considerations for mv plant cables -...
TRANSCRIPT
PD Testing
Considerations for MV Plant Cables
Cable Aging Management- SLIDE 2
Cable Testing Philosophy
Manu-facturing
Dam
age
Mis
take
Rep
air
Agin
g
Acce
ptan
ce
Test
ing
Mai
nten
ance
Te
stin
g
Trans-portation
In- stallation
Fact
ory
Test
ing Power
frequency 50/60 Hz
Operation Power frequency 50/60 Hz
Cable Aging Management- SLIDE 3
Various Manufacturing Defects
1. Cavity at shield 2. Cavities due to shrinkage or
gas-formation in insulation 3. Defects in the insulation
shield 4. Loosely bound solid particles
5. Protrusions 6. Splinters 7. Fibers 8. Contaminants in the
insulation shield
Cable Aging Management- SLIDE 4
Electrical Trees (XLPE)
• Often begins near – Protrusions at the
shield – Protrusions at the
conductor – Near impurities – At water trees
• Two Types – Branch type trees – Bush type trees
Cable Aging Management- SLIDE 5
Partial Discharge Theory
rRx
xEE
rRx
xE
void
ln
121
3
)(21
3
ln
1)(
εε
εε
+=
+=
=
5 © Kinectrics Inc., 2011
Cable Aging Management- SLIDE 6
Electrical Field Conditions
-6
-4
-2
0
2
4
6
0 45 90 135 180 225 270 315 360
Phase Angle
Vo
ltag
e/E
lect
ric
Fie
ld
Appl. Voltage [kV]
Background Field [kV/mm]
Void Breakdown Strength
Void Field [kV/mm]
Partial Discharge Theory
Cable Aging Management- SLIDE 7
Partial Discharge Theory Electrical Field Conditions
-20
-15
-10
-5
0
5
10
15
20
0 45 90 135 180 225 270 315 360
Phase Angle
Vo
ltag
e/E
lect
ric
Fie
ld
Appl. Voltage [kV]
Background Field [kV/mm]
Void Breakdown Strength
Void Field [kV/mm]
Initial Discharge
Return Discharge Second
Discharge
Cable Aging Management- SLIDE 8
Partial Discharge Theory Electrical Field Conditions
-40
-30
-20
-10
0
10
20
30
40
0 45 90 135 180 225 270 315 360
Phase Angle
Vo
ltag
e/E
lect
ric
Fie
ld
Appl. Voltage [kV]
Background Field [kV/mm]
Void Breakdown Strength
Void Field [kV/mm]
Cable Aging Management- SLIDE 9
PD Testing
• Diagnostic Test • Can be performed on-line or off-line • With respect to commissioning testing often performed either
during a HiPot test or after HiPot test • Should preferably be done at..
– At near power frequency – Elevated voltages to identify problem prior to in-service
failure • Most PD monitors require experts for operation and data
interpretation ⇒ expert test • No standard for field PD testing – (IEEE 400.3 is a guide) • Should be performed by independent third party
© Kinectrics
Cable Aging Management- SLIDE 10 © Kinectrics Inc., 2008
Electrical Trees (XLPE)
Cable Aging Management- SLIDE 11
PD Theory: Apparent Charge Apparent Charge at discharge location
Measured Apparent Charge
R
C
VPD
iPD
iPD
VPD
R
Measured Apparent
Charge
Attenuation Attenuation
VPD
R
© Kinectrics
Cable Aging Management- SLIDE 12
TDR on Tape Field Cable
Cable Aging Management- SLIDE 13
Cable Testing Philosophy
Manu-facturing
Dam
age
Mis
take
Rep
air
Agin
g
Acce
ptan
ce
Test
ing
Mai
nten
ance
Te
stin
g
Trans-portation
In- stallation
Fact
ory
Test
ing Power
frequency 50/60 Hz
Operation Power frequency 50/60 Hz
Cable Aging Management- SLIDE 14
Acceptance & Maintenance Tests
Types of Tests • Soaking • DC HiPot Testing • AC HiPot Testing • VLF Testing • Damped AC • Partial Discharge
Testing
Standards • IEC 60502, IEC 60840,
IEC 62067
Guides • IEEE 400
– 400.1 DC Testing – 400.2 VLF Testing – 400.3 PD Testing – 400.4 Damped AC – 400.5 AC Withstand
• Cigre 182 • Cigre 279
Cable Aging Management- SLIDE 15
VLF Testing
Pros • Inexpensive compared to AC
HiPot Non-Resonant testing • Effective in finding watertree’d
cable for field aged, distribution class cables
• Easy to perform • Non-expert test • IEEE Std 400.2
Cons • Still discussion on test levels versus
test time • Issues with charge injection and
trapped charge when testing at frequencies less than 0.1 Hz
• Not as effective in finding weak spots in the insulation as a conventional AC HiPot.
• Voltage wave may not be sinusoidal (depends on test kit).
• Not straight forward to interpret PD data acquired during VLF conditions
• Research still to be done on the effectiveness in detecting, for instance, interfacial phenomena
After-laying field tests
15 © Kinectrics Inc., 2011
Cable Aging Management- SLIDE 16
VLF vs. AC Testing After-laying field tests
-1
-0.5
0
0.5
1
0 1 2 3 4 5 6 7 8 9 10
-1
-0.5
0
0.5
1
0 1 2 3 4 5 6 7 8 9 10
0.1HZ
20HZ
16 © Kinectrics Inc., 2011
-1
-0.5
0
0.5
1
0 1 2 3 4 5 6 7 8 9 10
60HZ
Cable Aging Management- SLIDE 17
VLF vs. AC Testing Withstand Voltage of XLPE Cables
17 © Kinectrics Inc., 2011
Cable Aging Management- SLIDE 18
VLF vs. AC Testing
Withstand Voltage of XLPE Cables
VLF AC Withstand
Waveform Cable System Rating ( φ-φ)
Installation (φ-∅)
Acceptance ((φ-∅))
Maintenance (φ-∅)
Acceptance (φ-∅)
Maintenance (φ-∅)
[kV] [kV rms] [kV rms] [kVrms] [kVrms] [kVrms]
Sinusoidal
5 9 10 7 13 9 8 11 13 10
15 19 21 16 26 23 25 291 32 241 28 32 361 27 42 36 35 39 44 33 46 51 57 43 67 58 69 75 84 63 72
Cable Aging Management- SLIDE 19
AC HiPot Testing
• Stipulated in IEC 60502 (MV), IEC 60840 (HV) and IEC 62067 (EHV) as well as most cable testing standards
• Testing at power frequency from 20 Hz to 300 Hz • Recommended high potential test level for acceptance testing
ranges from 1.25U0 to 2U0 but typically 1.7U0. • High potential voltage applied for 60 minutes • AC HiPot testing is gaining ground in Europe and North-
America • Proven test methodology for identifying installation related
defects.
19 © Kinectrics Inc., 2011
Cable Aging Management- SLIDE 20
AC HiPot Testing Pros • Proven test methodology;
test levels and duration well established
• Based on IEC standards • Reliable equipment
available. • Decades of experience with
tests • Can perform PD testing
during AC HiPot tests • Gets ‘soft’ failure so
meaningful forensics can be performed
Cons • Not a diagnostic test • Requires heavy equipment • Not necessarily cheap
20 © Kinectrics Inc., 2011
Cable Aging Management- SLIDE 21
The Phenomenon of Resonance
iR
iC
iL
L R
CCable
Cable Aging Management- SLIDE 22
MV Test Spec (Plant Cables)
Equipment
Rated Voltage
(kV)
AC Testing DC Testing Hipot Test Partial Discharge Test
Test Level (kV)
Time (mins)
Extinction Level (kV)
Allowable Pulse Mag. (pC)
Time (mins)
Test Level (kV)
Time (minutes)
Power Cable
Unshielded:
Shielded: (including cable bus)
Bus Duct
Isolated Phase Bus
Metal-Enclosed Rigid
Switchgear
4.16
4.16 8
13.8
25
13.8
4.16
13.8
N/A
9 (13) 13 (18) 19 (27)
45 (60)
27 (36)
14 (19)
27 (36)
N/A 5 5 5 1 1 1 1
N/A
4.5 (4.5) 7.5 (7.5) 13 (13)
19
10.5 (10.5)
3.5 (3.5)
10.5 (10.5)
N/A
3 (3) 3 (3) 3 (3)
100
100 (100)
100 (100)
100 (100)
N/A
2 2 2
2
2
2
2
25 (35)
25 (35) 35 (45) 55 (70)
64
38 (50)
N/A
N/A
5
15 15 15
1
1
N/A
N/A
Cable Aging Management- SLIDE 23
PD Interpretation Criteria Comm. Testing (Off-Line) • Measure PDIV, PDEV • Measure PD Level & Intensity • Identify signature partial
discharge pattern • Identify location of partial
discharge source ⇒ Guiding criterion is that the
cable system should be PD free at the specified test voltage at commissioning fro HV &EHV systems
⇒ Less then 3pC or 3pC for MV systems using conventional systems
Maintenance Testing (On-Line) • Assess individual PD sources
separately • Identify location of partial
discharge source • Assess impact of individual PD
sources (insulation materials, experience)
⇒ Develop individual assessment/ranking of joints and cable sections
23 © Kinectrics Inc., 2011
Cable Aging Management- SLIDE 24
PD Testing
Pros • Can help identify insulation
defects which does not cause failure during an AC HiPot test
• Can use external, non-invasive sensors
• Can be performed continuously at each accessory using daisy chained PD systems
Cons • No standard or acceptance
criteria • For long lengths of cable a
distributed PD measurement should be performed (at each accessory)
• Requires an expert to perform the test and evaluate the data
• Cannot compare factory PD tests to field tests
• May be practically difficult to perform (manhole access, traffic control)
Cable Aging Management- SLIDE 25
Off-Line vs. On-Line
Off-Line • Requires cable disconnected and
cable conductors exposed. • Requires external power source • Done at elevated voltage • Can perform meaningful
sensitivity assessment • Can measure PDIV, PDEV • For cross-bonded cable systems,
SVLs must be shorted and, preferably, the cross links removed thus creating a continuous sheath
On-Line • Non-invasive test • Done at rated voltage • PDIV and PDEV cannot be
measured • Often, multiple PD sources from
various types of HV equipment are detected
• Can only detect sources present at the time of testing!
• Can be performed continuous over long lengths of time thus characterizing the dynamic PD behaviou
© Kinectrics
Cable Aging Management- SLIDE 26
PD Monitors
Measurement Parameters • Magnitude • Phase Angle ⇒ Derive pulse count
rate • Signal Shape
Types of Monitors • Traditional PD
Monitors • Conventional PD
Monitors • Modern Partial
Discharge Monitors
© Kinectrics
Cable Aging Management- SLIDE 27
AC HiPot & Conv. PD Testing
Cable Aging Management- SLIDE 28
Broad Band PD Measurements
Cable Aging Management- SLIDE 29
HFCT For Voltage Reference LFCT For Voltage Reference
Sensor Connections
Cable Aging Management- SLIDE 30
AC HiPot & Unconv. PD Testing
• The frequency content of a partial discharge pulse depends on… – Duration
• Strength of the electrical field
• Length of the partial discharge it self
– Pulse propagation path
⇒ different PD sources have different frequency content
Cable Aging Management- SLIDE 31
• Off-line Hi-Pots (ac, VLF)
Dielectric loss measurements
Partial Discharge testing
Cable Aging Management- SLIDE 32
Summary of Partial Discharge Data
Cable ID (Phase) AC Hipot DIV (kV) DEV (kV) PD @ 13 kV (pC) 2ENA02NC1-AA/AG (Red) 2ENA02NC1-AA/AG (Black) 2ENA02NC1-AA/AG (Blue)
Passed Passed Passed
10.8 16.8 13.9
10.6 16.1 13.7
185 0 0
2ENA02NC1-AB/AH (Red) 2ENA02NC1-AB/AH (Black) 2ENA02NC1-AB/AH (Blue)
Passed Passed Passed
11.9 17.5 16.5
10.7 16.0 15.0
190 0 0
2ENA02NC1-AC/AI (Red) 2ENA02NC1-AC/AI (Black) 2ENA02NC1-AC/AI (Blue)
Passed Passed Passed
18.9 >19 14.2
17.3 >19 13.4
0 0 0
2ENA02NC1-AD/AJ (Red) 2ENA02NC1-AD/AJ (Black) 2ENA02NC1-AD/AJ (Blue)
Passed Passed Passed
15.7 11.6 16.8
14.8 11.2 15.4
0 330 0
2ENA02NC1-AE/AK (Red) 2ENA02NC1-AE/AK (Black) 2ENA02NC1-AE/AK (Blue)
Passed Passed Passed
>19 >19 >19
>19 >19 >19
0 0 0
2ENA02NC1-AF/AL (Red) 2ENA02NC1-AF/AL (Black) 2ENA02NC1-AF/AL (Blue)
Passed Passed Passed
>19 18.6 17.7
>19 18.0 16.1
0 0 0
Cable Aging Management- SLIDE 33
Example 1: On-Line PD • 142 circuits of single conductor 5 kV
EPR
• 19 years to 21 years old
• All cables feeding 4.2 kV induction motors
Cable Aging Management- SLIDE 34
Example 1: On-Line PD (5kV)
• Partial discharge activity detected through out the system • However, of 142 cables, only 7 subjected to partial discharge
activity from the cable system it self – In one case, partial discharge activity was detected from a cable splice – The remaining six cases related to tracking along cable termination
surfaces
• The remaining discharge activity detected originated from the 4.2 kV induction motors, the bus system or other connected HV equipment
Cable Aging Management- SLIDE 35
Example 2: On-Line PD (27.5)
• Industrial client • 42 cable sections, 27.5 kV XLPE • 12 years old • Cable circuit constitute single supply line to the plant
⇒ crucial to avoid unforeseen failure • On-line partial discharge measurements performed
routinely as a maintenance test
Cable Aging Management- SLIDE 36
Example 2: On-Line PD (27.5)
Cable Aging Management- SLIDE 37
Ex 3: Periodic/Remote Monitoring
• Custom made sensor – Cable length – Cable specifications
• Non-invasive install, can be performed live
• Connected to termination box
Cable Aging Management- SLIDE 38
Ex 3: Periodic/Remote Monitoring
Cable Aging Management- SLIDE 39
Ex 3: Periodic/Remote Monitoring
• Permanent installation at substation
• 1 day installation • Suspected faulty
equipment • PD measured from
vacuum bottle • Verified during
subsequent off-line testing
PROCESSING
Cable Aging Management- SLIDE 40
Remote Monitoring Setup – Example 1
Cable Aging Management- SLIDE 41
Cable Testing also involves… Being nice to stray doggies at work sites - even while you’re busy!
“The greatness of a nation and its moral progress can be judged by the way its animals are treated.. I hold that, the more helpless a creature, the more entitled it is to protection by man from the cruelty of man" - Mahatma Gandhi (1869 - 1948)
Cable Aging Management- SLIDE 42
Contact information
Terry Herrmann Structural Integrity Associates [email protected] (303) 542-1415 Steve Biagiotti Structural Integrity Associates [email protected] (303)542-1402 www.structint.com
Rick Easterling Kinectrics [email protected]
(804) 550-3109
Mark Fenger Kinectrics [email protected]
(416) 300-8464
Howard Sedding Kinectrics [email protected]
(416) 207-6000 x6172
www.kinectrics.com