ch6 power system slide09
TRANSCRIPT
-
8/14/2019 Ch6 Power System Slide09
1/70
BEE3133
Electrical Power SystemsChapter 6: System Protection
Rahmatul Hidayah Salimin
-
8/14/2019 Ch6 Power System Slide09
2/70
Introduction
System Protection: the equipment use
to detect and isolate the faulty section
from the system automatically.
-
8/14/2019 Ch6 Power System Slide09
3/70
Introduction
Short circuit occur when equipmentinsulation fails due to system overvoltagescaused by:
Lightning or switching surges Flashover line-line (caused by wind) Flashover to tree
Insulation contamination by dirt/salt Mechanical failure
Cable insulation failure
Natural causes Tower/pole or conductor falls Objects fall on conductors
-
8/14/2019 Ch6 Power System Slide09
4/70
Introduction
Short circuit currents can be several ordersof magnitude larger than normal operatingcurrents
If it is allowed to persist, may cause: Damage to the equipment due to heavy currents,
unbalanced current, or low voltage produces bythe short circuit
Fire and explosion effect equipment/people
Disruption of service in the entire power systemarea
-
8/14/2019 Ch6 Power System Slide09
5/70
Introduction
Careful design, operation and
maintenance of system protection can
minimize the occurrence of shortcircuit but cannot eliminate them.
-
8/14/2019 Ch6 Power System Slide09
6/70
Fault Currents and Voltages
-
8/14/2019 Ch6 Power System Slide09
7/70
Function of System Protection
Cause the prompt removal from service of anyelements of power system when it suffers ashortcircuit, or when it start to operate in any abnormal
manner that might cause damage or otherwiseinterfere with the effective operation of the rest ofthe system.
Provide indication of the locationand type of failureso that the data can be used to assist in expediting
repair and analyzing the effectiveness of fault-prevention and mitigation features.
-
8/14/2019 Ch6 Power System Slide09
8/70
Function of System Protection
Why do we need system protection:
Detect fault
Isolate faulted component
Restore faulted component
Aims:
Continued supply for rest of system Protect faulted part from damage
-
8/14/2019 Ch6 Power System Slide09
9/70
Types of Protection
A Fuses For LV Systems, Distribution Feeders and
Transformers, VTs, Auxiliary Supplies
B - Over current and earth fault Widely used in All Power Systems
Non-Directional Directional
-
8/14/2019 Ch6 Power System Slide09
10/70
Types of Protection
C - Differential For Distribution Feeders, Busbars,
Transformers, Generators etc
High Impedance
Low Impedance
Restricted E/F
Biased
Pilot Wire
-
8/14/2019 Ch6 Power System Slide09
11/70
Types of Protection
D - Distance For Transmission and Sub-transmission Lines
and Distribution Feeders, Also used as back-up protection for
transformers and generators withoutsignaling with signaling to provide unitprotection e.g.:
Time-stepped distance protection Phase comparison for transmission lines Directional comparison for transmission lines
-
8/14/2019 Ch6 Power System Slide09
12/70
Types of Protection
E - Miscellaneous:
Under and over voltage
Under and over frequency A special relay for generators, transformers, motors
etc.
Control relays: auto-reclose, tap change control, etc.
Tripping and auxiliary relays
-
8/14/2019 Ch6 Power System Slide09
13/70
Design Criteria/Characteristics
Simplicity
Economy
Speed
Sensitivity
Selectivity
Reliability
-
8/14/2019 Ch6 Power System Slide09
14/70
Design Criteria/Characteristics
Reliability Operate dependably and in healthy operating
condition when fault conditions occur, even after
remaining idle for months or years. Selectivity
Clearly discriminate between normal andabnormal system condition to avoid unnecessary,false trips.
Sensitivity Ability to distinguish the fault condition, although
the different between fault and normal conditionis small.
-
8/14/2019 Ch6 Power System Slide09
15/70
Design Criteria/Characteristics
Speed Fault at any point in the system must be
detected and isolated rapidly to minimize fault
duration and equipment damage. Any intentionaltime delays should be precise.
Economy Provide maximum protection at minimum cost
Simplicity Minimize protection equipment and circuitry
http://slide09%20chapter06.ppt/http://slide09%20chapter06.ppt/ -
8/14/2019 Ch6 Power System Slide09
16/70
Economic Factor
Total cost should take account of :
Relays, schemes and associated panels and panel wiring
Setting studies
Commissioning
CTs and VTs
Maintenance and repairs to relays
Damage repair if protection fails to operate
Lost revenue if protection operates unnecessarily
-
8/14/2019 Ch6 Power System Slide09
17/70
Economic Factor
The cost of protection is equivalent to an insurance policy
against damage to plant, and loss of supply and customer
goodwill. Acceptable cost is based on a balance of economics and
technical factors. Cost of protection should be balanced
against the cost of potential hazards.
There is an economic limit on what can be spent.
MINIMUM COST :Must ensure that all faulty equipment is
isolated by protection.
-
8/14/2019 Ch6 Power System Slide09
18/70
Relationship between reliability of supply, its
value and cost to the consumer
-
8/14/2019 Ch6 Power System Slide09
19/70
System Protection Components
Transducer / Instrument Transformer
Relay
Circuit Breaker
-
8/14/2019 Ch6 Power System Slide09
20/70
System Protection Components
Function:
Transducers/Instrument Transformers Provide low current and voltage, standardized levels suitable for
the relays operation. Relays
Discriminate between normal operating and fault conditions.
When current exceed a specified value relay will be operated andcause the trip coil of CB to be energized/open their contact.
Circuit Breakers Open the line
-
8/14/2019 Ch6 Power System Slide09
21/70
System Protection Components
-
8/14/2019 Ch6 Power System Slide09
22/70
System Protection Components
-
8/14/2019 Ch6 Power System Slide09
23/70
System Protection Flow
RelayTransducer Fault
OccurCircuit
Breaker
FaultClear
voltage or current rise from normal condition
voltage/current is reduced to match with relay rating
activate circuit breaker
circuit isolation
-
8/14/2019 Ch6 Power System Slide09
24/70
Zones of Protection
For fault anyway within the zone, the
protection system responsible to
isolate everything within the zone fromthe rest of the system.
Isolation done by CB
Must isolate only the faulty equipmentor section
-
8/14/2019 Ch6 Power System Slide09
25/70
Zones of Protection
Zones are defined for:
Generators
Transformers
Buses
Transmission and distribution lines
Motors
-
8/14/2019 Ch6 Power System Slide09
26/70
Zones of Protection
-
8/14/2019 Ch6 Power System Slide09
27/70
Zones of Protection
Characteristics:
Zones are overlapped.
Circuit breakers are located in the overlapregions.
For a fault anywhere in a zone, all circuit
breakers in that zone open to isolate thefault.
http://../Owner/Desktop/Slide09%20Chapter06.ppthttp://../Owner/Desktop/Slide09%20Chapter06.ppt -
8/14/2019 Ch6 Power System Slide09
28/70
Overlapped of Protection
No blind spot:
Neighboring zones are overlapped to avoid
the possibility of unprotected areas
Use overlapping CTs:
Isolation done by CB. Thus, it must be
inserted in each overlap region to identifythe boundary of protective zones.
-
8/14/2019 Ch6 Power System Slide09
29/70
Overlapped of Protection
Overlap accomplish by having 2 sets of
instrument transformers and relays for each
CB. Achieved by the arrangement of CT and CB.
-
8/14/2019 Ch6 Power System Slide09
30/70
Primary & Back-up Protection
Primary protection is the protection
provided by each zone to its elements.
However, some component of a zoneprotection scheme fail to operate.
Back-up protection is provided which
take over only in the event of primaryprotection failure.
-
8/14/2019 Ch6 Power System Slide09
31/70
Example
a) Consider the power system shown below, with the
generating source beyond buses 1, 3 and 4. What
are the zones of protection in which the system
should be divided? Which circuit breakers will openfor faults at P1 and P2?
1
2
3
4
P1
B
P2A C
-
8/14/2019 Ch6 Power System Slide09
32/70
Fault at P1 = A, B, C
Fault at P2 = A, B, C,D, E
1
2
3
4
P1
B
P2A C
D
E
-
8/14/2019 Ch6 Power System Slide09
33/70
Example
a) If three circuits breakers are added at the tap
point 2, how would the zones of protection be
modified? Which circuit breakers will operate for
fault at P1 and P2 under these conditions?1
2
3
4
P1
B
P2A C
-
8/14/2019 Ch6 Power System Slide09
34/70
1
23
4
P1
B
P2A C
D
E
H
F G
Fault at P1 = A, F
Fault at P2 = C,D,E,G
-
8/14/2019 Ch6 Power System Slide09
35/70
Zone Discrimination
A system as shown with relays and breakers marked.A single fault has resulted in the operation ofbreakers B
1, B
2, B
3and B
4.Identify the location of the
fault Answer:
Fault in the overlap zone at breaker B2 as shown
-
8/14/2019 Ch6 Power System Slide09
36/70
Back-up Protection
1.Duplicate Primary
Provide primary protection when the primary-relaying equipment is out of service for maintenance
or repair Disconnect when primary relaying operates correctly
Operate with sufficient time delay (coordinationtime delay) if primary not operate
When short circuit occur, both primary and back-upstart to operate, but if primary is operate, then theback-up will reset.
-
8/14/2019 Ch6 Power System Slide09
37/70
Back-up Protection
2.Remote Back-up
located outside boundary of Zone of Protection
-
8/14/2019 Ch6 Power System Slide09
38/70
Example
Fault Primary Back-up
K C, D, E A, B, F
-
8/14/2019 Ch6 Power System Slide09
39/70
Example
Fault Primary Back-up
Line E, F C, D, E, F, G, H A, B, I, J
-
8/14/2019 Ch6 Power System Slide09
40/70
Transducers
Also known as Instrument Transformer
Use to reduce abnormal current & voltagelevels and transmit input signals to therelays of a protection system.
Why do we need transducer: The lower level input to the relays ensures that
the physical hardware used to construct therelays will be small & cheap
The personnel who work with the relays will beworking in a safe environment.
-
8/14/2019 Ch6 Power System Slide09
41/70
Transducers
Current and Voltage Transformers
Correct connection of CTs and VTs to the
protection is important directional,distance, phase comparison and
differential protections.
Earth CT and VT circuits at one point only;
-
8/14/2019 Ch6 Power System Slide09
42/70
VT and CT Schematic
-
8/14/2019 Ch6 Power System Slide09
43/70
Voltage Transformers
VT is considered to be sufficiently accurate.
It is generally modeled as an ideal transformer.
VT secondary connected to voltage-sensingdevice with infinite impedance.
-
8/14/2019 Ch6 Power System Slide09
44/70
Voltage Transformers
Types of VTs
Electromagnetic VT
Capacitive VT
Busbar VTs
Special consideration needed when used for line protection
LV application(12 kV or lower)
Industry standard transformer with a primary winding at a
system voltage and secondary winding at 67 V(line-to-neutral) and
116 V(line-to-line).
-
8/14/2019 Ch6 Power System Slide09
45/70
Voltage Transformers
-
8/14/2019 Ch6 Power System Slide09
46/70
Voltage Transformers
Voltage/Potential
Transformer
(VT/PT)
-
8/14/2019 Ch6 Power System Slide09
47/70
Voltage Transformers
-
8/14/2019 Ch6 Power System Slide09
48/70
Voltage Transformers
-
8/14/2019 Ch6 Power System Slide09
49/70
Voltage Transformers
HV and EHV
Capacitor-coupled VT (CVT)
C1 & C2 are adjusted, so that a few kVs ofvoltage is obtains across C
2
Then, stepped down by T
VTs must be fused or protected by MCB.
-
8/14/2019 Ch6 Power System Slide09
50/70
Voltage Transformers
-
8/14/2019 Ch6 Power System Slide09
51/70
Voltage Transformers
VT ratios:
ratio of the high voltage/secondary
voltage1:1 2:1 2.5:1 4:1
5:1 20:1 40:1 60:1
80:1 100:1 200:1 300:1400:1 600:1 800:1 1000:1
2000:1 3000:1 4500:1
-
8/14/2019 Ch6 Power System Slide09
52/70
Current Transformers
CT is an instrument transformer that is used
to supply a reduced value of current to
meters, protective relays, and other
instruments.
The primary winding consist of a single turn
which is the power conductor itself.
CT secondary is connected to a current-sensing device with zero impedance.
-
8/14/2019 Ch6 Power System Slide09
53/70
Current Transformers
CTs ratio(secondary current rating is 5A)
50:5 100:5 150:5 200:5
250:5 300:5 400:5 450:5500:5 600:5 800:5 900:5
1000:5 1200:5
CTs also available with the secondary ratingof 1A
-
8/14/2019 Ch6 Power System Slide09
54/70
Current Transformers
-
8/14/2019 Ch6 Power System Slide09
55/70
Current Transformers
-
8/14/2019 Ch6 Power System Slide09
56/70
Reclosers and Fuses
Automatic reclosers are commonly used fordistribution circuit protection.
Recloser: self-controlled device for automatically
interrupting and reclosing an AC circuit with presetsequence of openings and reclosures
Have built-in control to clear temporary faults andrestores service with momentary outages.
Disadvantages: increase hazard when circuit is physically contacted by
people.
Recloser should be locked out during live-line maintenance.
-
8/14/2019 Ch6 Power System Slide09
57/70
Reclosers and Fuses
1. An upstream fuse/relay
has detected a fault
2. Downstream systemisolated by fuse or
breaker
3. Automatic re-closing
after delay successful iffault not permanent
-
8/14/2019 Ch6 Power System Slide09
58/70
Relays
Discriminate between normal operatingand fault conditions.
Type of Relays Magnitude Relay
Directional Relay
Distance/Ratio Relay
Differential Relay
Pilot Relay
-
8/14/2019 Ch6 Power System Slide09
59/70
Magnitude Relays
Also called as Overcurrent Relay
Response to the magnitude of input quantities ie.current.
Energize CB trip coil when the fault current magnitudeexceeds a predetermined value or trips when a currentrises above a set point (pick-up current).
If it is less than the set point value, the relay remainsopen, blocking the trip coil.
Time-delay Overcurrent Relay also have the same
operating method but with an intentional time-delay.
-
8/14/2019 Ch6 Power System Slide09
60/70
Directional Relays
Responds to fault only in one direction, either to theleft or to the right of its location
Operation depends upon the direction (lead or lag) ofthe fault current with respect to a reference voltage.
The directional element of these relays checks thephase angle between the current and voltage of onephase, and allows the overcurrent unit to operate ifthis phase angle indicates current in the reversedirection.
-
8/14/2019 Ch6 Power System Slide09
61/70
Ratio Relays
Operate for certain relations between the
magnitudes of voltage, current and the phase angle
between them.
Measures the distance between the relay locationand the point of fault, in term of impedance,
reactance and admittance.
Respond to the ratio of two phasor quantities as
example Voltage and Current (Z = V/R) Also called impedance or distance relay
-
8/14/2019 Ch6 Power System Slide09
62/70
Differential Relays
Respond to the vector difference between two currents within
the zone protection determined by the location of CTs.
Not suitable for transmission-line protection because the
terminals of a line are separated by too great a distance to
interconnect the CT secondaries.
For the protection of generators, transformers, buses,
Most differential-relay applications are of the current-
differential type.
-
8/14/2019 Ch6 Power System Slide09
63/70
Differential Relays
Fault occur at X
Suppose that current flows through the primary circuit either toa load or to a short circuit located at X.
If the two current transformers have the same ratio, and are
properly connected, their secondary currents will merelycirculate between the two CTs as shown by the arrows, and nocurrent will flow through the differential relay.
Relay
-
8/14/2019 Ch6 Power System Slide09
64/70
A flow on one side only, or even some currentflowing out of one side while a larger currententers the other side, will cause a differentialcurrent.
In other words, the differential-relay currentwill be proportional to the vector differencebetween the currents entering and leaving theprotected circuit; and, if the differentialcurrent exceeds the relays pickup value, therelay
Relay
Differential Relays
-
8/14/2019 Ch6 Power System Slide09
65/70
Differential Relays
When a short circuit develop anywhere betweenthe two CTs.
If current flows to the short circuit from bothsides as shown, the sum of the CT secondarycurrents will flow through the differential relay.
It is not necessary that short-circuit currentflow to the fault from both sides to causesecondary current to flow through the
differential relay.
Relay
-
8/14/2019 Ch6 Power System Slide09
66/70
Pilot Relays
The term pilot means that between the
ends of the transmission line there is an
interconnecting channel of some sort overwhich information can be conveyed.
Use communicated information from
remote sites as input signals.
-
8/14/2019 Ch6 Power System Slide09
67/70
Pilot Relays
Transmitting fault signals from a remote zone
boundary to relays at the terminals of a long
TL
Pilot relaying provides primary protection only;back-up protection must be provided by
supplementary relaying.
Type : wire pilot, carrier-current pilot and
microwave pilot.
-
8/14/2019 Ch6 Power System Slide09
68/70
Pilot Relays
1 2
A B C
Station 1 consist of meter for reading
voltage, current and power factor.
Distance relay, tell the different between
fault at A (middle) and B (end) by knowingthe impedance characteristic per unit length
of the line.
ZA ZB
-
8/14/2019 Ch6 Power System Slide09
69/70
Pilot Relays
1 2
A B C
Could not possibly distinguish between fault Band C because impedance would be so small-
Mistake in tripping CB for fault B or C
Solution- indication from station B, when the
phase angle of the current at S-B(with respectto current A) is different by approximately 180o
from it value for fault in the line section AB.
-
8/14/2019 Ch6 Power System Slide09
70/70
Pilot Relays
(with respect to current A) is
different by approximately 180o
from it value for fault in the line
section
(with respect to current A) isnot different in degree from it
value for fault in the line
section
1 2
B CA