version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 109 Intended use: The iSWAY-FC ® series compact pressurization units are comprehensive technical solutions designated to overpressure protection of both vertical and horizontal escape routes in the various buildings in case of fire. iSWAY-FC ® COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND HEAT CONTROL SYSTEMS 6.0.1 Intended use and types of the units The iSWAY-FC ® series compact pressurization units (pressure differential kits in accordance with EN 12101-6) are comprehensive technical solutions designated to overpressure protection of both vertical and horizontal escape routes in the various buildings in case of fire. All iSWAY-FC ® series units are equipped with predictive algorithm regulators which provide automatic adjustment of the operating parameters to the dynamic changes of the ambient e.g. wind speed and direction, air temperature and internal parameters e.g. different evacuation scenarios. Capacity of the air supply axial flow fan is continuously adjusted by means of the Danfoss frequency inverter with the FIRE MODE function which shall be applied in smoke and heat control systems. Correspondent iSWAY-FC ® units can be equipped with dedicated automatics enabling to protect of certain spaces depending on the local requirements in the building. Due to the applied control system and wide range of accessories iSWAY-FC ® series units can be used to protect number of spaces with different cubature e.g. staircases, lift-shafts etc. Moreover due to the compact design and structure iSWAY-FC ® series compact pressurization units can be assembled almost anywhere inside the building e.g. technical floors, roof level or ground level. Technically iSWAY-FC ® series units are comprehensive technical solutions for overpressure protection against smokiness of escape routes in buildings in case of fire. Thanks to a compact design and a wide range of versions this units can be installed almost anywhere in the building, whereas varying performance of offered fans provides the required level of pressure gradient and normative velocity of air outflow from the protected spaces. Units from the iSWAY-FC ® series are designed to produce the set value of overpressure within the space of staircase, shaft of rescue elevator or in a system of separate elevator shafts (each with its own air supply point in reference to the fire floor. It is also possible the use iSWAY-FC ® units to control the pressure in the air supply duct. Figure 1. Actual air leakage rate Protected space pressure measurement point Reference pressure measurement point Protected space e.g. stairwell, lobby, lift shaft, corridor Exemplary illustration of connection of iSWAY-FC ® unit to the protected space. Functionality and reliability in aerodynamic, electrical and electronic aspects in accordance with: Technical Approval ITB AT-15-9020/2015, confirmed by Certificate of Conformity ITB-2189/W and the national Declaration of Conformity issued by SMAY Sp. z o. o. No. 282/2013 The manufacturer reserves the right to change, amend or update this data sheet at any time without notice.

Upload: others

Post on 13-Mar-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems109

Intended use:The iSWAY-FC® series compact pressurization units are comprehensive technical solutions designated to overpressure protection of both vertical and horizontal escape routes in the various buildings in case of fire.

iSWAY-FC®COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND HEAT CONTROL SYSTEMS

6.0.1

Intended use and types of the unitsThe iSWAY-FC® series compact pressurization units (pressure differential kits in accordance with EN 12101-6) are comprehensive technical solutions designated to overpressure protection of both vertical and horizontal escape routes in the various buildings in case of fire. All iSWAY-FC® series units are equipped with predictive algorithm regulators which provide automatic adjustment of the operating parameters to the dynamic changes of the ambient e.g. wind speed and direction, air temperature and internal parameters e.g. different evacuation scenarios. Capacity of the air supply axial flow fan is continuously adjusted by means of the Danfoss frequency inverter with the FIRE MODE function which shall be applied in smoke and heat control systems.

Correspondent iSWAY-FC® units can be equipped with dedicated automatics enabling to protect of certain spaces depending on the local requirements in the building.

Due to the applied control system and wide range of accessories iSWAY-FC® series units can be used to protect number of

spaces with different cubature e.g. staircases, lift-shafts etc. Moreover due to the compact design and structure iSWAY-FC® series compact pressurization units can be assembled almost anywhere inside the building e.g. technical floors, roof level or ground level.

Technically iSWAY-FC® series units are comprehensive technical solutions for overpressure protection against smokiness of escape routes in buildings in case of fire. Thanks to a compact design and a wide range of versions this units can be installed almost anywhere in the building, whereas varying performance of offered fans provides the required level of pressure gradient and normative velocity of air outflow from the protected spaces.

Units from the iSWAY-FC® series are designed to produce the set value of overpressure within the space of staircase, shaft of rescue elevator or in a system of separate elevator shafts (each with its own air supply point in reference to the fire floor. It is also possible the use iSWAY-FC® units to control the pressure in the air supply duct.

Figure 1.

Actual air leakage rate

Protected space pressure measurement point

Reference pressure measurement point

Protected space e.g. stairwell, lobby, lift shaft, corridor

Exemplary illustration of connection of iSWAY-FC® unit to the protected space.

Functionality and reliability in aerodynamic, electrical and electronic aspects in accordance with: Technical Approval ITB AT-15-9020/2015, confirmed by Certificate of Conformity ITB-2189/W and the national Declaration of Conformity issued by SMAY Sp. z o. o. No. 282/2013

The manufacturer reserves the right to change, amend or update this data sheet at any time without notice.

Page 2: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 110

SMOKE AND FIRE ZONE

Figure 2.

Actual air leakage rate

Protected space pressure measurement point

Reference pressure measurement point

Remote differential pressure sensor P-MACF

Protected space e.g. stairwell, lobby, lift shaft, corridor

Exemplary connection of iSWAY-FC®-D pressurization unit with remote differential pressure sensor and pressurized space.

Figure 3.

Actual air leakage rate

Protected space pressure measurement point

Reference pressure measurement point

Available static pressure measurement point

Motorized volume control damper SRC

MAC-D Min

Junction box PZ

Protected space e.g. stairwell, lobby, lift shaft, corridor

Exemplary connection of iSWAY-FC® pressurization unit with motorized volume control damper SRC and regulator MAC-D-MIN and pressurized space.

Note:Protected space is a space which is protected by means of an overpressure.

Page 3: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems111

Figure 4.

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on the roof Twin-Air-Intake module shall be applied (alternative air intake)

Reference pressure measurement point

∆p - differential pressure measurement tubes

Pressure measurement point in the stairwell

iSWAY-FC

Corridor Stairwell

e.g. 50 Pa

Cables interconnecting TSS with iSWAY-FC®

Fire brigades access level

TSS

Multiple injection into the stairwell.

Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance.Maximum length of the pressure differential measurement tubes shall not exceed 12 m.

Measurement taken with internal differential pressure sensor installed inside the unit’s casing through the pressure differential measurement tubes. In case of communication loss with the pressure sensor regulator switches automatically into safe emergency control mode (failure mode).

Page 4: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 112

Figure 5.

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on the roof Twin-Air-Intake module shall be applied (alternative air intake)

Reference pressure measurement point

∆p - differential pressure measurement tubes

Pressure measurement point in the stairwell

iSWAY-FC

Corridor Stairwell

e.g. 50 Pa

Cables interconnecting TSS with iSWAY-FC®

Fire brigades access level

TSS

Reference pressure measurement point

Pressure measurement point inside the air supply duct

P-MACF

Multiple injection into the stairwell – unit with remote differential pressure sensor.

Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance.Maximum length of the pressure differential measurement tubes shall not exceed 12 m.P-MACF remote differential pressure sensor connected with iSWAY-FC® unit with Local FireBus® communication loop.

In case when the unit is not located close to the protected space to avoid pressure difference measurement errors and delays remote differential pressure sensor P-MACF is installed directly within the protected space and connected to iSWAY-FC® unit with Local FireBus® communication loop (more details on the protocol later in this data sheet).

In case of communication loss with the pressure sensor regulator switches automatically into safe emergency control mode (failure mode) regulation based on pressure measurement inside the air supply duct.

Page 5: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems113

Figure 6.

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on the roof Twin-Air-Intake module shall be applied (alternative air intake)

Reference pressure measurement point

∆p - differential pressure measurement tubes

Pressure measurement point in the stairwell

iSWAY-FC

Corridor Stairwell

e.g.50 Pa

Cables interconnecting TSS with iSWAY-FC®

Fire brigades access level

TSS

Nawiew jednopunktowy (skoncentrowany) do przestrzeni klatki schodowej.

Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance.Maximum length of the pressure differential measurement tubes shall not exceed 12 m.P-MACF remote differential pressure sensor connected with iSWAY-FC® unit with Local FireBus® communication loop.

Single injection (concentrated) air supply dśs not require vertical air supply shaft and thus enable to save space which can be used for lobbies pressurization or else increase available usable area in the building.

In case of communication loss with the differential pressure sensor regulator switches automatically into safe emergency control mode (failure mode).

iSWAY-FC®-D unit with differential pressure sensor P-MACF and regulator MAC-FC for lobbies pressurization with constant capacity air supply rate and compensative air supply for mechanically smoke extracted corridors and separate units operating stairwells and lift shafts.

Page 6: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 114

Figure 7.

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on the roof Twin-Air-Intake module shall be applied (alternative air intake)

Reference pressure measurement point

∆p - differential pressure measurement tubes

Pressure measurement point in the stairwell

iSWAY-FC

Corridor Stairwell

50 Pa

P-MACF

e.g. 2 m/s

Punkt pomiaru ciśnieniaotoczenia (odniesienia)

iSWAY-FC-DPunkt pomiaru ciśnienia w kanale

Pressure measurement point in the stairwell

KWP-z

Fire-fi ghting lobby (vestibule)

Free

air

rele

ase

to th

e ou

tsid

e fr

om th

e fi r

e st

orey

KWP-o

P-MACF

e.g.45 Pa

avai

labl

e st

atic

pre

ssur

e in

side

air

sup

ply

duct

P-MACF

KWP-z

P-MACF

KWP-z

P-MACF

KWP-z

Pressure measurement point in the fi re-fi ghting lobby (vestibule)

Corridor Stairwell

P-MACF

KWP-z

Fire-fi ghting lobby (vestibule)

KWP-o

P-MACF

P-MACF

KWP-z

P-MACF

KWP-z

P-MACF

KWP-z

Reference pressure measurement point

iSWAY-FCiSWAY-FC-D

Pressure measurement point in the air suppply duct

avai

labl

e st

atic

pre

ssur

e in

side

air

sup

ply

duct

Free

air

rele

ase

to th

e ou

tsid

e fr

om th

e fi r

e st

orey

Simultaneous pressurization of the stairwell and fire-fighting lobbies (vestibules) with air compensative air transfer openings (from the lobbies to the corridors or other smoke extracted spaces).

Figure 8.

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on the roof Twin-Air-Intake module shall be applied (alternative air intake)

iSWAY-FC

Corridor Stairwell

50 Pa

MAC-D MIN

2 m/sReference pressure measurement point

iSWAY-FC-D

KWP-z

Fire-fi ghting lobby (vestibule)

Free

air

rele

ase

to th

e ou

tsid

e fr

om th

e fi r

e st

orey

KWP-o

45 Pa

avai

labl

e st

atic

pre

ssur

e in

side

air

sup

ply

duct

KWP-z

KWP-z

KWP-z

iSWAY-FCiSWAY-FC-D

Free

air

rele

ase

to th

e ou

tsid

e fr

om th

e fi r

e st

orey

24 V guaranteed

MAC-D MIN

24 V guaranteedPressure measurement point in the lobby

MAC-D MIN

24 V guaranteed

MAC-D MIN

24 V guaranteed

MAC-D MIN

24 V guaranteed

KWP-o – fi re damper (open), KWP-z – fi re damper (closed)

Corridor Stairwell

MAC-D MIN

Reference pressure measurement point

KWP-z

Fire-fi ghting lobby (vestibule)

KWP-o

avai

labl

e st

atic

pre

ssur

e in

side

air

sup

ply

duct

KWP-z

KWP-z

KWP-z

24 V guaranteed

MAC-D MIN

24 V guaranteed

Pressure measurement point in the lobby

MAC-D MIN

24 V guaranteed

MAC-D MIN

24 V guaranteed

MAC-D MIN

24 V guaranteed

Simultaneous pressurization of the stairwell and fire-fighting lobbies (vestibules) with electronic adjustable air transfers (from the lobbies to the corridors or other smoke extracted spaces).

Page 7: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems115

Location in the building and design options

Rysunek 9.

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on the roof Twin-Air-Intake module shall be applied (alternative air intake)

Corridor Stairwell

50 Pa

2 m/s

iSWAY-FC-D

KWP-z

Fire-fi ghting lobby (vestibule)

Free

air

rele

ase

to th

e ou

tsid

e fr

om th

e fi r

e st

orey

KWP-o

45 Pa

avai

labl

e st

atic

pre

ssur

e in

side

air

sup

ply

duct

Free

air

rele

ase

to th

e ou

tsid

e fr

om th

e fi r

e st

orey

KWP-o – fi re damper (open), KWP-z – fi re damper (closed)

iSWAY-FC-R

P-MACF

P-MACF

KWP-z

P-MACF

KWP-z

P-MACF

KWP-z

P-MACF

iSWAY-FC

iSWAY-FC-R

Inside air temperature measurement point

Outside air temperature measurement point

Outside air temperature measurement point

Corridor Stairwell

iSWAY-FC-D

KWP-z

Fire-fi ghting lobby (vestibule)

KWP-o

avai

labl

e st

atic

pre

ssur

e in

side

air

sup

ply

duct

iSWAY-FC-R

P-MACF

P-MACF

KWP-z

P-MACF

KWP-z

P-MACF

KWP-z

P-MACF

Inside air temperature measurement point

Outside air temperature measurement point

Inside air temperature measurement point

iSWAY-FC

iSWAY-FC-R

Outside air temperature measurement point

Zabezpieczenie przedsionków i klatki schodowej układem rewersyjnym z urządzeniami wspomagającymi.

1. Complex pressurization systems shall be fitted with Operating Conditions Monitoring Device (MSPU) with Control Board (TS) to enable monitoring, visualization of the system and manual key-protected override switches. TS and MSPU are usually installed in the BMS room.

2. Maximum length of the pressure differential measurement tubes shall not exceed 12 m.3. Application of single injection system shall be every time validated taking into consideration building architecture and

key design objectives e.g. allowable pressure differences.4. iSWAY-FC®D type pressurization unit can be interconnected with max. 32 P-MACF remote differential pressure

sensors using single FireBus® loop.5. Each remote P-MACF sensor has to have Fire Alarm Signal (FAS) provided. Depending on the location of the fire

pressurization unit communicates with the sensor closest to the fire floor and neglect other readings in order to enable possibly fast operation.

6. For fire-fighting lobbies (vestibules) equipped with electronic adjustable air transfers remote sensors P-MACF are replaced with MAC-D-MIN regulators controlling volume control dampers located in the lobby and corridor. Proper functioning of such system requires to receive Fire Alarm Signal (FAS) to trigger the system and enable measurement of pressure difference between the lobby and reference (e.g. corridor).

7. iSWAY-FC® type units intended for pressurization of the lobbies with electronic adjustable air transfers or more than one lift shaft pressurized by a single unit (individual pressure difference regulation) are by default fitted with factory automatics type “D” and marked as iSWAY-FC®-D.

8. iSWAY-FC® type units intendetd for stairwell pressurization where reversible flow is required are by default fitted with factory automatics type “R” and marked as iSWAY-FC®-R.

Use of P-MACF sensors and FireBus® loop communication protocol enable to save space and limit investment and operating costs by reducing total length of the data transmission cables and capacities of the air supply fans – air supply rates are precisely controlled and automatically adjusted to current needs. Application of electronic adjustable air transfers enables to save space and improve aesthetics by reducing required size of air transfer openings (compensative air supply for smoke exhaust).

Failsafe mode In case of communication loss with the pressure sensor regulator switches automatically into safe emergency control mode (failure mode) regulation based on pressure measurement inside the air supply duct. Desired pressure inside the air supply duct shall be determined experimentally using the results of on-site measurements.

Page 8: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 116

Exemplary locations of the unitsCompact structure allows for installing units inside e.g. machinery rooms and outside the building e.g. roof level, ground level etc. whereas wide range of applied fans enables to achieve desired pressure differences and directed airflow through the open doors.

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on the roof Twin-Air-Intake module shall be applied (alternative air intake)

iSWAY-FC

Cables interconnecting TSS with iSWAY-FC®

Fire brigades access level

TSS

Flexible differentia pressure measurement tube e.g. PVC tube protected with electroinstallation tube

Stairwell

3x400 V guaranteed power supplygeneral Fire Alarm Signal (FAS)

Static pressure measurement point inside the protected space

Figure 10. Example of iSWAY-FC® unit top fed stairwell pressurization system with pressurization unit located on the roof.

1. Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance.2. Complex pressurization systems shall be fitted with Operating Conditions Monitoring Device (MSPU) with Control

Board (TS) to enable monitoring, visualization of the system and manual key-protected override switches. TS and MSPU are usually installed in the BMS room.

3. Maximum length of the pressure differential measurement tubes shall not exceed 12 m.4. Application of single injection system shall be every time validated taking into consideration building architecture and

key design objectives e.g. allowable pressure differences.t

Page 9: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems117

Figure 11.

iSWAY-FC

Cables interconnecting TSS with iSWAY-FC®

Fire brigades access level

TSS

Flexible differentia pressure measurement tube e.g. PVC tube protected with electroinstallation tube

Stairwell

Static pressure measurement point inside the protected space

Reference pressure measurement point

KWP-o – fi re damper (open) KWP-z – fi re damper (closed)

KWP-o

Example of iSWAY-FC® unit based bottom fed stairwell pressurization system (with pressurization unit located in the machinery room).

Installation of the unitsTo provide maximum flexibility for the designers all iSWAY-FC® type units are delivered as a self-supporting structures with fan installed on shock absorbers enabling to be installed in any position (horizontal, vertical) depending on the local requirements on the site. However to guarantee comfort of the installers and maintenance crews it is recommended to define expected assembly position of the unit (1 or 2) upon placing an order.

In case when defining final assembly position of the unit is unknown factory automatics will be installed as per default mounting position (1).

Figure 12.

2 2 2 2

1 1 1 1

4

4

3

3

5

5

- Airfl ow direction – air supply unit- - Airfl ow direction – air exhaust unit - Assembly position

Example of the assembly position.

After defining assembly position drain holes plugs o14 shall be removed from the bottom profiles of the unit’s casing. M8 Layout of M8 mounting holes has been set in such a manner to enable any mounting position of the unit (see Scheme 12.). In case of vertical assembly special supporting foot is required which is not available from the range of additional equipment offered by SMAY.

Page 10: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 118

Measurement, monitoring and visualization For proper functioning of the iSWAY-FC® type unit it is indispensable to enable appropriate air intake, and provide all electrical connections (guaranteed power supply, data transmission cables, fire alarm system inputs, connections between the unit and TSS or TS and MSPU). Moreover all pressure measurement tubes shall be unobstructed and properly connected (pressure difference between the protected space e.g. stairwell and reference e.g. corridor). If pressure regulation is carried out basing on the measurements taken inside the air supply duct it is indispensable to connect appropriate pressure measurement tubes and probes (duct pressure measurement probe shall be installed on the straight part of the air supply ductwork.

Installed components of the control system P-MACF, MAC-D-MIN, MAC-LINK, T-MACF shall be interconnected with the iSWAY-FC®-D(R) unit by means of Local FireBus® loop communication bus.

In case when total number of P-MACF sensors dśsn’t exceed 4 per unit power supply is provided through the FireBus®, otherwise external power supply 24VDC shall be provided.

For differential pressure sensors operating the lobbies it is indispensable to address every sensor providing Fire Alarm Signal (FAS) to every sensor. In case of fire pressurization iSWAY-FC® unit communicates with the sensor located in the lobby at the fire floor.

For buildings where total number of units dśsn’t exceed 6 (without lobbies) manual control and monitoring are provided with Control-Signal Board TSS in appropriate version TSS-1 ÷ TSS-6 depending on number of units.

For more complex pressurization systems where involving number of units it is recommended to apply Control Board (TS) together with Operating Conditions Monitoring Device (MSPU) located at the fire brigades access level possibly close to the entrance (e.g. BMS room).

Control-Signal Board (TSS)

Control - Signal Board (TSS) is intended to enable basic manual controls and monitoring of the proper functioning of the units. Board is fitted with pressure difference value displays, key-protected manual override switches and indicators. Override switches are used to enable to start the unit, reset the failure, smoke detector, Fire Alarm Signal (FAS) and, depending on system structure, to control Twin-Air-Intake modules. Indicators show information on fire alarm signal, major failure and detection of the smoke inside the air supply unit.

TSS dimensions:

1. TSS-1 – 205x340 x 188 mm.2. TSS-2 – 305x340 x 188 mm.3. TSS-3 – 305x340 x 188 mm.

Figure 13.

8

1

2

3

4

5

6

7

9

11

12

10

Panel Tablicy Sterująco-Sygnalizacyjnej TSS.

1. Seven segment display (three segments).2. General failure indicator (red).3. Two-position, key-protected switch (manual fan start).4. Smoke in the unit indicator (yellow).5. Two-position, key-protected switch (locking the smoke detector or switching Twin-Air-Intake module).6. Smoke detector lock or Twin-Air-Intake module switch.7. Membrane fan.8. EMC cable pass.9. Fire Alarm Signal indicator (yellow).10. board power supply indicator (green).11. Two-position, key-protected switch (resetting fire alarm).12. UNI cable pass.13. Wall bracket.

Boards TSS-1 ÷TSS-3 can be used as a power supplies 24VDC (power supplied from the iSWAY-FC® unit).

Operating Conditions Monitoring Device (MSPU)

This device is an additional component which is recommended for complex pressurization systems and enables to control data transmission lines and monitor status and condition of the key components of the SAFETY WAY® type pressurization system. MSPU device shall be installed together with the TS Control Board. MSPU device consists of the number of components enclosed in one steel casing painted in RAL3000. Key component of the MSPU is an industrial computer with touch screen fitted in the front panel enabling to activate different features of the monitoring system. MSPU device is used to display operating parameters of the key components with individual graphics developed (including number of units, layout of protected spaces and other components depending on the system’s structure). In general MSPU device enables to detect and locate any possible failure of the system and reduce time required for periodic inspections and maintenance of the pressurization system.

Photo 1. General view of the Operating Conditions Monitoring Device MSPU.

Dimensions of the MSPU: 500 x 650 x 250 mm.

Control board (TS)

Control Board (TS) is always installed in the building along with MSPU at the fire brigades access level. In the front panel of the board light indicators of board power supply, Fire Alarm Signal (FAS) and general failure are fitted. Board is also fitted with overall switch enabling manual activation of the units which starts all units simultaneously. Since each unit can be individually stopped from the TS board it is also possible to start selected units or group of units. For each unit board also enables to reset fire alarm signal resulting in deactivation of the unit. All units after being triggered with fire alarm signal work independently and require manual stop. This manual switch can be also used to deactivate the unit. For security reasons this switch is key-protected. For each unit board is fitted with additional switch to lock the smoke sensor providing control

Page 11: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems119

signal for the Twin-Air-Intake module. This switch has two different functions depending on if the unit is equipped with Twin-Air-Intake module. In such case once smoke is detected inside the unit air intake openings are automatically switched. Alternatively for units without Twin-Air-Intake module detection of smoke inside the unit results in automatic stop of the unit. Smoke detection signal can be neglected using this switch and the unit remains active. Information on smoke detection inside the unit is displayed on the MSPU device located near the board.

Figure 14. General view of the Control Board TS-12.

Table 1. Dimensions of the TS.

Name Dimensions DxHxS[mm]

TS-1; TS-6 300 x 340 x 188

TS-7; TS-16 600 x 522 x 269

TS-17; TS-32 600 x 722 x 269

TS-33; TS-36 800 x 922 x 321

Remote differential pressure sensor (P-MACF)

P-MACF is a digital pressure differential transducer fitted with one differential pressure sensor and connector providing power supply and data transmission over two Local FireBus® channels. Built in, internal microprocessor system performs linearity correction while taking into account, inter alia, operating temperature, and characteristics entered at the time of calibration. High accuracy and stability of measurement is ensured by the use of sophisticated calibration equipment and long-term aging process of the elements of the device. The converter is designed to measure air pressure with small degree of contamination.

Depending on desired function and measuring range two different variants of the sensors P-MAC and P-MACF can be distinguished:

• P-MAC +/-250 – measuring range: -250 ÷ 250 Pa – pressure difference between protected space and the reference – for iSWAY-FC®,

• P-MAC +/-600 – measuring range: -600 ÷ 600 Pa – pressure difference between protected space and the reference or inside the air supply duct – for iSWAY-FC®,

• P-MACF +/-250 – measuring range: -250 ÷ 250 Pa – pressure difference between protected space and the reference – for iSWAY-FC®-D(R),

• P-MACF +/-600 – measuring range: -600 ÷ 600 Pa – pressure difference between protected space and the reference or inside the air supply duct – for iSWAY-FC®-D(R).

Remote differential pressure sensors are used in pressure differential systems in below cases:

• In case when iSWAY-FC® type units and pressurized spaces

are apart and thus length of the pressure measurement tubes exceeds 12 m. Then P-MACF sensor is connected to iSWAY-FC®-D unit with Local FireBus® communication loop. In case of the communication loss iSWAY-FC®-D unit gśs to the fail-safe mode when pressure difference regulation is provided using internal P-MACF sensor of the unit or else fixed setting of the regulator.

Dimensions of the P-MACF: 180x122x90 mm.

Photo 2. General view of the differential pressure sensor P-MACF.

• In case pressurized lobbies when electronic adjustable air transfers are not applied each lobby is fitted with independent P-MACF sensor. All lobbies sensors are connected to an appropriate iSWAY-FC®-D pressurization unit with Local FireBus® communication loop. For each sensor power supply 24VDC, Fire Alarm Signal (FAS) input and pressure measurement tubes shall be provided. The maximum number of sensors within single Local FireBus® loop is 32 including one sensor installed inside the unit . In case of fire sensor located at the fire floor receives fire alarm signal which enables to use this particular device to control pressure difference between the lobby and the reference or inside the air supply duct.

W przypadku utraty komunikacji urządzenia iSWAY-FC® z czujnikiem P-MACF, iSWAY-FC® przechodzi w awaryjny tryb pracy, polegający na regulacji ciśnienia w szachcie napowietrzającym. Ciśnienie w szachcie regulowane jest na podstawie „nauczonych” wartości parametru w trakcie normalnej pracy urządzenia.

Digital pressure regulator (MAC-D-MIN)

In case when fire-fighting lobbies are equipped with electronic adjustable air transfers to provide compensative air supply for smoke extracted corridors MAC-D-MIN regulators shall be applied. Such regulators with integrated pressure sensor are intended to control position of motorized volume control dampers installed in the air supply and air transfer ducts. Likewise P-MACF sensors MAC-D-MIN regulators are fitted with pressure measurement tubes terminals to measure pressure difference between the protected fire-fighting lobby and corridor and are connected to iSWAY-FC®-D unit with Local FireBus® communication loop. For each regulator power supply 24VDC and Fire Alarm Signal (FAS) input shall be provided. The maximum number of regulators within single Local FireBus® loop is 31. In case of fire regulator located at the fire floor receives fire alarm signal which enables to use this particular device to control pressure difference between the lobby and the reference or inside the air supply duct.

Dimensions MAC-D-MIN - 180 x250 x 90 mm.

Page 12: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 120

Photo 3. Regulator MAC-D-MIN for motorized volume control dampers (for pressure differential systems).

Junction box (PZ)

Junction box is used to connect volume control damper’s actuators with the regulators MAC-D-MIN. Four different types of junction boxes can be distinguished – PZ1 ÷PZ4. Number in the designation of the box correspond to number of Belimo NMQ24A-SR connected. Each junction box is power supplied with 24VDC (power consumption depends on the total number of actuators connected).

Photo 4. Junction box PZ.

Temperature sensor (T-MACF)

For SAFETY WAY® pressurization system where reversible airflow within the stairwell is produced it’s direction is automatically set basing on measured air temperature inside the stairwell and outside. This measurements are taken with T-MACF remote temperature sensors located by default at the top and bottom of the stairwell and transmitting signals to the MAC-FCR regulator installed in the iSWAY-FC(R)® unit through the Local FireBus® communication loop. E

Photo 5. Temperature sensor T-MACF (for pressure differential systems).

I/O adapter (MAC-LINK)

I/O adapters type MAC-LINK are intended to enable extend basic functions of the pressurization systems. This adapters use existing and available architecture of the FireBus® communication loop. MAC-LINK adapters are continuously monitored and thus any failure is immediately detected. Depending on actual needs adapters can be fitted with desired number of inputs and outputs.

Family of the MAC-LINK adapters can be divided into three basic groups listed below:

• MAC-LINK adapter with maximum 4 inputs and 4 outputs, • MAC-LINK-I adapter with 8 inputs, • MAC-LINK-O adapter with 8 outputs.

Maximum number of MAC-LINK adapters installed in single Local FireBus® loop is 8.

Photo 6. MAC-LINK digital I/O adapter.

ConstructionCasing

Body of the unit is made as of aluminum profiles with steel sheet profiles insulated with polyisocyanurate (PIR) foam. To enable access for servicing and maintenance side panels are removable.

Fan – Frequency Inverter

Fan powered by a frequency inverter supplies air into the protected space. In order to enable sharp changes of air supply rate all fans are fitted with breaking resistors taking energy out of the system while decreasing fan’s capacity.

Shut-off damper

In order to separate protected space from the outside (cold, dust and other pollutants) during normal use of the building all iSWAY-FC® type units are fitted with thermally insulated, motorized dampers installed at the air intake side. Shut-off damper’s actuator is equipped with the return spring to increase overall system reliability. In case of power failure (e.g. caused by cable damage), the shut-off damper switches to the fully open position assumed to be safe.

Duct smoke detector

All iSWAY-FC® type units by default are fitted with duct smoke detectors installed inside the unit’s casing. Depending on the programmed action upon smoke detection unit can be automatically switched off or else smoke detection alarm can be indicated.

Pressure measurement tubes connection terminals

Pressure measurement tubes terminals are in the boxes installed directly on the unit’s casing and marked as (+) for pressure in the protected space and (-) for the reference.

Page 13: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems121

Regulator MAC-FC(R)

MAC-FC(R) regulator is microprocessor electronic device intended for precise control of the pressure difference in accordance with the requirements listed in EN 12101-6 standard. It ensures full compliance with the requirements of the paragraph 5.4.2.5. “Variable supply fans or dampers controlled by pressure sensors shall not be used unless the system can achieve over 90 % of the new air supply requirements within 3 s of a door being opened or closed.”

MAC-FC(R) regulator adjusts automatically capacity of the fan by means of the frequency inverter depending on an actual value of pressure difference. Setting is automatically set depending on the status of its outputs and displayed interconnected device.

Main switch

The main switch is used to disconnect power supply of the unit for maintenance or in case of an unpredicted emergency.

Power Supply - Control Cabinet (SzA-FCZ)

SzA-FCZ cabinet is a component that power supplies iSWAY-FC® unit’s components and controls the adjustable volume control dampers using the information from MAC-FC(R) regulator. On the cabinet’s casing „Power supply control 3x400VAC and 24VDC” information is displayed whereas inside the cabinet 24VDC power supply equipment is installed. Additionally all power supply outputs for system’s components are protected.

Differential pressure sensor P-MAC or P-MACF

P-MAC and P-MACF are digital pressure differential transducers fitted with one differential pressure sensor and connector providing power supply and data transmission over Local FireBus® channels. Built in, internal microprocessor system performs linearity correction while taking into account, inter alia, operating temperature, and characteristics entered at the time of calibration. High accuracy and stability of measurement is ensured by the use of sophisticated calibration equipment and long-term aging process of the elements of the device. The converter is designed to measure air pressure with small degree of contamination.

Two different variants of the sensors P-MAC and P-MACF were described in paragraph: Measurement, monitoring and visualization.

Anti-Frost System

If required iSWAY-FC® type units can be fitted with an infrared heater in order to prevent shut-off damper from freezing (cold outside condition). In this case all seals of the in the shut-off damper are made from special material which remains flexible at low temperatures. Infrared heater is activated depending on the air temperature inside the unit by means of the thermostat. In order to increase heat absorption and direct heat transfer internal surfaces of the unit operate as screen and damper is painted in black.

Figure 15.

8 1 19 234 56 714

91516171819

11

12

13

20

10

Structure and key components of the iSWAY-FC® Unit.

1. Casing (steel sheet insulated with PIR foam).2. Infrared heater AF (option).3. Airflow measurement probe.4. Fan.5. Breaking resistor.6. Shut-off damper (air intake).7. Maintenance panel (servicing).8. Smoke detector.9. Frequency inverter.10. Control cabinet.11. Reference pressure measurement terminal (-).12. Protected space pressure measurement terminal (+).13. Main switch.14. Shut-off damper’s actuator.15. Cable tray.16. Thermostat (option).17. Differential pressure sensor.18. Regulator.19. Ventilation grille.20. Terminals of control cables and FireBus® communication loop.

Principle of operationControl objective is precise control of pressure difference between the protected space e.g. stairwell, lobby, lift shaft and the reference (overpressure within protected space). The inverter supplied from the power network sends a control signal to the fan motor alternating voltage with frequency inverter in the range 0 to 50 Hz. This enables precise control of the motor rotational speed i.e. fan capacity. The inverter receives a control signal from the regulator, which corresponds to the frequency of 0 to 50 Hz. Control strategy is based on precise regulation of actual pressure difference measured continuously with P-MAC(F) sensor e.g. 50 Pa. Control objective is in general reached with automatically adjusted capacity of the air supply fan taking into account actual leakage of the protected space (including door open/closed). It is assumed that overpressure of 50 Pa is considered as sufficient to hold back smoke and thus keep escape routes smoke free in case of fire. In case when total leakage of the protected space is exceeds assumed value e.g. more doors open simultaneously pressure drop within the protected space may occur.

The most innovative feature of the MAC-FC(R) regulator is application of neural network based predictive algorithm which eliminates fixed control system settings popular for instance for PID controllers. Control system can adapt to changes in the control object and learn. This ensures higher reliability and flexibility of the control system and adaptation to unforeseen scenarios e.g. broken window, blocked escape doors etc.

Tests carried out for iSWAY-FC® unit demonstrated that use of MAC-FC(R) regulator is enables to generate and control the nominal value of pressure difference and automatically adapt to changes introduced according to test procedure (range of fan capacity min / max, and the range of leakage values min / max).

Page 14: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 122

The iSWAY-FC® type unit was tested at I.F.I. Institute for Industrial Aerodynamics in Aachen, Germany in accordance with the current test procedure constituting part of the revised European standard revEN 12101-6.

Tests were carried out for the biggest unit considered to be the “worst case scenario” and thus representative for the whole family of kits fitted with 15 kW fan and max. capacity 50 500 m3/h and for the lowest air leakage rate of 200 m3/h. All tests results were positive and have proven that tested kit meets all the requirements in terms of response time, precise control, reliability, durability and immunity to oscillations.

All laboratory tests of the representative unit were carried out in full control range (up to 50 Hz) and all settings of the control system remained the same through all the tests in order to validate and confirm self-adaptation features.

Reliability of the device – test

In order to guarantee the highest available safety level automatic self-test function was introduced. By default every 24-hours shut-off damper and fan are activated (damper is opened and fan is started at the very low capacity) by MAC-FC regulator. During this test it is checked whether shut-off damper reaches fully open position and fan-inverter set functions properly. Results of such test are stored in the regulator’s memory. In case any abnormality is detected general failure signal is transmitted immediately.

Rysunek 16. Official summary of the performance parameters of tested iSWAY-FC® unit.

Operation modes

Control system is designed in a manner to produce and control pressure difference or else airflow as described below:

Door closed conditions: set value of pressure difference between the protected space and the reference is produced e.g. 50 Pa +/- 20% (design pressure difference and tolerance may vary depending on system architecture and design objectives to be met).

Door open conditions: set value of directed airflow through the open door between protected and unprotected spaces is produced e.g. min. 1.0 m/s (means of escape) or 2.0 m/s (means of fire-fighting).

Please note: to achieve airflow criterion (door open conditions) proper air release from the fire storey shall be provided.

In most cases opening the door results in sharp pressure drop whereas closing the door will result in significant pressure jump. Those differential pressures changes are more visible in small and airtight spaces e.g. lobbies. Control system of the pressurization unit shall be capable to stabilize pressure difference within 3 seconds after opening or closing the door to enable safe evacuation and support fire-fighting.

Please note: air leakage of the protected space may change rapidly e.g. stairwell with external windows or smoothly door closer operation and thus pressurization system shall be capable to compensate negative influence of an unpredicted processes.

The control system in accordance with the principle „we do not only realize fire scenarios, but save human lives” should realize control task in all conditions, regardless of the number of open / partially closed doors, broken windows, etc.

Communication and controlIn order to enable communication and control of the iSWAY-FC® units based pressurization system dedicated FireBus® protocol was developed and implemented. For any SAFETY WAY® type pressurization system 2 FireBus® loops can be distinguished:

• Global FireBus® interconnects in the loop MAC-FC(R) iSWAY-FC®(-D)(-R) regulators with TSS or TS (depending on system configuration). The tasks:

○ the transfer of Fire Alarm Signal (FAS) information between the devices,

○ monitoring the status of different pressurization system components and transmitting them to the TSS or MSPU,

○ transmitting control signals sent from TSS or TS switches to proper devices.

• Local FireBus® interconnects in the loop MAC-FC(R) iSWAY-FC®(-D)(-R) regulators with remote P-MACF differential pressure sensors, MAC-D-MIN regulators, T-MAC temperature sensors and MAC-LINK cards. The tasks:

○ communication between regulators MAC-FC, temperature sensors T-MACF, regulators MAC-D-MIN and MAC-LINK cards, with which it interoperates.

Local and Global FireBus® communication protocols have a loop topology which enables to increase its reliability and immunity to single damages of the data transmission lines (in such case required component can be accessed through the alternative branch of the loop).

Page 15: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems123

Dimensions and weight

W1

D1

W2

D2

B

A

187

C

Figure 17. External dimensions of the iSWAY-FC® type unit.

Table 2. Dimensions of the iSWAY-FC® unit and connecting elements.

External dimensions of the casing

A [mm]

B [mm]

C [mm]

D1 [mm]

D2 [mm]

W1=W2 [mm]

Size of the casing

0 1520 1070 870 435 435 770 x 770

1 1620 1320 1100 550 550 1000 x 1000

2 1720 1520 1300 650 650 1200 x 1200

Table 3. Performance and electrical parameters of the iSWAY-FC® units.

Urządzenie iSWAY-FC® - zestawienie parametrów urządzenia

TypCapacity

Available static

pressurePower supply Active

powerApparent

power

Electrical protection within

the unit

Electrical protection within the switchboard.

Recommended power supply cables Weight

[m3/h] [Pa] [V] [kW] [kVA] Typ [A] Typ [kg]

0.3 3000 900 3x400 3,38 3,45 FWC-10A10F gG 16 A NHXH FE180/E90 5x2,5 330

0.12 12000 430 3x400 5,47 5,57 FWC-16A10F gG 20 A NHXH FE180/E90 5x4 340

1.17 17000 380 3x400 5,26 5,36 FWC-16A10F gG 20 A NHXH FE180/E90 5x4 530

1.20 20000 390 3x400 6,96 7,10 FWC-16A10F gG 20 A NHXH FE180/E90 5x4 540

1.24 24000 360 3x400 9,22 9,40 FWC-20A10F gG 25 A NHXH FE180/E90 5x6 550

2.31 31000 400 3x400 9,22 9,40 FWC-20A10F gG 25 A NHXH FE180/E90 5x6 735

2.39 39000 420 3x400 13,00 13,26 FWC-32A10F gG 40 A NHXH FE180/E90 5x10 755

2.47 47000 300 3x400 17,40 17,75 FWC-40A10F gG 50 A NHXH FE180/E90 5x16 770

Page 16: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 124

Performance curvesiSWAY-FC(-D)

0

200

400

600

800

1000

1200

1400

1600

1800

0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000

2.472,391,241,201,170,120,3 2,31

iSWAY-FC -R

Chart 1.

0

200

400

600

800

1000

1200

0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000

1.17 1.20 1.24 2.31 2.39 2.47

Performance curves of an iSWAY-FC® fans.

Available structures of the unitThe basic version of the iSWAY-FC® unit is a compact structure intended (Fig. 18.) intended to be installed outside e.g. roof or ground level or inside e.g. machinery room. For units installed on the roof or technical floors Twin-Air-Intake module is recommended (Fig. 19.).

Other versions of an iSWAY-FC® units are unit with air intake (Fig. 20.) and vertical assembly unit with adjustable air intake module (Fig. 21.).

In order to achieve desired air intake rate of the pressurization fan, for units installed within the ductwork, it is recommend to provide straight duct section at least 1 m long before the fan on the air intake side.

Figure 18.

- Airfl ow direction – air supply unit

- Airfl ow direction – air exhaust unit

Basic version of the iSWAY-FC® unit to be installed horizontally fitted with flexible connectors on the air intake/supply sides (duct assembly

version).

Figure 19.

Stand-by air intake damper

Air fl ow direction

Stand-by air intake damper

min

imum

12

met

ers

iSWAY-FC® unit fitted with additional Twin-Air-Intake module (e.g. roof top assembly).

Figure 20. iSWAY-FC® with additional air intake module.

Page 17: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems125

Figure 21.

1479

2190

387

max

232

Vertical assembly version of the smallest „0” iSWAY-FC® unit (adjustable air intake closed).

Figure 22.

66

2510

387

max

A

325

Vertical assembly version of the smallest „0” iSWAY-FC® unit (adjustable air intake open).

Examples of electrical and data transmission connections

Figure 23.

D2 D2

BLE24

C1

SAP

ADAPTIVE

A13x400V

piSWAY-FC X.XX

1E2

1P1

BLE24

1P2

BLE24

C1

SAP

ADAPTIVE

A13x400V

piSWAY-FC X.XX

2E2

2P1

BLE24

2P2

TSS-2

B11x230V16W

MONITORING ROOM e.g. BMS room

Key:

- Control-Signal Board (TSS-2)

- Motorized shut-off damper

- Actuator Belimo BLE24-BELIMO

- Differential pressure measurement probes – tubes ø5 mm

BLE24

p

TSS-2

WIRINGMarking on the diagram

Connections of automation components Tye of the cable

TABELA 2

NHXH FE180/PH90 3x1,5

HDGs FE180/PH90 3x1,5

HTKSH FE180/PH90 ekw 2x2x0,8

HTKSH FE180/PH90 3x2x0,8

Guaranteed power supply cable 3x400V for iSWAY-FC

Guaranteed power supply 1x230VAC MSPU,TS, TSS

Przewód zasilający/sterujący 24VDC(podwójna czerpnia)

Pętla magistralna Global FireBus

Przewody ALARM SAP (NC)

Potwiedzenie Pracy (NO) Awaria zbiorcza (NC)

A1

B1

C1

D2

E2

Block diagram of connections between TSS-1 Control-Signal Board and one iSWAY-FC® unit.

Page 18: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 126

Figure 24.

D2 D2

BLE24

C1

SAP

ADAPTIVE

A13x400V

piSWAY-FC X.XX

1E2

1P1

BLE24

1P2

BLE24

C1

SAP

ADAPTIVE

A13x400V

piSWAY-FC X.XX

2E2

2P1

BLE24

2P2

TSS-2

B11x230V16W

POMIESZCZENIEMONITORINGU

Legenda:

- Tablica Sterująco - Sygnalizacyjna

- Przepustnica

- Siłownik BLE24-BELIMO

- Pomiar statycznej różnicy ciśnień - przewody impulsowe ø5

BLE24

p

TSS-2

OKABLOWANIEOznaczenie

na schemaciePołączenia elementów automatyki Typ kabla

TABELA 2

NHXH FE180/PH90 3x1,5

HDGs FE180/PH90 3x1,5

HTKSH FE180/PH90 ekw 2x2x0,8

HTKSH FE180/PH90 3x2x0,8

Przewód zasilania gwarantowanego3x400V dla iSWAY FC

Zasilanie gwarantowane 1x230VAC MSPU,TS, TSS

Przewód zasilający/sterujący 24VDC(podwójna czerpnia)

Pętla magistralna Global FireBus

Przewody ALARM SAP (NC)

Potwiedzenie Pracy (NO) Awaria zbiorcza (NC)

A1

B1

C1

D2

E2

Block diagram of connections between TSS-2 Control-Signal Board and two iSWAY-FC® units.

Figure 25.

D2 D2 D2

Key:

- Control-Signal Board (TSS-3)

- Motorized shut-off damper

- Actuator Belimo BLE24

- Differential pressure measurement probes – tubes ø5 mm

BLE24

C1

SAP

ADAPTIVE

A13x400V

piSWAY-FC X.XX

1E2

1P1

BLE24

1P2

BLE24

C1

SAP

ADAPTIVE

A13x400V

piSWAY-FC X.XX

2E2

2P1

BLE24

2P2

BLE24

C1

SAP

ADAPTIVE

A13x400V

piSWAY-FC X.XX

3E2

3P1

BLE24

3P2

TSS-3

B11x230V16W

MONITORING ROOM e.g. BMS room

BLE24

p

TSS-3

Block diagram of connections between TSS-3 Control-Signal Board and three iSWAY-FC® units.

Page 19: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems127

Figure 26. Exemplary block diagram of the expanded SAFETY WAY® pressure differential system (air release must be additionally provided).

Installation guidelinesEach iSWAY-FC® type unit shall be installed (units, air intakes, cable trays etc.) in such manner to avoid any collisions with other installations and enable free access to the removable inspection panels (maintenance and servicing). In order to enable easy access to the unit minimum distance from the fixed elements e.g. walls shall be maintained.

Page 20: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 128

Figure 27.

0,9 xB B

ServiceSide

Minimum distance of iSWAY-FC® unit from the fixed elements (e.g. walls).

Twin Air-Intake module (alternative air intake in case of smoke contamination)Air intake shall be provided for drawing air in from outside the building in such a way that it is not contaminated with smoke from a fire within the building. Air intake (intake) should always be positioned away from any potential fire hazards. In order to avoid contamination by the rising smoke, it is recommended to locate air intakes at the ground level or close to it (but well away from the basement smoke vents). If it is not possible, air intakes should be positioned at the roof level. It is essential that the air supply used for pressurization is never in danger of contamination by smoke. If the air intake is located at the roof level it is obligatory to provide smoke detector inside the air supply ductwork to cause automatic shutdown of the air supply fan. For the needs of the fire brigades manual override switch operating the air supply fan shall be provided.

Where air intakes are positioned at roof level there shall be two air intakes (Twin-Air-Intake module), spaced apart and facing different directions in such a manner that they could not be directly downwind of the same source of smoke. Each inlet shall be independently capable of providing the full air requirements of the system. Each inlet shall be protected by an independently operated smoke control damper system in such a way that if one damper closes due to smoke contamination, the other inlet will supply the air requirements of the system without interruption.

The discharge point of a smoke ventilation duct shall be a minimum of 1 m above the air intake and 5 m horizontally from it. Manual override switch to reopen the closed damper and to close the open damper shall be provided for fire brigade use.

Manual override switches of pressure differential system should be located in the following locations:

a) machinery room or machinery room of the pressure differential system (if separated), and

b) near the entrance to the building, at the site agreed with local authorities having jurisdiction.

These switches after activating should be locked in the „on” position, and should be designed so that their return to the „off” position is made by authorized personnel (e.g., by staff or by using code lock).

Described set of two alternative intakes operating automatically and enabling to switch to an alternative air intake is offered by SMAY company as a Twin-Air-Intake Module. Such module consists of two motorized volume control dampers with strictly

defined air tightness in accordance with EN 1751 and protected from the negative influence of ambient conditions. By default sizes of the air intake dampers are compatible with sizes of flexible connectors of the iSWAY-FC® units (easy assembly and connections).Przepustnica SRC-Z-U.

Multiblade air damper SRC-Z-U

Size of the casing iSWAY-FC B [mm] H [mm]

0 770 770

1 1000 1005

2 1200 1205

Figure 28.

BB+60

H

H+6

0

B+200

200

300

actuator

cable gland

damperactuator’s box

electric box

Dimensions of the Twin-Air-Intake module.

Identification of the unit

Figure 29. iSWAY-FC® rating plate.

Each iSWAY-FC® type unit is fitted with individual rating plate indicating parameters that enable precise identification of the unit.

Type – specifies the device’s technical specifications, e.g. FC 1.20 S/N – serial number Year – production year V [Δp] – capacity of the fan at available static pressureP [kW] – electric power of the unitΔP [Pa] – available static pressure

Page 21: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems129

iSWAY-FC® - Compact pressurization unit intended for smoke and heat control systemsUpon placing an order for iSWAY-FC® type unit following information shall be provided:

iSWAY - FC-<A>-<W>.<V><P>-<X>-<T>-<U>/<ADD>-<WER>

Where:

A control system*

none - standard control system

D - intended for local FireBus® loop

R - reversible flow fans (counteracting stack effect)

W size of the casing [mm]: 0 unit’s version 2012: 1500 x 1050 x 850; unit’s version 2015: 1520 x 1070 x 870

1 unit’s version 2012: 1600 x 1300 x 1080; unit’s version 2015: 1620 x 1320 x 1100

2 unit’s version 2012: 1700 x 1500 x 1280; unit’s version 2015: 1720 x 1520 x 1300

V capacity of the fan at 300 Pa

3 - capacity 3000 m3/h (for W = 0)

12 - capacity12000 m3/h (for W = 0)

17 - capacity 17000 m3/h (for W = 1)

20 - capacity 20000 m3/h (for W = 1)

24 - capacity 24000 m3/h (for W = 1)

31 - capacity 31000 m3/h (for W = 2)

39 - capacity 39000 m3/h (for W = 2)

47 - capacity 47000 m3/h (for W = 2)

P differential pressure sensor range*

none - -250; 250 Pa

HP - 600;600 Pa

X service side*

none - right side

L - left side

T operating temperatures range*

none - from -5 to +55°C

AF - from -25 to +55 °C – fitted with Anti Frost system

U location of the device*

none - inside the building

Z - outside the building

ADD accessories:

KE - flexible connector on the intake side

CP - air intake

UP - Twin-Air-Intake module

DA - automatic roof (for W=0, VER-2012)

SS - installation on welded feet – horizontal assembly

BF - installation on Big Foot - horizontal assembly

KM - fixation with angle bars – horizontal assembly

RS - installation on welded frame – horizontal assembly

SW - installation on self-aligned foot – vertical assembly with top air intake

(VER-2012)

PSW - installation on platform and self-aligned foot (VER-2012)

VER unit’s version

Page 22: COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND · 113 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems version 6.0.1 Figure 6. x - For systems

version 6.0.1 iSWAY-FC® - compact pressurization unit intended for smoke and heat control systems 130

2012 - version 2012 (casing thermally insulated with mineral wool and separate power supply equipment)

2015 - version 2015 (casing thermally insulated with PIR foam and integrated power supply equipment)

* optional values - default values will be used if optional values are not specified

Example of order: iSWAY – FC – D – 1.20 – AF / KE, KM – 2015

Upon placing an order where TSS-1, TSS-2, TSS-3, TS, MSPU, T-MACF, MAC-LINK, P-MACF,MAC-D-MIN, PZ are included it is indispensable to define number of each component listed above e.g.

Example:

TSS-1 - 1 pcs.T-MACF - 8 pcs.P-MACF -250÷ 250 – 16 pcs.

By default iSWAY-FC® units are fitted with flexible connectors on the air intake side to be installed on welded feet (SS) or fixed with angle bars (KM). All other components shall be ordered separately. Unit’s casing is painted in RAL color 9010 (white).

In case when pressurization system consists of more than 6 iSWAY-FC® type units it is recommended to provide control, visualization and monitoring of such pressurization system by means of Control Board (TS) and Operating Conditions Monitoring Device (MSPU) which enable easy integration of all components.