CONSULTANTS’ DAY
Hosted by DNR’s Remediation & Redevelopment Program
20 15
Site Investigations: Common Mistakes and Helpful Hints
Terry Evanson, Hydrogeologist Wisconsin DNR
Vapor Intrusion
![Page 2: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/2.jpg)
• Conceptual Site Model: – Do your facts fit your story?
• Screening the PVI pathway: – When is a full investigation needed?
• Sub-slab sampling: – Why not just test indoor air?
• Vapor mitigation: – OMM: who’s responsibility?
Key Points
![Page 3: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/3.jpg)
Sleuthing for Vapors
![Page 4: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/4.jpg)
Sleuthing for Vapors
![Page 5: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/5.jpg)
CSM Guides Investigation
Develop initial CSM
Conduct Investigation
Update CSM
Add’l data needs?
Remedial Action or assess for closure
No
Yes
• Plan investigation based on site-specific conditions
• Collect data to characterize site and to assess vapor pathway (soil gas, sub-slab vapor, etc.)
• Refine CSM • Update CSM. If
necessary, collect more data.
![Page 6: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/6.jpg)
![Page 7: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/7.jpg)
Screening/Investigating Petroleum VI
Screen using RR-800
No PVI Risk Depth to ground-water
1External soil gas samples
2Sub-slab samples
1 O2, CO2, CH4, LEL usually collected 2 O2, CO2, CH4, LEL + Summa Canister for PVOC; others if needed (1,2-DCA) 3 Low O2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10%
3 Low O2, high CO2/CH4/LEL
High O2, low CO2/CH4
/LEL
Mitigate Vapor > VRSL
Fail 1 or more criteria
Vapor < VRSL
![Page 8: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/8.jpg)
Separation Screening Distances Petroleum VI Risk
Screening Criteria RR-800 ITRC PVI Guidance
NAPL, horizontal distance from foundation 30 feet 30 feet NAPL, vertical distance from foundation 30 feet 15 feet Benzene dissolved in groundwater > 1ppm 20 feet 5 feet
Aerated / biologically active soil zone around foundation 5 feet 5 feet
![Page 9: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/9.jpg)
• Identify where vapors pose a risk to a building
• Indoor air alone not adequate to ID vapor intrusion
• External soil gas sampling can mislead conclusion of risk
• Proper management of building in the future
Why Sub-slab Samples?
![Page 10: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/10.jpg)
Sub-Slab Vapor Sampling Procedures
RR-986, Sub-Slab Vapor Sampling Procedures
![Page 11: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/11.jpg)
• When should multiple sub-slab sampling rounds* be collected? –Residential – in most situations –Commercial – depends on use –Industrial – if HPV method used,
one round sufficient
*RR-986, Sub-slab Vapor Sampling Procedures
Sub-Slab Vapor Sampling Procedures
![Page 12: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/12.jpg)
• VMS almost always installed in residential settings
• Commercial/industrial settings. If VMS NOT proposed: –Justify alternative approach –Additional data usually needed
Responding to Sub-slab VRSL Exceedance
![Page 13: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/13.jpg)
• Hire contractors experienced in vapor mitigation
• Design system prior to installation –Single family homes vs.
commercial/industrial • Document system performance
Vapor Mitigation Systems
![Page 14: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/14.jpg)
• RP’s responsibility for vapor mitigation systems (VMS) found in NR 724 – Design, implementation,
operation, maintenance and monitoring requirements
*Summary of Changes to the ch. NR 700 Series of Administrative rules (RR-965) http://dnr.wi.gov/files/PDF/pubs/rr/RR965.pdf
Vapor Mitigation Systems and OMM Responsibilities
![Page 15: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/15.jpg)
• Notification of Property Owners –Provide adequate information
early in process to property owners re: expected long-term OMM responsibilities
Vapor Mitigation Systems and OMM Responsibilities
![Page 16: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/16.jpg)
• Does the existing parking structure protect the VI pathway? DO NOT assume it does. – Ventilation rate – Control of the ventilation system – Pressure difference between garage
& occupied space – Elevator shafts
Existing Underground Parking Garages & Vapor Assessment
![Page 17: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/17.jpg)
• VI Internet page • RR-800, Addressing VI at
Remediation & Redevelopment Sites in WI
• RR-986, Sub-slab Vapor Sampling Procedures
Guidance Documents Relevant to VI
![Page 18: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/18.jpg)
• Conceptual Site Model: – Update with new data
• Screening the PVI pathway: – Majority of sites will not pose VI risk
• Sub-slab sampling: – Critical to identify buildings at risk of VI
• Vapor mitigation: – Plan & implement OMM from beginning
Summary of Key Points
![Page 19: CONSULTANTS’ DAY 2015...2 < 5% ; high CH4 ≥ 0.5%; LEL ≥ 10% 3 Low O 2, high CO 2 /CH 4 /LEL High O 2, low CO 2 /CH 4 /LEL Mitigate Vapor > VRSL Fail 1 or more criteria](https://reader033.vdocuments.site/reader033/viewer/2022043014/5fb0cc637600150585710caf/html5/thumbnails/19.jpg)
Thank you for attending Consul tants’ Day
Questions & Contacts