Combined Heat & Power Combined Heat & Power at at UNC Chapel Hill UNC Chapel Hill Raymond E. DuBose, P.E. Raymond E. DuBose, P.E. Director Director Energy Services Department Energy Services Department

Upload: others

Post on 27-Jun-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

Combined Heat & PowerCombined Heat & Poweratat

UNC Chapel HillUNC Chapel HillRaymond E. DuBose, P.E.Raymond E. DuBose, P.E.

DirectorDirectorEnergy Services DepartmentEnergy Services Department

Page 2: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

IntroductionIntroduction

Energy Supply systems overviewEnergy Supply systems overviewCogeneration FacilityCogeneration FacilityChilled Water System FeaturesChilled Water System FeaturesCHP PerformanceCHP Performance

Page 3: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

Energy Supply SystemsEnergy Supply Systems

District EnergyDistrict EnergyCentral Steam ProductionCentral Steam ProductionCentral Chilled Water ProductionCentral Chilled Water ProductionIntegral Electricity Generation, Purchase, Integral Electricity Generation, Purchase, & Distribution& Distribution

Page 4: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

DefinitionsDefinitions

Combined Heat & Power (CHP)Combined Heat & Power (CHP)==

CogenerationCogeneration==

Simultaneous generation of Simultaneous generation of steam and electricitysteam and electricity

Page 5: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

Cogeneration (CHP)Cogeneration (CHP)

Simultaneous production of electricity and Simultaneous production of electricity and steamsteamHigh thermal efficiencyHigh thermal efficiencyLow environmental impactLow environmental impact

Page 6: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

1880 1900 1920 1940 1960 1980 1997

U.S. Average Generating EfficienciesU.S. Average Generating Efficiencies100%

80%

60%

40%

20%

0%

Page 7: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

1880 1900 1920 1940 1960 1980 1997

U.S. Average Generating EfficienciesU.S. Average Generating Efficiencies100%

80%

60%

40%

20%

0%

UNC Cogen •

Page 8: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

UNC Chapel HillUNC Chapel HillCogeneration ConceptCogeneration Concept

Steam

ChilledWater

Electricity

Page 9: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

UNC Chapel Hill UNC Chapel Hill CogenerationCogeneration

Turbine 28 MWGenerator

Boilers

Steam

HeatingCoolingHot WaterSterilizationCooking/Dishwashing

Electricity

Page 10: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

UNC Chapel Hill Cogeneration FacilityUNC Chapel Hill Cogeneration Facility

Page 11: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

Circulating Fluidized Bed Circulating Fluidized Bed CombustionCombustion

Nitrous Oxides (Nitrous Oxides (NOxNOx) ) ----furnace temperaturefurnace temperature

Sulfur dioxide (SOSulfur dioxide (SO22) ) ----sorbentsorbent

Page 12: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

NSPS 40CFR60, Subpart DbNSPS 40CFR60, Subpart Db

SOSO22

90% reduction90% reduction1.2 lbs/1.2 lbs/MMBtuMMBtu

NOxNOx0.6 lbs/0.6 lbs/MMBtuMMBtu

OpacityOpacity20%20%

ParticulateParticulate0.5 lbs/0.5 lbs/MMBtuMMBtu

Page 13: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)
Page 14: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

UNC Cogen CFB System

Page 15: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

Chilled Water SystemsChilled Water Systems

Centralized production of chilled waterCentralized production of chilled waterDistribution of chilled water to serve Distribution of chilled water to serve campus needscampus needsUses electricity and steamUses electricity and steam

Page 16: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

North Chiller PlantNorth Chiller Plant

Page 17: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

Thermal Energy Thermal Energy StorageStorage

40,000 ton40,000 ton--hours capacityhours capacity4,000,000 gallons of water4,000,000 gallons of waterStratified storage tank 130 feet high x 80 Stratified storage tank 130 feet high x 80 feet diameterfeet diameterCompleted 2006Completed 2006Interconnected to primary distribution Interconnected to primary distribution lineslinesSupport plant chillers matched for Support plant chillers matched for charging tankcharging tank

Page 18: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)
Page 19: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

Duke EnergyDuke Energy

RealReal--time pricing (OPT/HP rate)time pricing (OPT/HP rate)Immediate response to pricing signalsImmediate response to pricing signalsSteam absorption chillersSteam absorption chillersThermal storage Thermal storage –– 10 MW10 MWCogeneration of electricityCogeneration of electricity

Page 20: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)

CHP PerformanceCHP Performance

Overall value $6,000,000 per yearOverall value $6,000,000 per year

Rate performance $2,000,000 per yearRate performance $2,000,000 per year

Page 21: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)
Page 22: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)
Page 23: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)
Page 24: Combined Heat & Power UNC Chapel Hill D… · Combined Heat & Power at UNC Chapel Hill Raymond E. DuBose, P.E. Director Energy Services Department. Introduction ... Cogeneration (CHP)