class ii transformer 250va, 500va, 1000va, 1400va (4 x ... · fits within the standard rail...
TRANSCRIPT
This document is protected by Copyright. The design of any article recorded in this document is protected by design right and the informationcontained in the document is confidential. The document may not be copied. Any design may not be reproduced and the information contained in thedocument may not be used or disclosed except with the prior written permission of and in the manner permitted by the proprietors, FT TransformersLTD
CLASS II TRANSFORMER
250VA, 500VA, 1000VA, 1400VA (4 X OUTPUT) &2000VA
OPERATION & MAINTENANCE MANUAL
Document Number: FT-O&M-DOC-05765
Revision. Version: 0.5
Release Status: FINAL
Date: 16/07/2013
Name Job Title Signature Date
Author R Bradley General Manager
Copy Number:
This document is controlled by FT Transformers. Any paper copy of this document must be assumed to beuncontrolled.
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 2 of 27
CHANGE HISTORY
Revision Author Date ReleaseStatus
ECOReference
01 R Bradley DRAFT
02 R Bradley DRAFT
03 R Bradley DRAFT
04 R Bradley FINAL
05 R Bradley FINAL
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 3 of 27
CONTENTS
Section Name PageCHANGE HISTORY ............................................................................................. 2
CONTENTS 3
REFERENCED MATERIAL AND STANDARDS 4
ABBREVIATIONS 5
1 INTRODUCTION 61.1 Purpose.................................................................................................... 61.2 Audience .................................................................................................. 61.3 Product Description.................................................................................... 61.4 Product Operation...................................................................................... 61.5 Contact Details.......................................................................................... 81.6 Comercial Conditions.................................................................................. 8
1.6.1 Warranty ........................................................................................... 81.6.2 Quality Assurance ............................................................................... 9
1.7 Asset Management .................................................................................... 9
2 SAFETY 102.1 General ...................................................................................................10
2.1.1 Manual Handling ................................................................................102.1.2 Rules For Electrical Safety ...................................................................102.1.3 Suitable Tools....................................................................................10
3 INSTALLATION AND COMMISSIONING 113.1.1 Delivery and Transportation ................................................................113.1.2 Installation........................................................................................113.1.3 Cables and Cable Connection...............................................................133.1.4 Commissioning ..................................................................................133.1.5 Voltage Adjustment............................................................................143.1.6 Energisation Of Equipment ..................................................................16
4 MAINTENANCE 174.1.1 Routine and Preventative Maintenance..................................................174.1.2 Recommended Spare Parts .................................................................174.1.3 Onsite Testing Procedure ....................................................................17
4.2 Training and Competence ..........................................................................174.3 Disposal ..................................................................................................17
5 TECHNICAL DATA 18
6 REPAIR PROCEDURE 20
Appendix A – General Arrangement 21
Appendix B – Transformer Connection Plates 22
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 4 of 27
Referenced Material and Standards
The following source material was used:
The following documents in italics to be revised for FT document numbers
Document / Standard Name
[1] NR/L2/SIG/300007, Product Specification for power Transformersfor Signalling Systems
[2] FT Declaration of Conformity
[3] NR/L2/ELP/27410, Specification for Class II based SignallingSystems
[4] NR/L2/ELP/27409, Product Specification for Functional Supplypoints (FSP)
[5] NR/SP/ELP/27242, Specification of Low Voltage ElectricalInstallations on Railway Premises
[6] NR/SP/ELP/27243, Specification for Signalling Power Supplies
[7] NR/SP/ELP/27244, Guidance for Signalling Power Supplies
[8] NR/SP/ELP/27247, Guidance for Low Voltage ElectricalInstallations on Railway Premises
[9] NR/GN/ELP/27310, Management of Signalling Power Supplies
[10] GI/RT7017, Signalling & Safety Related TelecommunicationsPower Supplies and Circuits
[11] GI/GN7517, Guidance on Signalling and Safety RelatedTelecomms and Power Supplies and Circuits
[12] BS 7671, Requirements for Electrical Installations: IEE WiringRegulations (17th Edition)
[13] BS EN 50122-1, Railway Applications – Fixed Installations
[14] BS EN 50272 - 2, Railway Applications – Fixed Installations
[15] BS EN 60664-1, Insulation Coordination for Equipment WithinLow-voltage Systems - Part 1
[16] BS EN 61180-1, High-voltage TestTechniques for low-voltageequipment - Part 1
[17] SAM1290, Impulse Test of A 700V transformer To BritishStandard BS EN 50124
[18] BR SM 440 – Apparatus Case Rack layouts
[19] EaWR, Electricity at Work Regulations 1989
Websites www.ft-transformers.co.ukwww.networkrail.co.ukwww.hse.gov.uk
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 5 of 27
Abbreviations
AC Alternating Current
CPC Circuit Protective Conductor
CSA Cross Sectional Area
DC Direct Current
DNO Distribution Network Operator
E&P Electrification and Plant
EaWR Electricity at Work Regulations
FLC Full Load Current
FSP Functional Supply Point
GRIP Guide to Railway Investment Projects
IEEE Institute of Electrical & Electronics Engineers
LSF Low Smoke and Fume
LSZH Low Smoke Zero Halogen
MET Main Earth Terminal
N.I.C.E.I.C National Inspection Council for Electrical Installation Contracting
NR Network Rail
O&M Operation and Maintenance
PF Power Factor
PSP Principle Supply Point
PVC Polyvinyl Chloride
REB Relocatable Equipment Building
SWA Steel Wire Armoured
THD Total Harmonic Distortion
TP&N Three Phase and Neutral
VA Volt-Amps (Unit for Apparent Power)
XLPE Cross-Linked Polyethylene
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 6 of 27
1 INTRODUCTION
1.1 Purpose
This Operation and Maintenance manual is for the Class II Hybrid Functional SupplyPoint (FSP) transformers in the range:
250VA
500VA
1000VA
1400VA (4x output)
2000VA
These are to be used within Class II Signalling Power Distribution Systems in line withNR/L2/ELP/27410, Specification for Class II based Signalling Systems.
1.2 Audience
The intended audience for this operation and maintenance manual are all authorisedand competent persons involved in, but not limited to, designers, installers, assetmanagers and maintainers.
1.3 Product Description
KEY FEATURES:
Double Insulated primary side protection in-line with NR/L2/SIG/30007,Product Specification for power Transformers for Signalling Systems (note:100VA units have double insulated primary and secondary).
4 No outputs at 350VA each (1400VA type only)
Inrush equal to the full load current i.e. 1 x FLC
Patented spray on covering technique for the FT coating to provide a furtherlevel of electrical and corrosive protection and future proof the unit.
Fits within the standard Rail apparatus (location) case, REB (RelocatableEquipment Building) and rack frame to BR-SM-440
THIS PRODUCT IS A REPLACEMENT FOR LEGACY TRANSFORMERS TOBR924A
THIS PRODUCT CAN BE USED AS A CLASS I REPLACEMENT
THIS PRODUCT IS NOT SUITABLE FOR USE IN TUNNELS
1.4 Product Operation
The transformers are designed and built to be supplied from a two wire 650VAC ( +/-10% ) supply at a nominal frequency of 50hZ ( +/-4 to 6% ).
The transformers are designed and built to supply 110V (+/- the accepted NetworkRail tap settings) at a nominal frequency of 50hZ
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 7 of 27
Figure 1 – Class II transformer common details
Figure 2 – Transformer I.D. Badge
50364 XXXXXX
0-10-25-600-650-700 V 50 Hz1 PH
F
4X 350VA0-5-10-110-120-140 V
NR/L2/SIG/30007 Class II Hybrid
XXXXX / 1 2013
40kg
YEAR
INS CLASS
PADS No.DESIGN
INPUT
OUTPUT
SPEC
SERIAL No.
FT TRANSFORMERS LIMITEDTEL XXXXXXXXXXXXXwww.ft.transformers.co.uk
2x Built inhandles
4 x vent louvers
12x durable nylonbolts and washers
Warning Labels(Top and Front)
2 x holes cut outeither side diameter
26MM for Primarycable connection
2 x holes cut outeither side diameter
26MM forSecondary cable
connection
Mounting slots
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 8 of 27
Figure 3 – Warning Label
1.5 Contact Details
Address: FT Transformers Ltd
Unit 7 Cyclo Works,
Lifford Lane,
Kings Norton,
Birmingham,
B30 3DY
Telephone: +44 (0) 121 451 3204
Facsimile: +44 (0) 121 433 4577
Email: [email protected]
1.6 Comercial Conditions
1.6.1 Warranty
DOUBLEINSULATEDEQUIPMENT
INSIDE
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 9 of 27
We offer a standard warranty period of the equipment procured and supplied by FTTransformers 12 months from putting into service. However FT Transformers will notaccept liability for any costs incurred by others. Extended warranty is available atextra cost subject to agreement.
1.6.2 Quality Assurance
All contracts employ the Company Quality Assurance System, which complies with therequirements of ISO9001 and has been independently assessed by Lloyd's RegisteredQuality Assurance
1.7 Asset Management
All units have a unique number which is completely traceable as required by BSI 9001.This number can be aide to any asset management system for a life log of the unit.
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 10 of 27
2 SAFETY
2.1 General
Personal protective equipment PPE shall be in-line with Network Rail and groupstandards. All persons are to make an assessment of the required level of PPE in-linewith authorised site requirements.
The Nominate Competent person should do risk assessments and Method statementbefore any electrical installation is undertaken.
2.1.1 Manual Handling
The manual handling procedures in section 3.1.1 ‘Delivery and Transportation’ of thisdocument should be followed together with ‘Manual Handling Operations Regulations1992 (as amended)’.
2.1.2 Rules For Electrical Safety
The Low Voltage Directive - ‘Guidelines On The Application Of directive 2006/95/EC’,regards the voltage of the signalling power system as ‘low’ but ‘SUFFICIENT TO KILL’.
Assume all equipment is live until proven dead
The rules of electrical isolation within BS7671 and best practise should be adhered tothrough out by ‘Authorised Nominate Competent’ persons.
Network Rail Safety Procedures should be followed throughout for permissionsrequired for isolation and safe disconntection of signalling supplies.
If required the appropriate Warning and /or Danger notices must be displayed
2.1.3 Suitable Tools
All tools including personal tools must be suitable for the operation for which they arebeing used and must be in good condition.
Spanner for M6 hex bolt
Philips screw driver
Flathead screw driver
Figure 4 – Example tools
or + +
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 11 of 27
3 INSTALLATION AND COMMISSIONING
Although outside the scope of this manual, electrical Inspection and testing must be inaccordance with BS 7671 17th edition “Requirements for Electrical Installations” andGuidance Note 3, and in accordance with N.I.C.E.I.C testing guidelines / standards.
3.1.1 Delivery and Transportation
The transformer(s) will arrive at the arranged delivery address intact. If there isdamage to the transformers of any kind please contact FT Transformers Ltd.
When delivering to the final site installation the transformer(s) should be fixedsecurely within the vehicle for transportation. It is advised that the transformer(s) andGLS-100 R coating be inspected before installation.
During on loading and offloading it is advised that two or more competent personmanually lift the transformer in place. Note the Health and Safety Executive ManualHandling Charts (MAC) assessment is attached in Appendix B for reference and can beused to aid any manual handling risk assessment. However, this does not invalidatecompetent person(s) from their responsibilities. The Manual Handling OperationsRegulations 1992 (as amended) shall be adhered to in this regard. FT transformersadvise the use of a mechanical lifting aid such as a stacker for weights 40kg and belowas shown in figure 5
3.1.2 Installation
Before installation commences the installer must carry out a risk assessment. Themounting rails, brackets or other such arrangement must be assessed for its capabilityof bearing the transformer weight.
It is advised that the transformer be mounted at the lower portion of any cubicle orrack to reduce the risk of stress on any such cubicle or rack.
Although the FT-100 R coating is extremely durable, care must be taken not to scratchit. If damage does arise, please see Section 7 Repair Procedure for FT-100 R
The transformer must be mounted in the orientation shown in figure 3 below with thefixing holes to the bottom. The transformer must be securely fixed to the mountingrails, brackets or other such arrangement capable of bearing the transformer load. ThePlastic nuts and bolts supplied must be used ONLY. If these are lost, please contact FTTransformers and arrangements will be made to supply replacements. Otherwise,plastic nuts and bolts can be readily obtained from the standard electrical wholesalers.
To gain access to the cable connection plate the method followed in figures 6 & 7should be followed.
1
2
3
Figure 5 – Use of a Stacker
Once the stacker is in positionand the appropriate adjustmentmade to the tray height (1) thetransformer(s) can be slid (3)off the tray and into amaintenance vehicle or trailer(2) for removal/ transport tosite.
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 12 of 27
Figure 3 - Mounting in Place
Figure 6 – Tightening mounting bolts and removing cable faceplate
1 1
2 2
33
12
2 22
Rack or other loadbearing structure for
transformer fixing
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 13 of 27
Figure 7 –Cable connection faceplate
3.1.3 Cables and Cable Connection
All cabling should meet the requirements of NR/L2/ELP/27410. For connectionfaceplate see Appendix B
POWER CABLES
Only Class II enhanced cable shall be used on the 650V primary side of thetransformer as part of a Class II signalling power distribution system and required byNR/L2/ELP/27410.
NOTE: CABLES MUST NOT BE SWA!
The signalling power distribution cable is connected to the transformer with terminalblocks, which are designed to accept a cable size between 0.5-mm.
The supply is connected to the transformer with KS terminal Blocks which are touchproof and designed to accept a cable size between 0.5-2.5mm.
110V cables on the secondary side shall be the standards signalling cable and/or PVCcable as required by the installation scheme.
EARTH CABLES
All earthing and bonding on the transformer to any such, installation, which it is fixed,shall comply with BS 50122-1, BS 7430 and BS 7671: The requirements for ElectricalInstallations.
The functional earth terminal block which are designed to accept a cable size ofbetween 0.5-10mm
3.1.4 Commissioning
Before electrical energisation takes place, make sure that all ventilation louvers areclear of any obstruction.
Cable connectionplate (note the
example shown isfor the 1400VA
multi-output unit
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 14 of 27
NOTE: ONLY PARALLEL OUTPUTS 1&2 TOGETHER AND OUTPUTS 3&4 TOGETHER.
DO NOT PARALLEL ALL FOUR OUTPUTS TOGETHER!
Visually check that the coating is undamaged. If the coating is damaged on theoutside but is undamaged internally the transformer is good for use. No maintenanceis required and there is no need to change the transformer under these circumstances.See Repair Procedure
3.1.5 Voltage Adjustment
The transformer terminals should be set to the nominal voltage T0/650v and t0/t110v
Under load conditions, monitor the input voltages for a few minutes and obtain anaverage value.
Disconnect the incoming supply and use the table below to set the primary taps
Input voltages obtainable associated tapsetting
Output voltages obtainable and ossociatedtap setting ( 650v primary nominal )
Voltage In Primary Taps Secondary Taps Voltage Out
575v T25 T600 t10 t110 100V
590v T10 T600 t5 t110 105V
600v T0 T600 t0 t110 110V
625v T25 T600 t10 t120 110V
640v T10 T600 t5 t120 115V
650v T0 T600 t0 t120 120V
675v T25 T600 t10 t140 130V
690v T10 T600 t5 t140 135V
700v T0 T600 t0 t140 140V
Under load, monitor the output voltages and adjust the output taps to obtain approx108-112 volts
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 15 of 27
Figure 8a - Transformer Wiring Schematic with voltage taps
T0
t5t10
t110t120
T10
T600T650T700
Output Ratings:
250VA, 500VA,
1000VA, 2000VA
T25
t140
t0
FUNCTIONAL EARTH
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 16 of 27
Figure 8b - Transformer Wiring Schematic with voltage taps for 1.4kVA
3.1.6 Energisation Of Equipment
Wherever possible electrical equipment should not be connected to or energised untilall work on that equipment and associated circuits is complete. The first energisationof LV electrical equipment will be authorised by the Authorised Nominated CompetantPerson.
Once the electrical supply to LV electrical equipment has been made Live a DangerLive notice, must be attached to the LV electrical equipment to prevent interferencewhere danger may arise. This notice should remain in place until all envisagedinstallation, extension or modification work on the LV electrical equipment or systems,which the LV electrical equipment forms a part of, is complete.
Organisational Policies and procedures should be adhered to.
T0
t5t10
t110t120
T10
T600T650T700
O/P 1 = 350VA
T25
t140
t0
FUNCTIONAL EARTH
t5t10
t110t120
O/P 2 = 350VA
t140
t0
t5t10
t110t120
O/P 3 = 350VA
t140
t0
t5t10
t110t120
O/P 4 = 350VA
t140
t0
NOTE: ONLY PARALLEL OUTPUTS1&2 TOGETHER AND OUTPUTS 3&4TOGETHER.DO NOT PARALLEL ALL FOUROUTPUTS TOGETHER!
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 17 of 27
4 MAINTENANCE
Ensure that all ventilation louvers are clear.
The maintenance schedule is set by Network Rail under its maintenance schedulingprocedures and control of asset register information ( NR/SP/SIG/10661 ) SignallingMaintenance Task Intervals
A Class II Hybrid transformer must only be replaced with a Class II Hybrid or fullyClass II transformer of equal specification. NEVER replace a Class II Hybridtransformer with a Class I transformer.
Each transformers is provided with a unique I.D. located on the transformer label, thisshould be quoted when the unit is examined for maintenance.
4.1.1 Routine and Preventative Maintenance
FT Transformers advise that routine maintenance be carried so as not to shorten thelife expectancy of the transformers. This may also include preventative maintenanceas part of the asset management.
4.1.2 Recommended Spare Parts
No spare parts are required for these transformers
4.1.3 Onsite Testing Procedure
1. Disconnect the incoming supply and secondary connections.
2. Using a 500v megger check insulation resistance ( primary to functionalearth )
3. ( Secondary to Functional Earth ) ( Primary to Secondary ) All values to begreater than 100M ohms.
4. Check Input and Output winding resistances with the values on data sheet atthe rear of this manual.
5. Reconnect the incoming supply to Primary Terminals.
6. Check the incoming supply voltage, adjust primary taps if required using thetable in 3.1.5.
7. Check secondary voltages, voltages should be within 10% of the terminalvoltage.
8. Reconnect the secondary and check the load current
9. The load current should not exceed the values shown on the data sheets
10.Check output tap voltages, voltages should be within 2% of the terminalvoltage, adjust output taps if required.
4.2 Training and Competence
All works involving the installation, commissioning, testing, and routine maintenanceshall be carried out by persons competent, trained and authorised to do so to NetworkRail, Group and British Standards.
4.3 Disposal
Equipment may be returned to FT Transformers Ltd or a waste disposal organisationcertified but not to limited to the WEE Directive 2002/96/EG
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 18 of 27
5 TECHNICAL DATA
RATING CONTINUOUS 250VA 500VA 1000VA 1400VA 2000VAIMTERMITENT RATING 15MINSIN EACH HOUR 300VA 600VA 1200VA 1680VA 2400VA
DESIGN NUMBER 50361 50362 50363 50364 50365
PRIMARY WINDINGCLASSIFICATION
CLASS 11 CLASS 11 CLASS 11 CLASS 11 CLASS 11
SECONDARY WINDINGCLASSIFICATION
CLASS 1 CLASS 1 CLASS 1 CLASS 1 CLASS 1
PRIMARY VOLTAGE 0-10-25-600-650-700V
0-10-25-600-650-700v
0-10-25-600-650-700v
0-10-25-600-650-700v
0-10-25-600-650-700v
FREQUENCY (Hz) 50/60 50/60 50/60 50/60 50/60
3PH OR 1PH 1PH 1PH 1PH 1PH 1PH
INSULATION CLASS F F F F F
RECOMMENDED PRIMARY FUSEPROTECTION
2A BS88 TYPEGG 690VRATED OR IEC60269
2A BS88 TYPEGG 690VRATED ORIEC 60269
4A BS88 TYPEGG 690VRATED ORIEC 60269
6A BS88 TYPEGG 690VRATED ORIEC 60269
6A BS88TYPE GG690V RATEDOR IEC 60269
EFFICIENCY` 92% 94% 95.% 95.2% 95%
PEAK INRUSH X FLC 3.1 1.5 1 1 1
PEAK INRUSH CURRENT 1.5A 1.15A 1.53A 2.15A 3.07AI^t OVER FIRST TWO CYCLES40mS 0.09 0.05 0.09 0.18 0.38IMPEDANCE (ALLSECONDARY’S SHORTCIRCUIT)MEASURED VALUE AT 20°C
2.43% 2.12% 2.88% 2.63% 3.43%
IMPEDANCE MAX 5% MAX 5% MAX 5% MAX 5% MAX 5%
SECONDARY VOLTAGE
0-5-10-110-120-140
0-5-10-110-120-140
0-5-10-110-120-140
4 X 0-5-10-110-120-140
0-5-10-110-120-140
RATING AT EACH TERMINALOUTPUT
250VA 500VA 1000VA 4 x @ 350VAEACH
2000VA
DURATION OF PROSPECTIVEFAULT CURRENT FOR EACHSEC
1 SEC 1 SEC 1 SEC 1 SEC 1 SEC
PROSPECTIVE FAULT CURRENTON SECONDARY(one winding short circuit)
77.57A 185.53A 286.78A 98.2A 486.14A
REGULATION FROM NO LOADAT FULL RATING OFTRANSFORMER
2.9% 2.2% 2.85% 2.8% 3.3%
INSULATION RESISTANCE @500VDC. BOTH WINDINGS TOCORE >51G OHMS >51G OHMS >51G OHMS >51G OHMS >51G OHMS
INSULATION RESISTANCE @500VDC. WINDING TOWINDING >51G OHMS >51G OHMS >51G OHMS >51G OHMS >51G OHMS
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 19 of 27
DIELECTRIC STRENGTHPRIMARY TO CORE 5.2kV 5.2kV 5.2kV 5.2kV 5.2kV
DIELECTRIC STRENGTHSECONDARY TO CORE 2.8kV 2.8kV 2.8kV 2.8kV 2.8kV
DIELECTRIC STRENGTHPRIMARY TO SECONDARY 5.2kV 5.2kV 5.2kV 5.2kV 5.2kV
IMPULSE WITSTAND PRIMARYWINDING 8kV 8kV 8kV 8kV 8kV
WINDING INDUCTANCE @650V
35mH 30.0mH 19mH *16.0mH 12.3mH
WINDING INDUCTANCE @110V
1mH 0.86mH 0.54mH *0.46mH 0.35mH
PRIMARY WINDINGRESISTANCE @20 DEG C
18.50 ohms 9.00 ohms 7.70 ohms 5.70 ohms 4.80 ohms
SECONDARY WINDINGRESISTANCE @20 DEG C
1.25 ohmS 0.45 ohms 0.26 ohms 0.62 ohmsEach coil
0.10 ohms
X/R RATIO 0.35 0.73 0.71 0.77 0.80
OPERATIONAL TEMPERATURERANGE
-20C TO 60C -20C TO 60C -20C TO 60C -20C TO 60C -20C TO 60C
HUMIDITY UP TO 100%RH
UP TO 100%RH
UP TO 100%RH
UP TO 100%RH
UP TO 100%RH
PRIMARY TERMINALSSCREW CLAMP0.5mm TO2.5mm
SCREWCLAMP0.5mm TO2.5mm
SCREWCLAMP0.5mm TO2.5mm
SCREWCLAMP0.5mm TO2.5mm
SCREWCLAMP0.5mm TO2.5mm
DIMENSIONSW x H x D279 x 289 x210
W x H x D279 x 289 x210
W x H x D315 x 289 x250
W x H x D325 x 289 x268
W x H x D325 x 289 x268
WEIGHT 20kG 35Kg 40Kg 40.3KG 50kg
* NOTE:
1400VA UNIT THE INDUCTANCE VALUES ARE WHEN ALL 4 WINDINGS ARESHORT CIRCUITED
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 20 of 27
6 REPAIR PROCEDURE
A repair procedure is not required for the FT Class II transformers.
The transformer housing has been flash tested to 10kV on the inside and outside, atotal of 20kV. Therefore integrity is maintained even if there is damage to one side ofthe housing. It does need to be replaced in this instance.
If there is damage internal and exernally to the housing then the transformer must besent back to FT transformer Ltd for reconditioning or replacement.
The transformer must only be replaced with a Class II hybrid or better transformer
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 21 of 27
Appendix A – General Arrangement
TO ACCESS PLATEWARNING LABEL FIXED
BOLTS8 x M6 NYLON
TO ACCESS PLATEI.D. LABEL FIXED
HOUSING LID
A
13
DC
289
J
12
E
I
GH F
LK
OP
EQUIPMENT INSIDEDOUBLE INSULATED
EQUIPMENT INSIDEDOUBLE INSULATED
T700
T650
T600
T25
T10
T0
t5
t0
t10
t110
t120
t140
250VA, 500VA, 1000VA, 2000VA,OUTPUT RATINGS:
FUNCTIONAL EARTH
T700
T650
T600
T25
T10
T0
t5
t0
t10
t110
t120
t140
FUNCTIONAL EARTH
WDG 4 = 350VA
t5
t0
t10
t110
t120
t140
WDG 3 = 350VA
t5
t0
t10
t110
t120
t140
WDG 2 = 350VA
t5
t0
t10
t110
t120
t140
WDG 1 = 350VA
OUTPUT RATING 1400VA
EQUIPMENT
INSULATED
DOUBLE
WARNING
CLASS II EQUIPMENT
REPLACE EXISTING OR FAULTY
EQUIPMENT SHALL BE USED TO
ONLY APPROVED CLASS II650 VOLTS
DANGER
EQUIPMENT
HEAVYWARNING
USE
MANUAL BEFORE
APPLICATION
REFER TO
BEFORE OPENING
ISOLATE 650V SUPPLY ELSEWHERE
www.ft-transformers.co.uk
TEL +44 XXXX XXX XXXX
FT TRANSFORMERS LIMITED
DESIGN
INPUT
OUTPUT
SPEC
SERIAL No.
50364
0-10-25-600-650-700 V
0-5-10-110-120-140 V
NR/L2/SIG/30007
XXXXX / 1
PADS No.
1 PH
4X 350 VA
50 Hz
kg
XXXXXX
F
YEAR
INS CLASS
2013
EQUIPMENT
INSULATED
DOUBLE
WARNING
CLASS II EQUIPMENT
REPLACE EXISTING OR FAULTY
EQUIPMENT SHALL BE USED TO
ONLY APPROVED CLASS II650 VOLTS
DANGER
EQUIPMENT
HEAVYWARNING
USE
MANUAL BEFORE
APPLICATION
REFER TO
BEFORE OPENING
ISOLATE 650V SUPPLY ELSEWHERE
Legend/Notes
Signed
Signed
Designed DateSigned
Drawn
Checked
Approved
Date
Date
Date
Alternative Reference
Drawing Number Revision
of
Sheet
Drawing Title
Contractor(s)
Scale(s) ELR & Mileage
Project
Rev Date Description of Revisions Drawn Chkd Appr
Status
Signed
Dra
win
g N
um
ber
Sheet Size A2 420 x 594
A B C D E F G H I J K L M N O P
279
315
210 100 203 283 165 112 187 204
250 138 240 282 140 123 230 210
181
217
55 46 35 15 41 19
325 268 138 257 287 140 129 235 210 217
52 70 34 22 30 28
57 70 32 20 30 30
RATING
250VA & 500VA
1000VA
1400VA & 2000VA
TRANSFORMER MEASUREMENTS
NOT TO BE USED IN TUNNELS
FOR BR924A TRANSFORMERSTHIS PRODUCT IS A DIRECT REPLACEMENT
RANGE DETAILS
CLASS II HYBRID TRANSFORMER
.
Designed Name
Drawn Name
Checked Name
Approved Name
NTS .
Drawing No.
FT-DRG-CL2-05765 1 1
Rev
Date
Date
Date
Date
Rev Date Revision Description Drn Chk
Status
Designed Name
Drawn Name
Checked Name
Approved Name
App
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 22 of 27
Appendix B – Transformer Connection Plates
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
This document is protected by Copyright. The design of any article recorded in this document is protected by design right and the information contained in the document is confidential. The document may not be copied. Any design may notbe reproduced and the information contained in the document may not be used or disclosed except with the prior written permission of and in the manner permitted by the proprietors, FT Transformers LTD
250VA
FUNCTIONAL EARTH
Class II protectivecover – primary
connection
t0
t5V
t10V
t110V
t120V
t140V
ISOLATE 650V
ISOLATE 650V
T0
T10V
T25V
T0 T10V
T25V
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
This document is protected by Copyright. The design of any article recorded in this document is protected by design right and the information contained in the document is confidential. The document may not be copied. Any design may notbe reproduced and the information contained in the document may not be used or disclosed except with the prior written permission of and in the manner permitted by the proprietors, FT Transformers LTD
500VA
FUNCTIONAL EARTH
Class II protectivecover – primary
connection
t0
t5V
t10V
t110V
t120V
t140V
ISOLATE 650V
ISOLATE 650V
T0
T10V
T25V
T0 T10V
T25V
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 25 of 27
1kVA
FUNCTIONAL EARTH
Class II protectivecover – primary
connection
t0
t5V
t10V
t110V
t120V
t140V
ISOLATE 650V
ISOLATE 650V
T0
T10V
T25V
T0 T10V
T25V
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 26 of 27
1.4kVA
FUNCTIONAL EARTH
Class II protectivecover – primary
connection
t0
t5V
t10V
t110V
t120V
t140V
t0
t5V
t10V
t110V
t120V
t140V
t0
t5V
t10V
t110V
t120V
t140V
Secondary connectionx 4
Primary supplycable tie
T600
T650
V
T700
V 5V
t0
t5V
t10V
t110V
t120V
t140V
T0
T10V
T25V
ISOLATE 650V ISOLATE 650V
ONLY PARALLEL OUTPUT 1&2 AND OUTPUT 3&4 DO NOT PARALLEL ALL FOUR OUTPUTS
O/P
2 3
50VA
O/P 1 350VA
O/P 2 350VA
O/P
1 3
50VA
CLASS II TRANSFORMER OPERATION & MAINTENANCE MANUALNO: FT-O&M-DOC-05765REVISION.VERSION: 0.5
DATE: 16/07/2013
Page 27 of 27
2kVA
FUNCTIONAL EARTH
Class II protectivecover – primary
connection
t0
t5V
t10V
t110V
t120V
t140V
ISOLATE 650V
ISOLATE 650V
T0
T10V
T25V
T0 T10V
T25V