Technical surge Session
Hydraulic Transient and Surge Protection Devices
Gwenn A. PHALEMPIN
![Page 2: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/2.jpg)
What Causes Pressure Surges?
Rapid Change in flow rate caused by:Valves (Opening, closing)Pumps (Start-up, stop, power failure)Check Valve (Slamming)Air/Vac Combinations (Air slam)
WORST CASE ANALYSED: Power Failure at Max Flow
![Page 3: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/3.jpg)
What happens when a valve shuts off?
![Page 4: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/4.jpg)
What happens when a pump starts?
![Page 5: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/5.jpg)
What happens when a pump stops?
High Pressure
Low Pressure
![Page 6: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/6.jpg)
What happens when a pump stops or a valve closes rapidly?
UPSREAM:Pressure rises
DOWNSTREAMPressure dropsWater Column Separation
CAVITATION: (Vapor pocket created: -14.5 psi)Flow reverses => water column rejoins.Vapor pocket collapse, high pressure spikes.
![Page 7: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/7.jpg)
Pump trip
Formation of vapor cavity
Growth of vapor cavity
Flow reversal
Steady state
Vapor cavity collapses
BangPressure Spike
Events following a pump trip
Pump trips
---Water pumped to tank
![Page 8: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/8.jpg)
Pump trip - check valve
![Page 9: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/9.jpg)
Surge pressures caused by a pump trip
![Page 10: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/10.jpg)
Damaged valve at pump station
![Page 11: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/11.jpg)
Two Types of Cavitation…
1 - Dynamic Cavitation: On pump impeller
2 – Transient Cavitation: Inside pipes
![Page 12: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/12.jpg)
Dynamic Cavitation – Negative pressure on pump impeller
![Page 13: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/13.jpg)
Vapor pocket collapse effects on pump impellers
![Page 14: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/14.jpg)
If cavitation destroys pump impellers…
What does cavitation do to pipes?
![Page 15: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/15.jpg)
Cavitation inside pipes
Vapor pocket collapses – HIGH PRESSURE
![Page 16: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/16.jpg)
Cavitation inside pipes
Vapor Pocket CollapseErosionFatiguePipe Wall Becomes thinnerPipe break
![Page 17: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/17.jpg)
Pipe lining damaged by negative pressures
![Page 18: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/18.jpg)
Pipe collapse
![Page 19: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/19.jpg)
Costly repairs…
![Page 20: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/20.jpg)
![Page 21: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/21.jpg)
In summary, Pressure Waves…
Origin: Rapid variation of flow velocity
Pressure waves propagate in the systemVelocities up to 4500 fps
Velocity depends on pipe material/diameter/thickness
High points in the system are more at riskMost likely to reach cavitation at high pointWater column separation
Pressure waves are reflected at the ends of the system
![Page 22: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/22.jpg)
Storage tankSame magnitude – opposite sign
Dead EndSame magnitude – same sign
PRESSURE DOUBLES!!
Local head lossPart reflected back – same signPart keeps going – same sign
WAVE REFLECTION
![Page 23: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/23.jpg)
Software animation of pressure waves
![Page 24: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/24.jpg)
How to reduce water hammer?
Flywheel
Vacuum/air release valve combinations
Surge anticipation valve
Variable Frequency Drive (VFD)
Stand pipe
Bypass check valve
Surge vessel
![Page 25: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/25.jpg)
Flywheel
Increase rotating inertia of the pump with a flywheel
Increases energy requirements
Can’t be used on submersible pumps
Accurate balance of the wheel
![Page 26: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/26.jpg)
Vacuum Breaker
May be required as little as every 500ft
Require high maintenance
Reaction time (delay to fully open)
Large volume of air admitted in the pipe
![Page 27: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/27.jpg)
Surge anticipation valve
Surge anticipation valveGood to relieve high pressure Ineffective against low pressure
![Page 28: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/28.jpg)
Variable Frequency Drive (VFD)
Great for normal operationControlled pump startupControlled pump shutdown
Ineffective during power failure
![Page 29: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/29.jpg)
Stand Pipe
Large structureNeeds to be taller than the maximum headExpensive solution
![Page 30: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/30.jpg)
Stand Pipe
![Page 31: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/31.jpg)
Bypass check valve
Needs positive pressure upstream to provide energy
Simple for overcoming negative pressures
Does not provide protection for positive pressures
![Page 32: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/32.jpg)
Surge vessel
•Advantages: Energy Free
Give and receive energy Low maintenance
NEEDS TO BE SIZED PROPERLY with
computer software
![Page 33: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/33.jpg)
Information required to do a surge analysis
Existing Hydraulic ModelEPAnet file export => KYpipe
Hydraulic Information About the SystemDetailed profile of the pipeMaximum and Minimum allowed pressuresMaximum Flow RatePipe characteristics (diameter/material)
![Page 34: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/34.jpg)
Welded Steel Pipe
Allowed negative pressure
-10.0 psig
Speed of pressure waves
1600 fps
![Page 35: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/35.jpg)
Concrete
Allowed negative pressure
0 to -10.0 psig (depending on seals technology)
Speed of pressure waves
1800 fps
![Page 36: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/36.jpg)
Pre-Stressed Concrete
Allowed Negative Pressure: 0 psig
Speed of pressure wave: 1800 fps
![Page 37: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/37.jpg)
HDPE – Thermo-Welded
Allowed negative pressure
-10.0 psig
Speed of pressure waves
800 fps
![Page 38: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/38.jpg)
PVC Pipe
Allowed negative pressure
0 to -3.0 psig
Speed of pressure waves
700 fps
![Page 39: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/39.jpg)
Ductile Iron Pipe
Allowed negative pressure
-6.0 psig
Speed of pressure waves
4500 fps
![Page 40: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/40.jpg)
KYpipe model of potable water distribution system
![Page 41: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/41.jpg)
KYpipe model of potable water distribution system
![Page 42: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/42.jpg)
KYpipe model of Waste Water system
![Page 43: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/43.jpg)
Sizing a surge tank with KYPIPE
Model will help determine the required surge tank’s…VolumeDesign pressureOutlet diameterPrecharge pressure
![Page 44: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/44.jpg)
Surge pressures resulting from a pump trip – with and without surge tank
![Page 45: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/45.jpg)
HYDROPNEUMATIC VESSELS
SURGE PROTECTION PRESSURE REGULATIONPUMP CYCLE CONTROL
COMPRESSOR TYPE
OR
BLADDER TYPE
![Page 46: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/46.jpg)
COMPRESSOR VESSELSAchieve their balance through a complicated system of controls.
- Air Receivers- Solenoid valves- Measuring Probes- Compressor- Control Panel
All these require constant maintenance, otherwise the system is not protected against water hammer.
The permanent dissolution of air into the water will eventually reappear elsewhere in the system. $$$$$$$$$$$$$$$$$$
![Page 47: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/47.jpg)
BLADDER VESSELSHydraulically work the same as
compressor tanks.
The major differences are…
- Precharge air is permanently contained within the vessel.
- Air doesn’t dissolve in the liquid
NO NEED FOR COMPRESSOR
STAND ALONE SYSTEM
LOW MAINTENANCE
![Page 48: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/48.jpg)
- Liquid contained within a rubber bladder.
- Bladder acts as a barrier between the gas and the liquid
- Predetermined precharge (air or nitrogen) is trapped between the shell and the bladder.
- Anti-extrusion grid
![Page 49: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/49.jpg)
![Page 50: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/50.jpg)
![Page 51: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/51.jpg)
In waste water the bladder is inverted and connected to the top of the vessel. The precharge is contained inside the bladder. By allowing the sewage to be contained inside the vessel and only using vertical configurations one can control the problems of sedimentation.
![Page 52: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/52.jpg)
Vertical only due to sedimentation
Head Losses and sedimentation build up are calculated in outlet design
Tee, 90 degree and bottom outlets
Range: 50 to 15,000 gallons.
10 to 15 year life expectancy for bladders.
Warranty directly related to Charlatte’s involvement in sizing vessel.
Load Cell monitoring
![Page 53: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/53.jpg)
![Page 54: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/54.jpg)
When it is possible a good solution is to use external atmospheric energy and feed the system with atmospheric air, using limitless amounts of free energy. This job is perfectly achieved by the A.R.A.A. vessel, without any air bubbles being introduced into the pipe work.
As these flat profiles are frequent in sewage systems, the design of the device is adapted to raw water and effluents. They have been successfully used for over ten years from 50 gallons up to 25,000 gallons.
![Page 55: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/55.jpg)
MANUFACTURING
![Page 56: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/56.jpg)
![Page 57: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/57.jpg)
Surge tank not properly welded
![Page 58: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/58.jpg)
CHARLATTE - Not Charlatte
Tank Leg Design
![Page 59: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/59.jpg)
COATING AND TESTING BLADDERS
EUV WASTE WATERBLADDER
POTABLE WATER BLADDER
![Page 60: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/60.jpg)
Hydrochoc 30,000 gallon potable bladder surge vessel Chicago
![Page 61: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/61.jpg)
![Page 62: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/62.jpg)
Anti-extrusion grid and bladder clamping system
Outlets 8” dia. and above
![Page 63: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/63.jpg)
BLADDER TYPE VESSELS
![Page 64: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/64.jpg)
4 x 25,000 gallons
Clear Water Bladder Tanks
150 psi design pressure
10’ dia. X 55’ Length
![Page 65: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/65.jpg)
![Page 66: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/66.jpg)
SURGE VESSELS IN SERVICE
CITY OF FAIRVIEW OREGON.2x528 GALLON WASTE
WATER BLADDER SURGE VESSELS.
TAZEWELL COUNTY PSATAZEWELL COUNTY, VIRGINIA.
2x400 GALLONPOTABLE WATER BLADDER VESSELS.
![Page 67: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/67.jpg)
VERTICAL 3x18,000 GAL
2x20,000 GALLON BLADDER SURGE VESSELS.
![Page 68: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/68.jpg)
2 Hydrochoc 10,000 gallon 250 psi bladder type surge vessels Ontario Canada.
Hydrochoc 22,500 gallon 150 psi bladder type surge vessels Omaha Nebraska.
![Page 69: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/69.jpg)
1,050 gallons Hydrofort Vessel in Kuai, Hawaii
-Pump Cycle control tank.-Magnetic Level Gauge controls the pumps.
![Page 70: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/70.jpg)
LEVEL MONITORING SYSTEM
![Page 71: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/71.jpg)
LEVEL MONITORING SYSTEM
![Page 72: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/72.jpg)
EUV 3x10,000 gallon 450psi Raw water inverted bladder surge vessels
![Page 73: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/73.jpg)
![Page 74: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/74.jpg)
Hydrofort 7925 gallon bladder type hydro vessel Florida
![Page 75: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/75.jpg)
EUV 2641 gallon inverted bladder for wastewater Georgia.
![Page 76: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/76.jpg)
8 x 26,500 gallons compressor tanks – Abu Dhabi
![Page 77: Charlatte America](https://reader038.vdocuments.site/reader038/viewer/2022110401/55cf94eb550346f57ba54ff1/html5/thumbnails/77.jpg)
WWW.CHARLATTETANKS.COM