class ii transformer 250va, 500va, 1000va, 1400va (4 x ... · fits within the standard rail...

28
This document is protected by Copyright. The design of any article recorded in this document is protected by design right and the information contained in the document is confidential. The document may not be copied. Any design may not be reproduced and the information contained in the document may not be used or disclosed except with the prior written permission of and in the manner permitted by the proprietors, FT Transformers LTD CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X OUTPUT) & 2000VA OPERATION & MAINTENANCE MANUAL Document Number: FT-O&M-DOC-05765 Revision. Version: 0.5 Release Status: FINAL Date: 16/07/2013 Name Job Title Signature Date Author R Bradley General Manager Copy Number: This document is controlled by FT Transformers. Any paper copy of this document must be assumed to be uncontrolled.

Upload: others

Post on 01-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

This document is protected by Copyright. The design of any article recorded in this document is protected by design right and the informationcontained in the document is confidential. The document may not be copied. Any design may not be reproduced and the information contained in thedocument may not be used or disclosed except with the prior written permission of and in the manner permitted by the proprietors, FT TransformersLTD

CLASS II TRANSFORMER

250VA, 500VA, 1000VA, 1400VA (4 X OUTPUT) &2000VA

OPERATION & MAINTENANCE MANUAL

Document Number: FT-O&M-DOC-05765

Revision. Version: 0.5

Release Status: FINAL

Date: 16/07/2013

Name Job Title Signature Date

Author R Bradley General Manager

Copy Number:

This document is controlled by FT Transformers. Any paper copy of this document must be assumed to beuncontrolled.

Page 2: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 2 of 27

CHANGE HISTORY

Revision Author Date ReleaseStatus

ECOReference

01 R Bradley DRAFT

02 R Bradley DRAFT

03 R Bradley DRAFT

04 R Bradley FINAL

05 R Bradley FINAL

Page 3: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 3 of 27

CONTENTS

Section Name PageCHANGE HISTORY ............................................................................................. 2

CONTENTS 3

REFERENCED MATERIAL AND STANDARDS 4

ABBREVIATIONS 5

1 INTRODUCTION 61.1 Purpose.................................................................................................... 61.2 Audience .................................................................................................. 61.3 Product Description.................................................................................... 61.4 Product Operation...................................................................................... 61.5 Contact Details.......................................................................................... 81.6 Comercial Conditions.................................................................................. 8

1.6.1 Warranty ........................................................................................... 81.6.2 Quality Assurance ............................................................................... 9

1.7 Asset Management .................................................................................... 9

2 SAFETY 102.1 General ...................................................................................................10

2.1.1 Manual Handling ................................................................................102.1.2 Rules For Electrical Safety ...................................................................102.1.3 Suitable Tools....................................................................................10

3 INSTALLATION AND COMMISSIONING 113.1.1 Delivery and Transportation ................................................................113.1.2 Installation........................................................................................113.1.3 Cables and Cable Connection...............................................................133.1.4 Commissioning ..................................................................................133.1.5 Voltage Adjustment............................................................................143.1.6 Energisation Of Equipment ..................................................................16

4 MAINTENANCE 174.1.1 Routine and Preventative Maintenance..................................................174.1.2 Recommended Spare Parts .................................................................174.1.3 Onsite Testing Procedure ....................................................................17

4.2 Training and Competence ..........................................................................174.3 Disposal ..................................................................................................17

5 TECHNICAL DATA 18

6 REPAIR PROCEDURE 20

Appendix A – General Arrangement 21

Appendix B – Transformer Connection Plates 22

Page 4: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 4 of 27

Referenced Material and Standards

The following source material was used:

The following documents in italics to be revised for FT document numbers

Document / Standard Name

[1] NR/L2/SIG/300007, Product Specification for power Transformersfor Signalling Systems

[2] FT Declaration of Conformity

[3] NR/L2/ELP/27410, Specification for Class II based SignallingSystems

[4] NR/L2/ELP/27409, Product Specification for Functional Supplypoints (FSP)

[5] NR/SP/ELP/27242, Specification of Low Voltage ElectricalInstallations on Railway Premises

[6] NR/SP/ELP/27243, Specification for Signalling Power Supplies

[7] NR/SP/ELP/27244, Guidance for Signalling Power Supplies

[8] NR/SP/ELP/27247, Guidance for Low Voltage ElectricalInstallations on Railway Premises

[9] NR/GN/ELP/27310, Management of Signalling Power Supplies

[10] GI/RT7017, Signalling & Safety Related TelecommunicationsPower Supplies and Circuits

[11] GI/GN7517, Guidance on Signalling and Safety RelatedTelecomms and Power Supplies and Circuits

[12] BS 7671, Requirements for Electrical Installations: IEE WiringRegulations (17th Edition)

[13] BS EN 50122-1, Railway Applications – Fixed Installations

[14] BS EN 50272 - 2, Railway Applications – Fixed Installations

[15] BS EN 60664-1, Insulation Coordination for Equipment WithinLow-voltage Systems - Part 1

[16] BS EN 61180-1, High-voltage TestTechniques for low-voltageequipment - Part 1

[17] SAM1290, Impulse Test of A 700V transformer To BritishStandard BS EN 50124

[18] BR SM 440 – Apparatus Case Rack layouts

[19] EaWR, Electricity at Work Regulations 1989

Websites www.ft-transformers.co.ukwww.networkrail.co.ukwww.hse.gov.uk

Page 5: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 5 of 27

Abbreviations

AC Alternating Current

CPC Circuit Protective Conductor

CSA Cross Sectional Area

DC Direct Current

DNO Distribution Network Operator

E&P Electrification and Plant

EaWR Electricity at Work Regulations

FLC Full Load Current

FSP Functional Supply Point

GRIP Guide to Railway Investment Projects

IEEE Institute of Electrical & Electronics Engineers

LSF Low Smoke and Fume

LSZH Low Smoke Zero Halogen

MET Main Earth Terminal

N.I.C.E.I.C National Inspection Council for Electrical Installation Contracting

NR Network Rail

O&M Operation and Maintenance

PF Power Factor

PSP Principle Supply Point

PVC Polyvinyl Chloride

REB Relocatable Equipment Building

SWA Steel Wire Armoured

THD Total Harmonic Distortion

TP&N Three Phase and Neutral

VA Volt-Amps (Unit for Apparent Power)

XLPE Cross-Linked Polyethylene

Page 6: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 6 of 27

1 INTRODUCTION

1.1 Purpose

This Operation and Maintenance manual is for the Class II Hybrid Functional SupplyPoint (FSP) transformers in the range:

250VA

500VA

1000VA

1400VA (4x output)

2000VA

These are to be used within Class II Signalling Power Distribution Systems in line withNR/L2/ELP/27410, Specification for Class II based Signalling Systems.

1.2 Audience

The intended audience for this operation and maintenance manual are all authorisedand competent persons involved in, but not limited to, designers, installers, assetmanagers and maintainers.

1.3 Product Description

KEY FEATURES:

Double Insulated primary side protection in-line with NR/L2/SIG/30007,Product Specification for power Transformers for Signalling Systems (note:100VA units have double insulated primary and secondary).

4 No outputs at 350VA each (1400VA type only)

Inrush equal to the full load current i.e. 1 x FLC

Patented spray on covering technique for the FT coating to provide a furtherlevel of electrical and corrosive protection and future proof the unit.

Fits within the standard Rail apparatus (location) case, REB (RelocatableEquipment Building) and rack frame to BR-SM-440

THIS PRODUCT IS A REPLACEMENT FOR LEGACY TRANSFORMERS TOBR924A

THIS PRODUCT CAN BE USED AS A CLASS I REPLACEMENT

THIS PRODUCT IS NOT SUITABLE FOR USE IN TUNNELS

1.4 Product Operation

The transformers are designed and built to be supplied from a two wire 650VAC ( +/-10% ) supply at a nominal frequency of 50hZ ( +/-4 to 6% ).

The transformers are designed and built to supply 110V (+/- the accepted NetworkRail tap settings) at a nominal frequency of 50hZ

Page 7: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 7 of 27

Figure 1 – Class II transformer common details

Figure 2 – Transformer I.D. Badge

50364 XXXXXX

0-10-25-600-650-700 V 50 Hz1 PH

F

4X 350VA0-5-10-110-120-140 V

NR/L2/SIG/30007 Class II Hybrid

XXXXX / 1 2013

40kg

YEAR

INS CLASS

PADS No.DESIGN

INPUT

OUTPUT

SPEC

SERIAL No.

[email protected]

FT TRANSFORMERS LIMITEDTEL XXXXXXXXXXXXXwww.ft.transformers.co.uk

2x Built inhandles

4 x vent louvers

12x durable nylonbolts and washers

Warning Labels(Top and Front)

2 x holes cut outeither side diameter

26MM for Primarycable connection

2 x holes cut outeither side diameter

26MM forSecondary cable

connection

Mounting slots

Page 8: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 8 of 27

Figure 3 – Warning Label

1.5 Contact Details

Address: FT Transformers Ltd

Unit 7 Cyclo Works,

Lifford Lane,

Kings Norton,

Birmingham,

B30 3DY

Telephone: +44 (0) 121 451 3204

Facsimile: +44 (0) 121 433 4577

Email: [email protected]

1.6 Comercial Conditions

1.6.1 Warranty

DOUBLEINSULATEDEQUIPMENT

INSIDE

Page 9: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 9 of 27

We offer a standard warranty period of the equipment procured and supplied by FTTransformers 12 months from putting into service. However FT Transformers will notaccept liability for any costs incurred by others. Extended warranty is available atextra cost subject to agreement.

1.6.2 Quality Assurance

All contracts employ the Company Quality Assurance System, which complies with therequirements of ISO9001 and has been independently assessed by Lloyd's RegisteredQuality Assurance

1.7 Asset Management

All units have a unique number which is completely traceable as required by BSI 9001.This number can be aide to any asset management system for a life log of the unit.

Page 10: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 10 of 27

2 SAFETY

2.1 General

Personal protective equipment PPE shall be in-line with Network Rail and groupstandards. All persons are to make an assessment of the required level of PPE in-linewith authorised site requirements.

The Nominate Competent person should do risk assessments and Method statementbefore any electrical installation is undertaken.

2.1.1 Manual Handling

The manual handling procedures in section 3.1.1 ‘Delivery and Transportation’ of thisdocument should be followed together with ‘Manual Handling Operations Regulations1992 (as amended)’.

2.1.2 Rules For Electrical Safety

The Low Voltage Directive - ‘Guidelines On The Application Of directive 2006/95/EC’,regards the voltage of the signalling power system as ‘low’ but ‘SUFFICIENT TO KILL’.

Assume all equipment is live until proven dead

The rules of electrical isolation within BS7671 and best practise should be adhered tothrough out by ‘Authorised Nominate Competent’ persons.

Network Rail Safety Procedures should be followed throughout for permissionsrequired for isolation and safe disconntection of signalling supplies.

If required the appropriate Warning and /or Danger notices must be displayed

2.1.3 Suitable Tools

All tools including personal tools must be suitable for the operation for which they arebeing used and must be in good condition.

Spanner for M6 hex bolt

Philips screw driver

Flathead screw driver

Figure 4 – Example tools

or + +

Page 11: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 11 of 27

3 INSTALLATION AND COMMISSIONING

Although outside the scope of this manual, electrical Inspection and testing must be inaccordance with BS 7671 17th edition “Requirements for Electrical Installations” andGuidance Note 3, and in accordance with N.I.C.E.I.C testing guidelines / standards.

3.1.1 Delivery and Transportation

The transformer(s) will arrive at the arranged delivery address intact. If there isdamage to the transformers of any kind please contact FT Transformers Ltd.

When delivering to the final site installation the transformer(s) should be fixedsecurely within the vehicle for transportation. It is advised that the transformer(s) andGLS-100 R coating be inspected before installation.

During on loading and offloading it is advised that two or more competent personmanually lift the transformer in place. Note the Health and Safety Executive ManualHandling Charts (MAC) assessment is attached in Appendix B for reference and can beused to aid any manual handling risk assessment. However, this does not invalidatecompetent person(s) from their responsibilities. The Manual Handling OperationsRegulations 1992 (as amended) shall be adhered to in this regard. FT transformersadvise the use of a mechanical lifting aid such as a stacker for weights 40kg and belowas shown in figure 5

3.1.2 Installation

Before installation commences the installer must carry out a risk assessment. Themounting rails, brackets or other such arrangement must be assessed for its capabilityof bearing the transformer weight.

It is advised that the transformer be mounted at the lower portion of any cubicle orrack to reduce the risk of stress on any such cubicle or rack.

Although the FT-100 R coating is extremely durable, care must be taken not to scratchit. If damage does arise, please see Section 7 Repair Procedure for FT-100 R

The transformer must be mounted in the orientation shown in figure 3 below with thefixing holes to the bottom. The transformer must be securely fixed to the mountingrails, brackets or other such arrangement capable of bearing the transformer load. ThePlastic nuts and bolts supplied must be used ONLY. If these are lost, please contact FTTransformers and arrangements will be made to supply replacements. Otherwise,plastic nuts and bolts can be readily obtained from the standard electrical wholesalers.

To gain access to the cable connection plate the method followed in figures 6 & 7should be followed.

1

2

3

Figure 5 – Use of a Stacker

Once the stacker is in positionand the appropriate adjustmentmade to the tray height (1) thetransformer(s) can be slid (3)off the tray and into amaintenance vehicle or trailer(2) for removal/ transport tosite.

Page 12: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 12 of 27

Figure 3 - Mounting in Place

Figure 6 – Tightening mounting bolts and removing cable faceplate

1 1

2 2

33

12

2 22

Rack or other loadbearing structure for

transformer fixing

Page 13: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 13 of 27

Figure 7 –Cable connection faceplate

3.1.3 Cables and Cable Connection

All cabling should meet the requirements of NR/L2/ELP/27410. For connectionfaceplate see Appendix B

POWER CABLES

Only Class II enhanced cable shall be used on the 650V primary side of thetransformer as part of a Class II signalling power distribution system and required byNR/L2/ELP/27410.

NOTE: CABLES MUST NOT BE SWA!

The signalling power distribution cable is connected to the transformer with terminalblocks, which are designed to accept a cable size between 0.5-mm.

The supply is connected to the transformer with KS terminal Blocks which are touchproof and designed to accept a cable size between 0.5-2.5mm.

110V cables on the secondary side shall be the standards signalling cable and/or PVCcable as required by the installation scheme.

EARTH CABLES

All earthing and bonding on the transformer to any such, installation, which it is fixed,shall comply with BS 50122-1, BS 7430 and BS 7671: The requirements for ElectricalInstallations.

The functional earth terminal block which are designed to accept a cable size ofbetween 0.5-10mm

3.1.4 Commissioning

Before electrical energisation takes place, make sure that all ventilation louvers areclear of any obstruction.

Cable connectionplate (note the

example shown isfor the 1400VA

multi-output unit

Page 14: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 14 of 27

NOTE: ONLY PARALLEL OUTPUTS 1&2 TOGETHER AND OUTPUTS 3&4 TOGETHER.

DO NOT PARALLEL ALL FOUR OUTPUTS TOGETHER!

Visually check that the coating is undamaged. If the coating is damaged on theoutside but is undamaged internally the transformer is good for use. No maintenanceis required and there is no need to change the transformer under these circumstances.See Repair Procedure

3.1.5 Voltage Adjustment

The transformer terminals should be set to the nominal voltage T0/650v and t0/t110v

Under load conditions, monitor the input voltages for a few minutes and obtain anaverage value.

Disconnect the incoming supply and use the table below to set the primary taps

Input voltages obtainable associated tapsetting

Output voltages obtainable and ossociatedtap setting ( 650v primary nominal )

Voltage In Primary Taps Secondary Taps Voltage Out

575v T25 T600 t10 t110 100V

590v T10 T600 t5 t110 105V

600v T0 T600 t0 t110 110V

625v T25 T600 t10 t120 110V

640v T10 T600 t5 t120 115V

650v T0 T600 t0 t120 120V

675v T25 T600 t10 t140 130V

690v T10 T600 t5 t140 135V

700v T0 T600 t0 t140 140V

Under load, monitor the output voltages and adjust the output taps to obtain approx108-112 volts

Page 15: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 15 of 27

Figure 8a - Transformer Wiring Schematic with voltage taps

T0

t5t10

t110t120

T10

T600T650T700

Output Ratings:

250VA, 500VA,

1000VA, 2000VA

T25

t140

t0

FUNCTIONAL EARTH

Page 16: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 16 of 27

Figure 8b - Transformer Wiring Schematic with voltage taps for 1.4kVA

3.1.6 Energisation Of Equipment

Wherever possible electrical equipment should not be connected to or energised untilall work on that equipment and associated circuits is complete. The first energisationof LV electrical equipment will be authorised by the Authorised Nominated CompetantPerson.

Once the electrical supply to LV electrical equipment has been made Live a DangerLive notice, must be attached to the LV electrical equipment to prevent interferencewhere danger may arise. This notice should remain in place until all envisagedinstallation, extension or modification work on the LV electrical equipment or systems,which the LV electrical equipment forms a part of, is complete.

Organisational Policies and procedures should be adhered to.

T0

t5t10

t110t120

T10

T600T650T700

O/P 1 = 350VA

T25

t140

t0

FUNCTIONAL EARTH

t5t10

t110t120

O/P 2 = 350VA

t140

t0

t5t10

t110t120

O/P 3 = 350VA

t140

t0

t5t10

t110t120

O/P 4 = 350VA

t140

t0

NOTE: ONLY PARALLEL OUTPUTS1&2 TOGETHER AND OUTPUTS 3&4TOGETHER.DO NOT PARALLEL ALL FOUROUTPUTS TOGETHER!

Page 17: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 17 of 27

4 MAINTENANCE

Ensure that all ventilation louvers are clear.

The maintenance schedule is set by Network Rail under its maintenance schedulingprocedures and control of asset register information ( NR/SP/SIG/10661 ) SignallingMaintenance Task Intervals

A Class II Hybrid transformer must only be replaced with a Class II Hybrid or fullyClass II transformer of equal specification. NEVER replace a Class II Hybridtransformer with a Class I transformer.

Each transformers is provided with a unique I.D. located on the transformer label, thisshould be quoted when the unit is examined for maintenance.

4.1.1 Routine and Preventative Maintenance

FT Transformers advise that routine maintenance be carried so as not to shorten thelife expectancy of the transformers. This may also include preventative maintenanceas part of the asset management.

4.1.2 Recommended Spare Parts

No spare parts are required for these transformers

4.1.3 Onsite Testing Procedure

1. Disconnect the incoming supply and secondary connections.

2. Using a 500v megger check insulation resistance ( primary to functionalearth )

3. ( Secondary to Functional Earth ) ( Primary to Secondary ) All values to begreater than 100M ohms.

4. Check Input and Output winding resistances with the values on data sheet atthe rear of this manual.

5. Reconnect the incoming supply to Primary Terminals.

6. Check the incoming supply voltage, adjust primary taps if required using thetable in 3.1.5.

7. Check secondary voltages, voltages should be within 10% of the terminalvoltage.

8. Reconnect the secondary and check the load current

9. The load current should not exceed the values shown on the data sheets

10.Check output tap voltages, voltages should be within 2% of the terminalvoltage, adjust output taps if required.

4.2 Training and Competence

All works involving the installation, commissioning, testing, and routine maintenanceshall be carried out by persons competent, trained and authorised to do so to NetworkRail, Group and British Standards.

4.3 Disposal

Equipment may be returned to FT Transformers Ltd or a waste disposal organisationcertified but not to limited to the WEE Directive 2002/96/EG

Page 18: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 18 of 27

5 TECHNICAL DATA

RATING CONTINUOUS 250VA 500VA 1000VA 1400VA 2000VAIMTERMITENT RATING 15MINSIN EACH HOUR 300VA 600VA 1200VA 1680VA 2400VA

DESIGN NUMBER 50361 50362 50363 50364 50365

PRIMARY WINDINGCLASSIFICATION

CLASS 11 CLASS 11 CLASS 11 CLASS 11 CLASS 11

SECONDARY WINDINGCLASSIFICATION

CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1

PRIMARY VOLTAGE 0-10-25-600-650-700V

0-10-25-600-650-700v

0-10-25-600-650-700v

0-10-25-600-650-700v

0-10-25-600-650-700v

FREQUENCY (Hz) 50/60 50/60 50/60 50/60 50/60

3PH OR 1PH 1PH 1PH 1PH 1PH 1PH

INSULATION CLASS F F F F F

RECOMMENDED PRIMARY FUSEPROTECTION

2A BS88 TYPEGG 690VRATED OR IEC60269

2A BS88 TYPEGG 690VRATED ORIEC 60269

4A BS88 TYPEGG 690VRATED ORIEC 60269

6A BS88 TYPEGG 690VRATED ORIEC 60269

6A BS88TYPE GG690V RATEDOR IEC 60269

EFFICIENCY` 92% 94% 95.% 95.2% 95%

PEAK INRUSH X FLC 3.1 1.5 1 1 1

PEAK INRUSH CURRENT 1.5A 1.15A 1.53A 2.15A 3.07AI^t OVER FIRST TWO CYCLES40mS 0.09 0.05 0.09 0.18 0.38IMPEDANCE (ALLSECONDARY’S SHORTCIRCUIT)MEASURED VALUE AT 20°C

2.43% 2.12% 2.88% 2.63% 3.43%

IMPEDANCE MAX 5% MAX 5% MAX 5% MAX 5% MAX 5%

SECONDARY VOLTAGE

0-5-10-110-120-140

0-5-10-110-120-140

0-5-10-110-120-140

4 X 0-5-10-110-120-140

0-5-10-110-120-140

RATING AT EACH TERMINALOUTPUT

250VA 500VA 1000VA 4 x @ 350VAEACH

2000VA

DURATION OF PROSPECTIVEFAULT CURRENT FOR EACHSEC

1 SEC 1 SEC 1 SEC 1 SEC 1 SEC

PROSPECTIVE FAULT CURRENTON SECONDARY(one winding short circuit)

77.57A 185.53A 286.78A 98.2A 486.14A

REGULATION FROM NO LOADAT FULL RATING OFTRANSFORMER

2.9% 2.2% 2.85% 2.8% 3.3%

INSULATION RESISTANCE @500VDC. BOTH WINDINGS TOCORE >51G OHMS >51G OHMS >51G OHMS >51G OHMS >51G OHMS

INSULATION RESISTANCE @500VDC. WINDING TOWINDING >51G OHMS >51G OHMS >51G OHMS >51G OHMS >51G OHMS

Page 19: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 19 of 27

DIELECTRIC STRENGTHPRIMARY TO CORE 5.2kV 5.2kV 5.2kV 5.2kV 5.2kV

DIELECTRIC STRENGTHSECONDARY TO CORE 2.8kV 2.8kV 2.8kV 2.8kV 2.8kV

DIELECTRIC STRENGTHPRIMARY TO SECONDARY 5.2kV 5.2kV 5.2kV 5.2kV 5.2kV

IMPULSE WITSTAND PRIMARYWINDING 8kV 8kV 8kV 8kV 8kV

WINDING INDUCTANCE @650V

35mH 30.0mH 19mH *16.0mH 12.3mH

WINDING INDUCTANCE @110V

1mH 0.86mH 0.54mH *0.46mH 0.35mH

PRIMARY WINDINGRESISTANCE @20 DEG C

18.50 ohms 9.00 ohms 7.70 ohms 5.70 ohms 4.80 ohms

SECONDARY WINDINGRESISTANCE @20 DEG C

1.25 ohmS 0.45 ohms 0.26 ohms 0.62 ohmsEach coil

0.10 ohms

X/R RATIO 0.35 0.73 0.71 0.77 0.80

OPERATIONAL TEMPERATURERANGE

-20C TO 60C -20C TO 60C -20C TO 60C -20C TO 60C -20C TO 60C

HUMIDITY UP TO 100%RH

UP TO 100%RH

UP TO 100%RH

UP TO 100%RH

UP TO 100%RH

PRIMARY TERMINALSSCREW CLAMP0.5mm TO2.5mm

SCREWCLAMP0.5mm TO2.5mm

SCREWCLAMP0.5mm TO2.5mm

SCREWCLAMP0.5mm TO2.5mm

SCREWCLAMP0.5mm TO2.5mm

DIMENSIONSW x H x D279 x 289 x210

W x H x D279 x 289 x210

W x H x D315 x 289 x250

W x H x D325 x 289 x268

W x H x D325 x 289 x268

WEIGHT 20kG 35Kg 40Kg 40.3KG 50kg

* NOTE:

1400VA UNIT THE INDUCTANCE VALUES ARE WHEN ALL 4 WINDINGS ARESHORT CIRCUITED

Page 20: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 20 of 27

6 REPAIR PROCEDURE

A repair procedure is not required for the FT Class II transformers.

The transformer housing has been flash tested to 10kV on the inside and outside, atotal of 20kV. Therefore integrity is maintained even if there is damage to one side ofthe housing. It does need to be replaced in this instance.

If there is damage internal and exernally to the housing then the transformer must besent back to FT transformer Ltd for reconditioning or replacement.

The transformer must only be replaced with a Class II hybrid or better transformer

Page 21: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 21 of 27

Appendix A – General Arrangement

Page 22: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

TO ACCESS PLATEWARNING LABEL FIXED

BOLTS8 x M6 NYLON

TO ACCESS PLATEI.D. LABEL FIXED

HOUSING LID

A

13

DC

289

J

12

E

I

GH F

LK

OP

EQUIPMENT INSIDEDOUBLE INSULATED

EQUIPMENT INSIDEDOUBLE INSULATED

T700

T650

T600

T25

T10

T0

t5

t0

t10

t110

t120

t140

250VA, 500VA, 1000VA, 2000VA,OUTPUT RATINGS:

FUNCTIONAL EARTH

T700

T650

T600

T25

T10

T0

t5

t0

t10

t110

t120

t140

FUNCTIONAL EARTH

WDG 4 = 350VA

t5

t0

t10

t110

t120

t140

WDG 3 = 350VA

t5

t0

t10

t110

t120

t140

WDG 2 = 350VA

t5

t0

t10

t110

t120

t140

WDG 1 = 350VA

OUTPUT RATING 1400VA

EQUIPMENT

INSULATED

DOUBLE

WARNING

CLASS II EQUIPMENT

REPLACE EXISTING OR FAULTY

EQUIPMENT SHALL BE USED TO

ONLY APPROVED CLASS II650 VOLTS

DANGER

EQUIPMENT

HEAVYWARNING

USE

MANUAL BEFORE

APPLICATION

REFER TO

BEFORE OPENING

ISOLATE 650V SUPPLY ELSEWHERE

www.ft-transformers.co.uk

TEL +44 XXXX XXX XXXX

FT TRANSFORMERS LIMITED

DESIGN

INPUT

OUTPUT

SPEC

SERIAL No.

50364

0-10-25-600-650-700 V

0-5-10-110-120-140 V

NR/L2/SIG/30007

XXXXX / 1

PADS No.

1 PH

4X 350 VA

50 Hz

kg

XXXXXX

F

YEAR

INS CLASS

2013

EQUIPMENT

INSULATED

DOUBLE

WARNING

CLASS II EQUIPMENT

REPLACE EXISTING OR FAULTY

EQUIPMENT SHALL BE USED TO

ONLY APPROVED CLASS II650 VOLTS

DANGER

EQUIPMENT

HEAVYWARNING

USE

MANUAL BEFORE

APPLICATION

REFER TO

BEFORE OPENING

ISOLATE 650V SUPPLY ELSEWHERE

Legend/Notes

Signed

Signed

Designed DateSigned

Drawn

Checked

Approved

Date

Date

Date

Alternative Reference

Drawing Number Revision

of

Sheet

Drawing Title

Contractor(s)

Scale(s) ELR & Mileage

Project

Rev Date Description of Revisions Drawn Chkd Appr

Status

Signed

Dra

win

g N

um

ber

Sheet Size A2 420 x 594

A B C D E F G H I J K L M N O P

279

315

210 100 203 283 165 112 187 204

250 138 240 282 140 123 230 210

181

217

55 46 35 15 41 19

325 268 138 257 287 140 129 235 210 217

52 70 34 22 30 28

57 70 32 20 30 30

RATING

250VA & 500VA

1000VA

1400VA & 2000VA

TRANSFORMER MEASUREMENTS

NOT TO BE USED IN TUNNELS

FOR BR924A TRANSFORMERSTHIS PRODUCT IS A DIRECT REPLACEMENT

RANGE DETAILS

CLASS II HYBRID TRANSFORMER

.

Designed Name

Drawn Name

Checked Name

Approved Name

NTS .

Drawing No.

FT-DRG-CL2-05765 1 1

Rev

Date

Date

Date

Date

Rev Date Revision Description Drn Chk

Status

Designed Name

Drawn Name

Checked Name

Approved Name

App

GrizzleA
Text Box
L
GrizzleA
Text Box
M
GrizzleA
Text Box
N
GrizzleA
Text Box
B
GrizzleA
Text Box
O/P
GrizzleA
Text Box
O/P
GrizzleA
Text Box
O/P
GrizzleA
Text Box
O/P
GrizzleA
Text Box
ONLY PARALLEL OUTPUT 1&2 AND OUTPUT 3&4 DO NOT PARALLEL ALL FOUR OUTPUTS
GrizzleA
Rectangle
Page 23: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 22 of 27

Appendix B – Transformer Connection Plates

Page 24: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

This document is protected by Copyright. The design of any article recorded in this document is protected by design right and the information contained in the document is confidential. The document may not be copied. Any design may notbe reproduced and the information contained in the document may not be used or disclosed except with the prior written permission of and in the manner permitted by the proprietors, FT Transformers LTD

250VA

FUNCTIONAL EARTH

Class II protectivecover – primary

connection

t0

t5V

t10V

t110V

t120V

t140V

ISOLATE 650V

ISOLATE 650V

T0

T10V

T25V

T0 T10V

T25V

Page 25: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

This document is protected by Copyright. The design of any article recorded in this document is protected by design right and the information contained in the document is confidential. The document may not be copied. Any design may notbe reproduced and the information contained in the document may not be used or disclosed except with the prior written permission of and in the manner permitted by the proprietors, FT Transformers LTD

500VA

FUNCTIONAL EARTH

Class II protectivecover – primary

connection

t0

t5V

t10V

t110V

t120V

t140V

ISOLATE 650V

ISOLATE 650V

T0

T10V

T25V

T0 T10V

T25V

Page 26: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 25 of 27

1kVA

FUNCTIONAL EARTH

Class II protectivecover – primary

connection

t0

t5V

t10V

t110V

t120V

t140V

ISOLATE 650V

ISOLATE 650V

T0

T10V

T25V

T0 T10V

T25V

Page 27: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 26 of 27

1.4kVA

FUNCTIONAL EARTH

Class II protectivecover – primary

connection

t0

t5V

t10V

t110V

t120V

t140V

t0

t5V

t10V

t110V

t120V

t140V

t0

t5V

t10V

t110V

t120V

t140V

Secondary connectionx 4

Primary supplycable tie

T600

T650

V

T700

V 5V

t0

t5V

t10V

t110V

t120V

t140V

T0

T10V

T25V

ISOLATE 650V ISOLATE 650V

ONLY PARALLEL OUTPUT 1&2 AND OUTPUT 3&4 DO NOT PARALLEL ALL FOUR OUTPUTS

O/P

2 3

50VA

O/P 1 350VA

O/P 2 350VA

O/P

1 3

50VA

Page 28: CLASS II TRANSFORMER 250VA, 500VA, 1000VA, 1400VA (4 X ... · Fits within the standard Rail apparatus (location) case, REB (Relocatable Equipment Building) and rack frame to BR-SM-440

CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5

DATE: 16/07/2013

Page 27 of 27

2kVA

FUNCTIONAL EARTH

Class II protectivecover – primary

connection

t0

t5V

t10V

t110V

t120V

t140V

ISOLATE 650V

ISOLATE 650V

T0

T10V

T25V

T0 T10V

T25V