    Properties of Concretefor use in Eurocode 2How to optimise the engineering properties of concrete in

    design to Eurocode 2

    A cement and concrete industry publication

    P.Bamforth BSc (Hons) PhD C Eng MICE

    D.Chisholm BE (Hons) CPEng IntPE(NZ)

    J.Gibbs BA MICT

    T.Harrison BSc PhD C Eng FICT MICE

  • 8/2/2019 Concrete EU Eurocode 2 p59

    2/59

    Properties of concrete for usEurocode 2

    Contents

    Symbols ii1. Introduction 1

    2. Assumptions underlying Eurocode 2 4

    3. Compressive strength 5

    4. Tensile strength 11

    5. Bond strength 17

    6. Modulus of elasticity 19

    7. Tensile strain capacity 24

    8. Creep 26

    9. Shrinkage 30

    10. Thermal expansion 35

    11. Thermal conductivity 37

    12. Specific heat 38

    13 Fire resistance 39

  • 8/2/2019 Concrete EU Eurocode 2 p59

    3/59

    Symbols

    c cover to reinforcement

    cp

    specific heat

    cv

    coefficient of variation

    D thermal diffusivity

    Ec

    tangent modulus

    Ecd

    design value of modulus of elast

    Ec,eff

    effective modulus of elasticity o

    Ecm

    mean secant modulus of elastici

    fbd

    ultimate (design) bond stress

    fcd

    design compressive strength

    fcd,fat

    design fatigue strength

    fck specified characteristic cylinder fck,c

    confined characteristic compres

    fck,cube

    specified characteristic cube com

    fcm

    mean concrete cylinder compres

    fcm,cube

    mean concrete cube compressiv

    fctd

    design tensile strength

    fctk

    characteristic axial tensile streng

    fctm mean axial tensile strengthfctm,sp

    mean splitting tensile strength

    fctm,fl

    mean flexural tensile strength

    fct,sp

    tensile splitting strength

    fcu

    specified characteristic cube com

    s coefficient for cement type used

    sr,max

    crack spacing

    t time

    coefficient applied to age functio

    ccoefficient of thermal expansion

    cc

    coefficient for long-term and loa

    strength

    ct

    coefficient for long-term and loa

    (t) age function for strength

  • 8/2/2019 Concrete EU Eurocode 2 p59

    4/59

    c

    thermal conductivity

    density

    p,eff

    ratio of area of reinforcement to

    f bar diameter

    (, t0) creep coefficient at time t=

    c

    constant compressive stress app

  • 8/2/2019 Concrete EU Eurocode 2 p59

    5/59

  • 8/2/2019 Concrete EU Eurocode 2 p59

    6/59

    1. Introduction

    In the design of concrete structures, engineers have t

    concrete type(s) aimed at meeting the specific perfor

    For instance where calculated deflections exceed serv

    achieve lower deflections by increasing the class of co

    of elasticity, rather than by resizing members.

    With this flexibility goes the responsibility for ensuring

    production and subsequent site operations will enabl

    specified requirements in service.

    Typically concrete is specified by compressive strengt

    characteristic compressive strength required. However

    concrete are used that are not normally part of the corelate to both structural integrity and serviceability. B

    of concrete structures, Part 1-1 General rules and rules for

    these properties which are generally assumed to be re

    strength, expressed either as the characteristic or the

    using expressions which include one or other of these

    This publication covers the background to the use of

    structured to provide guidance on:

    the range of concrete properties required in the de

    how each property is determined in BS EN 1992-1

    how the property can be measured.

    how the measured value may be used in design.

    options for modifying the value of the property.

    The guidance is intended to provide design engineers

    concrete behaviour, so that they can optimise the us

    in their design.

    Section 3 of BS EN 1992-1-1 gives principles and rule

    1.1 Scope

  • 8/2/2019 Concrete EU Eurocode 2 p59

    7/59

    BS EN 1992-1-1 (Eurocode 2: Design of concrete struc

    design of concrete structures and in table 3.1 gives re

    mechanical properties of concrete for use in design. T

    number of assumptions and in general will be conser

    values will be appropriate; however, in some circumst

    limit the design possibilities. Engineers who wish to t

    concrete construction may therefore wish to look at identify where changes may be cost-effective. This ma

    to use higher-strength concrete, when serviceability c

    the design process.1 As an example, if a higher value o

    spans could be increased without increasing thicknes

    also lead to lower shrinkage and creep values.

    Designers may therefore wish to specify a value highe

    particular property and this guide provides informatiodesigner should, however, seek assurance from the co

    that the concrete required to achieve the specified va

    see Section 1.2.

    In addition to compressive strength, the following me

    used in some design procedures, and guidance is prov

    targeted values may be achieved for normal-weight c tensile and flexural strength

    bond strength

    modulus of elasticity

    tensile strain capacity

    creep.

    Table 3.1 of BS EN 1992-1-1 provides values for the pr

    characteristics of concrete for a range of strength class

    Table A1.

    I ddi i i l i h d iff

    1.1.1 Mechanical properties

    1 1 2 Other properties

  • 8/2/2019 Concrete EU Eurocode 2 p59

    8/59

    The achievement of ductility in a structure2 is not cove

    of concrete structures, the formation of plastic hinges

    reinforcement will continue to take the load while the

    cl 3.2.4 gives provisions for using reinforcement with

    will also improve the ductility of concrete, but this is

    and BS EN 1992-1-1.

    Where the specifier wishes to establish if a particular

    in design, he should first consult with the concrete su

    available. However, it may be necessary to request an

    supply) where the relationship between this property a

    strength can be established. Such testing can take som

    timetabled.

    If the property values from the test programme have s

    allow for a degree of uncertainty by building in a mar

    version from the property values to an equivalent com

    specification should then either be based on the com

    priate the types of materials that are expected to pro

    alternatively it should be agreed with the producer ththe required property.

    Most of the test methods for other properties listed i

    higher within-test coefficient of variation than for com

    initial testing should be designed to establish the pro

    strength only, and compressive strength should rema

    supply based on this relationship.

    In circumstances in which specified properties may re

    normal range of production, it is advisable for the spe

    with the concrete producer. In particular, the followin

    Additional lead time may be required for the proc

    d l d i

    1.2 Practical aspects of

    supply

  • 8/2/2019 Concrete EU Eurocode 2 p59

    9/59

    2. Assumptions underlying

    Importantly, Eurocode 2 assumes that design and co

    be subject to adequate supervision and quality co

    be carried out by personnel having the appropriat

    use materials and products as specified.

    meet the requirements for execution and workman

    2008), Execution of concrete structures, and its co

    It is also assumed that the structure will be used in ac

    be adequately maintained.

    In addition, BS EN 1990, Basis of structural design, imp

    using limit state principles. Limit states are states beyfulfils the design intent.

    Ultimate Limit States (ULS) are associated with

    failure, for example, through flexural failure, shear f

    Serviceability Limit States (SLS) correspond to c

    service requirements are no longer met, for examp

    cracking or stress.

    In design, both limit states are checked (or verified) a

    relevant design situations. ULS calculations always us

    calculations almost always use mean values.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    10/59

    3. Compressive strength

    The only engineering property of concrete that is rou

    compressive strength. This has a relationship to most

    provides the basis for estimating these.

    It is important that the design strength of a structure

    durability, fire design or structural design requiremen

    design stage. This will avoid having to recheck and/or

    consequence of an increased strength requirement to

    example, from which there could be implications. As

    strength as a result of going to a higher class of concr

    ratio will need to be increased for crack control purpo

    In BS EN 206-1: Concrete Specification, performanc

    pressive strength is expressed as a strength class. BS

    compressive cylinder strength fck

    (based on 2:1 cylinde

    It also provides the basis for expressions in BS EN 199

    properties (for example, tensile strength, E-value, cre

    precise values may be derived when necessary from te

    test standard.

    While the specified 28-day characteristic strength is th

    there are situations where it may be appropriate to u

    an instance includes where the structure will not be l

    and the concrete is of a type and in a situation where

    develop significantly beyond 28 days.

    In addition, it may be necessary to know the strength

    transfer of pre-stress, or for removal of props.

    In the UK the compressive strength is tested using cu

    Com

    3.1 Strength class

  • 8/2/2019 Concrete EU Eurocode 2 p59

    11/59

    The design compressive strength of concrete, fcd

    , acco

    fcd

    = cc

    fck

    /c

    where

    fck

    = characteristic cylinder compressive streng

    c

    = partial (safety) factor for concrete

    cc

    = a coefficient taking account of long-term e

    (which is reduced under sustained load) and

    the way the load is applied.

    Expression (1) is equivalent to the term fcd

    = 0.67fcu

    /

    represented as fck,cube

    ). In each case the material safety

    recommends that cc

    = 1.

    However, cc

    is an NDP and the UK National Annex t

    cc

    should be 0.85 for compression in flexure and axia

    (for example, shear, torsion and web compression s

    be taken conservatively as 0.85 for all phenomena. Th

    consistent with that of BS 8110 as shown in Figure 1 f

    3.3 Design strength

    Fre

    uency

    q

    Mean =fcm

    Characteristic fck

    Design

    = 0.85 / 1.5

    f

    fcd

    ck

    CYLINDER strength

    Mean fcm, c

    =

    0 10 20 30 40

    fck /1.5

    (

    Compatibledesign strength

    BS 8110

    BS EN 1992-1-1 f c

    Figure 1Compressive strength definitions to BS EN

    1992-1-1 and BS 8110 for strength classC30/37.

    EC2 3.15

  • 8/2/2019 Concrete EU Eurocode 2 p59

    12/59

    3.4 Confined concrete

    Com

    Confinement of concrete results in a modification of t

    Confinement can be generated by links or cross-ties ad

    stresses. This results in an increased effective compres

    strains as outlined in BS EN 1992-1-1, Clause 3.1.9. Th

    expressions:

    fck,c

    = fck

    (1000 + 5.0 2

    /fck

    ) for 2

    0.05fck

    fck,c

    = fck

    (1125 + 2.5 2/f

    ck) for

    2> 0.05f

    ck

    where

    2

    is the effective lateral stress due to confinem

    Mechanical properties are used to check serviceability

    always related to the mean compressive strength and

    simplicity, the mean strength is assumed to be the ch

    (cylinder), equivalent to plus 10MPa in terms of cube

    nature of the relationships between the mechanical pr

    strength, the use of a margin of 8MPa (cylinder) and 1

    and there is no justification for using a lower margin.

    The target mean strength, fcm

    , is also the value used t

    intended to take account of the normal variability tha

    This margin of 8MPa for cylinders is consistent with a

    deviation (SD) of about 5MPa:

    fck

    = fcm

    1.64SD, where 1.64SD = 8

    Therefore

    SD = 8/1.64 5MPa

    The margin is 10MPa for cubes, which is equivalent to

    6MP Thi i ll i hi h bili fTable 1

    3.5 Target mean strength

    EC2 3.24

    EC2 3.25

  • 8/2/2019 Concrete EU Eurocode 2 p59

    13/59

    Numerous types of cement are available and in gener

    assumed that the cement type will not affect the 28-

    However, the cement type has a significant effect on

    and other properties, and the concrete supplier should

    development data. Alternatively BS EN 1992-1-1 exp

    are given below. Appendix A, Table A2 provides detail

    cements and combinations.

    While design is usually based on the 28-day strength

    gives an expression for the development of the mean

    with time at 20C as follows:

    fcm

    (t) = [cc

    (t)] fcm

    wherefcm

    (t) is the mean compressive strength at age td

    where

    s is a coefficient which depends on cement type= 0.20 for cement of strength classes CEM 42.5R,

    = 0.25 for cement of strength classes CEM 32.5R,

    = 0.38 for cement of strength classes CEM 32.5N

    (where Class R = high early strength; Class N = no

    early strength).

    Usually the cement class will not be known at the des

    should be assumed unless the following alternatives Where ground granulated blastfurnace slag (ggbs)

    bination or where fly ash (fa) exceeds 20%, class N

    Where ggbs exceeds 65% or fa exceeds 35%, Clas

    C i h b i d f E i (4)

    3.6 Development of

    compressive strength with

    time

    cc(t) = exp {s[1 (28)0.5

    ]} tEC2 3.2

    EC2 3.1

  • 8/2/2019 Concrete EU Eurocode 2 p59

    14/59

    Com

    CEM 42.5RCEM 52.5NCEM 52.5 (Class R)

    CEM 32.5RCEM 42.5 (Class N

    CEM 32.5 (Class S)

    1 10 Age (days)

    1.4

    1.2

    1.0

    0.8

    0.6

    0.4

    0.2

    0.0

    Proportionof

    28

    -day

    compressivestrength

    R

    N

    N

    Figure 2Rate of compressive strength development at

    20C for different cement strength classes.

    In reality there is a wide range of strength developme

    If the designer has information that shows that the con

    more rapidly, this information could be used, for exam

    BS EN 1992-1-1 notes that the estimated strength de

    not be used retrospectively to justify a non-conformi

    The strength obtained using standard test specimens

    the actual compressive strength in the structure. This

    including the process of manufacture and curing whic

    small test specimens. BS EN 13791Assessment of in-s

    and pre-cast concrete components requires that the m

    0.85 times the strength of standard specimens. This f

    factor m and should not be confused with cc which

    The rate of strength development in the structure its

    type of concrete (mainly cement type and conten

    concrete placing temperature

    bi

    3.7 Strength in the

    structure

  • 8/2/2019 Concrete EU Eurocode 2 p59

    15/59

    10 10100 1000

    Age (days) Age

    1.8 1.8

    1.6 1.6

    1.4 1.4

    1.2 1.2

    1.0 1.0

    0.8 0.8

    0.6 0.6

    0.4 0.4

    0.2 0.2

    0.0 0.0

    Proportionof

    28-

    daycubestrength

    Proportionof

    28-

    daycubestrength

    1.5 m blocks 300 mm walls

    CEMI

    CEMIIIA (50% ggbs)

    CEMIIB-V (30% fly ash)

    a) b)

    cube

    Figure 3Strength development measured from cores. Examples of long-term strength development are sho

    by testing 1:1 cores extracted from both 1.5m cubes a

    and values are expressed as a proportion of the 28-da

    strength of the CEM I concrete only marginally excee

    one year, concrete using CEM IIIA was more than 20%

    was more than 40% higher, indicating the long-term

    cement types provided conditions are sufficiently mocontinue.

    Computer models based on maturity calculations are a

    development if necessary. The producer can provide ba

    type, class and content, and the adiabatic temperatu

    model is being used. The models assume that there is

    continue without interruption and this is a reasonablafter casting. The validity of this assumption for longe

    assessed on a case-by-case basis.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    16/59

    4. Tensile strength

    In design, tensile strength is used in both serviceability

    for example:

    In general, considerations of cracking, shear, punc

    The evaluation of the cracking moment for prestre

    The design of reinforcement to control crack width

    early-age thermal contraction.

    Developing moment-curvature diagrams and in th

    calculation of deflection, higher tensile strengths l

    lower deflection.

    The design of fibre-reinforced concrete.

    It is also used in the design of unreinforced concre

    pavements.

    It should be noted that increasing the tensile strength

    For example, in the case of early thermal cracking, hig

    increased minimum steel ratio to accommodate the

    when a crack occurs. In addition higher strength norm

    binder content and hence higher temperature rise an

    Tensile strength is commonly defined in one of three

    splitting strength or flexural strength. Values derived

    Table 2.

    4.1 How tensile strength is

    dealt with in BS EN 1992-1-1

    Mix designation C12/16 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60 C55/6

    Mean axial tensilestrength fctm

    1.6 1.9 2.2 2.6 2.9 3.2 3.5 3.8 4.1 4.2

    Table 2Values of tensile strength in relation to

    strength class.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    17/59

    The design tensile strength of concrete, fctd

    , according

    fctd

    = ct

    fctk

    0.05

    /c

    where

    fctk

    0.05

    = characteristic tensile strength of concre

    c

    = partial (safety) factor for concrete = 1.5

    ct

    = coefficient taking account of long-term

    is an NDP with a recommended value o

    In BS EN 1992-1-1, the term tensile strength refers t

    under concentric tensile loading.

    For normal structural uses, the mean tensile strength,

    by the expressions:

    Strength classes C50/60 fctm

    = 0.30 fck

    (2/3)

    Strength classes > C50/60 fctm

    = 2.12 loge

    [1

    Note that for strength classes C50/60 fctm

    is derive

    strength classes > C50/60 the tensile strength is deri

    The direct tensile strength is a value that is rarely det

    European or International Standard. However, where

    by the tensile splitting test in accordance with BS EN

    the tensile strength to be calculated from the tensile

    fct

    = 0.90 fct,sp

    When using this approach, tests should be on concre

    pressive strength, as this will result in the best estima

    4.1.1 Tensile strength used in

    design

    4.1.2 Tensile splitting strength

    EC2 3.16

    EC2 Table 3.1

    EC2 3.3

  • 8/2/2019 Concrete EU Eurocode 2 p59

    18/59

    The flexural strength is the higher of:

    fctm,fl

    = (1.6 h/1000) fctm

    where

    h is the total member depth in mm

    or fctm,fl

    = fctm

    Rearranging Expression (11), the fctm

    may be estimated

    on a 100 100mm prism in accordance with BS EN 1

    fctm

    = fctm,fl

    /1.5

    BS EN 1992-1-1 provides expressions for calculating te

    fctm

    (t) = [cc

    (t)]fctm

    where

    cc

    (t) is defined in Expression (5)

    = 1 for t < 28 days

    = 2/3 for t 28 days.

    Hence up to 28 days the development of tensile streng

    strength. However, beyond 28 days the tensile streng

    extent as shown in Figure 4.

    4.1.4 Effect of age

    CEM 42.5RCEM 52.5N

    1.4

    1.2

    strength

    Figure 4Rate of tensile strength development at 20C

    for different cement strength classes.

    EC2 3.23

    EC2 3.4

  • 8/2/2019 Concrete EU Eurocode 2 p59

    19/59

    When estimating development of tensile strength, fo

    risk of early-age cracking and the requirement for crac

    recommends that tests should be carried out, taking

    conditions and the dimensions of the structural mem

    itself may not reflect directly the exposure conditions

    member, but it may be possible to test specimens wi

    In Figure 5, which shows the development of tensile s

    restrained movement, the upper two lines show the t

    the lower of these lines (fb) reflecting the 0.7 reductio

    lower two lines show the induced early-age contract

    The upper of the two lines (2b) shows the additional

    It can be seen that in addition to the risk of restraine

    cracking from long-term drying shrinkage after ten ye

    effect of temperature which can be significant is not

    StrengthMPa

    4.0

    3.0

    2.0

    1.0

    0

    1

    2

    Days

    Years

    1 2 3 5 7 10 14 28 56 100

    0.5

    T

    h

    en

    t

    sile

    sreng

    t

    Tensile

    stre

    ss

    T

    Sus

    Contractio

    n +cre

    Contraction stress+

    Age

    Figure 5Development of tensile strength and tensile

    stress from restrained movement.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    20/59

    Figure 6Location of the weakest link in (a) the

    flexural test, (b) the tensile splitting test,and (c) the direct tensile test.

    (a) Flexural Test

    Weakest link in unde

    (c) Direct tensile strength

    W

    (b) Splitting test

  • 8/2/2019 Concrete EU Eurocode 2 p59

    21/59

    Because of high test variability of tensile testing, it is r

    be based on the measurement of compressive streng

    information on the relationship between tensile and

    concrete for comparison with that given in BS EN 199

    Where information on the development of tensile stre

    is sought, the test method needs to be agreed and th

    either the tensile splitting test BS EN 12390-6, or the fl

    reference method is used. Due to testing variability, at

    should be tested at each age. To compensate for the la

    ded that the result is presented as a mean value, rath

    Depending on what the data are required for, the con

    should be either:

    those that are expected to give the target mean cotest value is then taken as the corresponding mea

    those that are expected to give the characteristic c

    test value is then taken as the corresponding chara

    Depending upon the specific requirements it may be

    decrease the tensile strength. For example, to resist c

    desirable, but if cracking is likely to occur then the mi

    reduced for a lower tensile strength. Factors which ha

    are as follows:

    Compressive strength: in general the tensile streng

    pressive strength.

    The relative volumes of cement paste and aggregate

    Coarse aggregate type: concrete containing high-qtends to have higher tensile strength than concret

    crushed flint gravels in particular may result in a lo

    with the glassy flint surfaces.

    Aggregate size: the tensile strength tends to be hig

    d t th i i t f d

    4.3 Some testing practical

    advice

    4.4 Factors influencing

    tensile strength

  • 8/2/2019 Concrete EU Eurocode 2 p59

    22/59

    5. Bond strength

    In reinforcement design, BS EN 1992-1-1 covers only

    Knowledge of the bond strength of reinforcement is r

    To establish anchor and lap lengths.

    To enable crack spacing and crack width to be calc

    BS EN 1992-1-1 provides information on bond in rela

    bond stress is given by the expression:

    fbd = 2.25 12fctd

    where

    fbd

    is the ultimate (design) bond stress

    1

    is a coefficient related to the quality of the

    the bar during concreting

    = 1.0 for condition of good bond

    = 0.7 for all other cases and for bars in struc

    2

    is related to bar diameter

    = 1.0 for f 40mm (NDP)

    = (140 f)/100 for f> 40mm

    fctd

    is the design tensile strength defined as:

    fctd

    = ct fctk,0.05

    /c

    where

    c is the partial safety factor for concrete = 1.5

    ctis a coefficient taking account of long-term

    unfavourable effects resulting from the way

    5.1 How bond strength is

    dealt with in BS EN 1992-1-1

    EC2 8.2

  • 8/2/2019 Concrete EU Eurocode 2 p59

    23/59

    where

    c is the cover to reinforcement

    f is the bar diameter

    p,eff

    is the ratio of the area of reinforcement to t

    The coefficients 3.4 and 0.425 are the UKs NDPs

    k1

    is a coefficient which takes account of the b

    = 0.8 for high bond bars.

    The coefficient k1

    has replaced the ratio fct

    /fb

    (= 0.67)

    crack spacing in BS 8007. Other more significant chan

    BS 8007, most notably a reduction in the effective are

    the steel, have led to the required area of reinforcemen

    reduced.

    Observations of early-age cracking suggest that the rrally applicable, with occasional crack widths in exces

    would be unacceptable to adopt a significantly less ro

    mended in CIRIA C6606 that the factor of 0.7 (BS EN

    where it cannot be shown that good bond exists) sho

    value to 0.8/0.7 = 1.14 until experience with applicat

    indicates that a value of 0.8 is acceptable.

    Bond testing is covered by BS EN 10080. The test req

    involves four-point bending of a test beam which con

    bar in the tensile zone. This has replaced the previous p

    force and slip is measured and the bond strength is c

    stress at which a particular magnitude of slip occurs.

    The bond strength is determined by the characteristi

    concrete as follows:

    F d f d b h j d ib h d

    5.3 Measuring bond

    strength

    5.4 Factors influencing

    bond strength

    Mo

  • 8/2/2019 Concrete EU Eurocode 2 p59

    24/59

    Mo

    6. Modulus of elasticity

    The value of the modulus of elasticity, E-value, chose

    analysis with regard to stiffness of members. For exam

    deflection often the controlling factor in slab des

    moment analysis

    requirements for prestressed elements column shortening under load

    stresses due to restrained movements.

    Such movements are also influenced by creep which

    There are two types of elastic modulus. The static m

    deformation of a cylinder under an applied load, usua

    The dynamic modulus is determined by resonance m

    ultrasonic pulse velocity (UPV). The two test procedu

    value of the modulus. Static modulus is the value usu

    The E-value is the ratio between stress (load/area) an

    length/length). As concrete is not a truly elastic mate

    and strain is not constant. Three E-value conventions

    the secant modulus

    the tangent modulus

    the initial tangent modulus (see Figure 7).

    6.1 Definitions

    Tangent

    modulusInitialtangentmodulus

    Secant

    Stress

    Figure 7Diagrammatic stressstrain relationships for

    concrete.11

  • 8/2/2019 Concrete EU Eurocode 2 p59

    25/59

    These are all measurements of the static modulus. Th

    approximately equal to the dynamic modulus and, by

    low stress levels. The most generally useful measure is

    1992-1-1 it is the secant modulus, Ecm, that is used in

    In design, the secant modulus, Ecm

    (in GPa), is derived

    fcm

    (in MPa), from the expression:

    Ecm

    = 22 [fcm

    /10]0.3 GPa

    In Figure 8 moduli derived from Expression (17) are se

    c = 0 to 0.4fcm with quartzite aggregates. For limestonis reduced by 10% and 30% respectively and for basa

    6.2 How E-value is dealt

    with in BS EN 1992-1-16.2.1 Use of E-value in design

    60

    50

    40

    30

    20

    10

    0

    C12/16

    C16/20

    C20/25

    C25/30

    C30/37

    C35/45

    C40/50

    C45/55

    C50/60

    C5 5

    Compressive strength c

    Modulusof

    ela

    sticity(GP

    a)

    Figure 8Modulus of elasticity in relation to

    compressive strength class and aggregatetype.

    Although not explicitly stated in BS EN 1992-1-1, Claus

    aggregates may also be applied to concretes with sili

    assumes that the designer knows the aggregate to be

    EC2 Table 3.1

    Mo

  • 8/2/2019 Concrete EU Eurocode 2 p59

    26/59

    Mo

    Poissons ratio is also used in elastic analysis and in a

    taken as 0.2 for uncracked concrete and 0 for cracked

    The variation of modulus of elasticity with time is est

    Ecm(t) = [fcm(t)/fcm]0.3Ecm

    where Ecm

    (t) and fcm

    (t) are the values at an age of tda

    28 days. The rate of development of modulus of elastic

    that modulus develops more rapidly than strength in

    ficant growth beyond 28 days. In addition the cemen

    This is not surprising as the usually stiffer aggregate c

    of the concrete and is therefore the dominant factor.

    6.2.2 Variation with age

    CEM 42.5RCEM 52.5NCEM 52.5 (Class R)

    CEM 32.5RCEM 42.5 (Class N)

    CEM 32.5 (Class S)

    1 10

    Age (days)

    1.4

    1.2

    1.0

    0.8

    0.6

    0.4

    0.2

    0.0

    Proportionof2

    8-daymodulus

    28

    R

    N

    N

    Figure 9Rate of development of modulus of elasticity

    at 20C for different cement strength classes.

    Work is in progress within the European Committee fo

    6.3 Measuring the E-value

    6.3.1 Test methods

    EC2 3.5

  • 8/2/2019 Concrete EU Eurocode 2 p59

    27/59

    The initial tangent modulus may be determined in

    1. By undertaking ultrasonic pulse velocity (UPV) me

    EN 12504-4. However, there is no procedure for c

    initial tangent modulus. The procedure is covered

    that this procedure will be included in the UK Nati

    2. Measuring the dynamic modulus by means of a varia

    for measuring the dynamic modulus ( initial tange

    As deflection forms part of the serviceability limit sta

    so the concrete mix proportions used for testing shou

    compressive strength.

    Care is needed when selecting a test machine to use in calibration for cube testing may not be suitable for

    tend to be with high-capacity machines (heavy plate

    seating is not free to rotate. The indication of a probl

    large differences between the three strain readings.

    When a measured E-value is being used, the designer

    partial safety factor of cE

    , say 1.1 in place of the norm

    A safety factor cE

    less than 1.1 is not recommended d

    with the measured value and variability of production

    There are a number of factors to be considered:

    Compressive strength. While a higher strength lea

    there is no direct proportionality. For example, to necessary to increase the strength by at least thre

    a cost-effective solution.

    Aggregate E-value. The aggregate comprises abo

    stiffer than the cement paste. Hence the E-value of

    h E l f h Fi 10 h h

    6.3.2 Guidance on E-value

    testing

    6.4 Factors influencing

    modulus of elasticity

    Mo

  • 8/2/2019 Concrete EU Eurocode 2 p59

    28/59

    60

    55

    50

    45

    40

    35

    30

    25

    20

    15

    10

    M

    od

    ulu

    so

    fe

    las

    ticit

    y(C

    oncre

    te

    GP

    a)

    C12/16 C20/25 C30/37 C40/50 C50/60 C60

    Strength class

    Figure 10The relationship between strength class,

    aggregate E-value (and specific gravity) andconcrete E-value.

    Mo

    Mineral additions. The presence of either fly ash

    reduced elastic deformations provided the design

    than 28 days at 20C and conditions are such that

  • 8/2/2019 Concrete EU Eurocode 2 p59

    29/59

    7. Tensile strain capacity

    The tensile strain capacity, ctu

    , is the maximum strain

    without a continuous crack forming. It is used in the

    CIRIA C6606 to assess the risk of early-age thermal cr

    width.

    Tensile strain capacity of concrete ctu

    is not dealt with

    comprehensive review of published data14 a simple lin

    between ctu

    and the ratio of the tensile strength fctm

    t

    in compression) as follows:

    ctu

    = [1.01(fctm

    /Ecm

    ) 106] + 8.4 microstrain

    Simplifying this expression to:

    ctu

    = fctm

    /Ecm

    was found to provide a lower bound value for use in d

    of ctu have been derived from estimates given in BS E(Section 4) and elastic modulus (Section 6) for each s

    gate types.

    Values estimated from BS EN 1992-1-1 apply under c

    take account of sustained loading during an early the

    1. a creep coefficient, which increases the tensile stra

    2. a coefficient to take account of reduced capacity u

    The net effect on ctu

    is an increase of 23%6. Results o

    Figure 11. To assess cracking at later life, ctu

    may be d

    applying age factors to fctm

    and Ecm

    , that is:

    7.1 How tensile strain

    capacity is dealt with in

    BS EN 1992-1-1

    Ten

  • 8/2/2019 Concrete EU Eurocode 2 p59

    30/59

    Ten

    140

    120

    100

    80

    60

    40

    20

    0

    Straincap

    acity(microstrain)

    C12/16

    C16/20

    C20/25

    C25/30

    C30/37

    C35/45

    C40/50

    C45/55

    C50/60

    C 5

    Compressive strength cla

    Figure 11Early-age (three-day) tensile strain capacity

    under sustained loading.

    There is no standard test for measuring tensile strain

    measuring tensile strain capacity ctu

    is to subject pris

    measure the strain up to failure.15 Direct measuremen

    conditions within a test specimen that are similar to

    cracking - for example, stress rig tests subject a dog-b

    cycle. During heating the concrete is allowed to expa

    contraction. When the concrete cracks, the release of

    used to derive the strain at failure. This may be comp

    temperature change and hence, with a knowledge of

    expansion), the restrained thermal contraction require

    calculated.

    Direct measurement of ctu generally requires a large monitoring equipment. An alternative approach is to

    tensile strength fctm

    and elastic modulus Ecm

    .14

    7.2 Measuring tensile strain

    capacity

  • 8/2/2019 Concrete EU Eurocode 2 p59

    31/59

    8. Creep

    Creep is time-dependent deformation (strain) under

    load-induced deformations such as shrinkage, swellin

    Creep strain is typically two to four times the elastic s

    needed for several reasons:

    To estimate long-term deflections in beams and lowalls. This may be important, for example, in esta

    when fixing rigid, brittle partitions to a concrete fr

    To estimate prestress losses.

    To estimate stress relaxation and redistribution ov

    reducing the risk and/or extent of cracking. Creep

    stresses induced by other restrained movements, fo

    contraction; or by loading.

    St

    ra

    in

    Figure 12Time-dependent deformations in concrete

    subjected to a sustained load - change instrain of a loaded and drying specimen.11

    Generally, creep depends on ambient humidity, the d

    composition of the concrete. It is also influenced by t

    first loaded and on the duration and magnitude of th

    8.1 How creep is dealt with

    in BS EN 1992-1-1

  • 8/2/2019 Concrete EU Eurocode 2 p59

    32/59

    The creep coefficient (, t0) is determined by the f

    Relative humidity for indoor conditions (RH = 5

    (RH = 80%). More creep occurs under dryer condi

    Element geometry defined by a notional thicknes

    Strength class.

    Age at loading which affects the stress/strength

    Cement class Slow, Normal or Rapid strength ga

    Stress/strength ratio at loading Expression (21ratio of 0.45 based on the characteristic cylinder st

    the stress exceeds this value, micro-cracking will ca

    sions are provided in BS EN 1992-1-1 for taking th

    In order to develop creep curves showing the develop

    mative) of BS EN 1992-1-1 provides an expression whic

    element size, the strength class and the age at loadinshown in Figure 13 for two examples:

    a 500 1000mm precast bridge beam using C35/

    loaded at 28 days;

    an internal floor slab (50% RH) using C30/37 load

    About 50% of the ultimate creep occurs during the fi

    first few years. The coefficient of variation using the a

    to be 20%.

    Elastic Strai

    Creep stra

    500 x 1000mm beam, extern

    250mm slab, internal

    4.0

    3.5

    3.0

    2.5

    2.0

    1.5

    1.0

    0.5

    l+

    creepcoef

    ficient

    Figure 13Estimates of creep coefficients, .

  • 8/2/2019 Concrete EU Eurocode 2 p59

    33/59

    There is currently no European standard test for creep

    series, but a test is being developed for repair products

    and uses 40 40 160mm prisms which makes it un

    Work has started on an ISO test (ISO/ DIS 1920-9) a

    standard stage.

    ASTM C 512 provides a method of measuring the total

    of concrete. While some standard conditions are defin

    varied to obtain information relevant to a specific pro

    are cast, two used for strength testing, two used for c

    loading to determine the changes of strain without lo

    and to autogenous shrinkage. The applied load shall n

    pressive strength at the time of loading. Readings are t

    then again 26 hours later, and then at defined intervone year. A procedure is given for calculating the cree

    According to Brooks,17 the equipment for the ASTM C

    researchers tend to use smaller, less expensive equipm

    8.2 Measurement of creep

    8.2.1 Test methods

    35

    30

    25

    20

    15

    10

    5

    0

    Ef

    fec

    tivemo

    du

    lus

    500 x 1000m

    250mm slab

    0 1 2 3 4 5 6

    Age (years)

    C35/45C30/37

    Elasticmodulus

    Figure 14Estimates of effective modulus, Ec,eff.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    34/59

    Achieving representative drying conditions. Drying

    ratio and it is not normally practical to vary the sp

    take a worse case, or test at a different relative hum

    parts of the section.

    Achieving a representative temperature. In the nor

    of structures, the effect of temperature is relativel

    sidered for specific applications.

    Continuing the test for a sufficiently long period topolation for the life of the structure. Gilbert16 has rev

    for the shape of the creep coefficient versus time c

    useful expressions. He also concluded that the exp

    creep from 28-day creep test data were not reliab

    recommended. Testing of concretes for nuclear pr

    months was acceptable, representing about half a

    log timescale.

    Expression (1) of ASTM C 512 should be used to calcu

    deformation at, say, 30 years. The expression may als

    coefficient (as opposed to assuming it, as in BS EN 19

    deformation by the measured elastic strain.

    Factors affecting creep, other than those already inclu

    are as follows:

    Aggregate volume. As creep takes place in the cem

    of the aggregates will reduce creep.

    The type of cement is important if the age of load

    more rapidly will have higher strength at the age o

    ratio and a lower creep. However, where the stressand the environment is one where the strength wi

    develop more strength after loading will have a low

    why under some circumstances concretes contain

    or CEM III (blastfurnace cement) tend to have low

    Th f i f i ifi l

    8.3 Factors influencing

    creep

  • 8/2/2019 Concrete EU Eurocode 2 p59

    35/59

    9. Shrinkage

    For design purposes, shrinkage is a combination of au

    shrinkage. While it is recognised that shrinkage may o

    state, these deformations are not considered within t

    Knowledge of shrinkage is important for several reaso If shrinkage is restrained, cracking may occur and t

    reinforcement to limit crack widths.

    In prestressed concrete, shrinkage will result in los

    In asymmetrically reinforced concrete, deflections

    Axially loaded columns or walls may be subject to

    Creep may be increased with increased shrinkage.

    Autogenous shrinkage, ca

    , occurs during early hydr

    consumption of water during hydration, the hydratio

    than the unhydrated cement and water. Historically,

    structural concrete was assumed to be of low magnit

    ignored in design. However the tensile strain capacity

    100 microstrain, see Section 7, hence, in relation to thconcrete, even this small strain may be significant. BS

    autogenous shrinkage occurs in all structural concret

    hardening, BS EN 1992-1-1 recommends that it shou

    new concrete is cast against hardened concrete, i.e. i

    cracking.

    In high-strength concrete with a low w/c ratio, the auhigher and may exceed the drying shrinkage.

    Drying shrinkage, cd

    , is caused by the loss of water fr

    Generally this loss of water is from the cement paste

    the main loss of water and contribution to the drying

    9.1 Types of shrinkage

  • 8/2/2019 Concrete EU Eurocode 2 p59

    36/59

    The ultimate autogenous shrinkage is calculated from

    strength and is given by the expression:

    ca

    () = 2.5(fck

    10) 106

    and at time, tdays, the autogenous shrinkage is:

    ca(t) = ca() [1 exp ( 0.2 t0.5)]

    Design values of autogenous shrinkage estimated usi

    shown against age in Figure 15.

    9.2.1 Autogenous shrinkage

    220

    200

    180

    160

    140

    120

    100

    80

    60

    40

    20

    0

    0 50 100 150 20Time (days)

    Autogen

    ous

    shrinkage(microstrain)

    Figure 15Autogenous shrinkage in relation to strength

    class.

    9 2 2 D i g h i k g

    EC2 3.11 and 3.13

    EC2 3.12

  • 8/2/2019 Concrete EU Eurocode 2 p59

    37/59

    Some typical values for indoor and outdoor exposure

    BS EN 1992-1-1 for a range of notional thicknesses ar

    While the procedures in BS EN 1992-1-1 take account

    of aggregate type. There is no recognition of the high

    when certain aggregate types are used. However, wh

    expected that the shrinkage of the aggregates would

    There is no specific European or international standard

    shrinkage. Measurement is particularly difficult as it m

    500

    450

    400

    350

    300

    250

    200

    150

    100

    50

    0

    250

    200

    150

    100

    50

    00.01 0.1 1 10 100 0.01 0.1

    Time (years) Tim

    Dryingshrinkage(micros

    train)

    Dryingshrinkage(microstrain)

    6 months 30 yrs

    150mm

    225mm

    300mm

    500mm1000mm

    b) OUTDOORa) INDOOR

    Figure 16Drying shrinkage for (a) indoor and (b)

    outdoor conditions using C30/37 in sectionsof varying notional thickness.

    9.3 Measurement ofshrinkage

    9.3.1 Autogenous shrinkage

  • 8/2/2019 Concrete EU Eurocode 2 p59

    38/59

    Any drying shrinkage test on concrete will give the to

    combined drying shrinkage and residual autogenous sh

    normal-strength classes (up to C40/50), the compone

    would be expected to be small (< 20 microstrain) but f

    autogenous shrinkage may dominate. Hence, for high

    for the autogenous shrinkage (which takes place up t

    reading is taken) should be added to the drying shrinka

    value for use in design.

    As drying shrinkage is related to the serviceability limi

    used for testing this property should be those that ar

    compressive strength. If the drying shrinkage test use

    interest, the values obtained in the short-term test ca

    BS EN 1992-1-1 and the basic (unrestrained by reinfo

    calculated. By assuming proportional changes, it is alshrinkage at other relative humidities.

    Work has started on an ISO test (ISO/DIS 1920-8). T

    standard stage and is based on an Australian test pro

    The AS 1012.13 test method for measuring drying shr

    prisms that are 285mm long. After 24 hours in the m

    lime-saturated water for seven days at 23 2C, aftespecimen is measured to an accuracy of 0.001mm (t

    stored in a chamber at 23 2C and 50 4% relativ

    length readings being taken at regular intervals in the

    The rate of drying shrinkage is a function of the speci

    typical shrinkage value after eight weeks drying is 750

    The drying shrinkage of aggregates is measured on coIn the UK, in areas where aggregates with high drying

    a drying shrinkage limit of 750 microstrain on the agg

    requirement, but they would be expected to take any re

    The drying shrinkage obtained by this test should not be

    b i f ) d i h i k i f h

  • 8/2/2019 Concrete EU Eurocode 2 p59

    39/59

    Other factors which may affect autogenous shrinkag

    The use of a small proportion of lightweight aggre

    example, replacement of 6% of sand20 will mainta

    reduce auto-genous shrinkage).

    There is limited evidence (summarised in referenc

    be affected by the use of mineral additions. Likely

    using CEM I alone expressed as weight of addition o

    increased by 10% for every 1% of silica fume reduced in direct proportion to the mass perc

    increased by 8% for every 10% of ggbs.

    It is not recommended that these changes are use

    autogenous shrinkage is desirable it may be appro

    these options.

    Drying shrinkage is caused by the loss of water from t

    from the aggregate. In addition to the parameters inclu

    the following factors will influence drying shrinkage:

    The relative volume of the cement paste and aggr

    volume will reduce shrinkage. This may be achieve

    aggregate size. Increasing the aggregate volume fr

    shrinkage by about 20%.16

    The relative stiffness of the cement paste and agg

    shrinkage of the cement paste, so the higher the E

    the shrinkage.

    Use of aggregates with a low drying shrinkage.

    Use of plasticising admixtures to achieve the requir

    increasing the cement content will reduce drying s

    Use of special admixtures that either reduce or co

    9.4.2 Drying shrinkage

    T

  • 8/2/2019 Concrete EU Eurocode 2 p59

    40/59

    10. Thermal expansion

    The coefficient of thermal expansion, c, of concrete

    produced in concrete subject to a unit change in tem

    microstrain per degree centigrade (/C). Values are t

    occurrence of thermal strain has a number of design

    The need to provide joints to accommodate the m The provision of tolerances for elements attached t

    panels.

    Design of reinforcement to control crack widths w

    restrained. This may be of particular concern at ea

    from the cement and additions (see Section 14) m

    to about 50C, and subsequent contraction on co

    cracking.6

    The Eurocode states that unless more accurate inform

    thermal expansion may be taken as 10 microstrain/

    this may not be a conservative value.

    10.1 How the coefficient of

    thermal expansion is dealt

    with in BS EN 1992-1-1

    Coarse aggregate/rock group Thermal expansRock S

    Chert or flint 7.413.0 1

    Quartzite 7.013.2 1

    Sandstone 4.312.1 9

    Marble 2.216.0 4

    Siliceous limestone 3.69.7 8

    Granite 1.811.9 8

    Dolerite 4.58.5 A

    Basalt 4.09.7 7

    Limestone 1.811.7 4

    Glacial gravel 9

    Sintered fly ash (coarse and fine) 5

    Table 3Coefficients of thermal expansion of coarse

    aggregate and concrete5,20.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    41/59

    While in design c

    is assumed to be constant for a pa

    with both age and moisture content. Semi-dry concr

    of thermal expansion than saturated concrete.17 It is i

    undertaken under conditions that reflect the service en

    in relation to the value obtained.

    In-house methods have to be used. Typically, measurin

    specimen that is placed on roller bearings in a water tuntil there is equilibrium of temperature, and a set of le

    then heated to, say, 80C and kept constant until this

    the specimen depth. A second set of readings is taken

    expansion calculated.

    When testing for early-age values, this may be achiev

    (commonly 1m3 with 100mm polystyrene insulation o

    couples and strain gauges. Both temperature and stra

    calculated during cooldown.6

    The concrete mix proportions for the test should be t

    target mean compressive strength.

    As aggregate comprises about 70% of the concrete v

    on the coefficient of thermal expansion as shown in T

    Reducing paste volume will lead to a small reduction in

    but this change is significantly less than that achieved

    10.3 Factors influencing the

    coefficient of thermal

    expansion

    The

  • 8/2/2019 Concrete EU Eurocode 2 p59

    42/59

    11. Thermal conductivity

    The thermal conductivity of concrete, c, determines

    transported through it and hence the rate of heat los

    design it may be necessary when estimating temperat

    in some specific situations as follows:

    Predicting early-age temperature rise and differen Estimating temperature differentials under transie

    storage vessels that are regularly filled and emptie

    Thermal conductivity is not dealt with in BS EN 1992

    The measurement of thermal conductivity is address

    general method for testing the thermal performance

    the test involves imposing a temperature gradient th

    achieve moisture stability and specimens are general

    obtained will therefore be more representative of theto be used in early-age analyses, the measured value

    There are three principal factors influencing the therm

    1. The aggregate type.

    2. The aggregate volume aggregate has a higher the

    and water.

    3. The moisture content as concrete hydrates and

    by water empties and the conductivity reduces.

    Published values of thermal conductivity vary conside

    11.1 How thermal

    conductivity is dealt with inBS EN 1992-1-1

    11.2 Measurement of

    thermal conductivity

    11.3 Factors influencing

    thermal conductivity

  • 8/2/2019 Concrete EU Eurocode 2 p59

    43/59

    12. Specific heat

    The specific heat of concrete, cp, is required in the de

    (through the expression D =c/c

    p) used in thermal

    concrete may vary from 0.75 to 1.17kJ/kgC.22 This is a

    that the temperature rise associated with a particular

    by as much as 20% from a mean value of about 0.9

    therefore, that a representative value is used in early-a

    based on heat generation from the cement.

    Specific heat is not dealt with in BS EN 1992-1-1.

    Specific heat is generally measured using calorimetrybe predicted with a reasonable degree of accuracy usvalues for the individual constituents.

    Two factors in particular influence the specific heat o1. The aggregate type. Aggregate constitutes the larg

    specific heat for rocks ranges from 0.8 to 1.0kJ/kgmay result in a 15% difference for concrete.

    2. The water content. Water has a specific heat that mix constituents. Dealing with the water content heat differs for free water (4.18kJ/kgC) and bound

    Therefore to calculate the specific heat for concrete, bound water need to be known and this is determine

    method is described in CIRIA C660

    6

    and values derivedthermal analysis are given in Figure 17 for concretes ww/c ratios. Late-life values may be 510% lower.

    12.1 How specific heat is

    dealt with in BS EN 1992-1-1

    12.2 Measurement of

    specific heat

    12.3 Factors influencing

    specific heat

    1.0Figure 17

    The relationship between cement content, w/cratio and early age specific heat of concrete

  • 8/2/2019 Concrete EU Eurocode 2 p59

    44/59

    13. Fire resistance

    Concrete is non-combustible and does not support th

    smoke, toxic gases or emissions when exposed to fire

    load. Not surprisingly, the European Commission has

    fire designation, namely A1.

    Concrete has a slow rate of heat transfer which makes

    compartments, and under typical fire conditions con

    Structural fire design is dealt with in BS EN 1992-1-2.

    The effects of fire on concrete are loss of strength of th

    surface. Loss of strength of concrete starts as a result o

    the effect is modest up to about 300C, being of the

    300C the strength loss is much more severe and at

    50%.23 Due to the slow heat transfer through concre

    limited to the surface zone and the section retains m

    with most types of concrete but the severity depends u

    class and the moisture content. Sometimes explosive s

    in vapour pressure as water turns into steam. Spallingconcrete as its ability to relieve the vapour pressure r

    the integrity of the remaining reinforced concrete is u

    BS EN 1992-1-2 provides three methods of determinin

    tabulated data (for member analysis only); simplified

    analysis or parts of structures); and advanced calcula

    including global structural analysis). In special cases fi

    levels and resistance are calculated, may be used.

    Information on fire resistance is given in BS EN 1992

    13.1 The effects of fire

    13.2 How fire resistance is

    dealt with in BS EN 1992-1-2

  • 8/2/2019 Concrete EU Eurocode 2 p59

    45/59

    High-strength concrete is dealt with separately in Sec

    information presented for three strength classes definUK National Annex as follows:

    Class 1 C55/67 and C60/75

    Class 2 C70/85 and C80/95

    Class 3 C90/105.

    The effect of temperature on the compressive strength

    No distinction is made for aggregate type. High-stren

    adversely affected by temperature.

    Compressive s

    Calcareo

    Silic

    Tensilestrength

    Temperature (

    Relativestrength

    1.0

    0.9

    0.8

    0.7

    0.6

    0.5

    0.4

    0.3

    0.2

    0.1

    00 200 400 600 800

    Class 1C55/67 & C60/75

    Relativestrength

    0.8

    Class 3C90/105

    1.0

    0.9

    0.7

    0.6

    0.5

    0.4

    0.3

    0 2

    Siliceous aggregate

  • 8/2/2019 Concrete EU Eurocode 2 p59

    46/59

    There is a vast database of concrete fire testing over m

    rating of concrete members is based. Historically, lab

    structural members which could be tested; however,

    been performed at facilities such as the Building Rese

    Cardington. Criteria for fire testing are based on main

    restricting transfer of heat and smoke.

    In most normal situations, concrete can be considere

    that further enhancement is not necessary. For a few

    ment of the fire protection or resistance may be requ

    as follows:

    Use of limestone aggregates rather than siliceous

    Use of lightweight aggregate concretes. When dry

    but laboratory tests indicate possible poor perform

    fire begins.23

    Calcium aluminate cement has a higher resistance

    types. While this cement is widely used for non-st

    refractory linings, there is still debate over its suita

    local provisions need to be followed.

    Recognition that high-strength, low-permeability c

    some situations, structural considerations overridemay be little practical scope for reducing concrete

    BS EN 1992-1-2 recommends the option of using n

    polypropylene fibres. The mechanism is believed t

    absorbed in the cement matrix, providing voids for

    caused by steam build-up. However, further resea

    mechanism.23

    Notwithstanding the above recommendations, it sho

    normal approach is to improve the fire resistance of an

    concrete itself. The most widely used approach is to in

    to use render and plaster coatings. Where the loss of

    ifi i l l f h b id

    13.3 How fire resistance ismeasured

    13.4 Improving the fire

    resistance of concrete

  • 8/2/2019 Concrete EU Eurocode 2 p59

    47/59

    14. Adiabatic temperature

    For the control of early-age thermal cracking, a limit

    rature rise of concrete or on allowable temperature diff

    Compliance may require either appropriate concrete se

    initial testing of the proposed concrete and/or some

    which requires information on the heat generation of

    Full-scale trials are generally expensive and the contr

    producer to undertake some initial testing of the conc

    temperature rise, i.e. the temperature rise under perfe

    this condition is difficult to achieve and the concrete

    of the adiabatic temperature rise.

    CIRIA C6606 provides temperature rise data for a rang

    the cement content and type, and a simple numerica

    ture rise and thermal gradients in walls. The model us

    as a basis for temperature prediction.

    The control of early-age thermal cracking is dealt with

    design of liquid-retaining and containment structures.

    BS EN 1992-1-1, Section 7.3 for the design of reinforce

    conditions of conti-nuous edge restraint, i.e. a wall on

    determined in part by the magnitude of the restrained

    on temperature rise and fall in relation to the concret

    range of concretes and element sizes.

    There are numerous tests that may be used to measu

    14.1 The need for adiabatic

    temperature rise data

    14.2 How early-age

    temperature rise is dealt

    with in BS EN 1992-3

    14 3 Measuring the

    Adiabati

  • 8/2/2019 Concrete EU Eurocode 2 p59

    48/59

    per unit weight of cement (kJ/kg) based on the mass

    calorimeter. The specific heat of the mortar is about 1

    obtained using the semi-adiabatic test are shown in F

    combinations.25

    When generating data to make predictions of temper

    is to test concrete using constituents and proportions

    representative of, the mix to be used in practice. Whi

    design stage, it is advisable, where thermal cracking i

    soon as the concrete mixes have been established. O

    may be required and this provides an opportunity to

    Under conditions where a high temperature rise is ex

    with a high cement content, or when placing at high appropriate to provide information on temperature r

    a cube, commonly 1m3, which is insulated on all face

    polystyrene.

    0 10 20 30 40 0 10 200 0

    10 10

    20 20

    30 30

    40 40

    50 50

    60 60

    70 70

    80 80

    Temperaturerise( C)

    Te

    mp

    eraturerise( C)

    Time (hours) Time (ho

    CEM I

    20% fly ash

    35% fly ash

    50% fly ash

    Figure 20Semi-adiabatic test results for concretes

    containing (a) fly ash and (b) ggbs24 (bindercontent = 500kg/m3).

    (a) flyash (b) ggbs

  • 8/2/2019 Concrete EU Eurocode 2 p59

    49/59

    If it is necessary to reduce the temperature rise in-sit

    available6 as follows:

    Cooling the aggregates by spraying with water or

    Using ice to partially replace mix water.

    Using liquid nitrogen to cool the mixed concrete.

    Using cooling pipes in the element to remove hea

    Using low-insulation formwork to permit rapid he

    temperature gradients are not critical).

    In addition to reducing early-age temperature rise, th

    to reduce the risk of thermal cracking:6

    Using aggregate with a low coefficient of thermal

    Using aggregate which leads to a high tensile strai

    Reducing restraint by planning pour sizes and sequ

    Reducing restraint by introducing full- or partial-m

    Using high-insulation formwork or surface insulati

    sections when temperature gradients are critical.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    50/59

    15. Durability

    Design for durability uses a deemed-to-satisfy approa

    proportions and cover provided for a variety of expos

    constituent materials are also specified or their prope

    dations for the UK are provided in BS 8500 Part 1 wh

    Standard to BS EN 206-1, which is in turn referenced8500-1 gives recommendations for an intended wo

    years. However the UK National Annex for Eurocode

    working life of 120 years for Category 5 structures wh

    engineering structures. It can be assumed that the BS

    also suitable for an indicative design working life of 12

    Corrosion of reinforcement occurs when the protecti

    environment in concrete is lost, either as a result of ca

    Exposure conditions are categorised as follows:

    X0 no risk of reinforcement corrosion or attack

    XC reinforcement corrosion induced by carbona

    XD reinforcement corrosion induced by chloride

    XS reinforcement corrosion induced by chlorides

    For each of these environmental actions and levels of

    values are given for maximum w/c ratio, minimum st

    content. BS 8500-1 provides limits specific to the UK

    that it allows a trade-off between concrete quality an

    BS EN 8500-1 gives four levels of freezethaw exposu

    ment is the recognised means for resisting freezetha

    required, typically in the range 35.5%, with the highe

    a smaller maximum aggregate size Also limits are pla

    15.1 Preventing

    reinforcement corrosion

    15.2 Preventing freeze

    thaw damage

  • 8/2/2019 Concrete EU Eurocode 2 p59

    51/59

    BS EN 206-1 defines only three levels of chemical att

    groundwater (XA1 to XA3). The XA action is redefined

    exposure classes limiting values and test methods rec

    significantly from UK practice. BRE Special Digest 126 c

    actions including those for mobile groundwater, acids

    recommends this BRE approach. Recommendations i

    Design Chemical (DC) classes which take account of th

    acidity, the mobility of the groundwater and the hydroguidance on additional protective measures (APM) th

    BS EN 206-1 deals with alkalisilica reaction through

    constituent materials shall not contain harmful ingre

    be detrimental to durability. BS 8500-2 requires the

    minimise the risk of potentially damaging ASR. Follow

    is deemed to satisfy this requirement.

    In addition to the deemed-to-satisfy prescriptive app

    performance-based design methods for durability. Su

    appropriate under a range of circumstances including the working life significantly exceeds 50 years

    the structure is special, requiring a low probabilit

    the environmental actions are particularly aggress

    In adopting the performance-based approach based o

    are proven and representative of actual conditions, a

    criteria. When analytical methods are used these sho

    that are representative of actual conditions.

    15.3 Preventing chemicalattack

    15.4 Avoiding alkalisilica

    reaction

    15.5 Performance-based

    design for durability

    The use of re

  • 8/2/2019 Concrete EU Eurocode 2 p59

    52/59

    16. The use of recycled agg

    The UK aggregate industry optimises the use of recy

    wider aim of sustainable development.

    BS EN 206-1 notes that it does not include provision

    suitability may be established on the basis of the gen

    European Technical Approval, or national standards o

    their use in concrete conforming to BS EN 206-1.

    BS 8500-2 permits the use of RA and RCA (recycled

    to specific requirements of BS 8500 and which, when

    aggregates, meet the requirements of BS EN 12620. Tlimited to strength classes C40/50 and to less aggr

    carbonation and the lowest levels of freezethaw and

    contains a full specification for RCA but not for RA as t

    robust general specification for every possible type of

    A particular feature of both RA and RCA is a lower sp

    aggregates. Oven-dried values may typically be 2.02

    typically in the range 2.32.8 for primary aggregates.

    higher absorption and less stiffness. Properties of con

    factors should therefore be considered when RA or RC

    modulus, creep and shrinkage, which are all influence

    deflections and creep deformations are of importance

    be considered carefully. It should also be appreciated t

    combination with primary aggregate and any effects

    to the relative proportions of the materials used.

    16.1 Requirements of

    BS EN 206-1 and BS 8500

    16.2 Properties influenced

    by the use of Recycled

    Aggregate and Recycled

    Concrete Aggregate

  • 8/2/2019 Concrete EU Eurocode 2 p59

    53/59

    References

    1. GILBERT, R. I. Design properties of materials changes pr

    2. BEEBY, A. Why do we need ductility in reinforced concr

    No. 5, pp. 2729.

    3. HARRISON, T. A. Formwork striking times criteria, pred

    CIRIA, 1995, Report 136, ISBN 0 86017 431 X.

    4. THE CONCRETE SOCIETY. In situ strength of concrete a

    core strength and the standard cube strength. Camberley

    Society, 2004, Project Report No. 3.

    5. HARRISON, T. A. Early-age thermal crack control in concr

    edition, ISBN 0 86017 329.

    6. BAMFORTH, P. B. Early-age thermal crack control in con

    revision to CIRIA Report 91, ISBN 0 86017 660 6.

    7. RYLE, R. The influence of test machines on cylinder splittiNo. 77.

    8. SHERIFF, T. The control of ready-mixed concrete using the

    DoE requirements. Institute of Concrete Technology, 197

    9. DHIR, R. K., TITTLE, P. A. J. and McCARTHY, M. J. Role of

    durability of concrete. University of Dundee, 2001, cont

    (CC 1629)).

    10. DAVIDSON, R. J. Report on an investigation into the varia

    Taylor Woodrow, 1987, Report No. 014H/87/3241.11. NEVILLE, A. M. Properties of Concrete. Longman, 1995.

    12. BAMFORTH, P. B., PRICE, W. F. and FLEISCHER, C. C. Th

    nuclear power station structures. Nuclear Energy, 1997,

    13. IDE, J. M. Comparison of statically and dynamically dete

    Proceedings of the National Academy of Sciences, 1936,

    14. TASDEMIR, M. A., LYDON, F. D. and BARR, B. I. G. The te

    of Concrete Research, 1996, Vol. 48, No. 176, Sept., pp.

    15. SWADDIWUDHIPONG, S., LU, H. R. and LEE, T. H. Prob

    concrete. 3rd International Conference on Concrete under

    Canada, 1820 June 2001 (eds N. Banthai, K. Satai and

    pp. 16021609.

    16. GILBERT, R. I. Time effects in concrete structures. Amste

  • 8/2/2019 Concrete EU Eurocode 2 p59

    54/59

    BS EN 1990, Eurocode: Basis of structural design (includi

    BS EN 1992, Eurocode 2: Design of concrete structures

    Part 1-1 General rules and rules for buildings (includ

    Part 1-2 General rules Structural fire design (inclu

    Part 3 Liquid retaining and containment structures

    BS EN 196-8, Methods of testing cement. Heat of hydrat

    BS EN 196-9, Methods of testing cement. Heat of hydrat

    BS EN 197-1, Composition, specifications and conformity

    BS EN 206-1, Concrete specification, performance, pro

    BS EN 1367-4, Tests for thermal and weathering properti

    shrinkage. BSI, 1998.

    BS EN 1770, Products and systems for the protection and

    BS EN 10080 Steel for the reinforcement of concrete: w

    European and other

    national standards

    23. CATHER, R. Concrete and fire exposure. InAdvanced co(eds J. Newman and Ba. S. Choo). 2003, ISBN 0 7506 5

    24. WADSO, J.An experimental comparison between isother

    and solution calorimetry for the study of cement hydration

    No.1534-01, Technical Report 533, Tekniikantie 12.

    25. DHIR, R. K., PAINE, K. A. and ZHENG, L. Design data for

    University of Dundee, 2006, Research Contract No. CTU

    26. BUILDING RESEARCH ESTABLISHMENT. Concrete in agg

    Special Digest 1.

    27. BUILDING RESEARCH ESTABLISHMENT.Alkalisilica rea

    1999, Digest 330.

    28. THE CONCRETE SOCIETY.Alkalisilica reaction; minimis

    Camberley, The Concrete Society, 1999, Technical Repo

    29. BAMFORTH, P. B. The derivation of input data for mode

    exposure trials. Magazine of Concrete Research, 1999, V

    30. WALEED, N. and CANISIUS, T. D. G. Investigation of the

    engineering properties of concrete. 2006, WRAP Aggreg

    31. ALDER, A. J. J. and ROBERTS, C. P. The use of recycled co

    Crowthorne, Transport Research Laboratory, 2005, TRL

  • 8/2/2019 Concrete EU Eurocode 2 p59

    55/59

    BS EN 13791,Assessment of insitu compressive strength icomponents. BSI, 2007.

    BS 1881-209, Testing concrete: recommendations for the

    elasticity. BSI, 1990.

    BS 4449, Steel for reinforcement of concrete: weldable r

    BS 8007, Code of practice for design of structures contain

    BS 8110, Structural use of concrete. Code of practice for

    BS 8500-1, Concrete complementary British Standard and guidance for the specifier. BSI, 2006.

    BS 8500-2, Concrete complementary British Standard

    constituent materials and concrete. BSI, 2006.

    DD ENV 13670-1, Execution of concrete structures. Com

    PD 6687, Background paper to the UK National Annexes

    AASHTO, TP 60-00 Standard test method for coefficien

    concrete. AASHTO, 2004.

    AS 1012.13-1995, Methods of testing concrete determin

    samples prepared in the field or in the laboratory. Standa

    ASTM C 157/C, Standard test method for length change

    concrete. ASTM, 2006.

    ASTM C 512, Standard test method for creep of concrete

    ISO/WD 1920-5, Testing concrete Part X: Determinatiosamples prepared in the field or in the laboratory(draft).

    ISO/WD 1920-9, Testing concrete Part Y: Determinatio

    compression (draft).

    International standards

  • 8/2/2019 Concrete EU Eurocode 2 p59

    56/59

    Appendix ATable A1

    Extract from BS EN 1992-1-1 - Table 3.1.

    25/30

    C30/37

    C35/45

    C40/50

    C45/55C50/60

    C55/67

    C60/75

    C70

    /85

    C80/95

    C90/105

    Analyticalrelation

    5

    30

    35

    40

    45

    50

    55

    60

    70

    80

    90

    0

    37

    45

    50

    55

    60

    67

    75

    85

    95

    105

    3

    38

    43

    48

    53

    58

    63

    68

    78

    88

    98

    fcm=

    fck

    +8

    (MPa

    )

    6

    2.9

    3.2

    3.5

    3.8

    4.1

    4.2

    4.4

    4.6

    4.8

    5.0

    fctm=

    0.3

    0xf

    ck

    (2/3) C50

    /60

    fctm=

    2.1

    2In

    [1+

    (fcm

    /10

    )]

    >C5

    0/60

    8

    2.0

    2.2

    2.5

    2.7

    2.9

    3.0

    3.1

    3.2

    3.4

    3.5

    fctk,0.

    05

    =0

    .7xfc

    tm

    5 %

    f i

    l

  • 8/2/2019 Concrete EU Eurocode 2 p59

    57/59

    Table A2Nomenclature and composition for cements

    and combination typesa.

    Broad designationb Composition

    CEM I Portland cement

    SRPC Sulfate-resisting Portland cement

    IIA Portland cement with 620% fly ashground granulated blastfurnace slaglimestone, or 610% silica fumec

    IIB-S Portland cement with 2135% groungranulated blastfurnace slag

    IIB-V Portland cement with 2535% fly as

    IIB+SR Portland cement with 2535% fly as

    IIIAd, e Portland cement with 3665%ground granulated blastfurnace slag

    IIA+SRe Portland cement with 3665%ground granulated blastfurnace slag

    with additional requirements thatenhance sulfate resistance

    IIIBe, g Portland cement with 6680%ground granulated blastfurnace slag

    IIIB+SRe Portland cement with 6680%ground granulated blastfurnace slagwith additional requirements thatenhance sulfate resistance

    IVB-V Portland cement with 3655% fly as

    Keya There are a number of cements and combinations not listed in this table that may

    Special Digest 12 for the sulfate-resisting characteristics of other cements and com

    b The use of these broad designations is sufficient for most applications. Where a m

    required, select from the notations given in BS 85002: 2006, Table 1.

    c When IIA or IIAD is specified, CEM I and silica fume may be combined in the con

    2000, Cl. 5.2.5.2.3.

    d Where IIIA is specified, IIIA+SR may be used.

    e Inclusive of low early strength option (see BS EN 1974 and the L classes in BS 85

    f +SR indicates additional restrictions related to sulfate resistance. See BS 85002

    g Where IIIB is specified, IIIB+SR may be used.

  • 8/2/2019 Concrete EU Eurocode 2 p59

    58/59

    Table A3Standard methods for measurement of

    physical properties.

    Property Standard tests Co

    Compressive strength,cylinders and cubes

    BS EN 12390-3

    Tensile splitting strength BS EN 12390-6

    Flexural strength BS EN 12390-5

    Direct tensile strength No standards

    Bond strength BS EN 10080 Ben

    Static modulus of electricity

    (secant modulus)

    Standard BS EN test

    under development

    Tensile strain capacity No standards Maydivid

    Dynamic modulus of elasticity( initial tangent modulus)

    BS EN 12504-4

    BS 1881-209

    Thisof ufor tmodthatNatmea

    ( in

    Creep No standard EN test.ASTM C 512-02ISO/WD 1920-Y

    MeaMea

    Autogenous shrinkage No standards

    Drying shrinkage of concrete No standard EN test.ASTM C 157/CISO/WD 1920-X

    Drying shrinkage of aggregate BS EN 1367-4 Tho

    meadryi

    Autogenous shrinkage No standards

    Coefficient of thermalexpansion

    No standards

    Thermal conductivity BS EN 12667

    Specific heat No standards

    Adiabatic heat BS EN 196-9

    ~

    CI/Sfb

    UDC624.012.4.001.63

  • 8/2/2019 Concrete EU Eurocode 2 p59

    59/59

    Properties of Concrete for use in Eurocode 2

    This publication is aimed at providing both civil and structural

    design engineers with a greater knowledge of concrete

    behaviour. This will enable the optimal use of the material

    aspects of concrete to be utilised in design. Guidance relates

    to the use of concrete properties for design to Eurocode 2

    and the corresponding UK National Annex.

    In the design of concrete structures, engineers have the flexibility to

    specify particular concrete type(s) to meet the specific performance

    requirements for the project. For instance where calculated

    deflections exceed serviceability limits, the designer can achieve

    lower deflections by increasing the class of concrete and the

    associated modulus of elasticity, rather than by resizing members.

    This publication will assist in designing concrete structures taylor-

    made for particular applications.

    CCIP-029

    Published January 2008

    ISBN 978-1-904482-39-0

    Price Group P

    The Concrete Centre

    Riverside House, 4 Meadows Business Park,

    Station Approach, Blackwater, Camberley, Surrey, GU17 9AB

    Tel: +44 (0)1276 606 800

    www.concretecentre.com

    Phil Bamforth spent his early career managing construction

    consultancy and research for Taywood Engineering, and has a wide

    experience in concrete technology and construction both in the

    UK and abroad. Now in private consultancy, supporting design and

    construction activities in concrete, he has written numerous papers

    related to concrete material performance.

    Derek Chisholm is project manager for technical publications at

    The Concrete Centre and has a background in concrete materials

    technology.

    John Gibbs is technical advisor for the European Ready-Mixed

    Concrete Organisation (ERMCO). He has spent most of his career in

    the ready-mixed, quarrying and construction industries.

    Tom Harrison is technical director of the British-Ready Mix

    Concrete Association and in that capacity chaired the committee

    that produced Guidance to the Engineering Properties of Concrete

    from which this publication has developed.