chapter 12.pdf - iapmo - iapmo group plumbing code/chapter 12.pdfchapter 12 fuel piping 167 1201.0...
TRANSCRIPT
CHAPTER 12
FUEL PIPING
167
1201.0 Scope of Gas Piping.
(A) Coverage of piping systems shall extend fromthe point of delivery to the connections witheach gas utilization device. For other than undi-luted liquefied petroleum gas systems, the pointof delivery shall be considered the outlet of theservice meter assembly, or the outlet of theservice regulator or service shutoff valve whereno meter is provided. For undiluted liquefiedpetroleum gas systems, the point of deliveryshall be considered the outlet of the final pres-sure regulator, exclusive of the line gas regulators,in the system. [NFPA 54:1.1.1.1(A)]
(B) Piping systems requirements shall includedesign, materials, components, fabrications,assembly, installation, testing, inspection, opera-tion, and maintenance. [NFPA 54:1.1.1.1(C)]
(C) This code shall not apply to the following (refer-ence standards for some of which appear inChapter 14): [NFPA 54:1.1.1.2]
(1) Portable LP-Gas appliances of all types thatare not connected to a fixed fuel pipingsystem. [NFPA 54:1.1.1.2(1)]
(2) Installation of farm equipment such asbrooders, dehydrators, dryers, and irriga-tion equipment. [NFPA 54:1.1.1.2(2)]
(3) Raw material (feedstock) applications,except for piping to special atmospheregenerators. [NFPA 54:1.1.1.2(3)]
(4) Oxygen-fuel gas cutting and weldingsystems. [NFPA 54:1.1.1.2(4)]
(5) Industrial gas applications using gases suchas acetylene and acetylenic compounds,hydrogen, ammonia, carbon monoxide,oxygen, and nitrogen. [NFPA 54:1.1.1.2(5)]
(6) Petroleum refineries, pipeline compressor orpumping stations, loading terminals,compounding plants, refinery tank farms,and natural gas processing plants. [NFPA54:1.1.1.2(6)]
(7) Large integrated chemical plants or portionsof such plants where flammable orcombustible liquids or gases are producedby chemical reactions or used in chemicalreactions. [NFPA 54:1.1.1.2(7)]
(8) LP-Gas installations at utility gas plants.[NFPA 54:1.1.1.2(8)]
(9) Liquefied natural gas (LNG) installations.[NFPA 54:1.1.1.2(9)]
(10) Fuel gas piping in electric utility powerplants. [NFPA 54-09:1.1.1.2(10)]
(11) Proprietary items of equipment, apparatus,or instruments such as gas-generating sets,compressors, and calorimeters. [NFPA54:1.1.1.2(11)]
(12) LP-Gas appliances for vaporization, gasmixing, and gas manufacturing. [NFPA54:1.1.1.2(12)]
(13) LP-Gas piping for buildings under construc-tion or renovations that are not to becomepart of the permanent building pipingsystem—that is, temporary fixed piping forbuilding heat. [NFPA 54:1.1.1.2(13)]
(14) Installation of LP-Gas systems for railroadswitch heating. [NFPA 54:1.1.1.2(14)]
(15) Installation of LP-Gas and compressednatural gas systems on vehicles. [NFPA54:1.1.1.2(15)]
(16) Gas piping, meters, gas-pressure regulators,and other appurtenances used by the servinggas supplier in distribution of gas, other thanundiluted LP-Gas. [NFPA 54:1.1.1.2(16)]
1202.0 General.
The regulations of this chapter shall govern theinstallation of fuel gas piping in or in connectionwith any building, structure or within the propertylines of any premises up to five (5) psi (34.5 kPa),other than service pipe. Fuel oil piping systems shallbe installed in accordance with NFPA 31.
1203.0 Definitions.
For the purposes of this code, these definitions shallapply to this chapter. Certain terms, phrases, words,and their derivatives shall be interpreted as set forthin this section, provided, however, that whenever thewords “gas meters” appear, they shall be construedto also mean valves and those devices required forthe regulation of pressure and the measurement ofnatural gas being dispensed for any building, struc-ture, or premises.
1203.1 Appliance Fuel Connector – An assemblyof listed semi-rigid or flexible tubing and fittings tocarry fuel between a fuel-piping outlet and a fuel-burning appliance.
1203.2 Bonding Jumper – A reliable conductor toensure the required electrical conductivity betweenmetal parts required to be electrically connected.[NFPA 70:100.1]
1203.3 Fuel Gas – Natural, manufactured, liquefiedpetroleum, or a mixture of these.
READ ONLY
READ ONLY
168
1203.4 – 1206.1 IDAHO STATE PLUMBING CODE
1203.4 Gas Piping – Any installation of pipe,valves, or fittings that is used to convey fuel gas,installed on any premises or in any building, butshall not include:
(1) Any portion of the service piping.
(2) Any approved piping connection six (6) feet(1,829 mm) or less in length between an existinggas outlet and a gas appliance in the same roomwith the outlet.
1203.5 Gas-Piping System – Any arrangement ofgas piping or regulators after the point of deliveryand each arrangement of gas piping serving abuilding, structure, or premises, whether individu-ally metered or not.
1203.6 Grounding Electrode – A device that estab-lishes an electrical connection to the earth.
1203.7 Liquefied Petroleum Gas (LPG) Facilities –Liquefied petroleum gas (LPG) facilities meanstanks, containers, container valves, regulating equip-ment, meters, and/or appurtenances for the storageand supply of liquefied petroleum gas for anybuilding, structure, or premises.
1203.8 Provision for Location of Point of Delivery –
The location of the point of delivery shall be accept-able to the serving gas supplier. [NFPA 54:5.2]
1203.9 Quick-Disconnect Device – A hand-oper-ated device that provides a means for connectingand disconnecting an appliance or an applianceconnector to a gas supply and that is equipped withan automatic means to shut off the gas supply whenthe device is disconnected. [NFPA 54:3.3.28.3]
1203.10 Service Piping – The piping and equip-ment between the street gas main and the gas pipingsystem inlet that is installed by, and is under thecontrol and maintenance of, the serving gas supplier.
1203.11 Transition Gas Riser – Any listed orapproved section or sections of pipe and fittingsused to convey fuel gas and installed in a gas pipingsystem for the purpose of providing a transitionfrom below ground to above ground.
1204.0 Inspection.
1204.1 Upon completion of the installation, alter-ation, or repair of any gas piping, and prior to theuse thereof, the Authority Having Jurisdiction shallbe notified that such gas piping is ready for inspec-tion.
1204.2 All excavations required for the installationof underground piping shall be kept open until suchtime as the piping has been inspected and approved.If any such piping is covered or concealed beforesuch approval, it shall be exposed upon the directionof the Authority Having Jurisdiction.
1204.3 The Authority Having Jurisdiction shallmake the following inspections and either shallapprove that portion of the work as completed orshall notify the permit holder wherein the same failsto comply with this code.
1204.3.1 Rough Piping Inspection. Thisinspection shall be made after all gas pipingauthorized by the permit has been installed andbefore any such piping has been covered orconcealed or any fixture or appliance has beenattached thereto. This inspection shall include adetermination that the gas-piping size, material,and installation meet the requirements of thiscode.
1204.3.2 Final Piping Inspection. This inspec-tion shall be made after all piping authorized bythe permit has been installed and after allportions thereof that are to be covered orconcealed are so concealed and before anyfixtures, appliance, or shutoff valve has beenattached thereto. This inspection shall be inaccordance with Section 1214.1. Test gaugesused in conducting tests shall comply withSection 319.0, Test Gauges.
1204.4 In cases where the work authorized by thepermit consists of a minor installation of additionalpiping to piping already connected to a gas meter,the foregoing inspections shall be permitted to bewaived at the discretion of the Authority HavingJurisdiction. In this event, the Authority HavingJurisdiction shall make such inspection as deemedadvisable in order to be assured that the work hasbeen performed in accordance with the intent of thiscode.
1205.0 Certificate of Inspection.
1205.1 If, upon final piping inspection, the installa-tion is found to comply with the provisions of thiscode, a certificate of inspection shall be permitted tobe issued by the Authority Having Jurisdiction.
1205.2 A copy of the certificate of such final pipinginspection shall be issued to the serving gas suppliersupplying gas to the premises.
1205.3 It shall be unlawful for any serving gassupplier, or person furnishing gas, to turn on orcause to be turned on, any fuel gas or any gas meteror meters, until such certificate of final inspection, asherein provided, has been issued.
1206.0 Authority to Render Gas Service.
1206.1 It shall be unlawful for any person, firm, orcorporation, excepting an authorized agent or
READ ONLY
READ ONLY
169
FUEL PIPING 1206.1 – 1209.4
employee of a person, firm, or corporation engagedin the business of furnishing or supplying gas andwhose service pipes supply or connect with theparticular premises, to turn on or reconnect gasservice in or on any premises where and when gasservice is, at the time, not being rendered.
1206.2 It shall be unlawful to turn on or connect gasin or on any premises unless all outlets are properlyand securely connected to gas appliances or cappedor plugged with screw joint fittings.
1207.0 Authority to Disconnect.
1207.1 The Authority Having Jurisdiction or theserving gas supplier is hereby authorized to discon-nect any gas piping or appliance or both that shall befound not to conform to the requirements of thiscode or that are found defective and in such condi-tion as to endanger life or property.
1207.2 Where such disconnection has been made, anotice shall be attached to such gas piping or appli-ance or both that shall state the same has beendisconnected, together with the reasons thereof.
1207.3 It shall be unlawful to remove or disconnectany gas piping or gas appliance without capping orplugging with a screw joint fitting, the outlet fromwhich said pipe or appliance was removed. Outletsto which gas appliances are not connected shall beleft capped, gas-tight on any piping system that hasbeen installed, altered, or repaired.
Exception: When an approved listed quick-disconnect device is used.
1208.0 Temporary Use of Gas.
Where temporary use of gas is desired and theAuthority Having Jurisdiction deems the use neces-sary, a permit shall be permitted to be issued forsuch use for a period of time not to exceed thatdesignated by the Authority Having Jurisdiction,provided that such gas-piping system otherwiseconforms to the requirements of this code regardingmaterial, sizing, and safety.
1209.0 Gas-Piping System Design, Materials, and
Components.
1209.1 Piping Plan.
1209.1.1 Installation of Piping System. Whererequired by the Authority Having Jurisdiction, apiping sketch or plan shall be prepared beforeproceeding with the installation. This plan shallshow the proposed location of piping, the size of
different branches, the various load demands,and the location of the point of delivery. [NFPA54:5.1.1]
1209.1.2 Addition to Existing System. Whenan additional gas utilization appliance is beingconnected to a gas-piping system, the existingpiping shall be checked to determine whether ithas adequate capacity (see Section 1209.4.3). Ifinadequate, the existing system shall be enlargedas required, or separate gas piping of adequatecapacity shall be provided. [NFPA 54:5.1.2]
1209.2 Provision for Location of Point of Delivery.
The location of the point of delivery shall be accept-able to the serving gas supplier. [NFPA 54:5.2]
1209.3 Interconnections Between Gas-Piping
Systems.
1209.3.1 Interconnections Supplying Sepa-
rate Users. Where two (2) or more meters, ortwo (2) or more service regulators where metersare not provided, are located on the samepremises and supply separate users, the gas-piping systems shall not be interconnected onthe outlet side of the meters or service regula-tors. [NFPA 54:5.3.1]
1209.3.2 Interconnections for Standby Fuels.
Where a supplementary gas for standby use isconnected downstream from a meter or a serviceregulator where a meter is not provided, adevice to prevent backflow shall be installed. Athree-way valve installed to admit the standbysupply and, at the same time, shut off theregular supply, shall be permitted to be used forthis purpose. [NFPA 54:5.3.2]
1209.4 Sizing of Gas-Piping Systems.
1209.4.1 General Considerations. Gas-pipingsystems shall be of such size and so installed asto provide a supply of gas sufficient to meet themaximum demand and supply gas to eachappliance inlet at not less than the minimumsupply pressure required by the appliance.[NFPA 54-09:5.4.1]
1209.4.2 Maximum Gas Demand. The volumeof gas to be provided (in cubic feet per hour)shall be determined directly from the manufac-turer's input ratings of the gas utilization appli-ance served. Where the input rating is not indi-cated, the gas supplier, appliance manufacturer,or a qualified agency shall be contacted or therating from Table 12-1 shall be used for esti-mating the volume of gas to be supplied. Thetotal connected hourly load shall be used as thebasis for piping sizing, assuming the appliance isoperating at full capacity simultaneously.
READ ONLY
READ ONLY
170
1209.4 – Table 12-1 IDAHO STATE PLUMBING CODE
Exception: Sizing shall be permitted to bebased upon established load diversityfactors. [NFPA 54:5.4.2]
1209.4.3 Sizing Methods. Gas piping shall besized in accordance with one of the following :
(1) Pipe sizing tables or sizing equations in thischapter.
(2) Other approved engineering methods accept-able to the Authority Having Jurisdiction.
(3) Sizing tables included in a listed pipingsystem manufacturer's installation instruc-tions. [NFPA 54:5.4.3]
1209.4.4 Allowable Pressure Drop. The designpressure loss in any piping system undermaximum probable flow conditions, from thepoint of delivery to the inlet connection of theappliance, shall be such that the supply pressureat the appliance exceeds or is equal to theminimum pressure required by the appliance.[NFPA 54-09:5.4.4]
1209.5 Acceptable Piping Materials and Joining
Methods.
1209.5.1 General.
1209.5.1.1 Acceptable Materials. Materialsused for piping systems shall comply withthe requirements of this chapter or shall beacceptable to the Authority Having Jurisdic-tion. [NFPA 54:5.6.1.1]
1209.5.1.2 Used Materials. Pipe, fittings,valves, or other materials shall not be usedagain unless they are free of foreign mate-rials and have been ascertained to beadequate for the service intended. [NFPA54:5.6.1.2]
1209.5.1.3 Other Materials. Material notcovered by the standards specifications listedherein shall be investigated and tested todetermine that it is safe and suitable for theproposed service and, in addition, shall berecommended for that service by the manufac-turer and shall be acceptable to the AuthorityHaving Jurisdiction. [NFPA 54:5.6.1.3]
1209.5.2 Metallic Pipe.
1209.5.2.1 Cast-iron pipe shall not be used.[NFPA 54:5.6.2.1]
1209.5.2.2 Steel and wrought-iron pipeshall be not less than standard weight(Schedule 40) and shall comply with one ofthe following standards:
(1) ASME B36.10, Welded and SeamlessWrought-Steel Pipe
TABLE 12-1
Approximate Gas Input for Typical Appliances
[NFPA 54: Table 5.4.2.1]
ApplianceInput Btu/h.
(Approx.)
Space Heating Units
Warm air furnace
Single family
Multifamily, per unit
Hydronic boiler
Single family
Multifamily, per unit
Space-and Water-Heating Units
Hydronic boiler
Single family
Multifamily, per unit
Water-Heating Appliances
Water heater, automatic
storage 30 to 40 gal. tank
Water heater, automatic
storage 50 gal. tank
Water heater, automatic instantaneous
Capacity at 2 gal./minute
Capacity at 4 gal./minute
Capacity at 6 gal./minute
Water heater, domestic,
circulating or side-arm
Cooking Appliances
Range, freestanding,
domestic
Built-in oven or broiler unit,
domestic
Built-in top unit,
domestic
Other Appliances
Refrigerator
Clothes dryer, Type 1
(domestic)
Gas fireplace direct vent
Gas logBarbecue
Gaslight
100,000
60,000
100,000
60,000
120,000
75,000
35,000
50,000
142,800
285,000
428,400
35,000
65,000
25,000
40,000
3,000
35,000
40,000
80,000
40,000
2,500
For SI units: 1 Btu per hour = 0.293 W
READ ONLY
READ ONLY
171
FUEL PIPING 1209.5
(2) ASTM A 53, Standard Specification forPipe, Steel, Black and Hot-Dipped, Zinc-Coated Welded and Seamless
(3) ASTM A 106, Standard Specification forSeamless Carbon Steel Pipe for High-Temperature Service [NFPA 54:5.6.2.2]
1209.5.2.3 Copper and brass pipe shall notbe used if the gas contains more than anaverage of 0.3 grains of hydrogen sulfide perone-hundred (100) scf of gas (0.7 mg/100 L).[NFPA 54:5.6.2.3]
Threaded copper, brass, or aluminumalloy pipe shall not be used with gasescorrosive to such material. [NFPA 54:5.6.2.4]
1209.5.2.4 Aluminum alloy pipe shallcomply with ASTM B 241, Standard Specifica-tion for Aluminum-Alloy Seamless Pipe andSeamless Extruded Tube (except that the useof alloy 5456 is prohibited) and shall bemarked at each end of each length indi-cating compliance. Aluminum alloy pipeshall be coated to protect against externalcorrosion where it is in contact withmasonry, plaster, insulation or is subject torepeated wettings by such liquids as water,detergents, or sewage. [NFPA 54:5.6.2.5]
Aluminum alloy pipe shall not be usedin exterior locations or underground. [NFPA54:5.6.2.6]
1209.5.3 Metallic Tubing. Seamless copper,aluminum alloy, or steel tubing shall not be usedwith gases corrosive to such material. [NFPA54:5.6.3]
1209.5.3.1 Steel tubing shall comply withASTM A 254, Standard Specification for Copper
Brazed Steel Tubing. [NFPA 54-09:5.6.3.1]
1209.5.3.2 Copper and brass tubing shallnot be used if the gas contains more than anaverage of 0.3 grains of hydrogen sulfide perone-hundred (100) scf of gas (0.7 mg/100 L).Copper tubing shall comply with standardType K or L of ASTM B 88, Standard Specifi-
cation for Seamless Copper Water Tube, orASTM B 280, Specification for Seamless Copper
Tube for Air-Conditioning and Refrigeration
Field Service. [NFPA 54:5.6.3.2]
1209.5.3.3 Aluminum alloy tubing shallcomply with ASTM B 210, Standard Specifica-
tion for Aluminum-Alloy Drawn Seamless
Tubes, or ASTM B 241, Standard Specification
for Aluminum Alloy Seamless Pipe and Seam-
less Extruded Tube. Aluminum alloy tubing
shall be coated to protect against externalcorrosion where it is in contact withmasonry, plaster, insulation or is subject torepeated wettings by liquids such as water,detergent, or sewage. Aluminum alloytubing shall not be used in exterior locationsor underground. [NFPA 54:5.6.3.3]
1209.5.3.4 Corrugated stainless steel tubingshall be tested and listed in compliance withthe construction, installation, and perfor-mance requirements of CSA LC-1, Standardfor Fuel Gas Piping Systems Using CorrugatedStainless Steel Tubing. [NFPA 54:5.6.3.4]
1209.5.4 Plastic Pipe, Tubing, and Fittings.
Plastic pipe, tubing, and fittings used to supplyfuel gas shall conform with ASTM D 2513, Stan-dard Specification for Thermoplastic Gas PressurePipe, Tubing, and Fittings. Pipe to be used shall bemarked "gas" and "ASTM D 2513.” [NFPA54:5.6.4.1]
Anodeless risers shall comply with thefollowing [NFPA 54:5.6.4.3]:
1209.5.4.1 Regulator Vent Piping. Plasticpipe, tubing, and fittings used to connectregulator vents to remote vent terminationsshall be PVC conforming to UL 651, Schedule40 and 80 Rigid PVC Conduit and Fittings.PVC vent piping shall not be installedindoors. [NFPA 54-09:5.6.4.2]
1209.5.4.2 Factory-assembled anodelessrisers shall be recommended by the manu-facturer for the gas used and shall be leak-tested by the manufacturer in accordancewith written procedures. [NFPA 54:5.6.4.3(1)]
1209.5.4.3 Service head adapters and field-assembled anodeless risers incorporatingservice head adapters shall be recom-mended by the manufacturer for the gasused by the manufacturer and shall bedesign-certified to meet the requirements ofCategory I of ASTM D 2513, Standard Specifi-cation for Thermostatic Gas Pressure Pipe,Tubing, and Fittings and the code of FederalRegulations, Title 49, Part 192.281(e). Themanufacturer shall provide the user withqualified installation instructions asprescribed by the code of Federal Regula-tions, Title 49, Part 192.283(b). [NFPA54:5.6.4.3(2)]
1209.5.4.4 The use of plastic pipe, tubing,and fittings in undiluted liquefied petroleumgas-piping systems shall be in accordancewith NFPA 58, Liquefied Petroleum Gas Code.[NFPA 54:5.6.4.3(3)]
READ ONLY
READ ONLY
1209.5.5 Workmanship and Defects. Gas pipeor tubing and fittings shall be clear and free fromcutting burrs and defects in structure orthreading, and shall be thoroughly brushed andchip and scale blown. Defects in pipe, tubing,and fittings shall not be repaired. Defective pipe,tubing, and fittings shall be replaced. [NFPA54:5.6.5]
1209.5.6 Protective Coating. Where in contactwith material or atmosphere exerting a corrosiveaction, metallic piping and fittings coated with acorrosion-resistant material shall be used.External or internal coatings or linings used onpiping or components shall not be considered asadding strength. [NFPA 54:5.6.6]
1209.5.7 Metallic Pipe Threads.
(A) Specifications for Pipe Threads. Metallicpipe and fitting threads shall be taper pipethreads and shall comply with ASMEB1.20.1, Standard for Pipe Threads, General
Purpose (Inch). [NFPA 54:5.6.7.1]
(B) Damaged Threads. Pipe with threads thatare stripped, chipped, corroded, or other-wise damaged shall not be used. Where aweld opens during the operation of cuttingor threading, that portion of the pipe shallnot be used. [NFPA 54:5.6.7.2]
(C) Number of Threads. Field threading ofmetallic pipe shall be in accordance withTable 12-2. [NFPA 54:5.6.7.3]
(D) Thread Compounds. Thread (joint)compounds (pipe dope) shall be resistant tothe action of liquefied petroleum gas or toany other chemical constituents of the gasesto be conducted through the piping. [NFPA54:5.6.7.4]
1209.5.8 Metallic Piping Joints and Fittings.
The type of piping joint used shall be suitable forthe pressure-temperature conditions and shallbe selected giving consideration to joint tight-ness and mechanical strength under the serviceconditions. The joint shall be able to sustain themaximum end force due to the internal pressureand any additional forces due to temperatureexpansion or contraction, vibration, fatigue, or tothe weight of the pipe and its contents. [NFPA54:5.6.8]
1209.5.8.1 Pipe Joints. Pipe joints shall bethreaded, flanged, brazed, or welded.Where nonferrous pipe is brazed, thebrazing materials shall have a melting pointin excess of 1,000°F (538°C). Brazing alloysshall not contain more than 0.05 percentphosphorus. [NFPA 54:5.6.8.1]
1209.5.8.2 Tubing Joints. Tubing jointsshall either be made with approved gastubing fittings, be brazed with a materialhaving a melting point in excess of 1,000°F(538°C), or made by press-connect fittingscomplying with CSA LC-4. Brazing alloysshall not contain more than 0.05 percentphosphorus. [NFPA 54:5.6.8.2]
1209.5.8.3 Flared Joints. Flared joints shallbe used only in systems constructed fromnonferrous pipe and tubing where experi-ence or tests have demonstrated that thejoint is suitable for the conditions and whereprovisions are made in the design to preventseparation of the joints. [NFPA 54:5.6.8.3]
1209.5.8.4 Metallic Fittings (Including
Valves, Strainers, Filters).
(1) Threaded fittings in sizes exceedingfour (4) inches (100 mm) shall not beused unless acceptable to the AuthorityHaving Jurisdiction.
(2) Fittings used with steel or wrought-ironpipe shall be steel, brass, bronze,malleable iron, or cast-iron.
(3) Fittings used with copper or brass pipeshall be copper, brass, or bronze.
(4) Fittings used with aluminum alloy pipeshall be of aluminum alloy.
(5) Cast-Iron Fittings.
(a) Flanges shall be permitted.
(b) Bushings shall not be used.
(c) Fittings shall not be used in systemscontaining flammable gas-airmixtures.
TABLE 12-2Specifications for Threading Metallic Pipe
[NFPA 54: Table 5.6.7.3]
Iron Pipe
Size (in.)
Approximate Length of
Threaded Portion (in.)
Approximate No. of
Threads to Be Cut
1/2 3/4 10
3/4 3/4 10
1 7/8 10
1-1/4 1 11
1-1/2 1 11
2 1 11
2-1/2 1-1/2 12
3 1-1/2 12
4 1-5/8 13
For SI units, 1 in. = 25.4 mm.
172
1209.5 IDAHO STATE PLUMBING CODE
READ ONLY
READ ONLY
173
FUEL PIPING 1209.5 – 1209.6
(d) Fittings in sizes four (4) inches (100mm) and larger shall not be usedindoors unless approved by theAuthority Having Jurisdiction.
(e) Fittings in sizes six (6) inches (150mm) and larger shall not be usedunless approved by the AuthorityHaving Jurisdiction.
(6) Aluminum Alloy Fittings. Threads shallnot form the joint seal.
(7) Zinc-Aluminum Alloy Fittings. Fittingsshall not be used in systems containingflammable gas-air mixtures.
(8) Special Fittings. Fittings such ascouplings; proprietary-type joints;saddle tees; gland-type compressionfittings; and flared, flareless, orcompression-type tubing fittings shallbe (1) used within the fitting manufac-turers' pressure-temperature recom-mendations; (2) used within the serviceconditions anticipated with respect tovibration, fatigue, thermal expansion, orcontraction; (3) installed or braced toprevent separation of the joint by gaspressure or external physical damage;and (4) acceptable to the AuthorityHaving Jurisdiction. [NFPA 54:5.6.8.4]
1209.5.9 Plastic Piping, Joints, and Fittings.
Plastic pipe, tubing, and fittings shall be joinedin accordance with the manufacturers' instruc-tions. The following shall be observed whenmaking such joints [NFPA 54:5.6.9]:
(A) The joint shall be designed and installed sothat the longitudinal pullout resistance ofthe joint shall be equal to the tensile strengthof the plastic piping material. [NFPA54:5.6.9(1)]
(B) Heat-fusion joints shall be made in accor-dance with AWS B2.4 Specification forWelding Procedure and Performance Qualifica-tion for Thermoplastics. Joints shall be madewith the joining method recommended bythe pipe manufacturer. Heat-fusion fittingsshall be marked "ASTM D 2513." [NFPA54:5.6.9(2)]
(C) Where compression-type mechanical jointsare used, the gasket material in the fittingshall be compatible with the plastic pipingand with the gas distributed by the system.An internal tubular rigid stiffener shall beused in conjunction with the fitting. Thestiffener shall be flush with the end of thepipe or tubing, shall extend not less than the
outside end of the pipe or tubing and shallextend not less than to the outside end of thecompression fitting when installed. Thestiffener shall be free of rough or sharpedges and shall not be a forced fit in theplastic. Split tubular stiffeners shall not beused. [NFPA 54:5.6.9(3)]
(D) Plastic piping joints and fittings for use inliquefied petroleum gas-piping systemsshall be in accordance with NFPA 58, Lique-fied Petroleum Gas Code [NFPA 54:5.6.9(4)]
1209.5.10 Flanges. Flanges shall comply withASME B16.1, Standard for Cast-Iron Pipe Flangesand Flanged Fittings; ASME B16.20, Standard forRing-Joint Gaskets and Grooves for Steel PipeFlanges; or MSS SP-6, Standard Finishes for ContactFaces of Pipe Flanges and Connecting-End Flanges ofValves and Fittings. The pressure-temperatureratings shall equal or exceed that required by theapplication. [NFPA 54:5.6.10]
(A) Flange Facings. Standard facings shall bepermitted for use under this code. Whereone-hundred and fifty (150) psi (1,090 kPa)steel flanges are bolted to Class 125 cast-ironflanges, the raised face on the steel flangeshall be removed. [NFPA 54:5.6.10.1]
(B) Lapped Flanges. Lapped flanges shall beused only above ground or in exposed loca-tions accessible for inspection. [NFPA54:5.6.10.2]
1209.5.11 Flange Gaskets. The material forgaskets shall be capable of withstanding thedesign temperature and pressure of the pipingsystem and the chemical constituents of the gasbeing conducted without change to its chemicaland physical properties. The effects of fire expo-sure to the joint shall be considered in choosingthe material. [NFPA 54:5.6.11]
(1) Acceptable materials include the following:
(a) Metal or metal-jacketed asbestos (plainor corrugated)
(b) Asbestos
(c) Aluminum "O" rings and spiral-woundmetal gaskets [NFPA 54:5.6.11.1]
(2) When a flanged joint is opened, the gasketshall be replaced. [NFPA 54:5.6.11.2]
(3) Full-face gaskets shall be used with allbronze and cast-iron flanges. [NFPA54:5.6.11.3]
1209.6 Gas Meters.
1209.6.1 Capacity. Gas meters shall be selectedfor the maximum expected pressure and permis-sible pressure drop. [NFPA 54:5.7.1]
READ ONLY
READ ONLY
174
1209.6 – 1209.7 IDAHO STATE PLUMBING CODE
1209.6.2 Location.
(A) Gas meters shall be located in ventilatedspaces readily accessible for examination,reading, replacement, or necessary mainte-nance. [NFPA 54:5.7.2.1]
(B) Gas meters shall not be placed where theywill be subjected to damage, such as adja-cent to a driveway; under a fire escape; inpublic passages, halls, or coal bins; or wherethey will be subject to excessive corrosion orvibration. [NFPA 54:5.7.2.2]
(C) Gas meters shall not be located where theywill be subjected to extreme temperatures orsudden extreme changes in temperature.Meters shall not be located in areas wherethey are subjected to temperatures beyondthose recommended by the manufacturer.[NFPA 54:5.7.2.4]
1209.6.3 Supports. Gas meters shall besupported or connected to rigid piping so as notto exert a strain on the meters. Where flexibleconnectors are used to connect a gas meter todownstream piping at mobile homes in mobilehome parks, the meter shall be supported by apost or bracket placed in a firm footing or byother means providing equivalent support.[NFPA 54:5.7.3]
1209.6.4 Meter Protection. Meters shall beprotected against overpressure, back-pressure,and vacuum where such conditions are antici-pated. [NFPA 54:5.7.4]
1209.6.5 Identification. Gas piping at multiplemeter installations shall be marked by a metaltag or other permanent means attached by theinstalling agency, designating the building orthe part of the building being supplied. [NFPA54:5.7.5]
1209.7 Gas Pressure Regulators.
1209.7.1 Where Required. A line gas pressureregulator or gas appliance pressure regulator, asapplicable, shall be installed where the gassupply pressure exceeds that at which thebranch supply line or gas utilization appliance isdesigned to operate or varies beyond designpressure limits. [NFPA 54:5.8.1]
1209.7.2 Listing. The line gas pressure regulatorshall be listed in accordance with CSA Z21.80.[NFPA 54:5.8.2]
1209.7.3 Location. The gas pressure regulatorshall be accessible for servicing. [NFPA 54:5.8.3]
1209.7.4 Regulator Protection. Pressure regu-lators shall be protected against physicaldamage. [NFPA 54:5.8.4]
1209.7.5 Venting.
(A) Line Gas Pressure Regulators.
(1) An independent vent to the outside ofthe building, sized in accordance withthe regulator manufacturer's instructions,shall be provided where the location ofa regulator is such that a ruptureddiaphragm will cause a hazard. Wherethere is more than one (1) regulator at alocation, each regulator shall have aseparate vent to the outside or, ifapproved by the Authority HavingJurisdiction, the vent lines shall bepermitted to be manifolded in accor-dance with accepted engineering prac-tices to minimize back-pressure in theevent of diaphragm failure. (See NFPA54:5.9.7 for information on properlylocating the vent.) Materials for ventpiping shall be in accordance withSection 1209.5.
Exception: A regulator and ventlimiting means combination listedas complying with CSA Z21.80,Standard for Line Pressure Regulators,shall be permitted to be used withouta vent to the outdoors.
(2) The vent shall be designed to preventthe entry of water, insects, or otherforeign materials that could causeblockage.
(3) At locations where regulators might besubmerged during floods, a special anti-flood-type breather vent fitting shall beinstalled, or the vent line shall beextended above the height of theexpected flood waters.
(4) A regulator shall not be vented to thegas appliance flue or exhaust system.[NFPA 54:5.8.5.1]
(B) Venting of Gas Appliance Pressure Regu-
lators. Venting of gas appliance pressureregulators shall comply with the followingrequirements:
(1) Gas appliance pressure regulatorsrequiring access to the atmosphere forsuccessful operation shall be equippedwith vent piping leading outdoors or, ifthe regulator vent is an integral part ofthe appliance, into the combustionchamber adjacent to a continuous pilot,unless constructed or equipped with avent-limiting means to limit the escapeof gas from the vent opening in theevent of diaphragm failure.
READ ONLY
READ ONLY
175
FUEL PIPING 1209.7 – 1209.11
(2) Vent-limiting means shall be employedon listed gas appliance pressure regula-tors only.
(3) In the case of vents leading outdoors,means shall be employed to preventwater from entering this piping and alsoto prevent blockage of vents by insectsand foreign matter.
(4) Under no circumstances shall a regu-lator be vented to the gas utilizationappliance flue or exhaust system.
(5) In the case of vents entering thecombustion chamber, the vent shall belocated so the escaping gas will bereadily ignited by the pilot and the heatliberated thereby will not adverselyaffect the normal operation of the safetyshutoff system. The terminus of the ventshall be securely held in a fixed positionrelative to the pilot. For manufacturedgas, the need for a flame arrester in thevent piping shall be determined.
(6) Vent lines from a gas appliance pres-sure regulator and bleed lines from adiaphragm-type valve shall not beconnected to a common manifold termi-nating in a combustion chamber.
Vent lines shall not terminate in posi-tive-pressure-type combustion cham-bers. [NFPA 54:9.1.19]
(C) Discharge of Vents.
(1) The discharge stacks, vents, or outletparts of all pressure-relieving and pres-sure-limiting devices shall be located sothat gas is safely discharged into theoutside atmosphere.
(2) Discharge stacks or vents shall bedesigned to prevent the entry of water,insects, or any other foreign materialthat could cause blockage. The dischargestack or vent line shall be not less thanthe same size as the outlet of the pres-sure-relieving device. [NFPA 54:5.9.7]
1209.7.6 Bypass Piping. Valved and regulatedbypasses shall be permitted to be placed aroundgas line pressure regulators where continuity ofservice is imperative. [NFPA 54:5.8.6]
1209.7.7 Identification. Line pressure regulatorsat multiple regulator installations shall bemarked by a metal tag or other permanentmeans designating the building or the part of thebuilding being supplied. [NFPA 54:5.8.7]
1209.8 Back-Pressure Protection.
1209.8.1 Where to Install. Protective devicesshall be installed as close to the utilization
appliance as practical, where the design ofutilization appliances connected are such thatair, oxygen, or standby gases could be forcedinto the gas supply system. [NFPA 54:5.10.1.1]Gas and air combustion mixers incorporatingdouble diaphragm "zero" or "atmosphere"governors or regulators shall require no furtherprotection unless connected directly tocompressed air or oxygen at pressures of five(5) psi (34 kPa) or more. [NFPA 54:5.10.1.2]
1209.8.2 Protective Devices. Protective devicesshall include but not be limited to the following:
(1) Check valves
(2) Three-way valves (of the type thatcompletely closes one side before starting toopen the other side)
(3) Reverse flow indicators controlling positiveshutoff valves
(4) Normally closed air-actuated positiveshutoff pressure regulators [NFPA 54:5.10.2]
1209.9 Low-Pressure Protection. A protectivedevice shall be installed between the meter and thegas utilization appliance if the operation of the appli-ance (i.e., gas compressors) is such that it couldproduce a vacuum or a dangerous reduction in gaspressure at the meter. Such devices include, but arenot limited to, mechanical, diaphragm-operated, orelectrically operated low-pressure shutoff valves.[NFPA 54:5.11]
1209.10 Shutoff Valves. Shutoff valves shall beapproved and shall be selected giving considerationto pressure drop, service involved, emergency use,and reliability of operation. Shutoff valves of size one(1) inch (25 mm) National Pipe Thread and smallershall be listed. [NFPA 54:5.12]
1209.11 Expansion and Flexibility.
1209.11.1 Design. Piping systems shall bedesigned to have sufficient flexibility to preventthermal expansion or contraction from causingexcessive stresses in the piping material, exces-sive bending or loads at joints, or undesirableforces or moments at points of connections toequipment and at anchorage or guide points.Formal calculations or model tests shall berequired only where reasonable doubt exists asto the adequate flexibility of the system. [NFPA54:5.13.1]
Flexibility shall be provided by the use ofbends, loops, offsets, or couplings of the sliptype. Provision shall be made to absorb thermalchanges by the use of expansion joints of thebellows type, or by the use of "ball" or "swivel"joints. Expansion joints of the slip type shall notbe used inside buildings or for thermal expan-
READ ONLY
READ ONLY
176
1209.11 – 1211.1 IDAHO STATE PLUMBING CODE
sion. Where expansion joints are used, anchorsor ties of sufficient strength and rigidity shall beinstalled to provide for end forces due to fluidpressure and other causes. [NFPA 54:5.13.1.1]
Pipe alignment guides shall be used withexpansion joints according to the recommendedpractice of the joint manufacturer. [NFPA54:5.13.1.2]
1209.11.2 Special Local Conditions. Wherelocal conditions include earthquake, tornado,unstable ground, or flood hazards, specialconsideration shall be given to increasedstrength and flexibility of piping supports andconnections. [NFPA 54:5.13.2]
1210.0 Excess Flow Valve.
Where automatic excess flow gas valves are installed,they shall be listed, sized, and installed in accor-dance with the manufacturer’s instructions. [NFPA54-09:5.13]
1211.0 Gas Piping Installation.
1211.1 Piping Underground.
1211.1.1 Clearances. Underground gas pipingshall be installed with sufficient clearance fromany other underground structure to avoidcontact therewith, to allow maintenance, and toprotect against damage from proximity to otherstructures. In addition, underground plasticpiping shall be installed with sufficient clearanceor shall be insulated from any source of heat soas to prevent the heat from impairing theserviceability of the pipe. [NFPA 54:7.1.1]
1211.1.2 Protection Against Damage.
(A) Cover Requirements. Underground pipingsystems shall be installed with a minimumof eighteen (18) inches (460 mm) of cover.Where external damage to the pipe is notlikely to result, the cover shall be aminimum of twelve (12) inches (300 mm).Where a minimum of twelve (12) inches (300mm) of cover cannot be provided, the pipeshall be installed in conduit or bridged(shielded). [NFPA 54:7.1.2.1]
(B) Trenches. The trench shall be graded sothat the pipe has a firm, substantiallycontinuous bearing on the bottom of thetrench. [NFPA 54:7.1.2.2]
(C) Backfilling. Where flooding of the trench isdone to consolidate the backfill, care shall beexercised to see that the pipe is not floatedfrom its firm bearing on the trench bottom.[NFPA 54:7.1.2.3]
1211.1.3 Protection Against Corrosion. Gaspiping in contact with earth or other materialthat could corrode the piping shall be protectedagainst corrosion in an approved manner. Whendissimilar metals are joined underground, aninsulating coupling or fitting shall be used.Piping shall not be laid in contact with cinders.Uncoated threaded or socket-welded joints shallnot be used in piping in contact with soil orwhere internal or external crevice corrosion isknown to occur. [NFPA 54:7.1.3]
1211.1.4 Protection Against Freezing. Wherethe formation of hydrates or ice is known tooccur, piping shall be protected against freezing.[NFPA 54:7.1.4]
1211.1.5 Piping Through Foundation Wall.
Underground piping installed through the outerfoundation or basement wall of a building, shallbe encased in a protective sleeve or protected byan approved device or method. The spacebetween the gas piping and the building orsleeve shall be sealed to prevent entry of gas andwater. [NFPA 54:7.1.5]
1211.1.6 Piping Underground Beneath Build-ings. Where the installation of gas piping under-ground beneath buildings is unavoidable, thepiping shall be encased in an approved conduitdesigned to withstand the superimposed loads.[NFPA 54:7.1.6] The conduit shall extend into anormally usable and accessible portion of thebuilding and, at the point where the conduitterminates in the building, the space between theconduit and the gas piping shall be sealed toprevent the possible entrance of any gas leakage.Where the end sealing is of a type that will retainthe full pressure of the pipe, the conduit shall bedesigned for the same pressure as the pipe. Theconduit shall extend not less than (4) inches (100mm) outside the building, be vented above gradeto the outside, and be installed so as to prevent theentrance of water and insects. [NFPA 54:7.1.6.1]
1211.1.7 Plastic Pipe.
(A) Connection of Plastic Piping. Plastic pipeshall be installed outside, undergroundonly.
Exception No. 1: Plastic pipe shall bepermitted to terminate above groundwhere an anodeless riser is used.
Exception No. 2: Plastic pipe shall bepermitted to terminate with a wall headadapter above ground in buildings,including basements, where the plasticpipe is inserted in a piping materialpermitted for use in buildings. [NFPA54:7.1.7.1]
READ ONLY
READ ONLY
177
FUEL PIPING 1211.1 – 1211.2
(B) Connections Between Metallic and
Plastic Piping. Connections made betweenmetallic and plastic piping shall be madeonly with fittings conforming to one of thefollowing:
(1) ASTM D2513, Standard Specification forThermoplastic Gas Pressure Pipe, Tubing,and Fittings, Category I transition fittings.
(2) ASTM F1973, Standard Specification forFactory Assembled Anodeless Risers andTransition Fittings in Polyethylene (PE)and Polyamide 11 (PA11) Fuel Gas Distri-bution Systems.
(3) ASTM F2509, Standard Specification forField-Assembled Anodeless Riser Kits forUse on Outside Diameter ControlledPolyethylene Gas Distribution Pipe andTubing. [NFPA 54-09:7.1.7.2]
(C) An electrically continuous corrosion-resis-tant tracer wire (minimum AWG 14) or tapeshall be buried with the plastic pipe to facili-tate locating. One (1) end shall be broughtabove ground at a building wall or riser.[NFPA 54:7.1.7.3]
1211.2 Installation of Piping.
1211.2.1 Piping installed above ground shall besecurely supported and located where it will beprotected from physical damage (also see1211.1.4). Where passing through an outsidewall, the piping shall also be protected againstcorrosion by coating or wrapping with an inertmaterial approved for such applications. Wherepiping is encased in a protective pipe sleeve, theannular space between the gas piping and thesleeve shall be sealed at the wall to prevent theentry of water, insects, or rodents. [NFPA54:7.2.1]
1211.2.2 Building Structure.
(1) The installation of gas piping shall not cause structural stresses within building compo-nents to exceed allowable design limits.[NFPA 54:7.2.2.1]
(2) Approval shall be obtained before anybeams or joists are cut or notched. [NFPA54:7.2.2.2] Permission shall be obtained fromthe Authority Having Jurisdiction.
1211.2.3 Other than Dry Gas. Drips, sloping,protection from freezing, and branch pipeconnections, as provided for in Section 1211.1.4,1211.8.1, and Section 1211.10, shall be providedwhen other than dry gas is distributed andclimactic conditions make such provisions neces-sary. [NFPA 54:7.2.3]
1211.2.4 Gas Piping to be Sloped. Piping forother than dry gas conditions shall be sloped notless than one-fourth (1/4) inch in fifteen (15) feet(8 mm in 4,572 mm) to prevent traps. [NFPA54:7.2.4]
1211.2.4.1 Ceiling Locations. Gas pipingshall be permitted to be installed in acces-sible spaces between a fixed ceiling and adropped ceiling, whether or not such spacesare used as a plenum. Valves shall not belocated in such spaces.
Exception: Appliance shutoff valvesrequired by this code shall be permittedto be installed in accessible spacescontaining vented gas utilization appli-ances.
1211.2.5 Prohibited Locations. Gas pipinginside any building shall not be installed in orthrough a circulating air duct, clothes chute,chimney or gas vent, ventilating duct, dumb-waiter, or elevator shaft. [NFPA 54:7.2.5] Thisprovision shall not apply to ducts used toprovide combustion and ventilation air in accor-dance with Section 507.0 or to above-ceilingspaces as covered in Section 1211.2.4.1.
1211.2.6 Hangers, Supports, and Anchors.
(A) Piping shall be supported with metal pipehooks, metal pipe straps, metal bands, metalbrackets, metal hangers, or building struc-tural components, suitable for the size ofpiping, of adequate strength and quality;and located at intervals so as to prevent ordamp out excessive vibration. Piping shallbe anchored to prevent undue strains onconnected equipment and shall not besupported by other piping. Pipe hangersand supports shall conform to the require-ments of MSS SP-58, Pipe Hangers andSupports Materials, Design and Manufacture.[NFPA 54:7.2.6.1]
(B) Spacings of supports in gas-piping installa-tions shall not exceed as shown in Table 12-3. Spacing of supports for CSST shall be inaccordance with the CSST manufacturer'sinstruction. [NFPA 54:7.2.6.2]
(C) Supports, hangers, and anchors shall beinstalled so as not to interfere with the freeexpansion and contraction of the pipingbetween anchors. All parts of the supportingequipment shall be designed and installedso they will not be disengaged by move-ment of the supported piping. [NFPA54:7.2.6.3]
READ ONLY
READ ONLY
1211.2.7 Removal of Pipe. Where pipingcontaining gas is to be removed, the line shall befirst disconnected from sources of gas and thenthoroughly purged with air, water, or inert gasbefore any cutting or welding is done. (SeeSection 1214.6.) [NFPA 54:7.2.7]
1211.3 Concealed Piping in Buildings.
1211.3.1 General. Gas piping in concealed loca-tions shall be installed in accordance with thissection. [NFPA 54:7.3.1]
1211.3.2 Connections. Where gas piping is tobe concealed, unions, tubing fittings, right andleft couplings, bushings, swing joints, andcompression couplings made by combinations offittings shall not be used. Connections shall be ofthe following type:
(1) Pipe fittings such as elbows, tees, andcouplings.
(2) Joining tubing by brazing (see Section1209.5.8.2).
(3) Fittings listed for use in concealed spacesthat have been demonstrated to sustain,without leakage, any forces due to tempera-ture expansion or contraction, vibration, orfatigue based on their geographic location,application, or operation.
(4) Where necessary to insert fittings in gas pipethat has been installed in a concealed location,the pipe shall be reconnected by welding,flanges, or the use of a ground joint unionwith the nut center-punched to prevent loos-ening by vibration. [NFPA 54:7.3.2]
1211.3.3 Piping in Partitions. Concealed gaspiping shall not be located in solid partitions.[NFPA 54:7.3.3]
1211.3.4 Tubing in Partitions. This provisionshall not apply to tubing that pierces walls,floors, or partitions or to tubing installed verti-cally and horizontally inside hollow walls or
partitions without protection along its entireconcealed length where both of the followingrequirements are met:
(1) A steel striker barrier not less than 0.0508inches (1.3 mm) thick, or equivalent, isinstalled between the tubing, the finishedwall and extends at least 4 inches (100 mm)beyond concealed penetrations of plates, firestops, wall studs, and so on.
(2) The tubing is installed in single runs and isnot rigidly secured. [NFPA 54:7.3.4]
1211.3.5 Piping in Floors. In industrial occu-pancies, gas piping in solid floors such asconcrete shall be laid in channels in the floor andcovered to permit access to the piping withminimum damage to the building. Where pipingin floor channels could be exposed to excessivemoisture or corrosive substances, the pipingshall be protected in an approved manner.[NFPA 54:7.3.5.1]
Exception: In other than industrial occupan-cies and where approved by the AuthorityHaving Jurisdiction, gas piping embeddedin concrete floor slabs constructed with port-land cement shall be surrounded with aminimum of one and one half (1-1/2) inches(38 mm) of concrete and shall not be inphysical contact with other metallic struc-tures such as reinforcing rods or electricallyneutral conductors. Piping, fittings, andrisers shall be protected against corrosion inaccordance with Section 1209.5.6. Pipingshall not be embedded in concrete slabscontaining quick-set additives or cinderaggregate. [NFPA 54:7.3.5.2]
1211.4 Piping in Vertical Chases. (See Section1202.0.) Where gas piping exceeding five (5) psi (34kPa) is located within vertical chases in accordancewith Section 1211.5, the requirements of Sections1211.5.1 through 1211.5.3 shall apply. [NFPA 54:7.4]
1211.5 Maximum Design Operating Pressure. Themaximum design operating pressure for pipingsystems located inside buildings shall not exceed five(5) psi (34 kPa) unless one (1) or more of thefollowing conditions are met:
(1) The piping system is welded.
(2) The piping is located in a ventilated chase orotherwise enclosed for protection against acci-dental gas accumulation.
(3) The piping is located inside buildings or sepa-rate areas of buildings used exclusively for oneof the following:
TABLE 12-3
Support of Piping
[NFPA 54: Table 7.2.6.2]
Steel Pipe,
Nominal Size
of Pipe (in.)
Spacing of
Supports
(ft.)
Nominal Size
of Tubing
Smooth-wall
(In. O.D.)
Spacing of
Supports
(ft.)
1/2 6 1/2 4
3/4 or 1 8 5/8 or 3/4 6
1-1/4 or larger 10 7/8 or 1 8
(horizontal) (horizontal)
1-1/4 or larger every floor 1 or larger every floor
(vertical) level (vertical) level
For SI units: 1 ft. = 0.305 m.
178
Table 12-3 – 1211.5 IDAHO STATE PLUMBING CODE
READ ONLY
READ ONLY
179
FUEL PIPING 1211.5 – 1211.7
(a) Industrial processing or heating
(b) Research
(c) Warehousing
(d) Boiler or mechanical equipment rooms
(4) The piping is a temporary installation for build-ings under construction.
(5) The piping serves appliances or equipment usedfor agricultural purposes.
(6) The piping system is an LP-Gas piping systemwith a design operating pressure greater than 20psi and complies with NFPA 54:5.5.2. LiquefiedPetroleum Gas Systems designed to operatebelow -5ºF (-21ºC) with butane or a propane-butane mix shall be designed to either accommo-date liquid LP-Gas or to prevent LP-Gas vaporfrom condensing back into liquid. [NFPA 54-09:5.5.1]
1211.5.1 Pressure Reduction. (See Section1202.0.) Where pressure reduction is required inbranch connections for compliance with Section1211.5, such reduction shall take place eitherinside the chase or immediately adjacent to theoutside wall of the chase. Regulator venting anddownstream overpressure protection shall complywith Section 1209.7.4 and NFPA Section 5.9. Theregulator shall be accessible for service and repairand vented in accordance with one (1) of thefollowing:
(1) Where the fuel gas is lighter than air, regula-tors equipped with a vent-limiting meansshall be permitted to be vented into thechase. Regulators not equipped with a vent-limiting means shall be permitted to bevented either directly to the outdoors or to apoint within the top one (1) foot (0.3 m) of thechase.
(2) Where the fuel gas is heavier than air, theregulator vent shall be vented only directlyto the outdoors. [NFPA 54:7.4.1]
1211.5.2 Liquefied Petroleum Gas Systems.
The maximum operating pressure of LP-Gaspiping systems shall be:
(1) In accordance with Section 1211.5.1;
(2) In accordance with NFPA 58, where thepressure exceeds twenty (20) psi (138 kPa)and;
(3) Designed to either accommodate liquid LP-Gas or prevent LP-Gas vapor from condensingback into a liquid in buildings having systemsdesigned to operate below -5ºF (-21ºC) or withbutane or a propane–butane mix.
1211.5.3 Construction. Chase constructionshall comply with local building codes withrespect to fire resistance and protection of hori-zontal and vertical openings. [NFPA 54:7.4.2]
1211.5.4 Ventilation. A chase shall be ventilatedto the outdoors and only at the top. The open-ings shall have a minimum free area (in squareinches) equal to the product of one-half (1/2) ofthe maximum pressure in the piping (in psi)times the largest nominal diameter of that piping(in inches), or the cross-sectional area of thechase, whichever is smaller. Where more thanone (1) fuel gas piping system is present, the freearea for each system shall be calculated and thelargest area used. [NFPA 54:7.4.3]
1211.6 Appliance Over Pressure Protection. Themaximum operating pressure for piping systemsserving appliances designed to operate at fourteen(14) inches w.c. inlet pressure or less shall be two (2)psig unless an over-pressure protection devicedesigned to limit pressure at the appliance to two (2)psig upon failure of the line gas pressure regulator isinstalled.
1211.7 Gas Pipe Turns. Changes in direction of gaspipe shall be made by the use of fittings, or factorybends. [NFPA 54:7.5]
1211.7.1 Metallic Pipe. Metallic pipe bendsshall comply with the following:
(1) Bends shall be made only with bendingequipment and procedures intended for thatpurpose.
(2) Bends shall be smooth and free from buck-ling, cracks, or other evidence of mechanicaldamage.
(3) The longitudinal weld of the pipe shall benear the neutral axis of the bend.
(4) The pipe shall not be bent through an arc ofmore than 90 degrees.
(5) The inside radius of a bend shall be not lessthan six (6) times the outside diameter of thepipe. [NFPA 54:7.5.1]
1211.7.2 Plastic Pipe. Plastic pipe bends shallcomply with the following:
(1) The pipe shall not be damaged and theinternal diameter of the pipe shall not beeffectively reduced.
(2) Joints shall not be located in pipe bends.
(3) The radius of the inner curve of such bendsshall be not less than twenty-five (25) timesthe inside diameter of the pipe.
(4) Where the piping manufacturer specifies theuse of special bending equipment or proce-dures, such equipment or procedures shallbe used. [NFPA 54:7.5.2]
READ ONLY
READ ONLY
180
1211.7 – 1211.11 IDAHO STATE PLUMBING CODE
1211.7.3 Elbows. Factory-made welding elbowsor transverse segments cut therefrom shall havean arc length measured along the crotch of atleast one (1) inch (25 mm) for pipe sizes two (2)inches and larger. [NFPA 54:7.5.3]
1211.8 Drips and Sediment Traps.
1211.8.1 Provide Drips Where Necessary. Forother than dry gas conditions, a drip shall beprovided at any point in the line of pipe wherecondensate could collect. Where required by theAuthority Having Jurisdiction or the serving gassupplier, a drip shall also be provided at theoutlet of the meter. This drip shall be so installedas to constitute a trap wherein an accumulationof condensate will shut off the flow of gas beforeit will run back into the meter. [NFPA 54:7.6.1]
1211.8.2 Location of Drips. Drips shall beinstalled only in such locations that they will bereadily accessible to permit cleaning oremptying. A drip shall not be located where thecondensate is likely to freeze. [NFPA 54:7.6.2]
1211.8.3 Sediment Traps. (See Section 1212.7.)
1211.9 Outlets.
1211.9.1 Location and Installation.
(1) The outlet fittings or piping shall be securelyfastened in place. [NFPA 54:7.7.1.1]
(2) Outlets shall not be located behind doors.[NFPA 54:7.7.1.2]
(3) Outlets shall be located far enough fromfloors, walls, patios, slabs, and ceilings topermit the use of wrenches withoutstraining, bending, or damaging the piping.[NFPA 54:7.7.1.3]
(4) The unthreaded portion of gas pipingoutlets shall extend not less than one (1)inch (25 mm) through finished ceilings orindoor or outdoor walls. [NFPA 54:7.7.1.4]
(5) The unthreaded portion of gas-pipingoutlets shall extend not less than two (2)inches (50 mm) above the surface of floorsor outdoor patios or slabs. [NFPA 54:7.7.1.5]
(6) The provisions of Sections 1211.9.1(4) and(5) shall not apply to listed quick-disconnectdevices of the flush-mounted type or listedgas convenience outlets. Such devices shallbe installed in accordance with the manufac-turer’s installation instructions. [NFPA54:7.7.1.6]
1211.9.2 Cap Outlets.
(A) Each outlet, including a valve, shall beclosed gas-tight with a threaded plug or capimmediately after installation and shall beleft closed until the gas utilization appliance
is connected thereto. When an appliance isdisconnected from an outlet and the outlet isnot to be used again immediately, it shall beclosed gas-tight.
Exception No. 1: Laboratory equipmentinstalled in accordance with 1212.2(A)shall be permitted.
Exception No. 2: The use of a listedquick-disconnect device with integralshutoff or listed gas convenience outletshall be permitted. [NFPA 54:7.7.2.1]
(B) Appliance shutoff valves installed in fire-places shall be removed and the pipingcapped gas-tight where the fireplace is usedfor solid-fuel burning. [NFPA 54:7.7.2.2]
1211.10 Branch Pipe Connection. When a branchoutlet is placed on a main supply line before it isknown what size pipe will be connected to it, theoutlet shall be of the same size as the line thatsupplies it. [NFPA 54:7.8]
1211.11 Manual Gas Shutoff Valves. (Also seeSection 1212.5)
1211.11.1 Valves at Regulators. An accessiblegas shutoff valve shall be provided upstream ofeach gas pressure regulator. Where two (2) gaspressure regulators are installed in series in asingle gas line, a manual valve shall not berequired at the second regulator. [NFPA 54:7.9.1]
1211.11.2 Valves Controlling Multiple
Systems.
(A) Accessibility of Gas Valves. Main gasshutoff valves controlling several gas pipingsystems shall be readily accessible for opera-tion and installed so as to be protected fromphysical damage. They shall be marked witha metal tag or other permanent meansattached by the installing agency so that thegas piping systems supplied through themcan be readily identified. [NFPA 54:7.9.2.1]
(B) Shutoff Valves for Multiple House Lines.
In multiple-tenant buildings suppliedthrough a master meter, or through one (1)service regulator where a meter is notprovided, or where meters or service regula-tors are not readily accessible from theequipment location, an individual shutoffvalve for each apartment or tenant line shallbe provided at a convenient point of generalaccessibility.
In a common system serving a numberof individual buildings, shutoff valves shallbe installed at each building. [NFPA54:7.9.2.2]
READ ONLY
READ ONLY
181
FUEL PIPING 1211.11 –1212.1
1211.11.3 Emergency Shutoff Valves. An exte-rior shutoff valve to permit turning off the gassupply to each building in an emergency shall beprovided. The emergency shutoff valves shall beplainly marked as such and their locationsposted as required by the Authority HavingJurisdiction. [NFPA 54:7.9.2.3]
1211.11.4 Shutoff Valve For Laboratories.Each laboratory space containing two (2) ormore gas outlets installed on tables, benches, orin hoods in educational, research, commercialand industrial occupancies shall have a singleshutoff valve through which such gas outlets aresupplied. The shutoff valve shall be accessibleand shall be located within the laboratory orlocated adjacent to the laboratory’s egress doorand shall be identified. [NFPA 54-09:7.9.2.4]
1211.12 Prohibited Devices. No device shall beplaced inside the gas piping or fittings that willreduce the cross-sectional area or otherwise obstructthe free flow of gas, except where proper allowancein the piping system design has been made for sucha device and where approved by the AuthorityHaving Jurisdiction. [NFPA 54:7.10]
1211.13 Systems Containing Gas-Air MixturesOutside the Flammable Range. Where gas-airmixing machines are employed to produce mixturesabove or below the flammable range, they shall beprovided with stops to prevent adjustment of themixture to within or approaching the flammablerange. [NFPA 54:7.11]
1211.14 Systems Containing Flammable Gas-AirMixtures. Systems containing flammable gas-airmixtures shall be in accordance with NFPA 54.
1211.15 Electrical Bonding and Grounding.
1211.15.1 Pipe and Tubing other than CSST.Each above ground portion of a gas pipingsystem other than CSST that is likely to becomeenergized shall be electrically continuous andbonded to an effective ground-fault currentpath. Gas piping, other than CSST shall beconsidered to be bonded when it is connected toappliances that are connected to the appliancegrounding conductor of the circuit supplyingthat appliance. [NFPA 54-09:7.13.1]
1211.15.2 CSST gas piping systems shall bebonded to the electrical service grounding elec-trode system at the point where the gas serviceenters the building. The bonding jumper shall benot smaller than six (6) AWG copper wire.[NFPA 54-09:7.13.2]
1211.15.3 Gas piping shall not be used as agrounding conductor or electrode. This does notpreclude the bonding of metallic piping to agrounding system. [NFPA 54-09:7.13.3]
1211.15.4 Where a lightning protection systemis installed, the bonding of the gas piping systemshall be in accordance with NFPA 780, Standardfor Installation of Lightning Protection Systems.[NFPA 54-09:7.13.4]
1211.16 Electrical Circuits. Electrical circuits shallnot utilize gas piping or components as conductors.[NFPA 54:7.14]
Exception: Low-voltage (50V or less) controlcircuits, ignition circuits, and electronic flamedetection device circuits shall be permitted tomake use of piping or components as a part ofan electric circuit.
1211.17 Electrical Connections.
(A) Electrical connections between wiring andelectrically operated control devices in apiping system shall conform to the require-ments of NFPA 70, National Electrical Code.(See Section 1211.15) [NFPA 54:7.15.1]
(B) Any essential safety control depending onelectric current as the operating mediumshall be of a type that will shut off (fail safe)the flow of gas in the event of currentfailure. [NFPA 54:7.15.2]
1212.0 Appliance Connections to Building Piping.
1212.1 Connecting Gas Appliances. Gas utiliza-tion appliances shall be connected to the buildingpiping in compliance with Sections 1212.5 and 1212.6by one of the following [NFPA 54:9.6.1]:
(1) Rigid metallic pipe and fittings. [NFPA 54:9.6.1(1)]
(2) Semirigid metallic tubing and metallic fittings.Aluminum alloy tubing shall not be used inexterior locations. [NFPA 54:9.6.1(2)]
(3) Listed flexible gas connectors in compliance withCSA Z21.24, Standard for Connectors for Gas Appli-ances. The connector shall be used in accordancewith the terms of their listing that are completelyin the same room as the appliance. [NFPA54:9.6.1(3)]
(4) CSST where installed in accordance with themanufacturer's instructions. [NFPA 54:9.6.1(5)]
(5) Listed nonmetallic gas hose connectors in accor-dance with 1212.3. [NFPA 54:9.6.1(6)]
(6) Gas-fired food service (commercial cooking)appliances listed for use with casters or otherwisesubject to movement for cleaning, and other largeand heavy gas utilization appliances that can bemoved, shall be connected in accordance with theconnector manufacturer's installation instructionsusing a listed appliance connector complyingwith CSA Z21.69, Standard for Connectors forMovable Gas Appliances. The commercial cookingappliance connector installation shall be config-ured in accordance with the manufacturer’sinstallation instructions. [NFPA 54-09:9.6.1.1]
READ ONLY
READ ONLY
182
1212.1 – 1212.7 IDAHO STATE PLUMBING CODE
(7) Movement of appliances with casters shall belimited by a restraining device installed in accor-dance with the connector and appliance manu-facturer's installation instructions. [NFPA 54-09:9.6.1.2]
(8) In 1212.1(2), (3), and (5), the connector or tubingshall be installed so as to be protected againstphysical and thermal damage. Aluminum alloytubing and connectors shall be coated to protectagainst external corrosion where they are incontact with masonry, plaster, insulation, or aresubject to repeated wettings by such liquids aswater (except rain water), detergents, orsewage.[NFPA 54:9.6.1(7)]
1212.2 Suspended Low-Intensity Infrared TubeHeaters. Suspended low-intensity infrared tubeheaters shall be connected to the building pipingsystem with a connector listed for the application inaccordance with CSA Z21.24/CGA 6.10, Connectorsfor Gas Appliances. [NFPA 54-09:9.6.1.3]
(A) The connector shall be installed in accordancewith the tube heater installation instructions,and shall be in the same room as the appliance.[NFPA 54-09:9.6.1.3(A)]
(B) Only one connector shall be used per appliance.[NFPA 54-09:9.6.1.3(B)]
1212.3 Use of Nonmetallic Gas Hose Connectors.Listed nonmetallic gas hose connectors shall be usedin accordance with the terms of their listing and asfollows [NFPA 54:9.6.2]:
(A) Indoor. Indoor gas hose connectors shall beused only to connect laboratory, shop, andironing equipment requiring mobility duringoperation. An equipment shutoff valve shall beinstalled where the connector is attached to thebuilding piping. The connector shall be ofminimum length and shall not exceed six (6) feet(1,829 mm). The connector shall not be concealedand shall not extend from one (1) room toanother or pass through wall partitions, ceilings,or floors. [NFPA 54:9.6.2(1)]
(B) Outdoor. Outdoor gas hose connectors arepermitted to connect portable outdoor gas-firedappliances. An appliance shutoff valve, a listedquick-disconnect device, or a listed gas conve-nience outlet shall be installed where the connectoris attached to the supply piping and in such amanner to prevent the accumulation of water orforeign matter. This connection shall be made onlyin the outdoor area where the appliance is to beused. [NFPA 54:9.6.2(2)] The connector length shallnot exceed fifteen (15) feet (4,572 mm).
1212.4 Connection of Portable and Mobile Indus-
trial Gas Appliance.
(A) Where portable industrial gas utilization appli-ances, or appliances requiring mobility or
subject to vibration, are connected to thebuilding gas piping system by the use of a flex-ible hose, the hose shall be suitable and safe forthe conditions under which it can be used.[NFPA 54:9.6.3.1]
(B) Where industrial gas utilization appliancesrequiring mobility are connected to the rigidpiping by the use of swivel joints or couplings,the swivel joints or couplings shall be suitablefor the service required, and only the minimumnumber required shall be installed. [NFPA54:9.6.3.2]
(C) Where industrial gas utilization appliancessubject to vibration are connected to the buildingpiping system by the use of all-metal flexibleconnectors, the connectors shall be suitable forthe service required. [NFPA 54:9.6.3.3]
(D) Where flexible connections are used, they shallbe of the minimum practical length and shall notextend from one (1) room to another or passthrough any walls, partitions, ceilings, or floors.Flexible connections shall not be used in anyconcealed location. They shall be protectedagainst physical or thermal damage and shall beprovided with gas shutoff valves in readilyaccessible locations in rigid piping upstreamfrom the flexible connections. [NFPA 54:9.6.3.4]
1212.5 Appliance Shutoff Valves and Connec-
tions. Gas utilization appliance connected to apiping system shall have an accessible, approvedmanual shutoff valve with a nondisplaceable valvemember, or a listed gas convenience outlet installedwithin six (6) feet (1.8 m) of the appliance it serves.Where a connector is used, the valve shall beinstalled upstream of the connector. A union orflanged connection shall be provided downstreamfrom this valve to permit removal of controls.Shutoff valves serving decorative gas appliancesshall be permitted to be installed in fireplaces iflisted for such use. [NFPA 54:9.6.4, 9.6.4.1]
1212.6 Quick-Disconnect Devices. Quick-disconnectdevices used to connect appliances to the buildingpiping shall be listed. Where they are installedindoors, an approved manual shutoff valve with anondisplaceable valve member shall be installedupstream of the quick-disconnect device. [NFPA54:9.6.5]
1212.7 Sediment Trap. Where a sediment trap isnot incorporated as a part of the gas utilization appli-ance, a sediment trap shall be installed downstreamof the appliance shutoff valve as close to the inlet ofthe appliance as practical at the time of applianceinstallation. The sediment trap shall be either a teefitting with a capped nipple in the bottom outlet, as
READ ONLY
READ ONLY
183
FUEL PIPING 1212.7 –1214.2
illustrated in Figure 12-1, or other device recognizedas an effective sediment trap. Illuminating appli-ances, ranges, clothes dryers, decorative ventedappliances for installation in vented fireplaces, gasfireplaces, and outdoor grills shall not be required tobe so equipped. [NFPA 54-09:9.6.7]
1212.8 Installation of Piping. Piping shall beinstalled in a manner not to interfere with inspection,maintenance, or servicing of the gas utilizationequipment. [NFPA 54:9.6.8]
1213.0 Liquefied Petroleum Gas Facilities andPiping.
Liquefied petroleum gas facilities shall comply withNFPA 58, Liquefied Petroleum Gas Code.
1214.0 Pressure Testing and Inspection.
1214.1 General.
1214.1.1 Prior to acceptance and initial opera-tion, piping installations shall be inspected andpressure-tested to determine that the materials,design, fabrication, and installation practicescomply with the requirements of this code.[NFPA 54:8.1.1.1]
1214.1.2 Inspection shall consist of visual exam-ination during or after manufacture, fabrication,assembly, or pressure tests, as appropriate.Supplementary types of non-destructive inspec-tion techniques, such as magnetic-particle, radio-graphic, and ultrasonic, shall not be requiredunless specifically listed herein or in the engi-neering design. [NFPA 54:8.1.1.2]
1214.1.3 Where repairs or additions are madefollowing the pressure test, the affected pipingshall be tested. Minor repairs and additions arenot required to be pressure-tested provided thatthe work is inspected and connections are testedwith a noncorrosive leak-detecting fluid or otherleak-detecting methods approved by theAuthority Having Jurisdiction. [NFPA 54:8.1.1.3]
1214.1.4 Where new branches are installed fromthe point of delivery to new appliances, only thenewly installed branches shall be required to bepressure-tested. Connections between the newpiping and the existing piping shall be testedwith a noncorrosive leak-detecting fluid orapproved leak-detecting methods. [NFPA54:8.1.1.4]
1214.1.5 A piping system shall be tested as acomplete unit or in sections. Under no circum-stances shall a valve in a line be used as a bulk-head between gas in one (1) section of the pipingsystem and test medium in an adjacent section,unless two (2) valves are installed in series witha valved "telltale" located between these valves.A valve shall not be subjected to the test pres-sure unless it can be determined that the valve,including the valve-closing mechanism, isdesigned to safely withstand the pressure.[NFPA 54:8.1.1.5]
1214.1.6 Regulator and valve assemblies fabri-cated independently of the piping system inwhich they are to be installed shall be permittedto be tested with inert gas or air at the time offabrication. [NFPA 54:8.1.1.6]
1214.1.7 Test Medium. The test medium shallbe air, nitrogen, carbon dioxide, or an inert gas.OXYGEN SHALL NEVER BE USED. [NFPA54:8.1.2]
1214.2 Test Preparation.
1214.2.1 Pipe joints, including welds, shall beleft exposed for examination during the test.
Exception: Covered or concealed pipe endjoints that have been previously tested inaccordance with this code. [NFPA 54:8.1.3.1]
1214.2.2 Expansion joints shall be providedwith temporary restraints, if required for theadditional thrust load under test. [NFPA54:8.1.3.2]
1214.2.3 Appliances and equipment that are notto be included in the test shall be either discon-nected from the piping or isolated by blanks,blind flanges, or caps. Flanged joints at whichblinds are inserted to blank off other equipmentduring the test shall not be required to be tested.[NFPA 54:8.1.3.3]
1214.2.4 Where the piping system is connectedto appliances, equipment, or equipment compo-nents designed for operating pressures of lessthan the test pressure, such appliances, equip-ment, or equipment components shall beisolated from the piping system by discon-necting them and capping the outlets. [NFPA54:8.1.3.4]
Figure 12-1 Method of Installing a Tee Fitting
Sediment Trap. [NFPA 54: Figure 9.6.7]
READ ONLY
READ ONLY
1214.2.5 Where the piping system is connectedto appliances, equipment, or equipment compo-nents designed for operating pressures equal toor exceeding the test pressure, such appliancesshall be isolated from the piping system byclosing the individual appliance or equipmentshutoff valves. [NFPA 54:8.1.3.5]
1214.2.6 Testing of piping systems shall be donewith due regard for the safety of employees andthe public during the test. Bulkheads, anchorage,and bracing suitably designed to resist test pres-sures shall be installed if necessary. Prior totesting, the interior of the pipe shall be cleared offoreign material. [NFPA 54:8.1.3.6]
1214.3 Test Pressure.
1214.3.1 Test pressure shall be measured with amanometer or with a pressure-measuring devicedesigned and calibrated to read, record, or indi-cate a pressure loss due to leakage during thepressure test period. The source of pressure shallbe isolated before the pressure tests are made.Mechanical gauges used to measure test pres-sures shall have a range such that the highestend of the scale does not exceed five (5) timesthe test pressure. [NFPA 54:8.1.4.1]
1214.3.2 The test pressure to be used shall benot less than one and one-half (1-1/2) times theproposed maximum working pressure, but notless than three (3) psi (20 kPa), irrespective ofdesign pressure. [NFPA 54:8.1.4.2]
1214.3.3 Test duration shall be not less thanone-half (1/2) hour for each five-hundred (500)cubic feet (14 m3) of pipe volume or fractionthereof. When testing a system having a volumeless than ten (10) cubic feet (0.28 m3) or a systemin a single-family dwelling, the test durationshall be not less than ten (10) minutes. The dura-tion of the test shall not be required to exceedtwenty-four (24) hours. [NFPA 54:8.1.4.3]
1214.4 Detection of Leaks and Defects.
1214.4.1 The piping system shall withstand thetest pressure specified without showing anyevidence of leakage or other defects. Any reduc-tion of test pressures as indicated by pressuregauges shall be deemed to indicate the presenceof a leak unless such reduction can be readilyattributed to some other cause. [NFPA 54:8.1.5.1]
1214.4.2 The leakage shall be located by meansof an approved gas detector, a noncorrosive leakdetection fluid, or other approved leak detectionmethods. Matches, candles, open flames, orother methods that provide a source of ignitionshall not be used. [NFPA 54:8.1.5.2]
1214.4.3 Where leakage or other defects arelocated, the affected portion of the piping systemshall be repaired or replaced and retested. [SeeSection 1214.1.3.] [NFPA 54:8.1.5.3]
1214.5 Piping Systems Leak Check.
1214.5.1 Test Gases. Leak checks using fuelgas shall be permitted in piping systems thathave been pressure-tested in accordance withSection 1214.0. [NFPA 54:8.2.1]
1214.5.2 Turning Gas On. During the processof turning gas on into a system of new gaspiping, the entire system shall be inspected todetermine that there are no open fittings or endsand that valves at unused outlets are closed andplugged or capped. [NFPA 54-09:8.2.2]
1214.5.3 Leak Check. Immediately after the gasis turned on into a new system or into a systemthat has been initially restored after an interrup-tion of service, the piping system shall bechecked for leakage. Where leakage is indicated,the gas supply shall be shut off until the neces-sary repairs have been made. [NFPA 54:8.2.3]
1214.5.4 Placing Appliance in Operation. Gasutilization appliance shall not be placed in oper-ation until after the piping system has beentested in accordance with Section 1214.5.3 andpurged in accordance with Section 1214.6.[NFPA 54:8.2.4]
1214.6 Purging Requirements. The purging ofpiping shall be in accordance with Section 1214.6.1through Section 1214.6.3. [NFPA 54-09:8.3]
1214.6.1 Piping Systems Required to bePurged Outdoors. The purging of pipingsystems shall be in accordance with Section1214.6.1.1 through Section 1214.6.1.4 where thepiping system meets either of the following:
(1) The design operating gas pressure isexceeding 2 psig (14 kPa).
(2) The piping being purged contains one ormore sections of pipe or tubing greater than2 inches (51 mm) and exceeding the lengthsin Table 12-5. [NFPA 54-09:8.3.1]
TABLE 12-5Size and Length of Piping
[NFPA 54-09: Table 8.3.1.1]
Nominal PipeSize (inches)
Length of Piping(feet)
2-1/2 > 50
3 > 30
4 > 15
6 > 10
8 or larger Any length
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
184
1214.2 – Table 12-5 IDAHO STATE PLUMBING CODE
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
READ ONLY
READ ONLY
1214.6.1.1 Removal from Service. Whereexisting gas piping is opened, the sectionthat is opened shall be isolated from the gassupply and the line pressure vented inaccordance with Section 1214.6.1.3. Wheregas piping meeting the criteria of Table 12-5is removed from service, the residual fuelgas in the piping shall be displaced with aninert gas. [NFPA 54-09:8.3.1.1]
1214.6.1.2 Placing in Operation. Wheregas piping containing air and meeting thecriteria of Table 12-5 is placed in operation,the air in the piping shall first be displacedwith an inert gas. The inert gas shall then bedisplaced with fuel gas in accordance withSection 1214.6.1.3. [NFPA 54-09:8.3.1.2]
1214.6.1.3 Outdoor Discharge of Purged
Gases. The open end of a piping systembeing pressure vented or purged shalldischarge directly to an outdoor location.Purging operations shall comply with all ofthe following requirements:
(1) The point of discharge shall becontrolled with a shutoff valve.
(2) The point of discharge shall be locatednot less than 10 feet (3048 mm) fromsources of ignition, not less than 10 feet(3048 mm) from building openings, andnot less than 25 feet (7620 mm) frommechanical air intake openings.
(3) During discharge, the open point ofdischarge shall be attended and moni-tored with a combustible gas indicatorthat is in accordance with Section1214.6.1.4.
(4) Purging operations introducing fuel gasshall be stopped where 90 percent fuelgas by volume is detected within the pipe.
(5) Persons not involved in the purgingoperations shall be evacuated fromareas within 10 feet (3048 mm) of thepoint of discharge. [NFPA 54-09:8.3.1.3]
1214.6.1.4 Combustible Gas Indicator.The combustible gas indicator used duringpurging operations shall be listed and shall becalibrated in accordance with the manufac-turer’s instructions and recommendedschedule. The combustible gas indicator usedfor pipe discharge monitoring shall numeri-cally display a volume scale from 0 percent to100 percent with a resolution of not more than1 percent increments. [NFPA 54-09:8.3.1.4]
1214.6.2 Piping Systems Allowed to BePurged Indoors or Outdoors. The purging ofpiping systems shall be in accordance with the
provisions of Section 1214.6.2.1 where the pipingsystem meets both of the following: (1) The design operating pressure is 2 psig (14
kPa) or less.(2) The piping system being purged is
constructed entirely from pipe or tubing of 2inch (50 mm) nominal size or smaller, orlarger pipe or tubing with lengths shorterthan specified in Table 12-5. [NFPA 54-09:8.3.2]1214.6.2.1 Purging Procedure. The pipingsystem shall be purged in accordance withone or more of the following: (1) The piping shall be purged with fuel gas
and shall discharge to the outdoors.(2) The piping shall be purged with fuel gas
and shall discharge to the indoors oroutdoors through an appliance burnernot located in a combustion chamber.Such burner shall be provided with acontinuous source of ignition.
(3) The piping shall be purged with fuel gasand shall discharge to the indoors oroutdoors through a burner that has acontinuous source of ignition and that isdesigned for such purpose.
(4) The piping shall be purged with fuel gasthat is discharged to the indoors oroutdoors, and the point of dischargeshall be monitored with a listedcombustible gas detector in accordancewith Section 1214.6.2.2. Purging shall bestopped where fuel gas is detected.
(5) The piping shall be purged by the gassupplier in accordance with writtenprocedures. [NFPA 54-09:8.3.2.1]
1214.6.2.2 Combustible Gas Detector. Thecombustible gas detector used duringpurging operations shall be listed and shallbe calibrated or tested in accordance withthe manufacturer’s instructions and recom-mended schedule. The combustible gasdetector used for pipe discharge monitoringshall indicate the presence of fuel gas.[NFPA 54-09:8.3.2.2]1214.6.3 Purging Appliances and Equip-ment. After the piping system has beenplaced in operation, appliances and equip-ment shall be purged before being placedinto operation. [NFPA 54-09:8.3.3]
1215.0 Interconnections Between Gas PipingSystems.
1215.1 Interconnections Supplying SeparateUsers. Where two (2) or more meters, or two (2) ormore service regulators where meters are not
185
FUEL PIPING 1214.6 – 1215.1
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
TIA
READ ONLY
READ ONLY
provided, are located on the same premises andsupply separate users, the gas-piping systems shallnot be interconnected on the outlet side of the metersor service regulators. [NFPA 54:5.3.1]
1215.2 Interconnections for Standby Fuels.
Where supplementary gas for standby use isconnected downstream from a meter or a serviceregulator where a meter is not provided, a device toprevent backflow shall be installed. [NFPA 54:5.3.2.1]A three-way valve installed to admit the standbysupply and at the same time shut off the regularsupply shall be permitted to be used for thispurpose. [NFPA 54:5.3.2.2]
1216.0 Required Gas Supply.
1216.1 The following regulations, as set forth in thissection and in Section 1217.0, Required Gas PipingSize, shall be the standard for the installation of gaspiping. Natural gas regulations and tables are basedon the use of gas having a specific gravity of sixty-hundredths (0.60), supplied at six (6) to eight (8)inches (152–203 mm) water column pressure at theoutlet of the meter or regulator. For undiluted lique-fied petroleum gas, gas piping shall be permitted tobe sized at eleven (11) inches (279 mm) water columnpressure at the outlet of the meter or regulator andspecific gravity of one and fifty-hundredths (1.50).
Note: Where gas of a different specific gravity isto be delivered, the serving gas supplier shouldbe contacted for specific gravity conversionfactors to use in sizing piping systems from thepipe sizing tables in this chapter.
1216.2 The hourly volume of gas required at eachpiping outlet shall be taken as not less than themaximum hourly rating as specified by the manufac-turer of the appliance or appliances to be connectedto each such outlet.
1216.3 Where the gas appliances to be installed havenot been definitely specified, Table 12-1 shall bepermitted to be used as a reference to estimaterequirements of typical appliances.
To obtain the cubic feet per hour (L/sec.) of gasrequired, divide input of appliances by the averageBtu (Watt-hour) heating value per cubic foot (L) of thegas. The average Btu (Watt-hour) per cubic foot (L) ofthe gas in the area of the installation shall be permittedto be obtained from the serving gas supplier.
1216.4 The size of the supply piping outlet for anygas appliance shall not be less than one-half (1/2)inch (15 mm).
The minimum size of any piping outlet for amobile home shall be three-quarters (3/4) of an inch(20 mm).
1217.0 Required Gas Piping Size.
1217.1 Pipe Sizing Methods. Where the pipe size isto be determined using any of the methods inSections 1217.1.1 through 1217.1.3, the diameter ofeach pipe segment shall be obtained from the pipe-sizing tables in Section 1217.2 or from the sizingequations in Section 1217.3. [NFPA 54:6.1]
1217.1.1 Longest Length Method. The pipesize of each section of gas piping shall be deter-mined using the longest length of piping fromthe point of delivery to the most remote outletand the load of the section (see calculationexample in Figure 12-2). [NFPA 54:6.1.1]
1217.1.2 Branch Length Method. Pipe shall besized as follows [NFPA 54:6.1.2]:
(A) Pipe size of each section of the longestpipe run from the point of delivery tothe most remote outlet shall be deter-mined using the longest run of pipingand the load of the section. [NFPA54:6.1.2(1)]
(B) The pipe size of each section of branchpiping not previously sized shall bedetermined using the length of pipingfrom the point of delivery to the mostremote outlet in each branch and theload of the section. [NFPA 54:6.1.2(2)]
1217.1.3 Hybrid Pressure. The pipe size foreach section of higher-pressure gas piping shallbe determined using the longest length of pipingfrom the point of delivery to the most remoteline pressure regulator. The pipe size from theline pressure regulator to each outlet shall bedetermined using the length of piping from theregulator to the most remote outlet served by theregulator. [NFPA 54:6.1.3]
1217.2 Tables for Sizing Gas-Piping Systems.
Tables 12-8 through 12-41 shall be used to size gaspiping in conjunction with one (1) of the methodsdescribed in Sections 1217.1.1 through 1217.1.3.[NFPA 54:6.2]
1217.3 Sizing Equations. The inside diameter ofsmooth-wall pipe or tubing shall be determined bythe sizing equations 12-1 or 12-2, using the equiva-lent pipe length determined by Sections 1217.1.1through 1217.1.3. [NFPA 54:6.4]
Equation 12-1 Low-Pressure Gas Formula (Lessthan 1.5 psi [10.3 kPa]): [NFPA 54:6.4.1]
D=
( )∆H
Cr x L
Q0.381
0.20619.17
186
1215.1 – 1217.3 IDAHO STATE PLUMBING CODE
READ ONLY
READ ONLY
where:
D = inside diameter of pipe, inches
Q = input rate appliance(s), cubic feet per hour at 60˚F (16ºC) and 30-inch (759 mm) mercury column
L = equivalent length of pipe, feet
∆H =pressure drop, inches water column (27.7 in.H2O = 1 psi)
Cr = in accordance with Table 12-4
Equation 12-2 High-Pressure Gas Formula (1.5 psi[10.3 kPa] and above): [NFPA 54:6.4.2]
where:
D = inside diameter of pipe, inches
Q = input rate appliance(s), cubic feet per hour at60ºF (16ºC) and 30-inch (759 mm) mercurycolumn
P1 = upstream pressure, psia (P1 + 14.7)
P2 = downstream pressure, psia (P2 + 14.7)
L = equivalent length of pipe, feet.
Cr = in accordance with Table 12-4
Y = in accordance with Table 12-4
1217.4 To determine the size of each section of pipein any system within the range of the Table, proceedas follows:
(A) Measure the length of the pipe from the gas meter location to the most remote outlet on thesystem.
(B) Select the length in feet column and row showingthe distance, or the next longer distance if thetable does not give the exact length.
(C) Starting at the most remote outlet, find in therow just selected the gas demand for that outlet.
If the exact figure of demand is not shown,choose the next larger figure in the row.
(D) At the top of this column will be found thecorrect size of pipe.
(E) Using this same row, proceed in a similarmanner for each section of pipe serving thisoutlet. For each section of pipe, determine thetotal gas demand supplied by that section.Where gas piping sections serve both heatingand cooling appliances and the installationprevents both units from operating simultane-ously, only the larger of the two (2) demandloads needs be used in sizing these sections.
(F) Size each section of branch piping not previ-ously sized by measuring the distance from thegas meter location to the most remote outlet inthat branch and follow the procedures of steps B,C, D, and E above.
Note: Size branch piping in the order of theirdistance from the meter location, beginning with themost distant outlet not previously sized.
1217.5 For conditions other than those covered bySection 1217.1, such as longer runs or greater gasdemands, the size of each gas piping system shall bedetermined by standard engineering methodsacceptable to the Authority Having Jurisdiction, andeach such system shall be so designed that the totalpressure drop between the meter or other point ofsupply and any outlet when full demand is beingsupplied to all outlets, shall comply with therequirements of Section 1209.4.
1217.6 Where the gas pressure exceeds fourteen (14)inches (356 mm) or less than six (6) inches (152 mm)of water column, or when diversity demand factorsare used, the design, pipe, sizing, materials, location,and use of such systems first shall be approved bythe Authority Having Jurisdiction. Piping systemsdesigned for pressures exceeding the serving gassupplier's standard delivery pressure shall haveprior verification from the gas supplier of the avail-ability of the design pressure.
D= Q0.381
0.20618.93[ ](P1
2 – P22) • Y
Cr x L
TABLE 12-4
Cr and Y for Natural Gas and Undiluted Propane
at Standard Conditions [NFPA 54: Table 6.4.2]
Formula Factors Gas Cr Y
Natural Gas 0.6094 0.9992
Undiluted Propane 1.2462 0.9910
For SI units, 1 ft.3 = 0.028 m3; 1 ft. = 0.305 m; 1 in. water column
= 0.249 kPa; 1 psi = 6.894 kPa; 1,000 Btu/h = 0.293 kW.
187
FUEL PIPING 1217.4 – 1217.6
READ ONLY
READ ONLY
Solution:(1) Maximum gas demand of outlet A —
32 cubic feet per hour (0.21 L/sec.) (from Table 12-1).Maximum gas demand of outlet B —
3 cubic feet per hour (0.02 L/sec.) (from Table 12-1).Maximum gas demand of outlet C —
59 cubic feet per hour (0.46 L/sec.) (from Table 12-1).Maximum gas demand of outlet D —
136 cubic feet per hour (1.1 L/sec.) (150,000 Btu/hour [43,950 W]) divided by 1,100 Btu per cubic foot (11.4 Watt-hour/L)
(2) The length of pipe from the gas meter to the most remote outlet (outlet A) is 60 feet (18,288 mm).
(3) Using the length in feet column row marked 60 feet (18,288 mm) in Table 12-8:
Outlet A, supplying 32 cubic feet per hour (0.21 L/sec.), requires one-half (1/2) inch (15 mm) pipe. Section1, supplying outlets A and B, or 35 cubic feet per hour (0.24 L/sec.) requires one-half (1/2) inch (15 mm)pipe.
Section 2, supplying outlets A, B, and C, or 94 cubic feet per hour (0.7 L/sec.) requires three-quarter (3/4)inch (20 mm) pipe.
Section 3, supplying outlets A, B, C, and D, or 230 cubic feet per hour (1.8 L/sec.), requires one (1) inch (25mm) pipe.
(4) Using the column marked 60 feet (18,288 mm) in Table 12-8 (no column for actual length of 55 feet [16,764mm]:
Outlet B supplying 3 cubic feet per hour (0.02 L/sec.), requires one-half (1/2) inch (15 mm) pipe.
Outlet C, supplying 59 cubic feet per hour (0.46 L/sec.), requires one-half (1/2) inch (15 mm) pipe.
(5) Using the column marked 60 feet (18,288 mm) in Table 12-8:
Outlet D, supplying 136 cubic feet per hour (1.1 L/sec.), requires (3/4) inch (20 mm) pipe.
Figure 12-2 Example Illustrating Use of Tables 12-1 and 12-8
Problem: Determine the required pipe size of each section and outlet of the piping system shown in Figure 12-2.Gas to be used has a specific gravity of sixty-hundredths (0.60) and eleven-hundred (1,100) Btu per cubic foot(11.4 Watt-hour/L), delivered at eight (8) inch (203 mm) water column pressure.
188
Figure 12-2 Example IDAHO STATE PLUMBING CODE
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.5 in w.c.
Specific Gravity: 0.60
Pipe Size (in.)
Nominal: 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4 5 6 8 10 12
Actual ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938
Length (ft) Capacity in Cubic Feet of Gas per Hour
1020304050
172118958172
360247199170151
678466374320284
1,390957768657583
2,0901,4301,150
985873
4,0202,7602,2201,9001,680
6,4004,4003,5303,0202,680
11,3007,7806,2505,3504,740
23,10015,90012,70010,9009,660
41,80028,70023,00019,70017,500
67,60046,50037,30031,90028,300
139,00095,50076,70065,60058,200
252,000173,000139,000119,000106,000
399,000275,000220,000189,000167,000
60708090
100
6560565250
137126117110104
257237220207195
528486452424400
791728677635600
1,5201,4001,3001,2201,160
2,4302,2302,0801,9501,840
4,2903,9503,6703,4503,260
8,7608,0507,4907,0306,640
15,80014,60013,60012,70012,000
25,60023,60022,00020,60019,500
52,70048,50045,10042,30040,000
95,70088,10081,90076,90072,600
152,000139,000130,000122,000115,000
125150175200250
4440373430
9283777163
173157144134119
355322296275244
532482443412366
1,020928854794704
1,6301,4801,3601,2701,120
2,8902,6102,4102,2401,980
5,8905,3304,9104,5604,050
10,6009,6508,8808,2607,320
17,20015,60014,40013,40011,900
35,40032,10029,50027,50024,300
64,30058,30053,60049,90044,200
102,00092,30084,90079,00070,000
300350400450500
2725232221
5753494643
10899928682
221203189177168
331305283266251
638587546512484
1,020935870816771
1,8001,6501,5401,4401,360
3,6703,3703,1402,9402,780
6,6306,1005,6805,3305,030
10,7009,8809,1908,6208,150
22,10020,30018,90017,70016,700
40,10036,90034,30032,20030,400
63,40058,40054,30050,90048,100
550600650700750
2019181717
4139383635
7874716866
159152145140135
239228218209202
459438420403389
732699669643619
1,2901,2401,1801,1401,090
2,6402,5202,4102,3202,230
4,7804,5604,3604,1904,040
7,7407,3807,0706,7906,540
15,90015,20014,50014,00013,400
28,90027,50026,40025,30024,400
45,70043,60041,80040,10038,600
800850900950
1,000
1616151514
3433323130
6361595856
130126122118115
195189183178173
375363352342333
598579561545530
1,0601,020
992963937
2,1602,0902,0201,9601,910
3,9003,7803,6603,5503,460
6,3206,1105,9305,7605,600
13,00012,60012,20011,80011,500
23,60022,80022,10021,50020,900
37,30036,10035,00034,00033,100
1,1001,2001,3001,4001,500
1413121211
2827262524
5351494745
1091041009693
164156150144139
316301289277267
503480460442426
890849813781752
1,8101,7301,6601,5901,530
3,2803,1303,0002,8802,780
5,3205,0704,8604,6704,500
10,90010,4009,9809,5909,240
19,80018,90018,10017,40016,800
31,40030,00028,70027,60026,600
1,6001,7001,8001,9002,000
11111010
NA
2322222120
4442414039
8986848179
134130126122119
258250242235229
411398386375364
727703682662644
1,4801,4301,3901,3501,310
2,6802,5902,5202,4402,380
4,3404,2004,0703,9603,850
8,9208,6308,3708,1307,910
16,20015,70015,20014,80014,400
25,60024,80024,10023,40022,700
Table 12-8Schedule 40 Metallic Pipe [NFPA 54: Table 6.2(b)]
NA means a flow of less than 10 cfh.Note: All table entries are rounded to 3 significant digits.
Table 12-8FUEL PIPING
189
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 0.60
Pipe Size (in.)
Nominal: 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
Actual ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
1,5101,070
869753673
3,0402,1501,7601,5201,360
5,5603,9303,2102,7802,490
11,4008,0706,5905,7105,110
17,10012,1009,8808,5507,650
32,90023,30019,00016,50014,700
52,50037,10030,30026,30023,500
92,80065,60053,60046,40041,500
189,000134,000109,00094,70084,700
60708090
100
615569532502462
1,2401,1501,0801,010
934
2,2702,1001,9701,8501,710
4,6604,3204,0403,8103,510
6,9806,4706,0505,7005,260
13,50012,50011,70011,00010,100
21,40019,90018,60017,50016,100
37,90035,10032,80030,90028,500
77,30071,60067,00063,10058,200
125150175200250
414372344318279
836751695642583
1,5301,3701,2701,1701,040
3,1402,8202,6012,4102,140
4,7004,2203,9103,6103,210
9,0608,1307,5306,9606,180
14,40013,00012,00011,1009,850
25,50022,90021,20019,60017,400
52,10046,70043,30040,00035,500
300350400450500
253232216203192
528486452424401
945869809759717
1,9401,7901,6601,5601,470
2,9102,6702,4902,3302,210
5,6005,1504,7904,5004,250
8,9208,2107,6407,1706,770
15,80014,50013,50012,70012,000
32,20029,60027,50025,80024,400
550600650700750
182174166160154
381363348334322
681650622598576
1,4001,3301,2801,2301,180
2,0902,0001,9101,8401,770
4,0303,8503,6803,5403,410
6,4306,1305,8705,6405,440
11,40010,80010,4009,9709,610
23,20022,10021,20020,30019,600
800850900950
1,000
149144139135132
311301292283275
556538522507493
1,1401,1001,0701,0401,010
1,7101,6501,6001,5601,520
3,2903,1903,0903,0002,920
5,2505,0804,9304,7804,650
9,2808,9808,7108,4608,220
18,90018,30017,80017,20016,800
1,1001,2001,3001,4001,500
125119114110106
262250239230221
468446427411396
960917878843812
1,4401,3701,3201,2601,220
2,7702,6402,5302,4302,340
4,4204,2204,0403,8803,740
7,8107,4507,1406,8606,600
15,90015,20014,60014,00013,500
1,6001,7001,8001,9002,000
10299969391
214207200195189
382370358348339
784759736715695
1,1801,1401,1001,0701,040
2,2602,1902,1202,0602,010
3,6103,4903,3903,2903,200
6,3806,1705,9805,8105,650
13,00012,60012,20011,90011,500
Note: All table entries are rounded to 3 significant digits.
Table 12-9Schedule 40 Metallic Pipe [NFPA 54: Table 6.2(c)]
Table 12-9 IDAHO STATE PLUMBING CODE
190
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 3.0 psi
Pressure Drop: 2.0 psi
Specific Gravity: 0.60
Pipe Size (in.)
Nominal: 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
Actual ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
2,3501,6201,3001,110
985
4,9203,3802,7202,3202,060
9,2706,3705,1104,3803,880
19,00013,10010,5008,9907,970
28,50019,60015,70013,50011,900
54,90037,70030,30025,90023,000
87,50060,10048,30041,30036,600
155,000106,00085,40073,10064,800
316,000217,000174,000149,000132,000
60708090
100
892821764717677
1,8701,7201,6001,5001,420
3,5203,2303,0102,8202,670
7,2206,6406,1805,8005,470
10,8009,9509,2608,6808,200
20,80019,20017,80016,70015,800
33,20030,50028,40026,70025,200
58,70054,00050,20047,10044,500
120,000110,000102,00096,10090,800
125150175200250
600544500465412
1,2501,1401,050
973862
2,3602,1401,9701,8301,620
4,8504,4004,0403,7603,330
7,2706,5906,0605,6405,000
14,00012,70011,70010,9009,620
22,30020,20018,60017,30015,300
39,50035,70032,90030,60027,100
80,50072,90067,10062,40055,300
300350400450500
374344320300283
781719669627593
1,4701,3501,2601,1801,120
3,0202,7802,5902,4302,290
4,5304,1703,8703,6403,430
8,7208,0207,4607,0006,610
13,90012,80011,90011,20010,500
24,60022,60021,00019,70018,600
50,10046,10042,90040,20038,000
550600650700750
269257246236228
563537514494476
1,0601,010
969931897
2,1802,0801,9901,9101,840
3,2603,1102,9802,8602,760
6,2805,9905,7405,5105,310
10,0009,5509,1508,7908,470
17,70016,90016,20015,50015,000
36,10034,40033,00031,70030,500
800850900950
1,000
220213206200195
460445431419407
866838812789767
1,7801,7201,6701,6201,580
2,6602,5802,5002,4302,360
5,1304,9604,8104,6704,550
8,1807,9107,6707,4507,240
14,50014,00013,60013,20012,800
29,50028,50027,70026,90026,100
1,1001,2001,3001,4001,500
185177169162156
387369353340327
729695666640616
1,5001,4301,3701,3101,270
2,2402,1402,0501,9701,900
4,3204,1203,9403,7903,650
6,8906,5706,2906,0405,820
12,20011,60011,10010,70010,300
24,80023,70022,70021,80021,000
1,6001,7001,8001,9002,000
151146142138134
316306296288280
595576558542527
1,2201,1801,1501,1101,080
1,8301,7701,7201,6701,620
3,5303,4103,3103,2103,120
5,6205,4405,2705,1204,980
10,0009,6109,3209,0508,800
20,30019,60019,00018,40018,000
Table 12-10Schedule 40 Metallic Pipe [NFPA 54: Table 6.2(d)]
Note: All table entries are rounded to 3 significant digits
Table 12-10FUEL PIPING
191
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 5.0 psi
Pressure Drop: 3.5 psi
Specific Gravity: 0.60
Pipe Size (in.)
Nominal: 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
Actual ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
3,1902,2501,8401,5901,430
6,4304,5503,7203,2202,880
11,8008,3206,7905,8805,260
24,20017,10014,00012,10010,800
36,20025,60020,90018,10016,200
69,70049,30040,30034,90031,200
111,00078,60064,20055,60049,700
196,000139,000113,00098,20087,900
401,000283,000231,000200,000179,000
60708090
100
1,3001,2001,1501,060
979
2,6302,4302,3302,1501,980
4,8004,4504,2603,9203,620
9,8609,1308,5408,0507,430
14,80013,70012,80012,10011,100
28,50026,40024,70023,20021,400
45,40042,00039,30037,00034,200
80,20074,30069,50065,50060,400
164,000151,000142,000134,000123,000
125150175200250
876786728673558
1,7701,5901,4701,3601,170
3,2402,9102,6902,4902,200
6,6405,9605,5205,1004,510
9,9508,9408,2707,6506,760
19,20017,20015,90014,70013,000
30,60027,40025,40023,50020,800
54,00048,50044,90041,50036,700
110,00098,90091,60084,70074,900
300350400450500
506465433406384
1,060973905849802
1,9901,8301,7101,6001,510
4,0903,7603,5003,2903,100
6,1305,6405,2504,9204,650
11,80010,90010,1009,4808,950
18,80017,30016,10015,10014,300
33,30030,60028,50026,70025,200
67,80062,40058,10054,50051,500
550600650700750
364348333320308
762727696669644
1,4401,3701,3101,2601,210
2,9502,8102,6902,5902,490
4,4204,2104,0303,8803,730
8,5008,1107,7707,4607,190
13,60012,90012,40011,90011,500
24,00022,90021,90021,00020,300
48,90046,60044,60042,90041,300
800850900950
1,000
298288279271264
622602584567551
1,1701,1301,1001,0701,040
2,4102,3302,2602,1902,130
3,6103,4903,3803,2903,200
6,9406,7206,5206,3306,150
11,10010,70010,40010,1009,810
19,60018,90018,40017,80017,300
39,90038,60037,40036,40035,400
1,1001,2001,3001,4001,500
250239229220212
524500478460443
987941901866834
2,0301,9301,8501,7801,710
3,0302,9002,7702,6602,570
5,8405,5805,3405,1304,940
9,3208,8908,5108,1807,880
16,50015,70015,00014,50013,900
33,60032,00030,70029,50028,400
1,6001,7001,8001,9002,000
205198192186181
428414401390379
806780756734714
1,6501,6001,5501,5101,470
2,4802,4002,3302,2602,200
4,7704,6204,4804,3504,230
7,6107,3607,1406,9306,740
13,40013,00012,60012,30011,900
27,40026,50025,70025,00024,300
Table 12-11Schedule 40 Metallic Pipe [NFPA 54: Table 6.2(e)]
Note: All table entries are rounded to 3 significant digits.
Table 12-11 IDAHO STATE PLUMBING CODE
192
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.3 in. w.c.
Specific Gravity: 0.60
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
20141110
NA
4229232017
8558474035
148102827062
2101441169988
448308247211187
806554445381337
1,270873701600532
2,6501,8201,4601,2501,110
60708090
100
NANANANANA
1614131312
3229272624
5652484543
7973686460
170156145136129
306281262245232
482443413387366
1,000924859806761
125150175200250
NANANANANA
1110
NANANA
2220181715
3834312926
5348454137
114103958978
206186171159141
324294270251223
675612563523464
300350400450500
NANANANANA
NANANANANA
1312111110
2322201918
3331282725
7165615754
12811811010397
202186173162153
420387360338319
550600650700750
NANANANANA
NANANANANA
NANANANANA
1716151514
2423222120
5149474543
9288848178
145139133128123
303289277266256
800850900950
1,000
NANANANANA
NANANANANA
NANANANANA
1413131312
2019181817
4240393837
7573716967
119115111108105
247239232225219
1,1001,2001,3001,4001,500
NANANANANA
NANANANANA
NANANANANA
12111110
NA
1616151414
3534323130
6360585654
10095918884
208199190183176
1,6001,7001,8001,9002,000
NANANANANA
NANANANANA
NANANANANA
NANANANANA
1313131212
2928272625
5250494746
8279777472
170164159155151
Table 12-12 Semi-Rigid Copper Tubing [NFPA 54: Table 6.2(f)]
NA means a flow of less than 10 cfh.Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Table 12-12FUEL PIPING
193
READ ONLY
READ ONLY
Table 12-13Semi-Rigid Copper Tubing [NFPA 54: Table 6.2(g)]
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 0.60
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
2718151311
5538302623
11177615347
1951341079282
276190152131116
590406326279247
1,060730586502445
1,6801,150
925791701
3,4902,4001,9301,6501,460
60708090
100
10NANANANA
2119181716
4239363432
7468635956
10596908479
224206192180170
403371345324306
635585544510482
1,3201,2201,1301,0601,000
125150175200250
NANANANANA
14131211
NA
2826242220
5045413934
7064595548
151136125117103
271245226210186
427387356331294
890806742690612
300350400450500
NANANANANA
NANANANANA
1816151413
3128262523
4440383533
9486807571
169155144135128
266245228214202
554510474445420
550600650700750
NANANANANA
NANANANANA
1312121111
2221202019
3230292827
6864625957
122116111107103
192183175168162
399381365350338
800850900950
1,000
NANANANANA
NANANANANA
1010
NANANA
1818171716
2625242423
5553525049
9996939088
156151147143139
326315306297289
1,1001,2001,3001,4001,500
NANANANANA
NANANANANA
NANANANANA
1515141313
2221201918
4644424139
8480767371
132126120116111
274262251241232
1,6001,7001,8001,9002,000
NANANANANA
NANANANANA
NANANANANA
1312121111
1817171616
3837363534
6866646260
1081041019895
224217210204199
NA means a flow of less than 10 cfh.Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Table 12-13 IDAHO STATE PLUMBING CODE
194
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 1.0 in. w.c.
Specific Gravity: 0.60
INTENDED USE: Tube Sizing Between House Line Regulator and the Appliance.
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
3927211816
8055443833
162111897768
283195156134119
402276222190168
859590474406359
1,5501,060
853730647
2,4401,6801,3501,1501,020
5,0803,4902,8002,4002,130
60708090
100
1513131211
3028262423
6157534947
10799928682
152140131122116
326300279262247
586539502471445
925851791742701
1,9301,7701,6501,5501,460
125150175200250
NANANANANA
2018171614
4137343228
7265605650
10393857970
219198183170151
394357329306271
622563518482427
1,2901,1701,0801,000
890
300350400450500
NANANANANA
13121110
NA
2624222120
4541393634
6459555148
136125117110103
245226210197186
387356331311294
806742690647612
550600650700750
NANANANANA
NANANANANA
1918171616
3231302827
4644424039
9894908683
177169162155150
279266255245236
581554531510491
800850900950
1,000
NANANANANA
NANANANANA
1515141413
2626252423
3836353433
8078757371
144140135132128
228220214207202
474459445432420
1,1001,2001,3001,4001,500
NANANANANA
NANANANANA
1312121111
2221202019
3230292827
6864625957
122116111107103
192183175168162
399381365350338
1,6001,7001,8001,9002,000
NANANANANA
NANANANANA
1010
NANANA
1818171716
2625242423
5553525049
9996939088
156151147143139
326315306297289
Table 12-14Semi-Rigid Copper Tubing [NFPA 54-09: Table 6.2(h)]
NA means a flow of less than 10 cfh.Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Table 12-14FUEL PIPING
195
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 17.0 in. w.c.
Specific Gravity: 0.60
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
1901301059079
391269216185164
796547439376333
1,390956768657582
1,9701,3601,090
932826
4,2202,9002,3301,9901,770
7,5905,2204,1903,5903,180
12,0008,2306,6105,6505,010
24,90017,10013,80011,80010,400
60708090
100
7266625855
148137127119113
302278258243229
528486452424400
749689641601568
1,6001,4701,3701,2801,210
2,8802,6502,4602,3102,180
4,5404,1803,8903,6503,440
9,4608,7008,0907,5907,170
125150175200250
4844403833
10090837769
203184169157140
355321296275244
503456420390346
1,080974896834739
1,9401,7501,6101,5001,330
3,0502,7702,5402,3702,100
6,3605,7605,3004,9304,370
300350400450500
3028262423
6257535047
12611610810296
221203189177168
313288268252238
670616573538508
1,2101,1101,030
968914
1,9001,7501,6301,5301,440
3,9603,6403,3903,1803,000
550600650700750
2221201918
4543413938
9187838077
159152145140135
226215206198191
482460441423408
868829793762734
1,3701,3101,2501,2001,160
2,8502,7202,6102,5002,410
800850900950
1,000
1817171616
3735343332
7472706866
130126122118115
184178173168163
394381370359349
709686665646628
1,1201,0801,0501,020
991
2,3302,2502,1802,1202,060
1,1001,2001,3001,4001,500
1514141313
3129282726
6360575553
1091041009693
155148142136131
332316303291280
597569545524505
941898860826796
1,9601,8701,7901,7201,660
1,6001,7001,8001,9002,000
1212111111
2524242322
5149484745
8986848179
127123119115112
271262254247240
487472457444432
768744721700681
1,6001,5501,5001,4601,420
Table 12-15 Semi-Rigid Copper Tubing [NFPA 54: Table 6.2(i)]
Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Table 12-15 IDAHO STATE PLUMBING CODE
196
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 0.60
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
245169135116103
506348279239212
1,030708568486431
1,8001,240
993850754
2,5501,7601,4101,2101,070
5,4503,7503,0102,5802,280
9,8206,7505,4204,6404,110
15,50010,6008,5507,3106,480
32,20022,20017,80015,20013,500
60708090
100
9386807571
192177164154146
391359334314296
683628584548518
969891829778735
2,0701,9001,7701,6601,570
3,7303,4303,1902,9902,830
5,8705,4005,0304,7204,450
12,20011,30010,5009,8209,280
125150175200250
6357524943
12911710810089
263238219204181
459416383356315
651590543505448
1,3901,2601,1601,080
956
2,5002,2702,0901,9401,720
3,9503,5803,2903,0602,710
8,2207,4506,8506,3805,650
300350400450500
3936333130
8074696561
164150140131124
286263245230217
406373347326308
866797741696657
1,5601,4301,3301,2501,180
2,4602,2602,1001,9701,870
5,1204,7104,3804,1103,880
550600650700750
2827262524
5855535149
118112108103100
206196188181174
292279267256247
624595570548528
1,1201,0701,030
986950
1,7701,6901,6201,5501,500
3,6903,5203,3703,2403,120
800850900950
1,000
2322222120
4746444342
9693908885
168163158153149
239231224217211
510493478464452
917888861836813
1,4501,4001,3601,3201,280
3,0102,9202,8302,7402,670
1,1001,2001,3001,4001,500
1918181716
4038363534
8177747168
142135129124120
201192183176170
429409392376363
772737705678653
1,2201,1601,1101,0701,030
2,5402,4202,3202,2302,140
1,6001,7001,8001,9002,000
1615151414
3331303029
6664626059
116112108105102
164159154149145
350339329319310
630610592575559
994962933906881
2,0702,0001,9401,8901,830
Table 12-16Semi-Rigid Copper Tubing [NFPA 54: Table 6.2(j)]
Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Table 12-16FUEL PIPING
197
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 2.0 psi
Pressure Drop: 1.5 psi
Specific Gravity: 0.60
INTENDED USE: Pipe Sizing Between Point of Delivery and the House Line Regulator. Total Load Supplied by a
Single House Line Regulator Not Exceeding 150 Cubic Feet per Hour. †
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
303208167143127
625430345295262
1,270874702601532
2,2201,5301,2301,050
931
3,1502,1701,7401,4901,320
6,7404,6303,7203,1802,820
12,1008,3306,6905,7305,080
19,10013,10010,6009,0308,000
39,80027,40022,00018,80016,700
60708090
100
115106989287
237218203190180
482444413387366
843776722677640
1,2001,1001,020
961907
2,5602,3502,1902,0501,940
4,6004,2303,9403,6903,490
7,2506,6706,2105,8205,500
15,10013,90012,90012,10011,500
125150175200250
7770646053
159144133124110
324294270252223
567514472440390
804729670624553
1,7201,5601,4301,3301,180
3,0902,8002,5802,4002,130
4,8804,4204,0603,7803,350
10,2009,2008,4607,8706,980
300350400450500
4844413936
9991858075
202186173162153
353325302283268
501461429402380
1,070984916859811
1,9301,7701,6501,5501,460
3,0402,7902,6002,4402,300
6,3205,8205,4105,0804,800
550600650700750
3533323029
7268656360
146139133128123
254243232223215
361344330317305
771735704676652
1,3901,3201,2701,2201,170
2,1902,0902,0001,9201,850
4,5604,3504,1604,0003,850
800850900950
1,000
2827272625
5857555352
119115111108105
208201195189184
295285276268261
629609590573558
1,1301,1001,0601,0301,000
1,7901,7301,6801,6301,580
3,7203,6003,4903,3903,300
1,1001,2001,3001,4001,500
2423222120
4947454342
10095918885
175167160153148
248237227218210
530505484465448
954910871837806
1,5001,4301,3701,3201,270
3,1302,9902,8602,7502,650
1,6001,7001,8001,9002,000
1919181817
4039383736
8279777472
143138134130126
202196190184179
432419406394383
779753731709690
1,2301,1901,1501,1201,090
2,5602,4702,4002,3302,270
Table 12-17Semi-Rigid Copper Tubing [NFPA 54-09: Table 6.2(k)]
Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.†When this table is used to size the tubing upstream of a line pressure regulator, the pipe or tubing downstream of the line pressure regulator shall be
sized using a pressure drop no greater than 1 in. w.c.
Table 12-17 IDAHO STATE PLUMBING CODE
198
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 5.0 psi
Pressure Drop: 3.5 psi
Specific Gravity: 0.60
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Cubic Feet of Gas per Hour
1020304050
511351282241214
1,050724582498441
2,1401,4701,1801,010
898
3,7502,5802,0701,7701,570
5,3203,6502,9302,5102,230
11,4007,8006,2705,3604,750
20,40014,00011,3009,6608,560
32,20022,20017,80015,20013,500
67,10046,10037,00031,70028,100
60708090
100
194178166156147
400368342321303
813748696653617
1,4201,3101,2201,1401,080
2,0201,8601,7301,6201,530
4,3103,9603,6903,4603,270
7,7507,1306,6406,2305,880
12,20011,20010,5009,8209,270
25,50023,40021,80020,40019,300
125150175200250
13011810910190
269243224208185
547495456424376
955866796741657
1,3601,2301,1301,050
932
2,9002,6202,4102,2501,990
5,2104,7204,3504,0403,580
8,2207,4506,8506,3705,650
17,10015,50014,30013,30011,800
300350400450500
8175696562
167154143134127
340313291273258
595547509478451
844777722678640
1,8001,6601,5401,4501,370
3,2502,9902,7802,6102,460
5,1204,7104,3804,1103,880
10,7009,8109,1208,5608,090
550600650700750
5856535149
121115110106102
245234224215207
429409392376362
608580556534514
1,3001,2401,1901,1401,100
2,3402,2302,1402,0501,980
3,6903,5203,3703,2403,120
7,6807,3307,0206,7406,490
800850900950
1,000
4846454342
9895929087
200194188182177
350339328319310
497481466452440
1,0601,0301,000
967940
1,9101,8501,7901,7401,690
3,0102,9102,8202,7402,670
6,2706,0705,8805,7105,560
1,1001,2001,3001,4001,500
4038373534
8379767370
169161154148143
295281269259249
418399382367353
893852816784755
1,6101,5301,4701,4101,360
2,5302,4202,3202,2202,140
5,2805,0404,8204,6304,460
1,6001,7001,8001,9002,000
3332313029
6865636260
138133129125122
241233226219213
341330320311302
729705684664646
1,3101,2701,2301,2001,160
2,0702,0001,9401,8901,830
4,3104,1704,0403,9303,820
Table 12-18Semi-Rigid Copper Tubing [NFPA 54: Table 6.2(l)]
Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Table 12-18FUEL PIPING
199
READ ONLY
READ ONLY
Table 12-19Corrugated Stainless Steel Tubing (CSST) [NFPA 54-09: Table 6.2(m)]
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additionalfittings and/or bends.
(2) All table entries are rounded to 3 significant digits.
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additionalfittings and/or bends.
(2) All table entries are rounded to 3 significant digits.
Table 12-20Corrugated Stainless Steel Tubing (CSST) [NFPA 54: Table 6.2(n)]
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 0.60
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
Length (ft) Capacity in Cubic Feet of Gas per Hour
510152025
4632252219
6344353127
11582665852
13495776760
225161132116104
270192157137122
471330267231206
546383310269240
895639524456409
1,037746615536482
1,7901,2601,030
888793
2,0701,4701,2001,050
936
3,6602,6002,1401,8501,660
4,1402,9302,4002,0801,860
30405060
18151312
25211917
47413734
55474238
96837568
112978780
188162144131
218188168153
374325292267
442386347318
723625559509
856742665608
1,5201,3201,1801,080
1,7001,4701,3201,200
708090
100
1110109
16151413
31292826
36333230
63605754
74696562
121113107101
141132125118
248232219208
295277262249
471440415393
563527498472
1,000940887843
1,1101,040
983933
150200250300
7655
10987
20181615
23211917
42383432
48443936
78716357
91827467
17114813395
205179161148
320277247226
387336301275
691600538492
762661591540
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 3.0 in. w.c.
Specific Gravity: 0.60
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 46 48 60 62
Length (ft) Capacity in Cubic Feet of Gas per Hour
510152025
12083675751
160112907869
277197161140125
327231189164147
529380313273245
649462379329295
1,180828673580518
1,370958778672599
2,1401,5301,2501,090
978
4,4303,2002,5402,2001,960
5,0103,5602,9102,5302,270
8,8006,2705,1404,4604,000
10,1007,1605,8505,0704,540
30405060
46393532
63544844
1151008982
13411610495
225196176161
270234210192
471407363330
546471421383
895778698639
1,7901,5501,3801,260
2,0701,8001,6101,470
3,6603,1802,8502,600
4,1403,5903,2102,930
708090
100
29272624
41383634
76716763
88827773
150141133126
178167157149
306285268254
355331311295
593555524498
1,1701,0901,030
974
1,3601,2801,2001,140
2,4202,2602,1402,030
2,7202,5402,4002,280
150200250300
19171513
27232119
52454037
60524642
104918275
1221069587
206178159144
240207184168
409355319234
793686613559
936812728665
1,6601,4401,2901,180
1,8601,6101,4401,320
Table 12-19 – Table 12-20 IDAHO STATE PLUMBING CODE
200
READ ONLY
READ ONLY
Table 12-21Corrugated Stainless Steel Tubing (CSST) [NFPA 54: Table 6.2(o)]
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additionalfittings and/or bends.
(2) All table entries are rounded to 3 significant digits.
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 3/4 psi, do not use this table. Consult with
regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.(2) CAUTION: Capacities shown in table may exceed maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for
guidance.(3) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased
by an equivalent length of tubing according to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number ofadditional fittings and/or bends.
(4) All table entries are rounded to 3 significant digits.
Table 12-22Corrugated Stainless Steel Tubing (CSST) [NFPA 54-09: Table 6.2(p)]
Gas: Natural
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 0.60
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
Length (ft) Capacity in Cubic Feet of Gas per Hour
1025304050
270166151129115
353220200172154
587374342297266
700444405351314
1100709650567510
1,370876801696624
2,5901,6201,4801,2701,140
2,9901,8701,7001,4701,310
4,5102,8902,6402,3002,060
5,0373,2582,9872,6052,343
9,6006,0405,5104,7604,260
10,7006,7806,2005,3804,820
18,60011,90010,9009,4408,470
21,60013,70012,50010,9009,720
7580
100150200
9389796455
1241201078775
218211189155135
257249222182157
420407366302263
512496445364317
922892795646557
1,0701,030
920748645
1,6901,6401,4701,2101,050
1,9321,8741,6851,3891,212
3,4703,3603,0002,4402,110
3,9503,8203,4202,8002,430
6,9406,7306,0304,9404,290
7,9407,6906,8805,6204,870
250300400500
49443834
67615246
1211109686
141129111100
236217189170
284260225202
497453390348
576525453404
941862749552
1,090999871783
1,8901,7201,4901,330
2,1801,9901,7301,550
3,8503,5203,0602,740
4,3603,9803,4503,090
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 6.0 in. w.c.
Specific Gravity: 0.60
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 46 48 60 62
Length (ft) Capacity in Cubic Feet of Gas per Hour
510152025
173120968374
22916013011299
389277227197176
461327267231207
737529436380342
911649532462414
1,6901,180
960828739
1,9501,3701,110
958855
3,0002,1401,7601,5301,370
6,2804,4303,6103,1202,790
7,0505,0104,1003,5603,190
12,4008,8007,2106,2705,620
14,26010,1008,2607,1606,400
30405060
67575146
90786963
161140125115
189164147134
313273245225
379329295270
673580518471
778672599546
1,2501,090
978895
2,5402,2001,9601,790
2,9102,5302,2702,070
5,1404,4604,0003,660
5,8505,0704,5404,140
708090
100
42393735
58545148
1061009489
124116109104
209196185176
250234221210
435407383363
505471444421
830778735698
1,6601,5501,4601,380
1,9201,8001,7001,610
3,3903,1803,0002,850
3,8403,5903,3903,210
150200250300
28242119
39343027
73635752
85736660
145126114104
172149134122
294254226206
342295263240
573498447409
1,130974870793
1,3201,1401,020
936
2,3402,0301,8201,660
2,6302,2802,0401,860
Table 12-21 – Table 12-22FUEL PIPING
201
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 5.0 psi
Pressure Drop: 3.5 psi
Specific Gravity: 0.60
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
Length (ft) Capacity in Cubic Feet of Gas per Hour
1025304050
523322292251223
674420382329293
1,080691632549492
1,300827755654586
2,0001,2901,1801,030
926
2,5301,6201,4801,2801,150
4,9203,0802,8002,4202,160
5,6603,5403,2302,7902,490
8,3005,3104,8604,2303,790
9,1405,9115,4204,7274,251
18,10011,40010,4008,9708,020
19,80012,60011,50010,0008,930
34,40022,00020,10017,40015,600
40,40025,60023,40020,20018,100
7580
100150200
180174154124107
238230205166143
403391350287249
479463415339294
763740665548478
944915820672584
1,7501,6901,5101,2301,060
2,0201,9601,7401,4201,220
3,1103,0202,7102,2201,930
3,5063,4003,0572,5212,199
6,5306,3205,6504,6003,980
7,3207,0906,3505,2004,510
12,80012,40011,1009,1307,930
14,80014,30012,80010,5009,090
250300400500
95867466
12811610089
223204177159
263240208186
430394343309
524479416373
945860742662
1,090995858766
1,7301,5901,3801,040
1,9771,8131,5811,422
3,5503,2402,8002,500
4,0403,6903,2102,870
7,1106,5005,6505,060
8,1407,4306,4405,760
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1 psi, do not use this table. Consult with regu-
lator manufacturer for pressure drops and capacity factors. Pressure drops across regulator may vary with the flow rate.(2) CAUTION: Capacities shown in table may exceed maximum capacity of selected regulator. Consult tubing manufacturer for guidance.(3) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additionalfittings and/or bends.
(4) All table entries are rounded to 3 significant digits.
Table 12-23Corrugated Stainless Steel Tubing (CSST) [NFPA 54-09: Table 6.2(q)]
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.3 in. w.c.
Specific Gravity: 0.60
Pipe Size (in.)
Nominal OD: 1/2 3/4 1 1-1/4 1-1/2 2
Designation: SDR 9.33 SDR 11.0 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00
Actual ID: 0.660 0.860 1.077 1.328 1.554 1.943
Length (ft) Capacity in Cubic Feet of Gas per Hour
1020304050
153105847264
305210169144128
551379304260231
955656527451400
1,440991796681604
2,5901,7801,4301,2201,080
60708090
100
5853504644
116107999388
209192179168159
362333310291275
547503468439415
983904841789745
125150175200250
3935323027
7871656054
14112711710997
243221203189167
368333306285253
661598551512454
300350400450500
2422211918
4845423937
8881757066
152139130122115
229211196184174
411378352330312
Table 12-24Polyethylene Plastic Pipe [NFPA 54: Table 6.2(r)]
Note: All table entries are rounded to 3 significant digits.
Table 12-23 – Table 12-24 IDAHO STATE PLUMBING CODE
202
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: Less than 2 psi
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 0.60
Pipe Size (in.)
Nominal OD: 1/2 3/4 1 1-1/4 1-1/2 2
Designation: SDR 9.33 SDR 11.0 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00
Actual ID: 0.660 0.860 1.077 1.328 1.554 1.943
Length (ft) Capacity in Cubic Feet of Gas per Hour
1020304050
2011381119584
403277222190169
726499401343304
1,260865695594527
1,9001,3101,050
898796
3,4102,3501,8801,6101,430
60708090
100
7670656158
153140131123116
276254236221209
477439409383362
721663617579547
1,3001,1901,1101,040
983
125150175200250
5146434035
10393868071
185168154144127
321291268249221
485439404376333
871789726675598
300350400450500
3229272624
6459555148
115106999388
200184171160152
302278258242229
542499464435411
Table 12-25Polyethylene Plastic Pipe [NFPA 54: Table 6.2(s)]
Note: All table entries are rounded to 3 significant digits.
Table 12-25FUEL PIPING
203
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 0.60
Pipe Size (in.)
Nominal OD: 1/2 3/4 1 1-1/4 1-1/2 2
Designation: SDR 9.33 SDR 11.0 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00
Actual ID: 0.660 0.860 1.077 1.328 1.554 1.943
Length (ft) Capacity in Cubic Feet of Gas per Hour
1020304050
1,8601,2801,030
878778
3,7202,5602,0501,7601,560
6,7104,6103,7103,1702,810
11,6007,9906,4205,4904,870
17,60012,1009,6908,3007,350
31,60021,70017,40014,90013,200
60708090
100
705649603566535
1,4101,3001,2101,1301,070
2,5502,3402,1802,0501,930
4,4104,0603,7803,5403,350
6,6606,1305,7005,3505,050
12,00011,00010,2009,6109,080
125150175200250
474429395368326
949860791736652
1,7101,5501,4301,3301,180
2,9702,6902,4702,3002,040
4,4804,0603,7303,4703,080
8,0507,2906,7106,2405,530
300350400450500
295272253237224
591544506475448
1,070981913856809
1,8501,7001,5801,4801,400
2,7902,5702,3902,2402,120
5,0104,6104,2904,0203,800
550600650700750
213203194187180
426406389374360
768733702674649
1,3301,2701,2201,1701,130
2,0101,9201,8401,7601,700
3,6103,4403,3003,1703,050
800850900950
1,000
174168163158154
348336326317308
627607588572556
1,0901,0501,020
990963
1,6401,5901,5401,5001,450
2,9502,8502,7702,6902,610
1,1001,2001,3001,4001,500
146139134128124
293279267257247
528504482463446
915873836803773
1,3801,3201,2601,2101,170
2,4802,3702,2702,1802,100
1,6001,7001,8001,9002,000
119115112109106
239231224218212
431417404393382
747723701680662
1,1301,0901,0601,0301,000
2,0301,9601,9001,8501,800
Table 12-26Polyethylene Plastic Pipe [NFPA 54: Table 6.2(t)]
Note: All table entries are rounded to 3 significant digits.
Table 12-26 IDAHO STATE PLUMBING CODE
204
READ ONLY
READ ONLY
Gas: Natural
Inlet Pressure: Less than 2.0 psi
Pressure Drop: 0.3 in. w.c.
Specific Gravity: 0.60
Plastic Tubing Size (CTS)* (in.)
Nominal OD: 1/2 3/4
Designation: SDR 7.00 SDR 11.00
Actual ID: 0.445 0.927
Length (ft) Capacity in Cubic Feet of Gas per Hour
1020304050
5437302623
372256205176156
60708090
100
2119181716
141130121113107
125150175200
14131211
95867974
225250275300
10NANANA
69656259
350400450500
NANANANA
54514745
Gas: Natural
Inlet Pressure: Less than 2.0 psi
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 0.60
Plastic Tubing Size (CTS)* (in.)
Nominal OD: 1/2 3/4
Designation: SDR 7.00 SDR 11.00
Actual ID: 0.445 0.927
Length (ft) Capacity in Cubic Feet of Gas per Hour
1020304050
7249393430
490337271232205
60708090
100
2725232221
186171159149141
125150175200
18171514
12511310497
225250275300
13121111
91868278
350400450500
10NANANA
72676359
Table 12-27Polyethylene Plastic Tubing [NFPA 54: Table 6.2(u)]
Table 12-28Polyethylene Plastic Tubing [NFPA 54: Table 6.2(v)]
* CTS = Copper tube size.NA means a flow of less than 10 cfh.Note: All table entries are rounded to 3 significant digits.
* CTS = Copper tube size.NA means a flow of less than 10 cfh.Note: All table entries are rounded to 3 significant digits.
Table 12-27 – Table 12-28FUEL PIPING
205
READ ONLY
READ ONLY
Gas: Undiluted Propane
Inlet Pressure: 10.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 1.50
INTENDED USE: Pipe Sizing Between First Stage (High Pressure Regulator) and Second Stage (Low Pressure Regulator).
Pipe Size (in.)
Nominal
Inside:1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
Actual: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length (ft.) Capacity in Thousands of Btu per Hour
1020304050
3,3202,2801,8301,5701,390
6,9504,7803,8403,2802,910
13,1009,0007,2206,1805,480
26,90018,50014,80012,70011,300
40,30027,70022,20019,00016,900
77,60053,30042,80036,60032,500
124,00085,00068,20058,40051,700
219,000150,000121,000103,00091,500
446,000306,000246,000211,000187,000
60708090
100
1,2601,1601,0801,010
956
2,6402,4302,2602,1202,000
4,9704,5704,2503,9903,770
10,2009,3808,7308,1907,730
15,30014,10013,10012,30011,600
29,40027,10025,20023,60022,300
46,90043,10040,10037,70035,600
82,90076,30070,90066,60062,900
169,000156,000145,000136,000128,000
125150175200250
848768706657582
1,7701,6101,4801,3701,220
3,3403,0202,7802,5902,290
6,8506,2105,7105,3204,710
10,3009,3008,5607,9607,060
19,80017,90016,50015,30013,600
31,50028,60026,30024,40021,700
55,70050,50046,50043,20038,300
114,000103,00094,70088,10078,100
300350400450500
528486452424400
1,1001,020
945886837
2,0801,9101,7801,6701,580
4,2703,9303,6503,4303,240
6,4005,8805,4705,1404,850
12,30011,30010,5009,8909,340
19,60018,10016,80015,80014,900
34,70031,90029,70027,90026,300
70,80065,10060,60056,80053,700
550600650700750
380363347334321
795759726698672
1,5001,4301,3701,3101,270
3,0702,9302,8102,7002,600
4,6104,4004,2104,0403,900
8,8708,4608,1107,7907,500
14,10013,50012,90012,40012,000
25,00023,90022,80021,90021,100
51,00048,60046,60044,80043,100
800850900950
1,000
310300291283275
649628609592575
1,2201,1801,1501,1101,080
2,5102,4302,3602,2902,230
3,7603,6403,5303,4303,330
7,2407,0106,8006,6006,420
11,50011,20010,80010,50010,200
20,40019,80019,20018,60018,100
41,60040,30039,10037,90036,900
1,1001,2001,3001,4001,500
261249239229221
546521499480462
1,030982940903870
2,1102,0201,9301,8501,790
3,1703,0202,8902,7802,680
6,1005,8205,5705,3505,160
9,7209,2708,8808,5308,220
17,20016,40015,70015,10014,500
35,00033,40032,00030,80029,600
1,6001,7001,8001,9002,000
213206200194189
446432419407395
840813789766745
1,7301,6701,6201,5701,530
2,5902,5002,4302,3602,290
4,9804,8204,6704,5404,410
7,9407,6807,4507,2307,030
14,00013,60013,20012,80012,400
28,60027,70026,90026,10025,400
Table 12-29Schedule 40 Metallic Pipe [NFPA 54-09: Table 6.3(a)]
Note: All table entries are rounded to 3 significant digits.
Table 12-29 IDAHO STATE PLUMBING CODE
206
READ ONLY
READ ONLY
Gas: Undiluted Propane
Inlet Pressure: 10.0 psi
Pressure Drop: 3.0 psi
Specific Gravity: 1.50
INTENDED USE: Pipe Sizing Between First Stage (High Pressure Regulator) and Second Stage (Low Pressure Regulator).
Pipe Size (in.)
Nominal
Inside:1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
Actual: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length (ft.) Capacity in Thousands of Btu per Hour
1020304050
5,8904,0503,2502,7802,460
12,3008,4606,7905,8105,150
23,20015,90012,80011,0009,710
47,60032,70026,30022,50019,900
71,30049,00039,40033,70029,900
137,00094,40075,80064,90057,500
219,000150,000121,000103,00091,600
387,000266,000214,000183,000162,000
789,000543,000436,000373,000330,000
60708090
100
2,2302,0501,9101,7901,690
4,6704,3004,0003,7503,540
8,7908,0907,5307,0606,670
18,10016,60015,50014,50013,700
27,10024,90023,20021,70020,500
52,10047,90044,60041,80039,500
83,00076,40071,10066,70063,000
147,000135,000126,000118,000111,000
299,000275,000256,000240,000227,000
125150175200250
1,5001,3601,2501,1601,030
3,1402,8402,6202,4302,160
5,9105,3604,9304,5804,060
12,10011,00010,1009,4108,340
18,20016,50015,20014,10012,500
35,00031,70029,20027,20024,100
55,80050,60046,50043,30038,400
98,70089,40082,30076,50067,800
201,000182,000167,800156,100138,400
300350400450500
935860800751709
1,9501,8001,6701,5701,480
3,6803,3903,1502,9602,790
7,5606,9506,4706,0705,730
11,30010,4009,6909,0908,590
21,80020,10018,70017,50016,500
34,80032,00029,80027,90026,400
61,50056,50052,60049,40046,600
125,400115,300107,300100,70095,100
550600650700750
673642615591569
1,4101,3401,2901,2401,190
2,6502,5302,4202,3302,240
5,4505,2004,9804,7804,600
8,1607,7807,4507,1606,900
15,70015,00014,40013,80013,300
25,00023,90022,90022,00021,200
44,30042,20040,50038,90037,400
90,30086,20082,50079,30076,400
800850900950
1,000
550532516501487
1,1501,1101,0801,0501,020
2,1702,1002,0301,9701,920
4,4504,3004,1704,0503,940
6,6606,4506,2506,0705,900
12,80012,40012,00011,70011,400
20,50019,80019,20018,60018,100
36,20035,00033,90032,90032,000
73,70071,40069,20067,20065,400
1,1001,2001,3001,4001,500
463442423406391
968923884849818
1,8201,7401,6701,6001,540
3,7403,5703,4203,2803,160
5,6105,3505,1204,9204,740
10,80010,3009,8709,4809,130
17,20016,40015,70015,10014,600
30,40029,00027,80026,70025,700
62,10059,20056,70054,50052,500
1,6001,7001,8001,9002,000
378366355344335
790765741720700
1,4901,4401,4001,3601,320
3,0602,9602,8702,7802,710
4,5804,4304,3004,1704,060
8,8208,5308,2708,0407,820
14,10013,60013,20012,80012,500
24,80024,00023,30022,60022,000
50,70049,00047,60046,20044,900
Table 12-30Schedule 40 Metallic Pipe [NFPA 54-09: Table 6.3(b)]
Note: All table entries are rounded to 3 significant digits.
Table 12-30FUEL PIPING
207
READ ONLY
READ ONLY
Gas: Undiluted Propane
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 1.50
INTENDED USE: Pipe Sizing Between 2 psi Service and Line Pressure Regulator
Pipe Size (in.)
Nominal 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
Actual ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length (ft.) Capacity in Thousands of Btu per Hour
1020304050
2,6801,8401,4801,2601,120
5,5903,8503,0902,6402,340
10,5007,2405,8204,9804,410
21,60014,90011,90010,2009,060
32,40022,30017,90015,30013,600
62,40042,90034,50029,50026,100
99,50068,40054,90047,00041,700
176,000121,00097,10083,10073,700
359,000247,000198,000170,000150,000
60708090
100
1,010934869815770
2,1201,9501,8201,7001,610
4,0003,6803,4203,2103,030
8,2107,5507,0206,5906,230
12,30011,30010,5009,8809,330
23,70021,80020,30019,00018,000
37,70034,70032,30030,30028,600
66,70061,40057,10053,60050,600
136,000125,000116,000109,000103,000
125150175200250
682618569529469
1,4301,2901,1901,110
981
2,6902,4402,2402,0801,850
5,5205,0004,6004,2803,790
8,2707,4906,8906,4105,680
15,90014,40013,30012,30010,900
25,40023,00021,20019,70017,400
44,90040,70037,40034,80030,800
91,50082,90076,30071,00062,900
300350400450500
425391364341322
889817760714674
1,6701,5401,4301,3401,270
3,4403,1602,9402,7602,610
5,1504,7404,4104,1303,910
9,9209,1208,4907,9607,520
15,80014,50013,50012,70012,000
27,90025,70023,90022,40021,200
57,00052,40048,80045,80043,200
550600650700750
306292280269259
640611585562541
1,2101,1501,1001,0601,020
2,4802,3602,2602,1702,090
3,7103,5403,3903,2603,140
7,1406,8206,5306,2706,040
11,40010,90010,4009,9909,630
20,10019,20018,40017,70017,000
41,10039,20037,50036,00034,700
800850900950
1,000
250242235228222
523506490476463
985953924897873
2,0201,9601,9001,8401,790
3,0302,9302,8402,7602,680
5,8305,6405,4705,3105,170
9,3009,0008,7208,4708,240
16,40015,90015,40015,00014,600
33,50032,40031,50030,50029,700
1,1001,2001,3001,4001,500
210201192185178
440420402386372
829791757727701
1,7001,6201,5501,4901,440
2,5502,4302,3302,2402,160
4,9104,6804,4904,3104,150
7,8307,4707,1506,8706,620
13,80013,20012,60012,10011,700
28,20026,90025,80024,80023,900
1,6001,7001,8001,9002,000
172166161157152
359348337327318
677655635617600
1,3901,3401,3001,2701,230
2,0802,0101,9501,9001,840
4,0103,8803,7603,6503,550
6,3906,1806,0005,8205,660
11,30010,90010,60010,30010,000
23,00022,30021,60021,00020,400
Table 12-31Schedule 40 Metallic Pipe [NFPA 54-09: Table 6.3(c)]
Note: All table entries are rounded to 3 significant digits.
Table 12-31 IDAHO STATE PLUMBING CODE
208
READ ONLY
READ ONLY
Gas: Undiluted Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
INTENDED USE: Pipe Sizing Between Single or Second Stage (Low Pressure Regulator) and Appliance
Pipe Size (in.)
Nominal
Inside:1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 4
Actual ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length (ft.) Capacity in Thousands of Btu per Hour
1020304050
291200160137122
608418336287255
1,150787632541480
2,3501,6201,3001,110
985
3,5202,4201,9401,6601,480
6,7904,6603,7503,2102,840
10,8007,4305,9705,1104,530
19,10013,10010,6009,0308,000
39,00026,80021,50018,40016,300
6080
100125150
110101948984
231212197185175
434400372349330
892821763716677
1,3401,2301,1401,0701,010
2,5702,3702,2002,0701,950
4,1003,7703,5103,2903,110
7,2506,6706,2105,8205,500
14,80013,60012,70011,90011,200
175200250300350
7467625851
155140129120107
292265243227201
600543500465412
899814749697618
1,7301,5701,4401,3401,190
2,7602,5002,3002,1401,900
4,8804,4204,0603,7803,350
9,9509,0108,2907,7106,840
400450500550600
4642403735
9789837873
182167156146138
373344320300283
560515479449424
1,080991922865817
1,7201,5801,4701,3801,300
3,0402,7902,6002,4402,300
6,1905,7005,3004,9704,700
650700750800850
3332302928
7066646159
131125120115111
269257246236227
403385368354341
776741709681656
1,2401,1801,1301,0901,050
2,1902,0902,0001,9201,850
4,4604,2604,0803,9203,770
900950
1,0001,1001,200
2726252524
5755535250
1071041009795
220213206200195
329319309300292
634613595578562
1,010978948921895
1,7901,7301,6801,6301,580
3,6403,5303,4203,3203,230
1,3001,4001,5001,6001,700
2322212019
4846444240
9086827976
185176169162156
277264253243234
534509487468451
850811777746719
1,5001,4301,3701,3201,270
3,0702,9302,8002,6902,590
1,8001,9002,000
191818
393837
747169
151146142
226219212
436422409
694672652
1,2301,1901,150
2,5002,4202,350
Table 12-32Schedule 40 Metallic Pipe [NFPA 54-09: Table 6.3(d)]
Note: All table entries are rounded to 3 significant digits.
Table 12-32FUEL PIPING
209
READ ONLY
READ ONLY
Table 12-33Semi-Rigid Copper Tubing [NFPA 54-09: Table 6.3(e)]
Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Gas: Undiluted Propane
Inlet Pressure: 10.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 1.50
INTENDED USE: Tube Sizing Between First Stage (High Pressure) Regulator and Second Stage (Low Pressure) Regulator.
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Thousands of Btu per Hour
1020304050
513352283242215
1,060727584500443
2,1501,4801,1901,020
901
3,7602,5802,0801,7801,570
5,3303,6702,9402,5202,230
11,4007,8306,2905,3804,770
20,50014,10011,3009,6908,590
32,30022,20017,90015,30013,500
67,40046,30037,20031,80028,200
60708090
100
194179166156147
401369343322304
816751699655619
1,4301,3101,2201,1501,080
2,0201,8601,7301,6301,540
4,3203,9803,7003,4703,280
7,7807,1606,6606,2505,900
12,30011,30010,5009,8509,310
25,60023,50021,90020,50019,400
125150175200250
13111810910190
270244225209185
549497457426377
959869799744659
1,3601,2301,1301,060
935
2,9102,6302,4202,2502,000
5,2304,7404,3604,0603,600
8,2507,4706,8806,4005,670
17,20015,60014,30013,30011,800
300350400450500
8175706562
168155144135127
342314292274259
597549511480453
847779725680643
1,8101,6601,5501,4501,370
3,2603,0002,7902,6202,470
5,1404,7304,4004,1303,900
10,7009,8409,1608,5908,120
550600650700750
5956545150
121115111106102
246235225216208
430410393378364
610582558536516
1,3001,2401,1901,1401,100
2,3502,2402,1402,0601,980
3,7003,5303,3803,2503,130
7,7107,3507,0406,7706,520
800850900950
1,000
4846454442
9996939088
201195189183178
351340330320311
498482468454442
1,0601,0301,000
970944
1,9201,8501,8001,7501,700
3,0202,9202,8402,7502,680
6,2906,0905,9105,7305,580
1,1001,2001,3001,4001,500
4038373534
8379767370
169161155148143
296282270260250
420400383368355
896855819787758
1,6101,5401,4701,4201,360
2,5402,4302,3202,2302,150
5,3005,0504,8404,6504,480
1,6001,7001,8001,9002,000
3332313029
6866646260
138134130126122
241234227220214
343331321312304
732708687667648
1,3201,2701,2401,2001,170
2,0802,0101,9501,8901,840
4,3304,1904,0603,9403,830
Table 12-33 IDAHO STATE PLUMBING CODE
210
READ ONLY
READ ONLY
Table 12-34Semi-Rigid Copper Tubing [NFPA 54-09: Table 6.3(f)]
NA means a flow of less than 10,000 Btu/hr.Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Gas: Undiluted Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
INTENDED USE: Tube Sizing Between Single or Second Stage (Low Pressure Regulator) and Appliance.
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Thousands of Btu per Hour
1020304050
4531252119
9364514439
1881291048979
329226182155138
467321258220195
997685550471417
1,8001,230
991848752
2,8301,9501,5601,3401,180
5,8904,0503,2502,7802,470
60708090
100
1716151413
3532302827
7166615754
12511510710095
177163152142134
378348324304287
681626583547517
1,070988919862814
2,2402,0601,9101,8001,700
125150175200250
1110
NANANA
2421201816
4844403733
8476706558
119108999282
254230212197175
458415382355315
722654602560496
1,5001,3601,2501,1701,030
300350400450500
NANANANANA
1514131211
3028262423
5248454240
7468636056
158146136127120
285262244229216
449414385361341
936861801752710
550600650700750
NANANANANA
1110
NANANA
2221201918
3836343332
5351494745
11410910410096
205196188180174
324309296284274
674643616592570
800850900950
1,000
NANANANANA
NANANANANA
1817171616
3130292827
4442414039
9390878583
168162157153149
264256248241234
551533517502488
1,1001,2001,3001,4001,500
NANANANANA
NANANANANA
1514141313
2625242322
3735343231
7875726966
141135129124119
223212203195188
464442423407392
1,6001,7001,8001,9002,000
NANANANANA
NANANANANA
1212111111
2120201919
3029282727
6462605857
115112108105102
182176170166161
378366355345335
Table 12-34FUEL PIPING
211
READ ONLY
READ ONLY
Table 12-35Semi-Rigid Copper Tubing [NFPA 54-09: Table 6.3(g)]
Note: All table entries are rounded to 3 significant digits.*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.
Gas: Undiluted Propane
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 1.50
INTENDED USE: Tube Sizing Between 2 psig Service and Line Pressure Regulator
Tube Size (in.)
Nominal:K & L: 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 2
ACR: 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 – –
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length (ft.) Capacity in Thousands of Btu per Hour
1020304050
413284228195173
852585470402356
1,7301,190
956818725
3,0302,0801,6701,4301,270
4,3002,9502,3702,0301,800
9,1706,3105,0604,3303,840
16,50011,4009,1207,8006,920
26,00017,90014,40012,30010,900
54,20037,30029,90025,60022,700
60708090
100
157144134126119
323297276259245
657605562528498
1,1501,060
983922871
1,6301,5001,3901,3101,240
3,4803,2002,9802,7902,640
6,2705,7605,3605,0304,750
9,8809,0908,4507,9307,490
20,60018,90017,60016,50015,600
125150175200250
10595888272
217197181168149
442400368343304
772700644599531
1,100992913849753
2,3402,1201,9501,8101,610
4,2103,8203,5103,2702,900
6,6406,0205,5405,1504,560
13,80012,50011,50010,7009,510
300350400450500
6660565350
135124116109103
275253235221209
481442411386365
682628584548517
1,4601,3401,2501,1701,110
2,6202,4102,2502,1101,990
4,1403,8003,5403,3203,140
8,6107,9207,3706,9206,530
550600650700750
4745434140
9793898682
198189181174168
346330316304293
491469449431415
1,0501,000
959921888
1,8901,8001,7301,6601,600
2,9802,8402,7202,6202,520
6,2105,9205,6705,4505,250
800850900950
1,000
3937363534
8077757271
162157152147143
283274265258251
401388376366356
857829804781760
1,5401,4901,4501,4101,370
2,4302,3502,2802,2202,160
5,0704,9004,7504,6204,490
1,1001,2001,3001,4001,500
3231302827
6764615957
136130124120115
238227217209201
338322309296286
721688659633610
1,3001,2401,1901,1401,100
2,0501,9501,8701,8001,730
4,2704,0703,9003,7403,610
1,6001,7001,8001,9002,000
2626252423
5553515048
11110810410199
194188182177172
276267259251244
589570553537522
1,0601,0301,000
966940
1,6701,6201,5701,5201,480
3,4803,3703,2703,1703,090
Table 12-35 IDAHO STATE PLUMBING CODE
212
READ ONLY
READ ONLY
Table 12-36Corrugated Stainless Steel Tubing (CSST) [NFPA 54-09: Table 6.3(h)]
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased
by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additionalfittings and/or bends.
(2) All table entries are rounded to 3 significant digits.
Table 12-37Corrugated Stainless Steel Tubing (CSST) [NFPA 54-09: Table 6.3(i)]
Gas: Undiluted Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in w.c.
Specific Gravity: 1.50
INTENDED USE: CSST Sizing Between Single or Second Stage (Low Pressure) Regulator and Appliance Shutoff Valve
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
Length (ft) Capacity in Thousands of Btu per Hour
5101520
72503934
99695549
18112910491
211150121106
355254208183
426303248216
744521422365
863605490425
1,420971775661
1,6381,179
972847
2,8301,9901,6201,400
3,2702,3201,9001,650
5,7804,1103,3702,930
6,5504,6403,7903,290
25304050
30282320
42393330
82746458
94877466
164151131118
192177153137
325297256227
379344297265
583528449397
762698610548
1,2501,140
988884
1,4801,3501,1701,050
2,6302,4002,0901,870
2,9402,6802,3302,080
60708090
19171515
26252322
53494544
60575250
107999490
126117109102
207191178169
241222208197
359330307286
502466438414
805745696656
961890833787
1,7101,5901,4901,400
1,9001,7601,6501,550
100150200250300
1411988
2015141211
4131282523
4736333026
8566605350
9875696157
1591231129990
186143129117107
270217183163147
393324283254234
621506438390357
746611531476434
1,3301,090
948850777
1,4801,2101,050
934854
Gas: Undiluted Propane
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 1.50
INTENDED USE: CSST Sizing Between 2 psi Service and Line Pressure Regulator
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
Length (ft) Capacity in Thousands of Btu per Hour
1025304050
426262238203181
558347316271243
927591540469420
1,110701640554496
1,7401,1201,030
896806
2,1701,3801,2701,100
986
4,1002,5602,3302,0101,790
4,7202,9502,6902,3202,070
7,1304,5604,1803,6303,260
7,9585,1474,7194,1163,702
15,2009,5508,7107,5306,730
16,80010,7009,7908,5007,610
29,40018,80017,20014,90013,400
34,20021,70019,80017,20015,400
7580
100150200
14714012410186
196189169137118
344333298245213
406393350287248
663643578477415
809768703575501
1,4601,4101,2601,020
880
1,6901,6301,4501,1801,020
2,6802,5902,3301,9101,660
3,0532,9612,6622,1951,915
5,4805,3004,7403,8603,340
6,2306,0405,4104,4303,840
11,00010,6009,5307,8106,780
12,60012,20010,9008,8907,710
250300400500
77696053
105968272
191173151135
222203175158
373343298268
448411355319
785716616550
910829716638
1,4901,3601,1601,030
1,7221,5781,3761,237
2,9802,7202,3502,100
3,4403,1502,7302,450
6,0805,5604,8304,330
6,9006,3005,4604,880
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1/2 psi (based on 13 in. w.c. outlet pressure),
DO NOT USE THIS TABLE. Consult with regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator mayvary with flow rate.
(2) CAUTION: Capacities shown in table may exceed maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for guidance.(3) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased by an
equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fittingsand/or bends.
(4) All table entries are rounded to 3 significant digits.
Table 12-36 – Table 12-37FUEL PIPING
213
READ ONLY
READ ONLY
Table 12-38Corrugated Stainless Steel Tubing (CSST) [NFPA 54-09: Table 6.3(j)]
Gas: Undiluted Propane
Inlet Pressure: 5.0 psi
Pressure Drop: 3.5 psi
Specific Gravity: 1.50
Tube Size (EHD)*
Flow Designation: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
Length (ft) Capacity in Thousands of Btu per Hour
1025304050
826509461396352
1,070664603520463
1,7101,090
999867777
2,0601,3101,1901,030
926
3,1502,0401,8701,6301,460
4,0002,5502,3402,0301,820
7,8304,8604,4303,8203,410
8,9505,6005,1004,4003,930
13,1008,4007,6806,6805,990
14,4419,3398,5647,4696,717
28,60018,00016,40014,20012,700
31,20019,90018,20015,80014,100
54,40034,70031,70027,60024,700
63,80040,40036,90032,00028,600
7580
100150200
284275243196169
376363324262226
637618553453393
757731656535464
1,2101,1701,050
866755
1,4901,4501,3001,060
923
2,7702,6802,3901,9401,680
3,1903,0902,7602,2401,930
4,9204,7704,2803,5103,050
5,5395,3724,8303,9833,474
10,3009,9908,9307,2706,290
11,60011,20010,0008,2107,130
20,30019,60017,60014,40012,500
23,40022,70020,30016,60014,400
250300400500
150136117104
202183158140
352322279251
415379328294
679622542488
828757657589
1,4901,3601,1701,050
1,7301,5701,3601,210
2,7402,5102,1801,950
3,1242,8652,4982,247
5,6205,1204,4303,960
6,3905,8405,0704,540
11,20010,3008,9208,000
12,90011,70010,2009,110
*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value ofEHD, the greater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1 psi, do not use this table. Consult with regu-
lator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate.(2) CAUTION: Capacities shown in table may exceed maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for
guidance.(3) Table includes losses for four 90 degree bends and two end fittings. Tubing runs with larger numbers of bends and/or fittings shall be increased by an
equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fittingsand/or bends.
(4) All table entries are rounded to 3 significant digits.
Gas: Undiluted Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
INTENDED USE: PE Sizing Between Integral 2-Stage Regulator at Tank or 2nd Stage (Low Pressure Regulator) and Building
Pipe Size (in.)
Nominal OD: 1/2 3/4 1 1-1/4 1-1/2 2
Designation: SDR 9.33 SDR 11.0 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00
Actual ID: 0.660 0.860 1.077 1.328 1.554 1.943
Length (ft) Capacity in Thousands of Btu per Hour
1020304050
340233187160142
680468375321285
1,230844677580514
2,1301,4601,1701,000
890
3,2102,2101,7701,5201,340
5,7703,9703,1802,7302,420
60708090
100
12911911010398
258237221207196
466428398374353
807742690648612
1,2201,1201,040
978924
2,1902,0101,8701,7601,660
125150175200250
8778726760
173157145135119
313284261243215
542491452420373
819742683635563
1,4701,3301,2301,1401,010
300350400450500
5450464341
10899928782
195179167157148
338311289271256
510469436409387
916843784736695
Table 12-39Polyethylene Plastic Pipe [NFPA 54-09: Table 6.3(k)]
Note: All table entries are rounded to 3 significant digits.
Table 12-38 – Table 12-39 IDAHO STATE PLUMBING CODE
214
READ ONLY
READ ONLY
Gas: Undiluted Propane
Inlet Pressure: 2.0 psi
Pressure Drop: 1.0 psi
Specific Gravity: 1.50
INTENDED USE: PE Pipe Sizing Between 2 psi Service and Line Pressure Regulator
Pipe Size (in.)
Nominal OD: 1/2 3/4 1 1-1/4 1-1/2 2
Designation: SDR 9.33 SDR 11.0 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00
Actual ID: 0.660 0.860 1.077 1.328 1.554 1.943
Length (ft) Capacity in Thousands of Btu per Hour
1020304050
3,1302,1501,7301,4801,310
6,2604,3003,4502,9602,620
11,3007,7606,2305,3304,730
19,60013,40010,8009,2408,190
29,50020,30016,30014,00012,400
53,10036,50029,30025,10022,200
60708090
100
1,1901,0901,010
952899
2,3702,1802,0301,9101,800
4,2803,9403,6703,4403,250
7,4206,8306,3505,9605,630
11,20010,3009,5909,0008,500
20,10018,50017,20016,20015,300
125150175200250
797722664618548
1,6001,4501,3301,2401,100
2,8802,6102,4002,2301,980
4,9904,5204,1603,8703,430
7,5306,8306,2805,8405,180
13,50012,30011,30010,5009,300
300350400450500
496457425399377
994914851798754
1,7901,6501,5301,4401,360
3,1102,8602,6602,5002,360
4,6904,3204,0203,7703,560
8,4307,7607,2206,7706,390
550600650700750
358341327314302
716683654628605
1,2901,2301,1801,1301,090
2,2402,1402,0401,9601,890
3,3803,2203,0902,9702,860
6,0705,7905,5505,3305,140
800850900950
1,000
292283274266259
585566549533518
1,0501,020
990961935
1,8301,7701,7101,6701,620
2,7602,6702,5902,5202,450
4,9604,8004,6504,5204,400
1,1001,2001,3001,4001,500
246234225216208
492470450432416
888847811779751
1,5401,4701,4101,3501,300
2,3202,2202,1202,0401,960
4,1703,9803,8103,6603,530
1,6001,7001,8001,9002,000
201194188183178
402389377366356
725702680661643
1,2601,2201,1801,1401,110
1,9001,8401,7801,7301,680
3,4103,3003,2003,1103,020
Table 12-40Polyethylene Plastic Pipe [NFPA 54-09: Table 6.3(l)]
Note: All table entries are rounded to 3 significant digits.
Table 12-40FUEL PIPING
215
READ ONLY
READ ONLY
Gas: Undiluted Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
INTENDED USE: PE Tube Sizing Between Integral
2-Stage Regulator at Tank or Second Stage (Low Pressure
Regulator) and Building.
Plastic Tubing Size (CTS) (in.)
Nominal OD: 1/2 1
Designation: SDR 7.00 SDR 11.00
Actual ID: 0.445 0.927
Length (ft) Capacity in Thousands of Btu per Hour
1020304050
12183675751
828569457391347
60708090
100
4642393735
314289269252238
125150175200
31282624
211191176164
225250275300
22212019
154145138132
350400450500
18161515
121113106100
Table 12-41Polyethylene Plastic Tubing [NFPA 54-09: Table 6.3(m)]
Note: All table entries are rounded to 3 significant digits.
Table 12-41 IDAHO STATE PLUMBING CODE
216
READ ONLY
READ ONLY