USER MANUAL USER MANUAL USER MANUAL 763.483 Ed. 1 Rev. 0 08/04/2013 CONTROL PANELS for 2 CONTROL PANELS for 2 CONTROL PANELS for 2 Q2P Q2P Q2P series ELECTRIC PUMPS series ELECTRIC PUMPS series ELECTRIC PUMPS Q2PME16EI Q2PTE08EI

Upload: others

Post on 11-Sep-2019

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

1

USER MANUALUSER MANUALUSER MANUAL

763.483 Ed. 1 Rev. 0 08/04/2013

CONTROL PANELS for 2 CONTROL PANELS for 2 CONTROL PANELS for 2 Q2P Q2P Q2P series ELECTRIC PUMPS series ELECTRIC PUMPS series ELECTRIC PUMPS

Q2PME16EI Q2PTE08EI

Page 2: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

2

1. WARNINGS GUIDE TO CONSULTING THE USER

MANUAL

2. PREFACE IMPORTANT CONSERVATION SYMBOLS DEMOLISHING AND DECOMMISSIONING

3. PRELIMINARY INFORMATION PRODUCT PRESENTATION INTENDED USE NON-PERMITTED USE NAMES OF PARTS IDENTIFICATION OF THE EQUIPMENT

4. TECHNICAL SPECIFICATIONS GENERAL SPECIFICATIONS

6. OPERATION AND USE 6.1 CONTROL PANEL

TYPES OF LIGHT SIGNALS MAIN LIGHTS (SYSTEM) MOTOR SIGNALS CONTROL BUTTONS RECORDING “REC” BUTTONS ALARM RESET BUTTON

6.2 OPERATION MODES DESCRIPTION AUTOMATIC PERMANENT HAND TEMPORARY HAND OFF

6.3 COMMON FUNCTIONS DRY RUNNING PROTECTION "SO" STOP INPUT ALARM FOR STOP VIA "SO" OR VIA

"DRY RUNNING" PROTECTION "W" STOP INPUT MOTOR PROTECTION ENABLING

6.4 AUXILIARY FUNCTION SELECTORS KEY SELECTOR J1 SELECTOR J3

6.5 INTERNAL ADJUSTMENT POTENTIOMETERS MOTOR OVERLOAD — OVERLOAD

1, 2 — STOP DELAY 1st MOTOR — M1 STOP

DELAY— START DELAY 2nd MOTOR — M2 START

DELAY— Potentiometer not active —Inom SET—

6.6 CURRENT PROTECTION RECORDING “REC” MOTOR DATA CHECK “TEST” MOTOR DATA OVERLOAD PROTECTION THRESHOLD

7. WARNINGS AND ALARMS 7.1 DESCRIPTION 7.2 SYSTEM

POWER SUPPLY "SO" STOP INPUT "W" STOP INPUT

7.3 MOTOR PROTECTION — TRIP — RUN

8. QUICK INFO 8.1 SIGNALS 8.2 CONTROLS 8.3 SELECTOR J1—FUNCTIONS

5. INSTALLATION 5.1 PRELIMINARY OPERATIONS

FASTENING THE EQUIPMENT 5.2 CONNECTION

SETUP ELECTRICAL CONNECTION

5.3 COMMISSIONING SHUTTING DOWN THE MOTORS MOTOR 1 PROTECTION SETTING MOTOR 2 PROTECTION SETTING INTERNAL POTENTIOMETER ADJUST-

MENT SETTING THE FUNCTIONS

obligatory implementation

Page 3: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

3

This document is to be considered an integral part of the equipment, therefore it must be conserved and kept throughout its duration and use.

Before implementing any intervention or operation on the equipment, it is recommended to carefully read all the information in this manual. Strictly follow the instructions given in this manual as safe operation and conservation of the equipment depend on proper use and application of the recommendations described further on.

The manufacturer declines all responsibility for damage caused to persons, objects or animals deriving from non-compliance with the requirements provided in this manual.

IMPORTANT

This signal indicates that serious dam-age can be caused to the equipment and/or persons if the operations de-scribed in the manual are not imple-mented correctly.

SYMBOLS

If the manual is lost, stolen or damaged, a copy may be requested from the manufacturer.

CONSERVATION

The electrical equipment must be disposed of as separate waste. Appropriate precaution must be taken when the equipment is to be demolished or decommissioned so as to prevent hazardous situations for persons or objects:

Disconnect the equipment from the power supply and release any residual energy;

The equipment must be delivered to a waste collection facility for electrical and electronic equipment set up by the local authorities.

DEMOLISHING AND DECOMMISSIONING

2. PREFACE 1. WARNINGS GUIDE TO CONSULTING THE USER MANUAL

To use the equipment, it is not necessary to read the entire manual, just certain parts which provide useful information, as explained below:

INSTALLATION …

Ch. 5.1, 5.2

and the

Specific for each model of equip-ment.

CALIBRATION ……Ch. 5.3

OPERATION in gene-ral ……………… Ch. 6.1, 6.2, 6.3

SIGNALS …………… Ch. 6.1

SELECTORS and PO-TENTIOMETER …………

…………………………… Ch. 6.4, 6.5

ALARMS ………… Ch. 6.1, 7

In any case, the CONTENTS contains all the indications necessary in order to find the information required.

TECHNICAL MANUAL TECHNICAL MANUAL TECHNICAL MANUAL

Page 4: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

4

3. PRELIMINARY INFORMATION

1. Disconnecting switch with door lock 2. Synoptic panel 3. Terminal block for control components 4. Terminal block for motors 5. Terminal block for power supply 6. Adjustment selectors and potentiometers

Any other use that does not comply with that stated in this manual is to be considered as improper use and is therefore, strictly forbidden.

NON-PERMITTED USE

The equipment has been solely designed and built for the functions and use described in this manual

INTENDED USE

The equipment consists of an electrical panel intend-ed for the control of water treatment electric pumps.

PRODUCT PRESENTATION

Example of Q2PTE08EI equipment:

NAMES OF PARTS

IDENTIFICATION OF THE EQUIPMENT

An external plate on the equipment states the identification data, such as: IDENTIFICATION: Product line Manufacturer : Name of the

manufacturer Code : Code Model : Model S/N : Serial number Date : Manufacturing date POWER SUPPLY Un : Voltage Fn : Frequency In : Current at full load Icc : Short-circuit withstand DOCUMENTATION AND STANDARD Standard : Standard Main Doc : Documentation MOTOR OUTPUT M : Identification I : Operating current P : Rated power WARNING Indication of electrical danger To be disposed of as electrical

or electronic waste CE marking Country of production

2

1

3

4

5

6

Page 5: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

5

4. TECHNICAL SPECIFICATIONS

Name and description: "Q2P" CONTROL PANEL FOR 2 ELECTRIC PUMPS WITH ELECTRONIC PROTECTION:

Power section: Power supply (depending on the models):

Single-phase: ~ 50/60Hz 230 / 240V ±10%; Three-phase: 3~ 50/60Hz 230 / 240V ±10%;

3~ 50/60Hz 400 / 415V ±10%; With internal selection of power supply;

2 outputs for three-phase or single-phase electric pumps with incorporated capacitor according to the unit model.

Neutral regime: TT, TN, IT system. Protection against indirect contact must be en-sured using external devices or suitable precau-tions, according to current standards.

Control inputs: 4 very low voltage float switch or pressure switch

inputs for the following: shutdown level or pressure detection (S0); Control level or pressure of the first electric

pump ("S1" input); Control level or pressure of the second electric

pump ("S2" input); Alarm level or pressure ("W" input).

Controls and signals: 2 buttons for every electric pump for the follow-

ing function modes: AUTOMATIC / alarm RESET; HAND / OFF; Enabling the motor current “Self-learning” fea-

ture for commissioning;

GENERAL SPECIFICATIONS 3 indicator lights for the following signals: Power supply status (regular operation or

fault); Stop float switch or pressure switch interven-

tion (input “S0”); Alarm float switch or pressure switch interven-

tion (input ”W”); 3 indicator lights for every electric pump for the

following signals: Operating mode (AUTOMATIC / OFF / HAND); Motor status (running, stopped due to dry

running; the alarms are distinguished individ-ually);

Motor protection triggered (overload, mini-mum load; the alarms are distinguished indi-vidually);

Acoustic signal: Continuous for system alarms: "W" input,

"SO" input (excludable), "dry running" protec-tion intervention (excludable);

Intermittent for motor alarms ("overload" or "minimum load" protection;

Single or double Beep for warning of special settings of internal selectors;

Functions set via the selectors: Auxiliary features:

Polarity inversion of "SO" stop input; Polarity inversion of "W" alarm input; Self hold, for electric pump start-up only via

relative "S1" and "S2" control inputs, electric pump stop only via "SO" stop input;

Alternate electric pump start-up and switch for uninterrupted running after 12 hours;

Alarm signal for interventions on "SO" stop input or for "dry running" protection interven-tions;

Motor protections (overload, minimum load, dry running) enabled permanently or in disabled tem-porarily (10s).

Protection against motor "dry running" enabled. Features which can be set from the potentiom-eter: Intervention threshold of motor 1 overload pro-

tection; Intervention threshold of motor 2 overload pro-

tection; Second electric pump start delay starting in AU-

TOMATIC mode (0—30s); Stop delay of the first electric pump started in

AUTOMATIC mode (0—180s).

Model Power Supply Motor start-up type

Q2PME16EI Single-phase 230 / 240V Direct

Q2PTE08EI Three-phase 230 / 240V 400 / 415V

Direct

For the electrical connection to the mains, refer to the section:

DATA FOR POWER SUPPLY in the

TECHNICAL MANUAL TECHNICAL MANUAL TECHNICAL MANUAL

Page 6: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

6

General functions: Motor start-up delay (10s) after reconnecting the

power supply voltage; Electric pumps started-up non-simultaneously,

with an interval of 2s, in AUTOMATIC mode, un-less otherwise set on the adjustment potentiome-ter of the "first pump start delay";

Periodic release of the impeller in AUTOMATIC mode (running 2s every 48h);

MANUAL run mode type: PERMANENT by a short press on the button;

It is subject to stop running due to the “S0” input or the “Dry Running” protection being triggered.

"TEMPORARY": by keeping the control button pressed; Running is not subject to stop via "SO" input or via intervention of the “Dry Running” pro-tection.

Alarms and protections: Intervention of float switch or pressure switch for

the following: Stop ("SO" input):

pump stop, signalling with relative fixed on warning light and any general alarm emis-sion if enabled;

Alarm ("W" input): signalling with relative fixed on warning light and general alarm emission;

Intervention of protection against: Motor overload with calculation of stored ener-

gy (I2t): pump stop, signalling with relative fixed on warning light and general alarm emission;

Minimum load of motor: pump stop, signalling with relative flashing warning light and general alarm emission;

Dry running: arresto della pompa, segnalazione con light and any general alarm emission if enabled; periodic reset attempts (10 minutes);

Start-up of second motor, if available, to replace the one that has stopped due to the intervention of any protective device (excluding the “dry run-ning” protection device).

Motor protection fuses for each motor (1 pair for Q2PME16EI and 3 pcs for Q2PTE08EI);

Auxiliary circuit protection fuses;

Informazioni tecniche: Insulation voltage, dependent on the power volt-

age: 300V for a 230/240V power supply; 450V for a 400/415V power supply;

Rated voltage of control circuits 12V; Voltage of control circuits for the contactor coils

(if present): 230/240V;

Personnel protection measures: Isolation of live parts; Protection using barriers or casings; Casing made of thermoplastic material or metal,

depending on the model; IP55 Degree of Protection (the degree of protec-

tion is guaranteed only if the connection cables have been properly installed).

Main disconnecting switch with door lock; Equipotential protection circuit (Earth); A tool is required to open the casing; Conditions of service: Stationary equipment; Installation inside a building; wall-mounted; with

accessible lateral, top and bottom sides (not re-cessed).

Natural ventilation; Room temperature –5/+40 °C, average tempera-

ture within 24h lower than +35 °C. Clean air with maximum relative humidity 50%

with a maximum temperature of +40 °C. Pollution degree 2 (Only non-conductive pollution

occurs except that occasionally a temporary conductivi-ty caused by condensation is to be expected)

Maximum altitude is 2,000m above sea level; Transportation, storage and installation tempera-

ture -25/+55 °C and a maximum of +70 °C when less than 24h;

Type of electrical connections of the functional units: FFF (fixed connections either connected or dis-connected using a tool for the main input or output circuit and auxiliary circuits).

EMC — Electromagnetic compatibility: “Environment 1” (equipment supplied by the low-voltage public system, residential, commercial and light industrial systems).

Reference standards: See the document DECLARATION OF CONFORMI-

TY.

Page 7: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

7

Otherwise, there may be a risk of: Incorrect system operation and

serious damage caused to the equipment.

Serious injuries, death or long term health risks.

ALL the INSTALLATION stages must be implemented

THOROUGHLY!

5. INSTALLATION

Degree of protection and conditions of service: those stipulated in the technical specifications of the equipment must meet the requirements of the type of installation.

Fastening the casing: this must be implemented through the special holes (already present or drilled) at the bottom or with the fastening brack-ets, if supplied.

Passing the connection cables: this is imple-mented by means of cable glands that must be installed on the lower part of the casing, after having drilled appropriate holes. The hole must have an adequate diameter for the cable gland to pass and must not have any burrs, so as to further guarantee the required degree of protection once the assembly process is complet-ed.

Connecting the cables in the terminal block: this must be implemented with the use of a tool of the right size, so as to avoid damaging the ter-minal itself.

Cleaning the casing: this must be implemented once installation is completed. This consists of the removal of all kinds of metal and/or plastic impu-rities that may have fallen inside the casing (for example, screws, washers, lengths of wire, sheath, drilling chips, dust, etc.).

Take great care when drilling and fas-tening so as to avoid touching or dam-aging the components and any control boards inside the equipment.

FASTENING THE EQUIPMENT

5.1 PRELIMINARY OPERATIONS

5.2 CONNECTION

Power supply: this must be of adequate voltage and current for the equipment.

Earth system: this must conform to applicable regulations so as to guarantee adequate dispersion.

Electrical power line protections: these must conform to applicable regulations.

Conductors: these must be made of copper, be as short as possible, with insulation and a cross-section that are adequate for the voltage and operating power, respectively.

Disconnect the mains before imple-menting any operation inside the electrical equipment and remember that the source side section of the main switch always remains live even if the disconnecting switch has been opened. The electrical connections must only be implemented by a qualified electrician.

SETUP

For the electrical connection to the mains, refer to the section:

DATA FOR POWER SUPPLY in the

TECHNICAL MANUAL TECHNICAL MANUAL TECHNICAL MANUAL

SWITCH OFF and OPEN the equipment.

0 — OFF

Page 8: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

8

The float switch or stop pressure switch at "SO" input, setting the contact status with micro switch J1-1 for running consent. OFF = with "contact closed". ON = with "contact open".

The float switches or functional control pressure switches, if present, at inputs "S1", "S2"; otherwise leave terminals open.

The float switch or alarm pressure switch at "W" input, setting the contact sta-tus with micro switch J1-2 for regular opera-tion (no alarm): OFF = with "contact closed". ON = with "contact open".

The sensor cable screen can be connected to the "Mass" terminal (internally connected to "PE").

Make sure that the “Voltage-change” selector is in the correct position based on the supply volta-ge

X S0 X S1 X S2 X W

SL/SP STOP

SL/SP 1

SL/SP 2

SL/SP MAX

Example: 2 single-phase motors.

M1

~50/60Hz 230 / 240V ±10%

N

QS1

N L PE

L

M2

N L1

M1

N L1

M2 PE

Example: 2 three-phase motors.

U V W U V W

T1 T2 T3

KM1

T1 T2 T3

KM2

M2 M1

3~50/60Hz 230 / 240V ±10% 400 / 415V ±10%

L1 L2 L3

QS1

L1 L2 L3 PE

“Voltage-change” selector

PE

230V

400V

ELECTRICAL CONNECTION

The electrical connection must be imple-mented as stipulated in the paragraph called:

CONNECTION DIAGRAM in the

TECHNICAL MANUAL TECHNICAL MANUAL TECHNICAL MANUAL

the power supply, the protective earth conductor and the electric pumps to the respective terminals. Refer also to the instructions supplied with the electric pumps, for the electrical connection as well as verification of the correct rotation direction.

Ensure that the rated power and current of the applied loads fall within the limits stipulated in the technical specifications of the equipment.

CONNECT :

Page 9: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

9

5.3 COMMISSIONING MOTOR 1 PROTECTION SETTING

ENABLE  the recording func on “REC”  

Press and hold both the HAND—OFF    and     AU‐TO—RESET bu ons on MOTOR 1 for more than 5 seconds. The indicator light RUN must blink with 2 flashes. 

SHUTTING DOWN THE MOTORS

SELECT   the  ”OFF"   opera ng mode for all motors 

Check  that  the OPERATION  indicator  light  is off on all the motors. If they are not, press the HAND—OFF  bu on on the affected motors once, briefly. 

START the motor in  "PERMANENT  HAND" mode  

Press the HAND—OFF bu on on MOTOR 1 once, briefly.  

Off 

2x

2 flashes 

On 

2x

2 flashes 

CLOSE, connect the power supply and SWITCH ON the equipment.  

I — ON

Page 10: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

10

U V W

M

1.  That  the DIRECTION  OF  ROTA‐TION  of  the  electric  pump  is correct.  

If  the  detected  direc on  is  not correct, stop the motor, discon‐nect  the  power  supply  and switch two phases of  the motor, as shown in the picture. 

Switch on the equipment once again, 

enable the  recording  func on “REC”, 

start  the  electric  pump  in  "PERMANENT HAND" mode.  

CHECK ...  

3.  That the water FLOW  / PRESSURE and  the  system  FUNCTIONS  are correct. 

2. That the CURRENT  consumed by the  electric pump complies with their own data plate as well as of the equipment. 

A

WAIT for the motor to stop ... 

… or stop it on purpose by pressing the HAND—OFF bu on on MOTOR 1 once, briefly . 

When  the motor stops,  the  indicator  light going off  indicates that recording has been completed successfully  and  the  system  has  exited  “REC” mode. 

20s

Off

3x

To repeat recording:   disable “REC” mode on MOTOR 1 by pushing 

and hold both the  HAND—OFF and AUTO—RESET bu ons on MOTOR 1 for more than 5 seconds. The OPERATION indicator light must go off 

enable “REC” mode on MOTOR 1.  start‐up the motor in “PERMANENT MANUAL” 

mode. 

If the "TRIP" and/or "RUN" indicator lights go on, these  indicate that the recording has failed. This must  be  repeated  once  the  fault  has  been  re‐solved:   

RECORDING ERROR 

RECORDING FAILED 

“TRIP”:The measured current exceeds the operating current

MOTOR 2 PROTECTION (if present)

ENABLE  the recording func on “REC”  

CHECK ...  

START the motor in  "PERMANENT  HAND" mode  

Press and hold both the HAND—OFF    and     AU‐TO—RESET bu ons on MOTOR 2 for more than 5 seconds. 

Press the HAND—OFF bu on on MOTOR 2 once, briefly.  

1.  The DIRECTION OF ROTATION of the electric pump. 

2.  The CURRENT absorbed by the electric pump. 

3.  The water FLOW or the PRESSURE and correct system OPERATION. 

WAIT FOR the motor stop ... 

Page 11: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

11

INTERNAL POTENTIOMETER ADJUSTMENT

Inom  SET Auxiliary func on— reserved 

M1 STOP DELAY  Stop delay on first motor 

90

M1 STOP DLY

60

30

120

150

s

180 0

Set the desired delay for stopping the first motor to be started up.

M2 START DELAY  Start delay on second motor 

15

M2 START DLY

10

5

20

25

s

30 0

Set the desired delay for starting the second motor to be started up.

TEST

100

110

120

90

REC

OVERLOAD no.

130

OVERLOAD1 and 2 at "110%" MOTOR 1 and 2 overload threshold 

We  recommend  se ng  a  value  not  less  than 110% on OVERLOAD poten ometers. Lower protec on  is  achieved by  se ng  a  value between 110% and 130%. The 90% value  is used only  in the case of moni‐toring and tuning system.  

Leave or bring the potentiometer to "0".

Inom SET

MAX 0

Potentiometers

OVERLOAD 1

OVERLOAD 2

Inom SET

M1 STOP DLY

M2 START DLY

SWITCH OFF and OPEN the equipment

OFF

Page 12: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

12

Selector in position ON

ON OFF

SETTING THE FUNCTIONS

Check and set micro switch J1‐1...8 as needed. The factory se ng is suitable for normal uses. In special cases, see the table below and the AU‐XILIARY  FUNCTIONS,  sec on  OPERATION  AND USE. 

N. Micro switch J1 — Features

1 CONTACT STATUS OF "SO" STOP INPUT FOR RUNNING CONSENT NC

2 CONTACT STATUS OF "W" ALARM INPUT FOR REGULAR OPERATIONS NC

3 SELF HOLD ENABLING No

4 PUMP ALTERNATION ENABLING Yes

5 Reserved OFF

6 DRY RUNNING or SHUTDOWN LEVEL / PRESSURE ALARM ("SO" input) No

7 MOTOR PROTECTION ENABLING Yes

8 Yes DRY RUNNING PROTECTION ENABLING

1 ON J3 OFF

Leave J3-1 and J3-2 on OFF

1 8 ON J1 OFF

factory setting

Selectors

J3

J1

N. Micro switch J3 — Features

1 Reserved N

2 Reserved L CAUTION: The use of selectors is reserved; their position must al-

ways be OFF.

Page 13: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

13

START-UP

CLOSE, connect the power supply  and SWITCH ON the equipment 

ENABLE the motors in  "AUTOMATIC" mode opera on 

Select AUTOMATIC operation by briefly pressing the AUTO-RESET button once for each motor

I — ON

On

WAIT  for the motor start  

The motors will be started by the system based on the func ons set and the status of the inputs. 

10s

… in all condi ons, including when the “Dry Run‐ning”  electronic  protec on  is  triggered  (if  ena‐bled). To enable the protec on, you must always keep running consent from "SO" input enabled. 

VERIFY the system works …. 

Page 14: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

14

GENERAL SIGNALS (SYSTEM)

Every indicator light gives more information about the system status by emitting light signals with dif-ferent frequencies. The table below shows the vari-ous types of light indicators. Acoustic signals are differentiated according to the type of warning. The table on the left shows the var-ious types of acoustic indications.

TYPES OF ILLUMINATED AND ACOUSTIC SIGNALS

"MAX" LEVEL/PRESSURE (W input)

"MAX": alarm via "W" input

"STOP" LEVEL/PRESSURE (SO input)

“STOP”: consent denied via "SO" input 

Type of sound emitted

Continuous

| Intermittent

() 1 Beep: 1 short beep + long pause

(()) 2 Beeps: 2 short beeps + long pause

6. OPERATION AND USE

6.1 CONTROL PANEL

SYMBOL

= Off

= On-fixed

= Normal blinking frequency

= 1 Flash + long pause

= 2 Flashes + long pause

= 3 Flashes + long pause

= 4 Flashes + long pause

LIGHT SIGNAL TIME

1x

2x

3x

4x

1 blink/ s

1 s

POWER SUPPLY

OK : control panel is on and working.

Page 15: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

15

MOTOR SIGNALS

RUN — MOTOR STATUS

RUN: motor running.

STOP: motor stopped by the controls or

by the protections being triggered.

DRY RUNNING (temporary shut-down): motor temporarily stopped due to the dry running protection being triggered.

OPERATION

AUTOMATIC: motor ready to be con-

trolled by the status of the inputs.

OFF: motor stopped, regardless of the sta-

tus of the control inputs.

PERMANENT HAND: motor running,

started-up via the HAND button being briefly pressed.

TEMPORARY HAND: motor running,

started-up via the HAND button being kept pressed.

RECORDING “REC” : motor ready to be started-up to record the current reference values.

2x

1x

3x

4x

| TRIP — PROTECTION INTERVENTION due to ...

OVERLOAD: motor overcurrent.

MINIMUM LOAD: motor current lower the minimum allowed (motor uncon-nected or contactor not activated).

INVALID DATA RECORDED: incorrect current motor.

CURRENT OUT OF LIMIT (in REC) : cur-rent exceeds the operating current limits of the equipment. CURRENT VERIFICATION ERROR (in TEST): measured motor current to be different to the registered one.

INCORRECT SETTING: “REC” or “TEST” modes active for more than 90s (from pushbuttons or from “OVERLOAD” potentiometer).

SELECTORS

() J1-7 = OFF

(()) J3-1 = R (ON)

Page 16: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

16

CONTROL BUTTONS

AUTOMATIC mode selection

Start-up in HAND mode Stop

MOTOR 2 control MOTOR 1 control

AUTOMATIC

Press once

TEMPORARY HAND

OFF

PERMANENT HAND

OFF

Press once

Press once

Press once

Press once

Press once

Page 17: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

17

RECORDING “REC” BUTTONS

ALARM STATUS

An alarm on a motor can be reset by pressing the RESET button on the motor itself.

Press and hold for more than 5 seconds both the HAND—OFF  and   AUTO—RESET  

bu ons on each motor . 

ALARM RESET BUTTON

ALARM reset

Enabling / Disabling the recording “REC” function.

MOTORE 1 MOTORE 2

“REC”

OFF

OFF

“REC”

Press once

ALARM

RESET

OFF

Page 18: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

18

6.2 OPERATION MODES

Each motor set to work in this function mode is con-trolled by the status of the sensors: SL/SP 1, SL/SP 2, connected respectively to

the following inputs “S1”, “S2”, start up and shut down the motors (the inputs depend on the mod-el of equipment).

SL/SP STOP connected to the "S0" input stops the motors or enables the motors to run.

SL/SP MAX connected to the "W" input emits an alarm signal.

The “Dry Running” protection stops the motor stops the motor that detected it, if enabled and triggered.

ALTERNATE START-UP This function is only available if both motors are enabled for AUTOMATIC operation. The closing of control inputs "S1", "S2" triggers the start-up of the respective motor which, in accordance with the setting of the micro switch, can be: J1-4 (=OFF) non-alternating; rather, each in-

put controls its motor (e.g.: "S1" controls motor 1, "S2" controls motor 2). (=ON) alternating at each command from the first input that closes; rather, with the motors stopped, the closing of the first input starts up the other motor, if available. (e.g. "S1" controls one of the two motors and then "S2" controls the other motor). The first motor that starts is the last to stop. A motor that runs continuously for 12 hours is shut down to start up the other motor if it is stopped, in AUTOMATIC mode, without active alarms.

AUTOMATICO

REPLACING THE MOTOR IN PROTECTION MODE When the “Alternating start-up” function is enabled, the intervention of any of the motor’s protective devices, with the exception of the “dry running” device, starts up the other motor if it is stopped, in AUTOMATIC mode, without active alarms.

DELAYED START-UP From the closure of control inputs "S1", "S2" ... the first motor to start is started up immedi-

ately without delays; the second motor to start is started up with a

delay M2 START DLY (0—30s) set on the po-tentiometer. The motors are never started up at the same time. The events are at least 2 seconds apart, even if the delay is set to 0s.

DELAYED SHUTDOWN From the opening of control inputs "S1", "S2" ... the second motor to start is stopped immedi-

ately without delays; the second motor to start is stopped with a

delay M1 STOP DLY (0—180s) set on the po-tentiometer.

The motors are never stopped at the same time. The events are at least 2 seconds apart, even if the delay is set to 0s.

SELF HOLD Enabled via micro switch setting: J1-3 (=OFF) not enabled; rather, each "S1",

"S2" control input starts up and stops its relative motor. (=ON) enabled; rather, each "S1", "S2" control input only starts up its relative mo-tor, while shutdown is carried out only via intervention of "SO" input.

PERIODIC RELEASE OF THE IMPELLER This protects the electric pumps from a long peri-od of idleness by starting up and running the pumps for 2 seconds periodically every 48 hours. The time elapsed since the last start-up is stored internally, even in the event of a power failure, and when it returns, the count resumes as nor-mal. The function is only active in AUTOMATIC mode, therefore: A motor at a standstill when OFF is selected

on the button is excluded from the control and does not trigger release start-up.

a motor started up in MANUAL mode is not considered as a release event.

The operation modes are individual for each motor. The mode is selected via the buttons of each motor and is reflected by the light signals between the but-tons as described in the CONTROL BUTTONS and MOTOR LIGHTS paragraphs in the CONTROL PANEL chapter of this OPERATION AND USE section. The function modes are described in the following paragraphs:

AUTOMATIC PERMANENT HAND TEMPORARY HAND OFF

DESCRIPTION

Page 19: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

19

Each motor set to work in this function mode is con-trolled by the control button and status of some sen-sors: SL/SP STOP connected to the "S0" input stops

the motors or enables the motors to run. SL/SP MAX connected to "W" input, emits an

alarm signal and cannot modify motor status. The intervention of the "dry running" protection de-vice, if enabled, stops the motor that detected it. Note: 1) the PERMANENT HAND mode is the same as the

AUTOMATIC with SL/SP 1, SL/SP 2 (inputs “S1”, S2”), always closed .

2) the shutdown and restart of the motors caused by the SL/SP STOP (input “S0” is immediate for all motors (not sequential).

PERMANENT HAND 6.3 COMMON FUNCTIONS

The system controls the smooth operation and when the electric pump no longer suctions water, in accordance with the setting of the micro switch, this causes: J1-8 (=OFF) protection disabled: no action on

the motor; (=ON) protection enabled: motor stops after about 10s at start-up or after 3s dur-ing normal running. An attempt to restore a motor stopped due to protection device intervention is carried out automatically after 10 minutes. The waiting time while attempting to re-store can also be cancelled by pressing the RESET button for the relative motor. The stopping of one motor does not cause start-up of the other motor, even if availa-ble.

DRY RUNNING PROTECTION

It is possible to select the input status for which running consent of motors is given via micro switch setting: J1-1 (=OFF) input closed.

(=ON) input open.

“SO" STOP INPUT

Via micro switch J1-6 setting, the following can be signalled as an alarm: stop condition via "SO" input provided that

the "Self hold" function is excluded (J1-3=OFF).

intervention of the “Dry Running” protection. J1-6 (=OFF) no alarm signal.

(=ON) active alarm signal.

ALARM FOR STOP VIA "SO" OR VIA "DRY RUNNING" PROTECTION

It is possible to select the input status for regular operation, meaning the absence of an alarm, via micro switch setting: J1-2 (=OFF) input closed, no alarm.

(=ON) input open, no alarm. Alarm reset is performed as soon as the input is set to normal status, according to the setting described above.

"W" ALARM INPUT Each motor set to work in this function mode is stopped and cannot be started regardless of the sta-tus of the sensors.

OFF

Each motor set to work in this function mode is only controlled by the control button, whereas all the sensors connected to the inputs do not intervene on operation. The DRY RUNNING protection does not intervene and does not stop the motors even if enabled. This is useful when maintenance must be imple-mented on the system. Note: The TEMPORARY HAND mode forces the

operator to be constantly present because s/he makes the motor run regardless of the status of the sensors.

It is recommended to use the "TEMPORARY HAND" mode only if nec-essary and always when managed di-rectly by the operator.

TEMPORARY HAND

Page 20: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

20

6.4 SELECTORS AUXILIARY FUNCTIONS

SELECTOR J1

1 8 ON J1 OFF

N. Micro switch J1 Features

OFF ON

1 "SO" INPUT Contact status for running consent

Closed (NC) (*)

Open (NA)

2 "W" INPUT Contact status for regular operation

Closed (NC) (*)

Open (NA)

3 SELF HOLD enabling No (*) Yes

4 PUMP ALTERNATION enabling No Yes (*)

5 Reserved Off (*) On

6 ALARM for "SO" or "dry running" intervention No (*) Yes

7 MOTOR PROTECTION enabling No () Yes (*)

8 DRY RUNNING PROTECTION enabling No Yes (*)

The picture at the side shows the posi-tion of the micro switch.

(*) shows the factory setting of the micro switches

Selector in ON position

ON

OFF

KEY To allow for some system tuning operations, it is possible to temporarily disable motor protections such as "overload, minimum load, dry running" via micro switch setting:

J1-7 (=OFF) protections disabled: protections do not intervene for a brief amount of time (10s) from when the motor is started. Running is permitted even if nominal cur-rent registration has not been performed (see chapter COMMISSIONING, section INSTALLATION). () The OFF status of the selector is sig-

nalled by means of a single Beep. (=ON) protections enabled: protections intervene according to their set modes.

MOTOR PROTECTION ENABLING

We do not recommend excluding pro-tections. Their exclusion should last no longer than necessary for tuning and then must immediately be re-enabled. This remains the responsibility of the operator.

Selectors

J3

J1

1 ON J3 OFF

SELECTOR J3

N. Micro switch J3 Features

OFF ON

1 Reserved N (*) R (())

2 Reserved L (*) H

IMPORTANT The use of selectors is reserved;

their position must always be OFF.

Page 21: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

21

STOP DELAY 1st MOTOR — M1 STOP DELAY —

90

M1 STOP DLY

60

30

120

150

s

180 0

Determine the desired delay for stopping the first motor to be started up (0—180s).

15

M2 START DLY

10

5

20

25

s

30 0

START DELAY 2nd MOTOR — M2 START DELAY —

Determine the desired delay for starting the second motor to be started up (0—30s).

Potentiometer—reserved feature — Inom SET —

Inactive feature: Leave or bring the potentiometer to "0".

Inom SET

MAX 0

6.5 INTERNAL ADJUSTMENT POTENTIOMETERS

MOTOR OVERLOAD — OVERLOAD 1, 2 —

TEST

100

110

120

90

REC

OVERLOAD no.

130

Each potentiometer is independent and acts only on its own engine. REC: select the mode (alternative to buttons) for

recording the motor current. TEST: select the mode for comparing the detected

motor current with the one recorded. 90—130%: in normal mode, select the intervention

threshold of motor overload protection with respect to the recorded current. We recommend setting a value not less than 110%. Lower protection is achieved by setting a value between 110% and 130%. The 90% value is used only in the case of monitoring and tuning the system.

For further information, see this section in the CUR-RENT PROTECTIONS chapter.

Potentiometers

OVERLOAD 1

OVERLOAD 2

Inom SET

M1 STOP DLY

M2 START DLY

Page 22: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

22

While the recording mode is active, the motor must be started up in PERMANENT HAND mode by press-ing the HAND-OFF button of the motor in question once, briefly.

The recording process is completed in about 20 se-conds. The motor shuts down automatically. If necessary, it is possible to halt motor running be-fore the time expires, again by pressing the HAND-OFF button once, briefly. If the process has been successful, the motor indi-cator lights go off and no signal is given.

It is essential to record motor data for electrical panel operation. It is independent for each motor and consists of self learning the current and cosφ of the motor at speed and during regular operation with the electrical pan-el in “REC” recording mode. The “REC” recording stage can be activated in two ways: 1. By push buttons: When the panel is on, press

and hold both the HAND—OFF and AUTO—RESET buttons on each motor for more than 5 seconds. A double flash of the OPERATION indicator light (control panel) indicates that recording is active.

By potentiometer: When the panel is off, using the internal “OVERLOAD” potentiometer for each motor positioned in “REC” mode. Close and switch on the equipment. A double flash o f t h e “ O V E R L O A D ” indicator light indicates that recording is ac-tive (NB: the indicator light is not visible with the equipment closed). .

6.7 CURRENT PROTECTION

RECORDING MOTOR DATA “REC”

TEST

100

110

120

90

REC

OVERLOAD n

130

2x

Indicator light

Example for MOTOR 1

ATTENTION If “REC” mode has been activated using the keys, after successful recording the system exits that mode and is ready for normal operation. The OPERATION indi-cator light also goes off and no longer emits a double flash. If the “REC” function has been activated by the potentiometer, it is necessary to return it to normal operation (“100-130%”) within 90 seconds. Otherwise, the TRIP indicator light will flash 4 times …………… To exit “REC” mode, push the buttons or switch off the device or position the potentiometer correctly.

4x

2x

2 flashes 

On

2x 2 flashes only in REC by push bu ons 

Page 23: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

23

If recording has found any invalid conditions, the data in the memory will be cleared and this will be shown on the “TRIP” and/or “RUN” indicators lights for the motor in question:

Recording must therefore be repeated once the fault has been resolved. To exit “REC” mode, press the HAND-OFF and AUTO-RESET buttons again or position the potentiometer correctly.

CHECKING MOTOR DATA “TEST”

It is not normally necessary to check motor data, but this may be useful in particular cases when checking and commissioning the electrical panel. It is independent for each motor and consists of comparing the current and cosφ recorded previously with those of the motor at speed and during regular operation with the electrical panel in “TEST” mode . The “TEST” stage can only be activated:

When the panel is off, using the internal “OVERLOAD” potentiometer for each motor positioned in “TEST” mode.

Active verification is signalled by a single flash of the internal “OVERLOAD” light for the motor in question. Motor data verification is started up in the same way as recording mode, i.e.:

Starting up the motor in “PERMANENT MANU-AL” mode.

Waiting for automatic completion. Checking the absence of signals on the “TRIP”

indicator lights. Moving the potentiometer back to the normal

operation positions (“100—130%”) within 90 seconds, otherwise, the TRIP indicator light will flash 4 times ……………………………

TEST

100

110

120

90

REC

OVERLOAD n

130

1x indicator

light

If necessary, it is possible to halt motor running be-fore the time expires, again by pressing the HAND-OFF button once, briefly, but in this case, the motor data check is not performed. If verification has found any invalid conditions, this will be shown on the “TRIP” indicator lights for the motor in question:

Verification or recording must therefore be repeated once the fault has been resolved.

FAILED VERIFICATION 

“TRIP” : INCORRECT CURRENT  

The measured current is different from that recorded. 

3x

OVERLOAD PROTECTION TRIGGER THRESHOLD

Normal electrical panel operation requires the “OVERLOAD” potentiometer to be positioned at a value between 100 and 130%.

We recommend setting a value not less than 110%.

Lower protection is achieved by setting a val-ue between 110% and 130%.

The 90% value is used only in the case of monitoring and tuning the system.

When the current measured exceeds the current recorded by the set % value, the “OVERLOAD” indi-cator light flashes and when the accumulation of energy [I2t] exceeds the limit value, the overload protection device is triggered and stops the motor. The internal “OVERLOAD” and the external “TRIP” indicator lights come on.

TEST

100

110

120

90

REC

OVERLOAD n

130

indicator light

OVERLOAD PROTECTION

CURRENT THRESHOLD EXCEEDED

PROTECTION TRIGGERED

RECORDING FAILED 

“TRIP”:The measured current exceeds the opera ng current limits of the equipment. 

3x

4x

Page 24: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

24

7. ALERTS AND ALARMS

7.1 DESCRIPTION

All anomalous conditions are displayed by the warning lights of the synoptic panel and by an acoustic signal.

"SO" STOP INPUT Stop sensor status

Signal Name Description Acoustic signal

Motor shut-down

Reset operation

“STOP" SENSOR “SO" input Open (if J1-1 = OFF) Closed (if J1-1 = ON)

Yes, continue Yes Automatic when the cause of the fault disappears.

Signal Name Description Acoustic signal

Motor shut-down

Reset operation

“MAX" SENSOR “W” input Open (if J1-2 = OFF) Closed (if J1-2 = ON)

Yes, continue No Automatic when the cause of the fault disappears.

“W" ALARM INPUT Maximum Level or Maximum Pressure sensor status

7.2 SYSTEM

Signal Name Description Acoustic signal

Motor shut-down

Reset operation

ALIMENTAZIONE ASSENTE

Apparecchiatura spen-ta o non funzionante.

No Sì Automatico, al ritorno della alimenta-zione.

POWER SUPPLY Power supply status and regular functioning of the equipment.

Page 25: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

25

7.3 MOTOR

Indicator light Name Description Acoustic

signal Motor

shutdown Reset operation

DRY RUNNING Dry running condition detected.

Yes, (1) continue

Yes (2) Automatic (3)

Notes: (1) Only with a "SO" or "dry running" ALARM active (J1-6 = ON). (2) Motor temporarily stopped and waiting for a reset attempt (3) Following the waiting time for the restart attempt (10 minutes).

MARCIA — RUN — Protection against DRY RUNNING triggered

PROTECTION — TRIP — Intervention of the motor protection device due to: Faults with current or incorrect settings.

All the protection devices described in this PROTECTION — TRIP paragraph intervene for serious faults in the motor or the system, and even though manual resetting is allowed, they must be resolved by removing the cause.

Indicator light Name Description Acoustic

signal Motor shut-

down Reset operation

OVERLOAD Motor current overload. Yes, intermittent

Yes Manual (1)

MINIMUM LOAD

Motor current on all phases lower than the minimum permitted.

Yes, intermittent

Yes Manual (1)

INVALID RECORDED CURRENT

A recording must be made. (2)

Yes, intermittent

Yes Manual (1)

CURRENT OUT OF LIMIT (in REC)

The measured motor current exceeds the op-erating current limits of the equipment (3)

Yes, intermittent

Yes Manual (5)

CURRENT VERIFICATION ERROR (in TEST)

The measured motor current is different from that recorded. (4)

Yes, intermittent

Yes Manual (5)

INCORRECT SETTING

“REC” MODE (recording) or “TEST” (verification) active for more than 90s (from pushbuttons or from potentiometer “OVERLOAD”).

Yes, intermittent

Yes Manual (6)

Notes: (1) From the RESET button of the motor itself. (2) Repeat recording, leaving sufficient time (more than 5 seconds) to perform the operation. (3) Repeat recording, connecting a motor whose current is within the operating limits of the device. (4) Repeat the recording and/or check, ensuring they are performed while running at full speed and in

normal conditions. (5) Switching the device off and then back again or disabling the "REC" or "TEST" function. (6) Switching the device off and back on again after having adjusted the internal potentiometer in a

position that is different from “REC” and “TEST”.

1x

3x

4x

Page 26: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

26

Blank page

Page 27: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for

27

8. QUICK INFO

Initial status Button control Operating

status Button control Final status

Press once AUTOMATIC Press once

OFF

Press once PERMANENT MANUAL Press once

Keep pressed TEMPORARY

MANUAL Release

>5s REC >5s

ALARM Press once

OFF

8.2 Controls

No. Function OFF ON

5 Inactive Off (*) On

6 "SO", dry running ALARM No (*) Yes

7 MOTOR PROTECTION No () Yes (*)

8 DRY RUNNING No Yes (*)

No. Function OFF ON

1 "SO" Status c/e/ contact for running consent

Closed (NC) (*)

Open (NA)

2 “W" Status de/ contact for regular operation

Closed (NC) (*)

Open (NA)

3 SELF HOLD No (*) Yes

4 PUMP ALTERNATION No Yes (*)

8.3 Selector J1 — Features

(*) factory setting

8.1 Signals

POWER SUPPLY

OK

“MAX” (W)

“MAX”

“STOP ” (S0)

“STOP”

|TRIP — MOTOR PROTECTION

OVERLOAD

MINIMUM LOAD

INVALID RECORDED CURRENT CURRENT LIMIT EXCEEDED (in

REC) INCORRECT CURRENT TEST (in

TEST)

INCORRECT SETTING

1x

3x

4x

RUN — MOTOR STATUS

GEAR

STOP

DRY RUNNING

2x

OPERATION

AUTOMATIC

OFF

PERMANENT MANUAL

TEMPORARY MANUAL

“REC” RECORDING

Type of sound emitted

Continuous

| Intermittent

() 1 Beep

(()) 2 Beeps

SELECTORS

() J1-7 = OFF

(()) J3-1 = R (ON)

Page 28: CONTROL PANELS for 2 series ELECTRIC PUMPS · control panels for 2 q2p series electric pumps q2pme16ei q2pte08ei . 2 1. warnings ... dry running protection "so" stop input alarm for