. That curve would represent what the fire protection system contractor could use for a

    fire protection system.

    Figure A.5.1.3.2 Available Water Supply Curve Example.

  • Second Revision No. 16-NFPA 24-2014 [ Section No. 5.2.1 ]

    5.2.1 Private Fire Service Mains.Hydraulic calculations shall show that the main is able to supply the total demand at the appropriatepressure for systems with multiple hydrants .

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 14:05:16 EDT 2014

    Committee Statement

    CommitteeStatement:

    The current wording appears to infer that pressures and flow are not material for single firehydrant installations. A 6" line may be completely insufficient to supply a single hydrant at the endof a long dead end with a high fire flow condition. The PC removes the multiple hydrant constraint.

    ResponseMessage:Public Comment No. 3-NFPA 24-2014 [Section No. 5.2.1]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    15 of 41 10/17/2014 8:56 AM

  • Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    16 of 41 10/17/2014 8:56 AM

  • Second Revision No. 6-NFPA 24-2014 [ Section No. 5.3.2 ]

    5.3.2 Where meters are required, they shall be listed for fire protection service .

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 11:39:39 EDT 2014

    Committee Statement

    CommitteeStatement:

    It is important to indicate the listing needs to be for fire protection. The word "service" wasadded to the proposed language in PC-6 for consistency with the remainder of the standard.

    ResponseMessage:Public Comment No. 6-NFPA 24-2014 [Section No. 5.3.2]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    17 of 41 10/17/2014 8:56 AM

  • Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    18 of 41 10/17/2014 8:56 AM

  • Second Revision No. 7-NFPA 24-2014 [ Section No. 5.9.2.4 ]

    5.9.2.4 Non-threaded Nonthreaded couplings shall be permitted where required by the AHJ.

    Non-threaded couplings shall be listed for use as permitted in 5.9.2.4 .

    5.9.2.4.1 Nonthreaded couplings shall be listed.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 11:45:33 EDT 2014

    Committee Statement

    CommitteeStatement:

    The two separate provisions should be written in two separate sections. Additionally, as writtenin the First Draft Report, the second sentence of Section 5.9.2.4 is referring to its own sectionnumber.

    ResponseMessage:Public Comment No. 7-NFPA 24-2014 [Section No. 5.9.2.4]Public Comment No. 13-NFPA 24-2014 [Section No. 5.9.2.4]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    19 of 41 10/17/2014 8:56 AM

  • Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    20 of 41 10/17/2014 8:56 AM

  • Second Revision No. 4-NFPA 24-2014 [ Section No. 5.9.4.4 ]

    5.9.4.4 The automatic drip shall be permitted to be buried where permitted by the AHJ.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 11:36:34 EDT 2014

    Committee Statement

    Committee Statement: This language is being deleted because it is already in Section 5.9.4.2.1.Response Message:Public Comment No. 8-NFPA 24-2014 [Section No. 5.9.4.4]Public Comment No. 15-NFPA 24-2014 [Chapter 5]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    21 of 41 10/17/2014 8:56 AM

  • Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    22 of 41 10/17/2014 8:56 AM

  • Second Revision No. 8-NFPA 24-2014 [ Section No. 6.2.1 ]

    6.2.1 A valve in accordance with Section 6.1 shall be installed in each pipeline from each water supply.6.2.1.1 Control valves shall not be installed in the piping from the fire department connection to the point itconnects to the fire service main.6.2.1.2 Control valves shall be permitted in the system piping downstream of the fire department connection.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 12:02:46 EDT 2014

    Committee Statement

    CommitteeStatement:

    Modified the wording to indicate that the valve downstream of the FDC can only be insystem piping.

    Response Message:Public Comment No. 9-NFPA 24-2014 [Section No. 6.2.1]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    23 of 41 10/17/2014 8:56 AM

  • Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    24 of 41 10/17/2014 8:56 AM

  • Second Revision No. 14-NFPA 24-2014 [ Section No. 10.1.4.1 ]

    10.1.4.1* Underground piping shall be permitted to extend into the building through the slab or wall not more than24 in. (0.6 m).

    Supplemental Information

    File Name DescriptionSR-14_A.10.1.4.1.docx edited

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 13:31:05 EDT 2014

    Committee Statement

    CommitteeStatement:

    The standard allows PVC underground piping to enter a building to supply the sprinkler systeminside a building. The concerns of this approach include: 1. Weight of the spinkler riser on the PVCpipe - is it tested for vertical loading in this regard 2. Incompatibility with various chemicals, includingfloor coatings - the Arrangement section in NFPA 13 no longer seems to adequately address thatpotential concern. 3. Potential to exposure from sunlight. These concerns should be addressedwhere applicable. This language was proposed for the body of NFPA 13, but has been relocated tothe annex of NFPA 24 as these concerns may not apply for every project, but rather should beconsidered on a case by case basis.

    ResponseMessage:

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    25 of 41 10/17/2014 8:56 AM

  • Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    26 of 41 10/17/2014 8:56 AM

  • A.10.1.4

    Where nonmetallic underground piping is provided above grade or inside a building, the following

    should be considered:

    2.1. Exposure from direct rays of sunlight

    3.2. Compatibility with chemicals such as floor coatings and termiticides/insecticides

    4.3. Support of piping and appurtenances attached thereto (e.g., sprinkler risers, backflow

    preventers…etc)

    Formatted: Font: Bold

  • Second Revision No. 9-NFPA 24-2014 [ Section No. 10.2.1.3 ]

    10.2.1.3 Approved fittings shall be permitted to be used.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 12:11:52 EDT 2014

    Committee Statement

    CommitteeStatement:

    There are available fittings on the market that are listed or are in accordance with Table10.2.1.1. This section allows practically anything as long as it is approved.

    ResponseMessage:Public Comment No. 10-NFPA 24-2014 [Section No. 10.2.1.3]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    27 of 41 10/17/2014 8:56 AM

  • Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    28 of 41 10/17/2014 8:56 AM

  • Second Revision No. 10-NFPA 24-2014 [ Section No. 10.4.2.1.7.1 ]

    10.4.2.1.7.1 Heat tracing not listed for underground use shall be permitted when piping is installed in accordance with10.4.2.2.5 10.1.4.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 12:16:15 EDT 2014

    Committee Statement

    Committee Statement: I believe this is the correct section to reference.Response Message:Public Comment No. 11-NFPA 24-2014 [Section No. 10.4.2.1.7.1]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    29 of 41 10/17/2014 8:56 AM

  • Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    30 of 41 10/17/2014 8:56 AM

  • Second Revision No. 11-NFPA 24-2014 [ Section No. 10.5.1.1 ]

    10.5.1.1* The requirement of 10.6.8 10.5.1 shall not preclude the bonding of the underground piping to the lightningprotection grounding system as required by NFPA 780 in those cases where lightning protection isprovided for the structure.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 12:16:35 EDT 2014

    Committee Statement

    Committee Statement: Editorial correction. The reference was not revised during the Chapter 10 rewrite.Response Message:Public Comment No. 12-NFPA 24-2014 [Section No. 10.5.1.1]

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    31 of 41 10/17/2014 8:56 AM

  • Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    32 of 41 10/17/2014 8:56 AM

  • Second Revision No. 13-NFPA 24-2014 [ Section No. 10.10.1 ]

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    33 of 41 10/17/2014 8:56 AM

  • 10.10.1 Approval of Underground Piping.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    34 of 41 10/17/2014 8:56 AM

  • The installing contractor shall be responsible for the following:

    (1) Notifying the AHJ and the owner's representative of the time and date testing is to be performed

    (2) Performing all required acceptance tests

    (3) Completing and signing the contractor's material and test certificate(s) shown in Figure 10.10.1

    Figure 10.10.1 Sample of Contractor's Material and Test Certificate for Underground Piping.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    35 of 41 10/17/2014 8:56 AM

  • Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 13:26:44 EDT 2014

    Committee Statement

    Committee Statement: The modifications made in SR 12 require this statement to be modified for correlation.Response Message:

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    36 of 41 10/17/2014 8:56 AM

  • Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    37 of 41 10/17/2014 8:56 AM

  • Second Revision No. 12-NFPA 24-2014 [ Section No. 10.10.2.1.3 ]

    10.10.2.1.3 The minimum rate of flow shall be not less than one of the following: in accordance with Table10.10.2.1.3 .

    Hydraulically calculated water demand flow rate of the system, including any hose requirements

    Maximum flow rate available to the system under fire conditions

    Table 10.10.2.1.3 Flow Required to Produce Velocity of 10 ft/sec (3 m/sec) in Pipes

    Nominal Pipe Size Flow Rate

    in. mm gpm L/min

    2 51 100 37921⁄2 63 150 5683 76 220 8334 102 390 1,476 14765 127 610 2,309 23096 152 880 3,331 33318 204 1,560 1560 5,905 5905

    10 254 2,440 2440 9,235 923512 305 3,520 3520 13,323

    10.10.2.1.3.1 Where the flow rates established in Table 10.10.2.1.3 are not attainable, the maximum flow rateavailable to the system shall be acceptable.

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Jun 17 13:01:16 EDT 2014

    Committee Statement

    CommitteeStatement:

    This section was reviewed by the NFPA 24 Flushing Task Group. Matching the hydraulic calculationdemand is an unreasonable option, and the annex note A.10.10.2.1.3(2) gives support to this. Therequirement for flushing of the underground is not intended to be a means of proving the watersupply is available at the time of installation. Some system hydraulically calculated water demandflow rates may be low enough that achieving that flow would not result in flushing any debris

    ResponseMessage:

    Ballot Results

    This item has passed ballot

    * Flow in accordance with Table 10.10.2.1.3

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    38 of 41 10/17/2014 8:56 AM

  • 31 Eligible Voters3 Not Returned

    28 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    39 of 41 10/17/2014 8:56 AM

  • Second Revision No. 18-NFPA 24-2014 [ Section No. A.5.1.2 ]

    A.5.1.2 An adjustment to the waterflow test data to account for the following should be made, as appropriate:

    Daily and seasonal fluctuations

    Possible interruption by flood or ice conditions

    Large simultaneous industrial use

    Future demand on the water supply system

    Other conditions that could affect the water supply

    Submitter Information Verification

    Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Fri Jun 20 11:58:33 EDT 2014

    Committee Statement

    CommitteeStatement:

    This section suggesting water supply adjustments is being removed in favor of mandatorylanguage in Chapter 5 for making an adjustment to waterflow data. See SR 17 for the exactlanguage.

    ResponseMessage:

    Ballot Results

    This item has passed ballot

    31 Eligible Voters3 Not Returned

    27 Affirmative All0 Affirmative with Comments1 Negative with Comments0 Abstention

    Not ReturnedLaguna, Alan R.Mowrer, David S.Sanchez, Daniel

    Affirmative AllBiggins, James B.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    40 of 41 10/17/2014 8:56 AM

  • Brown, Phillip A.Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Glumac, Tanya M.Hayward, LaMarHebenstreit, JeffLake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Olson, Shawn C.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    Negative with CommentAsp, Roland A. If SR-17 (Waterflow test data adjustment) does not pass ballot, the language of A.5.1.2 should remain in theannex of the standard.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    41 of 41 10/17/2014 8:56 AM

  • National Fire Protection Association

    1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

    M E M O R A N D U M

    To: NFPA Technical Committee on Private Water Supply Piping Systems

    From: Elena Carroll, Administrator, Technical Projects

    Date: September 30, 2014

    Subject: NFPA 291 Second Draft TC FINAL Ballot Results (A2015 Cycle)

    According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

    31 Members Eligible to Vote 4 Not Returned (Glumac, Mowrer, Olson, Sanchez) 27 Affirmative on All Revisions

    0 Negatives 0 Abstentions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each second revision.

    There are two criteria necessary for each second revision to pass ballot: (1) simple majority and (2) affirmative 2/3 vote. The mock examples below show how the calculations are determined.

    (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes are required to pass ballot. (Sample calculation: 20 members eligible to vote ÷ 2 = 10 + 1 = 11)

    (2) Example for Affirmative 2/3: Assuming there are 20 vote eligible committee members and 1 member did not

    return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample calculation: 20 members eligble to vote – 1 not returned – 2 abstentions = 17 x 0.66 = 11.22 = 12 )

    As always please feel free to contact me if you have any questions.

  • Second Revision No. 1-NFPA 291-2014 [ Global Comment ]

    Revise the metric values throughout the standard to follow the soft conversions provided by the metrictask group.

    Supplemental Information

    File Name DescriptionMetrification_AUT-PRI.xlsx

    Submitter Information Verification

    Submitter Full Name: Matthew KlausOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Tue Jul 08 07:01:02 EDT 2014

    Committee Statement

    CommitteeStatement:

    For the 2016 edition of NFPA 13, the technical committees responsible for the standard chose tomove from hard conversions to soft conversions. NFPA 291 is considered part of the sprinkler projectand therefore also will move to a soft conversion.

    ResponseMessage:

    Ballot Results

    This item has passed ballot

    31 Eligible Voters4 Not Returned

    27 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedGlumac, Tanya M.Mowrer, David S.Olson, Shawn C.Sanchez, Daniel

    Affirmative AllAsp, Roland A.Biggins, James B.Brown, Phillip A.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    1 of 2 9/30/2014 9:12 AM

  • Charrette, James A.Chen, Flora F.Clark, Jr., Stephen A.Dudley, Jeffry T.Ellis, Byron E.Frakes, Brandon W.Fuller, David B.Gagnon, Robert M.Hayward, LaMarHebenstreit, JeffLaguna, Alan R.Lake, JohnLarsen, MichaelMaddry, James M.Maughan, Kevin D.Morgan, Bob D.O'Dell, Dale H.Ramos, MartinSchifiliti, James R.Schwab, Peter T.Sheppard, J. WilliamSu, Chen-HsiangTwele, Scott M.Wagoner, Kenneth W.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    2 of 2 9/30/2014 9:12 AM

  • English (in.) Metric (mm) SI Unit Eng. Unit Factor

    1/4 6 L gal 1 gal = 3.785 L

    3/8 10 mm/min gpm/ft2 1 gpm/ft2 = 40.746 mm/min

    1/2 15 dm3 gal 1 gal = 3.785 dm3

    3/4 20 Pa psi 1 psi = 6894.757 Pa

    1 25 bar psi 1 psi = 0.0689 bar

    1 1/4 32 Pa --> bar - 1 bar = 1E5 Pa

    1 1/2 40

    1 3/4 45

    2 50 SI Unit Eng. Unit Factor

    2 1/2 65 m ft 1 ft = 0.3048 m

    3 80 m in 1 in = 0.0254 m

    3 1/2 90 mm in 1 in = 25.4 mm

    4 100

    5 125

    6 150 SI Unit Eng. Unit Factor

    8 200 m2 ft2 1 ft2 = 0.0929 m2

    10 250 m2 in2 1 in2 = 0.0006452 m2

    12 300 mm2 in2 1 in2 = 645.15 mm2

    14 350 m3 ft3 1 ft3 = 0.02832 m3

    16 400 mm3 in3 1 in3 = 16387 mm3

    18 450

    20 500

    24 600 SI Unit Eng. Unit Factor

    kJ/kg Btu/lb 1 Btu/lb = 2.326 kJ/kg

    g oz. 1 oz = 28.35 g

    kJ/m2 Btu/ft2 1 Btu/ft2 = 11.356 kJ/m2

    Piping Equivalents Conversion Factors (T.1.6.1.3)

    Length

    Area, Volume

    Other

  • National Fire Protection Association

    1 Batterymarch Park, Quincy, MA 02169-7471

    Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

    M E M O R A N D U M

    To: NFPA Technical Committee on Residential Sprinkler Systems

    From: Elena Carroll, Administrator, Technical Projects

    Date: October 16, 2014

    Subject: NFPA 13D Second Draft TC FINAL Ballot Results (A2015 Cycle)

    According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

    30 Members Eligible to Vote

    1 Not Returned (Dannaway)

    28 Affirmative on All Revisions

    3 Affirmative with Comment on one or more Revisions (Deegan, Feid, Schwab)

    1 Negatives on one or more Revisions (Deegan)

    0 Abstentions

    The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of

    the vote for each second revision.

    There are two criteria necessary for each second revision to pass ballot: (1) simple majority and (2) affirmative 2/3 vote. The mock examples below show how the calculations are determined.

    (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes

    are required to pass ballot. (Sample calculation: 20 members eligible to vote ÷ 2 = 10 + 1 = 11)

    (2) Example for Affirmative 2/3: Assuming there are 20 vote eligible committee members and 1 member did not

    return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample

    calculation: 20 members eligble to vote – 1 not returned – 2 abstentions = 17 x 0.66 = 11.22 = 12 )

    As always please feel free to contact me if you have any questions.

  • Second Revision No. 14-NFPA 13D-2014 [ Global Comment ]

    Revise the metric values throughout the standard to follow the soft conversions provided by themetric task group

    Supplemental Information

    File Name Description13_Metrification_-_AUT-RSS.xlsx metric conversions

    Submitter Information Verification

    Submitter Full Name: Matthew KlausOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Fri Jun 20 12:12:59 EDT 2014

    Committee Statement

    CommitteeStatement:

    The conversions proposed for the 2016 edition will be based on a soft conversion scheme asopposed to the traditional hard conversion. The attached spreadsheet provides the proposedconversion.

    ResponseMessage:

    Ballot Results

    This item has passed ballot

    30 Eligible Voters1 Not Returned

    29 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedDannaway, Samuel S.

    Affirmative AllBell, Kerry M.Benn, FredBittenbender, Jonathan C.Bradley, Frederick C.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    1 of 51 10/16/2014 12:39 PM

  • Brown, Phillip A.Deegan, Thomas G.Feid, JeffreyFlancher, Dawn M.Haagensen, Dana R.Hoover, Tonya L.Hopkins, MarkHunter, Jerry R.Isman, Kenneth E.Johnson, Gary L.Leyton, Stephen M.Nickson, Ronald G.O'Brian, MichaelOrlowski, StevenPilette, Maurice M.Puchovsky, Milosh T.Pugsley, Scott C.Schwab, Peter T.Skare, Eric J.Skinner, Timothy J.Stanley, George W.Van Walraven, EdVictor, Terry L.Webb, Ronald N.Yu, Hong-Zeng

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    2 of 51 10/16/2014 12:39 PM

  • English (in.) Metric (mm) SI Unit Eng. Unit Factor

    1/4 6 L gal 1 gal = 3.785 L

    3/8 10 mm/min gpm/ft2 1 gpm/ft2 = 40.746 mm/min

    1/2 15 dm3 gal 1 gal = 3.785 dm3

    3/4 20 Pa psi 1 psi = 6894.757 Pa

    1 25 bar psi 1 psi = 0.0689 bar

    1 1/4 32 Pa --> bar - 1 bar = 1E5 Pa

    1 1/2 40

    1 3/4 45

    2 50 SI Unit Eng. Unit Factor

    2 1/2 65 m ft 1 ft = 0.3048 m

    3 80 m in 1 in = 0.0254 m

    3 1/2 90 mm in 1 in = 25.4 mm

    4 100

    5 125

    6 150 SI Unit Eng. Unit Factor

    8 200 m2 ft2 1 ft2 = 0.0929 m2

    10 250 m2 in2 1 in2 = 0.0006452 m2

    12 300 mm2 in2 1 in2 = 645.15 mm2

    14 350 m3 ft3 1 ft3 = 0.02832 m3

    16 400 mm3 in3 1 in3 = 16387 mm3

    18 450

    20 500

    24 600 SI Unit Eng. Unit Factor

    kJ/kg Btu/lb 1 Btu/lb = 2.326 kJ/kg

    g oz. 1 oz = 28.35 g

    kJ/m2 Btu/ft2 1 Btu/ft2 = 11.356 kJ/m2

    Piping Equivalents Conversion Factors (T.1.6.1.3)

    Length

    Area, Volume

    Other

  • Second Revision No. 1-NFPA 13D-2014 [ Section No. 2.3.3 ]

    2.3.3 ASTM Publications.ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

    ASTM A 53 ASTM A53/A53M , Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated,Welded and Seamless, 2010 2012 .

    ASTM A 135 ASTM A135/A135M , Standard Specification for Electric-Resistance-Welded Steel Pipe,2009 (2004) .

    ASTM A 234 ASTM A234/A234M , Standard Specification for Piping Fittings of Wrought Carbon Steel andAlloy Steel for Moderate and High Temperature Service, 2010 2013 e1 .

    ASTM A 795 ASTM A795/A795M , Standard Specification for Black and Hot-Dipped Zinc-Coated(Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use, 2008 2013 .

    ASTM B 32 ASTM B32 , Standard Specification for Solder Metal, 2008.

    ASTM B 43 ASTM B43 , Standard Specification for Seamless Red Brass Pipe, 2009.

    ASTM B 75 ASTM B75 /B75M , Standard Specification for Seamless Copper Tube, 2002 2011 .

    ASTM B 88 ASTM B88 , Standard Specification for Seamless Copper Water Tube, 2009.

    ASTM B 251 ASTM B251 , Standard Specification for General Requirements for Wrought SeamlessCopper and Copper-Alloy Tube, 2010.

    ASTM B 813 ASTM B813 , Standard Specification for Liquid and Paste Fluxes for Soldering Applicationsof Copper and Copper-Alloy Tube, 2010 (2010) .

    ASTM B 828 ASTM B828 , Standard Practice for Making Capillary Joints by Soldering of Copper andCopper Alloy Tube and Fittings, 2002.

    ASTM F 437 ASTM F437 , Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC)Plastic Pipe Fittings, Schedule 80, 2009.

    ASTM F 438 ASTM F438 , Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride)(CPVC) Plastic Pipe Fittings, Schedule 40, 2009.

    ASTM F 439 ASTM F439 , Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride)(CPVC) Plastic Pipe Fittings, Schedule 80, 2009 2013 .

    ASTM F 442 ASTM F442/F442M , Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC)Plastic Pipe (SDR-PR), 2009 2013 e1 .

    ASTM F 876 ASTM F876 , Standard Specification for Crosslinked Polyethylene (PEX) Tubing, 2011 2013e1 .

    Submitter Information Verification

    Submitter Full Name: Matthew KlausOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Thu Jun 19 13:34:11 EDT 2014

    Committee Statement

    Committee Statement: standards date updates

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    3 of 51 10/16/2014 12:39 PM

  • Response Message:Public Comment No. 16-NFPA 13D-2014 [Section No. 2.3.3]Public Comment No. 29-NFPA 13D-2014 [Section No. 2.3.3]

    Ballot Results

    This item has passed ballot

    30 Eligible Voters1 Not Returned

    29 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedDannaway, Samuel S.

    Affirmative AllBell, Kerry M.Benn, FredBittenbender, Jonathan C.Bradley, Frederick C.Brown, Phillip A.Deegan, Thomas G.Feid, JeffreyFlancher, Dawn M.Haagensen, Dana R.Hoover, Tonya L.Hopkins, MarkHunter, Jerry R.Isman, Kenneth E.Johnson, Gary L.Leyton, Stephen M.Nickson, Ronald G.O'Brian, MichaelOrlowski, StevenPilette, Maurice M.Puchovsky, Milosh T.Pugsley, Scott C.Schwab, Peter T.Skare, Eric J.Skinner, Timothy J.Stanley, George W.Van Walraven, EdVictor, Terry L.Webb, Ronald N.Yu, Hong-Zeng

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    4 of 51 10/16/2014 12:39 PM

  • Second Revision No. 13-NFPA 13D-2014 [ Section No. 4.5 ]

    4.5* Documentation.Documentation shall be available provided upon request to ensure adequate demonstrate that the watersupply, listed devices, and adequate sprinkler coverage have been addressed comply with therequirements of this standard .

    Submitter Information Verification

    Submitter Full Name: Matthew KlausOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Thu Jun 19 16:54:30 EDT 2014

    Committee Statement

    CommitteeStatement:

    The word adequate is difficult to enforce. The revised language makes the section moreenforceable.

    Response Message:

    Ballot Results

    This item has passed ballot

    30 Eligible Voters1 Not Returned

    28 Affirmative All1 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedDannaway, Samuel S.

    Affirmative AllBell, Kerry M.Benn, FredBittenbender, Jonathan C.Bradley, Frederick C.Brown, Phillip A.Feid, JeffreyFlancher, Dawn M.Haagensen, Dana R.Hoover, Tonya L.Hopkins, MarkHunter, Jerry R.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    5 of 51 10/16/2014 12:39 PM

  • Isman, Kenneth E.Johnson, Gary L.Leyton, Stephen M.Nickson, Ronald G.O'Brian, MichaelOrlowski, StevenPilette, Maurice M.Puchovsky, Milosh T.Pugsley, Scott C.Schwab, Peter T.Skare, Eric J.Skinner, Timothy J.Stanley, George W.Van Walraven, EdVictor, Terry L.Webb, Ronald N.Yu, Hong-Zeng

    Affirmative with CommentDeegan, Thomas G. Affirmative with Comment – I agree with the intent of this change but adding the words “..and applicable listings.”should probably be included after the word “standard”.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    6 of 51 10/16/2014 12:39 PM

  • Second Revision No. 2-NFPA 13D-2014 [ Section No. 5.1.1.1 ]

    5.1.1.1* Where a sprinkler is removed from a fitting or welded outlet, it shall not be reinstalled except as permittedby 5.1.1.1.1.5.1.1.1.1 Dry sprinklers shall be permitted to be reinstalled, where they are not removed by applying torque at thepoint where the sprinkler is attached to the barrel when removed in accordance with the manufacturer’sinstallation and maintenance instructions .

    Submitter Information Verification

    Submitter Full Name: Matthew KlausOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Thu Jun 19 14:06:11 EDT 2014

    Committee Statement

    CommitteeStatement:

    The first draft language eliminates the possibility of removing dry sprinklers with a head wrencheven if the manufacturer recommends it. At least one manufacturer recommends installing andremoving their dry sprinklers with a head wrench. The wording has been modified to allow the useof a head wrench if the manufacturer recommends it.

    ResponseMessage:Public Comment No. 26-NFPA 13D-2014 [Section No. 5.1.1.1]Public Comment No. 27-NFPA 13D-2014 [Section No. A.5.1.1.1.1]

    Ballot Results

    This item has passed ballot

    30 Eligible Voters1 Not Returned

    29 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedDannaway, Samuel S.

    Affirmative AllBell, Kerry M.Benn, FredBittenbender, Jonathan C.Bradley, Frederick C.

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    7 of 51 10/16/2014 12:39 PM

  • Brown, Phillip A.Deegan, Thomas G.Feid, JeffreyFlancher, Dawn M.Haagensen, Dana R.Hoover, Tonya L.Hopkins, MarkHunter, Jerry R.Isman, Kenneth E.Johnson, Gary L.Leyton, Stephen M.Nickson, Ronald G.O'Brian, MichaelOrlowski, StevenPilette, Maurice M.Puchovsky, Milosh T.Pugsley, Scott C.Schwab, Peter T.Skare, Eric J.Skinner, Timothy J.Stanley, George W.Van Walraven, EdVictor, Terry L.Webb, Ronald N.Yu, Hong-Zeng

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    8 of 51 10/16/2014 12:39 PM

  • Second Revision No. 4-NFPA 13D-2014 [ Section No. 5.1.2.1 ]

    5.1.2.1 Tanks, expansion tanks, gauges, pumps, hangers, waterflow detection devices, and valves shall not berequired to be listed.

    Submitter Information Verification

    Submitter Full Name: Matthew KlausOrganization: National Fire Protection AssocStreet Address:City:State:Zip:Submittal Date: Thu Jun 19 14:24:08 EDT 2014

    Committee Statement

    CommitteeStatement:

    Gauges are not always required but when they are utilized, should not be required to belisted.

    Response Message:Public Comment No. 10-NFPA 13D-2014 [Section No. 5.1.2.1]

    Ballot Results

    This item has passed ballot

    30 Eligible Voters1 Not Returned

    29 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

    Not ReturnedDannaway, Samuel S.

    Affirmative AllBell, Kerry M.Benn, FredBittenbender, Jonathan C.Bradley, Frederick C.Brown, Phillip A.Deegan, Thomas G.Feid, JeffreyFlancher, Dawn M.Haagensen, Dana R.Hoover, Tonya L.Hopkins, Mark

    National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

    9 of 51 10/16/2014 12:39 PM

  • Hunter, Jerry R.Isman, Kenneth E.Johnson, Gary L.Leyton, Stephen M.Nickson, Ronald G.O'Brian, MichaelOrlowski, StevenPilette, Maurice M.Puchovsky, Milosh T.Pugsley, Scott C.Schwab, Peter T.Skare, Eric J.Skinner, Timothy J.Stanley, George W.Van Walraven, EdVictor, Terry L.Webb, Ronald N.Yu, Hong-Zeng

    National Fire Protection Association Report http://submittals.nfpa.org/Terr