  • 8/11/2019 Com Dnp Enus

    1/84

  • 8/11/2019 Com Dnp Enus

    2/84

    NOTE

    For your own safety, please observe the warnings and safety instructions contained in this manual.

    Disclaimer of Liability

    This document has been subjected to rigorous technical review before being

    published. It is revised at regular intervals, and any modifications andamendments are included in the subsequent issues. The content of this doc-ument has been compiled for information purposes only. Although Siemens

    AG has made best efforts to keep the document as precise and up-to-dateas possible, Siemens AG shall not assume any liability for defects anddamage which result through use of the information contained herein.

    This content does not form part of a contract or of business relations; nordoes it change these. All obligations of S iemens AG are stated in the relevantcontractual agreements.

    Siemens AG reserves the right to revise this document from time to time.

    Document version: V1.10

    Release status: 03.2012

    Version of the product described: V1.1

    Copyright

    Copyright Siemens AG 2012 All rights reserved.

    The disclosure, duplication, distribution and editing of this document, or utili-zation and communication of the content are not permitted, unless autho-rized in writing. All rights, including rights created by patent grant or registra-tion of a utility model or a design, are reserved.

    Registered Trademarks

    SIPROTEC, DIGSI , SIGUARD, SIMEASand SICAMare registeredtrademarks of Siemens AG. Any unauthorized use is illegal. All other desig-nations in this document can be trademarks whose use by third parties fortheir own purposes can infringe the rights of the owner.

  • 8/11/2019 Com Dnp Enus

    3/84

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    3

    Preface

    Purpose of the Manual

    This manual contains information about:

    Communication within the SIPROTEC 5 family of devices and to higher-level control centers

    Installation of the modules

    Setting parameters in DIGSI 5

    Information on commissioning

    Target Audience

    Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and main-

    tenance of automation, selective protection and control equipment, and operational crew in electrical installa-

    tions and power plants.

    Scope

    This manual applies to the SIPROTEC 5 device family.

    Further Documentation

    [DwPreCom-110203-enUS-01.tif]

  • 8/11/2019 Com Dnp Enus

    4/84

    Preface

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    4

    Device manuals

    Device manuals describe the functions and applications of a specific SIPROTEC 5 device. The printed

    manual and the device's online help have the same informational structure.

    Hardware manual

    The Hardware manual describes the hardware components and device combinations of the SIPROTEC 5

    range.

    Operating manual

    The Operating manual describes the basic principles and procedures for operating and assembling the

    devices of the SIPROTEC 5 range.

    Communication protocol manuals

    The Communication protocol manuals include a description of specific protocols for communication within

    the SIPROTEC 5 family and to higher-level control centers.

    Product information

    The Product information includes general information about device installation, technical data, limit values

    for input and output modules, and conditions when preparing for operation. This document is delivered

    with each SIPROTEC 5 device.

    DIGSI 5 online helpThe DIGSI 5 online help contains a help package for DIGSI 5 and CFC.

    The help package for DIGSI 5 includes a description of the basic operation of software, the DIGSI princi-

    ples and editors. The help package for CFC includes an introduction to CFC programming, basic exam-

    ples of working with CFC, and a reference chapter with all the CFC components available for the

    SIPROTEC 5 range.

    SIPROTEC 5/DIGSI 5 Tutorial

    The tutorial on the DVD contains brief information about important product features, more detailed infor-

    mation about the individual technical areas, as well as operating sequences with tasks based on practical

    operation and a brief explanation.

    System catalog

    The system catalog describes the SIPROTEC 5 system features. Device catalogs

    The device catalogs describe device-specific features such as functional scope, hardware and applica-

    tions.

    Indication of Conformity

    [ScCEsign-080211-xxXX-01.tif]

    This product complies with the directive of the Council of the European Communities

    on harmonization of the laws of the Member States relating to electromagnetic com-

    patibility (EMC Council Directive 2004/108/EC) and concerning electrical equipmentfor use within specified voltage limits (Low Voltage Directive 2006/95/EC).

    This conformity has been proved by tests performed according to the Council Directive

    in accordance with the generic standards EN 61000-6-2 and EN 61000-6-4 (for EMC

    directive) and with the standard EN 60255-27 (for Low Voltage Directive) by Siemens

    AG.

    The device is designed and manufactured for application in an industrial environment.

    The product conforms with the international standards of IEC 60255 and the German

    standard VDE 0435.

  • 8/11/2019 Com Dnp Enus

    5/84

    Preface

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    5

    Other Standards

    IEEE Std C 37.90

    The technical data of the product is approved in accordance with UL.

    File E194016

    [ScPrefUL-070211-xxXX-01.tif]

    Additional Support

    For questions about the system, please contact your Siemens sales partner.

    Support

    Our Customer Support Center provides a 24-hour service.

    Phone: +49 (1805) 24-7000

    Fax: +49 (1805) 24-2471

    Email: [email protected]

    Training Courses

    Inquiries regarding individual training courses should be addressed to our Training Center:

    Siemens AG

    Siemens Power Academy

    Humboldtstrasse 59

    90459 Nuremberg

    Phone: +49 (911) 433-7415

    Fax: +49 (911) 433-5482

    Email: [email protected]

    Internet: http://www.siemens.com/energy/power-academy

    Safety Information

    This manual is not a complete index of all safety measures required for operation of the equipment (module,

    device). However, it comprises important information that must be noted for purposes of personal safety, as

    well as in order to avoid material damage. Information is highlighted and illustrated as follows according to the

    degree of danger.

  • 8/11/2019 Com Dnp Enus

    6/84

    Preface

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    6

    DANGER

    DANGERmeans that death or severe injury willresult if the measures specified are not taken.

    Comply with all instructions, in order to avoid death or severe injuries.

    WARNING

    WARNINGmeans that death or severe injury mayresult if the measures specified are not taken.

    Comply with all instructions, in order to avoid death or severe injuries.

    CAUTION

    CAUTIONmeans that medium-severe or slight injuries canoccur if the specified measures are not taken.

    Comply with all instructions, in order to avoid medium-severe or slight injuries.

    NOTICE

    NOTICEmeans that material damage canresult if the measures specified are not taken.

    Comply with all instructions, in order to avoid material damage.

    NOTE

    Important information about the product, product handling, or a certain section of the documentation, which

    must be given particular attention.

    Qualified Electrical Engineering Personnel

    Only qualified electrical engineering personnel may commission and operate the equipment (module, device)

    described in this document. Qualified electrical engineering personnel in the sense of this manual are people

    who can demonstrate technical qualifications as electrical technicians. These persons may commission, iso-

    late, ground and label devices, systems and circuits according to the standards of safety engineering.

  • 8/11/2019 Com Dnp Enus

    7/84

    Preface

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    7

    Use as Prescribed

    The equipment (device, module) may only be used for such applications as set out in the catalogs and the tech-

    nical description, and only in combination with third-party equipment recommended and approved by Siemens.

    Problem-free and safe operation of the product depends on the following:

    Proper transport

    Proper storage, setup, and installation Proper operation and maintenance

    When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper

    action is not taken, death, severe injury, or property damage can result.

    The equipment must be grounded at the grounding terminal before any connections are made.

    All circuit components connected to the power supply may be subject to dangerous voltage.

    Hazardous voltages may be present in equipment even after the supply voltage has been disconnected

    (capacitors can still be charged).

    Equipment with exposed current transformer circuits must not be operated. Prior to disconnecting the

    equipment, ensure that the current transformer circuits are short-circuited.

    The limit values stated in the document may not be exceeded. This must also be considered during testing

    and commissioning.

  • 8/11/2019 Com Dnp Enus

    8/84

    Preface

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    8

  • 8/11/2019 Com Dnp Enus

    9/84

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    9

    Table of Contents

    Preface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    1 Protocol Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

    1.1 Protocol Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

    1.1.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

    1.1.2 Physical Layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

    1.1.3 Data-Link Layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

    1.1.4 Pseudo Transport Layer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

    1.1.5 Application Layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151.2 Ethernet Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    1.2.1 RSTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    1.2.1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    1.2.2 SNTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    1.2.3 DCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    1.2.4 DHCP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    1.3 Transfer through Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

    1.3.1 Requirements for the Physical, Transport, and Application Layers . . . . . . . . . . . . . . . . . . . . . . . . .19

    1.3.2 Acknowledgments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

    1.3.3 Message Transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .191.4 Functional Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

    1.5 Fault Record Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22

    1.6 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

    1.7 Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

    1.8 Amount of Mappable Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

    2 Parameters and Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

    2.1 General Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

    2.2 Settings for the Serial Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30

    2.3 Settings for Communication through Ethernet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

    3 Parameterizing in DIGSI 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33

    3.1 Communication Module Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34

    3.2 Communication Module Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

    3.3 Signals to the Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38

    3.4 Select Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39

  • 8/11/2019 Com Dnp Enus

    10/84

    Table of Contents

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    10

    3.5 Adapting Mappings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.5.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.5.2 Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    3.5.3 Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    3.5.4 Measured Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    3.5.5 Counter Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433.5.6 Mapping on the Object Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    3.5.7 Number Representation Depending on the Parameterization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    3.5.8 Copy Mapping Rows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    3.6 Copying Mappings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    3.7 Exporting Mappings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    3.8 Changing Mappings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    3.9 Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    4 Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    4.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    4.2 Serial Communication Modules for Short Distances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    4.2.1 Special Features of the Serial Electrical Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    4.2.2 USART-AB-1EL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    4.2.3 USART-AC-2EL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    4.2.4 USART-AD-1FO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    4.2.5 USART-AE-2FO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

    4.3 Ethernet Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

    4.3.1 Operation of Ethernet Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

    4.3.2 ETH-BA-2EL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    4.3.3 ETH-BB-2FO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 664.4 Configuration, Installation, Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    4.4.1 Fasteners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    4.4.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    4.4.3 Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    5 Commissioning and Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    5.1 Diagnostic Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    5.2 Diagnostic Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

    6 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    6.1 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

    Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

    Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

  • 8/11/2019 Com Dnp Enus

    11/84

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    11

    1 Protocol Characteristics

    1.1 Protocol Structure 12

    1.2 Ethernet Services 18

    1.3 Transfer through Ethernet 19

    1.4 Functional Scope 20

    1.5 Fault Record Transfer 22

    1.6 Operating Modes 24

    1.7 Time Synchronization 25

    1.8 Amount of Mappable Information 26

  • 8/11/2019 Com Dnp Enus

    12/84

    Protocol Characteristics

    1.1 Protocol Structure

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    12

    1.1 Protocol Structure

    1.1.1 Description.

    DNP3 has a graded architecture. Instead of the OSI model, however, a simplified 3-layer model suggested by

    the IEC is used. This model was named EnhancedPerformance Architecture(EPA) by the IEC. However,DNP3 adds a 4th layer, a pseudo transport layer, with which messages can be segmented. The used graphics

    are taken from the standard DNP3Spec-V1-Introduction-20071215.pdf.

    [DwEPADia-060511-xxXX-01.tif]

    Figure 1-1 EPA Diagram

    The SIPROTEC 5 device supports the DNP3, level 2 version.

    Additional information is available in the following documents:

    DNP3Spec-V1-Introduction-20071215.pdf

    DNP3Spec-V2-Part1-ApplicationLayer- 20090315.pdf

    DNP3Spec-V2-Part2-ApplicationLayer- 20090315.pdf

    DNP3Spec-V2-Part3-ApplicationLayer-20071215.pdf

    DNP3Spec-V2-Sup1-SecureAuthentication-20100317.pdf

    DNP3Spec-V3-TransportFunction-20070203.pdf

    DNP3Spec-V4-DataLinkLayer-20070203.pdf

    DNP3Spec-V5-LayerIndependent-20071215.pdf

    DNP3Spec-V6-Part1-ObjectLibraryBasics-20071215.pdf

    DNP3Spec-V6-Part2-Objects-20090315.pdf

    DNP3Spec-V6-Part3-ParsingCodes-20090420.pdf

    DNP3Spec-V7-IPNetworking-20070711.pdf

    DNP3Spec-V8-Apdx1-DeviceProfile-20100223.pdf

    DNP3Spec-V8-Interoperability-20090611.pdf

  • 8/11/2019 Com Dnp Enus

    13/84

    Protocol Characteristics

    1.1 Protocol Structure

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    13

    1.1.2 Physical Layer.

    The physical layer mainly deals with the physical media through which the protocol is transferred. The physical

    layer deals with, for example, the condition of the media (free or occupied) and the synchronization through the

    media (start and stop).

    DNP3 most frequently uses a simple, asynchronous serial transmission like RS232 or RS485 with physical

    media like pilot wires and optical fiber. Moreover, the transmission can take place through Ethernet.

    [DwDalila-140211-xxXX-01.tif]

    Figure 1-2 Physical Layer

  • 8/11/2019 Com Dnp Enus

    14/84

    Protocol Characteristics

    1.1 Protocol Structure

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    14

    1.1.3 Data-Link Layer.

    The data-link layer manages the logical connection between the transmitter and the receiver of the information

    and improves the fault tolerance of the physical line. This is achieved with DNP3 by starting every data trans-

    mission package with a data head, and a 16 bit CRC (cyclic redundancy check) is executed for every 16 bytes

    of the package.

    A package is a part of the complete message transferred through the physical layer. The maximum size of adata package is 256 bytes. Each package has a 16-bit source address and a 16-bit target address, which can

    also be a general address (0xFFFF).

    The 10-byte data-link layer head contains:

    The address information

    A 16-bit start code

    The frame length

    A data link control byte

    The data link control byte displays the cause of the data transmission and the status of the logical connection.

    The data link control byte can have the following values:

    ACK (data link confirmation)

    NACK (negative confirmation)

    Connection needs to be reset

    Connection is reset

    Data link confirmation from the package required

    If a data link confirmation is needed, the receiver must respond with an ACK data package if the package was

    received and the CRC checks were successful. If no data link confirmation is requested, no response is re-

    quired.

    1.1.4 Pseudo Transport Layer.

    The pseudo transport layer segments application messages in multiple data transmission packages.

    The pseudo transport layer implements an individual byte function code for every package. The byte function

    code displays what the data transmission package is:

    The 1st package of a message

    The last package of a message

    Both (for individual message packages)

    The function code delivers a running package number. This subsequent package number is increased with

    each package and allows the receiver's transport layer to analyze the package.

    [DwTrfnct-140211-xxXX-01.tif]

    Figure 1-3 Pseudo Transport Layer

  • 8/11/2019 Com Dnp Enus

    15/84

    Protocol Characteristics

    1.1 Protocol Structure

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    15

    1.1.5 Application Layer.

    The application layer responds to received messages and creates messages based on the necessity and avail-

    ability of the user data. As soon as messages are available, they are sent to the pseudo transport layer. The

    messages are segmented here, sent to the data-link layer and transferred through the physical layer.

    If the data that is to be sent is too large for an individual application message, a number of application messag-

    es can be created and sent in a sequential manner. Each message is an independent application message.Their only connection with each other is the label in all messages that says that more messages will follow.

    Only the last message does not contain this label. Each application message refers to a fragment due to the

    fact that the user data may be fragmented. A message can thus be a single fragment message or a multi-frag-

    ment message.

    Application packages from DNP3 slaves are normally responses to queries. A DNP3 slave can also send a

    message without a request, thus, an unsolicited response.

    As in the data-link layer, application fragments can be sent with a confirmation request. An application confir-

    mation indicates that a message was not only received, but rather it was also syntactically analyzed without

    any errors. A data transmission confirmation or an ACK indicate only that the transmission package was re-

    ceived and that the CRC checks were error-free.

    Each application package begins with an application layer header, followed by one or more object heads/objectdata. The application layer header contains an application control code and an application-function code.

    If one of the following conditions is fulfilled, then the application control code contains labels:

    The package is a multi-package message.

    An application layer acknowledgment is requested for the package.

    The package is not requested.

    The application control code contains a continual application layer number. With this application layer number,

    the receiving application layer can recognize alien packages or lost packages.

    The application-function code in the header of the application layer indicates the cause or the requested func-

    tion in the message. While DNP3 allows a number of data types in a single message, it also allows only an

    individual query for a data type within the message.

    Examples for application-function codes include:

    Acknowledgments for confirmation on the application layer

    Read and write

    Select and execute (SBO (select before operate), controls)

    Direct control (for switching objects without SBO)

    Save and delete (for counters)

    Restart (both cold and warm)

    Enable and disable non-requested messages

    Selection of the classes

    The application-function code in the header of the application layer applies for all object headers. Thus, theapplication-function code applies for all data within the message package.

  • 8/11/2019 Com Dnp Enus

    16/84

  • 8/11/2019 Com Dnp Enus

    17/84

    Protocol Characteristics

    1.1 Protocol Structure

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    17

    [DwAplay2-140211-xxXX-01.tif]

    Figure 1-5 Application Layer - Part 2

  • 8/11/2019 Com Dnp Enus

    18/84

    Protocol Characteristics

    1.2 Ethernet Services

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    18

    1.2 Ethernet Services

    1.2.1 RSTP

    1.2.1.1 Overview.

    The Rapid Spanning Tree Protocol (RSTP) serves for the reorganization of the network structure in the event

    of an error. In other words, RSTP reroutes the data to another path after the failure of a network path.

    1.2.2 SNTP.

    The Simple Network Time Protocol is used to synchronize clocks via the Internet. With SNTP, client computers

    can synchronize their clocks with a time server via the Internet.

    SNTP is available for the integrated Ethernet interface (Port J) of the device:

    SNTP uses UDP port 123 (UDP - User Datagram Protocol).

    1.2.3 DCP.

    The Discovery and Basic Configuration Protocol (DCP) is used for automatic recognition of devices without a

    configured IP address. DIGSI 5 can find all SIPROTEC 5 devices in the network using DCP.

    DCP is not required for the functionality of communication protocols. The protocol can however in parallel be

    configured for a DIGSI Life List functionality.

    The DIGSI Life List shows the connected devices. You can monitor and process these devices via the DIGSI

    Life List.

    If you also desire a DIGSI Life List functionality through the LAN, then you must activate DCP.

    If you create a new device in DIGSI or add an Ethernet communication module to the device, DCP is activated.

    If you change this recommended default and want to switch off the DIGSI Life List functionality in the device,

    deactivate the DCP check box in the channel settings of the Ethernet communication module or for the inte-

    grated Ethernet interface.

    1.2.4 DHCP.

    The Dynamic Host Configuration Protocol (DHCP) enables a client, in this case the Ethernet interface, to

    access IP address and configuration data from a DHCP server. In this case, a DHCP server has to be available

    in the network. If DHCP is activated, you do not have to configure the Ethernet interface network settings your-

    self.

  • 8/11/2019 Com Dnp Enus

    19/84

  • 8/11/2019 Com Dnp Enus

    20/84

    Protocol Characteristics

    1.4 Functional Scope

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    20

    1.4 Functional Scope.

    The DNP3 interface of the SIPROTEC 5 device supports the following functions:

    Function Description

    Binary inputs with status Remote Terminal Unit (RTU)

    Object 01 and variation 02 describe the state of a digital input channel or in-

    ternal software information.

    They are also used during the general interrogation by an RTU to synchro-

    nize the database. The general interrogations are conducted after the run or

    cyclically during the runtime.

    Binary inputs with changed

    time

    Object 02 and variation 02 describe the changes of a digital input channel or

    of internal software information with the associated change time. The binary

    inputs are used for spontaneous process events.

    Binary outputs with status Object 10 and variation 02 describe the current status of a binary output

    channel.

    The control relay output block controls the binary output channels. See also

    object 12.

    Control relay output block Object 12 and variation 01 are used for commands for the process or for the

    setting-up of internal functions.32-bit binary meter with

    marking

    Object 20 and variation 01 are used for the display of metered values for

    active and reactive power.

    32-bit binary change meter

    without time

    Object 22 and variation 01 are used for the display of changed meter data for

    active and reactive power.

    32 bit analog inputs

    (measured values)

    Object 30 and variation 01 describe signed 32-bit values for the digitalized

    analog signals or their calculated values.

    16 bit analog inputs

    (measured values)

    Object 30 and variation 02 describe signed 16-bit values for the digitalized

    analog signals or their calculated values. They are used for the general inter-

    rogation during start-up. A measured value snapshot is also possible.

    32-bit analog change values

    without time

    Object 32 and variation 01 are used for the display of a changed analog

    value.

    16-bit analog change valueswithout time

    Object 32 and variation 02 are used for the display of a changed analogvalue.

    Time and date

    Write function

    Object 50, variation 01

    The time and date object are used for time synchronization.

    Time and date

    Read function

    Read the system time of the device.

    Date and time are displayed in milliseconds.

    Here midnight on January 1, 1970 is 00:00 hours, 00:00 minutes, 00:00

    seconds and 00:00 milliseconds.

    Data class Object 60, variation 01, 02, 03, 04

    These objects indicate different classes of information elements:

    The class 0 contains all information objects that are not distinguished in

    terms of class 1 to 3.

    The classes 1 to 3 contain groups of events from information elements.

    The data from class 1 has the highest priority, followed by class 2, class 3,and the static data.

    Class 1 always means class 0 + 1 and class 2 means class 0 + 2.

    File transfer Object 70, variation 01, 02, 03, 04, 05, 06, 07

    Transfer of a fault record possible

    Internal displays Object 80, variation 01

    Writing the value 00 on index 7 leads to reset of the bit Restartin the flag byte

    for all data objects.

    Writing to Index 4 resets the Need TimeBit.

  • 8/11/2019 Com Dnp Enus

    21/84

    Protocol Characteristics

    1.4 Functional Scope

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    21

    NOTE

    These variations are set. You cannot change the variations in DIGSI.

  • 8/11/2019 Com Dnp Enus

    22/84

    Protocol Characteristics

    1.5 Fault Record Transfer

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    22

    1.5 Fault Record Transfer

    Configuration of a Fault Record

    The content of a fault is parameterized as described in the Operating manual.

    NOTE

    If the fault record for the serial DNP3 protocol is read via the DNP3 master, Siemens recommends 5 seconds

    as the setting for the maximum length of a fault (default setting in device). If the fault record is longer, the con-

    nection to the device could be broken because large data volumes have to be transferred serially. This con-

    straint does not apply for DNP3 TCP (Ethernet).

    Transferring a Fault Record

    The file transfer can be used to transfer a fault record (Object 70). The Rcd Mademessage is used to query

    the availability of the fault record. When the message is mapped and there is a new fault in the device the

    message is transferred. Cyclical reading of the directory is also possible. If there are files in the directory, thenthere are also fault records. Specifically, the transfer takes place as follows:

    The following steps are required to read the directory:

    Reading of the directory with File Transport Object (obj 70 var 7)

    Waiting for the response

    If the read operation was successful, the master station increases the block number and reads the next

    block.

    If the status indicator Lastis set in the response, the master station closes the file with File Operation

    Status Object(obj 70 var 4).

    Every fault record is identified by an existing file. The following information is transferred for this:

    File Name Offset

    File Name Size

    File Type

    File Size

    Time Of Creation

    Permissions

    Request ID

    File Name

    The master station can now select the required fault. The transfer takes place in the same manner as with

    reading the directory.

  • 8/11/2019 Com Dnp Enus

    23/84

    Protocol Characteristics

    1.5 Fault Record Transfer

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    23

    [ScDNPftr-261010-enUS-01.TIF]

    Figure 1-6 File Transfer in DIGSI

    NOTE

    Transferring a fault using a serial connection can take a long time and results in a significant load on the com-

    munication connection.

  • 8/11/2019 Com Dnp Enus

    24/84

    Protocol Characteristics

    1.6 Operating Modes

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    24

    1.6 Operating Modes.

    The behavior of the protocol does not depend on the operating mode of the device. The protocol is not activated

    in the operating modes fallback, boot system and hardware test.

  • 8/11/2019 Com Dnp Enus

    25/84

    Protocol Characteristics

    1.7 Time Synchronization

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    25

    1.7 Time Synchronization.

    The accuracy of the time synchronization is less than 5 ms.

    NOTE

    If you require a more accurate time synchronization, perform the time synchronization via DCF/IRIG-B.

  • 8/11/2019 Com Dnp Enus

    26/84

    Protocol Characteristics

    1.8 Amount of Mappable Information

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    26

    1.8 Amount of Mappable Information.

    The following information may be mapped:

    Information Maximum mappable amount

    Indications + Controllables at Tx 500

    Controllables at Rx 20Settings at Tx 0

    Measurements at Tx 100

    Counters at Tx 10

  • 8/11/2019 Com Dnp Enus

    27/84

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    27

    2 Parameters and Properties

    2.1 General Settings 28

    2.2 Settings for the Serial Connection 30

    2.3 Settings for Communication through Ethernet 31

  • 8/11/2019 Com Dnp Enus

    28/84

    Parameters and Properties

    2.1 General Settings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    28

    2.1 General Settings.

    During the parameterization, make the following settings for the serial communication between the systems

    control and the SIPROTEC 5 device through DNP3:

    Parameter name Description Settings

    Slave address Link address of the SIPROTEC 5 device Permitted range = 1 to 65 532

    Standard setting = 1

    Master address Address of the DNP3 master Permitted range = 1 to 65 532

    Standard setting = 10

    Time zone

    Time zone of the DNP3 device (has to be the

    same as the SIPROTEC 5 device's time zone)

    UTC

    Local

    Standard setting = UTC

    Light Idle state You determine the communication medium with

    this parameter. If the communication takes place

    via a fiber optic cable (LWL), the rest position will

    be specified at the same time.

    The non-flickering light state is relevant only for

    optical modules.

    Not active: Communication via

    RS485

    ON: Communication via optical

    fiber; rest position light on

    OFF: Communication via optical

    fiber; rest position light off (standard

    setting)Link retries The number of transmission attempts (LinkRe-

    tries)

    If the receiver did not send a confirmation, a data

    package will be transferred again.

    Setting: Sending with confirmation

    Standard setting = 2

    Link con re

    quires

    The receiver is asked to send a confirmation of

    the last package.

    Not for all telegrams (standard set-

    ting)

    For subdivided telegrams

    For all telegrams

    Link con time

    out

    During this period of time (in ms; LinkConfTime-

    out), a confirmation from the receiver is waited for

    until a repeat of the last telegram occurs. That

    happens only if the confirmation was sent. The

    time starts after transmission of the last byte.

    Standard setting = 3000 ms

    App con requires This parameter establishes when a confirmation

    of the application layer is required.

    If messages contain amended

    data, then a confirmation of the

    application layer is required.

    If telegrams from divided packag-

    es are not the completion of a

    package, then a confirmation of

    the application layer is required

    (standard setting).

    App con time out The receiver waits a desired amount of time (in

    ms) until the previous response is confirmed.

    If the confirmation of the application layer is used

    together with the link confirmation, then make

    sure that the time-out of the application layer (Ap-plTimeout) is long enough in order to end all

    transmissions.

    The following formula describes this requirement:

    [FoZeitDN-090310-enUS-01.tif]

    Standard setting = 9000 ms

  • 8/11/2019 Com Dnp Enus

    29/84

    Parameters and Properties

    2.1 General Settings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    29

    The following parameters only make sense if the parameter Enable unsolicitedis set to On:

    Need time syn. Time interval (in ms) until the internal display

    Time requiredis set. This time interval is includ-

    ed in every response message. The time interval

    signals to the master to start a new time synchro-

    nization with the device.

    0 = The internal display is never set.

    Standard setting = 120 000 ms

    Arm Select Timer

    A command must be selected and executed inthis time (in ms).

    Standard setting = 1000 ms

    Enable unsolic

    ited

    You determine whether unrequested transmis-

    sion is configured with this parameter.

    Off = The non-requested transmis-

    sion is not configured and can never

    be switched on from a connected

    master (standard setting).

    On = The non-requested transmis-

    sion is configured and must be

    made possible after the 1st non-re-

    quested response from the master.

    Unsolicited events

    1

    1. This parameter is divided into class 1, 2, and 3

    This parameter regulates a conditionof the non-requested transmission for

    every class of changed events (class

    1, class 2, and class 3).

    If the number of events per class cor-

    responds with this value or exceeds

    this value, then a non-requested re-

    sponse will be sent.

    Standard setting = 10

    Unsolicited time

    2

    2. This parameter is divided into class 1, 2, and 3

    This parameter regulates a condition

    of the non-requested transmission for

    every class of changed events (class

    1, class 2, and class 3).

    If the time (in ms) after an event corre-

    sponds to this value or exceeds this

    value, a response will be transmitted

    unrequested. Also sent if only 1 event

    occurred.

    Standard setting = 15 000 ms

    Unsolicited retry If no non-requested response was

    sent within the Unsolicited time

    parameter, then this parameter regu-

    lates how often a different non-re-

    quested response should be sent.

    Standard setting = 5

    Unsolicited con time

    out

    Time (in ms) until the receiver con-

    firmed the non-requested response. If

    this parameter has the value 0 or it is

    smaller than the App con time out

    parameter, then the non-requestedresponse is sent again as soon as the

    App con time outparameter has

    expired. If an inquiry is received to

    read, then the read query will first be

    answered. The unrequested re-

    sponse is then not transmitted.

    Standard setting = 6000 ms

    Parameter name Description Settings

  • 8/11/2019 Com Dnp Enus

    30/84

    Parameters and Properties

    2.2 Settings for the Serial Connection

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    30

    2.2 Settings for the Serial Connection.

    Additionally execute these settings for the communication on the serial module:

    Parameter Name Description Settings

    Baud rate The DNP3 communication module

    supports baud rates in the range from

    2400 Bd to 57 600 Bd.

    Standard setting = 19 200 Bd

    Data bit

    7 data bits or 8 data bits can be set on

    the communication module.

    8 data bits must be set for the DNP3

    protocol.

    Stop bit The DNP3 communication module

    supports 1 stop bit and 2 stop bits.

    Standard setting = 1 stop bit

    Parity You set the parity with this parameter. No parity (standard setting)

    Even parity

    Odd parity

  • 8/11/2019 Com Dnp Enus

    31/84

    Parameters and Properties

    2.3 Settings for Communication through Ethernet

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    31

    2.3 Settings for Communication through Ethernet.

    Additionally execute these settings for the communication on the Ethernet module:

    The other required IP settings are taken from the module setting.

    [ScEthSet-060511-enUS-01.tif]

    Figure 2-1 IP Settings in the Module Setting

    Parameter Name Description Settings

    Port Port number in the range of 1 to

    61 439

    Standard setting = 20 000

  • 8/11/2019 Com Dnp Enus

    32/84

    Parameters and Properties

    2.3 Settings for Communication through Ethernet

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    32

  • 8/11/2019 Com Dnp Enus

    33/84

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    33

    3 Parameterizing in DIGSI 5

    3.1 Communication Module Selection 34

    3.2 Communication Module Configuration 35

    3.3 Signals to the Communication Modules 38

    3.4 Select Mapping 39

    3.5 Adapting Mappings 40

    3.6 Copying Mappings 48

    3.7 Exporting Mappings 49

    3.8 Changing Mappings 50

    3.9 Time Synchronization 51

  • 8/11/2019 Com Dnp Enus

    34/84

    Parameterizing in DIGSI 5

    3.1 Communication Module Selection

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    34

    3.1 Communication Module Selection.

    The devices are delivered equipped with communication modules. You can install and replace communication

    modules retrospectively. When doing so, you must ensure that both the protocol firmware as well as the pa-

    rameterization of the protocol are first transferred through DIGSI 5.

    Select the communication modules from the library in the Hardware Editorworking area in DIGSI 5. The type

    of communication protocols to be used is the deciding factor when selecting the communication module. Theserial DNP3 protocol runs on serial modules (USART = Universal Synchronous/Asynchronous Receiver/Trans-

    mitter) with electrical RS485-interfaces or optical 820-nm-interfaces. The module can have 1 or 2 interfaces.

    The DNP3 protocol through TCP runs on all Ethernet modules.

    Operating the DNP3 protocol through the integrated Ethernet interface (Port J) is not possible.

    In the Project Tree, select the Devices and Networksarea.

    [ScProjtr-300311-enUS-01.tif]

    Figure 3-1 Selection in Project Tree

    Move the communication module by drag and drop from the hardware catalog to the plug-in module position

    of the device.

    You must set the communication module after placing it on the plug-in module position and configure it with the

    DNP3 protocol.

  • 8/11/2019 Com Dnp Enus

    35/84

    Parameterizing in DIGSI 5

    3.2 Communication Module Configuration

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    35

    3.2 Communication Module Configuration.

    The installed communication modules are configured in the working area Hardware Editorin DIGSI. There are

    modules with 1 or 2 serial interfaces. Here a module with 2 RS485 interfaces is used.

    [ScDNPMpr-251110-enUS-01.tif]

    Figure 3-2 Serial Communication-Module Configuration

    Each communication channel of a communication module must be configured individually.

    Highlight the channel to be configured in the Device view. The protocol types are listed in the working-area

    window that opens. These can be routed on the highlighted channel.

    Depending on the type of communication module, one or more protocols can be routed per channel. However,

    the DNP3 protocol cannot be parameterized jointly with another protocol on one channel. The DNP3 protocol

    can be configured twice on 2 channels of a module or on one channel of a different module also in the device.

    Through this, the protocol can be executed redundantly, also on different modules.

    DIGSI defines the selection of the combinable protocols. The combination of the individual modules is visible

    in DIGSI.

    With the selection of the communication channel, the parameters required for the DNP3 protocol are shown.

    The following images show the settings for the serial connection and the settings for the communication

    through Ethernet.

    You can find more detailed information on this in chapter 2.1 General Settings.

  • 8/11/2019 Com Dnp Enus

    36/84

    Parameterizing in DIGSI 5

    3.2 Communication Module Configuration

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    36

    [ScDNPset-251110-enUS-01.tif]

    Figure 3-3 Settings for the Serial Connection

  • 8/11/2019 Com Dnp Enus

    37/84

    Parameterizing in DIGSI 5

    3.2 Communication Module Configuration

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    37

    [ScDNPEth-251110-enUS-01.tif]

    Figure 3-4 Settings for Communication through Ethernet

  • 8/11/2019 Com Dnp Enus

    38/84

    Parameterizing in DIGSI 5

    3.3 Signals to the Communication Modules

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    38

    3.3 Signals to the Communication Modules

    Description of the Signals to the Communication Modules

    There are different signals for each communication module:

    Channel Live

    The signal Channel Livedisplays the data flow. Therefore, the signal indicates that the communication

    service is transmitting and receiving data on the module.

    Consider that multiple services can run in parallel on one Ethernet module. The representation is defined

    in the standard IEC 61850, Edition 2.

    Module ready

    The signal Module readyindicates that the module has started and the protocol applications are started.

    You can reallocate this signal, for example, LED, log, or message. Then you can recognize whether the

    IEC 61850 services, for example, GOOSE, are started on the Ethernet module and are working correctly.

    NOTE

    Starting the module can take some time.

    Health

    The signal Healthindicates the state of the module. The following 3 states can occur in this case:

    - Okay

    Module OK indicates, that the module is working.

    - Warning

    This state is not used.

    - Alarm

    The state Alarmis set when there is a failure of the module.

    Each protocol application has a Healthnode. If a protocol has problems at startup, for example, missing pa-

    rameters, no mapping, no hardware support, the status is set to Alarm. An alarm in a protocol causes an alarm

    of the module.

  • 8/11/2019 Com Dnp Enus

    39/84

    Parameterizing in DIGSI 5

    3.4 Select Mapping

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    39

    3.4 Select Mapping.

    With the selection of the protocol on a channel, the mapping for the DNP3 protocol is also determined.

    The routings defined in the mapping are displayed in the Communication Data Mapping Editor for each chan-

    nel. Standard mapping contains prioritized indications, measured values, and commands.

    A standard mapping is provided for the DNP3 protocol. The standard mapping contains the routings, which are

    specified by the DNP3 protocol.

    Routings in the communication matrix are also possible without selecting an existing mapping file.

    [ScMapSln-251110-enUS-01.TIF]

    Figure 3-5 Select Mapping

    NOTE

    YAfter instantiating the protection functions, assign the standard mapping sas the second to last step. After this,

    you must parameterize the time synchronization.

    Retrospectively created data objects are not automatically included in an existing mapping.

  • 8/11/2019 Com Dnp Enus

    40/84

    Parameterizing in DIGSI 5

    3.5 Adapting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    40

    3.5 Adapting Mappings

    3.5.1 Description.

    You can copy mappings within a device to other channels.

    The prioritized signals are displayed in the working area Communication Mapping .

    You can change the mapping on a channel with the following options:

    Routing additional signals by highlighting in the Receiveor Transmitcolumn and entering the DNP3 pa-

    rameters

    Removing existing signals (removing the marker)

    Changing the protocol routings (group and index)

    All information, which is not dimmed in the Communication Mapping working area can be routed to the pro-

    tocol. The routing of some typical data types is explained in more detail below:

    3.5.2 Indications.

    The indications are routed by highlighting the object in the Transmitcolumn. Notifications are information that

    is sent to a DNP3 master. After this, the parameters required for the DNP3 protocol must be entered.

    The following parameters are necessary:

    Object group

    Object group 1 is preset for messages.

    Index

    Class

    You can route the following IEC 61850 data types to DNP3 messages (binary inputs):

    SPS (Single point status)

    DPS (Double point status)

    ACD (Directional protection activation information)

    ACT (Protection activation information)

    You can map the two data types ACD and ACT to SPS indications only via conversions. Conversions are used

    to map individual information contained in the data types.

    [ScDNPMap-080611-enUS-01.tif]

    Figure 3-6 Mapping Table

  • 8/11/2019 Com Dnp Enus

    41/84

    Parameterizing in DIGSI 5

    3.5 Adapting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    41

    3.5.3 Commands.

    The commands are routed by highlighting in the Receivecolumn. The mapping of the commands occurs like

    the mapping of messages. Here object group 12 is preset.

    NOTE

    For commands, the DNP3 protocol allows both direct operate and a select before switching. The type of switch-ing is configured by the switching object; this means the protocol takes over the mode that is parameterized in

    the switching object.

    You can route the following IEC 61850 data types to DNP3 commands (binary output):

    SPC (Single Point Control)

    DPC (Double Point Control)

    If a command status signal should be mapped or if it is preset through the control model, the status signal from

    the command will be parameterized in the same line under the Transmitcolumn.

    [ScMapCtr-060511-enUS-01.tif]

    Figure 3-7 Mapping Commands

    Supported Control Models

    The SIPROTEC 5 device supports the control models (according to IEC 61850):

    Direct with normal security

    SBO (Select before operate) with normal security

    Direct with enhanced security

    SBO with enhanced security

    3.5.4 Measured Values.

    The measured values are routed by highlighting the object in the Transmitcolumn. After this, the parameters

    required for the DNP3 protocol must be entered.

    The following parameters are necessary:

    Group

    Index

    Scaling

  • 8/11/2019 Com Dnp Enus

    42/84

    Parameterizing in DIGSI 5

    3.5 Adapting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    42

    Object

    Class

    [ScMmeDNP-251110-enUS-01.tif]

    Figure 3-8 Mapping Measured Values

    Scaling Measured Values

    The measured values between the SIPROTEC 5 device and the DNP3 master are transferred as integer values

    in 16-bit or 32-bit format. 16 bits correspond with a range from 0 to 65 535; 32 bits correspond with a range

    from 0 to 4 294 967 295.

    You can find more detailed information on this in chapter 3.4 Select Mapping.

    The measured values are available in the SIPROTEC 5 device in floating-point format, related to the parame-

    terized rated variables of the primary system in percentage.

    Convert Measured Values

    Before the transfer of a measured value through DNP3, the measured values must be converted in the SIPRO-

    TEC 5 device. The measured values are scaled.

    The scaling of a measured value determines the form of transmission. These forms of transmission are:

    Value type

    Scaling factor

    Scaling Factor

    The measured value is multiplied in the SIPROTEC 5 device by the scaling factor. The measured values are

    then changed into integer measured values (for DNP3) in the floating-point procedure.

    Through multiplication with a multiple of 10, decimal points can also be transferred into integer measured

    values.

  • 8/11/2019 Com Dnp Enus

    43/84

    Parameterizing in DIGSI 5

    3.5 Adapting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    43

    Calculation Formula for Integer Measured Values

    The following conditions must be met for the calculation:

    The floating-point number (measured valueFloat) is available in the corresponding value type (primary or

    secondary value).

    The floating-point number (measured valueFloat) is available as a percent value.

    The integer measured value (measured valueInteger) for the transmission through DNP3 is calculated accordingto the following formula:

    [FoMwIntr-230310-enUS-01.tif]

    Setting the Measured-Value Threshold

    In the measured-value processing via DNP3, there are measured-value thresholds you can set. The measured-

    value threshold for the individual measured values is not set in the communication matrix but centrally in the

    routing matrix. The following measured-value thresholds are preset:

    This setting value applies to the currently measured value. If, for instance, the measured value is 110 kV and

    the preset value is 2 %, then the measured value will be transmitted in the event that the measured values

    changes by 2.2 kV.

    3.5.5 Counter Values.

    All of the IEC 61850 objects of type BCR (Binary Counter Reading) in the SIPROTEC 5 device can be routed

    to counter values (object type 20). The routing takes place by marking the object in the Transmitcolumn.

    An Example Calculation for a Measured Performance Value

    The following parameters are included in the parameter set:

    Rated operating voltage of the primary system = 12.00 kV

    Rated operating current of the primary system = 100 A

    The measured performance value is calculated based on the following formula:

    Measured-Value Threshold Setting value

    db1for values from type frequencies:

    (neutral zone for values of the type Frequencies)

    1. db = dead band

    0,1 %

    dbfor values from type voltages:

    (neutral zone for values of the type Voltages)

    2 %

    dbfor values from type currents:

    (neutral zone for values of the type Currents)

    10 %

    dbfor values from type power:

    (neutral zone for values of the type Power)

    10 %

    dbfor values from type all others:

    (neutral zone for values of the type all others)

    10 %

    dbAngfor values from all type angles:

    (neutral zone dbAng for values of all type angles)

    1 %

  • 8/11/2019 Com Dnp Enus

    44/84

    Parameterizing in DIGSI 5

    3.5 Adapting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    44

    [FoLeisMW-121109-enUS-01.tif]

    In the SIPROTEC 5 device, this measured performance value is stated from 0.00 MW to 9.99 MW, that is, with

    2 relevant decimal points.

    Siemens recommends a scaling factor of 100 for the transmission as an integer measured value through DNP3.

    With this, a value from 0 to 999 is transferred to the master.

    If the scaling factor is less than 100, then important information about the decimal points is lost during the trans-

    mission. A scaling factor larger than 100 does not create any precise information. The accuracy is only simu-

    lated, but really non-existent. Thus, with a scaling factor of 100 there is an interpretation of the integer mea-

    sured value (measured valueInteger) through DNP3 with: 32 768. This corresponds with a value of 327.68

    MW.

    3.5.6 Mapping on the Object Status.

    The following table shows mapping on the object status.

    Table 3-1 Mapping on the Object Status

    IEC 61850 Implementation Preferred DNP3 Implementation

    Attribute name Attribute type Value/Value

    range

    Point Type Point Count

    or Note

    Comment

    PACKED LIST - - - -

    validity CODED

    ENUM

    good - ONLINE set if

    good

    -

    questionable - COMM_LOST -

    detailQual PACKED LIST - - - -

    overflow BOOLEAN DEFAULT

    FALSE

    - ROLLOVER -

    outOfRange BOOLEAN DEFAULT

    FALSE

    - OVER_RANG

    E

    -

    badReference BOOLEAN DEFAULT

    FALSE

    - REFERENCE

    _ERR

    -

    oscillatory BOOLEAN DEFAULT

    FALSE

    - CHATTER_FI

    LTER

    -

    failure BOOLEAN DEFAULT

    FALSE

    - OFFLINE -

    oldData BOOLEAN DEFAULT

    FALSE

    - COMM_LOST -

    inconsistent BOOLEAN DEFAULT

    FALSE

    - DISCONTI-

    NUITY

    -

    inaccurate BOOLEAN DEFAULT

    FALSE

    - - -

    source CODED

    ENUM

    process - - -

    substituted - LOCAL_FOR

    CED

    -

    test BOOLEAN DEFAULT

    FALSE

    - LOCAL_FOR

    CED

    -

    operatorBlocked BOOLEAN DEFAULT

    FALSE

    - LOCAL_FOR

    CED

    -

  • 8/11/2019 Com Dnp Enus

    45/84

    Parameterizing in DIGSI 5

    3.5 Adapting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    45

    3.5.7 Number Representation Depending on the Parameterization.

    If you determine the scaling of a measured value, then you first set the number format and the unit. The number

    format contains the number of relevant decimal places.

    Percent Values

    For percent values, Siemens recommends a scaling factor of 100. This results in an interpretation of the integer

    measured value (measured valueInteger) through DNP3 with a measured value from 32 767. This corresponds

    with a percentage value of 327.67%.

    Secondary Values

    If, for example, the values from the transducer inputs are specified in mA, then the transmission of a measured

    value as a secondary value makes sense.

    The number of significant decimal points depends on the system and transducer data.

    Primary Values

    The position of the decimal point and the respective unit are determined for primary values based on the pa-

    rameterized rated variables of the primary system.

    3.5.8 Copy Mapping Rows.

    You can highlight and copy individual mapping rows, columns, or cells. To cut, copy, and paste, use either the

    buttons in the toolbar or right-click on the corresponding row, column, or cell.

    [DiIconCP-240111-xxXX-01.tif]

    Figure 3-9 Cut, Copy, and Paste Buttons

    [ScRowCPa-250111-enUS-01.TIF]

    Figure 3-10 Copy Individual Mapping Rows

  • 8/11/2019 Com Dnp Enus

    46/84

  • 8/11/2019 Com Dnp Enus

    47/84

    Parameterizing in DIGSI 5

    3.5 Adapting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    47

    [ScCPSeAr-240111-enUS-01.TIF]

    Figure 3-13 Copy Range

    [ScMapPas-250111-enUS-01.TIF]

    Figure 3-14 Paste Copied Range

  • 8/11/2019 Com Dnp Enus

    48/84

    Parameterizing in DIGSI 5

    3.6 Copying Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    48

    3.6 Copying Mappings.

    Once created, mappings can be copied to another channel on which the DNP3 protocol also runs and also

    transferred to another device.

    [ScCopChn-240111-enUS-01.TIF]

    Figure 3-15 Copy Mapping Settings from a Channel

    [ScPasChn-250111-enUS-01.TIF]

    Figure 3-16 Paste Mapping Settings from a Channel

    NOTE

    When copying to a different device, only the mappings are copied for which the same function groups/func-

    tions/function blocks exist in the source and target device.

  • 8/11/2019 Com Dnp Enus

    49/84

    Parameterizing in DIGSI 5

    3.7 Exporting Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    49

    3.7 Exporting Mappings.

    Once created, mappings can be exported to a data file. The master/client configuration software can be con-

    figured using this export. The Siemens substation control unit parameterization software can import this file di-

    rectly.

    To export a device mapping file, select the device and click the Projectmenu. Then select the menu item

    Export. The Exportdialog appears.

    You can select from the following data formats for the export:

    Device-dependent data formats, for example, TEAX, DEX5 etc.

    Protocol-dependent data formats

    For every protocol for which parameters are set, there is a special format with the appropriate file exten-

    sion DigT103 or DigDNP.

    Finally, click Export.

    [ScMapExp-241110-enUS-01.TIF]

    Figure 3-17 Exporting Mapping to a Data File

  • 8/11/2019 Com Dnp Enus

    50/84

    Parameterizing in DIGSI 5

    3.8 Changing Mappings

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    50

    3.8 Changing Mappings

    NOTE

    If you change a standard mapping, all existing mapping information will be lost. DIGSI shows a message there-

    fore.

    [ScChgMap-060511-enUS-01.tif]

    Figure 3-18 Message in DIGSI

  • 8/11/2019 Com Dnp Enus

    51/84

    Parameterizing in DIGSI 5

    3.9 Time Synchronization

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    51

    3.9 Time Synchronization.

    2 main clocks can be parameterized in the SIPROTEC 5 device. If one of the time sources in the device is set

    to DNP3, then the time synchronization runs through a DNP3 master. The time sources are set in DIGSI 5 or

    on the device.

    Make the time synchronization settings in DIGSI 5 in the Time SettingsEditor in the Parameterscategory.

    [ScTmSncr-080611-enUS-01.tif]

    Figure 3-19 Time Synchronization

    Adjust the time sources in the Time Source 1and Time Source 2fields. If the DNP3 protocol is parameterized

    for a number of channels in the device, you can select this protocol for both sources.

  • 8/11/2019 Com Dnp Enus

    52/84

    Parameterizing in DIGSI 5

    3.9 Time Synchronization

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    52

    [ScTsrDNP-251110-enUS-01.tif]

    Figure 3-20 Setting the Time Sources

    If the time source in the device is set to DNP3, then the time synchronization can run through a DNP3 master.

    The time source is set in DIGSI 5 or on the device.

    In the DNP3 protocol, you have the possibility to execute time synchronization with local time or with UTC. The

    selection occurs in DIGSI 5 with the parameters designated for this. The time zones for the time synchroniza-tion parameterization and in the DNP3 protocol have to be identical if set to local.

    The SIPROTEC 5 device monitors the continuous reception of the time synchronization telegram. After expiry

    of the set time in Error display after:a time synchronization errormessage is generated. The faulty time in

    the device is also displayed. This time fault remains until a new time synchronization telegram is received.

    NOTE

    During parameterization, the time in Time synchronization requiredmust be greater than the synchronization

    interval of the DNP3 master. Siemens recommends a synchronization interval of 1 min. However, the master

    can also send the telegram every 5 min or 10 min. When setting the interval to 1 min, the time in the device is

    set to invalid if no synchronization telegram is received in 2 min. In the meantime, the device sets the clock via

    the internal quartz-crystal oscillator.

  • 8/11/2019 Com Dnp Enus

    53/84

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    53

    4 Communication Modules

    4.1 Overview 54

    4.2 Serial Communication Modules for Short Distances 59

    4.3 Ethernet Modules 64

    4.4 Configuration, Installation, Replacement 67

  • 8/11/2019 Com Dnp Enus

    54/84

    Communication Modules

    4.1 Overview

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    54

    4.1 Overview.

    SIPROTEC 5 devices can be ordered with factory-installed plug-in modules. The plug-in modules can also be

    installed and replaced in the SIPROTEC 5 devices afterwards. You do not have to open the device for this.

    NOTE

    The communication modules available for reordering are not preconfigured. Use DIGSI to carry out the func-tional adjustment for the desired protocol application.

    The communication modules can be installed in the base module and in the expansion module with the plug-

    in module assembly CB202. A maximum of 2 communication modules each can be installed. You can use only

    one CB202 in the device.

    The plug-in module assembly CB202 is a module with an integrated power supply.

    The plug-in module assembly CB202 communicates with the base module using a special connecting cable.

    This connecting cable (CAT 5 FTP patch cable) is always included in the scope of delivery of the CB202

    module or the devices with CB202 module and need not be ordered separately.

    Make sure that you route the communication lines separately from network circuits.

  • 8/11/2019 Com Dnp Enus

    55/84

    Communication Modules

    4.1 Overview

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    55

    [DwCM201P-030211-xxXX-01.tif]

    Figure 4-1 Plug-In Module Positions and Communication Connections in the Base Module

    (1) Time synchronization G

    (2) Plug-in module position E

    (3) Detached on-site operation panel H

    (4) Plug-in module position F(5) Integrated Ethernet interface J

    (6) Connection to the expansion module with CB202 module

    (7) Grounding terminal

  • 8/11/2019 Com Dnp Enus

    56/84

    Communication Modules

    4.1 Overview

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    56

    [DwLMNPPo-030211-xxXX-01.tif]

    Figure 4-2 Plug-In Module Positions and Communication Connections in the Expansion Module with

    CB202

    (1) 2-pole terminal to connect power supply

    (2) COM link L (connection to interface K of the base unit)

    (3) Plug-in module position M(4) Plug-in module position N

    (5) Plug-in module position P

    (6) Grounding terminal

    NOTE

    You cannot insert any communication module at plug-in module position M. The plug-in module position M is

    only intended for a measuring-transducer module.

    The following communication modules can be used for SIPROTEC 5: Serial modules

    Application: Communication to the substation automation technology via substation-control protocols

    Protection interface (only optical serial modules) for interfacing to external communication converters for

    short direct connections.

    2 different communication protocols or 2 different applications can be operated on serial modules with 2

    connections. The DNP3 protocol for the substation automation technology as well as a protection inter-

    face, for example, can be operated on a serial optical module for short distances with 2 connections.

    Assign the protocol application to the corresponding channel of the communication module with DIGSI 5.

  • 8/11/2019 Com Dnp Enus

    57/84

    Communication Modules

    4.1 Overview

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    57

    Ethernet Modules

    Application: Ethernet-based communication to the substation automation technology via substation-

    control protocols (for example, IEC 61850 and DNP3)

    - Secure communication to DIGSI 5

    - Communication between the devices (IEC 61850-GOOSE)

    - Synchrophasor protocol

    The modules can be operated with or without an integrated switch.

    Long-distance modules

    Application: Direct protection-interface communication over long distances using multimode or singlem-

    ode optical fibers.

    The designation of the modules corresponds to the following scheme, which is typically explained with the

    module USART-AB-1EL. The module designation consists of 3 blocks.

    You can find information on communication applications for the plug-in modules in the following tables.

    Table 4-1 Communication Applications and Plug-In Modules

    1. Block Type of module

    USART = Serial module for close or long range

    ETH = Ethernet module

    2. Block Unique code for the module in the device's product code

    The code consists of 2 letters.

    3. Block Number and physical design of the connections

    1 = 1. Connection/1st channel

    2 = 2nd connection/2nd channel

    EL = Electrical connection

    FO = Fiber-optic connection

    LD = Long-distance transmission

    Port or plug-in module

    Frontinterface

    PortG:Timesynchroniza

    tion

    PortJ:IntegratedEthernet

    Moduletype:USART-AB-1EL

    Moduletype:USART-AC-2EL

    Moduletype:USART-AD-1FO

    Moduletype:USART-AE-2FO

    Moduletype:ETH-BA-2E

    L

    Moduletype:ETH-BB-2FO

    Physical connection

    USB-A

    D-Sub 9 socket

    1 x electrical Ethernet 10/100 Mbit/s, RJ45

    1 x electrical serial RS485, RJ45

    2 x electrical serial RS485, RJ45

    1 x optical serial, 820 nm, ST connector, 1.5 km over

    62.5/125 m multimode optical fiber

    2 x optical serial, 820 nm, ST connector, 1.5 km over

    62.5/125 m multimode optical fiber

    2 x electrical Ethernet 10/100 Mbit/s, RJ45, 20 m

    2 x optical Ethernet 100 Mbit/s, 1300 nm, LC duplex plug,

    2 km over 50/125 m or 62.5/125 m multimode optical

    fiber

  • 8/11/2019 Com Dnp Enus

    58/84

    Communication Modules

    4.1 Overview

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    58

    NOTE

    The USARTand ETHplug-in module types may be used in slots Eand Fin the base module as well as in slots

    Nand Pin the CB202 expansion module. They are not intended for use in slot Min the CB202expansion

    module.

    Applications

    DIGSI 5 protocol X X X X

    IRIG-B, DCF77, highly accurate 1-s pulse X

    IEC 61850-8-1 server (incl. GOOSE, reporting to 6 cli-

    ents)

    X X

    IEC 61850-8-1 server (without GOOSE, reporting to 6 cli-

    ents)

    X

    IEC 60870-5-103 (expanded) X X X X

    DNP3 serial X X X X

    DNP3 over Ethernet X X

    Synchrophasor (IEEE C37.118 IP)1 X X

    Protection interface (Sync. HDLC, IEEE C37.94)2 X X

    Additional Ethernet Protocols and Services

    DHCP (automatic IP configuration), DCP X X X

    RSTP (Ethernet ring redundancy) X X

    SNTP (time synchronization over Ethernet) X X X

    SNMP V3 (network management protocol) X X

    1. Additional modules for the protection interface: see next table

    2. In process

    Port or plug-in module

    Frontinterface

    PortG:Timesynchronization

    PortJ:Integ

    ratedEthernet

    Moduletype

    :USART-AB-1EL

    Moduletype

    :USART-AC-2EL

    Moduletype

    :USART-AD-1FO

    Moduletype

    :USART-AE-2FO

    Moduletype

    :ETH-BA-2EL

    Moduletype

    :ETH-BB-2FO

    Physical connection

  • 8/11/2019 Com Dnp Enus

    59/84

    Communication Modules

    4.2 Serial Communication Modules for Short Distances

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    59

    4.2 Serial Communication Modules for Short Distances

    4.2.1 Special Features of the Serial Electrical Modules.

    The serial electrical modules are equipped with RJ45 connections. These are not Ethernet connections. The

    serial signals of the RS485 interface are routed to the RJ45 connections (see following figure).

    [DwRJ45Pb-030211-enUS-01.tif]

    Figure 4-3 RJ45 Terminals for the Serial Signals of the RS485 Interface

    Cabling Examples of Devices with Serial Electrical Modules

    Serial electrical RS485 connections of devices in the SIPROTEC 5 series can be cabled with low-cost Ethernet

    patch cables. Special bus cables and adaptors are not needed. Pay attention to the following note if you include

    devices from the SIPROTEC 4 series in the connection.

    NOTE

    The RS485 interface in devices of the SIPROTEC 4 series is a D-Sub 9 connection with connected terminating

    resistor.

    If you connect devices from the SIPROTEC 5 series with devices from the SIPROTEC 4 series, use a Y

    adaptor with the order designation 7XV5103-2BA00. Complete the connection on the last device with a terminal

    resistor. For the SIPROTEC 5 device, use a terminal resistor with the order designation RS485-Terminator

    7XV5103-5BA00.

    [DwSerMa1-030211-enUS-04.tif]

    Figure 4-4 Communication with a Single Master Using an RS485 Bus

  • 8/11/2019 Com Dnp Enus

    60/84

    Communication Modules

    4.2 Serial Communication Modules for Short Distances

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    60

    The above figure shows the cabling using the new RJ45 sockets in a simplified format. The serial RS485 bus

    can be extended by simply connecting Ethernet patch cables from device to device.

    [DwSerMa2-030211-enUS-05.tif]

    Figure 4-5 Redundant Communication with 2 Masters Using RS485 Bus (For Example, Redundant

    IEC 60870-5-103 Protocol)

    The above figure shows the use of both connections on one module for connecting the devices to 2 indepen-

    dent masters following the same principle as with a single master.

    Reorders

    When reordering serial communication modules, specify the product code for the physical version of themodule. The order configurator (IPC configurator) shows you which applications are capable of running on the

    module:

    Serial

    1-channel or 2-channel

    Electrical or optical

  • 8/11/2019 Com Dnp Enus

    61/84

    Communication Modules

    4.2 Serial Communication Modules for Short Distances

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    61

    4.2.2 USART-AB-1EL.

    4.2.3 USART-AC-2EL.

    Description Serial asynchronous communication module with one electrical interface

    Product code P1Zxxxxxxxxxx

    Figure

    [DwUSAAB1-040211-xxXX-01.tif]

    Connector type 2 x RJ45

    Baud rate 1.2 kbits/s to 115.2 kbits/s

    Protocol IEC 60870-5-103

    DNP3

    Description Serial asynchronous communication module with 2 independent electri-

    cal interfaces

    Product code P1Zxxxxxxxxxx

    Figure

    [DwUSAAC2-040211-xxXX-01.tif]

    Connector type 4 x RJ45

    Baud rate 1.2 kbits/s to 115.2 kbits/s

    For 1 or 2 protocols or applications

    (1 application per connection)

    IEC 60870-5-103

    DNP3

  • 8/11/2019 Com Dnp Enus

    62/84

    Communication Modules

    4.2 Serial Communication Modules for Short Distances

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    62

    4.2.4 USART-AD-1FO.

    Description Serial asynchronous or synchronous communication module with one in-

    dependent optical interface

    Product code P1Zxxxxxxxxxx

    Figure

    [DwUSAAD1-040211-xxXX-01.tif]

    Connector type 2 x ST

    Wavelength = 820 nm

    Baud rate Asynchronous: 1.2 kbits/s to 115.2 kbits/s

    Synchronous: 64 kBit/s to 2 Mbit/sFor 1 protocol or application IEC 60870-5-103

    DNP3

    Protection-interface communication

    Max. range 2 km when using a fiber-optic cable 62.5m/125m

    Transmit Power Minimum Typical Maximum

    50m/125m, NA1= 0.2 peak -19.8 dBm -15.8 dBm -12.8 dBm

    62.5m/125m, NA1= 0.275 peak -16.0 dBm -12.0 dBm -9.0 dBm

    Receiver sensitivity

    Optical power for high

    Optical power for low

    Maximum -24 dBm

    Minimum -40 dBm

    Optical budget Minimum 4.2 dB for 50m/125m, NA1= 0.2 peak

    Minimum 8.0 dB for 62.5 m/125m, NA1= 0.275 peak

    Path attenuation In the case of multimode optical fibers, you can expect a path at-

    tenuation of 3 dB/km

    Laser class 1 as per EN 60825-1/-2 When using fiber-optic cables 62.5m/125m and

    50m/125m

    Comment:1Numerical aperture (NA = sin (launch angle))

  • 8/11/2019 Com Dnp Enus

    63/84

  • 8/11/2019 Com Dnp Enus

    64/84

    Communication Modules

    4.3 Ethernet Modules

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    64

    4.3 Ethernet Modules

    4.3.1 Operation of Ethernet Modules.

    The Ethernet modules of the SIPROTEC 5 series can be operated optionally with or without integrated switch

    function. This applies for the electrical as well as the optical module. This function can be selected via the pa-rameterization. It is not necessary to make any indication in the order. The optical Ethernet modules are com-

    patible with the EN100 modules of the SIPROTEC 4 series. If the RSTP protocol is active the optical modules

    of the SIPROTEC 4 series and the SIPROTEC 5 series can be operated in a ring.

    When using SIPROTEC 4 devices with module firmware V4.0.5 and SIPROTEC 5 devices, the maximum

    allowable number of participants is 30 devices. When using SIPROTEC 4 devices with module firmware

    V4.0.7 and SIPROTEC 5 devices, the maximum allowable number of participants is 40 devices. When using

    SIPROTEC 5 devices, the maximum allowable number of participants is 40 devices.

    Figure 4-6shows operation of the Ethernet modules with integrated switch function. All devices of a station are

    shown which are connected to one another with optical fibers. The devices form optical rings. In addition, 2

    switches are used on the substation controller for the SICAM PAS. The 2 switches take the requirements for

    the redundancy into account.Additional participants with electrical interfaces can also be connected to the SICAM PAS (for example, the

    DIGSI 5 control PC). An external switch is sufficient. Optical communication modules are primarily used for this

    topology, as there can be substantial distances between the devices.

    If the Ethernet modules are installed in expansion modules with a CB202 PCB assembly, the power supply can

    be provided with an independent battery. The integrated switch can maintain its function when the device is

    switched off. The data are transmitted in optical and electric rings. This prevents opening of the ring. The ring

    continues to operate when 1 or more devices are switched off.

    [DwETH1Sw-030211-enUS-01.tif]

    Figure 4-6 Operation of Ethernet Modules with an Integrated Switch Function

  • 8/11/2019 Com Dnp Enus

    65/84

  • 8/11/2019 Com Dnp Enus

    66/84

  • 8/11/2019 Com Dnp Enus

    67/84

    Communication Modules

    4.4 Configuration, Installation, Replacement

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    67

    4.4 Configuration, Installation, Replacement

    4.4.1 Fasteners.

    The fasteners of the plug-in modules are shown in the following figure regarding the example of an installed

    module and an empty, covered slot.

    [DwStePos-030211-xxXX-01.tif]

    Figure 4-8 Fasteners

    (1) Fastening screw

    (2) Cut-out for prying out the modules

    (3) Plug-in module

    (4) Fastening screw

    (5) Cover plate

    4.4.2 Installation

    NOTE

    The modules available for reordering are not preconfigured. For communication modules, use DIGSI 5 to carry

    out the functional adjustment to the required protocol application.

  • 8/11/2019 Com Dnp Enus

    68/84

    Communication Modules

    4.4 Configuration, Installation, Replacement

    SIPROTEC 5 , Manual

    C53000-G5040-C006-2, Release 03.2012

    68

    Preparing Installation

    DANGER

    Danger due to live voltage when installing the plug-in modules.

    Noncompliance with the safety notes means that death or severe injuries will occur.

    Install plug-in modules on the electrically deactivated device only.

    CAUTION

    Exercise caution with laser beams of the optical plug-in modules.

    Noncompliance with the safety notes means that medium-severe or slight injuries can occur.

    Do not look directly into the optical fiber terminals of the active optical plug-in modules, not even with

    optical devices. The laser beams can damage the eyes.

    De-energize the device.

    NOTE

    Laser class 1 is adhered to in compliance with EN 60825-1 and EN 60825-2, in the case of 62.5m/125m

    optical fibers.

    In the case of a surface-mounted device with integrated on-site operation panel, remove the entire on-siteoperation panel.

    Undo the fastening screw and remove the cover plate from the plug-in module position.

    Installing the Plug-In Module

    Push in the plug-in module on the inner guide as far as it will go.

    Ensure that the EMC contact spring is seated correctly.

    Bolt down the plug-in module on the assembly frame to a torque of 0.4 Nm.

    Connect the leads to the terminals.

    Then check for secure attachment of the connectors.

    If necessary, fit the on-site operation panel again.

    Completing Installation

    Resume operation of the device.