concrete specification

28
Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I March 2015 Tender Documents Page 4/3 SECTION 4 - CONCRETE WORKS Concrete work shall consist of furnishing all materials and constructing structures of the forms, shapes and dimensions shown on the Drawings or as directed in accordance with the details shown on the Drawings and these Specifications. 4/1 CEMENT SULPHATE RESISTING CEMENT 4/1.1 Sulphate Resisting Cement shall comply with BS EN 197-1:2011, Class 42.5N or ASTM C150/C150M-2012 Type V. In addition the cement shall comply with the following:- The acid soluble alkali level measured as (Na 2 O+0.658 K 2 O) shall not exceed 0.6% by weight determined in accordance with BS EN 196-2 : 2005 The heat of hydration shall not exceed 290 KJ/Kg at 7 days when tested in accordance with BS 4550: Part 3 Section 3.8. The specific surface shall be not greater than 375 m²/Kg and not less than 280 m²/Kg when tested as described in BS EN 196: Part 6: 1992. The chloride content shall not exceed 0.1% when tested in accordance with Clause 4 of BS EN 196-2 : 2005 The tricalcium aluminate content shall be 3.5% max when tested according to the method BS EN 196-2 : 2005 ORDINARY PORTLAND CEMENT 4/1.2 Ordinary Portland Cement shall conform to the requirements of BS EN 197-1:2011, Class 42.5N or ASTM C150 Type I and with the following amendments:- The acid soluble alkali level measured as (Na 2 O+0.658 K 2 O) shall not exceed 0.6% by weight determined in accordance with in BS EN 196-2 2013. The heat of hydration shall not exceed 290 KJ/Kg at 7 days when tested in accordance with BS 4550: Part 3 Section 3.8. Contain not less than 4% and not more than 8% proportion of tricalcium aluminate by weight when tested according to the method BS EN 196-2 : 2013. Contain less than 2.7% proportion of Sulphur Trioxide by weight according to the method ASTM C563-13 or ASTM C114-2013. The specific surface (fineness) shall be not greater than 375 m²/Kg and not less than 280 m²/Kg when tested as described in BS EN196 : Part 6: 2010.

Upload: asad-jamil-jawanda

Post on 23-Jan-2016

319 views

Category:

Documents


0 download

DESCRIPTION

r1041

TRANSCRIPT

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/3

SECTION 4 - CONCRETE WORKS Concrete work shall consist of furnishing all materials and constructing structures of the forms, shapes and dimensions shown on the Drawings or as directed in accordance with the details shown on the Drawings and these Specifications. 4/1 CEMENT SULPHATE RESISTING CEMENT 4/1.1 Sulphate Resisting Cement shall comply with BS EN 197-1:2011, Class 42.5N

or ASTM C150/C150M-2012 Type V. In addition the cement shall comply with the following:-

The acid soluble alkali level measured as (Na2O+0.658 K2O) shall not

exceed 0.6% by weight determined in accordance with BS EN 196-2 : 2005

The heat of hydration shall not exceed 290 KJ/Kg at 7 days when tested in accordance with BS 4550: Part 3 Section 3.8.

The specific surface shall be not greater than 375 m²/Kg and not less than

280 m²/Kg when tested as described in BS EN 196: Part 6: 1992. The chloride content shall not exceed 0.1% when tested in accordance

with Clause 4 of BS EN 196-2 : 2005 The tricalcium aluminate content shall be 3.5% max when tested according

to the method BS EN 196-2 : 2005 ORDINARY PORTLAND CEMENT 4/1.2 Ordinary Portland Cement shall conform to the requirements of BS EN

197-1:2011, Class 42.5N or ASTM C150 Type I and with the following amendments:- The acid soluble alkali level measured as (Na2O+0.658 K2O) shall not

exceed 0.6% by weight determined in accordance with in BS EN 196-2 2013.

The heat of hydration shall not exceed 290 KJ/Kg at 7 days when tested in

accordance with BS 4550: Part 3 Section 3.8. Contain not less than 4% and not more than 8% proportion of tricalcium

aluminate by weight when tested according to the method BS EN 196-2 : 2013.

Contain less than 2.7% proportion of Sulphur Trioxide by weight according

to the method ASTM C563-13 or ASTM C114-2013. The specific surface (fineness) shall be not greater than 375 m²/Kg and not

less than 280 m²/Kg when tested as described in BS EN196 : Part 6: 2010.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/4

The chloride content shall not exceed 0.1% when tested in accordance with Clause 4 of BS EN 196-2: 2013.

For any type of cement, the following physical & mechanical test shall also

to be included:

o Consistency in accordance with BS EN 196-3:2008. o Setting time in accordance with BS EN 196-3:2008 o Soundness in accordance with BS EN 196-3:2008. o Compressive strength in accordance with BS EN 196-1:2005

Requirements of Cementatious Supplementary Materials (CSM) If fly ash is recommended for concrete works, it shall conform to the requirements of ASTM C618-12 or BS EN 450-1:2012. If Ground Granulated Blast Furnace Slag (GGBS) and blended cement is recommended for concrete works, it shall conform to the requirements of following standard specifications: ASTM C595/C595M-07 ASTM C989/C989M-14

MODERATE SULPHATE RESISTING PORTLAND CEMENT 4/1.3 Moderate sulphate resisting Portland Cement shall comply with ASTM C150

Type II. It shall also comply with Clause 4/1.2. In addition the cement shall comply with the following:- The acid soluble alkali level measured as (Na2 0+0.658 K2 0) shall not

exceed 0.6% by weight determined in accordance with BS EN196 – 2 2005

The specific surface (fineness) shall not be greater than 375 sq.m/Kg and not less than 280 sq.m/Kg when tested as described in BS EN 196: Part 6: 1992.

The chloride content shall not exceed 0.1% when tested in accordance

with Clause 4 of BS EN 196-2 : 2005

Contain not less than 4% and not more than 8% proportion of tricalcium aluminate by weight when tested according to the method BS EN 196-2 : 2005

Contain less than 2.7% proportion of Sulphur trioxide by weight For any type of cement, the following physical & mechanical test shall also be included: Consistency in accordance with BS EN 196-3: 2008

Setting time in accordance with BS EN 196-3: 2008

Soundness in accordance with BS EN 196-3: 2008

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/5

Compressive Strength BS EN 196-1: 2005 Mechanical and physical requirements given as characteristic values

Strength Class

Compressive Strength MPa Initial Setting Time min.

Soundness (expansion)

mm Early Strength Standard Strength

2 days 7 days 28 days

32.5 N - ≥ 16.0 ≥ 32.5

≤ 52.5

≥ 75

≤ 10

32.5 R ≥ 10.0 -

42.5 N ≥ 10.0 ≥ 42.5 ≤ 62.5 ≥ 60

42.5 R ≥ 20.0 -

52.5 N ≥ 20.0 - ≥ 52.5 ≥ 45

52.5 R ≥ 30.0 -

GENERAL

4/1.4 Each cement batch shall bear manufacturer's name and batch number. Type

of cement shall be the same as mentioned in the approved analysis report. Each separate consignment of cement shall be tested by the manufacturer before delivery and certified copies of such tests shall be supplied to the Engineer before any part of the consignment is used in the works. The Engineer reserves the right to order a re-test of cement at any time. Approval of cement does not relieve the Contractor of the responsibility to produce concrete of the specified strength.

4/1.5 Cement shall be delivered to site in bulk, or with the Engineer's approval, may

be supplied in sealed bags which shall bear the manufacturer's name and the date of manufacture. Each consignment shall be accompanied by a copy of the manufacturer's batch test certificate and certificate of guarantee.

4/1.6 Each consignment of cement shall be kept separate, identified and used in

order of delivery. 4/1.7 Any consignment not used within 2 months from the date of manufacture will

not be allowed to be used in the works. 4/1.8 One brand only of cement as approved by the Engineer shall be used

throughout the works unless otherwise authorized by the Engineer in writing. 4/1.9 Each cement batch shall bear manufacturer’s name and batch number

• Type of cement shall be the same as mentioned in the approved analysis report.

• Each separate consignment shall be tested by manufacture before delivery.

• Certified copies of batch test certificate and certificate of guarantee shall be supplied to the Engineer before any part of the consignment is used in the works.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/6

• The Engineer reserves the right to order a re-test of cement at any time

• Approval of cement does not relieve the Contractor of the responsibility to produce concrete of the specified strength.

• Cement shall be delivered to site in bulk, or with the Engineer’s approval, may be supplied in sealed bags bearing manufacturer’s name and date of manufacture.

• Each consignment shall be kept separate, identified and used in order of delivery.

• Any consignment not used within 2 months from the date of manufacture will not be allowed to be used in the works.

4/2 AGGREGATES GENERAL REQUIREMENTS 4/2.1 Except as may be modified hereunder the aggregate (fine and coarse) for all

types of concrete shall comply in all respects with BS 882 "Concrete aggregates from natural sources" and the fine aggregate shall also comply with Dubai Municipality Administrative Order No. 143/91.

4/2.2 The aggregates used in the permanent works shall be naturally occurring or

crushed materials obtained only from approved sources. 4/2.3 Before any material from a particular source is used, the Contractor shall

obtain representative samples of fine and coarse aggregates and carry out the necessary tests and analyses to show that the samples comply with the Specification. During the progress of the works, the grading and chemical characteristics may be checked at frequent intervals.

4/2.4 The results of these tests, etc. shall be submitted to the Engineer and his

approval shall be obtained before any of the material is used in the works. Part of each sample will be required for concrete trial mixes and part shall be retained for comparison with subsequent deliveries.

4/2.5 Sampling for testing and analysis shall be carried out, where applicable, in accordance with BS 812 Part 102:1989.

4/2.6 The maximum size of the aggregate shall not be larger than 1/5 of the narrowest dimension between sides of the member for which the concrete is to be used and not larger than 3/4 of the maximum clear distance between reinforcing bars.

4/2.7 Fine aggregate shall be natural or crushed sand and beach sand shall not be permitted for use in concrete mixes.

4/2.8 Coarse aggregate shall be crushed aggregate obtained from a quarry approved by the Engineer.

4/2.9 Unless otherwise authorized by the Engineer coarse aggregate shall be delivered to site in separate sizes according to the maximum specified aggregate size for each grade of concrete.

4/2.10 Aggregates shall meet the requirements of Table 4.1.

4/2.11 The frequency of testing of aggregates shall be in accordance with Table 4.2 or as directed by the Engineer.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/7

TABLE 4.1: LIMITS FOR PHYSICAL, CHEMICAL AND MECHANICAL PROPERTIES OF AGGREGATES FOR CONCRETE

TEST METHODS PERMISSIBLE LIMITS SR. KIND OF REQUIREMENT ---------------------- ----------------------------------- NO. BS 812 / ASTM FINES COARSE

1. Grading BS EN 933-1:

2012 (Dry) Standard Standard

2. Material finer Than 0.075 mm BS EN 933-

1:2012 or ASTM C117:2004 (Wet)

Natural, uncrushed/ crushed max.3% max.1% Crushed rock max.7% max.1% 3. Clay lumps and friable particles C142/C142M:

2010 max.1% max.1%

4. Light weight pieces C123 max.0.5% max.0.5% 5. Organic impurities for

fine aggregate C40 : 2004 The color of

the Supernatant liquid is lighter than standard color solution

6. Water absorption C128 : 2012a C128 : 2012

max.2.3% max.2.0%

7. Specific Gravity C128 : 2012a

C128 : 2012 min.2.60 min.2.60

(apparent) 8. Shell content in

aggregates BS EN 933-7:1998

Coarser than 10 mm max.5% Between 5mm-10mm Max.15% 9. Particle shape BS 812:90 Flakiness index Part 105 :

Section 105.1 max.25

Elongation index Part 105 : Section 105.2

max.25

The index shall be max.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/8

TABLE 4.1: LIMITS FOR PHYSICAL, CHEMICAL AND MECHANICAL PROPERTIES OF AGGREGATES FOR CONCRETE

TEST METHODS PERMISSIBLE LIMITS SR. KIND OF REQUIREMENT ---------------------- ----------------------------------- NO. BS 812 / ASTM FINES COARSE

25 for combined aggregates but should not exceed more than 30 for individual sizes.

9a. Partially crushed faces

of coarse aggregate with at least one crushed face.

DMS 8 : 2001 100%.

10. Acid soluble Part 117, Chlorides, CL Appendix C For reinforced concrete made with SRPC cements max.0.03% max.0.01% OPC & MSRPC

cements max.0.03% max.0.02%

For mass concrete Made with SRPC cements max.0.03% max.0.02% OPC & MSRPC

cements max.0.03% max.0.04%

For prestressed concrete & steam Cured structural concrete max.0.03% max.0.01% 11. Acid soluble sulphates, S03 BS EN 1744-

1:1998 max.0.3% max.0.3%

12. Soundness, MgS04 (5 cycles) C88 : 2013 max.12% max.12% 13. Mechanical strength 10% fines value Part 111 min100KN or Impact value Part 112 max.30% Los Angeles Abrasion C131 : 2014

C535 : 2014 max.30%

14. Drying Shrinkage Part 120 max.0.05% 15. Potential reactivity,

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/9

TABLE 4.1: LIMITS FOR PHYSICAL, CHEMICAL AND MECHANICAL PROPERTIES OF AGGREGATES FOR CONCRETE

TEST METHODS PERMISSIBLE LIMITS SR. KIND OF REQUIREMENT ---------------------- ----------------------------------- NO. BS 812 / ASTM FINES COARSE

Note 2 Of Aggregates, Chemical Method C289 Innocuous Innocuous Of Cement-Aggregate Combination C227 6 month

expansion

0.10% max.

Note 1 : There is no requirement of shell content in sands passing 4 mm

sieve size. Note 2 : Aggregates may initially be assessed for its reactivity in accordance

with ASTM C289 and if potential reactivity is indicated, then mortar bar tests in accordance with ASTM C227 shall be carried out.

TABLE 4.2: FREQUENCY OF ROUTINE TESTS ON AGGREGATES

SR. KIND OF REQUIREMENT - TEST FREQUENCY RATE NO. TEST METHOD

1. Grading - BS EN 933-1:1997 Per 1,000m3 2. Material finer than 0.075 mm - - do - BS EN 933-1 or ASTM C117:2004 3. Clay lumps and Friable Particles Per 4,000m3 - ASTM C 142 4. Organic impurities ASTM C 40 Per 2,000m3 5. Water absorption - ASTM C128 :

2007/C127 : 2007 - do -

6. Specific Gravity - ASTM C128 : 2007/C127

: 2007 - do -

7. Shell content - BS EN 933-7:1998 - do - 8. Particle shape BS 812 :1990 Section 105 - do -

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/10

TABLE 4.2: FREQUENCY OF ROUTINE TESTS ON AGGREGATES

SR. KIND OF REQUIREMENT - TEST FREQUENCY RATE NO. TEST METHOD

Part 105.1.& Section 105 Part 105.2 9. Acid soluble chlorides, CL Qualitative-BS 812 : 1988 Part 117 Per 1,000m3 Appendices A/B Quantitative-BS 812 : 1988 Part 117 Each 12 concrete Appendix C days if result is more than 75% of the limit and each month if result is less than 75% of the limit. 10. Acid soluble sulphates,

S03 - BS EN 1744-1:1998 Per 1000 M3 or Each 24 concrete days if

result is more than 75% of the limit & each 2 months if result is less than 75% of the limit which ever is less 11. Soundness, Mg S04 (5 cycles) Each 48 concrete ASTM C88 : 2005 Days or 2,000 m3 12. Mechanical Strength 10% Fines or impact value Each 72 concrete - BS 812 Parts 111, 112 Days or 4,000 m3 Los Angeles abrasion - - do - ASTM C 131/C 535 13. Moisture variation in sand - by Twice daily Moisture Meters 14. Drying Shrinkage At the start of the project BS 812 Part 120 and whenever there is a change in the source of supply. 15. Potential Reactivity: At the start of the project of aggregates and wherever there is a (ASTM C 295, C 289) change in the source of Supply of Carbonate (ASTM C 586)

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/11

TABLE 4.2: FREQUENCY OF ROUTINE TESTS ON AGGREGATES

SR. KIND OF REQUIREMENT - TEST FREQUENCY RATE NO. TEST METHOD

of Cement aggregate combination (ASTM P214 and C 227) 16 Light weight pieces test (ASTM C 123) Per 2,000 m3

Note : Drying Shrinkage and potential reactivity of aggregates shall be

determined initially at the start of the project or whenever there is a change in the source of supply.

4/3 FINE AGGREGATES 4/3.1 The gradation of fine aggregate shall be in accordance with BS 882 latest

edition. 4/3.2 Each batch of aggregate delivered to site shall be kept separate from previous

batches and shall be stored for at least 3 (three) working days before use to allow inspection and tests to be carried out.

4/3.3 Fine Aggregate shall be clean sharp natural and/or crushed sand. 4/3.4 The Contractor shall mechanically wash aggregate to remove salts and other

impurities in order to meet the requirement specified. 4/4 COARSE AGGREGATE FOR CONCRETE 4/4.1 Coarse aggregate shall be prepared as single sized aggregate and blended to

produce normal size grading. The combined grading shall be within the appropriate grading limits given in BS EN 12620: 2000.

4/4.2 Aggregates that are deleteriously reactive with the alkalis in the cement in an

amount sufficient to cause excessive expansion of concrete shall not be used. 4/4.3 The Contractor shall mechanically wash aggregate to remove salts and other

impurities in order to meet the requirement specified.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/12

4/5 COMBINED AGGREGATE 4/5.1 Approved coarse aggregate and fine aggregate in each batch shall be

combined in proportions as specified in BS EN 12620:2000 and as approved by the Engineer. However, in no case shall materials passing the 0.075mm, sieve exceed three (3) percent by weight of the combined aggregate.

4/5.2 The combined aggregate gradation used in the work shall be as specified,

except when otherwise approved or directed by the Engineer. Changes from gradation to another shall not be made during progress of the work unless approved by the Engineer.

4/6 WATER FOR CONCRETE 4/6.1 The Contractor shall make his own arrangement and obtain approval for the

supply of water. 4/6.2 The mixing water should be clear, apparently clean and free from matter

harmful to concrete in its fresh or hardened state. Potable water can be used. Water of questionable quality should comply with the physical tests of Table 4.3 and chemical limitation listed in Table 4.4. Water shall also meet the requirement of BS EN 1008:2002.

4/6.3 The temperature of water for concrete should not be less than 5 degree

Celsius nor more 25 degree Celsius. Water may be cooled to not less than 5 degree Celsius by the gradual addition of chilled water or ice but on mixing, no ice particles should be present in the mix. Alternatively, flaked ice may be used. The ice to be used should be crushed and should be the product of frozen water which complies with acceptance criteria of Tables 4.3 and 4.4.

4/6.4 Water for curing concrete shall not contain impurities in sufficient amounts to

cause discoloration of the concrete. Sources of Water shall be maintained at such depth and the water shall be withdrawn in such a manner as to exclude silt, mud, grass and other foreign matter.

TABLE 4.3

ACCEPTANCE CRITERIA AND PHYSICAL TESTS FOR MIXING WATER

Limits ASTM Test

Compressive strength,min.% 90 C 109 : 2002 control at 7 days Setting time, deviation from 1:00 early from control,h:min. to 1:30 later C 191 :2004

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/13

TABLE 4.4: CHEMICAL LIMITATIONS FOR MIXING WATER

Max. Concentration, Limit, ppm Test Method

1. Chloride as C1 250 ASTM D 512:

(2004) 2. Sulphates as SO4 350 ASTM D 516:2002 3. Alkali carbonates 500 ASTM D 513:2006 and bicarbonates 4. Total dissolved solids, including 1, 2 & 3 above 2000 BS 1377 : Part 3 :

1990: Test 8 5. PH min.7/max. 9 ASTM D1293 :

1999

4/7 APPLICABLE TESTS AND CODES 4/7.1 All concrete, aggregate, cement, steel and water shall be tested during the

construction as per frequency in Tables 4.2 and 4.6 or as directed by the Engineer. All test samples shall be supplied by the Contractor at his expense. Samples shall be obtained in accordance with BS 812, BS EN 1008, BS 1881 and BS EN 196. Testing shall be at the frequencies stated above or relevant standards. All sampling shall be carried out by the Engineer.

Table 4.6 Frequency of Routine Testing:

ITEM Sampling Method

Test Method Test Frequency Rate

a. Cement - as per BS EN 196

BS EN 196-7

BS EN-196 Each 500m3 of concrete poured.

b. Steel

1. Deformed S. Bar as per BS 4449:2005

BS 4449:2005

ASTM E415 Each size 100 ton

2. Strand as per BS 5896:1980 if needed

BS 5896 BS 5896 - APPENDIX

A

As per Clause 23.3 of BS 5896

c. Concrete

1. Air content, as per BS EN 12350-7:2009

BSEN 12350-1

BSEN 12350-7:2009

Once at the time of mix design of concrete or as directed by the Engineer.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/14

ITEM Sampling Method

Test Method Test Frequency Rate

2. Flexural strength of Prism as per BS EN 12390-5

BSEN 12350-1

BSEN 12390-5

Once at the time of mix design of concrete or as directed by the Engineer.

3. Bleeding as per ASTM C232/C232M-14

BS EN 12350-1:2000

ASTM C 232/C32M-

14

One at the time of mix design of concrete or as directed by the Engineer.

4. Splitting Tensile of Conc. Cylinder as per ASTM C-496:1996 & others

BS EN 12350-1:2000

C-496 One at the time of mix design of concrete or as directed by the Engineer.

5. Depth of Water Penetration (BS EN 12390 P-8:2000)

BSEN 12350-1:2000

BS EN 12390-8

Each 2000m3 of a particular grade of structural concrete or as directed by the Engineer.

6. ISAT as per BS 1881-p-208:1996

BS EN 12350-1:2000

BS 1881 - 208:1996

Each 2000m3 of a particular grade of structural concrete or as directed by the Engineer.

7. Water absorption of Hardened Conc. As per BS 1881 P122

BS EN 12350-1:2000

BS 1881-122:1983

Each 2000m3 of a particular grade of structural concrete or as directed by the Engineer.

8. Rapid chloride permeability

BS EN 12350-1

:2000

ASTM C 1202

Each 2000m3 of a particular grade of structural concrete or as directed by the Engineer.

9. Slump test - as per BS EN 12350-2:2009

BS EN 12350-1

BS EN 12350-2:2009

From each transit mixture load arrived at site

10. Concrete Mix Design (Mixing and Sampling in the lab) as per BS 1881 P125 & In Site (Sampling) as per BS EN 12350-1:2000

All mixes are to be designed once for verification and approval.

11. Kerbs-as per BS 7263 BS EN 1339:2003

BS EN 1339:2003

Sample to be taken from each batch of upto 1000 kerb in whole consignment

d. Water BS EN 1008:2002

BS EN 1008-:2002

For DEWA WD no test is required or other than DEWA twice a week or as directed by the Engineer.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/15

4/7.2 WORKABILITY

Workability shall be assessed by the following tests the requirements for which shall be as specified elsewhere in the documents. Slump test shall be performed according to BS EN 12350-2:2009 Compaction factor shall be performed according to BS EN 12350-4:2000 Vebe time shall be performed according to BS EN 12350-3:2000 Flow test shall be performed according to BS EN 12350-5:2000

4/7.3 COMPRESSION TEST The Compression tests shall be performed on cubes 150 x 150 x 150 mm as

described in BS EN 12390-3:2002. Sampling, making test cubes and curing of cubes shall be in accordance with BS EN (12350-1:2000 and 12390-1:2000) respectively.

4/8 REINFORCEMENT BARS 4/8.1 All reinforcement bars shall be of a deformed type in accordance with

BS 4449:2005, except that plain bars may be used where specifically indicated on the Drawings. Plain bars shall be in accordance with BS 4449:2005.

4/8.2 All steel reinforcement shall conform to the requirements of the Specifications

for Deformed High Yield Steel Bars grade 500 N/mm2 Type 2, unless otherwise shown on the Drawings or specified by the Engineer. The Bond Strength and Surface Geometry requirements as per Clause No. 7.4 of BS EN 4449:2005

4/8.3 Certification. Three (3) copies of a mill test report shall be furnished to the

Engineer for each lot of steel reinforcement bars proposed for use on the project.

4/8.4 Identification. The bars in each lot shall be legibly tagged by the manufacturer

and/or fabricator before being offered for inspection. The tag shall show the manufacturer's test number and lot number and other applicable data that will identify the material with the certificate issued for that lot of steel.

4/8.5 The fabricator shall furnish three (3) copies of a certification which shows the

heat number or numbers from which each size of bar in the shipment was fabricated.

4/8.6 The Engineer reserves the right to sample and inspect all reinforcement steel

upon its arrival at the work site. The Contractor shall provide a certificate confirming that samples taken from the bars delivered to the works pass all the required tests. The frequency of sampling and the method of quality control shall be in accordance with BS 4449 – 2005.

4/8.7 All reinforcement bars shall be free from detrimental dirt, mill scale, loose rust,

paint, grease, oil or other foreign substance, fins, or tears. There shall be no

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/16

evidence of visual flaws in the bars, test specimens or on the sheared ends of the bars.

4/8.8 Uncoated reinforcement shall be grit-blasted before use to remove rust, oil,

grease, salt and other deleterious materials and where pitting has occurred the causes and products thereof. Repeated blasting may be required when the reinforcement is in position, or partially cast in. Partially set concrete adhering to exposed bars during concreting operations shall be removed.

4/8.9 The minimum thickness of concrete cover to reinforcement shall be as shown

on the drawings. Only approved concrete spacers shall be used. The concrete shall be of similar grade to the main concrete and shall have non metallic ties.

4/9 BAR SCHEDULES AND SHOP DRAWINGS 4/9.1 Before ordering reinforcing steel, the Contractor shall check the bar schedules

and adjust them if necessary to the approval of the Engineer. Bar schedules shall show the weight of each bar, the total weight of each bar size and the total weight of bars, and bending diagrams for bars in accordance with BS 4466.

4/9.2 The Contractor shall provide and submit to the Engineer for approval any

working drawings additional to the Contract Drawings which may be found necessary for the production of revised bar schedules or for the completion of the works.

4/9.3 The approval of working drawings, or revised bar schedules by the Engineer

shall in no way relieve the Contractor of responsibility for the correctness of such drawings or schedules.

4/10 BAR CUTTING AND BENDING 4/10.1 Reinforcement shall be cut and bent in accordance with BS 8666:2005.

Cutting or bending by the application of heat is not permitted. Welding of reinforcement shall only be permitted when approved in writing by the Engineer. If such approval is given then the workmanship shall be in accordance with BS EN 1011. The Contractor shall submit full technical details of his proposed procedures prior to seeking approval.

4/10.2 Hot rolled high yield bars shall not be straightened or bent again, having once

been bent. If the Engineer gives approval to bend mild steel reinforcement projecting from the concrete, the internal radius of bend shall not be less than four times the nominal size of the bar.

4/11 PLACING AND FIXING REINFORCEMENT 4/11.1 Reinforcement shall be placed and maintained in the position shown in the

Contract Drawings. Unless otherwise permitted by the Engineer, all bar intersections shall be tied together using 1.2mm diameter steel wire or No. 18 gauge stainless steel wire as indicated on the drawings and the ends of the tying wire shall be turned into the main body of the concrete.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/17

4/11.2 Metal supports, approved by the Engineer, shall be provided and used to retain the reinforcement at proper distances from the forms. Supports under horizontal bars at the bottom of base slabs shall be spaced at not more than eighty (80) diameters of the bar. All reinforcement shall be so rigidly supported and fastened that displacement will not occur during construction. Reinforcing steel shall be inspected in place and must be approved by the Engineer before any concrete is deposited.

4/11.3 No splices shall be made in the reinforcement except where described in the

Contract Drawings or where approved by the Engineer. 4/11.4 Reinforcement temporarily left projecting from the concrete at construction or

other joints shall not be bent out of position during the periods in which concreting is suspended, except with the approval of the Engineer.

4/12 WELDED WIRE FABRIC 4/12.1 Welded wire fabric to be used for the reinforcement of concrete shall conform

to the following requirements: - Dimensions. Welded steel wire fabric shall conform to the size and

dimensions shown on the Drawings. - Properties. Wire fabric furnished under this specification shall conform to

the requirements for "Welded Steel Wire Fabric for Concrete Reinforcement" BS 4483 or equivalent.

4/13 SPACER BLOCKS 4/13.1 Spacers as approved by the Engineer shall be of such material and design as

will be durable, not lead to corrosion of the reinforcement and not cause spalling of the concrete cover.

4/13.2 Spacer blocks made from cement, sand and small aggregate shall match the

mix proportions of the surrounding concrete so far as is practicable with a view to being comparable in strength, durability and appearance.

4/14 ADMIXTURES 4/14.1 Unless agreed by the Engineer neither admixtures nor cements containing

additives shall be used. 4/14.2 Where the use of admixture had been agreed by the Engineer, they shall

conform to the requirements of Type A, Type D, Type F or Type G as specified in ASTM C494 and shall be used in strict accordance with the manufacturer's instructions.

Preliminary tests of cube strength and other tests shall be carried out using the

combination of aggregates cements and admixtures proposed for use. 4/14.3 The Contractor shall be entirely responsible for the use of any approved

admixtures.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/18

4/14.4 Approved methods and equipment shall be used for dispensing and

incorporating the admixture into the concrete. The dispensing unit shall be designed so that the discharge of the admixture is visible.

4/15 CONCRETE MIX SPECIFICATION 4/15.1 Concrete shall be as shown in the Table of 4.5. The number of mixes may

require to be increased. The criteria given in the Table are designed to produce concrete of the

required strength and durability. If the maximum aggregate size is 10 mm then the cement content stipulated

for the class of concrete given in table 4.5 shall be increased by 40 Kg per m3. All concrete mixes shall be verified by DM - DCL TABLE 4.5 TABLE OF MIXES WITHOUT ANY ADMIXTURE OR ADDITIVE

Concrete Class

Max. Size Agg

Min. Qty of

Cement

Max. Free

Water/ Cement

Ratio

Characteristic Cube Strength

CCS

7-day 28-day mm. kg.per m3 N/mm2 N/mm2

45/20 20 400 0.425 33 45 40/20 20 370 0.475 30 40 37/20 20 350 0.50 26 37 35/20 20 330 0.525 25 35 30/20 20 310 0.55 20 30 25/20 20 275 0.60 16 25 15/20 20 250 0.65 10 15

The CCSs are for concrete which has been cured at a temperature of 23

degrees C + 2 degree C, and are the values below which no more than 5% of the test results fall. The 7-day strengths shall be used only as a guide.

4/15.2 Concrete shall comply with BS 8110 except where BS 8007 or this

specification differs. Sampling for test purposes shall comply with BS EN 12350-1:2000 (on site) & BS 1881 Part 125:1986 (in laboratory). If air-entertainment is specified the average air content at the time of placing measured in accordance with BS EN 12350-7:2009 shall be: Concrete containing 20mm Maximum size aggregate 5% + 1%

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/19

Concrete for water-retaining shall be watertight and shall comply with the recommendations of BS 8007. Concrete for paving or precast units shall be tested to BS EN 12390: Part 5: 2000 and shall have minimum flexural beam strength of 3.5N/mm2 at 28 days. If the concrete has a specified CCS of 40N/mm2 or greater, then the minimum flexural strength shall be 4N/mm2. If concrete specimens are cured at higher temperatures or for longer periods than BS EN 12390-1:2000 requires, the adjusted CCS shall be calculated as follows: 100f'/f = A + B log {24D (T+12)/1000} f’ = adjusted CCS f = specified CCS T = curing temperature D = age at testing in days A&B = are coefficients given in the following table. The above equation applies only to OPC, MSRPC and SRPC.

Recorded Cube Strength N/mm2 A B

Less than 15 10.0 67.5 15 to 35 20.0 60.0 Greater than 35 30.0 52.5

This calculation may be applied for curing at temperatures up to 27 degrees C. Before placing concrete the Contractor shall obtain approval of the mixes proposed for each class of concrete and the average target strengths. The mixes shall be designed to achieve the minimum workability for the Contractor to place and compact the concrete with the equipment proposed for use. The mean strength shall exceed the CCS by a margin of 1.64 times the standard deviation expected from the concreting plant, except that no standard deviation less than 3.5 N/mm2 shall be used as a basis for designing a mix. Unless otherwise approved a standard deviation of 7 N/mm2 shall be used for initial mixes.

4/15.3 The ultimate compressive strength of the concrete shall be determined on test specimens obtained and prepared in accordance with BS EN 12390-1:2000.

4/15.4 Mixes for structural concrete shall be designed by the Contractor. The class of

concrete (shown on the drawings) is denoted by the 28 day characteristic cube strength and the maximum size of aggregate.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/20

4/15.5 The chloride and sulphate levels in the concrete mix shall comply with the following requirements:-

Maximum Limits of acid soluble Chloride and Sulphate content as a

percentage by Weight of Cement in the Mix.

TYPE OF CONCRETE CHLORIDES SULPHATES AS Cl AS SO3 ACCORDING TO BS-1881 : 1988

PART 124

Amd 01:1998 Amd 06:2002 a. For reinforced concrete if made with OPC/MSRPC 0.30 3.70 if made with SRPC 0.06 3.70 b. Prestressed concrete &

Heat-cured reinforced concrete

0.10 3.70

c. For mass concrete if made with OPC/MSRPC 0.60 3.70 if made with SRPC 0.12 3.70

Note: BSEN 196-21: 1992 Clause 8, Method of Testing Cement Part 21 will be

used to determine the percentage chloride by weight of cement. The OPC and MSRPC cements can also contain chlorides, the relevant standard BS EN 197-1 allows up to 0.1% Cl. Therefore any chloride content present in the cement has to be taken into account while computing total Cl in the mix. In case the cement contains the maximum limit of 0.1% Cl, then the aggregates, water and admixtures used for prestressed concrete or heat cured reinforced concrete should be absolutely free of chlorides.

4/16 CONCRETE MIX DESIGN TRIAL MIXES 4/16.1 Preliminary laboratory tests shall be carried out to determine the mixes to

satisfy the specification with the approved materials. Trial mixes shall be tested to determine the following properties of mixes proposed for initial field tests: a) Bleeding in accordance with ASTM C232/C232M-14 (non-vibrating) shall

not exceed 0.5%.

b) Drying shrinkage in accordance with BS 1881 Part 5.

c) Air content if applicable BS EN 12350: P7: 2009.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/21

d) Free water/cement ratio.

e) Workability BS EN 12350-2:2000

f) Chloride permeability shall be maximum 2,000 coulombs, when tested in accordance with ASTM C-1202: 2007.

g) Fresh and hardened concrete densities BS EN (12350-6:2000 and 12390-7:2000) respectively.

h) Compressive strength BS EN 12390-3:2000.

i) Depth of Water Penetration Test BS EN 12390 Part 8 : 2000 (maximum 10 mm at 28 days) (maximum 15 mm at 7 days).

j) The Initial Surface Water Absorption Test as per BS 1881: P-208: 1996. Maximum permissible limit for ISAT is 0.2 ml/m2/sec

k) Water absorption of Hardened concrete as per BS 1881: P122: 1983 and the maximum permissible limit shall be 2.0%.

If the values obtained are unacceptable, the mixes shall be re-designed.

4/16.2 The concrete mixes shall be prepared as per BS 1881-125-2013 and tests shall be carried out as per BS EN 12504 and BS EN 12390. At least 35 days before commencement of concreting trial mixes shall be prepared under full-scale site conditions and tested in accordance with BS 1881: 1983.

Samples of concrete incorporating the reinforcing details to be used shall be cast and examined, before hardening using hand tools, and after hardening by coring to assess the mixes. Cores shall be taken in accordance with BS EN 12504-1:2009. Trial mixes shall be made on each of three days; the workability shall equate to the designed target value. Six cubes from each mix shall be taken, three for test at 28 days.

Further trial mixes shall be made if the range (the maximum minus the minimum of the three cube results in any batch) exceeds 15% of the average of that batch, or if the range of the three batch averages exceeds 20% of the overall average of the batches.

The mixes shall be tested to determine the following properties: a) Bleeding in accordance with ASTM C232/C232M-14

b) Air content if applicable BS 12350: P7: 2009.

c) Free water/cement ratio

d) Flexural strength of concrete specimen as per BS EN 12390-5:2009. Splitting tensile strength of concrete cylinder shall be in accordance with ASTM C496-11.

The average 28-day CCS of the three trial mixes shall not be less than the designed mean strength, and the results of the above tests shall be acceptable before the mix is approved. Otherwise the mix shall be re-designed.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/22

4/16.3 The Engineer will review the Contractor's trial-mixes and test the test cubes at

seven (7) and twenty-eight (28) days. The Engineer will then determine which of the trial mixes shall be used. If none of the trial mixes for a class of concrete meets the Specifications, the Engineer will direct the Contractor to prepare additional trial-mixes. No class of concrete shall be prepared or placed until its job-mix proportions have been approved by the Engineer.

4/16.4 The approval of the job-mix proportions by the Engineer or his assistance to

the Contractor in establishing those proportions, in no way relieves the Contractor of the responsibility of producing concrete which meets the requirements of these Specifications.

4/16.5 The Engineer may also require practical tests to be made on the Site by filling

trial moulds to confirm the suitability of the mix for the works, the type of plant used for mixing, the method of compaction used and the formwork face intended for use in the works.

4/16.6 All costs connected with the preparations of trial-mixes and the design of the

job-mixes shall be borne by the Contractor. 4/16.7 In the event, any Concrete mix that is currently being used in another running

RTA projects, is proposed by the contractor for approval of using that mix in this contract, then

1. Prior to according the approval or otherwise, the Engineer must ensure

that all copies of test results pertaining to another running RTA project submitted by that contractor comply with all specifications as stated in this contract and shall also ensure that the proposed mix complies with clause 4/16 by verifying that proposed mix at DCL.

2. The Engineer has to make sure that all constituents of concrete are tested

and meeting the standard specified requirements. In case there are changes in the materials or constituents, which may affect the properties of the concrete. Then the mix design shall be re-verified. All the mix designs verification shall be done at DCL.

NOTE: Any mix that is obsolete & currently not in use shall not be accepted at all for re-approval.

4/17 QUALITY CONTROL 4/17.1 TEST CUBES Cubes shall be manufactured in an on-site laboratory, specially equipped for

the purpose, in controlled conditions. They shall be made, cured, stored, transported and tested to BS EN (12390-1 and 12390-3:2000). The method of compacting cubes shall be as approved and shall be means of vibrating table in the laboratory or 25mm vibrating poker on site.

4/17.2 SAMPLING CUBES

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/23

A sample of concrete shall be taken at random on eight separate occasions during the first five days of using a mix at least one sample being taken each day. The standard deviation shall be calculated from at least 40 individual cube results each representing separate batches of similar concrete produced by the same plant under the same supervision. The current margin for the plant shall be thus established as 1.64 times the standard deviation.

Thereafter one sample shall be taken at random for each class of concrete in

accordance with Clause 4/31 of the Specification. In addition to the above requirements, at least one sample shall be taken from

each individual structural unit, or part of a unit, when the latter is the product of a single pour.

From each sample three cubes shall be made for testing at 28 days and three

for testing at 7 days for control purposes. Six cylinder samples shall also be taken to determine the split tensile strength

of the concrete 3 at 7 days and 3 at 28 days, as specified in ASTM C496: 1996. These samples shall be taken from every 100 batches, but at least once a week during concreting operations, and shall coincide with samples taken for test cubes.

The frequency of sampling may be required to be varied if directed by the

Engineer. The procedures shall be repeated when materials or design mixes are

changed. 4/17.3 CUBE STRENGTH RESULTS The results will be acceptable if:

i) The average strength determined at the age of 28 days from a sample of three or more cube test results exceed the Characteristic Cube Strength (CCS) which is the 28 days cube strength obtained in the approved trial mix by 0.5 times the current margin.

ii) No individual result of the sample is less than that (CCS which is the 28 days cube strength obtained in the approved trial mix minus 3 N/mm2),

iii) Number of individual results in the sample below CCS which is the 28 days cube strength obtained in the approved trial mix is not more than one.

If the above criteria is not satisfied, the unit represented by the sample is questionable and the following actions may be instructed as appropriate: i) Cutting and testing cores from placed concrete. ii) Non-destructive testing of placed concrete. iii) Load-testing relevant structural units. iv) Cutting out and replacing defective concrete.

If the range of individual cube strengths made from the same sample

exceeds 15% of the mean, then the method of making, curing and testing cubes shall be checked. In the event of a sample having a range

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/24

exceeding 20%, then the result shall be unacceptable and the Engineer may order any of the following actions:

a) Changing the mix. b) Improving quality control. c) Cutting and testing cores from placed concrete. d) Non-destructive testing of placed concrete.

In the event of cutting and testing of cores are required, the Contractor

shall cut cores from approved locations and test them to BS EN 12504-1:2009.

4/17.4 DURABILITY TESTS Concrete shall be tested for durability properties by undertaking absorption

and permeability tests where appropriate, or directed by the Engineer, as directed below:

Water absorption tests shall be carried out in the laboratory on 75mm diameter

cores cut at an age of 24 to 28 days to enable the tests to be carried out between 28 and 32 days in accordance with BS 1881-122: 2011. The upper acceptable limit for absorption after 30 minutes shall be 2%.

Effective permeability tests in accordance with the method described in BS EN

12390-8: 2009 shall be carried out. The maximum acceptable penetration at seven days shall be 15 mm and the maximum acceptable penetration at 28 days shall be 10mm.

Initial surface absorption test as per BS 1881: P-208: 1996 shall be carried out.

Maximum permissible limit for ISAT is 0.2 ml/m2/sec. Rapid chloride penetration test as per ASTM C1202-12 shall be carried out.

4/17.5 OTHER TESTS When instructed by the Engineer concrete shall be tested for drying shrinkage

and wetting expansion, for which 75x75mm prisms shall be prepared and tested in accordance with BS ISO 1920-8:2009 or BS EN 772:98 and BS EN 771-2:2011. The maximum acceptable limits shall be:

Drying Shrinkage : 0.05% Wetting Expansion : 0.03% Cubes may be required and trials carried out to determine stripping times for

formwork, the duration of curing and to check testing and sampling errors. The air content of air-entrained concrete shall be determined 12350-7:2009 for

each batch produced until consistency has been achieved, when batches may be tested. The maximum value shall not exceed 2%.

Compaction factor, slump, veb or other workability tests shall be carried out as

required during concreting of permanent works to control workability at the

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/25

batching plant at the site of the pour. The degree of workability shall be as for the trial mixes; permitted tolerances shall be in accordance with BS 5328.

4/18 CONCRETE DESIGN LIMITS 4/18.1 The following will be designated by the Engineer within the limits of the

Specifications.

a) The minimum Cement content in kg. per cubic metre of concrete. b) The maximum allowable water/cement ratio including surface moisture,

but excluding water absorbed by the aggregates. c) Slump or Slumps designated at the point of delivery. d) Changes requested by the Contractor in mix proportioning previously

approved shall be made only with the agreement of the Engineer. e) When, in the opinion of the Engineer, cement is being lost due to windy

conditions, the Contractor shall add additional amounts of cement as directed by the Engineer. No additional payment shall be made for the added cement.

f) Failure of the mixed concrete to meet specifications as determined by

the Engineer will be grounds for the Engineer to reject the concrete. g) Bleeding limitations when tested in accordance with ASTM

C232/C232M-14. 4/19 CONSISTENCY OF CONCRETE 4/19.1 The consistency of concrete shall be determined in the field by the Slump

Test. The consistency of concrete at the time of delivery will be designated by the Engineer and shall not vary by more than 25mm from the designated consistency.

4/20 TOLERANCES IN PROPORTIONING THE MATERIALS 4/20.1 CEMENT In the case of bagged cement it shall be measured as packed by the

manufacturer: a sack of cement shall weigh fifty (50) kilograms. Measurement for proportioning all cement shall be accurate to within two (2) percent throughout the range of use. Only full bags, undamaged or unbroken will be permitted.

4/20.2 WATER The mixing water shall be measured by weight or by volume. In either case

the measurement shall be accurate to within one (1) percent throughout the range of use.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/26

4/20.3 AGGREGATE The aggregates shall be measured by weight to an accuracy within two (2)

percent through-out the range of use. 4/21 ASSEMBLY AND HANDLING MATERIALS ASSEMBLY 4/21.1 Aggregates shall be assembled in such quantities that sufficient material

approved by the Engineer is available to complete any continuous pour necessary for any element. The batching site shall be of adequate size to permit the stockpiling of sufficient, unsegregated materials, having proper and uniform moisture content, to ensure continuous and uniform operation. Aggregates shall enter the mixer in a manner approved by the Engineer and in such a manner to ensure that no matter foreign to the concrete or matter capable of changing the desired proportions is included. In the event two (2) or more sizes or types of coarse or fine aggregates are used on the same project, only one (1) size or type of each aggregate may be used on one continuous concrete pour.

STOCKPILING Of AGGREGATES 4/21.2 All aggregates shall be stockpiled before use in order to prevent segregation

of material, to ensure uniform moisture content and to provide uniform conditions for proportioning plant control.

4/21.3 The use of equipment or methods of handling aggregates which result in the

degradation and contamination of the aggregates is strictly prohibited. Bulldozers with metal tracks shall not be used on coarse aggregate stockpiles. All equipment used for handling aggregates shall be approved by the Engineer.

4/21.4 Stockpiling of aggregates shall be in the manner approved by the Engineer,

and in addition, every precaution shall be taken to prevent segregation. Segregation shall be prevented by making no layer higher than one and one-half (1.5) metres and if two (2) or more layers are required, each successive layer shall not be allowed to "cone" down over the next lower layer.

4/21.5 Aggregates shall not be stockpiled against the supports of proportioning

hoppers and weighing devices. SEGREGATION 4/21.6 Segregated aggregates shall not be used until they have been thoroughly

remixed and the resultant pile is of uniform and acceptable gradation at any point from which a representative sample is taken. The Contractor shall re-mix aggregate piles when ordered by the Engineer.

TRANSPORTING Of AGGREGATES 4/21.7 If aggregates are to be transported from a central proportioning plant to the

mixer in batch-boxes or dump trucks, such equipment shall be of sufficient

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/27

capacity to carry the full volume of materials for each batch of concrete. Partitions separating batches shall be approved by the Engineer and shall be adequate and effective to prevent spilling from one compartment to another whilst in transit or being dumped.

CEMENT 4/21.8 Cement shall be stored in a dry weather-proof shed with a raised wooden floor

or in a silo and shall be delivered in quantities sufficient to ensure that there is no suspension or interruption of the work of concreting at any time. If stored in sheds, each consignment shall be kept separate and distinct.

4/22 MIXING CONCRETE 4/22.1 The weighing and water-dispensing mechanisms shall be maintained in good

order. Their accuracy shall be maintained within the tolerances described in BS 1305 and checked against accurate weights and volumes when required by the Engineer.

4/22.2 The mass of cement and of aggregate indicated by the mechanism employed

shall be within a tolerance of 2% of the respective mass per batch agreed by the Engineer. The mass of the fine and coarse aggregates shall be adjusted to allow for the free water contained in them. The water to be added to the mix shall be reduced by the quantity of free water contained in the fine and coarse aggregates, which shall be determined by the Contractor by a method approved by the Engineer immediately before mixing begins and further as the Engineer requires.

4/22.3 Unless otherwise agreed by the Engineer, concrete shall be mixed in a batch

type mixer manufactured in accordance with BS 1305. Where appropriate the batch capacity, method of loading, mixing time and drum speed shall conform to the details furnished in accordance with the requirements of BS 3963 for the mix which corresponds most closely to the mix proportions being used. The mixing blades of pan mixers shall be maintained within the tolerances specified by the manufacturer of the mixer and the blades shall be replaced when it is no longer possible to maintain the tolerance by adjustment. The period of mixing, judged from the time that all the ingredients including water are in the mixing drum shall be as ordered by the Engineer's representative but shall not be less than 2 minutes or 20 revolutions of the drum whichever is the longer.

All plants shall be equipped with an approved automatic cycling and

monitoring system installed as part of the batching equipment. The system shall include equipment for accurately proportioning the various components of the mixture by mass. Admixtures may be measured volumetrically. The automatic proportioning system shall be capable of consistently delivering each constituent within the tolerances specified. All records of batches shall show the batch weights, the batch number, the day, the month, the year and the time of day to the nearest minute for each batch. This information shall be imprinted on the record so that each batch may be permanently identified. The Engineer will be provided with a clear and legible copy of all batch records for concrete supplied for the project.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/28

4/22.4 Mixers which have been out of use for more than 30 minutes shall be thoroughly cleaned before any fresh concrete is mixed.

4/22.5 The method of discharge from the mixer shall be such as to cause no

segregation whether partial or otherwise of the concrete materials. 4/22.6 The Contractor shall ensure that the constituent materials of the concrete are

sufficiently cool to prevent the concrete from stiffening in the interval between its discharge from the mixer and compaction in its final position. Precautions shall include the shading of aggregate stockpiles and the use of chilled water.

4/23 READY MIXED CONCRETE 4/23.1 Ready mixed concrete as defined in BS 5328, batched off the site, may be

used only with the agreement of the engineer and shall comply with all requirements of the Contract.

4/23.2 The Concrete shall be carried in purpose-made agitators, operating

continuously, or truck mixers. The concrete shall be compacted and in its final position within 1 hour of the introduction of cement to the aggregates, unless a longer time is agreed by the Engineer. The time of such introduction shall be recorded on the delivery note together with the weight of the constituents of each mix.

4/23.3 When truck mixed concrete is used, water shall be added under the

supervision, either at the Site or at the central batching plant as agreed by the Engineer but in no circumstances shall water be added in transit.

4/23.4 Unless otherwise agreed by the Engineer, truck mixer units and their mixing

and discharge performance shall comply with the requirements of BS 4251. Mixing shall continue for the number and rate of revolutions recommended in accordance with Item 9 in Appendix B of BS 4251 or, in the absence of the manufacturer's instructions, mixing shall continue for not less than 100 revolutions at a rate of not less than 7 revolutions per minute.

4/23.5 Pumping concrete through delivery pipes may be permitted but only with the

prior approval of the Engineer. 4/23.6 Re-mixing of concrete which has commenced to set shall not be allowed and

in no case shall such concrete be used in the Works. 4/23.7 Coarse aggregate shall be kept in identified stockpiles from which samples

can be collected and tested as specified. 4/23.8 The concrete supplier is required to certify that the Cl content in the mix being

delivered is within the limits specified in Clause 4/15.5. The Cl and SO3 content shall be checked at frequent intervals.

4/24 TRANSPORT AND PLACING 4/24.1 The method of transport and placing concrete shall be to the approval of the

Engineer. Concrete shall be so transported and placed that contamination, segregation or loss of the constituent materials does not occur.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/29

4/24.2 All formwork and reinforcement shall be clean and free from standing water

immediately before placing concrete. No concrete work shall be stopped or temporarily discontinued within forty-five

(45) centimeters of the top of any finished surface, unless such work is finished with a coping having a thickness less than forty-five (45) centimeters in which case the joint shall be made at the under edge of the coping.

Concrete in simple slab spans shall be placed in one (1) continuous operation

for each span, unless otherwise indicated on the drawings or approved by the Engineer.

4/24.3 Prior to placing any concrete on natural surfaces a blinding layer of Class 15

concrete shall be laid to a minimum of 75 mm thickness unless otherwise specified on the drawings. This blinding shall be suitably cured prior to subsequent concrete placement. The blinding shall be clean and free from any dust or impurities prior to subsequent concrete placement.

4/24.4 No concrete shall be placed in a foundation until the extent of excavation and

the character of bearing material have been approved and no concrete shall be placed in any structure until the placement of reinforcing steel and the adequacy of the forms and falsework have been approved.

4/24.5 Concrete shall not be placed in any part of the Works until the Engineer's

approval has been given. If concrete has not started within 24 hours of such approval being given, approval shall again be requested. Concreting shall then proceed continuously over the area between construction joints. Fresh concrete shall not be placed against in-situ concrete which has been in position for more than 30 minutes unless a construction joint is formed in accordance with the Specification. When the concrete has been in place for 4 hours, or less as directed by the Engineer, further concrete shall not be placed against it for a further 20 hours.

4/24.6 Concrete when deposited shall have a temperature of not more than 32 deg. C

unless otherwise specified. Concrete shall be compacted in its final position within 30 minutes of discharge from the mixer unless carried in purpose made agitators operating continuously, when the time shall be within 1 hour of the introduction of cement to the mix and within 30 minutes of discharge from the agitator.

4/24.7 Except where otherwise agreed by the Engineer, concrete shall be deposited in horizontal layers to a compacted depth not exceeding 400mm where internal vibrators are used or 300mm in all other cases.

4/24.8 Unless otherwise agreed by the Engineer, concrete shall not be dropped into

place from a height exceeding 2m. When trunking or chutes are used they shall be kept clean and used in such a way as to avoid segregation. Where steep slopes are required for placing concrete with chutes, the chutes shall be equipped with baffle boards or be in short lengths that reverse the direction of the movement. Chutes and the use of chutes must be approved by the Engineer. All chutes shall be kept clean and free from coating of hardened concrete by thoroughly flushing with water after each run. The water used for flushing shall be discharged clear of the concrete already in place.

Project R1041: Dubai Parks Access from Sheikh Zayed Road General Specifications Volume 2 Part I

March 2015 Tender Documents Page 4/30

4/24.9 No concrete shall be placed in flowing water. Underwater concrete shall be placed in position by tremies, or by pipeline from the mixer.

4/24.10 Full details of the method proposed shall be submitted in advance to the

Engineer and his approval obtained before placing begins. Where the concrete is placed by the tremie, its size and method of operation shall be in accordance with BS 8004. During and after concreting under water, pumping or dewatering operations in the immediate vicinity shall be suspended until the Engineer permits them to be continued.

4/24.11 Approved measures shall be taken to avoid premature stiffening of concrete

placed in contact with hot, dry surfaces. Surfaces including reinforcement against which concrete is to be placed shall be shielded against the direct rays of the sun and shall be sprayed with water to prevent excessive absorption by the surfaces of water from the fresh concrete.

4/24.12 A complete record shall be kept of the date, time, temperature and conditions

of placing the concrete in each portion of the work and shall be available for inspection by the Engineer at any time.

4/24.13 Unless otherwise shown on the drawings all concrete placed below ground

level shall have a minimum protection to its outside faces as follows: Underside - Protected by the laying of a grade 1000 approved polyethylene

sheeting on the blinding concrete. The sheeting shall be returned up the outside faces of the concrete and suitably sealed.

Sides - Coated with 3 coats of an approved bitumen rubber latex emulsion

flexible damp and vapour-proof liquid membrane conforming to BRE Digest No. 54.

4/25 COMPACTION OF CONCRETE 4/25.1 All concrete shall be compacted to produce a dense homogeneous mass.

Unless otherwise agreed by the Engineer, it shall be compacted with the assistance of vibrators. Sufficient vibrators in serviceable condition shall be on site so that spare equipment is available in the event of breakdown. A 50mm diameter internal vibrator shall be deemed capable of compacting 20 Cu. m./hr. Internal vibrators shall be capable of producing not less than 10,000 cycles per minute.

4/25.2 Vibration shall not be applied by way of the reinforcement. Where immersion

vibrators are used, contact with reinforcement and all inserts shall be avoided. 4/25.3 Concrete shall not be subject to vibration between 4 and 24 hours after

placing. 4/25.4 Vibrators shall be so manipulated as to work the concrete thoroughly around

the reinforcement and embedded fixtures and into corners and angles of the forms. Vibrators shall not be used as a means to cause concrete to flow or its position in lieu of placing. The vibration at any point shall be of sufficient duration to accomplish compaction. After initial set of the concrete, the forms