ch6 power system slide09

Upload: hafiz-azman

Post on 30-May-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/14/2019 Ch6 Power System Slide09

    1/70

    BEE3133

    Electrical Power SystemsChapter 6: System Protection

    Rahmatul Hidayah Salimin

  • 8/14/2019 Ch6 Power System Slide09

    2/70

    Introduction

    System Protection: the equipment use

    to detect and isolate the faulty section

    from the system automatically.

  • 8/14/2019 Ch6 Power System Slide09

    3/70

    Introduction

    Short circuit occur when equipmentinsulation fails due to system overvoltagescaused by:

    Lightning or switching surges Flashover line-line (caused by wind) Flashover to tree

    Insulation contamination by dirt/salt Mechanical failure

    Cable insulation failure

    Natural causes Tower/pole or conductor falls Objects fall on conductors

  • 8/14/2019 Ch6 Power System Slide09

    4/70

    Introduction

    Short circuit currents can be several ordersof magnitude larger than normal operatingcurrents

    If it is allowed to persist, may cause: Damage to the equipment due to heavy currents,

    unbalanced current, or low voltage produces bythe short circuit

    Fire and explosion effect equipment/people

    Disruption of service in the entire power systemarea

  • 8/14/2019 Ch6 Power System Slide09

    5/70

    Introduction

    Careful design, operation and

    maintenance of system protection can

    minimize the occurrence of shortcircuit but cannot eliminate them.

  • 8/14/2019 Ch6 Power System Slide09

    6/70

    Fault Currents and Voltages

  • 8/14/2019 Ch6 Power System Slide09

    7/70

    Function of System Protection

    Cause the prompt removal from service of anyelements of power system when it suffers ashortcircuit, or when it start to operate in any abnormal

    manner that might cause damage or otherwiseinterfere with the effective operation of the rest ofthe system.

    Provide indication of the locationand type of failureso that the data can be used to assist in expediting

    repair and analyzing the effectiveness of fault-prevention and mitigation features.

  • 8/14/2019 Ch6 Power System Slide09

    8/70

    Function of System Protection

    Why do we need system protection:

    Detect fault

    Isolate faulted component

    Restore faulted component

    Aims:

    Continued supply for rest of system Protect faulted part from damage

  • 8/14/2019 Ch6 Power System Slide09

    9/70

    Types of Protection

    A Fuses For LV Systems, Distribution Feeders and

    Transformers, VTs, Auxiliary Supplies

    B - Over current and earth fault Widely used in All Power Systems

    Non-Directional Directional

  • 8/14/2019 Ch6 Power System Slide09

    10/70

    Types of Protection

    C - Differential For Distribution Feeders, Busbars,

    Transformers, Generators etc

    High Impedance

    Low Impedance

    Restricted E/F

    Biased

    Pilot Wire

  • 8/14/2019 Ch6 Power System Slide09

    11/70

    Types of Protection

    D - Distance For Transmission and Sub-transmission Lines

    and Distribution Feeders, Also used as back-up protection for

    transformers and generators withoutsignaling with signaling to provide unitprotection e.g.:

    Time-stepped distance protection Phase comparison for transmission lines Directional comparison for transmission lines

  • 8/14/2019 Ch6 Power System Slide09

    12/70

    Types of Protection

    E - Miscellaneous:

    Under and over voltage

    Under and over frequency A special relay for generators, transformers, motors

    etc.

    Control relays: auto-reclose, tap change control, etc.

    Tripping and auxiliary relays

  • 8/14/2019 Ch6 Power System Slide09

    13/70

    Design Criteria/Characteristics

    Simplicity

    Economy

    Speed

    Sensitivity

    Selectivity

    Reliability

  • 8/14/2019 Ch6 Power System Slide09

    14/70

    Design Criteria/Characteristics

    Reliability Operate dependably and in healthy operating

    condition when fault conditions occur, even after

    remaining idle for months or years. Selectivity

    Clearly discriminate between normal andabnormal system condition to avoid unnecessary,false trips.

    Sensitivity Ability to distinguish the fault condition, although

    the different between fault and normal conditionis small.

  • 8/14/2019 Ch6 Power System Slide09

    15/70

    Design Criteria/Characteristics

    Speed Fault at any point in the system must be

    detected and isolated rapidly to minimize fault

    duration and equipment damage. Any intentionaltime delays should be precise.

    Economy Provide maximum protection at minimum cost

    Simplicity Minimize protection equipment and circuitry

    http://slide09%20chapter06.ppt/http://slide09%20chapter06.ppt/
  • 8/14/2019 Ch6 Power System Slide09

    16/70

    Economic Factor

    Total cost should take account of :

    Relays, schemes and associated panels and panel wiring

    Setting studies

    Commissioning

    CTs and VTs

    Maintenance and repairs to relays

    Damage repair if protection fails to operate

    Lost revenue if protection operates unnecessarily

  • 8/14/2019 Ch6 Power System Slide09

    17/70

    Economic Factor

    The cost of protection is equivalent to an insurance policy

    against damage to plant, and loss of supply and customer

    goodwill. Acceptable cost is based on a balance of economics and

    technical factors. Cost of protection should be balanced

    against the cost of potential hazards.

    There is an economic limit on what can be spent.

    MINIMUM COST :Must ensure that all faulty equipment is

    isolated by protection.

  • 8/14/2019 Ch6 Power System Slide09

    18/70

    Relationship between reliability of supply, its

    value and cost to the consumer

  • 8/14/2019 Ch6 Power System Slide09

    19/70

    System Protection Components

    Transducer / Instrument Transformer

    Relay

    Circuit Breaker

  • 8/14/2019 Ch6 Power System Slide09

    20/70

    System Protection Components

    Function:

    Transducers/Instrument Transformers Provide low current and voltage, standardized levels suitable for

    the relays operation. Relays

    Discriminate between normal operating and fault conditions.

    When current exceed a specified value relay will be operated andcause the trip coil of CB to be energized/open their contact.

    Circuit Breakers Open the line

  • 8/14/2019 Ch6 Power System Slide09

    21/70

    System Protection Components

  • 8/14/2019 Ch6 Power System Slide09

    22/70

    System Protection Components

  • 8/14/2019 Ch6 Power System Slide09

    23/70

    System Protection Flow

    RelayTransducer Fault

    OccurCircuit

    Breaker

    FaultClear

    voltage or current rise from normal condition

    voltage/current is reduced to match with relay rating

    activate circuit breaker

    circuit isolation

  • 8/14/2019 Ch6 Power System Slide09

    24/70

    Zones of Protection

    For fault anyway within the zone, the

    protection system responsible to

    isolate everything within the zone fromthe rest of the system.

    Isolation done by CB

    Must isolate only the faulty equipmentor section

  • 8/14/2019 Ch6 Power System Slide09

    25/70

    Zones of Protection

    Zones are defined for:

    Generators

    Transformers

    Buses

    Transmission and distribution lines

    Motors

  • 8/14/2019 Ch6 Power System Slide09

    26/70

    Zones of Protection

  • 8/14/2019 Ch6 Power System Slide09

    27/70

    Zones of Protection

    Characteristics:

    Zones are overlapped.

    Circuit breakers are located in the overlapregions.

    For a fault anywhere in a zone, all circuit

    breakers in that zone open to isolate thefault.

    http://../Owner/Desktop/Slide09%20Chapter06.ppthttp://../Owner/Desktop/Slide09%20Chapter06.ppt
  • 8/14/2019 Ch6 Power System Slide09

    28/70

    Overlapped of Protection

    No blind spot:

    Neighboring zones are overlapped to avoid

    the possibility of unprotected areas

    Use overlapping CTs:

    Isolation done by CB. Thus, it must be

    inserted in each overlap region to identifythe boundary of protective zones.

  • 8/14/2019 Ch6 Power System Slide09

    29/70

    Overlapped of Protection

    Overlap accomplish by having 2 sets of

    instrument transformers and relays for each

    CB. Achieved by the arrangement of CT and CB.

  • 8/14/2019 Ch6 Power System Slide09

    30/70

    Primary & Back-up Protection

    Primary protection is the protection

    provided by each zone to its elements.

    However, some component of a zoneprotection scheme fail to operate.

    Back-up protection is provided which

    take over only in the event of primaryprotection failure.

  • 8/14/2019 Ch6 Power System Slide09

    31/70

    Example

    a) Consider the power system shown below, with the

    generating source beyond buses 1, 3 and 4. What

    are the zones of protection in which the system

    should be divided? Which circuit breakers will openfor faults at P1 and P2?

    1

    2

    3

    4

    P1

    B

    P2A C

  • 8/14/2019 Ch6 Power System Slide09

    32/70

    Fault at P1 = A, B, C

    Fault at P2 = A, B, C,D, E

    1

    2

    3

    4

    P1

    B

    P2A C

    D

    E

  • 8/14/2019 Ch6 Power System Slide09

    33/70

    Example

    a) If three circuits breakers are added at the tap

    point 2, how would the zones of protection be

    modified? Which circuit breakers will operate for

    fault at P1 and P2 under these conditions?1

    2

    3

    4

    P1

    B

    P2A C

  • 8/14/2019 Ch6 Power System Slide09

    34/70

    1

    23

    4

    P1

    B

    P2A C

    D

    E

    H

    F G

    Fault at P1 = A, F

    Fault at P2 = C,D,E,G

  • 8/14/2019 Ch6 Power System Slide09

    35/70

    Zone Discrimination

    A system as shown with relays and breakers marked.A single fault has resulted in the operation ofbreakers B

    1, B

    2, B

    3and B

    4.Identify the location of the

    fault Answer:

    Fault in the overlap zone at breaker B2 as shown

  • 8/14/2019 Ch6 Power System Slide09

    36/70

    Back-up Protection

    1.Duplicate Primary

    Provide primary protection when the primary-relaying equipment is out of service for maintenance

    or repair Disconnect when primary relaying operates correctly

    Operate with sufficient time delay (coordinationtime delay) if primary not operate

    When short circuit occur, both primary and back-upstart to operate, but if primary is operate, then theback-up will reset.

  • 8/14/2019 Ch6 Power System Slide09

    37/70

    Back-up Protection

    2.Remote Back-up

    located outside boundary of Zone of Protection

  • 8/14/2019 Ch6 Power System Slide09

    38/70

    Example

    Fault Primary Back-up

    K C, D, E A, B, F

  • 8/14/2019 Ch6 Power System Slide09

    39/70

    Example

    Fault Primary Back-up

    Line E, F C, D, E, F, G, H A, B, I, J

  • 8/14/2019 Ch6 Power System Slide09

    40/70

    Transducers

    Also known as Instrument Transformer

    Use to reduce abnormal current & voltagelevels and transmit input signals to therelays of a protection system.

    Why do we need transducer: The lower level input to the relays ensures that

    the physical hardware used to construct therelays will be small & cheap

    The personnel who work with the relays will beworking in a safe environment.

  • 8/14/2019 Ch6 Power System Slide09

    41/70

    Transducers

    Current and Voltage Transformers

    Correct connection of CTs and VTs to the

    protection is important directional,distance, phase comparison and

    differential protections.

    Earth CT and VT circuits at one point only;

  • 8/14/2019 Ch6 Power System Slide09

    42/70

    VT and CT Schematic

  • 8/14/2019 Ch6 Power System Slide09

    43/70

    Voltage Transformers

    VT is considered to be sufficiently accurate.

    It is generally modeled as an ideal transformer.

    VT secondary connected to voltage-sensingdevice with infinite impedance.

  • 8/14/2019 Ch6 Power System Slide09

    44/70

    Voltage Transformers

    Types of VTs

    Electromagnetic VT

    Capacitive VT

    Busbar VTs

    Special consideration needed when used for line protection

    LV application(12 kV or lower)

    Industry standard transformer with a primary winding at a

    system voltage and secondary winding at 67 V(line-to-neutral) and

    116 V(line-to-line).

  • 8/14/2019 Ch6 Power System Slide09

    45/70

    Voltage Transformers

  • 8/14/2019 Ch6 Power System Slide09

    46/70

    Voltage Transformers

    Voltage/Potential

    Transformer

    (VT/PT)

  • 8/14/2019 Ch6 Power System Slide09

    47/70

    Voltage Transformers

  • 8/14/2019 Ch6 Power System Slide09

    48/70

    Voltage Transformers

  • 8/14/2019 Ch6 Power System Slide09

    49/70

    Voltage Transformers

    HV and EHV

    Capacitor-coupled VT (CVT)

    C1 & C2 are adjusted, so that a few kVs ofvoltage is obtains across C

    2

    Then, stepped down by T

    VTs must be fused or protected by MCB.

  • 8/14/2019 Ch6 Power System Slide09

    50/70

    Voltage Transformers

  • 8/14/2019 Ch6 Power System Slide09

    51/70

    Voltage Transformers

    VT ratios:

    ratio of the high voltage/secondary

    voltage1:1 2:1 2.5:1 4:1

    5:1 20:1 40:1 60:1

    80:1 100:1 200:1 300:1400:1 600:1 800:1 1000:1

    2000:1 3000:1 4500:1

  • 8/14/2019 Ch6 Power System Slide09

    52/70

    Current Transformers

    CT is an instrument transformer that is used

    to supply a reduced value of current to

    meters, protective relays, and other

    instruments.

    The primary winding consist of a single turn

    which is the power conductor itself.

    CT secondary is connected to a current-sensing device with zero impedance.

  • 8/14/2019 Ch6 Power System Slide09

    53/70

    Current Transformers

    CTs ratio(secondary current rating is 5A)

    50:5 100:5 150:5 200:5

    250:5 300:5 400:5 450:5500:5 600:5 800:5 900:5

    1000:5 1200:5

    CTs also available with the secondary ratingof 1A

  • 8/14/2019 Ch6 Power System Slide09

    54/70

    Current Transformers

  • 8/14/2019 Ch6 Power System Slide09

    55/70

    Current Transformers

  • 8/14/2019 Ch6 Power System Slide09

    56/70

    Reclosers and Fuses

    Automatic reclosers are commonly used fordistribution circuit protection.

    Recloser: self-controlled device for automatically

    interrupting and reclosing an AC circuit with presetsequence of openings and reclosures

    Have built-in control to clear temporary faults andrestores service with momentary outages.

    Disadvantages: increase hazard when circuit is physically contacted by

    people.

    Recloser should be locked out during live-line maintenance.

  • 8/14/2019 Ch6 Power System Slide09

    57/70

    Reclosers and Fuses

    1. An upstream fuse/relay

    has detected a fault

    2. Downstream systemisolated by fuse or

    breaker

    3. Automatic re-closing

    after delay successful iffault not permanent

  • 8/14/2019 Ch6 Power System Slide09

    58/70

    Relays

    Discriminate between normal operatingand fault conditions.

    Type of Relays Magnitude Relay

    Directional Relay

    Distance/Ratio Relay

    Differential Relay

    Pilot Relay

  • 8/14/2019 Ch6 Power System Slide09

    59/70

    Magnitude Relays

    Also called as Overcurrent Relay

    Response to the magnitude of input quantities ie.current.

    Energize CB trip coil when the fault current magnitudeexceeds a predetermined value or trips when a currentrises above a set point (pick-up current).

    If it is less than the set point value, the relay remainsopen, blocking the trip coil.

    Time-delay Overcurrent Relay also have the same

    operating method but with an intentional time-delay.

  • 8/14/2019 Ch6 Power System Slide09

    60/70

    Directional Relays

    Responds to fault only in one direction, either to theleft or to the right of its location

    Operation depends upon the direction (lead or lag) ofthe fault current with respect to a reference voltage.

    The directional element of these relays checks thephase angle between the current and voltage of onephase, and allows the overcurrent unit to operate ifthis phase angle indicates current in the reversedirection.

  • 8/14/2019 Ch6 Power System Slide09

    61/70

    Ratio Relays

    Operate for certain relations between the

    magnitudes of voltage, current and the phase angle

    between them.

    Measures the distance between the relay locationand the point of fault, in term of impedance,

    reactance and admittance.

    Respond to the ratio of two phasor quantities as

    example Voltage and Current (Z = V/R) Also called impedance or distance relay

  • 8/14/2019 Ch6 Power System Slide09

    62/70

    Differential Relays

    Respond to the vector difference between two currents within

    the zone protection determined by the location of CTs.

    Not suitable for transmission-line protection because the

    terminals of a line are separated by too great a distance to

    interconnect the CT secondaries.

    For the protection of generators, transformers, buses,

    Most differential-relay applications are of the current-

    differential type.

  • 8/14/2019 Ch6 Power System Slide09

    63/70

    Differential Relays

    Fault occur at X

    Suppose that current flows through the primary circuit either toa load or to a short circuit located at X.

    If the two current transformers have the same ratio, and are

    properly connected, their secondary currents will merelycirculate between the two CTs as shown by the arrows, and nocurrent will flow through the differential relay.

    Relay

  • 8/14/2019 Ch6 Power System Slide09

    64/70

    A flow on one side only, or even some currentflowing out of one side while a larger currententers the other side, will cause a differentialcurrent.

    In other words, the differential-relay currentwill be proportional to the vector differencebetween the currents entering and leaving theprotected circuit; and, if the differentialcurrent exceeds the relays pickup value, therelay

    Relay

    Differential Relays

  • 8/14/2019 Ch6 Power System Slide09

    65/70

    Differential Relays

    When a short circuit develop anywhere betweenthe two CTs.

    If current flows to the short circuit from bothsides as shown, the sum of the CT secondarycurrents will flow through the differential relay.

    It is not necessary that short-circuit currentflow to the fault from both sides to causesecondary current to flow through the

    differential relay.

    Relay

  • 8/14/2019 Ch6 Power System Slide09

    66/70

    Pilot Relays

    The term pilot means that between the

    ends of the transmission line there is an

    interconnecting channel of some sort overwhich information can be conveyed.

    Use communicated information from

    remote sites as input signals.

  • 8/14/2019 Ch6 Power System Slide09

    67/70

    Pilot Relays

    Transmitting fault signals from a remote zone

    boundary to relays at the terminals of a long

    TL

    Pilot relaying provides primary protection only;back-up protection must be provided by

    supplementary relaying.

    Type : wire pilot, carrier-current pilot and

    microwave pilot.

  • 8/14/2019 Ch6 Power System Slide09

    68/70

    Pilot Relays

    1 2

    A B C

    Station 1 consist of meter for reading

    voltage, current and power factor.

    Distance relay, tell the different between

    fault at A (middle) and B (end) by knowingthe impedance characteristic per unit length

    of the line.

    ZA ZB

  • 8/14/2019 Ch6 Power System Slide09

    69/70

    Pilot Relays

    1 2

    A B C

    Could not possibly distinguish between fault Band C because impedance would be so small-

    Mistake in tripping CB for fault B or C

    Solution- indication from station B, when the

    phase angle of the current at S-B(with respectto current A) is different by approximately 180o

    from it value for fault in the line section AB.

  • 8/14/2019 Ch6 Power System Slide09

    70/70

    Pilot Relays

    (with respect to current A) is

    different by approximately 180o

    from it value for fault in the line

    section

    (with respect to current A) isnot different in degree from it

    value for fault in the line

    section

    1 2

    B CA