chiller system (igbc-2016)finalv3 · low flow condenser : hd(m) kw ... design for low pressure...
TRANSCRIPT
K Y YowDir, Technical Center of ExcellenceTrane, Ingersoll Rand
Latest Trends in Chiller System Technologies
IGBC Conference 2016Grand Hyatt ,Mumbai 06-08 Oct 2016
Agenda
� Chiller vs Chiller Plant
� ASHRAE GreenGuide - Performance Goals of Chiller Pl ant
� Distribution Efficiency – Low Resistance and Low Flo w/Rt
� Design For Low Pump Head
� Variable Primary Flow
� Singapore case Studies ( GreenMark Platinum Plants)
� Recommended Key Technologies ( Product & System)
Chiller is just a part of Chiller System
Chiller
PLANT
Chiller
PLANT
Pumps
Chiller
Chillers
Cooling Towers
Controls
High Performance Chiller High Performance Chiller System
Multi-stage/Multiple/VSD/compressorDirect drive / Gear drive/Oiless (MB, Ceramics)Adaptive Controls
Holistic Approach to Building efficiency
(0.48 to 0.52 kw/Rt at AHRI conditions) (0.52 to 0.60 kw/Rt at Operating conditions)
M&V
(Product level Technologies)
Energy efficient HVAC systems are the key
Key: Energy Efficiency of HVAC System
Every Building can be a High Performance Building
By Design Through Upgrade
Good for business & Responsible to environment
Without compromising comfort or productivity
Energy Use Cost Emis sions
Chiller Plant Performance Goals
Big opportunity to Reduce KWI of Ancillary Equipment
( ASHRAE GreenGuide)
Reduces2/3
Ancillary
Reduces 1/3 Energy
Both NEW & Existing
ASHRAE GreenGuide
( DT : 7C-11C)
( DT : 7C-10C)
LOW FLOW Design => Low Distribution Energy
*ASHRAE 90.1(2016) will have Addendum :15F (8.3C) DT as a Prescriptive Requirement ( Exceptions Apply)
Chilled Water Pump : Kw/Rt is function of (Flow per RT) and Head
Head(m)
Kw per /M3/S
STD
LARGE
2.40 GPM/RT to 1.67 GPM/RT => Low Pumping Kw/Rt (0. 02)
Pumping Energy Performance Index Table
( Maintain same pipe size)
Delta T
Deg C Gpm/Rt Lps/Rt 10 15 20 25 30 40
127 190 253 316 380 506
3 4.45 0.280 0.035 0.053 0.071 0.089 0.106 0.142
4 3.34 0.210 0.027 0.040 0.053 0.066 0.080 0.106
5 2.67 0.168 0.021 0.032 0.043 0.053 0.064 0.085
5.56 2.40 0.151 0.019 0.029 0.038 0.048 0.057 0.077
6 2.22 0.140 0.018 0.027 0.035 0.044 0.053 0.071
7 1.91 0.120 0.015 0.023 0.030 0.038 0.046 0.061
8 1.67 0.105 0.013 0.020 0.027 0.033 0.040 0.053
9 1.48 0.093 0.012 0.018 0.024 0.030 0.035 0.047
10 1.33 0.084 0.011 0.016 0.021 0.027 0.032 0.043
Flow/Rt Pump Kw/Rt at different Heads
Hd varies with GPM 1.8
Smaller Pump/Electricals : Savings re-invest in Higher EFF Chillers
Condenser Water Pump :
Hd(m)
Kw per /M3/S
3.0 GPM/Rt to 2.0 GPM/Rt => Low Pumping Kw/Rt (0.02 4)
STD
LARGE
Delta T
Deg C Gpm/RtLps/Rt 10 15 20 25 30 35
127 190 253 316 380 443
3 5.30 0.334 0.042 0.063 0.084 0.106 0.127 0.148
4 3.98 0.250 0.032 0.048 0.063 0.079 0.095 0.111
5 3.18 0.200 0.025 0.038 0.051 0.063 0.076 0.089
5.3 3.00 0.189 0.024 0.036 0.048 0.060 0.072 0.084
6 2.65 0.167 0.021 0.032 0.042 0.053 0.063 0.074
7 2.27 0.143 0.018 0.027 0.036 0.045 0.054 0.063
8 1.99 0.125 0.016 0.024 0.032 0.040 0.048 0.055
9 1.77 0.111 0.014 0.021 0.028 0.035 0.042 0.049
10 1.59 0.100 0.013 0.019 0.025 0.032 0.038 0.044
Flow/Rt Pump Kw/Rt at different Heads
Smaller Pumps/Electricals and Smaller Cooling Tower ( due to Bigger Range)
LOW FLOW Condenser :
Hd(m)
Kw per /M3/S
Benefit of Low Flow Expands at partload Conditions
STD
LARGE
Delta T
Deg C Gpm/RtLps/Rt 10 15 20 25 30 35
127 190 253 316 380 443
3 5.30 0.334 0.042 0.063 0.084 0.106 0.127 0.148
4 3.98 0.250 0.032 0.048 0.063 0.079 0.095 0.111
5 3.18 0.200 0.025 0.038 0.051 0.063 0.076 0.089
5.3 3.00 0.189 0.024 0.036 0.048 0.060 0.072 0.084
6 2.65 0.167 0.021 0.032 0.042 0.053 0.063 0.074
7 2.27 0.143 0.018 0.027 0.036 0.045 0.054 0.063
8 1.99 0.125 0.016 0.024 0.032 0.040 0.048 0.055
9 1.77 0.111 0.014 0.021 0.028 0.035 0.042 0.049
10 1.59 0.100 0.013 0.019 0.025 0.032 0.038 0.044
Flow/Rt Pump Kw/Rt at different Heads
At Constant Flow, STD 3.0 GPM/RT Design can hit >0.1 Kw/Rt at 50-60% load
GPM/RT increases during chiller Partload => Higher Kw/Rt
KWI Savings Expands at Part Load
Design for LOW Pressure Resistance CHW/CW SystemGoal : Max 15 - 20m ( CHW)
Max 10 -12m ( CW)
� Low WPD Chiller Evap/Cond ( <4m)
� Avoid 90 Deg Bends in Piping� Over Size Riser Pipe where
justified� Avoid use of Balancing Valve� Locate CT near plantroom� Elevate Pumps to same elevation
as chiller connection
� Replace 4 X 650Rt with 3 X 700 RT� Relocate Chiller plant to Carpark� Locate new CTs next to plant� Re-design with VPF (existing Pri-Sec)� Remove Balancing Valves
Green Energy Management (GEM) Project by Grand Hyatt Spore (1999)
1.0 Kw/Rt to 0.59 Kw/Rt
Case Study 1 : Hotel
A/C A/C
BAS
Airside
Existing Air-cooled Chiller plant >1.3 Kw/RT
Case Study 2 : Existing Office Building
Operating0.56 Kw/rt
Retrofit : ( 2 x 500 RT ) 0.514 Kw/RT
Ancillary Kw/Rt = 0.041 ( 8% of System)
8C CHW(select at6.7C)
Case Study 3 : Existing Commercial Bldg
3.5 Million Sq Ft Business Park Development ( 7,000 RT)
Sustaining 0.58 Kw/RT since completion in 2010 ( 6Y operation)
Case Study 4 : Existing Business Park Performance Audit after 6 Yrs
Meeting the GreenGuide Goals of 0.55 Kw/Rt Plant ?
6.2 C , Tropics Temperate Climate
0.503
0.015
0.024
0.005
Site
0.547
Case Study : A Singapore Site ( 3600 RT at 6,2C)
Singapore Project achieving 0.55 Kw/Rt ( Average 0 .57 )
M+V Captures and Display All Essential Data for Analytics
Ministry of the Environment and Water Resources, Si ngapore
Energy saving system design
Improvement 35%(0.86 to 0.57 Kw/Rt)
Scope: • 1 x 850RT Low-pressure Centrifugal Chillers (0.48 Kw/Rt) replacing existing 2 X 500 RT R134a chiller( 8 yrs Old)• New chilled water and condenser water pumps c/w VSD• System efficiency of <0.60kW/RT
GreenMark Platinum
Case Study 5 : Govt Building
2012 Energy Retrofit ( Guaranteed Energy Savings Performance)
Energy Retrofit is more than one-to-one chiller Cha nge-out
Re-configure Pumping ( Pri-Sec to VPF)Re-Engineer Piping layout to Minimise Friction Loss
STRAIGHT CW PIPE CONNECTION TO CHILLER
CWS PIPE NOZZLE
Many pipe bends and turns – high frictional loss CHW/CW water
distribution system
Balancing valve - high
∆∆∆∆P
BEFORE AFTER
Components Recommended Performance
System Optimisation( New/Existing Plants)
Chillers 0.48-0.52 Kw/Rt (rated at AHRI conditions)Low Water pressure Drop (<3m)
Optimise ( Not one-to-one changeout)Large DT ( CHW 7-11C)/ (CW 7-10C) Convert to Variable Primary FlowCHW Temp: 5 to 7.5C Can consider Reset (Operation).
Pumps/Motors Min 85% (P) /93%(M) Eff CHW/CW Kw/Rt < 0.03CHW Head <20mCW Head <15m
VSD for CHW PumpsVSD for CW Pumps (optional)
Cooling Towers Kw/Rt <0.03Exceeds 90.1 Rating requirement
Equipped with VSDProvide Extra CTs if possible(Good for Optimisation)
Piping LOW Resistance Retrofit to :Avoid 90 Deg. BendsAvoid Bal ValvesLayout Piping first
M+V Investment Grade (SS591/IPMVP STDS)
Continuous Monitoring and Optimisation
Designing High Performance Chiller Plant ( Better than 0.60 Kw/Rt)
Recommended Technologies For Designing better than 0.60 Kw/Rt Plant
Simple Technologies for Breakthrough Performance in Existing Buildings
<0.60Kw/Rt
PLANT
<0.60Kw/Rt
PLANT
Pumps
Chillers
Cooling Towers
Controls
M&V
Thank You