contactor vs circuit breaker
DESCRIPTION
Vacuum Contactor, Vacuum Circuit BreakerTRANSCRIPT
points to be considered while selecting the appropriate bypass device for soft starter [ for medium
voltage application ]
Sr.
No.
Parameter Vacuum contactor Vacuum circuit breaker
1 Fault level Up to 9 KA only, not suitable for line
side application due to fault level
limitation.
Upto 63 KA, typically 25 KA, suitable
for line side soft starter application.
2 Max. current
carrying
capacity
Max 400 A available Up to 1600 A, typically 630-1250 A
3 Closing and
tripping
mechanism
Solenoid operated, unreliable due to
dependency upon external
parameters wiz. control supply
quality, voltage dip due to heavy
switching solenoid current.
Motor + spring charged operated,
guaranteed performance independent
of external parameters
4 Aux. contacts Limited due to small size and weak
mechanism of solenoid operated
armature
Flexible and reliable due to strong
mechanism, typically more number of
contacts available
5 Closing time 70mS 40mS
6 Tripping time 50mS 10mS
8 Contact travel 4-5 mm 7-8 mm
9 No of
consecutive
operation
5, limited by thermal capacity of
solenoid coils
25, limited by charging motor duty
10 Documented
total number of
operation
10,00,000 for vacuum bottles,
replace bottles after 10,00,000
operations
20,00,000 for vacuum bottles,
Service breaker every after 1,00,000
operations for spring charging
mechanism
11 Availability and
makes
Local makes available with no service
guarantee
Jayashree make [ manufacturing
outsourced tested and monitored by
Jayashree ] provided long service
support [ design life cycle planned up
to year 2025 ]