configurable cross-flow heat recovery … · single phase (cadb) ... configurable cross-flow heat...

26
Heat recovery units CADB/T-D Heat recovery units housed in galvanised steel boxes, white plastic coated, with a 25 mm thick double wall, class M0 fire proof thermal and acoustic insulation, configurable inlets and outlets, versions for horizontal installation and for vertical installation, intakes with a hermetic seal, F7 filter for inlet air and G4 filter for air extraction. With two double inlet centrifugal fans with built- in motor. CADB/T-D DP25 F7 Series Heat recovery without additional heat added. CADB/T-DI DP25 F7 Series Heat recoveries with a heating resistance. CADB/T-DC DP25 F7 Series Heat recoveries with a built-in hot water coil. Motors IP20, Class F (ranges 05, 08, 18 and 30). IP55, class F (ranges 45 and 56). Additional information Single phase (CADB) and three phase models (CADT). Flows from 450 to 5,600 m 3 /h. Versions with an electronic microprocessor (BASIC, PROGRAM, ADVANZ or DOMO) that enables the fan speed to be controlled. The versions with an electronic microprocessor in sizes 45 and 56 also incorporate a variable frequency drive. Horizontal and vertical versions, both with the possibility of a by-pass. All side panels are interchangeable, which makes it possible to directly position the intake and outtake connections on site. CONFIGURABLE CROSS-FLOW HEAT RECOVERY CADB/T-D DP25 F7 Series CADB/T-DI DP25 F7 CADB/T-DC DP25 F7 Stores Offices Cafes, bars and restaurants IMPORTANT UPDATE TO THE RANGE New standard configuration with a 25 mm thick double wall and F7 filters with low loss of load, manufactured in polypropylene, for inlet air and G4 manufactured in fibreglass for extraction. A P P L I C A T I O N S Collective ventilation dwellings

Upload: duongthu

Post on 31-Mar-2018

223 views

Category:

Documents


1 download

TRANSCRIPT

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Heat recovery units housed in galvanised steel

boxes, white plastic coated, with a 25 mm

thick double wall, class M0 fire proof thermal

and acoustic insulation, configurable inlets and

outlets, versions for horizontal installation and for

vertical installation, intakes with a hermetic seal,

F7 filter for inlet air and G4 filter for air extraction.

With two double inlet centrifugal fans with built-

in motor.

CADB/T-D DP25 F7 Series

Heat recovery without additional heat added.

CADB/T-DI DP25 F7 Series

Heat recoveries with a heating resistance.

CADB/T-DC DP25 F7 Series

Heat recoveries with a built-in hot water coil.

Motors

IP20, Class F (ranges 05, 08, 18 and 30).

IP55, class F (ranges 45 and 56).

Additional information

Single phase (CADB) and three phase models

(CADT).

Flows from 450 to 5,600 m3/h.

Versions with an electronic microprocessor

(BASIC, PROGRAM, ADVANZ or DOMO) that

enables the fan speed to be controlled.

The versions with an electronic microprocessor

in sizes 45 and 56 also incorporate a variable

frequency drive.

Horizontal and vertical versions, both with the

possibility of a by-pass.

All side panels are interchangeable, which

makes it possible to directly position the intake

and outtake connections on site.

CONFIGURABLE CROss-FLOw hEAt RECOVERY

CADB/T-D DP25 F7 SeriesCADB/T-DI DP25 F7CADB/T-DC DP25 F7

Stores Offices Cafes, bars and restaurants

IMPORTANT UPDATE TO THE RANGE

New standard configuration with a 25 mm thick

double wall and F7 filters with low loss of load,

manufactured in polypropylene, for inlet air and G4

manufactured in fibreglass for extraction.

A P P L I C A T I O N S

Collectiveventilationdwellings

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Pressure sockets

Pressure sockets before for

clogging filter control.

External weatherproofterminal box

IP55 terminal box located on

the outside of the heat reco-

very casing for easy wiring

access.

BASIC

ADVANZ

PROGRAM

DOMO

Condensationdrain

Drain pipe to evacuate water

from condensation.

Robust construction

High quality finishing with

aluminium profile structure,

providing a robust assembly.

2 high-efficiency filters

2 filters:

F7 filter for inlet air (filtration

efficiency: >80%).

G4 filter for extracted air (effi-

ciency: >90%).

Airtight connectors

Inlet and discharge circular

duct connection flanges with

integrated rubber air seal.

Vertical construction

Specific models for vertical

installation.

Low noise level

Internally lined with 25 mm M0

fire resistant acoustic

insulation.

Easy to mount

Single phase models integrated

hanging supports to install the

heat recovery unit.

Version with by pass

Versions with by pass enabling

100% of the air to by pass the

heat recovery (65% in single-

phase versions).

The by-pass works with a remo-

tely activated servomotor with a

manual switch (not included).

structural Advantages

Versions CADB-D/DC/DI Regulation with an electronic microprocessor

Versions that incorporate an electronic microprocessor (BASIC,

PROGRAM, ADVANZ or DOMO) that enables fan speed control.

The versions with an electronic microprocessor in sizes 45 and 56 also

incorporate a variable frequency drive.

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Versatile assembly

The design of these heat recovery units makes it possible for the user to configure them on site. All side panels are interchangeable, which makes it possible to directly position

the intake and outtake connections on site depending on the specific requirements.

All side panels areinterchangeable

structural Advantages

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Easy maintenance

Models CADB- 05 / 08 / 18 / 30: Rapid access to the filters from the bottom and sides. Easy access for cleaning the heat recovery from the bottom.

Models CADT-45 and CADT-56: Rapid access to the filters from the top. It is also possible to access from the side and

bottom.

Easy access for cleaning the heat recovery from the top.

Reference

C A D B D I H3 0 A T R I-

1 - CADB / CADT: Series

2 - D: Standard range

DI: Range with resistance incorporated

DC:Range with water coil incorporated

3 - Size

4 - A, B, C, D, E, G, H: Type of configuration

5 - H: Horizontal unit

V: Upright unit.

6 - MONO: Monophase support resistance.

TRI: Three phase support resistance

7 - BP: Version with by pass incorporated

8 - DP: Range with double wall insulation

(25 mm).

9 - F7: Air inlet filter F7.

10 - BASIC, PROGRAM, ADVANZ,

DOMO Control.

11 - Configuration control

VAV - Variable airflow

CAV - Constant airfflow (sizes 45 and 56)

(Not posible with BASIC)

COP - Constant pressure (sizes 45 and 56)

(Not possible with BASIC)

B P

1 2 3 4 5 6 7 8 9 10 11

D P 2 5 F 7

structural Advantages

B A S I C V A V

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Versions with an electronic microprocesor: Models and functions

BASIC PROGRAM ADVANZ DOMO

Manual fan speed selection: OFF + 3 speed

Manual fan speed selection: OFF + control of speed range [MIN-MAX] (alternative to 1 )

Imbalance between impulsion and extraction flow only for VAV versions with double inverter (does not apply to 3 speed versions)

Automatic control of fan speed: CO2, CO2/VOC and HR sensors with programmable PPM or HR range (by the installer); available for 3 speed versions and variable speed versions

Remote function of the fan speed signal is 0-10V (alternative to 4 )

Booster via remote NC contact at a pre-set time. Time can be altered by software

Remote "Boost" management by NC contact or proximity sensor (alternative to 6 and 8 )

Unit can be switched ON/OFF via remote switch (alternative to 6 or 7 )

Weekly programs

Prevention of icing of the heat exchanger (simple strategy): blower fan moves to low/off; Setting the extractor fan to maximum speed.

Prevention of build-up of frost in the heat exchanger: proportional mode management with pre-heating coils (alternative to 10 or 12 )

Exchanger frost prevention: Personalized funcions (through a switch NO-NC (alternative to 10 and 11 )

Management of electric post-heating (simple or double stage) in ON/OFF mode. The objec-tive is to attain the average internal temperature value (Tr)

Management of electric post-heating in proportional mode. The objective is to attain the average internal temperature value (Tr) and to keep the impelled air within a set range (Ti)

Management of water coil post-heating in ON/OFF mode. The objective is to attain the aver-age internal temperature value (Tr)

Management of water coil post-heating. The objective is to attain the average internal tem-perature value (Tr) and to keep the impelled air within a set range (Ti)

Management of post-cooling in proportional mode. The objective is to attain the average internal temperature value (Tr) and to keep the impelled air within a set range (Ti)

Remote signalling of the status of the unit via a volt free contact: closed contact=the unit is operating; open contact=the unit is stopped (alternative to 12 )

Monitoring of the state of the filters via period of operation of the equipment or via differen-tial pressure sensors

Monitoring of the state of the fans via a tachometric signal (if supported by the fan) or via differential pressure sensors

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

3 3 3 3

3 3 3

3 3 3

3 3 3

3 3

3 3

3 3

3 3

3 3 3

3 3 3 3

3 3

3 3

3

3 3

3

3 3

3 3

3 3

3 3 3 3

3 3 3 3

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Electronic microprocessors BAsIC model - Features and functions

BASIC CONTROL CADB/T-DPRINCIPAL FEATURESTerminal cabinet includes:• Proximity sensor l

• Integrated circuit card and terminal box l

Remote control unit (100 m max.) l

Ready-mounted, ready-wired temperature sensors:• Discharge temperature sensor (Tx) l

• New air intake temperature sensor (Te) l

• Ambient air return temperature sensor (Tr) l

Vacuum regulator valve, ready-mounted and wired:• Filter clogging l

Frequency regulator on Three phase models (sizes 45 and 56) l

OPTIONAL FEATURESVacuum regulator valve, ready-mounted and wired:• ABE-SCT circular battery ¥

• Differential pressure switch ¥

• Timer ¥

• TG-K310 duct-mountable temperature sensor -20 to + 10ºC ¥

• TI-10 potentiometer -20 to + 10ºC for panel mounting ¥

FUNCTIONSFlow rate adjustment:

• Manual fan speed selection:l- Single phase models: 3 speed

- Three phase models: 45%, 65% and 100% of maximum flow rateFree cooling function on models equipped with by-pass l

Prevention of icing of the heat exchanger:• Heat exchanger antifreeze protection (blower fan moves to low/off) l

Safety functions:• Filter clogging / vacuum regulator valve failure alarm l

• Temperature sensor fault alarm (wire severed, connection fault,...) l

• Console-control cabinet connection fault alarm l

l Included, ¥ Unmounted option

schematic diagram

T return(ambient)

T new air intakeT discharge

+

By-pass

0/VL/VM/VR

Boost HS/LSAlarms

BASIC

Self-regulatingantifreeze battery

The battery is regulated independently. The BASIC can not control it.

CADT/T-D DP25 F7 with BASIC control

HS: High speed LS: Low speed

Hea

t re

cove

ry u

nits

CA

DB

/T-D

PROGRAM CONTROL CADB/T-DPRINCIPAL FEATURES Terminal cabinet includes:

Proximity sensor • Integrated circuit card and terminal box•

Remote control unit (100 m max.) Ready-mounted, ready-wired temperature sensors:

Discharge temperature sensor (Tx)• New air intake temperature sensor (Te)• Ambient air return temperature sensor (Tr)•

Vacuum regulator valve, ready-mounted and wired:Filter clogging• Security (operation of fans)•

Frequency regulator on three phase models (sizes 45 and 56) OPTIONAL FEATURESCO2 sensor:

SCO2-010A ambient sensor with display / SCO2-010G in-duct measurement• ¥Self-regulating antifreeze battery:

ABE-SCT circular battery• ¥Differential pressure switch• ¥Timer• ¥TG-K310 duct-mountable temperature sensor -20 to + 10ºC• ¥TI-10 potentiometer -20 to + 10ºC for panel mounting• ¥

FUNCTIONSFlow rate adjustment:

Manual fan speed selection (single phase models) or variable (three phase models •45/56). Timer boost function

Automatic modulation via built-in clock: daily and weekly programs •

Automatic speed settings (single phase models) or automatic speed variation •(Three phase models) based on air quality sensor readings (sensor optional)

Operates at constant pressure• *Free cooling function on models equipped with by-pass

Safety functions:Heat exchanger antifreeze protection (blower fan moves to low/off)• Filter clogging / vacuum regulator valve failure alarm • Temperature sensor fault alarm (wire severed, connection fault,...)• Console-control cabinet connection fault alarm• Included, ¥ Unmounted option

* Optional and on request in 45 and 56 models

Electronic microprocessors - PROGRAM model - Features and functions

schematic diagram

T return(ambient)

T new air intake T discharge

+

By-pass

CO2 Sensor

0/HS/MS/LS

Programmable timerBoost HS/ O� HS/LSSetpoint adjustmentAlarms

PROGRAM

Self-regulatingantifreeze battery

T supply air

By-pass

+

+

PROGRAM

T return(ambient)

T new air intake T discharge

CO2 Sensor

0/HS/MS/LS

Programmable timerBoost HS/ O� HS/LSSetpoint adjustmentAlarms

Self-regulatingantifreeze battery*

T supply air

PROGRAM CONTROL CADB/T-DI CADB/T-DCPRINCIPAL FEATURES Terminal cabinet includes:

Proximity sensor•

Integrated circuit card and terminal box• Remote control unit (100 m max.)

Ready-mounted, ready-wired temperature sensors:Discharge temperature sensor (Tx)•

New air intake temperature sensor (Te)•

Ambient air return temperature sensor (Tr)•

Supply air temperature sensor (Ti)•

Vacuum regulator valve, ready-mounted and wired: Filter clogging•

Security (operation of fans)•

Frequency regulator on three phase models (sizes 45 and 56)

OPTIONAL FEATURESMotorized 3-way control valve + 230V/24V transformer for hot water coil

- ¥

CO2 sensor:SCO2-010A ambient sensor with display / SCO2-010G in-duct •measurement ¥ ¥

Self-regulating antifreeze battery:ABE-SCT circular battery• ¥ ¥Differential pressure switch• ¥ ¥Timer• ¥ ¥TG-K310 duct-mountable temperature sensor -20 to + 10ºC• ¥ ¥TI-10 potentiometer -20 to + 10ºC for panel mounting• ¥ ¥

FUNCTIONSFlow rate adjustment:

Manual fan speed selection (single phase models) or variable •(three phase models 45/56). Timer boost function

Automatic modulation via built-in clock: daily and weekly •programs

Automatic speed settings (single phase models) or automatic •speed variation (Three phase models) based on air quality sensor readings (sensor optional)

Operates at constant pressure • * *Post heating battery regulation

Battery power regulation as per temperature setting and blower •sensor reading

Free cooling function on models equipped with by-pass

Safety functions:Heat exchanger antifreeze protection (blower fan moves to low/off)•

Fan shutdown timer setting for cooling electric battery •(postventilation)

-

Water coil antifreeze protection antigel de la batterie eau in each •sensor (opens 3-way control valve then stops power unit)

-

Filter clogging / vacuum regulator valve failure alarm •

Temperature sensor fault alarm (wire severed, connection fault,...)•

Ventilation fault alarm• Console-control cabinet connection fault alarm•

Included, - Not included, ¥ Unmounted option

* Optional and on request in 45 and 56 models

The battery is regulated independently. The PROGRAM can not control it.

The battery is regulated independently. The PROGRAM can not control it.

CADB/T-DI DP25 F7 with PROGRAM control CADB/T-DC DP25 F7 with PROGRAM control

HS: High speed MS: Medium speed LS: Low speed HS: High speed MS: Medium speed LS: Low speed

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Electronic microprocessors - ADVANZ and DOMO models - Features and functions

ADVANZ AND DOMO CONTROLS CADB/T-DPRINCIPAL FEATURESTerminal cabinet includes:• Proximity sensor l

• Integrated circuit card and terminal box l

Remote control unit (100 m max.) (Only ADVANZ) l

Ready-mounted, ready-wired temperature sensors:• Discharge temperature sensor (Tx) l

• New air intake temperature sensor (Te) l

• Ambient air return temperature sensor (Tr) l

Vacuum regulator valve, ready-mounted and wired:• Filter clogging l

• Security (operation of fans) l

Frequency regulator on three phase models (sizes 45 and 56) l

OPTIONAL FEATURESCO2 sensor:• SCO2-010A ambient sensor with display / SCO2-010G in-duct measurement ¥

Self-regulating antifreeze battery:• ABE-SCT circular battery ¥

• Differential pressure switch ¥

• Timer ¥

• TG-K310 duct-mountable temperature sensor -20 to + 10ºC ¥

• TI-10 potentiometer -20 to + 10ºC for panel mounting ¥

FUNCTIONSFlow rate adjustment:• Manual fan speed selection (single phase models) or variable (three phase models

45/56). Timer boost functionl

• Automatic modulation via built-in clock: daily and weekly programs l

• Automatic speed settings (single phase models) or automatic speed variation(Three phase models) based on air quality sensor readings (sensor optional)

l

• Remote function of the fan speed signal is 0-10V l

• Operates at constant pressure *Free cooling function on models equipped with by-pass l

Remote "Boost" management by NC contact or proximity sensor l

Remote indication of unit status l

Exchanger frost prevention:• Heat exchanger antifreeze protection (blower fan moves to low/off) l

• Proportional management using an antifreeze battery (pre-heating)) l

• Personalized funcions (through a switch NO-NC) l

Remote signaling of unit status l

Panel language configuration (ES/EN/DE/IT/FR) l

Safety functions:• Filter clogging / vacuum regulator valve failure alarm l

• Temperature sensor fault alarm (wire severed, connection fault,...) l

• Console-control cabinet connection fault alarm l

• Communicator regulation [adjustment] (Only DOMO) l

l Included, ¥ Unmounted option

* Optional and on request in 45 and 56 models

schematic diagram

T new air intake T discharge Self-regulatingantifreeze battery

T return(ambient)

CO2 Sensor

0/HS/MS/LS

Programable timer Boost HS / O� HS/LSSetpoint adjustmentAlarms

ADVANZDOMO

Register

Network(DOMO)

Boost HR

Supply air

T new air intake T discharge Self-regulatingantifreeze battery

T return(ambient)

CO2 Sensor

0/HS/MS/LS

Programmable timerBoost HR / O� HS/LSSetpoint adjustmentAlarms

Network(DOMO)

Register

Boost HS

T supply air

ADVANZDOMO

ADVANZ AND DOMO CONTROLS CADB/T-DI CADB/T-DCPRINCIPAL FEATURESTerminal cabinet includes:• Proximity sensor l l• Integrated circuit card and terminal box l lRemote control unit (100 m max.) (Only ADVANZ) l lReady-mounted, ready-wired temperature sensors:• Discharge temperature sensor (Tx) l l• New air intake temperature sensor (Te) l l• Ambient air return temperature sensor (Tr) l l• Supply air temperature sensor (Ti) l lVacuum regulator valve, ready-mounted and wired:• Filter clogging l l• Security (operation of fans) l lSolid-state relay on electrical battery l -No-frost safety sensor on hot water battery - lFrequency regulator on three phase models (sizes 45 and 56) l lOPTIONAL FEATURESMotorized 3-way control valve + 230V/24V transformer for hot water coil - ¥CO2 sensor:• SCO2-010A ambient sensor with display / SCO2-010G in-duct measurement ¥ ¥Self-regulating antifreeze battery:• ABE-SCT circular battery ¥ ¥• Differential pressure switch ¥ ¥• Timer ¥ ¥• TG-K310 duct-mountable temperature sensor -20 to + 10ºC ¥ ¥• TI-10 potentiometer -20 to + 10ºC for panel mounting ¥ ¥FUNCTIONSFlow rate adjustment:• Manual fan speed selection (single phase models) or variable

(three phase models 45/56). Timer boost functionl l

• Automatic modulation via built-in clock: daily and weekly programs l l

• Automatic speed settings (single phase models) or automatic speed variation (Three phase models) based on air quality sensor readings (sensor optional)

l l

• Remote function of the fan speed signal is 0-10V l l• Operates at constant pressure * *Post heating battery regulation• Battery power regulation as per temperature setting and blower sensor

readingl l

Free cooling function on models equipped with by-pass l lRemote "Boost" management by NC contact or proximity sensor l lRemote indication of unit status l lExchanger frost prevention:• Heat exchanger antifreeze protection (blower fan moves to low/off) l l• Proportional management using an antifreeze battery (pre-heating) l l• Personalized funcions (through a switch NO-NC) l lProportional function of post-heating or post-cooling l lRemote signaling of unit status l lPanel language configuration (ES/EN/DE/IT/FR) l lSafety functions:• Fan shutdown timer setting for cooling electric battery (postventilation) l l

• Water coil antifreeze protection antigel de la batterie eau in each sensor (opens 3-way control valve then stops power unit) - l

• Filter clogging / vacuum regulator valve failure alarm l l• Temperature sensor fault alarm (wire severed, connection fault,...) l l• Console-control cabinet connection fault alarm l l• Communicator regulation [adjustment] (Only DOMO) l l

* Optional and on request in 45 and 56 models

CADB/T-DI DP25 F7 with ADVANZ / DOMO control CADB/T-DC DP25 F7 with ADVANZ / DOMO control

HS: High speed MS: Medium speed LS: Low speed HS: High speed MS: Medium speed LS: Low speed

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Evolution of the efficiency of recovery according to the flowValues with the following conditions:

Outside air temperature -5ºC, inside

air temperature +20ºC with interior

RH of 80%.

Airflow (m3/h)

CADB 05

CADB 08

CADB 18

CADB 30

CADT 45

CADT 56

Effi

cien

cy

technical characteristicsModels without heater

Models with integrated electrical heater

Models with integrated water coil (water 70/80ºC)

Model Fan type Speed

(r.p.m.)

Nº of speeds

Motorpower

(kW)

Maximum absorbed current

motor (A)

Maximum absorbed current

total (A)

Maximum volume

(m3/h)

ProtectionIP

Efficiency%*

Thermalperfor-mance

(kW) **to 230V to 400V to 230V to 400V

CADB-DC 05 DP25 F7 146-HR93 1750 4 2 x 0,130 0,62 - 1,24 - 400 20 50,7 2,62CADB-DC 08 DP25 F7 146-HT67 2100 4 2 x 0,310 1,4 - 2,8 - 800 20 53,9 3,67CADB-DC 18 DP25 F7 9/7 1130 3 2 x 0,373 2,75 - 5,5 - 1900 20 51,6 10,67CADB-DC 30 DP25 F7 10/8 1400 3 2 x 0,550 4 - 8 - 3000 20 52,5 14,29CADT-DC 45 DP25 F7 10/10 1370 1 2 x 0,750 - 3,1 - 6,2 4500 55 54 30CADT-DC 56 DP25 F7 12/9 1420 1 2 x 1,500 - 3,9 - 7,8 5600 55 52,3 34,5* Values referring to the following conditions: Text air = -5ºC, Text exhaust air = +20ºC with RH exhaust air = 80% / max.airflow.** Values referring to the following conditions: water 70/80ºC, intake air temperature +8ºC nominal airflow.

Model Fan type Speed

(r.p.m.)

Nº of speeds

Motorpower

(kW)

Maximum absorbed current motor

(A)

Maximum absorbed current total

(A)

Maximum volume

(m3/h)

Available pressure at maximum

airflow(Pa)

ProtectionIP

to 230V to 400V to 230V to 400V

CADB-D 05 DP25 F7 146-HR93 1750 4 2 x 0,150 0,62 - 1,24 - 400 85 20CADB-D 08 DP25 F7 146-HT67 2100 4 2 x 0,355 1,4 - 2,8 - 800 100 20CADB-D 18 DP25 F7 9/7 1130 3 2 x 0,373 2,75 - 5,5 - 1900 140 20CADB-D 30 DP25 F7 10/8 1400 3 2 x 0,550 4 - 8 - 3000 180 20CADT-D 45 DP25 F7 10/10 1370 1 2 x 0,750 - 3,1 - 6,2 4500 100 55CADT-D 56 DP25 F7 12/9 1420 1 2 x 1,500 - 3,9 - 11,2 5600 120 55

Model Fan type Speed

(r.p.m.)

Nº of speeds

Motorpower

(kW)

Maximum absorbed

current motor (A)

Maximum absorbed current

total (A)

Maximum volume

(m3/h)

ProtectionIP

Efficiency%*

Resist.power

(kW)

Resist.voltage

(V)

Resist.absorbed current

(A)

Maximumcurrenttotal fan

+resistance

(A)to 230V to 400V to 230V to 400V

CADB-DI 05 MONO DP25 F7 146-HR93 1750 4 2 x 0,130 0,62 - 1,24 - 400 20 50,7 2 230 8,5 9,74CADB-DI 08 MONO DP25 F7 146-HT67 2100 4 2 x 0,310 1,4 - 2,8 - 800 20 53,9 4 230 17,5 20,3CADB-DI 18 MONO DP25 F7 9/7 1130 3 2 x 0,373 2,75 - 5,5 - 1900 20 51,6 6 230 26 33,80CADB-DI 30 TRI DP25 F7 10/8 1400 3 2 x 0,550 4 - 8 - 3000 20 52,5 8 400 11,55 19,59CADT-DI 45 TRI DP25 F7 10/10 1370 1 2 x 0,750 - 3,1 - 6,2 4500 55 54 12 400 17,32 23,52CADT-DI 56 TRI DP25 F7 12/9 1420 1 2 x 1,500 - 3,9 - 7,8 5600 55 52,3 12 400 17,32 25,12

* Values referring to the following conditions: Text air = -5ºC, Text exhaust air = +20ºC with RH exhaust air = 80% / max.airflow.

Hea

t re

cove

ry u

nits

CA

DB

/T-D

thermal efficiency recovery

Model Air volume

(m3/h)

T. ambient air T. outdoor air T. air treated

(ºC)

Minimum

efficiency

(%)

Power

(kW)ºCH.R. % ºC

H.R. %

CADB-D 05 DP25 F7 400 20

50

-10 80 5,6 52,2 2,7

-5 80 7,7 50,7 2,2

0 70 9,4 46,9 1,6

5 60 11,7 44,9 1,2

60

-10 80 7 56,7 2,9

-5 80 8,6 54,4 2,3

0 70 10,5 52,5 1,8

5 60 12,1 47,4 1,2

CADB-D 08 DP25 F7 800 20

50

-10 80 6,6 55,4 4,5

-5 80 8,5 53,9 3,7

0 70 10 49,8 2,7

5 60 12,1 47,4 1,9

60

-10 80 8 60,1 4,9

-5 80 9,5 57,9 4

0 70 11,2 55,8 3,1

5 60 12,5 50,3 2,1

CADB-D 18 DP25 F7 1.900 20

50

-10 80 5,9 53,1 10,3

-5 80 7,9 51,6 8,4

0 70 9,5 47,7 6,2

5 60 11,8 45,6 4,4

60

-10 80 7,3 57,7 11,2

-5 80 8,8 55,4 9

0 70 10,7 53,4 6,9

5 60 12,2 48,2 4,7

CADB-D 30 DP25 F7 3.000 20

50

-10 80 6,2 54 16,6

-5 80 8,1 52,5 13,4

0 70 9,7 48,5 9,9

5 60 11,9 46,3 7,1

60

-10 80 7,6 58,7 18

-5 80 9,1 56,4 14,5

0 70 10,9 54,4 11,2

5 60 12,4 49,1 7,5

CADT-D 45 DP25 F7 4.500 20

50

-10 80 6,6 55,2 25

-5 80 8,5 54 20,3

0 70 10,1 50,2 15,2

5 60 12,1 47,6 10,7

60

-10 80 8,1 60,3 27,3

-5 80 9,8 59,3 22,3

0 70 11,3 56,3 17

5 60 12,8 51,7 11,7

CADT-D 56 DP25 F7 5.600 20

50

-10 80 6,3 54,5 31,7

-5 80 8,1 52,3 25,4

0 70 9,8 48,8 18,9

5 60 11,9 46,1 13,4

60

-10 80 7,5 58,5 34,1

-5 80 9,4 57,5 27,9

0 70 10,9 54,5 21,2

5 60 12,5 50 14,6

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Complete chart for standard versions

CADB/t-DHORIZONTAL

Range 05

CADB-D 05 CH DP25 F7

CADB-D 05 CH BP DP25 F7

UPRIGHT

Range 05

CADB-D 05 AV DP25 F7

CADB-D 05 AV BP DP25 F7

CADB-D 05 BV DP25 F7

CADB-D 05 BV BP DP25 F7

CADB-D 05 HV DP25 F7

CADB-D 05 HV BP DP25 F7

Range 08

CADB-D 08 CH DP25 F7

CADB-D 08 CH BP DP25 F7

Range 08

CADB-D 08 AV DP25 F7

CADB-D 08 AV BP DP25 F7

CADB-D 08 BV DP25 F7

CADB-D 08 BV BP DP25 F7

CADB-D 08 HV DP25 F7

CADB-D 08 HV BP DP25 F7

Range 18

CADB-D 18 CH DP25 F7

CADB-D 18 CH BP DP25 F7

Range 18

CADB-D 18 AV DP25 F7

CADB-D 18 AV BP DP25 F7

CADB-D 18 BV DP25 F7

CADB-D 18 BV BP DP25 F7

CADB-D 18 HV DP25 F7

CADB-D 18 HV BP DP25 F7

Range 30

CADB-D 30 CH DP25 F7

CADB-D 30 CH BP DP25 F7

Range 30

CADB-D 30 AV DP25 F7

CADB-D 30 AV BP DP25 F7

CADB-D 30 BV DP25 F7

CADB-D 30 BV BP DP25 F7

CADB-D 30 HV DP25 F7

CADB-D 30 HV BP DP25 F7

Range 45

CADT-D 45 CH DP25 F7

CADT-D 45 CH BP DP25 F7

Range 45

CADT-D 45 AV DP25 F7

CADT-D 45 AV BP DP25 F7

CADT-D 45 BV DP25 F7

CADT-D 45 BV BP DP25 F7

CADT-D 45 HV DP25 F7

CADT-D 45 HV BP DP25 F7

Range 56

CADT-D 56 CH DP25 F7

CADT-D 56 CH BP DP25 F7

Range 56

CADT-D 56 AV DP25 F7

CADT-D 56 AV BP DP25 F7

CADT-D 56 BV DP25 F7

CADT-D 56 BV BP DP25 F7

CADT-D 56 HV DP25 F7

CADT-D 56 HV BP DP25 F7

HORIZONTAL

Range 05

CADB-DI 05 AH MONO DP25 F7

CADB-DI 05 DH MONO DP25 F7

CADB-DI 05 EH MONO DP25 F7

CADB-DI 05 GH MONO DP25 F7

CADB-DI 05 AH MONO BP DP25 F7

CADB-DI 05 DH MONO BP DP25 F7

CADB-DI 05 EH MONO BP DP25 F7

CADB-DI 05 GH MONO BP DP25 F7

UPRIGHT

Range 05

CADB-DI 05 CV MONO DP25 F7

CADB-DI 05 DV MONO DP25 F7

CADB-DI 05 EV MONO DP25 F7

CADB-DI 05 CV MONO BP DP25 F7

CADB-DI 05 DV MONO BP DP25 F7

CADB-DI 05 EV MONO BP DP25 F7

CADB/t-DI

Range 08

CADB-DI 08 AH MONO DP25 F7

CADB-DI 08 DH MONO DP25 F7

CADB-DI 08 EH MONO DP25 F7

CADB-DI 08 GH MONO DP25 F7

CADB-DI 08 AH MONO BP DP25 F7

CADB-DI 08 DH MONO BP DP25 F7

CADB-DI 08 EH MONO BP DP25 F7

CADB-DI 08 GH MONO BP DP25 F7

Range 08

CADB-DI 08 CV MONO DP25 F7

CADB-DI 08 DV MONO DP25 F7

CADB-DI 08 EV MONO DP25 F7

CADB-DI 08 CV MONO BP DP25 F7

CADB-DI 08 DV MONO BP DP25 F7

CADB-DI 08 EV MONO BP DP25 F7

Range 18

CADB-DI 18 AH MONO DP25 F7

CADB-DI 18 DH MONO DP25 F7

CADB-DI 18 EH MONO DP25 F7

CADB-DI 18 GH MONO DP25 F7

CADB-DI 18 AH MONO BP DP25 F7

CADB-DI 18 DH MONO BP DP25 F7

CADB-DI 18 EH MONO BP DP25 F7

CADB-DI 18 GH MONO BP DP25 F7

Range 18

CADB-DI 18 CV MONO DP25 F7

CADB-DI 18 DV MONO DP25 F7

CADB-DI 18 EV MONO DP25 F7

CADB-DI 18 CV MONO BP DP25 F7

CADB-DI 18 DV MONO BP DP25 F7

CADB-DI 18 EV MONO BP DP25 F7

Range 30

CADB-DI 30 AH TRI DP25 F7

CADB-DI 30 DH TRI DP25 F7

CADB-DI 30 EH TRI DP25 F7

CADB-DI 30 GH TRI DP25 F7

CADB-DI 30 AH TRI BP DP25 F7

CADB-DI 30 DH TRI BP DP25 F7

CADB-DI 30 EH TRI BP DP25 F7

CADB-DI 30 GH TRI BP DP25 F7

Range 30

CADB-DI 30 CV TRI DP25 F7

CADB-DI 30 DV TRI DP25 F7

CADB-DI 30 EV TRI DP25 F7

CADB-DI 30 CV TRI BP DP25 F7

CADB-DI 30 DV TRI BP DP25 F7

CADB-DI 30 EV TRI BP DP25 F7

Range 45

CADT-DI 45 AH TRI DP25 F7

CADT-DI 45 DH TRI DP25 F7

CADT-DI 45 EH TRI DP25 F7

CADT-DI 45 GH TRI DP25 F7

CADT-DI 45 AH TRI BP DP25 F7

CADT-DI 45 DH TRI BP DP25 F7

CADT-DI 45 EH TRI BP DP25 F7

CADT-DI 45 GH TRI BP DP25 F7

Range 45

CADT-DI 45 CV TRI DP25 F7

CADT-DI 45 DV TRI DP25 F7

CADT-DI 45 EV TRI DP25 F7

CADT-DI 45 CV TRI BP DP25 F7

CADT-DI 45 DV TRI BP DP25 F7

CADT-DI 45 EV TRI BP DP25 F7

Range 56

CADT-DI 56 AH TRI DP25 F7

CADT-DI 56 DH TRI DP25 F7

CADT-DI 56 EH TRI DP25 F7

CADT-DI 56 GH TRI DP25 F7

CADT-DI 56 AH TRI BP DP25 F7

CADT-DI 56 DH TRI BP DP25 F7

CADT-DI 56 EH TRI BP DP25 F7

CADT-DI 56 GH TRI BP DP25 F7

Range 56

CADT-DI 56 CV TRI DP25 F7

CADT-DI 56 DV TRI DP25 F7

CADT-DI 56 EV TRI DP25 F7

CADT-DI 56 CV TRI BP DP25 F7

CADT-DI 56 DV TRI BP DP25 F7

CADT-DI 56 EV TRI BP DP25 F7

HORIZONTAL

Range 05

CADB-DC 05 AH DP25 F7

CADB-DC 05 DH DP25 F7

CADB-DC 05 EH DP25 F7

CADB-DC 05 GH DP25 F7

CADB-DC 05 AH BP DP25 F7

CADB-DC 05 DH BP DP25 F7

CADB-DC 05 EH BP DP25 F7

CADB-DC 05 GH BP DP25 F7

UPRIGHT

Range 05

CADB-DC 05 CV DP25 F7

CADB-DC 05 DV DP25 F7

CADB-DC 05 EV DP25 F7

CADB-DC 05 CV BP DP25 F7

CADB-DC 05 DV BP DP25 F7

CADB-DC 05 EV BP DP25 F7

CADB/t-DC

Range 08

CADB-DC 08 AH DP25 F7

CADB-DC 08 DH DP25 F7

CADB-DC 08 EH DP25 F7

CADB-DC 08 GH DP25 F7

CADB-DC 08 AH BP DP25 F7

CADB-DC 08 DH BP DP25 F7

CADB-DC 08 EH BP DP25 F7

CADB-DC 08 GH BP DP25 F7

Range 08

CADB-DC 08 CV DP25 F7

CADB-DC 08 DV DP25 F7

CADB-DC 08 EV DP25 F7

CADB-DC 08 CV BP DP25 F7

CADB-DC 08 DV BP DP25 F7

CADB-DC 08 EV BP DP25 F7

Range 18

CADB-DC 18 AH DP25 F7

CADB-DC 18 DH DP25 F7

CADB-DC 18 EH DP25 F7

CADB-DC 18 GH DP25 F7

CADB-DC 18 AH BP DP25 F7

CADB-DC 18 DH BP DP25 F7

CADB-DC 18 EH BP DP25 F7

CADB-DC 18 GH BP DP25 F7

Range 18

CADB-DC 18 CV DP25 F7

CADB-DC 18 DV DP25 F7

CADB-DC 18 EV DP25 F7

CADB-DC 18 CV BP DP25 F7

CADB-DC 18 DV BP DP25 F7

CADB-DC 18 EV BP DP25 F7

Range 30

CADB-DC 30 AH DP25 F7

CADB-DC 30 DH DP25 F7

CADB-DC 30 EH DP25 F7

CADB-DC 30 GH DP25 F7

CADB-DC 30 AH BP DP25 F7

CADB-DC 30 DH BP DP25 F7

CADB-DC 30 EH BP DP25 F7

CADB-DC 30 GHBP DP25 F7

Range 30

CADB-DC 30 CV DP25 F7

CADB-DC 30 DV DP25 F7

CADB-DC 30 EV DP25 F7

CADB-DC 30 CV BP DP25 F7

CADB-DC 30 DV BP DP25 F7

CADB-DC 30 EV BP DP25 F7

Range 45

CADT-DC 45 AH DP25 F7

CADT-DC 45 DH DP25 F7

CADT-DC 45 EH DP25 F7

CADT-DC 45 GH DP25 F7

CADT-DC 45 AH BP DP25 F7

CADT-DC 45 DH BP DP25 F7

CADT-DC 45 EH BP DP25 F7

CADT-DC 45 GH BP DP25 F7

Range 45

CADT-DC 45 CV DP25 F7

CADT-DC 45 DV DP25 F7

CADT-DC 45 EV DP25 F7

CADT-DC 45 CV BP DP25 F7

CADT-DC 45 DV BP DP25 F7

CADT-DC 45 EV BP DP25 F7

Range 56

CADT-DC 56 AH DP25 F7

CADT-DC 56 DH DP25 F7

CADT-DC 56 EH DP25 F7

CADT-DC 56 GH DP25 F7

CADT-DC 56 AH BP DP25 F7

CADT-DC 56 DH BP DP25 F7

CADT-DC 56 EH BP DP25 F7

CADT-DC 56 GH BP DP25 F7

Range 56

CADT-DC 56 CV DP25 F7

CADT-DC 56 DV DP25 F7

CADT-DC 56 EV DP25 F7

CADT-DC 56 CV BP DP25 F7

CADT-DC 56 DV BP DP25 F7

CADT-DC 56 EV BP DP25 F7

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Base on these standard configurations other configurations can be quickly and simply adapted by the installer.

CADB/t-D/DI/DC DP25 F7 standard configurations

CADB/t-D

CADB-D 05/08/18/30 CHCADT-D 45/56 CH

CADB-D 05/08/18/30 AVCADT-D 45/56 AV

CADB-D 05/08/18/30 BVCADT-D 45/56 BV

CADB-D 05/08/18/30 HVCADT-D 45/56 HV

Conf. CH Conf. AV Conf. BV Conf. HV

HORIZONTAL UPRIGHT

CADB/T-DI

CADB-DI 05/08/18 AH MONOCADB-DI 30 AH TRICADT-DI 45/56 AH TRI

CADB-DI 05/08/18 DH MONOCADB-DI 30 DH TRICADT-DI 45/56 DH TRI

CADB-DI 05/08/18 EH MONOCADB-DI 30 EH TRICADT-DI 45/56 EH TRI

CADB-DI 05/08/18 GH MONOCADB-DI 30 GH TRICADT-DI 45/56 GH TRI

CADB-DI 05/08/18 CV MONOCADB-DI 30 CV TRICADT-DI 45/56 CV TRI

CADB-DI 05/08/18 DV MONOCADB-DI 30 DV TRICADT-DI 45/56 DV TRI

CADB-DI 05/08/18 EV MONOCADB-DI 30 EV TRICADT-DI 45/56 EV TRI

CONf. AH CONf. DH CONf. EH CONf. GH

CONf. CV CONf. DV CONf. EV

HORIZONTAL

UPRIGHT

FILTRO

DESAGÜE

VENTILADORCENTRÍFUGO

AIRE NUEVO

AIRE EXTRAIDO

BATERÍAELÉCTRICA

BATERÍADE AGUA

NEW AIR

EXTRACTED AIR

Hea

t re

cove

ry u

nits

CA

DB

/T-D

CADB/t-D/DI/DC DP25 F7 standard configurations

CADB/t-DC

CADB-DC 05/08/18/30 AHCADT-DC 45/56 AH

CADB-DC 05/08/18/30 DHCADT-DC 45/56 DH

CADB-DC 05/08/18/30 EHCADT-DC 45/56 EH

CADB-DC 05/08/18/30 GHCADT-DC 45/56 GH

CADB-DC 05/08/18/30 CVCADT-DC 45/56 CV

CADB-DC 05/08/18/30 DVCADT-DC 45/56 DV

CADB-DC 05/08/18/30 EVCADT-DC 45/56 EV

Conf. AH Conf. DH Conf. EH Conf. GH

Conf. CV Conf. DV Conf. EV

HORIZONTAL

UPRIGHT

FILTRO

DESAGÜE

VENTILADORCENTRÍFUGO

AIRE NUEVO

AIRE EXTRAIDO

BATERÍAELÉCTRICA

BATERÍADE AGUA

NEW AIR

EXTRACTED AIR

Hea

t re

cove

ry u

nits

CA

DB

/T-D

CADB/t-D DP25 F7. Dimensions (mm)

A

E

a

b

ø1/2"

ø

D

h

C

B

A

E

a

b

ø1/2"

ø

D

h

C

B

Horizontal configuration (H)

Model A B C Ø D E a b h Weight(Kg)

CADB-D 05 640 640 345 200 172,5 175 120 265 200 32

CADB-D 08 820 820 360 250 180 220 120 265 200 44

CADB-D 18 1040 1040 535 315 315 275 120 265 200 91

CADB-D 30 1270 1270 630 355 360 332,5 120 265 200 125

CADT-D 45 1300 1200 855 450 427,5 315 200 400 650 171

CADT-D 56 1300 1200 855 450 427,5 315 200 400 650 176

Horizontal configuration (H) con by-pass (BP)

Model A B C Ø D E a b h Weight(Kg)

CADB-D 05 640 640 450 200 172,5 175 120 265 200 41

CADB-D 08 820 820 465 250 180 220 120 265 200 56

CADB-D 18 1040 1040 640 315 315 275 120 265 200 107

CADB-D 30 1270 1270 735 355 360 332,5 120 265 200 146

CADT-D 45 1300 1200 855 450 427,5 315 200 400 650 171

CADT-D 56 1300 1200 855 450 427,5 315 200 400 650 176

Electrical panel dimensions for all versions CADB-D/DC/DI Regulation with an electronic microprocessor (BASIC, PROGRAM, ADVANZ or DOMO).

* The electrical panel is installed in the side panel fan drive.

* The electrical panel is installed in the side panel fan drive.

Hea

t re

cove

ry u

nits

CA

DB

/T-D

CADB/t-D DP25 F7. Dimensions (mm)

C

D

ø1/2"

F

E

a

h

A

b

ø

B

100

C

D

ø1/2"

F

E

a

h

A

b

ø

B

100

A

b

C

D

ø

B

100

ø1/2"

F

E

a

h

A

b

C

D

ø

B

100

ø1/2"

F

E

a

h

Upright configuration (V)

Model A B C Ø D E F a b h Weight(Kg)

CADB-D 05 640 640 345 200 172,5 175 175 120 265 200 33

CADB-D 08 820 820 360 250 180 220 220 120 265 200 45

CADB-D 18 1040 1040 535 315 315 225 325 120 265 200 92

CADB-D 30 1270 1270 630 355 360 240 425 120 265 200 126

CADT-D 45 1300 1200 855 450 427,5 305 305 200 400 650 172

CADT-D 56 1300 1200 855 450 427,5 305 305 200 400 650 177

Upright configuration (V) con by-pass (BP)

Model A B C Ø D E F a b h Weight(Kg)

CADB-D 05 640 640 450 200 172,5 175 175 120 265 200 42

CADB-D 08 820 820 465 250 180 220 220 120 265 200 57

CADB-D 18 1040 1040 640 315 315 225 325 120 265 200 108

CADB-D 30 1270 1270 735 355 360 240 425 120 265 200 147

CADT-D 45 1300 1200 855 450 427,5 315 305 200 400 650 172

CADT-D 56 1300 1200 855 450 427,5 315 305 200 400 650 177

Electrical panel dimensions for all versions CADB-D/DC/DI Regulation with an electronic microprocessor (BASIC, PROGRAM, ADVANZ or DOMO).

* The electrical panel is installed in the side panel fan drive, can be positioned up, down, right or left (depending on configuration of the heat recovery).

* The electrical panel is installed in the side panel fan drive, can be positioned up, down, right or left (depending on configuration of the heat recovery).

Hea

t re

cove

ry u

nits

CA

DB

/T-D

CADB/t-DI-DC DP25 F7. Dimensions (mm)

A

b

ø1/2"

ø

øR

D

E

C

a

h

B

A

b

ø1/2"

øR

ø

D

E

C

a

h

B

Horizontal configuration (H)

Model A B C Ø D E ØR a b h Weight(Kg)

CADB-DI-DC 05 960 640 345 200 172,5 175 1/2" 120 265 200 40

CADB-DI-DC 08 1230 820 360 250 180 220 1/2" 120 265 200 56

CADB-DI-DC 18 1560 1040 535 315 315 275 1/2" 120 265 200 110

CADB-DI-DC 30 1905 1270 630 355 360 332,5 1" 120 265 200 155

CADT-DI-DC 45 1550 1200 855 450 427,5 315 1" 200 400 650 195

CADT-DI-DC 56 1550 1200 855 450 427,5 315 1" 200 400 650 200

Horizontal configuration (H) con by-pass (BP)

Model A B C Ø D E ØR a b h Weight(Kg)

CADB-DI-DC 05 960 640 450 200 172,5 175 1/2" 120 265 200 49

CADB-DI-DC 08 1230 820 465 250 180 220 1/2" 120 265 200 68

CADB-DI-DC 18 1560 1040 640 315 315 275 1/2" 120 265 200 126

CADB-DI-DC 30 1905 1270 735 355 360 332,5 1" 120 265 200 176

CADT-DI-DC 45 1550 1200 855 450 427,5 315 1" 200 400 650 195

CADT-DI-DC 56 1550 1200 855 450 427,5 315 1" 200 400 650 200

Electrical panel dimensions for all versions CADB-D/DC/DI Regulation with an electronic microprocessor (BASIC, PROGRAM, ADVANZ or DOMO).

* The electrical panel is installed in the side panel fan drive.

* The electrical panel is installed in the side panel fan drive.

Hea

t re

cove

ry u

nits

CA

DB

/T-D

CADB/t-DI-DC DP25 F7. Dimensions (mm)

A

b

ø

B

100

øR

C

D

ø1/2"

F

E

a

h

A

b

ø

B

100

øR

C

D

ø1/2"

F

E

a

h

Upright configuration (V)

Model A B C Ø D E F ØR a b h Weight(Kg)

CADB-DI-DC 05 960 640 345 200 172,5 175 175 1/2" 120 265 200 41

CADB-DI-DC 08 1230 820 360 250 180 220 220 1/2" 120 265 200 57

CADB-DI-DC 18 1560 1040 535 315 315 225 325 1/2" 120 265 200 111

CADB-DI-DC 30 1905 1270 630 355 360 240 425 1" 120 265 200 156

CADT-DI-DC 45 1550 1200 855 450 427,5 305 305 1" 200 400 650 196

CADT-DI-DC 56 1550 1200 855 450 427,5 305 305 1" 200 400 650 201

Upright configuration (V) con by-pass (BP)

Model A B C Ø D E F ØR a b h Weight(Kg)

CADB-DI-DC 05 960 640 450 200 172,5 175 175 1/2" 120 265 200 50

CADB-DI-DC 08 1230 820 465 250 180 220 220 1/2" 120 265 200 69

CADB-DI-DC 18 1560 1040 640 315 315 275 325 1/2" 120 265 200 127

CADB-DI-DC 30 1905 1270 735 355 360 332,5 425 1" 120 265 200 177

CADT-DI-DC 45 1550 1200 855 450 427,5 305 305 1" 200 400 650 196

CADT-DI-DC 56 1550 1200 855 450 427,5 305 305 1" 200 400 650 201

Electrical panel dimensions for all versions CADB-D/DC/DI Regulation with an electronic microprocessor (BASIC, PROGRAM, ADVANZ or DOMO).

* The electrical panel is installed in the side panel fan drive, can be positioned up, down, right or left (depending on configuration of the heat recovery).

* The electrical panel is installed in the side panel fan drive, can be positioned up, down, right or left (depending on configuration of the heat recovery).

Hea

t re

cove

ry u

nits

CA

DB

/T-D

0 100 200 300 400 500 600 Qv (m3/h)

0

50

100

150

200

250

300

350

400

PePa mmca

0

5

10

15

20

25

30

35

40

0

100

200

300

400

500

600

700

800Pabs ( W )

5052545658 Rend ( % )

V1

V2

V3

V1

V4

CADB-D/DI/DC 05

Performance curves

– Qv = Volume in m3/h.– Ps = Static pressure in mmwg and Pa– Pabs = Power absorbed at the maximum velocity (W).– Normal dry air at 20°C and 760 mmHg– Performance data in accordance with ISO 5801 and AMCA 210-99

Standards.

Additional pressure dropResistances: All 10 Pa models.Batteries: 05 Range 16Pa, 08 Range 13Pa, 18 Range 31Pa,

30 Range 27Pa, 45 Range 60Pa, 56 Range 100Pa.

CADB-D/DI/DC 18 CADB-D/DI/DC 30

CADT-D/DI/DC 45

Ps

Eff. (%)

mmWG

0 200 400 600 800 1000 1200 Qv (m3/h)

0

50

100

150

200

250

300

350

400

450

500

PePa mmca

0

5

10

15

20

25

30

35

40

45

50

300

400

500

600

700

800Pabs ( W )

535455565758596061 Rend ( % )

V1

V2

V3

V1

V4

CADB-D/DI/DC 08PsmmWG

0 1000 2000 3000 4000 5000 6000 7000 Qv (m3/h)

0

100

200

300

400

500

600

700

800

PePa mmca

0

10

20

30

40

50

60

70

80

0

1000

2000

3000

4000

5000

6000

7000

8000Pabs ( W )

63 60 59 58 56 54 53 52 Rend ( % )

CADB-D/DI/DC 56PsPs

PsPs

mmWGmmWG

mmWGmmWG

Eff. (%)

Eff. (%)

Eff. (%) Eff. (%)

Eff. (%)

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Acoustical characteristics

Mounting accessories

Lw, levels of noise transmitted in the inlet conduit and radiated in accordance with regulation EN ISO 3747.

AFRSpare filter

ModelSpare filter

Spare filter G4 Spare filter F7 Spare filter F9

CADB-D/DI/DC 05 AFR-D/DI/DC 05 G4 AFR-D/DI/DC 05 F7 AFR-D/DI/DC 05 F9

CADB-D/DI/DC 08 AFR-D/DI/DC 08 G4 AFR-D/DI/DC 08 F7 AFR-D/DI/DC 08 F9

CADB-D/DI/DC 18 AFR-D/DI/DC 18 G4 AFR-D/DI/DC 18 F7 AFR-D/DI/DC 18 F9

CADB-D/DI/DC 30 AFR-D/DI/DC 30 G4 AFR-D/DI/DC 30 F7 AFR-D/DI/DC 30 F9

CADT-D/DI/DC 45 AFR-D/DI/DC 45/56 G4 AFR-D/DI/DC 45/56 F7 AFR-D/DI/DC 45/56 F9

CADT-D/DI/DC 56 AFR-D/DI/DC 45/56 G4 AFR-D/DI/DC 45/56 F7 AFR-D/DI/DC 45/56 F9

Noise transmitted

CADB-D 05 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 21,5 17,5 15 27 16 7 4 29

LW V2 28,5 23,5 21 36 25 14 7 37

LW V3 33,5 29,5 27 42 33 23 15 43

LW V4 38,5 35,5 32 46 40 31 24 48

Noise radiated

CADB-D 05 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 15,5 13,5 12 23 13 6 4 25

LW V2 21,5 18,5 17 31 22 12 5 32

LW V3 26,5 23,5 22 36 28 20 12 37

LW V4 30,5 28,5 27 39 34 27 20 41

Noise transmitted

CADB-D 08 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 30,5 25,5 23 41 26 24 17 42

LW V2 36,5 33,5 31 47 36 34 29 48

LW V3 40,5 38,5 36 51 43 41 38 53

LW V4 43,5 41,5 40 53 47 45 41 55

Noise radiated

CADB-D 08 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 23,5 20,5 19 35 23 20 14 36

LW V2 28,5 27,5 26 40 31 29 25 41

LW V3 32,5 31,5 30 43 37 35 32 45

LW V4 34,5 33,5 33 45 40 38 35 48

Noise transmitted

CADB-D 18 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 49,5 48,5 57 62 59 53 43 65

LW V2 52,5 51,5 59 64 61 56 47 67

LW V3 51,5 53,5 61 65 63 59 20 69

Noise radiated

CADB-D 18 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 39,5 39,5 48 53 50 45 36 56

LW V2 42,5 42,5 50 54 52 48 40 58

LW V3 41,5 44,5 51 55 54 50 42 59

Noise transmitted

CADB-D 30 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 40,5 41,5 47 48 42 32 27 52

LW V2 53,5 50,5 60 64 62 58 47 68

LW V3 55,5 62,5 69 75 74 71 63 79

Noise radiated

CADB-D 30 125 250 500 1000 2000 4000 8000 dB(A)

LW V1 32,5 33,5 40 40 36 28 22 45

LW V2 42,5 41,5 51 54 53 49 40 58

LW V3 44,5 51,5 58 64 63 61 54 68

Noise transmitted

CADT-D 45 125 250 500 1000 2000 4000 8000 dB(A)

LW Vmax 66,5 67,5 67 69 64 65 54 75

Noise radiated

CADT-D 45 125 250 500 1000 2000 4000 8000 dB(A)

LW Vmax 62,5 61,5 61 63 58 57 41 69

Noise transmitted

CADT-D 56 125 250 500 1000 2000 4000 8000 dB(A)

LW Vmax 68,5 69,5 70 70 66 69 56 77

Noise radiated

CADT-D 56 125 250 500 1000 2000 4000 8000 dB(A)

LW Vmax 64,5 62,5 62 63 58 59 42 70

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Mounting accessories

MSOFlexible coupling

Model Flexible coupling

CADB-D/DI/DC 05 MSO-200

CADB-D/DI/DC 08 MSO-250

CADB-D/DI/DC 18 MSO-315

CADB-D/DI/DC 30 MSO-355

CADB-D/DI/DC 45 MSO-450

CADB-D/DI/DC 56 MSO-450

CAFIL*Filtering box

Model Filtering box

CADB-D/DI/DC 05 CAFIL-200

CADB-D/DI/DC 08 CAFIL-250

CADB-D/DI/DC 18 CAFIL-315

CADB-D/DI/DC 30 CAFIL-355

CADB-D/DI/DC 45 CAFIL-450

CADB-D/DI/DC 56 CAFIL-450

APCInlet/discharge protection guards

Model Inlet/discharge protection guards

CADB-D/DI/DC 05 APC-200

CADB-D/DI/DC 08 APC-250

CADB-D/DI/DC 18 APC-315

CADB-D/DI/DC 30 APC-355

CADB-D/DI/DC 45 APC-450

CADB-D/DI/DC 56 APC-450

SILSound attenuators to mount at theinlet and/or discharge of the heatrecovery units

Model Sound attenuator

CADB-D/DI/DC 05 SIL-200

CADB-D/DI/DC 08 SIL-250

CADB-D/DI/DC 18 SIL-315

CADB-D/DI/DC 30 SIL-355

CADB-D/DI/DC 45 SIL-450

CADB-D/DI/DC 56 SIL-450

TPP D-H

TPP D-V

TPP DI/DC-H

TPP DI/DC-V

Model Rain Cap

CADB-D 05 H TPP D-H 05

CADB-D 08 H TPP D-H 08

CADB-D 18 H TPP D-H 18

CADB-D 30 H TPP D-H 30

CADT-D 45 H TPP D-H 45/56

CADT-D 56 H TPP D-H 45/56

Model Rain Cap

CADB-D 05 V TPP D-V 05

CADB-D 08 V TPP D-V 08

CADB-D 18 V TPP D-V 18

CADB-D 30 V TPP D-V 30

CADT-D 45 V TPP D-V 45/56

CADT-D 56 V TPP D-V 45/56

Model Rain Cap

CADB-DI/DC 05 H TPP DI/DC-H 05

CADB-DI/DC 08 H TPP DI/DC-H 08

CADB-DI/DC 18 H TPP DI/DC-H 18

CADB-DI/DC 30 H TPP DI/DC-H 30

CADT-DI/DC 45 H TPP DI/DC-H 45/56

CADT-DI/DC 56 H TPP DI/DC-H 45/56

Model Rain Cap

CADB-DI/DC 05 V TPP DI/DC-V 05

CADB-DI/DC 08 V TPP DI/DC-V 08

CADB-DI/DC 18 V TPP DI/DC-V 18

CADB-DI/DC 30 V TPP DI/DC-V 30

CADT-DI/DC 45 V TPP DI/DC-V 45/56

CADT-DI/DC 56 V TPP DI/DC-V 45/56

TTP D/DI/DC BPTo heat recovery horizontal with by-pass

Model Rain Cap

CADB-D 05 H BP TPP D-H 05 BP

CADB-D 08 H BP TPP D-H 08 BP

CADB-D 18 H BP TPP D-H 18 BP

CADB-D 30 H BP TPP-D-H 30 BP

CADB-DI/DC 05 H BP TPP-DI/DC-H 05 BP

CADB-DI/DC 08 H BP TPP-DI/DC-H 08 BP

CADB-DI/DC 18 H BP TPP-DI/DC-H 18 BP

CADB-DI/DC 30 H BP TPP-DI/DC-H 30 BP

TPPExternal rain protection canopy

SIFÓN RECUPERADORES*Drain water drainage of the heat recovery

See complete information on the HEAT RECOVERY ACCESSORIES.

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Versions CADB-D 05 H to 30 Hwith by-pass

Model A B

CADB-D 05 V 610 900

CADB-D 08 V 640 1110

CADB-D 18 V 900 1400

CADB-D 30 V 1100 1750

CADT-D 45 V 1230 1710

CADT-D 56 V 1230 1710

AB

Versions CADB/T-D V with and without by-pass

Versions CADB-DI/DC 05 H to 30 Hwith by-pass

Versions CADB-DI/DC 05 H to 30 Hwithout by-pass

Versions CADT-DI/DC 45 H and 56H with and without by-pass

Model A B

CADB-DI/DC 05 V 610 1220

CADB-DI/DC 08 V 640 1530

CADB-DI/DC 18 V 900 1920

CADB-DI/DC 30 V 1100 2395

CADT-DI/DC 45 V 1230 1960

CADT-DI/DC 56 V 1230 1960

A

B

Versions CADB/T-DI/DC Vwith and without by-pass

AB

Model A B

CADB-D 05 H 770 770

CADB-D 08 H 980 980

CADB-D 18 H 1270 1270

CADB-D 30 H 1570 1570

CADT-D 45 H 1630 1730

CADT-D 56 H 1630 1730

Versions CADB-D 05 H to 30 Hwithout by-pass

Versions CADT-D 45 H and56 H with and without by-pass

External rain protection canopyincorporates 4 side panels

AB

Model A B

CADB-DI/DC 05 H 770 1090

CADB-DI/DC 08 H 980 1400

CADB-DI/DC 18 H 1270 1790

CADB-DI/DC 30 H 1570 2215

CADT-DI/DC 45 H 1630 1980

CADT-DI/DC 56 H 1630 1980

External rain protection canopyincorporates 4 side panels

Mounting accessories

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Electrical accessories

RQA3Automatic speed adjustment according toCO2 concentration.Works together with a CO2 probe(SCO2-A 1/10V ambient and, SCO2-AD orin the SCO2-G conduit).Only for 05 and 08 models.

Model Variable frequency drive Sensor

CADB-D/DI/DC 05 RQA3 SCO2-A / SCO2-AD / SCO2-G

CADB-D/DI/DC 08 RQA3 SCO2-A / SCO2-AD / SCO2-G

CADB-D/DI/DC 18 VAPZ-11 SCO2-A / SCO2-AD / SCO2-G

CADB-D/DI/DC 30 VAPZ-11 SCO2-A / SCO2-AD / SCO2-G

CADB-D/DI/DC 45 VFTM TRI 2,2 SCO2-A / SCO2-AD / SCO2-G

CADB-D/DI/DC 56 VFTM TRI 4 SCO2-A / SCO2-AD / SCO2-G

Accessories for the Variable Air Volume System by CO2 Accessories for Constant Pressure operation

VFTM TRIVariable frequency drive enabling the fanspeed to be modified according to CO2 con-centration.Works together with a CO2 probe (SCO2-Aambient and SCO2-AD or in the SCO2-Gconduit).Only for 45 and 56 models.

Model Variable frequency drive Sensor

CADB-D/DI/DC 05 Pack PR 5A 0-300Pa Included

CADB-D/DI/DC 08 Pack PR 5A 0-300Pa Included

CADB-D/DI/DC 18 Pack PR 11A 0-800Pa Included

CADB-D/DI/DC 30 Pack PR 11A 0-800Pa Included

CADB-D/DI/DC 45 VFTM TRI 2,2 TDP-S / TDP-D

CADB-D/DI/DC 56 VFTM TRI 4 TDP-S / TDP-D

VAPZ-11Controller, enabling the fan speed to bemodified according to CO2 concentration.Maximum current 11A.Works together with a CO2 probe (SCO2-Aambient and, SCO2-A and SCO2-AD or inthe SCO2-G conduit).Only for 18 and 30 models.

Model Electricalsupply

Maximum current

(A)

Voltage

(V)

IP Operatingtemperature

range

Dimensions LxAxH (mm)

VAPZ-11 230V-50Hz 11 110-230 IP55 -10 to +50 205x115x92

Pack PRVoltage regulator for single-phase motors with pressure probe included for control of constant pressure systems.

Model Electricalsupply

Maximumcurrent

(A)

Voltage

(V)

IP Operatingtemp. range

DimensionsLxAxH(mm)

Pack PR 5A 230V-50/60Hz 5 110-230 IP55 -10 to +50 176x200x80

Pack PR 11A 230V-50/60Hz 11 110-230 IP55 -10 to +50 176x200x80

SCO2-G 0/10 VCO2 sensor probe for duct mounting.Enable control of the ventilation in ductworkaccording to the CO2 concentration of the aircirculating through it.

For controlled equipment only a 0-10 V probe can be connected.

Model Electricalsupply

Power

(W)

Voltage

(V)

IP CO2range(pm)

Dimensions LxAxH (mm)

SCO2-G 0/10 V

24VDC-24VAC 5 0-10 Box IP65 0-2000 80x238x80

TDP-S / TDP-DPressure sensor.Enables you to control the pressure in thefan inlet.

TDP-SStandard pressure sensor.TDP-DPressure sensor, with display.

Model Electricalsupply

Maximumpower

(VA)

ØConnectors

(mm)

Voltage IP Pressurerange(Pa)

DimensionsLxAxH(mm)

TDP-S24VAC-24VDC 4 6,2

0-10 V / 4-20 mA

IP54 0-2500 75x36x80TDP-D

SCO2-A 0/10 VAmbient CO2 and temperature sensor.Enables control of the ventilation in sectionsof conduit according to the temperatureand relative humidity of the air circulatingthrough it or to the temperature.

SCO2-ADAmbient CO2 and temperature sensorwith display.Enable control of the ventilation ductworkaccording to the temperature and relativehumidity of the air circulating through it or tothe temperature.

Model Electricalsupply

Power

(W)

Voltage Heightinstal.

(m)

IP CO2range(pm)

Temperaturerange(ºC)

Dimensions LxAxH (mm)

SCO2-A 0/10 V 24VDC-

24VAC 5

0-10V1,5-3,5 IP20 0-2000 0-50 85x26x100

SCO2-AD 4-20mA

Hea

t re

cove

ry u

nits

CA

DB

/T-D

COM3 / COM43 and 4 speed switch

Model Switch Maximum current (A)

CADB-D/DI/DC 05 COM4 12

CADB-D/DI/DC 08 COM4 12

CADB-D/DI/DC 18 COM3 20

CADB-D/DI/DC 30 COM3 20

Electrical accessories

SQAAutomatically switches the fan on when the quality of the ambient air deteriorates below an acceptable level due to fumes, odours, tobacco, smoke or dampness etc…Adjustable run-on-timer facility which enables the fan to operate for a pre-selected time period after the air quality sensor has switched off.Important: this sensor must not be used to detect combustible gases or fires ans in con-nection with any safety alarm systems.

IP protection

Class Maximumcurrent

(A)

Operatingtemperature

(ºC)

Timeradjustment

IP21 II ( ) 2* 0-50 1-25 min.

* For inductive loads.

PULSER Electronic controller to regulate the heat output for single phase electric heater battery up to 16A, in order to maintain a constant pre-select-ed temperature.Depending on the selected temperature, the controller pulses the entire power output anduses a time-proportional control to main-tain that temperature. The PULSER incorpo-rates a built-in room temperature sensor with an input for external sensor. IP-30. Maximum heaterpower 3,6kW.

PULSER-ADDSupplementary unit for slave control fromanother PULSER to control batteries withpower ratings superior to the PULSERcapacity (3600W -16A- 230V).

TTC-25Electronic controller to regulate the heat output for three phase electric heater battery up to 25A, in order to maintain a constant pre-selected temperature.Depending on the selected temperature, thecontroller pulses the entire power output and uses a time-proportional control to maintain that temperature. The TTC-25 is designed to be fitted in a cabinet on DIN-rail. IP-20.

TG-R430Room sensor with set point adjustmentbetween 0 and +30ºC.

PULSER MElectronic controller similar to the PULSER, incorporating in addition, input for an external duct sensor to control minimum or maximum temperature limitations. IP-30. Maximum hea-terpower 3,6kW.

PULSER DElectronic controller to regulate the heat out-put for single phase electric heater battery up to 16A, in order to maintain a constant pre-selected temperature.Depending on the selected temperature, the controller pulses the entire power output and uses a time-proportional control to maintain that temperature. The PULSER D is designed to be fitted in a cabinet on DIN-rail. IP-20. Maximum heater power 3,6kW.).

TBI-10Potentiometer mounted on the main board panel for setting temperature between -20 and +10ºC. Used with the PULSER-D or TTC-25 mounted within cabinet, to set the minimum air temperature before entering in the heat exchanger.

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Electrical accessories

MCR-1Timer with set point between 1 sec and 100 h.Used in an electric heating system to delay the fan switch off after disconnecting the system.

TBI-30Potentiometer mounted on the main board panel for setting temperature between 0 and +30ºC. Used with the Pulser-D and with a TTC-25 duct sensor to set the air temperatu-re after the electric battery in post heatingoperation.

TRANSFORMER CADB/T-DCTransformer 200V / 24V AC for vales supply.

PRESSURE SWITCH DPS 2-30Differential pressure switch to control the fan running and the filter clogging up. Workingpressure range from 2 to 30 mmWG.

TG-K310, TG-K330 and TG-K360Duct temperature sensor.Temperature range:TG-K310 from -20 to 10ºCTG-K330 from 0 to 30ºCTG-K360 from 0 to 60ºC

3WV CADB/T-DC*Motorized 3-way valves.

* See complete information on the HEAT RECOVERY ACCESSORIES.

Model Valve DN (mm)

DN (")

Kvs (m3/h)

CADB-D/DI/DC 05 3 WV CADB-DC 05/30 15 1/2 2,5

CADB-D/DI/DC 08 3 WV CADB-DC 08/18 15 1/2 1,6

CADB-D/DI/DC 18 3 WV CADB-DC 08/18 15 1/2 1,6

CADB-D/DI/DC 30 3 WV CADB-DC 05/30 15 1/2 2,5

CADT-D/DI/DC 45 3 WV CADT-DC 45/56 20 3/4 6,3

CADT-D/DI/DC 56 3 WV CADT-DC 45/56 20 3/4 6,3

Hea

t re

cove

ry u

nits

CA

DB

/T-D

Ambient temperature and inlet air temperature control

Heat recovery CADB/T-D DP25 F7Electric heating batteries with built-in temperature control to fit on versions CADB/T-D: consists of electric resistances, conduit probe, electric battery regulator and internal potentiometer.

Heat recovery CADB/T-DI DP25 F7Control elements needed for managing the operation of the built-in resistances in the heat exchangers.

* The ADD Pulser should be installed with the M Pulser when the power exceeds 3.6 kW.

Model Heat recovery Ø(mm)

Power(W)

Voltage Nº stages Minimum airflow (m3/h)

ABE-SCT 200M CADB-D 05 200 2.000 230V-1-50Hz 1 170

ABE-SCT 250M CADB-D 08 250 4.000 230V-1-50Hz 2 270

ABE-SCT 315M CADB-D 18 315 6.000 230V-1-50Hz 2 430

ABE-SCT 355T CADB-D 30 355 8.000 400V-3-50Hz 2 560

ABE-SCT 450T CADT-D 45 450 12.000 400V-3-50Hz 2 710

ABE-SCT 500T CADT-D 56 450 12.000 400V-3-50Hz 2 1870

Built-in electric heaterAir ambient temperature control

Supply airtemperature

controlOptional

Controller in room Controller within cabinet (Din-rail) Duct sensorto limit

supply airtemperature

0/60ºC

Externalpotentiometer

on cabinet0/30ºC

TimerModel Supply

Power(kW)

Nº of stage

Electriccontroller

Controllerwith Min/Max

limitingsensor

Adjust.room

sensor0/30ºC

Electriccontroller

Duct sensor 0/30ºC

CADB-DI 05 Single phase 230V 2 1 PULSER PULSER M TG-R430 PULSER D TG-K330 TG-K360 TBI-30 MCR-1

CADB-DI 08 Single phase 230V 4 2 PULSER + P.ADD* PULSER + P.ADD* TG-R430 PULSER D + P.ADD* TG-K330 TG-K360 TBI-30 MCR-1

CADB-DI 18 Single phase 230V 6 2 PULSER + P.ADD* PULSER + P.ADD* TG-R430 PULSER D + P.ADD* TG-K330 TG-K360 TBI-30 MCR-1

CADB-DI 30 Three phase 400V 8 2 - - TG-R430 TTC-25 TG-K330 TG-K360 TBI-30 MCR-1

CADT-DI 45 Three phase 400V 12 2 - - TG-R430 TTC-25 TG-K330 TG-K360 TBI-30 MCR-1

CADT-DI 56 Three phase 400V 12 2 - - TG-R430 TTC-25 TG-K330 TG-K360 TBI-30 MCR-1

Installation with externalelectric heater Electric

heater type

Defrosting operation control(Heat exchanger protection)

Supply air temperature control

Model SupplyØ

(mm)Power(kW)

Electric heaterDuct

sensor -20/10ºC

Externalpotentiometer

-20/30ºCElectric heater

Duct sensor 0/30ºC

Externalpotentiometer

0/30ºC

CADB-D 05 Single phase 230V 200 2,1 ABE-200/2M PULSER D TG-K310 TBI-10 PULSER D TG-K330 TBI-30

CADB-D 08 Single phase 230V 250 3 ABE-250/3M PULSER D TG-K310 TBI-10 PULSER D TG-K330 TBI-30

CADB-D 18 Single phase 230V 315 4 ABE-315/4M PULSER D + P.ADD TG-K310 TBI-10 PULSER D + P.ADD TG-K330 TBI-30

CADB-D 30 Three phase 400V 400 6 ABE-355/60T TTC-25 TG-K310 TBI-10 TTC 25 TG-K330 TBI-30

CADT-D 45 Three phase 400V 400 9 ABE-400/90T TTC-25 TG-K310 TBI-10 TTC 25 TG-K330 TBI-30

CADT-D 56 Three phase 400V 400 9 ABE-400/90T TTC-25 TG-K310 TBI-10 TTC 25 TG-K330 TBI-30

Hea

t re

cove

ry u

nits

CA

DB

/T-D

The heater battery operation must be enslaving to the fan operation. The installation must include a pressure switch to switch off the electricheater battery supplies in case of fan failure.

Electric heater batteries

Accessories for air treatment

ABE-SCT*Electric heating batteries with built-in electronic temperature control.

BA-AF*External coil module for cold water.

ABE*Electric heater batteriesFunctions:- Defrosting operation.- Post heating operation.

HUMC*Adiabatic cooling module.

* See complete information on the HEAT RECOVERY ACCESSORIES.

Model Electric heater batteries

CADB-D/DI/DC 05 ABE-200/2M

CADB-D/DI/DC 08 ABE-250/3M

CADB-D/DI/DC 18 ABE-315/4M

CADB-D/DI/DC 30 ABE-355/60T

CADT-D/DI/DC 45 ABE-400/90T

CADT-D/DI/DC 56 ABE-400/90T

Model Adiabatic cooling module

CADB-D/DI/DC 05 HUMC-05

CADB-D/DI/DC 08 HUMC-08

CADB-D/DI/DC 18 HUMC-18

CADB-D/DI/DC 30 HUMC-30

CADT-D/DI/DC 45 HUMC-45

CADT-D/DI/DC 56 HUMC-56

Model External coil module

CADB-D/DI/DC 05 BA-AF 05

CADB-D/DI/DC 08 BA-AF 08

CADB-D/DI/DC 18 BA-AF 18

CADB-D/DI/DC 30 BA-AF 30

CADT-D/DI/DC 45 BA-AF 45

CADT-D/DI/DC 56 BA-AF 56

BA-AC*External coil module for hot water.

Model External coil module

CADB-D/DI/DC 05 BA-AC 05

CADB-D/DI/DC 08 BA-AC 08

CADB-D/DI/DC 18 BA-AC 18

CADB-D/DI/DC 30 BA-AC 30

CADT-D/DI/DC 45 BA-AC 45

CADT-D/DI/DC 56 BA-AC 56