certificate of approval no cf 5204 - performance glass

56
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182. CERTIFICATE OF APPROVAL No CF 5204 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of CGI INTERNATIONAL LIMITED International House, Millfield Lane, Haydock, WA11 9GA Tel: 01942 710720 Fax: 01942 710730 Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions appended hereto: ______________________________________________________________________________ CERTIFIED PRODUCT TECHNICAL SCHEDULE ‘Pyroguard T EIInsulating Fire Resisting Glass TS 25 Fire Resistant Glass, Glazing Systems and Materials Signed and sealed for and on behalf of CERTIFIRE Sir Ken Knight Issued: 24 th February 2014 Chairman - Management Council Valid to: 23 rd February 2019 Page 1 of 56

Upload: others

Post on 22-May-2022

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE OF APPROVAL No CF 5204

This is to certify that, in accordance with

TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of

CGI INTERNATIONAL LIMITED

International House, Millfield Lane, Haydock, WA11 9GA

Tel: 01942 710720 Fax: 01942 710730

Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions

appended hereto:

______________________________________________________________________________

CERTIFIED PRODUCT TECHNICAL SCHEDULE

‘Pyroguard T EI’ Insulating Fire Resisting Glass

TS 25 Fire Resistant Glass, Glazing Systems and Materials

Signed and sealed for and on behalf of CERTIFIRE

Sir Ken Knight Issued: 24th February 2014

Chairman - Management Council Valid to: 23rd

February 2019 Page 1 of 56

Page 2: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 2 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T Insulating Fire Resisting Glass This Certificate of Approval relates to the fire resistance of CGI International Limited ‘Pyroguard T Insulating’ laminated glass products when used in the following applications, as defined in BS 476: Part 22: 1987 but using test results achieved against the following Standards - BS EN 1363-1 Fire Resistance Tests, BS EN 1364-1 Fire Resistance Tests on Doors, Shutters and Openable Windows or BS 1364-3 Fire Resistance Tests for Non Loadbearing Elements – Curtain Walling This product is approved on the basis of: a) Initial type testing b) A design appraisal against TS25 c) Product surveillance under BS EN ISO 9001: 2008 d) Audit testing e) Inspection and surveillance of factory production control

Glass Specification

Application

Fire Resistance Performance (mins) Page

No. Integrity Insulation

Pyroguard T EI30/18-2

Multiple paned Timber framed screens 30 30 5-6

Pyroguard T EI30/18-2

Multiple paned Single Steel framed screens 30 30 7-8

Pyroguard T EI30/18-2

Multiple paned Steel framed screens 30 30 9-10

Pyroguard T EI30/18-2

Multiple paned Steel framed screens 60 30 11-12

Pyroguard T EI30/18-2

Multiple paned Steel framed screens 60 30 13-14

Pyroguard T EI90/32-2

Two paned Steel framed screens 60 60 15-16

Pyroguard T EI90/32-2

Multiple paned Steel framed screens 60 60 17-18

Pyroguard T EI90/32-2

Multiple paned Steel framed screens 90 90 19-20

Pyroguard T EI90/32-2

Two paned Steel framed screens 90 90 21-22

Pyroguard T EI120/47-3

Multiple paned Steel framed screens 120 120 23-24

*Pyroguard T EI30/18-2VI

Multiple panes of IGU in frame and in two Steel doors

30 30 25-26

*Pyroguard T EI30/18-2VI

Multiple panes of IGU in frame and in two Steel doors

60 30 27-28

Pyroguard T EI30/18-2VI

Multiple paned IGU Timber framed screens 30 30 29-30

Note* The fire resistant pane of the IGU construction can be used as a single glazed pane in any previously fire tested or CERTIFIRE approved system. Note: In this case the product code will change.

Page 3: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 3 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T Insulating Fire Resisting Glass (continued)

Glass Specification Application Fire Resistance Performance (mins)

Page No.

Integrity Insulation

*Pyroguard T EI30/18-2VI

IGUs in multiple paned Timber framed screens

60 30 31-32

*Pyroguard T EW30/13-1 VI

IGUs in multiple paned Steel framed screens

30 30 33-34

*Pyroguard T EW30/13-1 VI

IGUs in multiple paned Steel framed screens

60 30 35-36

*Pyroguard T EI30/13-1 VI

IGUs in multiple paned Steel framed screens

60 30 37-38

*Pyroguard T EI60/25-3VI

IGUs in multiple Steel framed screen 60 60 39-40

*Pyroguard T EW30/13-1 VI

IGUs in multiple paned Steel framed screens

90 30 41-42

*Pyroguard T

EI30/18-2VI

IGUs in multiple paned Steel framed screens

30 30 43-44

*Pyroguard T

EI90/32-2VI

IGUs in multiple paned Steel framed screens

60 60 45-46

*Pyroguard T

EI90/32-2VI

IGUs in multiple paned Steel framed screens

90 90 47-48

*Pyroguard T SWS

EI30/18-2VI

IGUs in multiple paned Steel framed screens

60 30 49-50

Pyroguard T SWS EI30/32-2

Four single Butt jointed panes in timber framed screens

30 30 51-52

Pyroguard T SWS EI60/40 and EI60/36-2

Three single Butt jointed panes in timber framed screens

60 60 53-54

Pyroguard T SWS

EI30/24-2

Three single Butt jointed panes in Steel framed screens

30 30 55-56

Note* The fire resistant pane of the IGU construction can be used as a single glazed pane in any previously fire tested or CERTIFIRE approved system. Note: In this case the product code will change.

Page 4: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 4 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T Insulating Fire Resisting Glass General Requirements Where the glass is installed in a timber or steel framed screen, the orientation of the screen shall be no more than ±10º from the vertical. The edge cover to each pane is normally a minimum of 12 mm minimum. See test reports for exact dimensions. Options Can be etched or sandblasted on one glass face. Self - adhesive films/foils may be applied to either glass surface. Insulating Glass Units (IGUs) may incorporate fixed aluminium blinds or Georgian bars within the cavity between the inner and outer glass layers. Note: Where IGUs are approved and the fire resistant pane is glazed to the non-fire side, the non-fire resistant glass on the fire side can be float, toughened or laminated glass. When the fire resistant pane is glazed to the fire side the non-fire resistant glass on the non-fire side can be any pane that does not contain a flammable organic material i.e. float glass or toughened glass but not a laminated or painted glass unless supported by test evidence not contained in this CF. Were a fire resistant IGU is required it can be manufactured from any single size glass listed in this certificate for a given fire performance. In this case, the IGU non fire glass must be glazed on the fire side and the IGU glazed into any previously fire tested or CERTIFIRE approved system. Within this certification IGU airspace widths vary from 6mm to 12mm for different products. The airspace widths are interchangeable for any product within this range. For larger airspace width contact the owner of this Certification. The fire resistant pane of the IGU construction can be used as a single glazed pane in any previously fire tested or CERTIFIRE approved system. For doors described in this Certificate then the glazed element can also be used in any previously fire tested or CERTIFIRE approved glazed insulated steel or timber framed door Additional non fire rated glass can be laminated to the fire glass but must be installed to the fire side.

Page 5: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 5 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Hardwood framed screens for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved framing doors system utilising the following basic specification:

Framework from Hardwood (e.g. Oak) and 90 mm by 50 mm section. Transoms and mullions assembled by steel screws 10 x 135 mm.

Hardwood beads 33 mm by 20 mm fixed with 3.5 x 45 mm screws.

Glazing and frame details as describe in Efectis test report No 271-37090

Page 6: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 6 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Hardwood framed screens for periods of 30 minutes integrity and insulation (Continued) The glass shall be glazed within a previously fire tested or CERTIFIRE approved framing doors system utilising the following basic specification: This Certificate of Approval relates to the sizes 18 mm thick Pyroguard T EI30/18-2 shown in Figure 1 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 1. Maximum Permitted Glass Dimensions

500 1000 1500 2000 2500 1495 1869

3000

2500

2000

1500

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

2495

Maximum Area 4.66m2

3119

Page 7: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 7 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Jansen Janisol 2 steel framed screens for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No 11-000423

Page 8: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 8 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Jansen Janisol 2 steel framed screens for periods of 30 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of 18 mm thick Pyroguard T EI30/18-2 shown in Figure 2 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

1284

1868

Figure 2. Maximum Permitted Glass Dimensions

1500 2000 2500 3000 3500 1264 1580 2594 3243

2500

2000

1500

1000

500

Glass Height

(mm)

Glass Width (mm)

Towards 0

1494

Maximum Area 4.16m2

1605

Maximum Area 2.36m2

Page 9: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 9 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Fuego Light 30 Forster steel framed screens for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 271-44217

Page 10: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 10 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Fuego Light 30 Forster steel framed screens for periods of 30 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of 18 mm thick Pyroguard T EI30/18-2 shown in Figure 3 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

1494

Maximum Area 2.37m2

1868

Figure 3. Maximum Permitted Glass Dimensions

1500 2000 2500 3000 3500 1269 1586 2594 3243

2500

2000

1500

1000

500

Glass Height

(mm)

Glass Width (mm)

Towards 0

1284

Maximum Area 4.16m2

1605

Page 11: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 11 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Fuego Light 30 Forster steel framed screens for periods of 60 minutes integrity and 30 Minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 271-44217

Page 12: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 12 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Fuego Light 30 Forster steel framed screens for periods of 60 minutes integrity and 30 Minutes insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes 18 mm thick Pyroguard T EI30/18-2 shown in Figure 4 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 4. Maximum Permitted Glass Dimensions

1500 2000 2500 3000 3500 1269 2594 2680 1311

2500

2000

1500

1000

500

Glass Height

(mm)

Glass Width (mm)

Towards 0

1284

Maximum Area 3.44m2

1326

1543

1494

Maximum Area 1.96m2

Page 13: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 13 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Jansen Janisol 2 steel framed screens for periods of 60 minutes integrity and 30 minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No 11-000423

Page 14: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 14 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 glass in Jansen Janisol 2 steel framed screens for periods of 60 minutes integrity and 30 minutes insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of 18 mm thick Pyroguard T EI30/18-2 shown in Figure 5 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

1284

1718

Figure 5. Maximum Permitted Glass Dimensions

1500 2000 2500 3000 3500 1264 2594 2983 1454

2500

2000

1500

1000

500

Glass Height

(mm)

Glass Width (mm)

Towards 0

1494

Maximum Area 3.83m2

1477

Maximum Area 2.17m2

Page 15: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 15 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI 90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 60 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No271-35263

Page 16: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 16 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI 90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 60 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes with 32 mm thick Pyroguard T EI90/32-2 shown in Figure 6 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 6. Maximum Permitted Glass Dimensions

1500 1600 1700 1800 1900 1875

5000

4000

3000

2000

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 5.31 m2

2834

3543

Page 17: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 17 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI 90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 60 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No271-35924

Page 18: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 18 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI 90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 60 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes with 32 mm thick Pyroguard T EI90/32-2 shown in Figure 7 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 7. Maximum Permitted Glass Dimensions

1000 1500 2000 3500 4000 2824 3530

2000

1750

1500

1250

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 5.3 m2

1875

Page 19: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 19 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 90 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No271-35924

Page 20: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 20 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 90 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of 32 mm thick Pyroguard T EI90/32-2 shown in Figure 8 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 8. Maximum Permitted Glass Dimensions

1000 1500 2000 3500 4000 2824

2000

1750

1500

1250

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 4.24 m2

Page 21: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 21 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 90 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No271-35263

Page 22: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 22 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 glass in ISO Hermetic RP Technik steel framed screen for periods of 90 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of 32 mm thick Pyroguard T EI90/32-2 shown in Figure 9 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 9. Maximum Permitted Glass Dimensions

1500 1600 1700 1800 1900

5000

4000

3000

2000

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 5.1 m2

2834

3401

Page 23: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 23 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T Interfire EI 120/47-3 glass in RP FEU 120 steel framed screen for periods of 120 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 08-V-437

Page 24: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 24 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T Interfire EI 120/47-3 glass in ISO FEU 120 (RP Technik) steel framed screen for periods of 120 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes with 47 mm thick Pyroguard T EI120/47-3 shown in Figure 10 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

1379

1724

Figure 10. Maximum Permitted Glass Dimensions

1000 1100 1200 1300 1400

3000

2500

2000

1500

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 3.67m2

2825

Page 25: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 25 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed doors for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel framing doors system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 11-V-693

Page 26: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 26 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed doors for periods of 30 minutes integrity and insulation (Continued) The insulated steel framing doors system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 35 mm thick Pyroguard T EI30/18-2 VI shown in Figure 11 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 11. Maximum Permitted Glass Dimensions

1000 1100 1200 1300 1400 1029 1286

3500

3000

2500

2000

1500

Glass Height

(mm)

Glass Width (mm)

Towards 0

2684

Maximum Area 3.45 m2 3355

Page 27: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 27 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed doors for periods of 60 minutes integrity and 30 minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel framing doors system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 11-V-693

Page 28: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 28 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed doors for periods of 60 minutes integrity and 30 minutes insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 35 mm thick Pyroguard T EI30/18-2 VI shown in Figure 12 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 12. Maximum Permitted Glass Dimensions

700 800 900 1000 1100 1029

3500

3000

2500

2000

1500

Glass Height

(mm)

Glass Width (mm)

Towards 0

2684

Maximum Area 2.76 m2

Page 29: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 29 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in hardwood frame for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved timber framing system utilising the following basic specification:

Intumecent seal between non fire glass and bead, 25 by 1.5mm Intumex (Odice) or (Flexpress 100 (Gluske) or 20 by 3 mm Fibrefrax FT paper (GLUSKE) or superwool(Odice).

Glazing and frame details as describe in Efectis test report No 09-V-481

Page 30: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 30 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in hardwood frame for periods of 30 minutes integrity and insulation (Continued) The insulated timber framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 35 mm thick Pyroguard T 30/18-2 VI shown in Figure 13 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 13. Maximum Permitted Glass Dimensions

1500 2000 2500 3000 3500 2585 3231

2500

2000

1500

1000

500

Glass Height

(mm)

Glass Width (mm)

Towards 0

1856

Maximum Area 4.8 m2

1485

Page 31: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 31 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in hardwood frame for periods of 60 minutes integrity and 30 minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved timber framing system utilising the following basic specification:

Intumecent seal between non fire glass and bead, 25 by 1.5mm Intumex (Odice) or (Flexpress 100 (Gluske) or 20 by 3 mm Fibrefrax FT paper (GLUSKE) or superwool(Odice).

Glazing and frame details as describe in Efectis test report No 09-V-481

Page 32: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 32 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in hardwood frame for periods of 60 minutes integrity and 30 minutes insulation (Continued) The insulated timber framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 30 mm thick Pyroguard T EI30/18-2 VI shown in Figure 14 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 14. Maximum Permitted Glass Dimensions

1500 2000 2500 3000 3500 2585 2628

2500

2000

1500

1000

500

Glass Height

(mm)

Glass Width (mm)

Towards 0

1510

Maximum Area 3.99 m2

1485

Page 33: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 33 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in steel framed Thermfix Vario Curtain Walling System with glazed panels for periods of 30 minutes integrity and 30 minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 007-CVB-RO495

Page 34: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 34 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in steel framed Thermfix Vario Curtain Walling System with glazed panels for periods of 30 minutes integrity and 30 minutes insulation The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU with 13 mm thick Pyroguard T EW30/13-1 VI shown in Figure 15 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 15. Maximum Permitted Glass Dimensions

500 1000 1500 2000 2500 1875

4000

3500

3000

2000

1500

Glass Height

(mm)

Glass Width (mm)

Towards 0

2928

Maximum Area 5.49m2

3660

Page 35: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 35 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in ISO Hermetic 45 N RP Technik steel framed system or Isofire 45 system for periods of 60 minutes integrity and 30 minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 12-V-207

Page 36: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 36 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in ISO Hermetic 45 N RP Technik steel framed system or Isofire 45 system for periods of 60 minutes integrity and 30 minutes insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU with 26 mm thick Pyroguard T EW30/13-1 VI shown in Figure 16 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 16. Maximum Permitted Glass Dimensions

1200 1400 1600 1800 2000 1479 1494 1578

4000

3500

3000

2500

2000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 4.18 m2

2800

1391 1484

Maximum Area 2.19m2

2988

Page 37: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 37 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in steel framed Thermfix Vario Curtain Walling System with glazed panels for periods of 60 minutes integrity and 30 minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 007-CVB-RO495

Page 38: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 38 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in steel framed Thermfix Vario Curtain Walling System with glazed panels for periods of 60 minutes integrity and 30 minutes insulation The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU with 13 mm thick Pyroguard T EW30/13-1 VI shown in Figure 17 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 17. Maximum Permitted Glass Dimensions

500 1000 1500 2000 2500 1875

4000

3500

3000

2000

1500

Glass Height

(mm)

Glass Width (mm)

Towards 0

2928

Maximum Area 5.49m2

3660

Page 39: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 39 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI60/25-3 VI glass in ISO Hermetic 60 N RP Technik steel framed system for periods of 60 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 09-V-234

Page 40: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 40 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI60/25-3 VI glass in ISO Hermetic 60 N RP Technik steel framed system for periods of 60 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 40 mm thick Pyroguard T EI60/25-3 VI shown in Figure 18 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 18. Maximum Permitted Glass Dimensions

1500 1600 1700 1800 1900 1415 1769

5000

4000

3000

2000

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 4.99 m2

2820

3525

Page 41: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 41 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in steel framed Thermfix Vario Curtain Walling System with glazed for periods of 90 minutes integrity and 30 minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in Efectis test report No 007-CVB-RO495

Page 42: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 42 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EW30/13-1 VI glass in steel framed Thermfix Vario Curtain Walling System with glazed panels for periods of 90 minutes integrity and 30 minutes insulation The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU with 13 mm thick Pyroguard T EW30/13-1 VI shown in Figure 19 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 19. Maximum Permitted Glass Dimensions

500 1000 1500 2000 2500

3000

2500

2000

1500

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

2928

Maximum Area 4.39 m2

Page 43: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 43 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed screens for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No10-000976

Page 44: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 44 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed screens for periods of 30 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 35 mm thick Pyroguard T EI30/18-2 VI shown in Figure 20 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

1372

1097

Figure 20. Maximum Permitted Glass Dimensions

1100 1300 1500 1700 1900 1484 1618 1855 1494

3000

2500

2000

1500

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

2855

Maximum Area 3.7m2

2284

Maximum Area 2.04m2

Page 45: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 45 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 VI glass in RP Technik steel framed screens for periods of 60 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFC test report No576

Page 46: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 46 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 VI glass in RP Technik steel framed screens for periods of 60 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 35 mm thick Pyroguard T EI90/32-2 VI shown in Figure 21 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 21. Maximum Permitted Glass Dimensions

500 1000 1500 2000 2500 1503 1879

1500

1400

1300

1200

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

1079

Maximum Area 2.03m2

1349

Page 47: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 47 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 VI glass in RP Technik steel framed screens for periods of 90 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFC test report No576

Page 48: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 48 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI90/32-2 VI glass in RP Technik steel framed screens for periods of 90 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 35 mm thick Pyroguard T EI90/32-2 VI shown in Figure 22 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 22. Maximum Permitted Glass Dimensions

500 1000 1500 2000 2500 1503 1804

1500

1400

1300

1200

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

1079

Maximum Area 1.95m2

1295

Page 49: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 49 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed screens for periods of 60 minutes integrity and 30 Minutes insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel system utilising the following basic specification:

Glazing and frame details as describe in IFT test report No10-000976

Page 50: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 50 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/18-2 VI glass in Fuego Light 30 Forster steel framed screens for periods of 60 minutes integrity and 30 Minutes insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of IGU of 35 mm thick Pyroguard T EI30/18-2 VI shown in Figure 23 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions

2323

1097

Figure 23. Maximum Permitted Glass Dimensions

1100 1300 1500 1700 1900 1294 1484 1319 1316 1509

3000

2500

2000

1500

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

Maximum Area 3.01m2

2284

Maximum Area 1.66m2

1116

Page 51: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 51 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/32-2 SWS Butt Jointed Glass in hardwood frame for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved timber framing system utilising the following basic specification:

Hardwood frame with a density of 650 kg/m3

and 107 mm by 38 mm section. Assembled in the construction with dowels and screws 10 x 160 mm every 900 mm. Double hardwood beads 35 mm by 20 mm fixed by screws 4 x 60 mm every 170 mm at angle of 30

0 degrees around the framework 30 x 2 mm Flexpress intumescent

strip.

Glazing material Kerafix 2000 mineral fibre 20 x 3 mmat glazed edges. Fire Resistant Sealant at butt joint between glass junction 30 mm wide.

80 by 6 mm Promatect H or Flammi 12(GLUSKE) setting blocks and Bottom edge clearance 6 mm, edge cover 14mm

Intumecent seal between non fire glass and bead, 25 by 1.5mm Intumex (Odice) or (Flexpress 100 (Gluske) or 20 by 3 mm Fibrefrax FT paper (GLUSKE) or superwool(Odice)

Glazing and frame details as describe in Efectis test report No 09-V-241

Page 52: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 52 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/32-2 SWS Butt Jointed Glass in hardwood frame for periods of 30 minutes integrity and insulation (Continued) The insulated timber framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of 32 mm thick Pyroguard T EI30/32-2 SWS shown in Figure 24 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 24. Maximum Permitted Glass Dimensions

1500 2000 2500 3000 3500 1830 2288

5000

4000

3000

2000

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

2900

Maximum Area 6.63 m2

3625

Page 53: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 53 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI60/40-2 and EI60/36-2 SWS Butt Jointed Glass in hardwood frame for periods of 30 minutes integrity and insulation For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved timber framing system utilising the following basic specification:

40 mm thick fire glass Pyroguard T EI60/40-2 SWS with 2 x 11 mm safety glass with 5.5.2 construction/2 x 6 mm intumescent interlayer/6 mm float glass, symmetrical glass construction with glazing beads on both side.

Alternatively constructed with 4.4.2 safety glass construction to give 36 mm thick fire glass Pyroguard T EI60/36-2 SWS.

Glazing and frame details as describe in Efectis test report No 08-V-295

Page 54: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 54 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI60/40-2 and EI60/36-2 SWS Butt Jointed Glass in hardwood frame for periods of 30 minutes integrity and insulation (Continued) The insulated timber framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of 40mm or 36 mm thick Pyroguard T EI60/40-2 SWS or Pyroguard T EI60/36-2 shown in Figure 25 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 25. Maximum Permitted Glass Dimensions

500 1000 1500 2000 2500 1830

3000

2500

2000

1500

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

2900

Maximum Area 5.31 m2

Page 55: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 55 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/24-2 SWS Butt Jointed Glass in Fuego Light 30 Forster steel partition system for periods of 30 minutes integrity and insulation. For this application the following conditions shall apply: The glass shall be glazed within a previously fire tested or CERTIFIRE approved insulated steel partition system utilising the following basic specification:

Glazing with a double bead system 15 x 20 mm on the fire side and 20 x 20 mm non fire side, screw fixed every 300 mm with 20 mm by 3 mm Flexlit Kerafix ceramic glazing (Gluske) tape. Thinnest beads on fire side.

The butt joints of the glazing were assembled side by side with 24 mm by 5 mm fire resistant silicone. Along the top of all glazing, Kerafix Silicone (GLUSKE) was applied on the unexposed side.

Clearance between glass and frame was 7.5 mm. Edge Cover was 12.5 mm.

Glazing and frame details as describe in Efectis test report No 12-V-236

Page 56: CERTIFICATE OF APPROVAL No CF 5204 - Performance Glass

This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.

CERTIFICATE No CF 5204 CGI INTERNATIONAL LIMITED

Page 56 of 56 Signed

Issued: 24th

February 2014 Valid to: 23

rd February 2019

Pyroguard T EI30/24-2 SWS Butt Jointed Glass in Fuego Light 30 Forster steel partition system for periods of 30 minutes integrity and insulation (Continued) The insulated steel framing system shall have test evidence or be CERTIFIRE approved for the inclusion of apertures of the proposed dimensions. This Certificate of Approval relates to the sizes of Pyroguard T EI30/24-2 SWS shown in Figure 26 below, when used in conjunction with the above system. The aspect ratio of the glass may be unlimited within these aperture dimensions.

Figure 26. Maximum Permitted Glass Dimensions

1000 1200 1400 1600 1800 1300 1560

4500

4000

3500

3000

2500

1000

Glass Height

(mm)

Glass Width (mm)

Towards 0

3265

Maximum Area 5.09 m2

3918