Changes to 2009 IFGC(International Fuel Gas Code)
• Adopted by Reference by section 301.3 Michigan Mechanical Code.
![Page 2: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/2.jpg)
Definitions Chapter 2
• Appliance – utilizes gas
• Apparatus and devices other than appliances.
![Page 3: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/3.jpg)
Make up air provisions 304.4
• Where exhaust fans, clothes dryers, Kitchen fans interfere with operation of appliances make up air is to be provided
• (Shall be determined in adequacy of space-Old Code)
![Page 4: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/4.jpg)
Access Service space 306.1 MMC & IFGC
• Removal of Appliance cannot result in removing other appliances, Piping & Ducts not associated with the appliance.
![Page 5: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/5.jpg)
Attic & Crawl Space installations 306.3
• Removal of the largest appliance opposed to largest part. ( Opening)
• Correlates with Michigan Mechanical Code Now
![Page 6: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/6.jpg)
Electrical Bonding 310.1.1
• CSST must be bonded to electrical service with #6 AWG
![Page 7: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/7.jpg)
Gas Piping Entering Building 404.4
• Gas line must enter a building above grade
Not approved Approved
![Page 8: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/8.jpg)
Shut of Valves 409.5.2 409.6
• Room heater shut off can be remotely located when I.D. as such
• Laboratory Valve required. – located at egress door –Research labs, schools, Industrial.
![Page 9: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/9.jpg)
Unions – 411.6
• Language now requiring unions for appliances within 6 ft of the appliance for rigid metal pipe.
• Code use to only regulate Valve upstream from union.
![Page 10: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/10.jpg)
Plastic Vent Joints 503.4.1.1
• When primer is required by Manufacturer’s Installation Instruction
• Primer must have a contrasting color.
![Page 11: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/11.jpg)
Commercial Cooking Appliance Interlock 505.11
• New Language to make sure that appliances with standing pilots not to be extinguished. –
• Compromise created for Cooking Stove companies.
• Dangerous if you have to keep relighting pilots
![Page 12: Changes to 2009 IFGC ( International Fuel Gas Code) Adopted by Reference by section 301.3 Michigan Mechanical Code](https://reader036.vdocuments.site/reader036/viewer/2022062517/56649f205503460f94c39409/html5/thumbnails/12.jpg)
Kitchen Return air allowed 618.5 (6)
• Serve only kitchen area only • Must be located 10 feet from cooking
appliances