control of power systems (1)

Upload: tahiratasneem

Post on 04-Jun-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Control of Power Systems (1)

    1/43

    Control ofPower Systems

    Prepared ByA K K Tahira Tasneem

    Assistant Professor - EEE

  • 8/13/2019 Control of Power Systems (1)

    2/43

    Outline Review of AGC and reactive power control System operating states by security control

    functions Monitoring, evaluation of system state by

    contingency analysis Corrective controls (Preventive, emergency and

    restorative) Energy control center SCADA system Functions monitoring , Dataacquisition and controls EMS system .

  • 8/13/2019 Control of Power Systems (1)

    3/43

    Review of AGC and reactive

    power control Modern implementation of automaticgeneration control (AGC) schemes usuallyconsists of a central location whereinformation pertaining to the system istelemetered.

    Control actions are determined in a digital

    computer and then transmitted to thegeneration units via the same telemetrychannels.

  • 8/13/2019 Control of Power Systems (1)

    4/43

    To implement an AGC system1. Unit megawatt output for each committed

    unit.

    2. Megawatt flow over each tie line toneighboring systems.3. System frequency.

  • 8/13/2019 Control of Power Systems (1)

    5/43

    The use of digital telemetry is becomingcommonplace in modern systems whereinsupervisory control.

    That is opening and closing substationbreakers, telemetry information and controlinformation (i.e) unit raise/lower is all sent viathe same channels.

  • 8/13/2019 Control of Power Systems (1)

    6/43

    The basic reset control loop for a unit consistsof an integrator with gain K

    Basic generation control loop.

  • 8/13/2019 Control of Power Systems (1)

    7/43

  • 8/13/2019 Control of Power Systems (1)

    8/43ACE calculation.

  • 8/13/2019 Control of Power Systems (1)

    9/43Overview of AGC logic.

  • 8/13/2019 Control of Power Systems (1)

    10/43

    AGC Features

    Assist action Filtering of ACE Telemetry failure logic Unit control detection Ramp control Rate limiting Unit control modes

  • 8/13/2019 Control of Power Systems (1)

    11/43

  • 8/13/2019 Control of Power Systems (1)

    12/43

    Normal

    EmergencyExtremis

    AlertRestorative

    Restart

    Resynchronisation

    Preventive Control

    Emergency Control

    E,I

    ,I E,I

    E , ,

    E Equality Constraint: I Inequality Constraints and - Negation

  • 8/13/2019 Control of Power Systems (1)

    13/43

    Normal State The system is, for most of the time, in its

    normal state. Frequency and Voltages are kept at rated or

    prescribed values.

    Real and Reactive power demanded by theloads match with the output of sources. E Equality

    I

    Inequality

    Loading of generators,transformers or transmission line is with intheir rating or capacity limits.

  • 8/13/2019 Control of Power Systems (1)

    14/43

    Alert State

    If the capacity margin below the thresholdvalue or if a disturbance occurs, the securitylevel is reduced and the system enters alertstate.

    All equalities and inequalities aremaintained.

    The system operates fully synchronized. Preventive control actions need to be

    initiated to restore reserve margin.

  • 8/13/2019 Control of Power Systems (1)

    15/43

    Emergency State Second contingency occurs before

    preventive action is effected. It may reached directly from normal state,

    if the original disturbance is more severe. The generation still tracks the load and the

    system remains synchronized. It is most urgent that the system be

    returned to a normal or at least alert state.

  • 8/13/2019 Control of Power Systems (1)

    16/43

  • 8/13/2019 Control of Power Systems (1)

    17/43

    Contingency Analysis To predict the effect of outages, contingency

    analysis techniques are used.

    Single line failure, multiple equipmentfailure and all possible outages are studied.

  • 8/13/2019 Control of Power Systems (1)

    18/43

  • 8/13/2019 Control of Power Systems (1)

    19/43

    Energy Control Centers

    The energy control center (ECC) hastraditionally been the decision-center for the

    electric transmission and generationinterconnected system. Minute-by-minute physical and economic

    operation of the power system.

  • 8/13/2019 Control of Power Systems (1)

    20/43

    In the continental U.S., there are only three

    interconnected regions:1. Eastern,2. Western, and

    3. Texas, But there are many control areas , with each

    control area having its own ECC.

  • 8/13/2019 Control of Power Systems (1)

    21/43

    Maintaining integrity and economy of aninter-connected power system requiressignificant coordinated decision-making.

    So one of the primary functions of the ECCis to monitor and regulate the physicaloperation of the interconnected grid.

    Two-level hierarchy of ECCs Independent System Operator (ISO) - high-

    level decision-making. The transmission owner ECC - lower-level

    decision-making.

  • 8/13/2019 Control of Power Systems (1)

    22/43

    High-level view of the ECC

    27

    Substation

    Remoteterminalunit

    SCADA Master Station

    C o m m u n i c a t

    i o n

    l i n

    k

    Energy control center with EMS

    EMS alarm displayEMS 1-line diagram

    ECC C t

  • 8/13/2019 Control of Power Systems (1)

    23/43

    ECC Components

    SCADA

    Overloads &Voltage Problems

    PotentialOverloads &

    Voltage Problems

    Breaker/Switch StatusIndications

    System Model Description

    Telemetry &Communications equipment

    StateEstimator

    NetworkTopology

    program

    AGC

    EconomicDispatch

    Calculation

    OPF

    ContingencySelection

    Contingency AnalysisSecurityConstrained OPF

    Display Alarms

    Updated SystemElectrical Model

    Analog Measurements

    Display to Operator

    Power flows,Voltages etc.,

    Display to Operator

    Bad MeasurementAlarms

    Generator OutputsGenerationRaise/Lower Signals

    State EstimatorOutput

    SubstationRTUs

  • 8/13/2019 Control of Power Systems (1)

    24/43

    The system control function traditionally used inelectric utility operation consists of three mainintegrated subsystems:

    The energy management system (EMS)

    The supervisory control and data acquisition(SCADA), and

    The communications interconnecting the EMSand the SCADA.

  • 8/13/2019 Control of Power Systems (1)

    25/43

    SCADA system

    Supervisory control indicates that theoperator, residing in the energy controlcenter (ECC), has the ability to controlremote equipment.

    Data acquisi tion indicates that informationis gathered characterizing the state of the

    remote equipment and sent to the ECC formonitoring purposes.

  • 8/13/2019 Control of Power Systems (1)

    26/43

    A SCADA system performs four functions:1. Data acquisition

    2. Networked data communication3. Data presentation4. Control

  • 8/13/2019 Control of Power Systems (1)

    27/43

    These functions are performed by four kinds of SCADAcomponents:

    1. Sensors (either digital or analogue) and control relays thatdirectly interface with the managed system.

    2. Remote telemetry units (RTUs). These are smallcomputerized units deployed in the field at specific sites andlocations. RTUs serve as local collection points for gatheringreports from sensors and delivering commands to controlrelays.

    3. SCADA master units. These are larger computer consolesthat serve as the central processor for the SCADA system.Master units provide a human interface to the system andautomatically regulate the managed system in response tosensor inputs.

    4. The communications network that connects the SCADAmaster unit to the RTUs in the field.

  • 8/13/2019 Control of Power Systems (1)

    28/43

    The monitoring equipment is normally locatedin the substations and is consolidated in theremote terminal unit (RTU).

    The RTUs are equipped with microprocessorshaving memory and logic capability.

    Newer RTUs generally have intranet orinternet capability.

    Relays located within the RTU, on command

    from the ECC, open or close selected controlcircuits to perform a supervisory action.

  • 8/13/2019 Control of Power Systems (1)

    29/43

  • 8/13/2019 Control of Power Systems (1)

    30/43

    Such supervisory actions are Opening or closing of a circuit breaker or

    switch Modifying a transformer tap setting Raising or lowering generator MW output

    or terminal voltage Switching in or out a shunt capacitor or

    inductor The starting or stopping of a synchronous

    condenser.

  • 8/13/2019 Control of Power Systems (1)

    31/43

    Information gathered by the RTU andcommunicated to the ECC includes both analoginformation and status indicators.

    Analog information includes Frequency, Voltages, Currents, and Real and Reactive power flows.

    Status indicators include Alarm signals (over-temperature, low relay battery

    voltage, illegal entry) Whether switches and circuit breakers are open or

    closed. Information is provided to the ECC through a

    periodic scan of all RTUs.

  • 8/13/2019 Control of Power Systems (1)

    32/43

    Communication technologies

    The form of communication required for SCADAis telemetry .

    Telemetry may be analog or digital.

    In analog telemetry, a voltage, current, orfrequency proportional to the quantity beingmeasured.

    In digital telemetry, the quantity being measured

    is converted to a code in which the sequence ofpulses transmitted indicates the quantity.

  • 8/13/2019 Control of Power Systems (1)

    33/43

    Block Diagram of Telemetering System

    Quantity to be

    telemetered

    Transducer A/Dconverter

    Telemetertransmitter

    Telemeterreceiver

    Computer

    D/Aconverter

    Indicatingmeter

    Recordingmeter

    Signal circuit (wire line,PLC, microwave, etc.)

  • 8/13/2019 Control of Power Systems (1)

    34/43

    Energy Management System (EMS)

    The EMS is a software system. Most utility companies purchase their EMS

    from one or more EMS vendors.

    These EMS vendors are companies specializingin design, development, installation, andmaintenance of EMS within ECCs.

  • 8/13/2019 Control of Power Systems (1)

    35/43

    Industrial for Power EMSElectrical ProcessSystem configurationFunctionality Power EMSReferencesBenefits

  • 8/13/2019 Control of Power Systems (1)

    36/43

    Critical LoadsLimited In-plant GenerationInsufficient reliability of Public Grid

    Why Power EMS?

    Load Shedding} Several GeneratorsContracted Power Importation Power Control} Different Electrical OperationalConfigurations possible Mode Control} Complex Distribution Networks

    Local only Control facilities SCADA

    } P EMS S O i

  • 8/13/2019 Control of Power Systems (1)

    37/43

    Fast Functions are performed by Controllers:

    Load Shedding / Re-Acceleration / Re-StartingPower Control

    Mode Control

    MCC

    A B B T r a n s m i t OyN e tw o r k P a r tn e r

    FEEDER TERMINAL REF541A B B N e t w o r k P a r t n e r

    Uaux =80. .. 265Vdc/ acfn =50HzIn =1/ 5A ( I)

    1MRS xxxxxx98150Un= 100/ 110V (U)

    Uon= 100/ 110V ( Uo)

    Ion= 1/ 5A (I o)

    9509

    A B B T r a n s m i t O yN e tw o r k P a r tn e r

    FEEDER TERMINAL REF541A B B N e t w o r k P a r t n e r

    Uaux =80. .. 265Vdc/ ac

    fn =50HzIn =1/ 5A ( I)

    1MRS xxxxxx

    98150Un= 100/ 110V (U)Uon= 100/ 110V ( Uo)

    Ion= 1/ 5A (I o)

    9509

    Substation N

    S800 I/O

    Serial links to AVR

    Serial Links to Emergency Diesel GeneratorSerial links to Governor

    A B B T r a n s m i t O yN e tw o r k P a r tn e r

    FEEDER TERMINAL REF541A B B N e t w o r k P a r t n e r

    Uaux = 80. . .265Vdc/ acf n=50HzI n= 1/ 5 A( I )

    1MRS xxxxxx98150Un = 100/ 110V ( U)

    Uon =100/ 110 V( Uo)

    Ion =1/ 5A ( Io)

    9509

    A B B T r a n s m i t O yN e tw o r k P a r tn e r

    FEEDER TERMINAL REF541A B B N e t w o r k P a r t n e r

    Uaux = 80. . .265Vdc/ ac

    f n=50HzI n= 1/ 5 A( I )

    1MRS xxxxxx

    98150Un = 100/ 110V ( U)Uon =100/ 110 V( Uo)

    Ion =1/ 5A ( Io)

    9509

    ACS 601

    TCP/IP Network

    X-terminals(Process DCS)

    Power EMS System Overview

    Control IT

    Substation 2Substation 1 Substation Z

    Operate IT Engineering IT

  • 8/13/2019 Control of Power Systems (1)

    38/43

    Functionality Power EMS

    Load Shedding Active and Reactive Power Control Supervision, Control and Data Acquisition

    (SCADA) Mode Control

    Re-Acceleration / Re-Starting Synchronisation

  • 8/13/2019 Control of Power Systems (1)

    39/43

    Load Shedding

    Functionality Power EMS

    ?

    Without Load SheddingWith Load Shedding

  • 8/13/2019 Control of Power Systems (1)

    40/43

    Load Shedding: The types

    Fast Load Shedding on Loss of PowerResources

    Load Shedding on Frequency Drop Slow Load Shedding on Overload Slow Load Shedding for Peak Shaving

    Manual Load Shedding

  • 8/13/2019 Control of Power Systems (1)

    41/43

  • 8/13/2019 Control of Power Systems (1)

    42/43

  • 8/13/2019 Control of Power Systems (1)

    43/43

    Thank You