chilled water thermal energy storage –– an alternative to ... water storag… · –– an...

Download Chilled Water Thermal Energy Storage –– an Alternative to ... Water Storag… · –– an Alternative to Static Icean Alternative to Static Ice. ... an Alternative to Static

If you can't read please download the document

Upload: dangdien

Post on 06-Feb-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • FEFPA Summer 2015

    Chilled Water Thermal Energy StorageChilled Water Thermal Energy Storage an Alternative to Static Icean Alternative to Static Ice

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Presentation By:Presentation By:

    Marc Rouleau, PEMarc Rouleau, PEExecutive Director of Facilities Management,District School Board of Collier County

    Adrian Roman, RA, AIAAdrian Roman, RA, AIADistrict Architect / Facilities Planning and Design,District School Board of Collier County

    Lawrin T. Ellis, PE, LEED AP,Lawrin T. Ellis, PE, LEED AP, CxACxAPrincipal / Senior Mechanical Engineer,TLC Engineering for Architecture

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Presentation OutlinePresentation Outline Introduction to Thermal Energy

    Storage (TES) Basic Design of Chilled Water

    Storage Systems Tank Location Construction of Chilled Water

    Storage Tank Operation of Chilled Water Storage

    Systems Economic Comparison of Chilled

    Water vs. Static Ice

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Introduction to Thermal Energy StorageIntroduction to Thermal Energy StorageThermal Energy Storage (TES)

    Basic Concept TES Systems remove heat from or add heat to astorage medium for use at another time

    Most Common Application is Comfort Cooling Energy is Charged, Stored, and Discharged - Can be Daily, Weekly,

    or Seasonally Storage unit is Ton-hour Means to Reduce Total Utility Bill and/or Size of Equipment

    Applications that Benefit from TES Loads are Cyclical Energy Costs are Time-Dependent (Time-of-Use Rate) Utility Rebates or Economic Incentives for Load-Shifting Equipment

    Focus on Static Ice and Chilled Water Storage

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Introduction to Thermal Energy StorageIntroduction to Thermal Energy StorageThermal Energy Storage (TES) - Static Ice

    Typical Storage Medium Water, due to High Latent Heat Capacityof 144 Btu/lb

    Latent Technology achieves capacity through change of state fromSolid to Liquid during Melt process

    Typically Requires about 1.455 ft3 ice per ton-hour of cooling Example 5,000 ton-hours Cooling requires 7,275 ft3 ice (roughly

    54,420 gallons/water)

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Introduction to Thermal Energy StorageIntroduction to Thermal Energy StorageThermal Energy Storage (TES) - Chilled Water

    Typical Storage Medium Water, specific heat of 1 Btu/lbF Sensible Technology achieves capacity through high specific heat of

    water Requires about 10.66 ft3 water per ton-hour (at 20 Degrees Delta T) Example 5,000 ton-hours Cooling requires 53,300 ft3 water (roughly

    398,725 gallons/water)

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsTypes of Chilled Water Storage Systems

    Simplest Form Series Storage Tank Effective at reducing on-peak electric demand Drawbacks Tendency for stagnation, Higher leaving water

    temperatures

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsTypes of Chilled Water Storage Systems

    Multiple Tanks Parallel Storage Tanks Minimizes stagnation associated with Series Tank Drawbacks Need accurate means of measuring tank volume,

    Complex Controls to ensure proper sequencing

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsTypes of Chilled Water Storage Systems

    Most Common Stratified Storage Tanks, System Preferredby Collier County Schools

    Exploits tendency of warm and cold water to stratify Drawbacks Requires specifically engineered diffusers

    designed to promote stratification

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsStratified Storage Tanks - Understanding Thermocline

    Naturally occurring change in density of water between 44-54degrees.

    Thermal layer separating warmer water at top from coolerwater at bottom.

    Design of Stratification Diffusers optimized to maintainThermocline.

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsStratified Storage Tanks Tank Sizing Estimates

    Building/Campus Load Profile Summer Peak Full Storage Shift TES Covers Load (Typical Operation) Total Capacity based on Ton-Hours Shifted

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsStratified Storage Tanks Tank Sizing Estimates

    Building/Campus Load Profile Summer Peak Part Storage Shift TES Covers Peak Loads, Alternate

    Approach to Full Shift

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsStratified Storage Tanks Tank Sizing Estimates

    Florida Power and LightTime of Use Tariff Summer and Winter PeakPeriods

    TES Operates During On-Peak Periods to MinimizeEnergy Costs

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsStratified Storage Tanks Tank Sizing Estimates

    Tank Storage Volume Calculation using Figure of Merit FOM of Sizing Estimates is approximately 0.9 (90%)

    Given FOM, Total Ton-Hrs and Tank Differential Temperature,solve of Volume Using:

    Note: Specific Gravity of Water at 50F is approximately 1.0.

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Design of Chilled Water Storage SystemsDesign of Chilled Water Storage SystemsStratified Storage Tanks Estimating Tank Geometry

    Tall, Slender Tanks are Preferred to Optimize Thermocline andMinimize Footprint

    Where practical, Tank Height should be greater than highestair vent in Chilled Water Lines Prevents Drainback

    Quick Formula for Tank Sizing:Volume, gallons = 5.875D2H

    whereD = Inside Tank Diameter, Feet

    H = Height of Water, Feet

    Assuming 750,000 gallons (6,583 Ton-hrs at 14 Degree Delta T) andDiameter of 50 feet, Height of Water is approximately 51.06 feet.

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank LocationAfter tank sizing estimates - but prior to construction -

    determine tank location

    Location can have a profound impact on cost, campusappearance and your relationship with the community

    Determining location is a balancing act school needs,cost, community concerns

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank LocationFirst step Review Local Ordinances

    Height restrictions Aesthetic limitations Prohibited structures Florida Statutes 1013.37(1)(a) and Florida Building Code 423.2.2

    exempts District from compliance with local Ordinances

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank LocationNext Determine optimal location(s)

    Distance from chiller plant and buildings Tank can act as chiller plant sound block Shield tank with buildings May be limited by retention areas, sporting fields, easements, terrain

    features, buried utilities

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank Location Conduct Internal Review

    Generate renderings All proposed locations Highlight potential visual impacts Illustrate plan to eliminate or minimize visual impacts

    Review locations with Principal and other stakeholders (maintenance,facility manager)

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank LocationRenderings may look like this view from above

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank LocationWith ground level views

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank Location

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank Location

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Tank LocationTank LocationMeet with local officials and community members

    Review HVAC system and main components HVAC Impact on student health and comfort Review utility rate structures Introduce concept of chilled water thermal energy storage Chilled water storage benefits

    Lower electric bill more than $5,000/month Extend life of chiller plant

    Review scope of work Present renderings to illustrate visual impact

    Emphasize reduced impact using paint and landscaping

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tanks

    Common construction for Tanks Steel and Pre-stressed Concrete

    Pre-stressed Concrete mostCommon for Larger Systems

    Typical Construction Concrete Base, Steel Diaphragm Wall with

    interior/exterior shotcrete on pre-stressed reinforcement (inside andoutside),

    Concrete Dome with InteriorInsulation,

    Exterior insulation, Exterior finish EIFS or Aluminum

    Siding

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Concrete Base

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Steel Diaphragm

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank - Steel Diaphragm, Readyfor Shotcrete

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Exterior Shotcrete

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Interior Prep/Shotcrete

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Installation of Dome

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Interior with Dome and Diffuser

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Exterior Finish Installation

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank Exterior Finish, Painted Siding

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Chilled Water Storage Tank ConstructionChilled Water Storage Tank ConstructionStratified Storage Tank FillEr Up!

    Utility Costs Coordination:Meet early with local water purveyorto establish sewer credits for wateruse during construction and tank fill.Temporarily install dedicated watermeter.

    Water Treatment Coordination:Account for adding inhibitor andbiocide to full tank prior to finalconnection to chilled water piping.

    Tank Settlement Survey:Allow 4-6 weeks for tank settlementfollowing fill. Verify with survey,minimum of three points on tank.

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation ofOperation of Static Ice TESStatic Ice TESMain Components in a Static Ice TES

    Chillers, 25% Glycol Brine Solution Nominal 23F Operation Static Ice Tanks Glycol /Chiller Loop Pumps Glycol Make-up/Mixing Tank Heat Exchanger Three-Way Isolation/Diverting Valves Ice Farm Piping and Low Temp Insulation (3-Inch Nominal)

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation ofOperation of Static IceStatic IceCentral Energy Plant with Static Ice TES

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation ofOperation of Static Ice TESStatic Ice TES

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation ofOperation of Static ice TESStatic ice TES

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation ofOperation of Static Ice TESStatic Ice TES

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation of Chilled Water StorageOperation of Chilled Water StorageMain Components in a Chilled Water TES

    Chillers, Water - Nominal 42F Operation Chilled Water Storage Tank Chiller Loop Pumps Two-Way Isolation Valves Storage Tank Piping with Standard Temp Insulation (2-Inch Nominal)

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation of Chilled Water StorageOperation of Chilled Water StorageCentral Energy Plant with Chilled Water StorageTES

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation of Chilled Water StorageOperation of Chilled Water Storage

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation of Chilled Water StorageOperation of Chilled Water Storage

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation of Chilled Water StorageOperation of Chilled Water Storage

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation of Chilled Water StorageOperation of Chilled Water StorageComparison of Chiller Performance Air Cooled

    Nominal 500-Ton Air Cooled Chiller, 25% Glycol Brine Solution Chilled Water Supply Temp 23F Operation during Ice Make Mode: Chiller Capacity

    352 Tons, Chiller Efficiency 1.24 kW/Ton at 80F Ambient Chilled Water Supply Temp 40F Operation during Chiller Mode: Chiller Capacity

    477 tons, Chiller Efficiency 1.13 kW/Ton at 85F Ambient

    Nominal 500-Ton Air Cooled Chiller, Water Chilled Water Supply Temp 42F Operation during Chilled Water Storage Charge

    Mode: Chiller Capacity 518 Tons, Chiller Efficiency 1.03 kW/Ton at 80F Ambient Chilled Water Supply Temp 42F Operation during Chiller Mode: Chiller Capacity

    503 tons, Chiller Efficiency 1.10 kW/Ton at 85F Ambient

    Chiller Capacity/Efficiency Comparison Additional 166 TonsCapacity and 0.21 kW/Ton Efficiency Gain in Chilled Water Charge vs.Ice Make Modes

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Operation of Chilled Water StorageOperation of Chilled Water StorageComparison of Chiller Performance Water Cooled

    Nominal 500-Ton Water Cooled Chiller, 25% Glycol Brine Solution Chilled Water Supply Temp 23F Operation during Ice Make Mode: Chiller Capacity

    374 Tons, Chiller Efficiency 0.835 kW/Ton at 80F Entering Condenser Water Chilled Water Supply Temp 40F Operation during Chiller Mode: Chiller Capacity

    480 tons, Chiller Efficiency 0.661 kW/Ton at 85F Entering Condenser Water

    Nominal 500-Ton Water Cooled Chiller, Water Chilled Water Supply Temp 42F Operation during Chilled Water Storage Charge

    Mode: Chiller Capacity 500 Tons, Chiller Efficiency 0.488 kW/Ton at 80FEntering Condenser Water

    Chilled Water Supply Temp 42F Operation during Chiller Mode: Chiller Capacity 480 tons, Chiller Efficiency 0.541 kW/Ton at 85F Entering Condenser Water

    Chiller Capacity/Efficiency Comparison Additional 126 TonsCapacity and 0.281 kW/Ton Efficiency Gain in Chilled Water Chargevs. Ice Make Modes

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison First Costs

    Gulf Coast High School, Laurel Oak Elementary School Static Ice at both Schools - GCHS Water-Cooled Plant, LOES Air Cooled Plant Both Plants in CIP for Maintenance Replacement Alternate Option to Provide Centralized Plant with TES Feasibility Study

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison First Costs

    GCHS/LOES Direct Replacement CEP First Cost Comparisons Pricing Estimates for Replacing Each Plant with Similar Equipment and Replacing Ice

    at Each School Alternate to Provide Centralized Campus Chilled Water Plant Considered Air-

    Cooled and Water-Cooled Options

    Direct Replacement of Systems at GCHS (Including Ice) - $1,667,150 Two Nominal 450-ton Ice Chillers; One Nominal 215-ton Base-load Chiller; 4,850 Ton-

    hours TES Static Ice

    Direct Replacement of Systems at LOES (Including Ice) - $ 618,325 Two Nominal 170-ton Ice Chillers; 2,500 Ton-hours TES Static Ice

    Total Direct Replacement Cost Estimate - $ 2,285,475

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison First Costs

    GCHS/LOES Centralized CEP First Cost Comparisons Alternate to Provide Centralized Campus Chilled Water Plant Considered Air-

    Cooled and Water-Cooled Options Added Additional 5-Percent Capacity in TES for Future Campus Growth, Additional

    Chiller Redundancy for TES Charging

    Centralized CEP with Redundancy and Chilled Water Storage Three Nominal 500-ton Chillers, 7,700 Ton-hrs of Chilled Water TES

    First Cost Estimate for Air Cooled Chiller Plant - $ 2,373,925

    First Cost Estimate for Water Cooled Chiller Plant - $ 2,985,750

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison First Costs

    GCHS/LOES Centralized CEP First Cost Comparisons Alternate to Provide Centralized Campus Chilled Water Plant Considered Air-

    Cooled and Water-Cooled Options Added Additional 5-Percent Capacity in TES for Future Campus Growth, Additional

    Chiller Redundancy for TES Charging

    Centralized CEP with Redundancy and Chilled Water Storage Three Nominal 500-ton Chillers, 7,700 Ton-hrs of Chilled Water TES

    First Cost Estimate for Air Cooled Chiller Centralized Plant with ChilledWater Storage vs. Direct Replacement - $ 88,150

    First Cost Estimate for Water Cooled Centralized Plant with ChilledWater Storage vs. Direct Replacement - $ 700,275

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison First Costs

    GCHS/LOES Centralized CEP First Cost Comparisons Alternate to Provide Centralized Campus Chilled Water Plant Considered Air-

    Cooled and Water-Cooled Options Added Additional 5-Percent Capacity in TES for Future Campus Growth, Additional

    Chiller Redundancy for TES Charging

    Total Estimated Cost for Static Ice Bank Replacement - $ 735,000

    Total Estimated Cost for Chilled Water Storage Tank - $ 913,000

    Net Add for Chilled Water Storage Tank - $ 178,000

    Estimated FPL Incentive Payment - $ 633,600

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison Energy Costs

    Total Plant Efficiency Direct Replacement Water Cooled Ice Chillers at GCHS Nominal 1.29 kW/ton (Includes Cooling Tower

    Make-up Water) at 630 Chiller Tons for Ice Make Air Cooled Ice Chillers at LOES Nominal 1.34 kW/ton at 240 Chiller Tons for Ice

    Make

    Total Plant Efficiency Centralized CEP with Chilled Water Storage Water Cooled Water Chillers Nominal 0.95 kW/ton (Includes Cooling Tower Make-

    up Water) at 1,000 Chiller tons for Tank Charge Air Cooled Water Chillers Nominal 1.14 kW/ton at 1,000 Chiller tons for Tank

    Charge

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison Energy Costs

    Total Plant Energy Direct Replacement, GCHS Water Cooled Ice Chillers at GCHS 630 Chiller Tons for Ice Make with 4,850 Ton-

    hrs of Ice Storage; Nominal Charge Time of 7.7 Hours At 1.29 kW/ton, 630 Chiller Tons for 7.7 Hours Rough Energy Estimate using FPL

    GSLDT-1, $ 2,584 Demand Charge and $ 272 Energy Charge

    Total Plant Energy Direct Replacement, LOES Air Cooled Ice Chillers at LOES 240 Chiller Tons for Ice Make with 2,500 Ton-hrs of

    Ice Storage; Nominal Charge Time of 10.4 Hours At 1.34 kW/ton, 240 Chiller Tons for 10.4 Hours Rough Energy Estimate using FPL

    GSLDT-1, $ 1,023 Demand Charge and $ 145 Energy Charge

    Total Energy Cost Estimate, Per Ice Bank Charge DirectReplacement for GCHS/LOES

    Demand Charge - $ 3,607 (Monthly) Energy Charge - $ 417 / Charge

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison Energy Costs

    Total Plant Energy Centralized CEP, Water Cooled At 0.95 kW/ton, 1,000 Chiller Tons for 7.7 Hours Rough Energy Estimate using FPL

    GSLDT-1, $ 3,021 Demand Charge and $ 318 Energy Charge

    Total Plant Energy Centralized CEP, Air Cooled At 1.14 kW/ton, 1,000 Chiller Tons for 7.7 Hours Rough Energy Estimate using FPL

    GSLDT-1, $ 3,625 Demand Charge and $ 381 Energy Charge

    Centralized Water Cooled vs. Direct Replacement Approximately $ 586 / Month Demand Savings Approximately $ 99 / TES Charge Energy Savings

    Centralized Air Cooled vs. Direct Replacement Approximately $ 18 / Month Demand Costs Approximately $ 36 / TES Charge Energy Savings

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison Life Cycle Costs

    Comparison of Direct Replacement vs. Centralized CEP with ChilledWater Storage

    25-Year Life Cycle Cost Analysis Assumptions Replacement of Air-Cooled Chillers at Year 15 Replacement of Static Ice Banks at Year 17 Maintenance Costs Energy Costs Water and Water Treatment Costs for Water Cooled Plants

    LCCA for Direct Replacement at GCHS - $ 8,920,694 LCCA for Direct Replacement at LOES - $ 5,427,270

    Combined LCCA for Direct Replacement - $ 14,347, 964

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison Life Cycle Costs

    Comparison of Direct Replacement vs. Centralized CEP with ChilledWater Storage

    25-Year Life Cycle Cost Analysis Assumptions Replacement of Air-Cooled Chillers at Year 15 Maintenance Costs Energy Costs Water and Water Treatment Costs for Water Cooled Plants

    LCCA for Centralized Water Cooled Plant - $ 8,853,915 LCCA for Centralized Air Cooled Plant - $ 13,827,641

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison 25-Year LCCAOwnership and Operating Costs, Including TES

    Centralized Air Cooled CEP vs. Direct Replacement - $ 520,323 Centralized Water Cooled CEP vs. Direct Replacement - $ 5,494,049

    Centralized Water Cooled vs. Air Cooled - $ 4,973,726

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceSystems Economics Comparison 25-Year LCCAOwnership and Operating Costs, Including TES

    Chilled Water Storage is Viable Economic Alternative to Static Ice forLong-term Ownership

    First-Cost Differences between Chilled Water Storage vs. Static IceDiminish as TES Storage Capacity Increases Economy of Scale

    Around 10,000 Ton-hrs of Storage, Costs are almost Identical

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Economics of Chilled Water vs. Static IceEconomics of Chilled Water vs. Static IceComparative Costs for Current Installations

    Gulfview Middle School Tank Construction Cost - $ 452,000 FPL Incentive - $ 209,760 Cost Difference - $ 242,240 Annual Energy Cost Savings - $ 50,000 Payback Approximately 5 Years

    Pelican Marsh Elementary School Tank Construction Cost - $ 791,660 FPL Incentive - $ 231,840 Cost Difference - $ 559,820 Annual Energy Cost Savings Waiting on Complete Year of Data

    Corkscrew Elementary/Middle Schools Tank Construction Cost - $ 966,018 FPL Incentive - $ 380,640 Cost Difference - $ 588,378 Annual Energy Cost Savings Waiting on Complete Year of Data

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    SummarySummary Introduction to Thermal Energy

    Storage (TES) Basic Design of Chilled Water

    Storage Systems Tank Location Construction of Chilled Water

    Storage Tank Operation of Chilled Water Storage

    Systems Economic Comparison of Chilled

    Water vs. Static Ice

  • Chilled Water TES an Alternative to Static IceRouleau, Roman, Ellis 7 July 2015

    Questions?Questions?