1
3220 Multi HazardConventional Suppression Control SystemP/N 30-32200X-X0X30-3220.0
Effective: December 2001
FEATURES• Microprocessor based Programmable• UL & ULC Listed, FM Approved• CSFM & MEA Approvals pending• Listed for FM-200, FE13 and HALON Clean Agent
Suppression Systems. Also for SprinklerSupervisory, Deluge and Preaction Systems
• Remote Hazard Control• Remote Display Units for Local or Global Repeat
Annunciation• Completely and easily field programmable• 80 character alphanumeric LCD Display• 270 event history bufferDESCRIPTIONThe Fenwal® 3220 is a microprocessor based program-mable Suppression Control System designed for operationwith Conventional Fenwal Ionization and PhotoelectricSmoke Detectors. In its simplest configuration, the Fenwal®3220 Main Control Panel (MCP) is a single hazard ControlPanel that can be field-expanded to be a large 8 hazardControl System with multiple Remote Display Units. Sys-tem expansion is achieved by adding up to 7 Remote Haz-ard Units (1 RHU per added Hazard) and up to 16 RemoteDisplay Units (RDU). The MCP communicates with theRHUs and RDUs on a dual path, Style 7 RS-485 network,monitors their status and displays system wide messages.
SYSTEM COMPONENTSMAIN CONTROL PANEL (MCP)MCP Power Supply:The MCP operates on 120/240 Vac 50/60 Hz Power Sup-ply. The Power Supply Unit is rated 4 Amps at 24 Vdc and isprovided a Battery Charger to charge a 24 Vdc backup Bat-tery. The Battery may be sized for 24 hour Standby with 5minutes Alarm or for 90 hour Standby with 10 minutes Alarmdepending on the Suppression System. The Power Supplycauses an immediate changeover to battery in case of lossof AC input or drop in input voltage.
MCP Display Panel:The MCP Display Panel is provided an LCD Display, fivestatus LEDs and a local buzzer It is also provided four Sys-tem Control Buttons and four Menu Control Buttons (seeFigure 1).
MCP Hazard Block:The MCP controls one Hazard Block and is provided thefollowing Input Circuits:• 2 Style B or Style D Initiating Circuits, each of which
can support 40 Fenwal Smoke Detectors• 1 Style B Manual Release Circuit for N.O. devices
• 1 Style B Abort Circuit for N.O. devices• 1 Style B Supervisory Circuit for N.O. devices• 1 Style B or Style D Waterflow Circuit for N.O. devices.The MCP is provided the following Output Circuits:• 2 Style Y or Style Z Indicating Appliance Circuits rated
2.5 Amps total at 24 Vdc for polarized A-V signals.• 1 Style Y Agent Release Circuit rated 3.4 Amps max at
24 Vdc. The circuit can be configured for Fenwal Initia-tors or Control Head Solenoids for Clean Agent Sys-tems or for FM Group A, B, D, E or G Solenoids forDeluge and Pre-Action Systems.
The MCP also provides the following Relay Outputs:• 1 Form C System Alarm Relay• 1 Form C System Trouble Relay• 1 Form C Programmable Relay• 5 Form C Programmable Relays (on socket mounted
Optional Relay Board)
Figure 1. MCP Display Panel
CONTROL
SUPERVISORYR
TM
SIGNALTROUBLESCROLL
SCROLL
SUP/TBL
ALARM
RESET
SILENCE
CONTROLS
ALARMPOWER ONPANEL
MAIN
SYSTEM
CONTROLSMENU
CANCEL ACCEPT
SIGNAL
SILENCED
MCP V1.0SYSTEM STATUS NORMAL
12:00 4/25/01ALM00 SUP0 TBL00
2
MCP Programming:All programming is done via the MCP keypad. When theSystem is initialized, the MCP downloads the Operating Con-figuration to the RHUs and RDUs.
MCP Enclosure:The MCP enclosure is rated NEMA 1 for indoor use. It isconstructed of 18 gauge steel, painted Fenwal beige andkept closed by a steel door with a key-lock. All operator in-terface switches and indicators are located behind the lockedcover. The enclosure is large enough to house two 12 Ah 12Vdc batteries for backup supply. Battery Enclosures areavailable for larger capacity batteries. Optional dead-frontenclosures are also available for use in Canada.
12 Ah 12 Vdc
Battery
J4
J5
TB6
TB7
TB4
TB1 TB2 P1&P2 TB3 TB5
J1
W200
W104 W101
W109
W108
ISP RES
SW90
CPU RES
SW1
WATERFLO
W ++
SUP'V
+
ABORT
+
Man
Rel +
DETECTOR
2 + +
DETECTOR
1 ++R-
24V DC
OUT +R+
24V
IN +
AC MAINS
INPUTL ENN L
NO
C
NC
A
M
L
NO
C
NC
T
L
B
NO
C
NC
V
R
F
+
SOUNDER
1
+
STOP V
++
SOUNDER
2
+ +
RELEASE
+A
CHANNEL
1
BAB A
CHANNEL
2
BAB
BATTERY
+
INTERNALSOUNDER
LCD
CONTRAST
VR1
- + - +
12 Ah 12 Vdc
Battery
MENU
CONTROLS
CANCEL ACCEPT
SILENCE
RESET
MAIN
CONTROL
PANEL
SUPERVISORY TROUBLE SILENCED
POWERON
ALARM
ALARM
SCROLL
TROUBLESCROLL
SYSTEMCONTROLSTM
MCP V 1.0SYSTEM STATUS NORMAL
12:00
01-30-01
Figure 3. Internal View
SYSTEM COMPONENTSREMOTE HAZARD UNIT (RHU)RHU Power Supply:The RHU Power Supply Unit is exactly the same as that ofthe MCP.
RHU Display Panel:The optional RHU Display can operate either in local orglobal mode. It is provided the same features as the MCPwith the exception of the Menu Controls (see Figure 4).
SILENCE
UNIT
SUPERVISORYR
SIGNALTROUBLE
ALARMPOWER ON
SCROLLSUP/TBL
REMOTEHAZARD
TM
SYSTEMCONTROLS
SCROLLALARM
RESET
SIGNAL
SILENCED
RHU # 1 V 1.0
LOCAL STATUS NORMAL
12:00 4-25-01
ALM00 SUP0 TBL00
Figure 4. Remote Hazard Unit Display Panel
RHU Hazard Block:Each RHU also controls one Hazard Block and is providedthe same Input and Output Circuits as the MCP with theexception of the three System Relays. The Optional RelayBoard (ORB) can also be mounted to the RHU.
RHU # 1w/ Display
RDU # 1 for MCP
RDU # 2 for RHU # 1
Main Control Panel
RHU # 2w/o Display
Two independant Style 7RS-485 Data Pairs. Max.length 4,000 ft. each.
120/240
Vac
24 Vdc
24 Vdc
24 Vdc
RDU # 4 for RHU # 2
RDU # 3 for RHU # 2
RHU # 2
RDU # 5 for
120/240
Vac
120/240Vac
Note: The system must comprise 1 MCP.
To expand, add up to 7 RHUs andup to 16 RDUs to the network.
SILENCE
UNIT
SUPERVISORYR
SIGNALTROUBLE
ALARMPOWER ON
SCROLLSUP/TBL
REMOTEHAZARD
TM
SYSTEMCONTROLS
SCROLLALARM
RESET
SIGNAL
SILENCED
RHU # 1 V 1.0
LOCAL STATUS NORMAL
12:00 4-25-01
ALM00 SUP0 TBL00
SYSTEMCONTROLS
ALARMSCROLL
SUP/TBLSCROOL
RDU #1 V 1.0SYSTEM STATUS NORMAL
12:00 04-25-01ALM00 SUP0 TBL00
R
TM
REMOTE DISPLAY UNIT
POWER
CONTROL
SUPERVISORYR
TM
SIGNALTROUBLESCROLL
SCROLL
SUP/TBL
ALARM
RESET
SILENCE
CONTROLS
ALARMPOWER ONPANEL
MAIN
SYSTEM
CONTROLSMENU
CANCEL ACCEPT
SIGNAL
SILENCED
MCP V1.0SYSTEM STATUS NORMAL
12:00 4/25/01ALM00 SUP0 TBL00
SYSTEMCONTROLS
ALARMSCROLL
SUP/TBLSCROOL
RDU #1 V 1.0SYSTEM STATUS NORMAL
12:00 04-25-01ALM00 SUP0 TBL00
R
TM
REMOTE DISPLAY UNIT
POWER
SYSTEMCONTROLS
ALARMSCROLL
SUP/TBLSCROOL
RDU #1 V 1.0SYSTEM STATUS NORMAL
12:00 04-25-01ALM00 SUP0 TBL00
R
TM
REMOTE DISPLAY UNIT
POWER
SYSTEMCONTROLS
ALARMSCROLL
SUP/TBLSCROOL
RDU #1 V 1.0SYSTEM STATUS NORMAL
12:00 04-25-01ALM00 SUP0 TBL00
R
TM
REMOTE DISPLAY UNIT
POWER
SYSTEMCONTROLS
ALARMSCROLL
SUP/TBLSCROOL
RDU #1 V 1.0SYSTEM STATUS NORMAL
12:00 04-25-01ALM00 SUP0 TBL00
R
TM
REMOTE DISPLAY UNIT
POWER
Figure 2. Typcial System Block Diagram
3
RHU Programming:The RHU receives its Operating Configuration from the MCP.
RHU Enclosure:The RHU Enclosure when using the Optional Display Panelis very similar to that of the MCP. In the case that this optionis not selected, the RHU Enclosure has no viewing window.
SYSTEM COMPONENTSREMOTE DISPLAY UNIT (RDU)RDU Power Supply:The RDU operates on 24 Vdc Power received either fromthe MCP, its associated RHU or any other UL Listed source.
RDU Display Panel:The RDU is a Display only unit and can be programmed tooperate either in local or global mode. In local mode, it mim-ics the Display of the MCP or the RHU to which it is as-signed whereas in global mode, it mimics the display of theMCP. The RDU Display Panel provides one LCD Display,one Status LED and System Controls (see Figure 6.)
RDU Hazard Block:RDUs may be used to accept one Manual Release and oneAbort input from the local protected zone to which its asso-ciated MCP/RHU is assigned.
RDU Backbox:The RDU Backbox is constructed of 18 gauge steel, paintedFenwal beige and kept closed by the Display Panel frontplate.
SYSTEM LOGSThe Fenwal® 3220 Control System is provided an EventLog and Configuration Log, both of which reside in the MainControl Panel. The Event Log is a compilation of all Alarm,Trouble, Supervisory and Event messages stored in non-volatile memory. Up to a maximum of 270 events can bestored at any given time. The occurrence of a new eventbeyond the maximum capacity erases the earliest event.
MENU STRUCTUREThe Main Menu of the Fenwal® 3220 Control System con-sists of the following items as shown on the tree structurein Figure 7. Specific functions are password protected tolimit access to authorized personnel only.
Figure 5. Hazard Block Inputs and Outputs
Detection Circuit # 1Style B or D
Detection Circuit # 2Style B or DSmoke and
Heat Detectors
Waterflow InputStyle B or D
Sprinkler System
Pull Station
Manual Release
AbortStyle B
Abort Station
Supervisory Signal
Release Circuit
Auxiliary Power 124 Vdc 24 Vdc
(Not resettable)Auxiliary Power 2
Inputs from
field devices
Outputs
RS485Port
RS-485 Data Highway
Clean Agent Control Head
Deluge System Solenoid
To Remote Display Units
To and from other
System Units
Form C Alarm Relay
Form C Trouble Relay
Form C Prog. Relay
Auxiliary Functions- Equipment Shutdown- Repeat Annunciation- DACT (MCP only)
Main Control Panel and Remote Hazard Units
PUSH
PULL
FIRE FIRE
PUSH / HOLD
SUPPRESSIONSYSTEM ABORT
Style B
Style B
5 Form C Prog. Relayson Option Relay Board
Indicating Circuit # 1
Style Y or Z
Indicating Circuit # 2
Style Y or ZAudible and VisualIndicating Devices
All relays except those on ORBare applicable to the MCP only.
FENWAL
Style Y
AG
EN
TR
EL
EA
SIN
GL
OG
IC
Clean Agent Initiators
Figure 6. Remote Display Unit Display Panel
SYSTEMCONTROLS
ALARMSCROLL
SUP/TBLSCROLL
RDU #1 V 1.0SYSTEM STATUS NORMAL
12:00 04-25-01ALM00 SUP0 TBL00
R
TM
REMOTE DISPLAY UNIT
POWER
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no re-sponsibility for the product's suitability for a particular application. The product must be properlyapplied to work correctly.If you need more information on this product, or if you have a particular problem or question, contactKIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.comProtection Systems
R
Figure 7. Menu Structure
TECHNICAL INFORMATIONMAIN CONTROL PANEL (MCP)Input Supply: 120/240 Vac 50/60 HzCurrent Draw: 3.0 Amps @ 120 Vac
1.4 Amps @ 240 VacOutput Rating: 4.0 Amps @ 24 VdcBattery Charger Output: 3.5 Amps max @ 27.3 VdcAux. Power Output: 0.5 Amp max @ 24 VdcQuantity per System: 1Enclosure Rating: NEMA 1Enclosure Material: 18 gauge steel, painted beigeDimensions (WxDxH): 15.5” x 5.0” x 15.5”
(393.7mm x 127mm x 393.7mm)Ambient Temperature: 32°F to 120°F (0°C to 49°C) max.Relative Humidity: 93% non-condensing max.
TECHNICAL INFORMATIONREMOTE HAZARD UNITS (RHU)Input Supply: 120/240 Vac 50/60 HzCurrent Draw: 3.0 Amps @ 120 Vac
1.4 Amps @ 240 VacOutput Rating: 4.0 Amps @ 24 VdcBattery Charger Output: 3.5 Amps max @ 27.3 VdcAux. Power Output: 0.5 Amp max @ 24 VdcQuantity per System: Maximum 7Enclosure Rating: NEMA 1Enclosure Material: 18 gauge steel, painted beigeDimensions (WxDxH): 15.5” x 5.0” x 15.5”
(393.7mm x 127mm x 393.7mm)Ambient Temperature: 32°F to 120°F (0°C to 49°C) max.Relative Humidity: 93% non-condensing max.
30-3220.0 12/01 Kidde-Fenwal Inc. Printed in USA
TECHNICAL INFORMATIONREMOTE DISPLAY UNITS (RDU)Input Supply: 24 Vdc (nominal)Quantity per System: Maximum 16Backbox Rating: NEMA 1Backbox Material: 18 gauge steel, painted beigeDimensions (WxDxH): 8.0” x 2.25 x 4.45”
(203.2mm x 57.1mm x 113.0mm)Ambient Temperature: 32°F to 120°F (0°C to 49°C) max.Relative Humidity: 93% non-condensing max.
ORDERING INFORMATION
������� ������ �
������������������� ���������������
��������
������������������� ���������������
��������
�������������� �� �������� �������������
������������ �!
������������� "�� �� �������� �������������
������������ �!
#������������� �� �������� �������������
������������ �!
������������� ��!�� ������ �!� �������������
$������������ �%�&����%�������� �&���������
'(��#�$#���)���� %��*+�������,�+��-�!.��
�����"/����
)(��#�$#���)���� %��*+�������,�+'�-�!.��
�����"/����
�����#�����$0��� %��*+�������,�+��-�!.��
�����"/����
����(���������� � �"��1� ���2���� %���������
� ���� %��*+�������,�+��
������$$���)� �"*���� ����3�&4� �5�� � ��
����"!
For design, installation, configuration and additional order-ing information, refer to the Fenwal® 3220 EngineeringManual P/N 06-235976-001.