Request For Quotation: JUNCTION BOX
Purchaser Details: Sub-Vendor Details:
RFQ Reference No.: ENR15002_JB ID :
Contract No.: ENR15002 Address:
MR Number :
Issue Date : 2-Aug-2015 Attention:
Quote Required Date: 6-Aug-2015 Tel. :
Total Attachments: Refer below Fax:
Total Pages : E-mail:
Originator : MA
A. Items to be quoted
Line Item Descriptions Unit Quantity Remark Vendor Delivery Date
1 JUNCTION BOX ENCLOUSRES Pieces 31 As per JB wiring and layout DWG
2 TERMINAL BLOCKS Set 31 As per JB wiring and layout DWG
3 SS 316 Drain and Breathers Pieces 31 As per JB wiring and layout DWG
4 DIN RAIL Set 31 As per JB wiring and layout DWG
5 WIRES DUCT Set 31 As per JB wiring and layout DWG
6 SS 316 PLUGS Set 31 As per JB wiring and layout DWG
B. ARAMCO APPLICABLE SPECSSR. NO. Document Title Current Issue
1 22-Jul-132 8-Aug-103 6-Feb-12
C. INFORMATION REQUIRED WITH QUOTATIONCommercial offerTechnical offer contains below:
1- Junction Box Layout dimenstional DWG with internal arrangment
2- 3rd Party certifiate
3- BOM with specs and Part number
4- Enclosure and internal components Catalogs
C. Attachment
SPDP Complete SPDP Folder175-340200 INSTRUMENTATION for PACKAGED UNITS ITRS-00-1130-0150 Rev.02H PACKING PROCEDURES-00-1130-0151 Rev.02H SHIPING PROCEDURESA-7907; Instrumentation (General) NON MATERIAL REQUIRMENTS
D. COMPLIANCE SHEET
SAES-J-902 Saudi Aramco Engineering Standard - Electrical Systems for InstrumentationSAES-P-104 Saudi Aramco Engineering Standard - Wiring Methods and Materials34-SAMSS-831 Saudi Aramco Material Specification Standard - Instrumentation for Packaged Units
SAES-J-902 Saudi Aramco Engineering Standard - Electrical Systems for InstrumentationSAES-P-104 Saudi Aramco Engineering Standard - Wiring Methods and Materials34-SAMSS-831 Saudi Aramco Material Specification Standard - Instrumentation for Packaged UnitsVE-536302 BASIS OF DESIGN FOR INSTRUMENTATION AND CONTROL
ENR15002-IE-002_REV.00 JB WIRING DIAGRAMENR15002-IE-003_REV.00 JB INSISDE & OUTSIDE LAYOUT
See Next sheet
P.O. Box 105689, Riyadh 11656, KSA.
-
JUNCTION BOX Compliance sheetPROJECT DATA ISSUEDPROJECT NAME Condensate Polishing Package (J50-U-0200) REVFACILITY EPC13 Utilities Distribution PackageLOCATION JAZANENVIRONMENTAL CONDITION SAFE AREA
PROJECT SPECS
Aspect ARAMCO requirements PROJECT REQUIREMENTS
1 Area classification non-hazardous areas As per ARAMCO specs2 Enclosure rating NEMA Type 4X or IEC 60529 Type IP 66 box As per ARAMCO specs3 Enclosure construction Type 316 stainless steel body, door, and hardware As per ARAMCO specs
Continuously welded seams, finished smooth. As per ARAMCO specs4 Door installation single door As per ARAMCO specs
Stainless steel hinge As per ARAMCO specsdoor shall open from left-to-right or from right-to-left As per ARAMCO specsRemovable door As per ARAMCO specs
5 Door lock316 Stainless steel captive clamps.
As per ARAMCO specs
As per ARAMCO specs
Keylocks and padlocks are not acceptable As per ARAMCO specs6 Mounting External mounting brackets As per ARAMCO specs
All field junction boxes shall be mounted vertically As per ARAMCO specs7 Internal Installation Collar studs for mounting inside panel As per ARAMCO specs
316 Stainless steel back panels As per ARAMCO specsData/Print pocket on inside of door As per ARAMCO specs
The DIN rail shall only be mounted on the inside panel (back-pan) of the junction box.As per ARAMCO specs
The terminals shall be mounted on vertical DIN rails (i.e., horizontal DIN rails are not allowed).As per ARAMCO specs
The DIN rail must be insulated from the Enclosure As per ARAMCO specs8 Earthing Ground stud for terminating A/C safety ground wire As per ARAMCO specs9 DRAIN & BREATHER 316 SS Drain & Breather must be provided
10 CERTIFICATION As per ARAMCO specs
11 TERMINAL BLOK Terminal blocks shall be channel (rail) mounted, As per ARAMCO specs
strip type, with tubular box clamp connector and compression bar or yoke for wire termination. As per ARAMCO specs
As a minimum, the thickness of the terminals shall be 5 mm or higher. As per ARAMCO specsMulti-deck and spring type terminal blocks are not acceptable As per ARAMCO specs
As per ARAMCO specs
As per ARAMCO specs
Min. 60 mm spacing between TB to JB sides and TB to ducts
-
JUNCTION BOX Compliance sheet2-Aug-15000
Vendor compliance
complycomplycomplycomplycomplycomplycomplycomply
comply
complycomplycomplycomplycomplycomplycomply
comply
complycomplycomply
comply
complycomply
complycomplycomply
comply
comply
Captive screws used in lieu of captive clamps as per latest SAES J 902
-
COVER SHEETCOMPLIANCE_SHEET