chapter 5 control using wireless transmitters. measurement and control data sampling rate to...

30
Chapter 5 Chapter 5 Control Using Wireless Transmitters

Upload: marjorie-wilkerson

Post on 22-Dec-2015

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Chapter 5Chapter 5

Control Using Wireless Transmitters

Page 2: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Measurement and Control Data Sampling Rate Measurement and Control Data Sampling Rate Measurement and Control Data Sampling Rate Measurement and Control Data Sampling Rate To achieve the best

control response, the rule of thumb is that feedback control should be executed four to 10 times faster than the process response time.

Most multi-loop controllers used in the process industry are designed to oversample the measurement by a factor of 2 to 10 to minimize delay being introduced by IO access.

Page 3: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Impact of Update Rate on Battery Life Impact of Update Rate on Battery Life Impact of Update Rate on Battery Life Impact of Update Rate on Battery Life When a wireless

measurement transmitter is used in a control application, it is not practical to provide the same oversampling as a multi-loop controller with a wired transmitter because it quickly depletes the battery in the wireless transmitter.

A wireless transmitter that communicates a new measurement value every 8, 16, or 32 seconds typically has a battery life in the range of 3–7 years.

Page 4: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

There is also an underlying assumption in traditional PID control that a new measurement is available each time control is executed and that control is executed at least four times faster than the process response time.

Depending on the process response time it may not be possible to provide measurement updates this frequently and still achieve a 3–7 year battery life.

Page 5: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

PID Control – Wireless Measurement Update Four PID Control – Wireless Measurement Update Four Times Faster Than the Process Response Time Times Faster Than the Process Response Time PID Control – Wireless Measurement Update Four PID Control – Wireless Measurement Update Four Times Faster Than the Process Response Time Times Faster Than the Process Response Time

The impact of wireless measurement update rate on control performance can be illustrated by considering a control application

Lambda controller tuning rules are applied to traditional PID control for a Lambda factor = 1.

– Process Gain = 1

– Process Deadtime = 2 seconds

– Process Time Constant = 6 seconds

Page 6: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Wireless Measurement Update Rate Two Times Wireless Measurement Update Rate Two Times Faster Than the Process Response Time Faster Than the Process Response Time Wireless Measurement Update Rate Two Times Wireless Measurement Update Rate Two Times Faster Than the Process Response Time Faster Than the Process Response Time

Page 7: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

PID Control – Wireless Measurement Update PID Control – Wireless Measurement Update Rate Set Equal to the Process Response Time Rate Set Equal to the Process Response Time PID Control – Wireless Measurement Update PID Control – Wireless Measurement Update Rate Set Equal to the Process Response Time Rate Set Equal to the Process Response Time

Page 8: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Wireless Measurement Update Rate Two Times Wireless Measurement Update Rate Two Times Slower Than the Process Response TimeSlower Than the Process Response TimeWireless Measurement Update Rate Two Times Wireless Measurement Update Rate Two Times Slower Than the Process Response TimeSlower Than the Process Response Time

Wireless update time exceeds the process response time, the control response to setpoint changes and disturbances becomes oscillatory.

Only for applications such as temperature control and level control that are characterized by slow process dynamics is it possible to use wireless transmitter update rates that are four times faster than the process response time and still achieve 3–7 year battery life.

Page 9: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Many of the control techniques and guidelines established during the development of single loop digital controllers in the mid-‘70s are based on providing a capability that mimics an electronic analog controller.

With the introduction of battery powered wireless transmitters, such update rates are impractical. Thus it is necessary to re-examine how control should be structured for use with wireless measurements.

Page 10: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Implementations of PID Controller ResetImplementations of PID Controller ResetImplementations of PID Controller ResetImplementations of PID Controller Reset Manufacturers of DCS have

approached PID implementation in a variety of ways.

Many commercial products create the reset component using a positive feedback network.

In a positive feedback network the time constant of the filter in the network defines the reset time in seconds per repeat.

Page 11: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Example – Process Response Exactly Matches Example – Process Response Exactly Matches Reset Network Filter ResponseReset Network Filter ResponseExample – Process Response Exactly Matches Example – Process Response Exactly Matches Reset Network Filter ResponseReset Network Filter Response

When the PID reset is implemented using a positive-feedback network, it is easy to see that the time constant in the filter contained in this network is a direct reflection of the process dynamic response.

Take, for example, a pure lag process where the PI controller is tuned for a Lambda factor of 1. On a change in setpoint, the PI controller output changes only once because the dynamic response of the filter exactly cancels the dynamic response of the process.

Page 12: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

PIDPlus for Wireless ControlPIDPlus for Wireless ControlPIDPlus for Wireless ControlPIDPlus for Wireless Control To provide the best

control when a measurement is not updated on a periodic basis, the PID may be restructured to reflect the reset contribution for the expected process response since the last measurement update.

This PID implementation is known as PIDPlus.

Page 13: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

PIDPlus with Continuously Updated Filter PIDPlus with Continuously Updated Filter PIDPlus with Continuously Updated Filter PIDPlus with Continuously Updated Filter To further enhance the

response for continuous changes in setpoint, the implementation of the PIDPlus algorithm can be modified as shown in this figure.

PIDPlus tuning is based on the process dynamics (for example, RESET = process time constant plus deadtime).

PIDPlus reset automatically compensates for variations in the measurement update rate and slow measurement update rates.

Page 14: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

PIDPlus ImplementationPIDPlus ImplementationPIDPlus ImplementationPIDPlus Implementation For those processes that

require derivative action, the contribution to the PID output should be recomputed and updated only when a new measurement is received.

The derivative calculation should use the elapsed time since the last new measurement to account for the fact that a new measurement value is not available for each execution of the PID.

Page 15: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Control for Wireless MeasurementControl for Wireless MeasurementControl for Wireless MeasurementControl for Wireless Measurement When the PIDPlus

algorithm is used with a wireless transmitter in a control application, the performance will be comparable to that achieved using a wired transmitter.

Example: PIDPlus using wireless transmitter compared to a standard PI controller where the wired measurement value.

Page 16: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Response for Measurement Loss Response for Measurement Loss during a Setpoint Changeduring a Setpoint ChangeResponse for Measurement Loss Response for Measurement Loss during a Setpoint Changeduring a Setpoint Change

The reliability of WirelessHART device communication has been well established. Even so, in the event of communication loss, the expected control behavior is of interest.

The example compares loss of communication with a PIDPlus against a PID with a wired transmitter where the wired measurement is frozen for a period of time.

Page 17: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Response for Measurement Loss after a Response for Measurement Loss after a Process DisturbanceProcess DisturbanceResponse for Measurement Loss after a Response for Measurement Loss after a Process DisturbanceProcess Disturbance

The response observed when the measurement was lost after a process disturbance is shown

As illustrated by these tests, the PIDPlus provides superior dynamic response under these lost measurement conditions.

PID response is significantly worse and may not be acceptable in many process applications.

Page 18: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Example – Enabling PIDPlus in a Control Module Example – Enabling PIDPlus in a Control Module Example – Enabling PIDPlus in a Control Module Example – Enabling PIDPlus in a Control Module In addition, in many common

applications such as flow or pressure control of a liquid or gas stream, an update rate that is four times faster than the process response time cannot be achieved if there is a requirement for a 3–7 year battery life.

In such cases the PIDPlus should be used to implement control using a slower update rate such as 8 or 16 seconds.

When PIDPlus is available as a standard feature of the distributed control system, the PIDPlus capability is selected through an option parameter of the PID.

Page 19: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Disabling Filtering in the Control PathDisabling Filtering in the Control PathDisabling Filtering in the Control PathDisabling Filtering in the Control Path A timestamp accompanies

new measurement values that are communicated by a transmitter to the WirelessHART gateway.

However, some distributed control systems detect the communication of a new measurement when the value changes. If the PIDPlus uses this mechanism to identify a new communication it is critical that filtering is not applied in the module processing

Page 20: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Setting Module Execution Rate ExampleSetting Module Execution Rate ExampleSetting Module Execution Rate ExampleSetting Module Execution Rate Example When control using a WirelessHART

measurement is implemented, the module execution rate should be set much faster that the communication update period.

For example, the module may be set to execute every 0.5 seconds even though the communication update rate is set to 8 seconds.

Scheduling the module execution in this manner can minimize any delay in a new measurement value being used in control. This is necessary since the module execution within the DCS is not synchronized with the measurement communication.

Page 21: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Single Use Bioreactor (SUB) with Single Use Bioreactor (SUB) with Wireless InstrumentationWireless InstrumentationSingle Use Bioreactor (SUB) with Single Use Bioreactor (SUB) with Wireless InstrumentationWireless Instrumentation

The benefits of using WirelessHART transmitters with a single use bioreactor have been demonstrated by Broadley James, a major manufacturer of bioreactors for product development and production.

A skid was instrumented with a 100L SUB (Single Use Bioreactor) with WirelessHART pH, temperature and pressure transmitters

The bioreactor pH and temperature were controlled over a series of batch runs using WirelessHART measurements.

Page 22: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Bioreactor ProcessBioreactor ProcessBioreactor ProcessBioreactor Process A wireless pressure

transmitter was used to monitor pressure within the bioreactor.

The pH measurement was communicated on a 1 second window communications.

The temperature was reported on a 2 second using continuous (periodic) communications.

Page 23: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Wireless Temperature Control Wireless Temperature Control Response in SUB UnitResponse in SUB UnitWireless Temperature Control Wireless Temperature Control Response in SUB UnitResponse in SUB Unit

A mammalian cell culture was used for each batch run.

For the purpose of comparison, wired pH and temperature measurements were also available during each batch run.

This screen capture shows the setpoint response of temperature control based on the WirelessHART input.

Page 24: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Wireless pH Control Response in SUB UnitWireless pH Control Response in SUB Unit Similarly good

performance was seen for pH control using the WirelessHART input.

The response to 0.05 changes in pH setpoint is shown in this screen capture.

Page 25: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Stripper Column at UT Stripper Column at UT Stripper Column at UT Stripper Column at UT During the development of the

PIDPlus, the performance was also verified in several field trials where the PIDPlus was used for control with WirelessHART transmitters.

The control of the Stripper Column shown on the left portion of the picture was addressed in a field trial conducted at the J.J. Pickle Research Campus, University of Texas

Page 26: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Stripper Pressure and Steam Flow ControlStripper Pressure and Steam Flow ControlStripper Pressure and Steam Flow ControlStripper Pressure and Steam Flow Control Standard WirelessHART

pressure and flow transmitters were installed to demonstrate and test control using the PIDPlus.

The control system was configured to allow the operator to switch between control using WirelessHART and PIDPlus and the wired transmitters and PID.

Page 27: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

The stripper column pressure control is shown in Figure 5-26 for two periods of operation:

1. PID control of steam flow and column pressure using wired measurement transmitters.

2. PIDPlus control of steam flow and column pressure using WirelessHART measurement transmitters.

The same dynamic control response was observed, as illustrated in these screen captures. For these tests, the same tuning was used for both wired and wireless control.

Page 28: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Field Evaluation of Wireless ControlField Evaluation of Wireless Control The control performance is shown

for column pressure and steam flow control for PIDPlus control using WirelessHART measurement transmitters (Test 2) vs PID control using wired measurement transmitters (Test 1).

Comparable control performance was achieved using WirelessHART measurements and PIDPlus vs control with wired measurements and PID. However, the number of measurement samples with a WirelessHART transmitter vs a wired transmitter was reduced by a factor of 10 for flow control and a factor of six for pressure control.

Page 29: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Exercise: Control Using Wireless TransmittersExercise: Control Using Wireless TransmittersExercise: Control Using Wireless TransmittersExercise: Control Using Wireless Transmitters

This workshop provides several exercises that can be used to further explore the control using a wireless measurement.

Step 1: Open the module that will be used in this workshop and observe the control and simulated processes.

Step 2: Initialize the Performance Index (IAE) and then change the SP parameter of both control loops by 10%. Observe the control response using a plot of the setpoint, control measurements and output.

Step 3: Note the IAE and the number of communications for the wireless and wired control. A significant difference should be seen in the number of communications for wired vs wireless control that were required to respond to the setpoint change.

Step 4: Initialize the Performance Index and change the Disturbance input from zero to 10. Observe the response of the PID and PIDPlus to this unmeasured process disturbance.

Step 5: Note the IAE and the number of communications for the wireless and wired control. A significant difference should be observed in the number of communications for wired vs wireless control that were required to respond to the unmeasured process disturbance.

Page 30: Chapter 5 Control Using Wireless Transmitters. Measurement and Control Data Sampling Rate  To achieve the best control response, the rule of thumb is

Process: Control Using Wireless TransmittersProcess: Control Using Wireless TransmittersProcess: Control Using Wireless TransmittersProcess: Control Using Wireless Transmitters

A simulation of two identical heater processes is used to compare the control performance of PIDPlus using a wireless transmitter and PID using a wired transmitter.