Page 1: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

The City Multi

YHM-A Range

For more information on Mitsubishi Electric visit www.barbourproductsearch.info

Page 2: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

The new City MultiYHM-A range providesthe per fect solution for more demandingapplications

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 3: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

the name Mitsubishi is synonymous with excellenceKnown the world over, Mitsubishi is a trusted global leaderassociated with a variety of products and services. Founded in1907, the company known today as Mitsubishi Electric, quicklyrose to the forefront of the air conditioning industry - a position we still enjoy today.

Unsurpassed air conditioning from Mitsubishi ElectricAir conditioning is an ideal way of controlling the air quality inside any building, large or small. Not only does it cool in the summer months but air conditioning can also heat, replacing traditionalheating systems. More and more people today are experiencing the benefits of comfortable working,living and leisure environments made possible with air conditioning. As market leaders, we prideourselves in providing high performance, competitive systems with low running costs.

Protecting the environmentMitsubishi Electric are the only air conditioning manufacturer recognised in the top 5 companies in the world for their sustainable environmental policy. Portfolio 21 only selects those companieswith an explicit commitment to sustainable business practices such as energy and resource efficiency, minimising ecological impacts of products and reducing greenhouse gas emissions. Our constant investment and product development enables Mitsubishi Electric to produce themost efficient equipment possible, whilst helping to protect the environment at the same time. For more information on Portfolio 21 please visit www.portfolio21.com.

The Forest Stewardship Council (FSC) is an international network promotingresponsible management of the world's forest. The paper this brochure isprinted on supports the development of responsible forest managementworldwide. The wood comes from FSC certified, well managed forests, company controlled sources and/or recycled material.

3

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 4: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

The New City Multi

YHM-A Range

The City Multi YHM-A range is Mitsubishi Electric’s answer to large scale VRF (Variable Refrigerant Flow) applications. The efficiencyof City Multi is second to none and offers a substantial increase in energy efficiency, with corresponding EER/COP ratings.

The City Multi Y Series range offers a simple and flexiblesolution where there is a demand for a changeover capability between heating and cooling, helping to ensurea constant, comfortable indoor climate. With a wide rangeof 76 indoor units, up to 50 (depending on the capacityavailable) can be connected to a single Y series outdoor unit.

Mitsubishi Electric also has the ability to provide simultaneousheating and cooling through its R2 systems. The differencehere being that this is achieved through only two pipesrather than the conventional three. By using MitsubishiElectric’s 2-pipe heat recovery technology, substantial savings can again be made on annual running costs. 50indoor units can now be connected to an R2 system.

Sophisticated technology, combined with a high levelof control and energy efficiency:

City Multi is perfectly positioned to meetthe demands of today’s market.

Highly eff icient& extremely flexible

4

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 5: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

� Increased Energy EfficiencyNew wrap around coil on 3 sides of the unit offers greater system efficiency. Highest ever COP’s compared to previous YGM-A models

� Increased Pipe LengthsTotal system pipe lengths of up to 1000m and furthest pipe lengths of 165m

� High Sensible Cooling FunctionRaised off coil temperatures offer a 10% increase in sensible cooling capacity over standard operation

� Low Starting Currents8 amp starting current for all models

� Reduced Noise LevelsDevelopments in fan blade shape and weight have produced an even higher performance and this alongsidethe compressor compartment now being sealed, have also managed to achieve lower noise levels. Acoustic Kits are also now available to reduce noise levels down to 47dB(A)

� Cooling Operation Set Temperature of 14ºC DBOffers benefits to environments such as gyms & laboratories (ducted & floor standing indoor units only)

� Effective Use of Space21% reduction in footprint size and a 10% reduction in height compared to previous YGM-A version

� Blue Fin TreatmentThe heat exchangers of all City Multi outdoor units have undergone this anti-corrosion treatment

� 100% Inverter ControlThe larger models now contain either 2 or 3 inverter driven compressors

� New High COP SystemAvailable in both Y Series and R2, alongside the standard systems

� Weight Reduction33kg reduction in weight (comparing size 250 unit against previous YGM-A model)

� Replace TechnologyEnables the reuse of existing R22 pipework, whilst allowing the upgradeto some of the most efficient systems available in the market

� Refrigerant Volume Checking FunctionEnabling customers to easily comply with the F-Gas regulation

5

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 6: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

The BasicsWhat is VRF?VRF stands for Variable Refrigerant Flow. A VRF air conditioning system modulates the flow of refrigerant depending upon the capacity requirements of the building. A VRF system comprises of a condensing unitsited externally and a series of multiple indoor units toprovide cooling and/or heating to the occupied space.

Our answer to VRFMitsubishi Electric sets the boundaries of VRF technologywith the City Multi range, which is available using R410Arefrigerant with zero ODP (Ozone Depletion Potential).The range has been specifically designed for today's building requirements and addresses key market issuessuch as energy efficiency, adaptability and reliability. Mitsubishi Electric manufactures the only 2-pipe heat recovery simultaneous heating and cooling system in theworld and equally unique, a water-cooled version. With user friendly control systems utilising Internet technology and integrated cooling and ventilation indoorunits, City Multi is the benchmark and market leader in VRF technology.

What is inverter driven technology?Mitsubishi Electric spends more than 5% of its turnoveron research and development, with our engineers alwayslooking at ways in which we can improve and lead in airconditioning efficiency. The use of inverter technology inour City Multi systems is paramount in this process, working by varying the compressor speed to match thecooling or heating load, thereby consuming only thepower necessary to match the exact requirement of the room.

When City Multi is operating at partial load, the energyefficiency of the system is significantly higher than at fullload. In a typical application partial load conditions prevailfor more than 90% of operation time. A fixed speed system can only operate at 100% capacity and cannot matchthe annual efficiencies of an inverter system.

What is a Heat Pump system?Mitsubishi Electric’s City Multi Y Series, is a heat pumpsystem, which provides either heating or cooling to abuilding at any given time.

What is a Heat Recovery system?Mitsubishi Electric’s City Multi R2 series has the ability toprovide heating and cooling at the same time in areasconnected to the same outdoor unit.

6

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 7: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

7

Why R410A?R410A is a more efficient refrigerant as it has a higherspecific heat capacity when compared to R407c or R22.This higher energy carrying capacity allows for smallerpipe sizes, longer pipe runs and reduces the volume of refrigerant within a system.

This is a major factor when complying with EN378, a European standard concerning safety and environmentalrequirements in the design, manufacture, installation, operation, maintenance and disposal of refrigerating systems.

Why Heat Recovery?Flexibility and efficiency are key factors when selecting aheat recovery system. For example, while a heat pumpsystem is adequate for a large open plan office, businessesthat have a more partitioned structure to an office will require the need to simultaneously heat or cool different sections of the office according to each usersindividual preferences.

The efficiency of this type of system comes from the ability to use the by-products of cooling and heating totransfer energy where it is required, thus acting as a balanced heat exchanger achieving up to 20% cost savings over a conventional heat pump system. The number of connection sites needed for an R2 systemare also significantly lower than those needed for a threepipe version. This helps to reduce installation costs, further increasing the savings associated with City Multi.

The BC Controller houses a liquid/gas separator, allowing the outdoor unit to deliver a mixture (2 phase)of hot gas for heating and liquid for cooling, all throughthe same pipe. Three pipe systems allocate a pipe toeach of these phases. When this mixture arrives at the BC Controller, it is separated and the correctphase delivered to each indoor unit depending on theindividual requirement of either heating or cooling.

How does the R2 Heat Recovery System operate on 2 Pipe’s?

The secret of City Multi heat recovery systems lies in the BC Controller

Comparison example of piping connection sites

= 3 sites= 2 sites

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 8: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

Energy efficiency has always been the driver for City Multi technological development. Technology that always delivers the quality and reliability needed for commercial air conditioning environments. Mitsubishi Electric spend more than 5% of their turnover on research and development, with our engineers always looking at ways in which we can improveand lead in Air Conditioning efficiency.

City Multi R410A YHM-A technology

Using the ver y latest in IPM (Intelligent Power Module) technology, precise control of energy input is achieved allowing City Multi to further improve COPs for R410A systems. IPM uses 1Hz steps of capacity control,matching building requirements through more accurate control of the occupied space with reduced power input. As in previous versions, IPM technology operates extremely effectively under par t load conditions (50-80% of operating capacity), a condition that most systems will be in for their normal working life. Therefore theconsideration of efficiency at part load is accounted for as well as when at peak load conditions, offering high system efficiency all year round.

Stable and smooth operation - 100% inverter control

All City Multi compressors are inverter-driven - Capable of precisely matching a building's cooling andheating demands.

The outdoor unit combinations comprise of one module for 8-18hp systems (for R2 up to 16hp), two modules for20-36hp systems (for R2, 18-32hp) and three modules for 38-50hp systems (Y series only). Each module carries one inverter compressor making simple and highly reliable control possible. Not only does it allow low starting currents,the inverter driven compressor also provides precise indoor comfort and adapts to the air conditioning load, achieving smooth transition across the range of compressor frequencies.

The technology to make

8

City Multi the

Y Series 8-18hp / R2 8-16hp Y Series 38-50hpY Series 20-36hp / R2 18-32hp

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 9: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

9

natural choiceHeat Interchange Unit

To further enhance the class leading efficiencyof City Multi, the unique Heat InterchangeCircuit provides extra sub cooling. This systemallows optimum refrigerant distribution tomultiple indoor units, by allowing more effective use of refrigerant flowing through theelectronic expansion valves. Because of theadded efficiency, volumes of refrigerantin systems are continuing to reduce.

The difference between YHM-A and previous Mitsubishi Electric models

Technology is key when increased efficiency is demanded. The City Multi YHM-A range is designed to deliver this.

A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerantcircuit (low pressure loss) including new accumulator design also adds a few more points to the efficiency scale. Enhancements to the heat interchange circuit, inverter driven fan motor and heat exchanger design, again add vitalincreases to overall system efficiency and COPs.

The importance of COP

COP stands for “Co-efficient of Performance”. It is a measure of the useful energy a system can deliver compared to the energy that it consumes. It is calculated by dividing the energy output by the energy input of a system. The higher the figure then the more efficient the system is deemed to be, with commensurate reduced running costs. For Heat Pumps to be included on the Energy Technology Product List under the Enhanced Capital Allowance scheme, they must achieve a heating COP of 3.4 and a cooling EER (energy efficiency ratio) of 3.0. Therefore every input of 1kW of energy must deliver an output of 3.4kW for heating and 3.0kW for cooling, achieving an energy label of B.

Total Energy Conservation

Comparison of COP (energy efficiency) of an 8hp YHM-A system.

CITY MULTI REFRIGERANT CIRCUIT

NORMAL REFRIGERANT CIRCUIT

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 10: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

10

A wide choice of models

The model line up

The new YHM-A outdoor models are modular in design and as such differingcombinations of them can be connected together to create the required outdoorunit size needed for a particular application.

Both the Y Series and R2 ranges come in standard (-P) and high COP (-EP) versions. In addition,the standard versions allow for space-saving by virtue of the combination of units having a smallerfoot print than the high COP versions.

Y Series Heat Pump - Standard Version

Series

Y

R2

Size

Model Name

PUHY-P YHM-A

PUHY-EP YHM-A

PURY-P YHM-A

PURY-EP YHM-A

200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250

8hp 10hp 12hp 14hp 16hp 18hp 20hp 22hp 24hp 26hp 28hp 30hp 32hp 34hp 36hp 38hp 40hp 42hp 44hp 46hp 48hp 50hp

� � � � � � � � � � � � � � � � � � � � �

� � � � � � � � � � � � �

� � � � � � � � � � �

� � � � � � �

10hp

PUHY-P250YHM-A

12hp

PUHY-P300YHM-A

Y Series (10-12hp) PUHY-P YHM-A

28hp

PUHY-P700YSHM-A

30hp

PUHY-P750YSHM-A

32hp

PUHY-P800YSHM-A

Y Series (28-36hp) PUHY-P YSHM-A

14hp

PUHY-P350YHM-A

16hp

PUHY-P400YHM-A

18hp

PUHY-P450YHM-A

Y Series (14 -18hp) PUHY-P YHM-A

38hp

PUHY-P950YSHM-A

40hp

PUHY-P1000YSHM-A

Y Series (38 -40hp) PUHY-P YSHM-A

20hp

PUHY-P500YSHM-A

22hp

PUHY-P550YSHM-A

24hp

PUHY-P600YSHM-A

26hp

PUHY-P650YSHM-A

Y Series (20 -26hp) PUHY-P YSHM-A

42hp

PUHY-P1050YSHM-A

Y Series (42hp) PUHY-P YSHM-A

44hp

PUHY-P1100YSHM-A

46hp

PUHY-P1150YSHM-A

48hp

PUHY-P1200YSHM-A

50hp

PUHY-P1250YSHM-A

Y Series (44-50hp) PUHY-P YSHM-A

34hp

PUHY-P850YSHM-A

36hp

PUHY-P900YSHM-A

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 11: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

11

Y Series Heat Pump - High COP Version

8hp

PUHY-EP200YHM-A

12hp

PUHY-EP300YHM-A

Y Series - High COP (8-12hp) PUHY-EP YHM-A

Y Series - High COP (28-30hp) PUHY-EP YSHM-A

16hp

PUHY-EP400YSHM-A

18hp

PUHY-EP450YSHM-A

20hp

PUHY-EP500YSHM-A

Y Series - High COP (16-20hp) PUHY-EP YSHM-A

32hp

PUHY-EP800YSHM-A

34hp

PUHY-EP850YSHM-A

28hp

PUHY-EP700YSHM-A

30hp

PUHY-EP750YSHM-A

Y Series - High COP (32-34hp) PUHY-EP YSHM-A

Y Series - High COP (22-26hp) PUHY-EP YSHM-A

36hp

PUHY-EP900YSHM-A

Y Series - High COP (36hp) PUHY-EP YSHM-A

22hp

PUHY-EP550YSHM-A

24hp

PUHY-EP600YSHM-A

26hp

PUHY-EP650YSHM-A

R2 Series Heat Recovery - Standard Version

10hp

PURY-P250YHM-A

12hp

PURY-P300YHM-A

R2 Series (10-12hp) PURY-P YHM-A

R2 Series (26-28hp) PURY-P YSHM-A

R2 Series (14-16hp) PURY-P YHM-A

30hp

PURY-P750YSHM-A

32hp

PURY-P800YSHM-A

26hp

PURY-P650YSHM-A

28hp

PURY-P700YSHM-A

R2 Series (30-32hp) PURY-P YSHM-A

R2 Series (18-24hp) PURY-P YSHM-A

14hp

PURY-P350YHM-A

16hp

PURY-P400YHM-A

20hp

PURY-P500YSHM-A

22hp

PURY-P550YSHM-A

24hp

PURY-P600YSHM-A

R2 Series Heat Recovery - High COP Version

8hp

PURY-EP200YHM-A

12hp

PURY-EP300YHM-A

R2 Series - High COP (8-12hp) PURY-EP YHM-A R2 Series - High COP (16-18hp) PURY-EP YSHM-A

24hp

PURY-EP600YSHM-A

R2 Series - High COP (24hp) PURY-EP YSHM-A

R2 Series - High COP (20-22hp) PURY-EP YSHM-A

16hp

PURY-EP400YSHM-A

18hp

PURY-EP450YSHM-A

20hp

PURY-EP500YSHM-A

22hp

PURY-EP550YSHM-A

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 12: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

High off coil / High sensible cooling

Poor design or application of air conditioning systems can sometimes lead to cold draughts and uneven room temperatures. Low off coil temperatures cause dehumidifying of the air which can create dry eyes and sore throats.

Mitsubishi Electric now provides a High Sensible Cooling Function specifically designed to deal with this. By raisingthe off coil temperature, a 10% increase in sensible cooling capacity over standard operation is achievable, the resultbeing greater comfort for occupants. These high SHF’s are available throughout the range of indoor units, allowingoptimum selection of units tailored to more specific design criteria.

Reduced noise levels

New fan designCity Multi VRF systems led the introduction of larger single fan rotors some ten years ago, achieving substantially lower noise levels over multiple designs. Continuing the development in the areas of blade shape and weight, Mitsubishi Electric have managed to achieve even higher performance and lower noise levels.

To reduce noise levels further and comply with inner city residential noise regulations, all outdoor units include NightSet-back mode. This function works by lowering the fan speed and compressor frequency proportionally with reduction in demand (44dBA for PUHY-P250YHM-A). The compressor compartment is also now sealed, further reducing noise levels.

Features & benefits

12

LowNoise

New fan designReduction of operation noise

New heat exchanger designImprovement of COP

New inverter compressorImprovement of COP

New control box designImprovement of reliability and easy maintenance

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 13: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

13

Acoustic kits

A range of Acoustic Kits designed for noise reduction are also available. An industry first, the kits offer a 10dBA noise level reduction from standard.

For supply and / or installation please contact Ambient Acoustics on 01934 712802

Cooling operation set temperature of 14ºC

Environments such as gyms, laboratories etc often require the ability to cool lower than the standard comfort cooling setpoint. By selecting a dip switch on the unit, a cooling operation set temperature of 14ºC DB is possible on the floorstanding and ducted models only. The indoor unit fan will be fixed at high speed during this operation.

Refrigerant volume checking function

This function runs the system, measuring various temperatures and pressures throughout the system, comparing these to the values stored in the units memory from the previous service. If a leakage has occurred the system will indicate so, enabling customers to easily comply with the F-Gas regulation.

Replace technology

This unique function allows the re-use of refrigerant piping, controllers, power and control wiring for all previously installed Mitsubishi Electric R22 and R407c Heat Recovery and Cooling only systems and partial replace of HeatPumps (pressure regulations require one pipe from the outdoor to the first branch to be replaced).

This function offers unprecedented savings on installation costs, disruption to business and down time, not to mention the considerable running cost and CO2 emission savings - more than halving the running costs compared toa 10 year old unit.

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 14: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

Features & benefits

14

Effective use of space

The new models have a smaller foot print requirement than previous models. The width and depth have been reduced by 7% and 13% respectively, with the height being reduced by 130mm. (PUHY-P250YHM-A compared toprevious YGM-A versions).

Weight reduction

Weight has been reduced by approximately 33kg

(PUHY-P250YHM-A compared to previous YGM-A versions).

YGM-A YHM-A

YGM-A YHM-A

8-12hp systems (Y / R2 Series) 1.43m2

14-18hp systems (Y Series)14-16hp systems (R2 Series)

1.89m2

mm

33kg

Approximately 21% reduction in foot print(PUHY-P250)

The unit can easily be transported, even into inaccessible buildings

The downsized outdoor unit can be transported through an 800mm wide lift door

The narrow space between buildings makes it difficult to use a crane 8-12hp outdoor units Example of lift

mm

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 15: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

Blue Fin treatment

The anti-corrosion Blue Fin treatment of the heat exchanger is especially effective in urban environments where the traffic pollutions can damage the aluminium fins reducing the capacity and life expectancy of the unit.

All City Multi R410A outdoor units have been treated with Blue Fin.

Heating operation range

At low ambient temperatures the guaranteed operating range in heating is minus 20ºC

Operating range in cooling is from anoutdoor temperature of -5ºC, while that in heating is from an outdoor temperature of -20ºC.

R410A pipe sizing

As R410A has a higher specific heat capacity than R22, the pipework is smaller. This means the pipe itself is cheaper, easier to install and less riser space is required within the building.

10hp model

15

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 16: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

� Reduced noiseReduced noise thanks to the use of a newly designed centrifugal fan and coil. The PEFY-P-VMS1-E is the quietest unit of its type in the market (22dBA - size 15).

� Ultra thin body Height of only 200mm and narrow width of 700mm (P15-32), 900mm (P40-50) and 1100mm (P63). This model can be easily installed into tight spaces such as ceiling cavities or drop ceilings.

� Low cooling operation set temperatureCooling operation set temperature can be set down to 14ºC DB when used with YHM-A.

� Static pressure5-50Pa

New indoor units for 2008

PEFY-P-VMS1-E Ceiling Concealed Ducted Unit

The ultra thin unit offers increased flexibility, and is particularly suitable for places where low noise operation is desired from a slim line body. This unit now comes in a size 15, ideal for hotel rooms!

P15Capacity

NoiseLevel

P20 P25 P32 P40 P50 P63

28 29 30 32 33 35 36

24 25 26 27 30 32 33

22 23 24 24 28 30 30

HighFan

Speed Med

Low

Noise level table (Standard static pressure) at 15Pa

Mor

e th

an 1

0mm

Mor

e th

an 2

0mm

Ceiling surface Access door

700mm

16

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 17: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

PFFY-P- VLRMM-E Floor Standing Concealed Unit

A compact concealed unit providing simple, effective air conditioning in perimeter zones. The unit is easy to install and at only 220mm deep offers an unobtrusive method of delivering highly efficient air-conditioningperformance.

� Reduced noiseNoise levels have been reduced compared to the previous PFFY-P-VLRM-E version.

� Low cooling operation set temperatureCooling operation set temperature can be set down to 14ºC dB when used with YHM-A.

� Static pressureThe new unit has 3 static pressure settings - 20/40/60Pa ideal for ducting in the perimeter zone.

� Concealed unit for hidden installation The unit can be hidden behind a wardrobe in a hotel, then ducted above and below the wardrobe doors. This offers lower noise, less disruption and a low visual impact.

17

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 18: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

18

Outdoor unit Y Series specifications

PUHY-P250YHM-A PUHY-P300YHM-A PUHY-P350YHM-A PUHY-P400YHM-A PUHY-P450YHM-A PUHY-P500YSHM-A PUHY-P550YSHM-A

Y Series Standard Outdoor Units 10-22hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

31.528.028.726.6

7.837.737.754.79

4.02 / 3.62

21

185

57

200

9207601710

380-415v, 50Hz

3

8

12.111.9

32

4 + earth

37.533.533.031.5

9.399.079.116.71

3.99 / 3.69

26

185

59

215

9207601710

380-415v, 50Hz

3

8

14.514.0

32

4 + earth

45.040.039.637.6

12.0911.2011.738.29

3.72 / 3.57

30

225

60

245

12207601710

380-415v, 50Hz

3

8

18.617.3

32

4 + earth

50.045.044.042.3

13.4713.2313.079.79

3.71 / 3.40

34

225

61

245

12207601710

380-415v, 50Hz

3

8

20.820.4

40

4 + earth

56.050.048.746.0

15.3816.2814.0011.40

3.64 / 3.07

39

225

62

245

12207601710

380-415v, 50Hz

3

8

23.725.1

50

4 + earth

63.056.054.851.5

16.4016.4714.9211.53

3.84 / 3.40

43

185 / 185

60

200 + 200

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

25.325.4

32 / 32

4 + earth

69.063.060.058.0

18.0618.3616.4312.85

3.82 / 3.43

47

185 / 185

60.5

200 + 215

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

27.928.3

32 / 32

4 + earth

PUHY-P600YSHM-A PUHY-P650YSHM-A PUHY-P700YSHM-A PUHY-P750YSHM-A PUHY-P800YSHM-A PUHY-P850YSHM-A PUHY-P900YSHM-A

Y Series Standard Outdoor Units 24-36hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

76.569.066.663.5

19.9218.7518.1313.13

3.84 / 3.68

50

185 / 225

60.5

200 + 245

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

30.728.9

32 / 32

4 + earth

81.573.070.967.2

21.9020.7919.9314.55

3.72 / 3.51

50

185 / 225

61

215 + 245

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

33.832.1

32 / 32

4 + earth

88.080.075.773.6

23.7122.4722.0516.18

3.71 / 3.56

50

225 / 225

61

245 + 245

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

36,634.7

32 / 32

4 + earth

95.085.081.778.2

25.4625.0723.6818.05

3.73 / 3.39

50

225 / 225

63

245 + 245

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

39.338.7

40 / 32

4 + earth

100.090.086.082.8

25.7027.6923.9019.94

3.89 / 3.25

50

225 / 225

64

245 + 245

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

39.742.8

50 / 32

4 + earth

108.096.095.088.3

28.4230.1826.1519.92

3.80 / 3.18

50

225 / 225

64.5

245 + 245

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

43.946.6

50 / 40

4 + earth

113.0101.099.492.9

30.2933.3327.8722.00

3.73 / 3.03

50

225 / 225

64.5

245 + 245

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

46.851.5

50 / 50

4 + earth

PUHY-P950YSHM-A PUHY-P1000YSHM-A PUHY-P1050YSHM-A PUHY-P1100YSHM-A PUHY-P1150YSHM-A PUHY-P1200YSHM-A PUHY-P1250YSHM-A

Y Series Standard Outdoor Units 38-50hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

119.5108.0105.299.4

30.0230.6827.6220.25

3.98 / 3.52

50

185 / 185 / 185

64

200 + 215 + 245

920 + 920 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

46.447.4

40 / 32 / 32

4 + earth

127.0113.0111.8104.0

33.1532.4730.5021.43

3.83 / 3.48

50

185 / 185 / 225

64

215 + 215 + 245

920 + 920 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

51.250.1

40 / 32 / 32

4 + earth

132.0118.0116.2108.6

35.0133.9032.2122.37

3.77 / 3.48

50

185 / 225 / 225

64

200 + 245 + 245

920 + 1220 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

54.152.4

40 / 32 / 32

4 + earth

140.0124.0123.2114.1

36.9335.8333.9823.65

3.79 / 3.46

50

225 / 225 / 225

64

245 + 245 + 245

1220 + 1220 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

57.055.3

40 / 32 / 32

4 + earth

145.0130.0127.6119.6

39.0839.3935.9526.00

3.71 / 3.30

50

225 / 225 / 225

64.5

245 + 245 + 245

1220 + 1220 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

60.460.8

50 / 32 / 32

4 + earth

150.0136.0132.0125.1

40.1041.7136.8927.53

3.74 / 3.26

50

225 / 225 / 225

65

245 + 245 + 245

1220 + 1220 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

61.964.4

50 / 40 / 32

4 + earth

156.5140.0137.7128.8

42.0645.0138.7029.71

3.72 / 3.11

50

225 / 225 / 225

65.5

245 + 245 + 245

1220 + 1220 + 1220760 + 760 + 7601710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

65.069.5

50 / 50 / 32

4 + earth

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 19: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

19

PUHY-EP200YHM-A PUHY-EP300YHM-A PUHY-EP400YSHM-A PUHY-EP450YSHM-A PUHY-EP500YSHM-A PUHY-EP550YSHM-A PUHY-EP600YSHM-A

Y Series High COP Outdoor Unit 8-24hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

25.022.423.021.3

5.775.185.713.21

4.33 / 4.32

17

185

57

200

9207601710

380-415v, 50Hz

3

8

8.98.0

20

4 + earth

37.533.533.031.5

9.288.259.006.11

4.04 / 4.06

26

225

60

245

12207601710

380-415v, 50Hz

3

8

14.312.7

32

4 + earth

50.045.044.042.3

11.5410.4111.197.70

4.33 / 4.32

34

185 / 185

60

200 + 200

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

17.816.0

20 / 20

4 + earth

56.050.048.746.0

13.0513.1511.889.21

4.29 / 3.80

39

185 / 185

60

200 + 200

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

20.120.3

32 / 20

4 + earth

63.056.054.851.5

15.1413.4613.789.42

4.16 / 4.16

43

185 / 225

62

200 + 245

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

23.420.8

32 / 20

4 + earth

69.063.060.058.0

17.1216.3215.5811.42

4.03 / 3.86

47

185 / 225

62

200 + 245

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

26.425.2

32 / 32

4 + earth

76.569.066.663.5

18.9316.9917.2311.89

4.04 / 4.06

50

225 / 225

63

245 + 245

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

29.226.2

32 / 32

4 + earth

PUHY-EP650YSHM-A PUHY-EP700YSHM-A PUHY-EP750YSHM-A PUHY-EP800YSHM-A PUHY-EP850YSHM-A PUHY-EP900YSHM-A

Y Series High COP Outdoor Unit 26-36hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

81.573.070.967.2

19.1318.3417.4112.84

4.26 / 3.98

50

225 / 225

63

245 + 245

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

29.528.3

32 / 32

4 + earth

88.080.075.773.6

20.0020.9918.6015.11

4.40 / 3.81

50

185 / 185 / 225

63

200 + 200 + 245

920 + 920 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

30.932.4

32 / 20 / 20

4 + earth

95.085.081.778.2

22.1921.7920.6415.69

4.28 / 3.90

50

185 / 185 / 225

63

200 + 200 + 245

920 + 920 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

34.333.6

32 / 32 / 20

4 + earth

100.090.086.082.8

23.4122.0021.7715.84

4.27 / 4.09

50

185 / 225 / 225

64

200 + 245 + 245

920 +1220 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

36.134.0

32 / 32 / 20

4 + earth

108.096.095.088.3

25.5924.6723.5416.28

4.22 / 3.89

50

185 / 225 / 225

64

200 + 245 + 245

920 +1220 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

39.538.1

32 / 32 / 32

4 + earth

113.0101.099.492.9

27.9024.8725.6716.41

4.05 / 4.06

50

225 / 225 / 225

65

245 + 245 + 245

1220 +1220 + 1220760 + 760 + 760

1710 + 1710 + 1710

380-415v, 50Hz

3

8 / 8 / 8

43.138.4

32 / 32 / 32

4 + earth

Y Series Piping Restrictions

Total Piping LengthFurthest Piping LengthFurthest Piping Length After 1st BranchBetween Indoor and Outdoor Units - HeightBetween Indoor and Indoor Units - Height

1000m max165m max40m max50m max (40m max if outdoor installed below)15m max

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 20: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

20

Outdoor unit R2 Series specifications

PURY-P250YHM-A PURY-P300YHM-A PURY-P350YHM-A PURY-P400YHM-A PURY-P500YSHM-A PURY-P550YSHM-A

R2 Series Standard Outdoor Unit 10-22hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

31.528.028.726.6

7.837.737.754.79

4.02 / 3.62

25

185

57

235

9207601710

380-415v, 50Hz

3

8

12.111.9

32

4 + earth

37.533.533.031.5

9.589.259.296.85

3.91 / 3.62

30

185

59

240

9207601710

380-415v, 50Hz

3

8

14.814.2

32

4 + earth

45.040.039.637.6

12.4712.4712.109.23

3.60 / 3.20

35

225

60

265

12207601710

380-415v, 50Hz

3

8

19.219.2

32

4 + earth

50.045.044.042.3

13.7113.7413.3010.17

3.64 / 3.27

40

225

61

265

12207601710

380-415v, 50Hz

3

8

21.121.2

40

4 + earth

63.056.054.851.5

16.7916.7515.2811.73

3.75 / 3.34

48

185 / 185

60

235 + 235

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

25.925.8

32 / 32

4 + earth

69.063.060.058.0

18.8118.6817.1213.08

3.66 / 3.37

48

185 / 185

61

235 + 240

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

29.028.8

32 / 32

4 + earth

PURY-P600YSHM-A PURY-P650YSHM-A PURY-P700YSHM-A PURY-P750YSHM-A PURY-P800YSHM-A

R2 Series Standard Outdoor Unit 24-32hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

76.569.066.663.5

20.8319.6418.9613.75

3.67 / 3.51

48

185 / 185

62

240 + 240

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

32.130.3

32 / 32

4 + earth

81.573.070.967.2

22.5522.8020.5215.96

3.61 / 3.20

48

185 / 225

62.5

240 + 265

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

34.835.2

32 / 32

4 + earth

88.080.075.773.6

24.3024.7222.6017.80

3.62 / 3.23

48

185 / 225

63

240 + 265

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

37.538.2

40 / 32

4 + earth

95.085.081.778.2

26.3627.8624.5120.06

3.60 / 3.05

48

225 / 225

63.5

265 + 265

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

40.743.0

40 / 32

4 + earth

100.090.086.082.8

27.6429.7525.7121.42

3.61 / 3.02

48

225 / 225

64

265 + 265

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

42.745.9

40 / 40

4 + earth

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 21: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

21

PURY-EP200YHM-A PURY-EP300YHM-A PURY-EP400YSHM-A PURY-EP450YSHM-A PURY-EP500YSHM-A PURY-EP550YSHM-A PURY-EP600YSHM-A

R2 Series High COP Outdoor Unit 8-24hp

Model ReferenceCapacity (kW) Heating (nominal)

Cooling (nominal)Heating (UK)Cooling (UK)

Power Input (kW) Heating (nominal)Cooling (nominal)Heating (UK)Cooling (UK)

COP/EER (nominal)

Max No. of Connectable Indoor Units

Airflow (m3/min) High

Noise (dBA)

Weight (kg)

Dimensions (mm) WidthDepth

(1650mm without legs) Height

Electrical Supply

Phase

Starting Current (A)

Running Current (A) HeatingCooling

Fuse Rating (MCB sizes BS EN 60947-2) - (A)

Mains Cable No. Cores

25.022.423.021.3

5.815.235.753.24

4.30 / 4.28

20

185

57

235

9207601710

380-415v, 50Hz

3

8

8.98.0

20

4 + earth

37.533.533.031.5

9.378.339.096.16

4.00 / 4.02

30

225

60

265

12207601710

380-415v, 50Hz

3

8

14.412.8

32

4 + earth

50.045.044.042.3

11.7310.5711.387.82

4.26 / 4.25

40

185 / 185

60

235 + 235

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

18.116.3

20 / 20

4 + earth

56.050.048.746.0

13.7713.0912.539.16

4.06 / 3.81

45

185 / 185

60

235 + 235

920 + 920760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

21.220.2

32 / 20

4 + earth

63.056.054.851.5

15.3313.7013.959.59

4.10 / 4.08

48

185 / 225

62

235 + 265

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

23.621.1

32 / 20

4 + earth

69.063.060.058.0

17.3716.3815.8111.47

3.97 / 3.84

48

185 / 225

62

235 + 265

920 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

26.825.3

32 / 32

4 + earth

76.569.066.663.5

19.1217.0017.4011.90

4.00 / 4.05

48

225 / 225

63

265 + 265

1220 + 1220760 + 760

1710 + 1710

380-415v, 50Hz

3

8 / 8

29.526.2

32 / 32

4 + earth

Outdoor Model Max LengthTable 1: Total Piping LengthR2 Series Piping Restrictions

Graph 1: Total Piping Length Restrictions

P250, P300P350, P400, EP200, EP300P500, P550, EP400, EP450, EP500, EP550P600, P650, EP600P700, P750, P800

550m*1

600m*1

750m*1

800m*1

950m*1

*1 Please refer to Graph 1

1000

PURY-P700,750,800 YSHM-A

PURY-P600,650,800 YSHM-A, PURY-EP600YSHM-A

PURY-P500,550 YSHM-A, PURY-EP400,450,500,550 YSHM-A

PURY-P350,400 YHM-A, PURY-EP200,300 YHM-A

PURY-P250,300YHM-A

900

800

700

600

500

400

300

200

100

0

10 20 30 40 50 60 70 80 90 100 110

Tota

l Ext

ende

d Pi

pe L

engt

h (m

)

Distance Between Outdoor Unit and BC Controller (m)

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 22: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

22

R2 Series Piping Restrictions

Item Pipe Section Max Length

R2 Series Piping Restrictions

Piping Length (1 BC Controller, No Sub BC Controller)

Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IU

A+B+a+b+c+dA+B+d

AB+dHH1

h1h2

(See Table 1)165m

110m*1

60m*2 (40m)50m40m15m15m

*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.

Item Pipe Section Max Length

R2 Series Piping Restrictions

Piping Length (>1 BC Controller for 1 Outdoor Unit)

Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IUHeight Between BC (Main or Sub) and BC (Sub)

A+B+C+D+E+a+b+c+d+e+fA+C+E+f

AB+d or C+D+e or C+E+f

HH1

h1h2h3

(See Table 1)165m

110m*1

60m*2 (40m)50m40m15m15m15m

*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 23: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

2323

Item Pipe Section Max Length

R2 Series Piping Restrictions

Piping Length (>1 BC Controller for 2 Outdoor Units)

Total Piping LengthFurthest Piping LengthLength Between OU and BCLength Between Furthest IU and BCHeight Between OU and IU (OU above IU)Height Between OU and IU (OU below IU)Height Between IU and BCHeight Between IU and IUHeight Between BC (Main or Sub) and BC (Sub)Length Between Main OU and Sub OUHeight Between Main OU and Sub OU

F+G+A+B+C+D+E+a+b+c+d+e+fF(G)+A+C+E+f

F(G)+AB+d or C+D+e or C+E+f

HH1

h1h2h3

F+G or Hh4

(See Table 1)165m

110m*1

60m*2 (40m)50m40m15m15m15m5m

0.1m

*1 Please refer to Graph 1. *2 Height difference between BC controller and furthest indoor unit is zero.

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 24: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

BC Controllers

CMB-P104V-G CMB-P105V-G CMB-P106V-G

BC Controllers

Model ReferenceNumber of Connections

Weight (kg)

Dimensions (mm) WidthDepthHeight

Electrical Supply

Phase

Power Input (kW)

Running Current (A)

Fuse Rating (BS88) - HRC (A)

Mains Cable No. Cores

4

24

648362 + 70

284

220-240v, 50Hz

Single

0.085

0.36

6

3

5

27

648362 + 70

284

220-240v, 50Hz

Single

0.104

0.44

6

3

6

29

648362 + 70

284

220-240v, 50Hz

Single

0.123

0.52

6

3

CMB-P104V-GB

Slave BC ControllersModel ReferenceNumber of Connections

Weight (kg)

Dimensions (mm) WidthDepthHeight

Electrical Supply

Phase

Power Input (kW)

Running Current (A)

Fuse Rating (BS88) - HRC (A)

Mains Cable No. Cores

4

22

648362 + 70

284

220-240v, 50Hz

Single

0.076

0.32

6

3

CMB-P108V-GB

8

32

648362 + 70

284

220-240v, 50Hz

Single

0.151

0.63

6

3

CMB-P108V-GA

Master BC Controllers

Model ReferenceNumber of Connections

Weight (kg)

Dimensions (mm) WidthDepthHeight

Electrical Supply

Phase

Power Input (kW)

Running Current (A)

Fuse Rating (BS88) - HRC (A)

Mains Cable No. Cores

8

44

1110450 + 70

289

220-240v, 50Hz

Single

0.161

0.68

6

3

CMB-P1010V-GA

10

49

1110450 + 70

289

220-240v, 50Hz

Single

0.198

0.83

6

3

CMB-P1013V-GA

13

57

1110450 + 70

289

220-240v, 50Hz

Single

0.255

1.07

6

3

CMB-P1016V-GA

16

64

1110450 + 70

289

220-240v, 50Hz

Single

0.312

1.30

6

3

CMB-P1016V-HA

16

73

1110450 + 70

289

220-240v, 50Hz

Single

0.312

1.30

6

3

CMB-P1016V-HB

16

57

1098362 + 70

284

220-240v, 50Hz

Single

0.301

1.26

6

3

Note: CMB-P-V-G units are for use with PURY-(E)P200-350 YHM-A outdoor unit only.

Note: CMB-P-V-GA units are for use with PURY-(E)P200-650Y(S)HM-A outdoor units only. CMB-P1016V-HA unit is for use with PURY-P700-800YSHM-A outdoor units only.

Note: CMB-P1016V-HB can be connected to a CMB-P1016V-HA.

24

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 25: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

25

Indoor unit specifications

PEFY-P15VMS1-E

PEFY-P-VMS1-E

Model Reference

Capacity (kW) Heating (nominal)

Cooling (nominal)

R410A Heating (UK)

R410A Cooling (UK)

R410A High Sensible Cooling (UK)

SHF R410A (UK)

High Sensible R410A (UK

Power Input (kW) Heating (nominal)

Cooling (nominal)

Airflow (m3/min) Lo-Mi-Hi

External Static Pressure (Pa) Lo-Mi1-Mi2-Hi

Noise (dBA) (5Pa) Lo-Mi-Hi

Weight (kg)

Dimensions (mm) Width

Depth

Height

Electrical Supply

Phase

Running Current (A) Heating

Cooling

Fuse Rating (BS88) - HRC (A)

Mains Cable No. Cores

1.9

1.7

1.8

1.5

1.2

0.93

1.00

0.03

0.05

5.0-6.0-7.0

5-15-35-50

22-24-28

19

700

700

200

220-240v, 50Hz

Single

0.31

0.42

6

3

PEFY-P20VMS1-E

2.5

2.2

2.3

2.0

1.6

0.85

1.00

0.03

0.05

5.5-6.5-8.0

5-15-35-50

23-25-29

19

700

700

200

220-240v, 50Hz

Single

0.36

0.47

6

3

PEFY-P25VMS1-E

3.2

2.8

3.0

2.5

2.0

0.84

0.90

0.04

0.06

5.5-7.0-9.0

5-15-35-50

24-26-30

19

700

700

200

220-240v, 50Hz

Single

0.39

0.50

6

3

PEFY-P32VMS1-E

4.0

3.6

3.7

3.2

2.6

0.78

0.85

0.05

0.07

6.0-8.0-10.0

5-15-35-50

24-27-32

20

700

700

200

220-240v, 50Hz

Single

0.39

0.50

6

3

PEFY-P40VMS1-E

5.0

4.5

4.6

4.0

3.3

0.75

0.82

0.05

0.07

8.0-9.5-11.0

5-15-35-50

28-30-33

24

900

700

200

220-240v, 50Hz

Single

0.45

0.56

6

3

6.3

5.6

5.8

5.0

4.1

0.74

0.78

0.07

0.09

9.5-11.0-13.0

5-15-35-50

30-32-35

24

900

700

200

220-240v, 50Hz

Single

0.56

0.67

6

3

PEFY-P63VMS1-E

8.0

7.1

7.4

6.3

5.2

0.75

0.79

0.07

0.09

12.0-14.0-16.5

5-15-35-50

30-33-36

28

1100

700

200

220-240v, 50Hz

Single

0.61

0.72

6

3

PEFY-P50VMS1-E

PFFY-P20VLRMM-E

PFFY-P-VLRMM-E

Model Reference

Capacity (kW) Heating (nominal)

Cooling (nominal)

R410A Heating (UK)

R410A Cooling (UK)

R410A High Sensible Cooling (UK)

SHF R410A (UK)

High Sensible R410A (UK)

Power Input (kW) Heating (nominal)

Cooling (nominal)

Airflow (m3/min) Lo-Mi-Hi

External Static Pressure (Pa) Lo-Mi-Hi

Noise (dBA) (20Pa) Lo-Mi-Hi

Weight (kg)

Dimensions (mm) Width

Depth

Height

Electrical Supply

Phase

Running Current (A) Heating

Cooling

Fuse Rating (BS88) - HRC (A)

Mains Cable No. Cores

2.5

2.2

2.3

2.0

1.6

0.80

0.88

0.04

0.04

4.5-5.5-6.5

20-40-60

31-36-40

18.5

886

220

639

220-240v, 50Hz

Single

0.34

0.34

6

3

PFFY-P25VLRMM-E

3.2

2.8

3.0

2.5

2.0

0.76

0.80

0.04

0.04

4.5-5.5-6.5

20-40-60

31-36-40

18.5

886

220

639

220-240v, 50Hz

Single

0.34

0.34

6

3

PFFY-P32VLRMM-E

4.0

3.6

3.7

3.2

2.6

0.75

0.81

0.04

0.04

6.5-7.5-9

20-40-60

27-32-37

20

1006

220

639

220-240v, 50Hz

Single

0.38

0.38

6

3

PFFY-P40VLRMM-E

5.0

4.5

4.6

4.0

3.3

0.75

0.79

0.05

0.05

8-9.5-11

20-40-60

30-36-40

21

1006

220

639

220-240v, 50Hz

Single

0.43

0.43

6

3

PFFY-P50VLRMM-E

6.3

5.6

5.8

5.0

4.1

0.76

0.80

0.05

0.05

10-12-14

20-40-60

32-37-41

25

1246

220

639

220-240v, 50Hz

Single

0.48

0.48

6

3

8.0

7.1

7.4

6.3

5.2

0.73

0.79

0.07

0.07

11-13-15.5

20-40-60

35-40-44

27

1246

220

639

220-240v, 50Hz

Single

0.59

0.59

6

3

PFFY-P63VLRMM-E

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 26: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

26

Accessories / Optional Extras

CMY-Y102S-G2CMY-Y102L-G2CMY-Y202-G2CMY-Y302-G2CMY-Y104-GCMY-Y108-GCMY-Y1010-GCMY-Y62-G-ECMY-Y100VBK2CMY-Y200VBK2CMY-Y300VBK2CMY-R100VBKCMY-R200VBKACH1ACOUSTIC KIT

PLP-6BASLP-2AAPAC-SH53TM-EPAC-SH59KF-EPLP-6BALMPLP-6BAJPAC-SA1ME-EPAR-SA9FA-ES70E40714

CMP-P40VLW-BCMP-P63VLW-BCMP-P100VLW-BCMP-P125VLW-BPAC-KH11OF

PMP-40BM

PAC-KE03DM-FPAC-KE04DM-FPAC-KE88LAFPAC-KE89LAFPAC-KE80TB-FPAC-KE140TB-F

CMY-R160-JCMY-Y102S-G

PAC-SE41TS-E

- Branch Pipe (Joint) for size 200 or below - total capacity of indoor units- Branch Pipe (Joint) for size 201-400 - total capacity of indoor units- Branch Pipe (Joint) for size 401-650 - total capacity of indoor units or first branch of P500-P650- Branch Pipe (Joint) for size 651 or above - total capacity of indoor units or first branch of P700-P1250- Branch Pipe (Header) for 4 branches- Branch Pipe (Header) for 8 branches- Branch Pipe (Header) for 10 branches- Branch Pipe for 2 branches (PUMY)- Twinning Kit for PUHY-P500-650YSHM-A / PUHY-EP400-650YSHM-A- Twinning Kit for PUHY-P700-900YSHM-A- Twinning Kit for PUHY-P950-1250YSHM-A / PUHY-EP700-900YSHM-A- Twinning Kit for PURY-P500-650YSHM-A / PURY-EP400-600YSHM-A- Twinning Kit for PURY-P700-800YSHM-A- PQFY Auto-Changeover controller- Acoustic kits for PUHY and PURY units

- Grille for PLFY-P-VBM-E- Grille for PLFY-P-VCM-E- Multi-function casement for PLFY-P-VBM-E- High efficiency filter for PLFY-P-VBM-E- Grille and infra-red controller for PLFY-P-VBM-E- Grille with filter lowering function for PLFY-P-VBM-E- ‘I See Sensor’ corner panel for PLFY-P-VBM-E- Infra-red signal receiver for PLFY-P-VBM-E- Infra-red Controller (PAR-SL97A-E) for PLFY-P-VBM-E

- Grille for PLFY-P20-40VLMD-E- Grille for PLFY-P50-63VLMD-E- Grille for PLFY-P80-100VLMD-E- Grille for PLFY-P125VLMD-E- OA duct flange for PLFY-P20-100VLMD-E

- Grille for PMFY-P-VBM-E

- Drain lift-up mechanism for PEFY-P-VMM-E- Drain lift-up mechanism for PEFY-P-VMH-E- Long life filter for PEFY-P80VMH-E- Long life filter for PEFY-P100-140VMH-E- Filter box for PEFY-P80VMH-E (necessary when long life filter is used)- Filter box for PEFY-P100-140VMH-E (necessary when long life filter is used)

- Joint pipe- Branch pipe

- Remote sensor

Outdoor Units

4-Way Blow Cassette Units

2-Way Blow Cassette Units

1-Way Blow Cassette Units

Ceiling Concealed Ducted Units

BC Controllers

Indoor Units

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 27: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

Constant &comfortableindoor climateswith the new City MultiYHM-A range

For more information on Mitsubishi Electric visit www.barbourcompendium.co.uk.

Page 28: City Multi YHM-A Range Brochure · A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss)

UNITED KINGDOM Mitsubishi Electric Europe Air Conditioning Systems DivisionTravellers Lane, Hatfield, Hertfordshire, AL10 8XB, England. General enquiries Tel: 01707 282880 Fax: 01707 278674

IRELAND Mitsubishi Electric Europe Westgate Business Park, Ballymount, Dublin 24, Ireland. Tel: Dublin (01) 419 8800 Fax: Dublin (01) 419 8890 International code: (003531)

Country of origin: United Kingdom – Japan – Thailand – Malaysia. ©Mitsubishi Electric Europe 2008. Mitsubishi and Mitsubishi Electric are trademarks of Mitsubishi Electric Europe B.V. The company reserves the right to make any variation in technical specification to the equipment described or to withdraw or replace products without prior notification or public announcement. Mitsubishi Electric is constantly developing and improving its products. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All goods are supplied subject to the Company’s General Conditions of Sale, a copy of which is available on request. Third-party product and brand names may be trademarks or registered trademarks of their respective owners.

Printed in January 2008

SAP No. 212984

Telephone: 01707 282880Post Sales Technical Support: 0870 3000 300Spares and Warranty Support: 0870 3000 800

email: [email protected] web: www.mitsubishielectric.co.uk/aircon