CLIC CES Meeting 14 jan 2009
A resume table for fire safety in LHC, and a possible scheme for other machine – part
1CERN –SC Fabio Corsanego
From past meeting of 12 Nov 2008 : Proposed Structure for Fire Safety Report
INTRODUCTIVE NOTES• Reference Codes for Fire Prevention• Description of the facility from the fire Safety Point of View
DESIGN CONDITIONS:• Characteristics of the Occupants• Ability and Resources of the Fire Service• Special Hazards in case of Fire, and Emergency Plan• Fire Load
MEASURES TO PREVENT THE INSURGENCY OF A FIRE• Properties of the Combustible Materials• Protection against Electric Faults• Lightning Protection• Worksite Organization (fire permits etc, work coordination)
ESCAPE IN THE EVENT OF A FIRE• Escape Strategy• Type of Stairways and Access Ways• Internal evacuation pathways• Travel Distance to Reach an Exit• Doors• Access Control Locking• Guidance Signs for escape• Emergency Lighting• Evacuation Alarm• Communication Devices
PROTECTION AGAINST THE SPREAD OF FIRE BETWEEN COMPARTMENTS• Subdivision into Fire Compartments• Fire Resistance Class of Structural and Non-structural Elements Separating the Fire
Compartments:• Technical rooms on surface
FACILITIES FOR FIREFIGHT:• Access routes for the rescue service:• Fire gas ventilation;• Equipment for Manual Fire Fighting:• Communication Systems;
HEATING, VENTILATION AND AIR CONDITIONING (HVAC), and SMOKE EXTRACTION• General aspects common to the whole facility• Commands (stop and activation) for the ventilation and smoke extraction system• Fire protection construction of plant rooms and shafts• Protected Access Shaft• TUNNEL and Transfer line VENTILATION• Exepriment Hall Ventilation and Smoke Extraction
FIRE PROTECTION INSTALLATIONS• Automatic fire detection• Evacuation alarm system• Automatic Fire suppression Systems
CERN-LHC-Underground
CERN LHC Surface Blds
… …
Reference codes no specific constr. codeCern can negotiate internally safety criteria and its application
swiss and french codes
Description from fire point of view
Depth =100m Length =27.5 km 6 large halls of 10 to 40000 m3
Industrial services halls, spread on the surface
Introductive notes
CERN-LHC-Underground CERN LHC Surface Blds … …
Occupants: Trained employees and collaborators(visitors w. restrictions)
Same, with basic training
Ability and resources of fire services
Internal professional fire brigade ( ~2 immediate teams + delayed on call)
Other hazards than heat and smoke in case of fire
Long ways, Energy stored in magnets, condensers cryo fluids, pressure buildup, flammable, inert gases, irradiation, contamination
Cryo and flammable fluids, condensers, contamination, irradiation, inert gases
Emergency plan Intervention Scaling up agreements via swiss and france firefighers
same
Fire load Low in standard tunnels, mild in power stations, large in experiments halls
Mild as average, locally high due to oils and flammable gases
Design Conditions
CERN-LHC-Underground CERN LHC Surface Blds
… …
Properties of combustible materials
Most cables and plastic are fire retardants low smoke- derogations
same
Protection against electric faults
Standard electric rules- ad hoc solution for physics equipment
Standard electric rules
Lightning protection
na yes
Worksite organization
Fire permits, work coordination, etc
same
Measures to prevent the insurgency of a fire
CERN-LHC-Underground CERN LHC Surface Blds … …
Escape strategy Occupants shall self rescue as rescue teams have long access time
Same
Type of stairways and access ways
Vertical paths (Stairs and lifts are smoke tight, fire resistant, free of combustibles and pressurized) horizontal paths are exposed to smoke and fire
Vertical paths are Smoke tight for multi floors buildings.Horizontal paths are exposed to smoke and fire
Travel distance to reach an exit
3 km for tunnels; few tens of meters for halls
30- 40 m to reach a different compartments with blind corridor <15m
Doors Sector doors are flat steel. Doors between experiment and caverns, and vertical ways are fire rated 2 hr
Fire doors are in most cases no more than 15 minutes
Access Control Locking
Yes. Forcible for evac w. interlock. In a few cases (CNGS) radioprotection inhibited usability of exits
Same
Escape in the event of a fire
CERN-LHC-Underground CERN LHC Surface Blds … …
Guidance signs for escape
Fluorescent panels every 30 m Fluorescent panels
Emergency lighting
emergency network. Tunnels have light every 30 m. Halls have lights spread as needed
same
Evacuation Alarm
Yes . Activated manually or remotely by control room
Communication devices
Phones. Secured point to point (red) phones.Mobile phone network.Radio FM repeaters for Fire brigadeExperiment may implement public address systems
Escape in the event of a fire (continued)
T.B. Continued with remaining chapters as described in last CES meeting.