Chapter… 3

CFD Analysis of Radiator

3.1 COMPUTATIONAL FLUID DYNAMICS MODELING

Computational fluid dynamics modeling was developed to predict the characteristics and

performance of flow systems. Overall performance is predicted by breaking the flow system

down into an appropriate number of finite volumes or areas, referred to as cells, and solving

expressions representing the continuity, momentum, and energy equations for each cell. The

process of breaking down the system domain into finite volumes or areas is known as mesh

generation. The number of cells in a mesh varies depending on the level of accuracy required, the

complexity of the system, and the models used. Equations solve for flow (x, y, and z velocities),

energy (heat fluxes and temperatures), chemical reactions (reaction kinetics and species

concentrations), and pressure based on various simplifications and/or assumptions (Anderson J.

D. 1995). Some simplifications and assumptions are discussed below. If performed correctly,

CFD modeling can accurately predict the performance of an entire system.

3.2 MODELING OBJECTIVE

The primary goal of this CFD analysis is to predict a flow behavior of radiator with

supporting velocity profile. CFD simulation is carried in 2 phases, viz.

Phase 1: Geometry and Meshing

1) Geometry modeling will be done in Ansys Workbench

2) Meshing will be done in Ansys Mesher.

a. Unstructured mesh is used for the analysis

b. Fine mesh at specific location to capture the flow behavior.

Phase 2: Steady State Simulation

1) Steady state incompressible simulation is perform for different flow and atmospheric

condition

2) Flow and Heat transfer will be solved considering different working scenario

3) Appropriate turbulence model will be used depending on the Reynolds

Number

1) Flow rates and pressure drops will be observed and verified

3.3 NUMERICAL MODEL DETAILS

The commercial CFD Code Ansys Fluent was used as preprocessor for solving the flow

physics. The computational Domain had to be represented as a finite volume model. Volume

mesh is generated in Ansys Mesher and refinement is done at specific location to capture the

flow behavior. Unstructured volume grid with 1375000 tetra-hydrel cells is used for the

simulation. In Fluent putting appropriate scaling factors for scaling the mesh/geometry, and

setting up the appropriate turbulence model, fluid properties, solver controls, convergence

monitors.

All simulations were performed using the Standard k-e turbulence model. For stability of the

solution the linear upwind scheme was used in the beginning, once stabilized a second order

upwind differencing scheme was used.

3.3.1 Boundary Conditions

Inlet and Outlets: For the inlet and outlet the static pressure is specified, which is fixed to

zero. Side and top walls, pressure outlet is considered. Porous Medium, the radiator is modeled

as porous medium to account for the pressure drop in the radiator.

Multiple Reference Frame (MRF) Zone, in a steady-state approximation in which individual

cell zones can be assigned different rotational speeds. The flow in fan zone is solved using the

moving reference frame equations.

Fig. 3.1 : Fluid domain for the radia

Extended fluid domain is considered for the CFD analysis to capture the fluid behavior. The

domain away from the radiator is open to atmosphere. The length of the domain is decided so

that the flow near the fan and inside the radiator is no

Simplified radiator model shown above have fan, shroud and radiator with tubes. Radiator

fan is rotating with different rpm is consider in the analysis.

Fig. 3.1 : Fluid domain for the radiator analysis

Extended fluid domain is considered for the CFD analysis to capture the fluid behavior. The

domain away from the radiator is open to atmosphere. The length of the domain is decided so

that the flow near the fan and inside the radiator is not getting affected.

Simplified radiator model shown above have fan, shroud and radiator with tubes. Radiator

fan is rotating with different rpm is consider in the analysis.

Extended fluid domain is considered for the CFD analysis to capture the fluid behavior. The

domain away from the radiator is open to atmosphere. The length of the domain is decided so

Simplified radiator model shown above have fan, shroud and radiator with tubes. Radiator

3.4 RESULTS AT 1500 RPM

1. Velocity pattern before Radiator

2. Velocity pattern at the center of Radiator

Fig. 3.2: Velocity contour at different location

In Fig. 3.2 velocities before radiator and at the central plane of radiator is shown for 1500

rpm speed of fan before radiator.

1. Velocity plot along horizontal and vertical line

2. Velocity plot along diagonal lines

Fig. 3.3 : Velocity plot is done at different location

Graph 1 shows velocity plot for horizontal and vertical line before radiator and in Graph-2

plotting is done for diagonal lines.

1. Velocity plot comparison with experimental

2. Velocity plot comparison with experimental

Fig. 3.4: Velocity plot comparison for CFD and Experimental at different location

CFD velocity result and experimental value are compared at different location in Fig. 3.4. In

the graph L1 to L8 represent the line location as per the Fig. 3.4. Velocity trend is near about

same for both CFD and experimental but the variation has been seen because of many

assumption and measurement constraints. Radiator domain in CFD has tubes and remaining as a

fluid domain, but in actual fins act as a resistance to the flow.

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 0.05 0.1 0.15

Ve

loci

ty (

m/s

)

Distance (m)

L 1

L 2

L 3

L 4

CFD

L1CFD

L2

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

0 0.1 0.2

Ve

loci

ty (

m/s

)

Distance (m)

L5

L6

L7

L8

CFD L5

CFD L6

CFD L7

CFD L8

3.5 RESULTS AT 1800 RPM

1. Velocity pattern before Radiator

2.Velocity pattern at the center of Radiator

Fig. 3.5 Velocity contour at different location

In Fig. 3.5 velocities before radiator and at the central plane of radiator is shown for 1800 rpm speed of fan before radiator.

1. Velocity plot along horizontal and vertical line

2. Velocity plot along diagonal lines

Fig. 3.6 : Velocity plot is done at different location

Graph 1 shows velocity plot for horizontal and vertical line before radiator and in graph-2

plotting is done for diagonal lines.

3.6 RESULTS AT 2000 RPM

1. Velocity pattern before Radiator

2. Velocity pattern at the center of Radiator

Fig. 3.7 : Velocity contour at different location

In Fig 3.7 velocities before radiator and at the central plane of radiator is shown for 2000

rpm speed of fan before radiator. High velocity region is visible compare to lower rpm.

1. Velocity plot along horizontal and vertical line

2. Velocity plot along diagonal lines

Fig. 3.8 : Velocity plot is done at different location

Graph 1 shows velocity plot for horizontal and vertical line before radiator and in graph-2 plotting is done for diagonal lines.

3.7 RESULTS AT 1500 RPM AND RADIATOR AS POROUS DOMAIN

1. Radiator model without tubes

2. Velocity pattern before and after Radiator

Fig. 3.9 Radiator model and velocity contour at different location

In Fig. 3.9 radiator model with porous domain is consider and in the second plot velocities

before and after radiator is shown for 1500 rpm speed.

1. Velocity plot along horizontal and vertical line

2. Velocity plot along diagonal lines

Fig. 3.10 Velocity plot is done at different location before radiator

Graph 1 shows velocity plot for horizontal and vertical line before radiator and in graph-2

plotting is done for diagonal lines.

1. Velocity plot along horizontal and vertical line

2. Velocity plot along diagonal lines

Fig. 3.11 : Velocity plot is done at different location after radiator

Graph 1 shows velocity plot for horizontal and vertical line after radiator and in graph-2 plotting is done for diagonal lines.

3.8 RESULTS AT 1500 RPM AND RADIATOR AS POROUS DOMAIN WITH MODIFICATION IN SHAPE

1. Radiator model without tubes

2. Radiator model side view

Fig. 3.12 Proposed radiator model

Proposed modified radiator model is shown in Fig.3.12 with porous domain. At the center radiator thickness is less compared to peripheral thickness.

1. Velocity pattern before and after Radiator

2. Velocity contour at side view of Radiator

Fig. 3.13 : Velocity contour at different location

In Fig. 3.13 radiator velocity before and after radiator is shown for 1500 rpm speed.

1. Velocity plot along horizontal and vertical line

2. Velocity plot along diagonal lines

Fig. 3.14 : Velocity plot is done at different location before radiator

Graph 1 shows velocity plot for horizontal and vertical line before radiator and in graph-2

plotting is done for diagonal lines.

1. Velocity plot along horizontal and vertical line

2. Velocity plot along diagonal lines

Fig. 3.15 : Velocity plot is done at different location after radiator

Graph 1 shows velocity plot for horizontal and vertical line after radiator and in graph-2

plotting is done for diagonal lines.

3.9 RESULTS & DISCUSSION

CFD simulation for different revolutions of fan is shown in Figs.3.2, 3.5, 3.7, 3.9, 3.13, it can be observed that,

1. Velocity of air increases with the increase in rpm of radiator fan.

2. CFD and experimental velocity values are compared at different locations in Fig. 3.4 for 1500 rpm.

3. Fins are not considered in the simulation. It will also create some resistance to the flow. Radiator domain in CFD has tubes and remaining as a fluid domain.

4. Variations in the results obtained by CFD and experimentation are observed near about 15 to 20% at different locations.

5. It can be observed that average velocity of air entering before the radiator inlet at the center core is almost zero, and it increases towards the periphery, because of change in shape. (For proposed radiator with porous zone as shown in fig. 3.12)

6. Shape optimization can be done to improve the radiator efficiency i.e.,

i) Smaller fins are provided at the centre and length of the fins increases towards periphery.

ii) Low velocity zones are created in the corners, hence eliminate corners and have circular radiator for optimum efficiency.

7. The new proposed radiator shape with porous zone is shown fig 3.12.

8. It is also observed from CFD analysis that, velocity of air increases from centre to extreme and further it remains constant.

9. Further it can be concluded that the air entering in the radiator, with new proposed

design possesses almost constant velocity at the exit.

3.10 TEST SET UP FOR TESTING

Fig.3.16 : Test Set Up

Figure 3.16 shows the schematic diagram of experimental setup used. It consists of heaters,

radiator, DC motor, anemometers, rotameters, infra-red temperature measuring gun, etc.

Heaters are used to supply hot water to about 70 to 80 � C to the radiator. Radiator is made

for Maruti Alto design conditions which can be changed. DC motor is used to have the variable

speed of the fan. Velocity of the air is measured at different points by using anemometer. Flow

rate of water is measured by rotameter. Temperature at various points on the radiator is measured

with the help of infra-red temperature measuring gun.

3.11 ACTUAL PHOTOGRAPHS OF EXPERIMENTAL SET UP

Fig. 3.17.1 Experimental Setup

Fig. 3.17.2 Experimental Setup

Figure 3.18 (a) Anemometer

Figure 3.18 (b) Anemometer Calibration Certificate

Figure 3.18 (c) Anemometer Calibration Certificate

Figure 3.19 (a) Infrared Temperature Measuring Gun

Figure 3.19 (b) Infrared Temperature Measuring Gun Calibration Certificate

3.12 BASIC RADIATOR DRAWING

3.12 BASIC RADIATOR DRAWING

Fig. 3.20

: Various Locatio

ns for

Temp

and Velocities

Fig. 3.21: Radiator CAD drawing

Fig. 3.22: Radiator with tube dimensions

3.13 GEOMERI

C MODE

LING

OF FA

N:

For

CFD analysis

of the

radiator, it is necessary to create a geometric model of the system. A model of the radiator and the fan was made in CATIA V5 and then exported to CFD analysis software.

Fig.3.23

Fan Model

Fig.3.24 Radiator Models

PART: A

SET: 1

Fig.3.25: Temperature and Velocity reading

NOTE1 : A,B,C,D,E,F,G,H,I,J,K,L,M,N,O,P are radial lines on Radiator on which temperature readings are

taken and denoted by faint Numericals

NOTE2 : V1,V2,V3,V4,V5,V6,V7,V8 are radial lines on Radiator on which Velocity reading are taken and

denoted by Dark Numerical

Temperature Vs Radial Distance

Fig.3.26 Temperature Vs Radial Distance for 100 lph & 1500 rpm

25

27

29

31

33

35

37

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

35

40

45

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.27 Velocity Vs Radial Distance for 100 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 2

Fig.3.28 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.29 Temperature Vs Radial Distance for 110 lph & 1500 rpm

25

30

35

40

45

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

35

40

45

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.30 Velocity Vs. Radial Distance for 110 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 3

Fig.3.31 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.32 Temperature Vs Radial Distance for 120 lph & 1500 rpm

27

29

31

33

35

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

27

32

37

42

0 50 100 150 200

I

J

K

L

M

27

28

29

30

31

32

33

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.33 Velocity Vs Radial Distance for 120 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 4

Fig.3.34 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.35 Temperature Vs Radial Distance for 130 lph & 1500 rpm

25

30

35

40

45

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.36: Velocity Vs Radial Distance for 130 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 5

Fig.3.37: Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.38 Temperature Vs Radial Distance for 140 lph & 1500 rpm

25

26

27

28

29

30

31

0 50 100 150 200

A

B

C

D

E

25

30

35

40

0 50 100 150 200

E

F

G

H

I

25

27

29

31

33

35

37

0 50 100 150 200

I

J

K

L

M

25

26

27

28

29

30

31

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig.3.39 Velocity vs. Radial Distance for 140 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 6

Fig.3.40 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.41 Temperature Vs Radial Distance for 150 lph & 1500 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

30

35

40

45

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.42 Velocity Vs Radial Distance for 150 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 7

Fig. 3.43 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.44 Temperature Vs Radial Distance for 160 lph & 1500 rpm

27

28

29

30

31

32

33

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

0 50 100 150 200

E

F

G

H

I

30

31

32

33

34

35

36

37

0 50 100 150 200

I

J

K

L

M

27

28

29

30

31

32

33

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig. 3.45 Velocity Vs Radial Distance for 160 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 8

Fig. 3.46 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.47 Temperature Vs Radial Distance for 170 lph & 1500 rpm

25

30

35

40

45

0 50 100 150 200

A

B

C

D

E

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

30

35

40

45

0 50 100 150 200

I

J

K

L

M

30

32

34

36

38

40

42

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.48 Velocity Vs Radial Distance for 170 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 9

Fig. 3.49 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.50 Temperature Vs Radial Distance for 180 lph & 1500 rpm

29

30

31

32

33

34

35

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

35

40

45

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig.3.51 Velocity Vs Radial Distance for 180 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 10

Fig.3.52 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.53 Temperature Vs Radial Distance for 190 lph & 1500 rpm

25

30

35

40

45

50

0 50 100 150 200

A

B

C

D

E

35

37

39

41

43

45

47

0 50 100 150 200

E

F

G

H

I

35

37

39

41

43

45

0 50 100 150 200

I

J

K

L

M

30

32

34

36

38

40

42

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.54 Velocity Vs Radial Distance for 190 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

SET: 11

Fig.3.55 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.56 Temperature Vs Radial Distance for 200 lph & 1500 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

35

40

45

0 50 100 150 200

I

J

K

L

M

20

25

30

35

40

45

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig.3.57 Velocity Vs Radial Distance for 200 lph & 1500 rpm

0

0.5

1

1.5

2

2.5

3

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Part: B

Set: 1

Fig.3.58 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.59 Temperature Vs Radial Distance for 100 lph & 1600 rpm

25

27

29

31

33

35

0 50 100 150 200

A

B

C

D

E

25

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

25

30

35

40

45

50

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig.3.60 Velocity Vs Radial Distance for 100 lph & 1600 rpm

0

0.5

1

1.5

2

2.5

3

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 2

Fig.3.61 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.62 Temperature Vs Radial Distance for 100 lph & 1700 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

25

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

25

30

35

40

45

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig.3.63 Velocity Vs Radial Distance for 100 lph & 1700 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 3

Fig.3.64 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.65 Temperature Vs Radial Distance for 100 lph & 1800 rpm

25

30

35

40

45

0 50 100 150 200

A

B

C

D

E

25

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

25

30

35

40

45

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig. 3.66 Velocity Vs Radial Distance for 100 lph & 1800 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 4

Fig. 3.67 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig. 3.68 Temperature Vs Radial Distance for 100 lph & 1900 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

25

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

25

30

35

40

45

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

0 50 100 150 200

M

N

O

P

A

Velocity Vs Radial Distance

Fig. 3.69 Velocity Vs Radial Distance for 100 lph & 1900 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 5

Fig.3.70 Temperature and Velocity reading

Temperature Vs Radial Distance

27

28

29

30

31

32

33

34

0 50 100 150 200

A

B

C

D

E

25

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

25

30

35

40

45

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

0 50 100 150 200

M

N

O

P

a

Fig.3.71 Temperature Vs Radial Distance for 100 lph & 2000 rpm

Velocity Vs Radial Distance

Fig.3.72 Velocity Vs Radial Distance for 100 lph & 2000 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

PART: C

Set: 6

Fig.3.73

Temperature and

Velocity

reading

Temperature Vs Radial

Distance

Fig.3.74 Temperature Vs Radial Distance for 120 lph & 1600 rpm

25

30

35

40

45

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

30

32

34

36

38

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig. 3.75 Velocity Vs Radial Distance for 120 lph & 1600 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 7

Fig.3.76 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.77 Temperature Vs Radial Distance for 120 lph & 1700 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

30

32

34

36

38

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.78 Velocity Vs Radial Distance for 120 lph & 1700 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 8

Fig.3.79 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.80 Temperature Vs Radial Distance for 120 lph & 1800 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

42

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.81 Velocity Vs Radial Distance for 120 lph & 1800 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 9

Fig.3.82 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.83 Temperature Vs Radial Distance for 120 lph & 1900 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.84 Velocity Vs Radial Distance for 120 lph & 1900 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 10

Fig.3.85 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.86 Temperature Vs Radial Distance for 120 lph & 2000 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

42

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

42

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.87 Velocity Vs Radial Distance for 120 lph & 2000 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

PART: D

Set: 11

Fig.3.88 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.89 Temperature Vs Radial Distance for 140 lph & 1600 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.90 Velocity Vs Radial Distance for 140 lph & 1600 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 12

Fig.3.91 Temperature and Velocity reading

Temperature Vs Radial Distance

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

42

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Fig.3.92 Temperature Vs Radial Distance for 140 lph & 1700 rpm

Velocity Vs Radial Distance

Fig.3.93 Velocity Vs Radial Distance for 140 lph & 1700 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 13

Fig.3.94 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.95 Temperature Vs Radial Distance for 140 lph & 1800 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.96 Velocity Vs Radial Distance for 140 lph 1800 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 14

Fig.3.97 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.98 Temperature Vs Radial Distance for 140 lph & 1900 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.99 Velocity Vs Radial Distance for 140 lph 1900 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 15

Fig.3.100 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.101 Temperature Vs Radial Distance 140 lph & 2000 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

42

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.102 Velocity Vs Radial Distance for 140 lph & 2000 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

PART: E

Set: 16

Fig.3.103 Temperature and Velocity reading

Temperature Vs Radial Distance

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Fig.3.104 Temperature Vs Radial Distance 160 lph & 1600 rpm

Velocity Vs Radial Distance

Fig.3.105 Velocity Vs Radial Distance for 160 lph & 1600 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 17

Fig.3.106 Temperature and Velocity reading

Temperature Vs Radial Distance

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Fig.3.107 Temperature Vs Radial Distance 160 rpm & 1700 rpm

Velocity Vs Radial Distance

Fig.3.108 Velocity Vs Radial Distance for 160 lph & 1700 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 18

Fig.3.109 Temperature and Velocity reading

Temperature Vs Radial Distance

25

30

35

40

45

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Fig.3.110 Temperature Vs Radial Distance 160 lph & 1800 rpm

Velocity Vs Radial Distance

Fig.3.111 Velocity Vs Radial Distance for 160 lph & 1800 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 19

Fig.3.112 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.113 Temperature Vs Radial Distance 160 lph & 1900 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.114 Velocity Vs Radial Distance for 160 lph & 1900 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 20

Fig.3.115 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.116 Temperature Vs Radial Distance 160 lph & 2000 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

35

40

45

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.117 Velocity Vs Radial Distance for 160 lph & 2000 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

PART: F

Set: 21

Fig.3.118 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.119 Temperature Vs Radial Distance 180 lph & 1600 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.120 Velocity Vs Radial Distance for 180 lph & 1600 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 22

Fig.3.121 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.122 Temperature Vs Radial Distance 180 lph & 1700 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.123 Velocity Vs Radial Distance for 180 lph & 1700 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 23

Fig.3.124 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.125 Temperature Vs Radial Distance 180 lph & 1800 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

27

29

31

33

35

37

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.126 Velocity Vs Radial Distance for 180 lph & 1800 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 24

Fig.3.127 Temperature and Velocity reading

Temperature Vs Radial Distance

25

27

29

31

33

35

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Fig.3.128 Temperature Vs Radial Distance 180 lph & 1900 rpm

Velocity Vs Radial Distance

Fig.3.129 Velocity Vs Radial Distance for 180 lph & 1900 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 25

Fig.3.130 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.131 Temperature Vs Radial Distance 180 lph & 2000 rpm

25

30

35

40

0 50 100 150 200

A

B

C

D

E

30

32

34

36

38

40

0 50 100 150 200

E

F

G

H

I

30

32

34

36

38

40

0 50 100 150 200

I

J

K

L

M

25

30

35

40

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.132 Velocity Vs Radial Distance for 180 lph & 2000 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 20 40 60 80 100 120 140 160 180

V1

V2

V3

V4

V5

V6

V7

V8

PART: G Set: 26

Fig.3.133 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.134 Temperature Vs Radial Distance 200 lph & 1600 rpm

25

30

35

40

45

50

0 50 100 150 200

A

B

C

D

E

30

35

40

45

50

55

0 50 100 150 200

E

F

G

H

I

30

35

40

45

50

0 50 100 150 200

I

J

K

L

M

25

30

35

40

45

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.135 Velocity Vs Radial Distance for 200 lph & 1600 rpm

0

0.5

1

1.5

2

2.5

3

3.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 27

Fig.3.136 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.137 Temperature Vs Radial Distance 200 lph & 1700 rpm

25

30

35

40

45

50

0 50 100 150 200

A

B

C

D

E

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

30

35

40

45

50

0 50 100 150 200

I

J

K

L

M

25

30

35

40

45

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.138 Velocity Vs Radial Distance for 200 lph & 1700 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 28

Fig.3.139 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.140 Temperature Vs Radial Distance 200 lph & 1800 rpm

25

30

35

40

45

50

0 50 100 150 200

A

B

C

D

E

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

30

35

40

45

50

0 50 100 150 200

I

J

K

L

M

30

35

40

45

50

0 50 100 150 200

A

M

N

O

P

Velocity VS Radial Distance

Fig.3.141 Velocity Vs Radial Distance for 200 lph & 1800 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 29

Fig.3.142 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.143 Temperature Vs Radial Distance 200 lph & 1900 rpm

25

30

35

40

45

50

0 50 100 150 200

A

B

C

D

E

30

35

40

45

50

55

0 50 100 150 200

E

F

G

H

I

30

35

40

45

50

0 50 100 150 200

I

J

K

L

M

25

30

35

40

45

50

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.144 Velocity Vs Radial Distance 200 lph & 1900 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8

Set: 30

Fig.3.145 Temperature and Velocity reading

Temperature Vs Radial Distance

Fig.3.146 Temperature Vs Radial Distance 200 lph & 2000 rpm

25

30

35

40

45

0 50 100 150 200

A

B

C

D

E

30

35

40

45

50

0 50 100 150 200

E

F

G

H

I

30

35

40

45

50

0 50 100 150 200

I

J

K

L

M

25

30

35

40

45

0 50 100 150 200

A

M

N

O

P

Velocity Vs Radial Distance

Fig.3.147 Velocity Vs Radial Distance for 200 lph & 2000 rpm

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200

V1

V2

V3

V4

V5

V6

V7

V8